COOLING ENERGY SAVING SYSTEM USING A WATER MIST DEVICE ON WINDOWS

Size: px
Start display at page:

Download "COOLING ENERGY SAVING SYSTEM USING A WATER MIST DEVICE ON WINDOWS"

Transcription

1 COOLING ENERGY SAVING SYSTEM USING A WATER MIST DEVICE ON WINDOWS Kybum Jeong Sang-Gon Choi Yuhan College Yuhan College Dept. of Building Services Dept. of Building Services 590 Gyeonginro Sosagu Bucheon 590 Gyeonginro Sosagu Bucheon Gyeonggi Korea Gyeonggi Korea jkb@yuhan.ac.kr tool007@yuhan.ac.kr ABSTRACT 1. INTRODUCTION Many buildings are covered with numerous windowpanes for design impressions, so the proportion of windows to a building s elevation is increasing. Accordingly, the cooling load for solar radiation heat accumulated through a window is getting larger. Moreover, global warming and heat island effect make the outside air temperature increase. In nearly all buildings, cool air is supplied evenly regardless of the direction the space is facing. Consequently, the west side spaces of buildings cannot keep the required cool temperature that tenants need, due to the solar heat coming in through the windows. The water mist system was projected to decrease the solar heat inflow through windows in this study. The experiments were carried out to appraise the performance of the solar heat defending tools. The room temperatures of two disconnected offices were evaluated when using solar heat control devices. The assessment results revealed that the water mist system was advanced to the coated glass and the vertical blinds for the saving of cooling energy The open-air temperature ascends due to Global Warming and heat island effect. Many buildings are enclosed with glass windows as a design impression and the ratio of window to elevation area is growing. As a result, the cooling load for solar radiation heat acquisition through glass windows is getting higher. In most edifices, cooling air is being supplied evenly despite the direction in which the room is facing. Accordingly, the west region spaces of a building cannot maintain the necessary cool temperature that occupants want by reason of the solar heat through windows. Solar heat lessening gadgets like vertical blinds and film coated glass have been used to screen solar gaining increase through the west facing window, but it seemed that those gadgets were not researched. In this study, the water mist system was projected to reduce the solar heat inflow through window systems. The experiments were performed to evaluate the performance of the solar heat protecting gears. The room temperatures of two west

2 facing rooms were measured to evaluate the efficiency of cooling energy for solar heat control devices. 2. EXPERIMENTAL MEASUREMENT 2.1 Water Mist System (a) Supply and mist system at the top The water mist system transports the water to the top of the window and sprayed downward on the surface of the window to block out solar heat and to save cooling energy. Figure 1 and 2 shows the diagram of the water mist system for the windows. The water mist system is installed at the top of the fixed window with a DN15 pipe which is perforated with 1mm holes, 10mm apart. Water is supplied and sprayed on the surface of the window to spread out evenly and to make a consistent layer of water on the plane. The sprayed water that flows downward is collected to the gutter at the bottom of the window, and returns to the water tank. The water supply pump has a 20 liter per minute (LPM) flow capability and 12 meters raise capacity to make constant flow rate at the end of the pipe; hence, to making an equal water layer depth on the whole surface of the windowpane. The water tank has a 50 liters capacity to supply water at the correct temperature uniformly. (b) Collect and return system at the bottom Fig. 2: Photos of water mist system 2.2 Experimental Method Figure 3 shows three measurement poles in the middle of the room to attain the indoor temperatures and measurement probes on each pole are allocated at five points at an equal distance from each other. Five thermocouples are attached on the surface of the glass, thus a total of twenty points from the thermocouples were measured. Data acquisition system NetDAQ was utilized to collect the data every 10 seconds. Fig. 1: Flow of water mist system Two unoccupied offices that have equal conditions in dimension and direction were selected to be evaluated and measured during the hot season from mid July to late August. Typical aluminum framed window system with 5mm double pane glass was selected and this was divided into 2 parts: the fixed window at the top and the sliding window at the bottom. From this window, the use of common double pane glass with no solar heat protection

3 device, vertical blinds (green color), film coated glass (reflection rate at 30%), water mist system, and chilled water mist system were measured and evaluated. The two offices for the experiment were ventilated well over 8 hours after finishing the measurement to make the two rooms first condition equal for the next experiment. After making the two rooms state uniform, the doors and windows were closed to defend the inlet of outdoor air. Two rooms without occupants and furniture were compared in the clear daytime to promote the effect of solar heat, but only data measured on the same day were compared to avoid the differences of temperature, clouds, and wind in unlike days. (a) Floor plan (b) Section Fig. 3: Measurement points of room temperature 3. RESULTS AND DISCUSSIONS The performance of the solar heat reduction methodsvertical blinds, film coated glass, water mist system, and chilled water mist system were quantified and assessed at two separate offices. The twenty points of room air temperature measured was averaged in the period of noon to 3 PM in which solar heat was the highest during the day. Air temperature measured every 10 seconds was averaged for 15 minutes and these values are shown and compared in figures 4 to Evaluation of Vertical Blinds and Film Coated Glass Figure 4 shows the comparison between vertical blinds and common double pane glass without any solar heat reduction devices on the window while the two rooms were air conditioned. The result concludes that the average room temperature with vertical blinds is lower by 0.7 (range 0.5~1.0) C than the average room temperature without blinds. Thus, vertical blinds can cool down the room temperature by reducing the solar heat through the window. Figure 5 illustrates the comparison between coated glass and common double pane glass without any devices in an air conditioned room. Contrast demonstrates the room temperature with coated glass is lower by 1.3 (range 1.1~1.5) C than the room temperature without coated glass. It indicates that coated film on glass can keep off solar rays, decrease cooling load, and save cooling energy. Figure 6 shows the assessment between vertical blinds and film coated glass. The results illustrates that the case of coated glass is lower by 0.6 (0.5~0.7) C than the case of

4 vertical blinds in room temperature. Coated glass is a little more efficient than the vertical blinds to reduce cooling energy and is validated again in figures 4 and 5. (2.1~2.5) C more than the common double pane glass in room temperature, and was confirmed the best device to save cooling energy. Coated glass can protect from solar heat on the surface of glass before entering the room and reflect the solar heat back, but vertical blinds are only capable of hindering solar heat after it enters the room. Due to these points, vertical blinds are less efficient in defending against solar heat and to save cooling energy. 3.2 Water Mist Device and Chilled Water Mist Device All the cases should be compared at the same time and the same condition, but outdoor environment was different during the experiment period, so they have to be compared relatively. The relative comparisons were analyzed; vertical blinds, coated glass, a water mist system, and a chilled water mist system can reduce more solar heat and is more superior at saving cooling energy in order of increasing efficiency. Figure 7 illustrates the evaluation between the room with a water mist system and a room without a water mist system in an air conditioned environment. This verifies that the case with the water mist system is lower by 1.8 (range 1.6~1.9) C in room temperature than the case of common double pane glass. Therefore, this system was more superior at saving cooling energy in hot seasons. Figure 8 demonstrates that the contrast between the water mist system and coated glass in the air conditioned room setting. The room temperature with the water mist system is lower by 1.1 (range 0.7~1.3) C than the room with coated glass. For that reason, the water mist system is more efficient than the coated glass at diminishing room temperature. In figure 9, we matched up the case with a chilled water mist system which was exposed to a supply of cool water in the pipe of the fan coil unit (FCU) where the water was then transported to the top of the window and sprayed downward compared to the case using common double pane glass. The chilled water mist system can reduce 2.2 Figure 10 illustrates the room temperature distribution contour at the center section of the room according to the solar heat protection device. At the window side of the room, we can contrast the differences of the temperature among four cases. The case of the water mist system is confirmed the most efficient to reduce the solar heat through the window glass. At the middle of the room, the case of common double pane glass (Fig. 10-a) shows the range of 26.0~27.5 C due to the solar heat flood, the water mist system(fig. 10-d) demonstrates the range of 25.0~26.0 C, then this contrast proves that the water mist system is more efficient at reducing solar heat. In the case of common glass, the temperature of the upper part of the room is higher than the temperature of the lower part of the room due to the accumulation of flooded solar heat through the window. In the case with the water mist system, the temperature of the upper part of the room is less than the temperature of the lower part by the effect of the water mist at the upper fixed window. Then the temperature of the lower part is a little high, since this is

5 due to the solar heat influx through the lower sliding window glass without the water mist system. The water mist system can shield off the solar heat influx throughout the window glass indicating that this system can cool down the temperature of the glass surface and reduce the thermal conduction through the glass. As a result, this system can save cooling energy. The combination of the water mist system with coated glass or vertical blinds can increase the solar heat reduction effect and can save more cooling energy. Fig. 6: Comparison between vertical blinds and film coated glass Fig. 4: Comparison between common glass and vertical blinds Fig. 7: Comparison between water mist systems and common glass Fig.8 Comparison between water mist system Fig. 5: Comparison between common glass and film coated glass and film coated glass

6 4. CONCLUSION Fig.9 Comparison between chilled water mist system and common glass (a) Common glass (b) Vertical blinds (c) Film coated glass (d) Water mist system Fig. 10 Comparison of indoor room temperature distribution contour In most buildings, cooled air is being supplied evenly despite the direction of the room in which it is facing. Accordingly, the west side spaces of a building cannot uphold the necessary cooling temperature that tenants want by reason of the solar heat coming through windows. In this study, the water mist system was projected to decrease the solar heat inflow through the window systems. The experiments were carried out to calculate the performance of the solar heat protecting tools. The room temperatures of two west sided rooms were measured to evaluate the saving efficiency of cooling energy for solar heat control devices. The experimental results are as follows. (1) The room temperature with vertical blinds is lower by 0.7 C than the room temperature without vertical blinds. And the room temperature with coated glass is lower by 1.3 C than the room temperature without coated glass. The data demonstrates that vertical blinds and coated film on glass can prevent solar heat from entering, and can cool down room temperature. (2) The case of the water mist system is lower by 1.8 C in room temperature than the case of common double pane glass with no solar heat protection. Also, the water mist system is lower by 1.1 C than the coated glass. Therefore, the water mist system is better than coated glass and vertical blinds at reducing room temperature. (3) The chilled water mist system heat exchanged with an FCU can reduce the room temperature by 2.2 C more than the common double pane glass, and was confirmed the best device in saving cooling energy.

7 (4) The comparison evaluation illustrates that the chilled water mist system, a regular water mist system, film coated glass, and vertical blinds are superior in order of decreasing efficiency to common double pane glass to cut cooling load in the room. The combination of these systems can augment the solar heat reduction effectively and can save more cooling energy. The water mist system can be utilized to decrease cooling load instead of remodeling cooling equipment that would require a high initial cost. This system can be adopted for structures with many glass windows like atriums to save cooling energy by reduction of solar heat. Only statistics taken on the same day were compared to avoid the differences in temperatures, clouds, and wind on different days. Future research would need more comparisons with plenty of data from long term measurements. (4) Duffie, J. and Beckman, W., Solar engineering of thermal process, John Wiley & Sons, Inc (5) Ha, D., Park, K. and Son, W., Study on the analysis of energy consumption corresponding window area ratio, Proceedings of the Society of Air-Conditioning and Refrigeration Engineers of Korea, Society of Air- Conditioning and Refrigeration Engineers of Korea, 2008 summer, pp (6) Kim, B., A study on thermal environmental and design methods to save energy in small glass-skin commercial buildings, Journal of Asian architecture and Building Engineering, 2004, Vol.3 No.1 (7) Park, Y. and Park, J., A study of energy use impacts by SHGCs of windows in detached house, Korean Journal of Air-Conditioning and Refrigeration Engineering, Society of Air-Conditioning and Refrigeration Engineers of Korea, 2010, v. 22, n.04, pp REFERENCES (1) ASHRAE, ASHRAE Handbook Fundamentals, ASHRAE (2) Choi, D., Choi, G., Kang, J. and Lee, S., The evaluation on thermal window high-tight composition of sliding door and open door, Proceedings of the Society of Air- Conditioning and Refrigeration Engineers of Korea, Society of Air-Conditioning and Refrigeration Engineers of Korea, 2009, pp (3) Choi, G., Kang, J., Yang, K. and Lee, S., A Research on air-tightness and thermal performance of windows system classified by windows type, Proceedings of the Society of Air-Conditioning and Refrigeration Engineers of Korea, Society of Air-Conditioning and Refrigeration Engineers of Korea, 2009, pp

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY Aivars Aboltins, Janis Palabinskis Latvia University of Agriculture aivars.aboltins@inbox.lv Abstract. The paper describes the results

More information

A STUDY ON THE APPLICABILITY OF THE TIME-DIVISION HOT-WATER SUPPLY HEATING FOR ONDOL - THE RADIANT FLOOR HEATING SYSTEM IN KOREA

A STUDY ON THE APPLICABILITY OF THE TIME-DIVISION HOT-WATER SUPPLY HEATING FOR ONDOL - THE RADIANT FLOOR HEATING SYSTEM IN KOREA A STUDY ON THE APPLICABILITY OF THE TIME-DIVISION HOT-WATER SUPPLY HEATING FOR ONDOL - THE RADIANT FLOOR HEATING SYSTEM IN KOREA Yong-Yee Kim 1, Ho-Tae Seok 2, Jeong-Min Choi 3, Hyun-Woo Lee 4,and Kwang-Woo

More information

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Improving Heating Performance of a MPS Heat Pump System With Consideration

More information

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former A study on reducing the energy demand of a liquid desiccant dehumidifier with a radiant panel system Tae Ha Leigh, 1 Dae Uk Shin, 1 Goo Sang Joe, 1 Min Gi Kim, 1 Myoung Souk Yeo, 2 and Kwang Woo Kim 2,*

More information

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2004 Experimental Study on the Performance and Oil Return Characteristics of

More information

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET I. S. Hwang and Y. L. Lee Department of Mechanical Engineering, Kongju National University, Korea E-Mail: ylee@kongju.ac.kr ABSTRACT

More information

DAYLIGHTING PERFORMANCE ON VENETIAN BLIND FOR HEALTHY APARTMENT HOUSING

DAYLIGHTING PERFORMANCE ON VENETIAN BLIND FOR HEALTHY APARTMENT HOUSING Paper s No. BUE-FISC2010 154 DAYLIGHTING PERFORMANCE ON VENETIAN BLIND FOR HEALTHY APARTMENT HOUSING Hwa Young Shin 1 / Yeunsook Lee 2 / Mi Seon Jang 2 / Ki Hoon Moon 3 / Jeong Tai Kim 1 * 1 Kyung Hee

More information

Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate

Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate KEYWORDS: Steel-plate forming, Induction heating, Triangle heating, Transverse shrinkage,

More information

A Study on the 2-D Temperature Distribution of the Strip due to Induction Heater

A Study on the 2-D Temperature Distribution of the Strip due to Induction Heater , pp.1-5 http://dx.doi.org/10.14257/astl.2015.90.01 A Study on the 2-D Temperature Distribution of the Strip due to Induction Heater Jong-Hyun Lee 1, Jin-Taek Kim 1, Sung-Hyuk Lim 2, Do-Gyun Jung 2, Hyeong-Jin

More information

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE HEFAT2012 9 th International nference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE Kim K.,

More information

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS Staņislavs GENDELIS, Andris JAKOVIČS Laboratory for mathematical modelling of environmental

More information

Residential Building Walls and Environment in Amman, Jordan

Residential Building Walls and Environment in Amman, Jordan Int. J. of Thermal & Environmental Engineering Volume 3, No. 2 (211) 1-7 Residential Building Walls and Environment in Amman, Jordan S. J. Sulaiman*, N. Beithou Department of Mechanical Engineering, Applied

More information

ω = (1) Kirby S. Chapman Ph.D.

ω = (1) Kirby S. Chapman Ph.D. White Paper: Relative Humidity Impacts of the AirFloor System in the Built Environment Kirby S. Chapman Ph.D. kirby.chapman@scavengetech.com Introduction Relative humidity is specified as one of the seven

More information

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES THERMAL SCIENCE, Year 2011, Vol. 15, No. 2, pp. 467-475 467 EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES by Krishnasamy SENTHILKUMAR a* and Pss

More information

High-efficiency Turbo Chiller (NART Series)

High-efficiency Turbo Chiller (NART Series) 67 High-efficiency Turbo Chiller (NART Series) Wataru Seki* 1 Kenji Ueda* 1 Jyou Masutani* 2 Yoichirou Iritani* 2 Turbo chillers are widely used for district heating and cooling, heat storage (regeneration)

More information

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

International Forum on Energy, Environment Science and Materials (IFEESM 2015) The Comparison and Analysis of Humidity Environment between Floor and Ceiling Radiant Cooling Systems that Combined with Displacement Ventilation Kai SUN 1 a *, Chuan-hui ZHOU 1 1 College of Urban Construction,

More information

EFFECT OF DIVERSE STREAM PATTERNS ON THE PERFORMANCE OF SOLAR AIR HEATER

EFFECT OF DIVERSE STREAM PATTERNS ON THE PERFORMANCE OF SOLAR AIR HEATER Int. J. Mech. Eng. & Rob. Res. 2013 P Velmurugan and R Kalaivanan, 2013 Research Paper ISSN 2278 0149 www.ijmerr.com Vol. 2, No. 1, January 2013 2013 IJMERR. All Rights Reserved EFFECT OF DIVERSE STREAM

More information

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System 4 th International Conference On Building Energy Environment Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System J Y Park H W

More information

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose

More information

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS , Volume 11, Number 2, p.21-26, 212 SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS C.Y. Tso and W.K. Chow Research Centre for Fire Engineering,

More information

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE Numbers of Abstract/Session (given by NOC) - 1 - STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE Seok Ho Yoon, Kong Hoon Lee, Chan Ho Song, and Ook Joong Kim Environment and Energy

More information

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE Proceedings of the Asian Conference on Thermal Sciences 2017, 1st ACTS March 26-30, 2017, Jeju Island, Korea ACTS-P00385 THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK

More information

Experimental Research on Monomial Cooling Measure of Greenhouse in Summer

Experimental Research on Monomial Cooling Measure of Greenhouse in Summer Smart Grid and Renewable Energy, 2013, 4, 48-52 http://dx.doi.org/10./sgre.2013.41007 Published Online February 2013 (http://www.scirp.org/journal/sgre) Experimental Research on Monomial Cooling Measure

More information

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1 HEFAT27 5 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp PERFORMANCE ANALYSIS OF AIR-COOLED CONDENSER USING MICRO-FIN TUBES P.A.Patil

More information

A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM

A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM Jae-Han Lim 1, Myoung-Souk

More information

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon

More information

Development of Motor Fan Noise Prediction Method in Consideration of Operating Temperature during Engine Idling

Development of Motor Fan Noise Prediction Method in Consideration of Operating Temperature during Engine Idling New technologies Development of Motor Fan Noise Prediction Method in Consideration of Operating Temperature during Engine Idling Yasuhito Suzuki* Masahiro Shimizu* Abstract In these years there is an increasing

More information

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 The Effect of the Ventilation and the Control Mode on the Performance of

More information

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM , Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,

More information

CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS

CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS Masaya Saito*, Satoshi Nasu*, Moto Nakano** and Kouko Miyakawa*** *Sapporo School of The Arts Geijustu-no-mori

More information

A study of Transient Performance of A Cascade Heat Pump System

A study of Transient Performance of A Cascade Heat Pump System Available online at www.sciencedirect.com ScienceDirect Energy Procedia 79 (2015 ) 131 136 2015 International Conference on Alternative Energy in Developing Countries and Emerging Economies A study of

More information

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Y. Momoi 1, K. Sagara 1, T. Yamanaka 1 and H. Kotani 1 1 Osaka University, Graduate School of Eng., Dept.

More information

Visual analysis on the nightscape lighting for the pedestrian and greenery zone of a neighborhood park

Visual analysis on the nightscape lighting for the pedestrian and greenery zone of a neighborhood park , pp.20-25 http://dx.doi.org/10.14257/astl.2015.89.05 Visual analysis on the nightscape lighting for the pedestrian and greenery zone of a neighborhood park Jun Kwon Jeong 1, Jack Ngarambe 1, Hong Soo

More information

Heat Transfer in Evacuated Tubular Solar Collectors

Heat Transfer in Evacuated Tubular Solar Collectors Heat Transfer in Evacuated Tubular Solar Collectors Graham L. Morrison, Indra Budihardjo and Masud Behnia School of Mechanical and Manufacturing Engineering University of New South Wales Sydney 2052 Australia

More information

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? Corresponding author: Jasmin Geppert University of Bonn Household and Appliance Technology Section Nussallee 5 D-53115 Bonn E-Mail: haushaltstechnik@uni-bonn.de

More information

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Risto Kosonen 1, Arsen Melikov 2, Boryana Yordanova 2 and Lyuben Bozkhov 2 1 Halton Oy 2 International

More information

Human response to thermal environment in rooms with chilled beams

Human response to thermal environment in rooms with chilled beams Human response to thermal environment in rooms with chilled beams Arsen Melikov 1, Boryana Yordanova 1, Lyuben Bozkhov 1, Viktor Zboril 1,2, Risto Kosonen 3 1 International Center for Indoor Environment

More information

A Study on Hierarchy of Spatial Configuration in Outpatient Department of General Hospital

A Study on Hierarchy of Spatial Configuration in Outpatient Department of General Hospital , pp.56-60 http://dx.doi.org/10.14257/astl.2015.100.13 A Study on Hierarchy of Spatial Configuration in Outpatient Department of General Hospital Sangwon Oh 1, Heangwoo Lee 2, Yongseong Kim 3 1 Speed-yooh@hanmail.net

More information

Performance Analysis of Water-Water Heat Pump System of 100 kw Scale for Cooling Agricultural Facilities

Performance Analysis of Water-Water Heat Pump System of 100 kw Scale for Cooling Agricultural Facilities Original Article J. of Biosystems Eng. 39(1):34-38. (2014. 3) http://dx.doi.org/10.5307/jbe.2014.39.1.034 Journal of Biosystems Engineering eissn : 2234-1862 pissn : 1738-1266 Performance Analysis of Water-Water

More information

Purdue e-pubs. Purdue University

Purdue e-pubs. Purdue University Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 206 Experimental Investigation of the Refrigerant Flow Distribution Characteristic

More information

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area Sahil

More information

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump Available online at www.sciencedirect.com Procedia Engineering 8 (2011) 165 170 2 nd International Science, Social-Science, Engineering and Energy Conference 2010: Engineering Science and Management Hot

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

Effects of seawater flow rate and evaporation temperature on performance of Sherbet type ice making machine

Effects of seawater flow rate and evaporation temperature on performance of Sherbet type ice making machine IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Effects of seawater flow rate and evaporation temperature on performance of Sherbet type ice making machine To cite this article:

More information

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System Feasibility of a Liquid Desiccant Application in an Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, S.K.Han 1, S.Y. Cho 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang

More information

Mango Sheet Drying by the Solar Dryer Combine with Electric Coil

Mango Sheet Drying by the Solar Dryer Combine with Electric Coil Mango Sheet Drying by the Solar Dryer Combine with Electric Coil Narin Koolnapadol, Rajabhat Rajanagarindra University, Thailand Chatchawan Nimrotham, Rajabhat Rajanagarindra University, Thailand The Asian

More information

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Control Method Of Circulating Refrigerant Amount For Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Control Method Of Circulating Refrigerant Amount For Heat Pump System Jin

More information

Development of magnetic pulse crimping process for highdurability

Development of magnetic pulse crimping process for highdurability RESEARCH ARTICLE OPEN ACCESS Development of magnetic pulse crimping process for highdurability connection terminal Ji-Yeon Shim*, Bong-Yong Kang** *( Carbon&Light Materials Application R&D Group, KITECH,

More information

MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM

MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM Proceedings of ASME FEDSM 3 4 th ASME_JSME Joint Fluids Engineering Conference Honolulu, Hawaii, USA, July 6-1, 23 MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING

More information

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor

More information

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING Vladimír Zmrhal 1, Jan Hensen 2 and František Drkal 1 1

More information

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance

More information

Fire Test Evaluation using the Kerosene and Aviation Fuel

Fire Test Evaluation using the Kerosene and Aviation Fuel Fire Test Evaluation using the Kerosene and Aviation Fuel K. S. Bang, J.C. Lee, C. S. Seo, K. S. Seo, H. J. Kim* Korea Atomic Energy Research Institute, 15 Dukjin-Dong, Yuseung-gu, Daejeon, Korea 35-353

More information

Design and Experimental Studies on Modified Solar Dryer

Design and Experimental Studies on Modified Solar Dryer International Journal of Engineering Research and Technology. ISSN 0974-3154 Volume 8, Number 1 (2015), pp. 43-47 International Research Publication House http://www.irphouse.com Design and Experimental

More information

[Patil* et al., 5(7): July, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116

[Patil* et al., 5(7): July, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY INTELLIGENT LIGHTING SYSTEM WITH ENERGY EFFICIENCY Neha Patil*, Prof.A.C.Wani * P. G.Student, M.E. [Digital Electronics], SSBT

More information

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Design and Research of the Digital VRV Multi- Connected Units With Three

More information

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN , Volume 6, Number 4, p.248-254, 04 RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN C.L. Choi Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Water

More information

Design of a high accuracy non-dispersive Infrared gas sensor for continuous emission monitoring of carbon monoxide emitted from an industrial stack

Design of a high accuracy non-dispersive Infrared gas sensor for continuous emission monitoring of carbon monoxide emitted from an industrial stack , pp.20-26 http://dx.doi.org/10.14257/astl.2015. Design of a high accuracy non-dispersive Infrared gas sensor for continuous emission monitoring of carbon monoxide emitted from an industrial stack Trieu-Vuong

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

Performance Analysis of Solar Air Heater Using Three Wire Mesh

Performance Analysis of Solar Air Heater Using Three Wire Mesh MIT International Journal of Mechanical Engineering, Vol. 5, No. 1, January 2015, pp. 13-17 13 Performance Analysis of Solar Air Heater Using Three Wire Mesh Sumit Kumar Singh Nitin Agarwal Vineet Tirth

More information

Transcritical CO2 Bottle Cooler Development

Transcritical CO2 Bottle Cooler Development Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains

More information

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU Energy and Buildings 39 (2007) 702 708 www.elsevier.com/locate/enbuild Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU Ming-Tsun Ke a, *, Kuo-Liang

More information

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model Yoshiyuki Shimoda, Osaka University Takuro Fujii, Osaka University Takao Morikawa, Osaka University Minoru

More information

REVIEW ON HOT GAS DEFROSTING SYSTEM FOR VAPOR COMPRESSION REFRIGERATION SYSTEM

REVIEW ON HOT GAS DEFROSTING SYSTEM FOR VAPOR COMPRESSION REFRIGERATION SYSTEM http:// REVIEW ON HOT GAS DEFROSTING SYSTEM FOR VAPOR COMPRESSION REFRIGERATION SYSTEM S.D.Kathwate 1, U.S.Wankhede 2 1 M. Tech. IV Semester student, Heat Power Engineering, 2 Professor, Mechanical Engineering

More information

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem A Simplified model for estimating the regeneration effectiveness of a counter flow regenerator for a liquid desiccant system M.H. Kim 1, H.J. Cho 1, and J.W. Jeong 1* 1 Division of Architectural Engineering,

More information

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN , Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen

More information

Modified geotextile tube a new geotextile tube for optimized retaining efficiency and dewatering rate

Modified geotextile tube a new geotextile tube for optimized retaining efficiency and dewatering rate Modified geotextile tube a new geotextile tube for optimized retaining efficiency and dewatering rate Hyeong-Joo Kim 1), Tae-Woong Park 2), Sung-Gil Moon 3), Hyeong-Soo Kim 4), Ri Zhang 5), and *Peter

More information

Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater

Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater MIRCEA NICOARĂ mircea.nicoara@mec.upt.ro AUREL RĂDUłĂ aurel.raduta@mec.upt.ro LAURENłIU ROLAND CUCURUZ roland.cucuruz@mec.upt.ro COSMIN

More information

TRANSMISSIVITY BEHAVIOR OF SHREDDED SCRAP TIRE DRAINAGE LAYER IN LANDFILL COVER SYSTEM *

TRANSMISSIVITY BEHAVIOR OF SHREDDED SCRAP TIRE DRAINAGE LAYER IN LANDFILL COVER SYSTEM * TRANSMISSIVITY BEHAVIOR OF SHREDDED SCRAP TIRE DRAINAGE LAYER IN LANDFILL COVER SYSTEM * Krishna R. Reddy, Aravind Marella and Prasanth Ala University of Illinois at Chicago, Department of Civil and Materials

More information

Hot Air-Microwave Combined Drying Characteristics of Gypsum Board. Won-Pyo Chun, Sung-Il Kim, and Ki-Woo Lee 1

Hot Air-Microwave Combined Drying Characteristics of Gypsum Board. Won-Pyo Chun, Sung-Il Kim, and Ki-Woo Lee 1 European Drying Conference - EuroDrying'11 Palma. Balearic Island, Spain, 26-28 October 11 Hot Air-Microwave Combined Drying Characteristics of Gypsum Board Won-Pyo Chun, Sung-Il Kim, and Ki-Woo Lee 1

More information

Experimental Studies on Aero Profile Thermosyphon Solar Water Heating System

Experimental Studies on Aero Profile Thermosyphon Solar Water Heating System International Journal of Engineering Research and Technology. ISSN 0974-3154 Volume 9, Number 1 (2016), pp. 89-94 International Research Publication House http://www.irphouse.com Experimental Studies on

More information

Adelaide Homes Design Guide 3 - Shading

Adelaide Homes Design Guide 3 - Shading Adelaide Homes Design Guide 3 - Shading Protecting windows and walls from excessive solar gain in the summer can greatly reduce over-heating. Properly designed retractable or movable shades will provide

More information

Development of Smart Phone Applications Linked with Fire Alarm Control Panel in Automatic Fire Detection System

Development of Smart Phone Applications Linked with Fire Alarm Control Panel in Automatic Fire Detection System , pp. 11-18 http://dx.doi.org/10.14257/ijsh.2016.10.2.02 Development of Smart Phone Applications Linked with Fire Alarm Control Panel in Automatic Fire Detection System Ha-Sung Kong 1, Jong-Seog Yang 2

More information

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling Enhancement using Herringbone wavy & Smooth Wavy fin Exchanger for Hydraulic Oil Cooling 1 Mr. Ketan C. Prasadi, 2 Prof. A.M. Patil 1 M.E. Student, P.V.P.I.T.,Budhagaon,Sangli AP-India 2 Associate Professor,

More information

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

More information

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator Dr. R. A. Kathar 1, S. D. Surushe 2 1 Associate Professor, Mechanical

More information

A TRNSYS Simulation Case Study on Utilization of Heat Pump For both Heating and Cooling

A TRNSYS Simulation Case Study on Utilization of Heat Pump For both Heating and Cooling Energy Science and Technology Vol. 3, No. 2, 2012, pp. 84-92 DOI:10.3968/j.est.1923847920120302.397 ISSN 1923-8460[PRINT] ISSN 1923-8479[ONLINE] www.cscanada.net www.cscanada.org A TRNSYS Simulation Case

More information

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System Kwanghee Seo 1) and Taewan Kim 2)* 1) KEPCO Engineering & Construction Company. INC., 269 Hyeoksin-ro,

More information

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 22 An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning

More information

Heat pump supplemental heating system for motor vehicles

Heat pump supplemental heating system for motor vehicles 1 Heat pump supplemental heating system for motor vehicles D Antonijevic and R Heckt Visteon Automotive Systems, Visteon Deutschland GmbH, Kerpen, Germany Abstract: The paper deals with the importance

More information

PASSIVE HEAT EXCHANGER ANTI-FOULING FOR SOLAR DHW SYSTEMS

PASSIVE HEAT EXCHANGER ANTI-FOULING FOR SOLAR DHW SYSTEMS Proceedings of ISEC 2005 2005 International Solar Energy Conference August 6-12, 2005, Orlando, Florida, USA ISEC2005-76232 PASSIVE HEAT EXCHANGER ANTI-FOULING FOR SOLAR DHW SYSTEMS Stephen J. Harrison

More information

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics Journal of Electronics and Information Science (2018) 3: 22-33 Clausius Scientific Press, Canada Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics Lian-Tuu Yeh, ASME Fellow

More information

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 The Development Of High Efficiency Air Conditioner With Two Compressors

More information

Analysis of Pullout Resistance of Soil-Nailing in Lateritic Soil

Analysis of Pullout Resistance of Soil-Nailing in Lateritic Soil Analysis of Pullout Resistance of Soil-Nailing in Lateritic Soil B,L.A. Isaka 1, B.C. Madushanka 1 and N.H. Priyankara 1 1 Department of Civil and Environmental Engineering Faculty of Engineering University

More information

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY Xiaoyun Xie, Yidan Tang, Xiaoqin Yi, Shuanqiang Liu,Yi Jiang Department of Building Science and Technology,

More information

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings Downloaded from orbit.dtu.dk on: May 5, 218 Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings Fang, Lei; Yuan, Shu;

More information

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK COURSE OUTLINE ACHP 244 AIR CONDITIONING II Prepared By: CHARLES STEAD Updated By: Michael J. Newtown, P.E. CANINO SCHOOL OF ENGINEERING

More information

Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating

Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating Vladimír Zmrhal Czech Technical University in Prague, Faculty of Mechanical Engineering Corresponding email: Vladimir.Zmrhal@fs.cvut.cz

More information

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Comparison of Performance of a Residential Air- Conditioning System Using

More information

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System Enhancement of COP by Using Spiral and Microchannel instead of conventional of VCR System 1 P.G. Lohote, 2 Dr.K.P. Kolhe. 1 P.G. Student, 2 Professor. 1,2 Department of Mechanical Engineering, JSPM s,

More information

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Effect of Height Difference on The Performance of Two-phase Thermosyphon

More information

High Efficiency R-134a Compressor for Domestic Refrigerator

High Efficiency R-134a Compressor for Domestic Refrigerator Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1996 High Efficiency R-134a Compressor for Domestic Refrigerator D. S. Kim Samsung Electronics

More information

MINIMISING THE RISK OF WATER HAMMER AND OTHER PROBLEMS AT THE BEGINNING OF STAGNATION OF SOLAR THERMAL PLANTS- A THEORETICAL APPROACH

MINIMISING THE RISK OF WATER HAMMER AND OTHER PROBLEMS AT THE BEGINNING OF STAGNATION OF SOLAR THERMAL PLANTS- A THEORETICAL APPROACH MINIMISING THE RISK OF WATER HAMMER AND OTHER PROBLEMS AT THE BEGINNING OF STAGNATION OF SOLAR THERMAL PLANTS- A THEORETICAL APPROACH Wolfgang Streicher Institute of Thermal Engineering, Graz University

More information

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers Ashraf A 1, Mohammed Shan N 2, Thoufeeq Azad 3, Bibin S4, Arun S 5 1-4 Students, 5 Assistant Professor Department of

More information

Operation of a Two-Phase Reverse Loop Thermosyphon

Operation of a Two-Phase Reverse Loop Thermosyphon Journal of Applied Science and Engineering, Vol. 18, No. 3, pp. 259 264 (2015) DOI: 10.6180/jase.2015.18.3.06 Operation of a Two-Phase Reverse Loop Thermosyphon Meng-Chang Tsai 1, Shung-Wen Kang 2 *, Heng-Yi

More information

ASHRAE JOURNAL ON REHEAT

ASHRAE JOURNAL ON REHEAT Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide

More information

HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL

HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL GROUP 1 HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL Daniel Abrahamson Department of Architecture University of Oregon Eugene, Oregon 97403 dva@uoregon.edu Dijon Jones Department of Architecture

More information

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Comparison of Thermal Comfort by Radiant Heating and Convective Heating Journal of Engineering, Project, and Production Management 2015, 5(1), 26-35 Comparison of Thermal Comfort by Radiant Heating and Convective Heating Shigeru Imai 1 and Shoichi Kojima 2 1 MSc Student, Department

More information

International Journal of Informative & Futuristic Research ISSN (Online):

International Journal of Informative & Futuristic Research ISSN (Online): Reviewed Paper Volume 2 Issue 9 May 2015 International Journal of Informative & Futuristic Research ISSN (Online): 2347-1697 Performance Comparison of R22 and R290 Refrigerants Using Smaller Paper ID IJIFR/

More information

A Study on Cooling Rate with Blade and Sound Fire Extinguisher

A Study on Cooling Rate with Blade and Sound Fire Extinguisher International Journal of Engineering Research and Technology. ISSN 0974-3154 Volume 11, Number 12 (2018), pp. 1969-1976 International Research Publication House http://www.irphouse.com A Study on Cooling

More information