EQGA AND EQGB HYGIENIC VERSION, CODE SUFFIX I = 3 AND 4
|
|
- Hope Alannah Boone
- 5 years ago
- Views:
Transcription
1 EQGA AND EQGB HYGIENIC VERSION, CODE SUFFIX I = 3 AND 4 ASSEMBLY AND MAINTENANCE INSTRUCTIONS Contents Page Hygienic version Delivery Safety precautions Mounting on the floor Suspending from the ceiling To install the drainage water trough To clean the casing To clean the finned-tube coils To clean the fan To clean the rotary heat exchanger To clean the plate heat exchanger To disinfect the air handling unit
2 2 Assembly and maintenance instructions HYGIENIC VERSION Recommendations for the selection of functions that meet requirements on hygiene, among others VDI 6022, are presented in the ACON product selection program for sizing and configuring a hygienic air handling unit. Internal docking Window for easy inspection Hygienically approved non-metallic components Thermal insulation to class T3 Condensation insulation to class TB3 Stainless or pre-painted casing Casing to leakage class L2 F7 bag filters, HEPA or Carbon filters Integrated or fully sealed fan beams without sharp edges Components which are simple to clean, for example coils, rotary heat exchangers and plate heat exchangers Large inspection spaces Provision for coil with withdrawable drip tray Floor without grooves and block joints DELIVERY The hygienic air handling unit is delivered in accordance with one of the following alternatives: As one delivery unit, i.e. one factory-assembled block unit. As one delivery unit, i.e. one factory-assembled unit mounted on a base frame. Several block units, which must be connected to form one unit on site. SAFETY PRECAUTIONS Lifting and transport of air handling units, mounting them on a base frame and fitting them with support feet, the docking of blocks, safety precautions and inspection prior to commissioning are specified in the General instructions, Safety Precautions, 8658 GB.
3 Assembly and maintenance instructions 3 MOUNTING ON THE FLOOR The floor on which the unit is placed must be flat, to ensure problem-free operation. Check the floor carefully to avoid distortion of the unit and thus ensure that the doors will not be difficult to open and close. EQAZ-05 adjustable feet are available to allow for individual height adjustment of the EQAZ-04 base frame. Place the support washer (supplied) under the foot as shown in Figure 8. It is important to make sure that the unit is level. If the air handling unit includes unit sections that are provided with drains, space must be available for a water trap (such as the EQAZ-08) as shown in Fig. 9. Adjustment of the lateral and longitudinal position of the air handling unit is best carried out by means of a roller crowbar or the like, as shown in Figures 10 and 11. Fig. 9 Block unit without base frame Free space for water trap = min. 150 mm N.B! The air handling unit should slope 2 % towards the inspection side to allow for drainage during cleaning. Flushing water can be collected in EQWZ-02 drainage water trough (accessory). Fig. 10 EQWZ-02 2% Block unit on EQAZ-04 base frame Fig. 7 MOUNTING ON ADJUSTABLE FEET Mount the feet spacing them evenly along the side beams if more than 4 feet are to be fitted. If 4 feet are used, fit one foot at each end of the side beams. To adjust the adjusting screw: 1) Back off the locking nut (A). 2) Adjust the height with set screw (B). 3) Lock the locking nut (A). Fig mm gap in the end of the base frame Fig. 8
4 4 Assembly and maintenance instructions SUSPENSION FROM THE CEILING Place the unit on a stand made on site as shown in the examples below. Suspend the unit from hangers. The larger units must be fitted with EQAZ-29 floor grating so that service personnel can enter the air handling unit. The stand must also be constructed so that the bottom panels are supported by either traversing or longitudinal support beams. Hanger Important! The position of the hangers can be easily adjusted with the stand according to the figure. A Hanger min. 800 Retaining flange A max. 35 mm along the inspection side on unit sizes Cut and remove the edge of the flange A at the hinge locations on unit sizes Retaining flange A max. 75 mm along the inspection side on unit sizes HEAVY-DUTY INSTALLATION Suitable installation for unit sizes Example 1 Hanger Clamp max. 1,5 m HEAVY-DUTY INSTALLATION Suitable installation for unit sizes Example 2 N.B! If the unit is fitted with a EQWZ-02 water drainage trough, the edge of the flange (A) should only be by the corner frame members of the casing. View A View A View B 2% View B 2% N.B! The tensile strength verification must be issued by an authorized HVAC installation engineer.
5 Assembly and maintenance instructions 5 TO INSTALL THE DRAINAGE WATER TROUGH, EQWZ-02 The drain water trough is supplied as a loose part and should be fitted after the air handling unit has been docked. Place the drain water trough onto the mounting angle bracket and fasten it with the screws supplied (see illustration). 2. Clean the coil with a high-pressure cleaner. If the coil is deeper than six tubes, a THD Power Clean is needed to ensure a full cleanability. 3. Point the nozzle at a 45-degree angle to have a free passage for the water jet through the coil. Make sure that the water penetrates the coil. 4. Remove all dirt. 5. Dry all surrounding parts in the unit. TO CLEAN THE CASING Carry out the following before cleaning the interior of the casing: Remove the filters Remove the withdrawable filter frame Remove the withdrawable sound attenuating baffles Remove the withdrawable droplet separators Remove anti-skid devices, if fitted Remove withdrawable drip trays CLEANING 1. Vacuum-clean surfaces to remove loose dust. 2. Apply suitable dirt and degreasing agent such as cold degreasing agent on interior surfaces. 3. Flush the surfaces clean with clean water after a few minutes. N.B! Do not use a high-pressure spray gun. The flushing water is collected in the drain water trough which can be connected to a drain or a collection vessel. CLEANABLE COILS FOR HYGIENE APPLICATIONS All coils with hygiene fins are fully cleanable according to the standards VDI3803 and VDI6022. This means that the coil can be cleaned with a high-pressure water system right through the core. The cleaning nozzle used for coils with a fin pitch of mm and deeper than six tubes is THD Power Clean manufactured by TECHNISCHER HYGIENE DIENST GMBH ( info@thd.info, web: If the coil is six tubes deep or less, an ordinary nozzle can be used. 1. Make sure that no sensitive equipment, either inside or outside the unit, can be harmed by the water. Be extra careful not to damage the filter. If the unit has an empty section (EQTC), use the special drip plate to protect the rest of the unit. CLEANING THE FAN 1. Open the inspection panel if the centrifugal fan section has one. 2. Vacuum-clean the fan to remove dry dust. 3. Apply suitable dirt and degreasing agent such as cold degreasing agent on the fan blades, motor (degree of protection IP54) and other surfaces. 4. Flush with clean water after a few minutes. N.B! Do not use a high-pressure spray gun. 5. If the fan casing is equipped with a means for drainage, the water will run out on the floor of the unit casing and be collected in the drainage water trough. Otherwise, wipe the interior of the fan casing dry with a cloth. TO CLEAN THE FANS 1. Vacuum-clean the surface of the rotor to remove dry dust. 2. Apply suitable dirt and degreasing agent such as cold degreasing agent onto the rotor surface and other surfaces. 3. Flush after a few minutes with a high-pressure spray gun. Aim the jet of water at right angles towards the rotor structure. The spray nozzle should appropriately be held approx. 50 mm away from the face surface of the rotor. Suitable pressure: up to 80 bar. 4. Vacuum-clean to remove water or blow surfaces clean with compressed air. Important! Do not use methyl ethyl ketone, aceton or corrosive liquids.
6 6 Assembly and maintenance instructions TO CLEAN THE PLATE HEAT EXCHANGER 1. Vacuum-clean the surface of the rotor to remove dry dust. 2. Apply suitable dirt and degreasing agent such as cold degreasing agent onto the heat exchanger surfaces. 3. Flush after a few minutes with a high-pressure spray gun. The spray nozzle should be held 3-5 cm from the face surface. Suitable pressure: up to 80 bar. EQRZ-01 flushing water tray is an accessory for collecting flushing water on the supply air side. 4. Vacuum-clean to remove water or blow surfaces clean with compressed air. 5. Clean the flushing water tray and drip tray. 6. Clean the droplet separator, if fitted. DISINFECTION If disinfection is required, for example, in hospital environments, after finishing the cleaning procedure described the above, the surfaces can be treated e.g. with any of the following agents: 5 % chlorinated solution 6 % hydrogen dioxide solution Hydrogen dioxide mist % isopropyl alcohol Hydrogen peroxide Apply the cleaning agent on all the surfaces inside the air handling unit. Warning! If a nozzle of a size delivering 2 litres/min at 7 bar is used, the supply pressure to the spray gun must not exceed 25 bar since the nozzle is inclined at an angle of 20 º to the face surface, and if the pressure is higher, the face surface may be deformed. Warning! Wear protective gloves and protective face mask. See the protection and safety instructions for the relevant cleaning agent. Supply air at the bottom Extract air Supply air The droplet separator, if fitted, can be removed by lifting and folding it. Drip tray for collecting condensate and flushing water Flushing water tray EQRZ-01 Supply air uppermost Supply air Extract air Flushing water tray EQRZ-01 Drip tray for collecting condensate and flushing water Make sure that the damper blades are open when you flush them clean
GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION
GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES Using the air handling unit... Free space for service and repair work... GENERAL INSTRUCTION Checking prior to commissioning...3
More informationIndholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL
Indholdsfortegnelse Danvent Air Handling Units SERVICE MANUAL Service Servicing of the Air Handling Unit Your ventilation system is equipped with a Danvent Air Handling Unit (AHU) which will contribute
More informationlindab we simplify construction Lindab Modular air handling units Service and maintenance manual
Lindab Modular air handling units Service and maintenance manual Service and maintenance manual General... 3 2 Warnings and Tips... 3 3 Functional sections... 3 3.1 Fan section... 3 3.2 Heater section
More informationDecentralised ventilation units
Notes on installation Decentralised ventilation units FSL / SCHOOLAIR GB/en TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany Phone: +49 (0) 2845 2020 Fax: +49 (0) 2845 202265 E-mail: trox@trox.de
More information39 HQ Air Handling Units AiroVision
VDI 6022 39 HQ Air Handling Units AiroVision Assembly/Installation, Commissioning, Maintenance Manual Type tested Production monitored AHU N : 08.02.251 Range: 39HQ DIN 1946-4 EN 13053 2 Code No: B.8.1.3i
More informationSmoke extraction duct of sheet steel
Smoke extraction duct of sheet steel The accessories that are available, as for example inspection openings, steel grilles, plenum boxes, ceiling diffusers, splitter attenuators, bends, tees and connecting
More informationK Specifications. Max. Water Volume
K 2.75 High Pressure Washer Operator Manual Overview... 2 Precautions... 2-4 Assembly Instructions... 4 Operating Instructions... 5 Using the Accessories... 6 Working with Detergents... 7 Shut Down and
More informationK 2.97 M. Specifications Operating pressure, max PSI Water volume GPM Voltage V Amp draw AMPS
K 2.97 M High Pressure Washer Operator Manual Overview... 2 Important Precautions... 3-4 Assembly Instructions... 4 Operating Instructions... 5 GFCI Instructions... 6 Using the Accessories... 6 Working
More information40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT
Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging
More informationAT4 Hygienic Application According to Guideline VDI 6022
Air-handling-units AT4 Hygienic Application According to Guideline VDI 6022 AT4 AHU for hygienic application The VDI guideline 6022, part 1 and 3 defines the hygienic requirements for AHU with regard to:
More informationModel K 330 M Part No
Model K 330 M Part No. 1.994-916.0 High Pressure Washer Operator Manual Overview..................................1 Precautions...............................1-3 Assembly Instructions.........................3
More informationHEAT RECOVERY AIR HANDLING UNIT
HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty
More informationModel K205 M Plus Part No
Model K205 M Plus Part No. 1.223-820.0 High Pressure Washer Operator Manual Overview..................................1 Precautions...............................1-3 Assembly Instructions.........................3
More informationModel K 280 M Part No
Model K 280 M Part No. 1.189-205.0 High Pressure Washer Operator Manual Overview...................................1 Precautions................................1-3 Assembly Instructions.........................3
More informationOPERATION AND MAINTNENCE MANUAL
OPERATION AND MAINTNENCE MANUAL VPI QUALITY WINDOWS 3420 E Ferry Ave. Spokane WA. 99202 TABLE OF CONTENTS Part 1) Storage and Handling... 2 Part 2) Installation, Protection and Initial Cleaning... 2 Part
More informationModel K 240 plus Part No
Model K 240 plus Part No. 1.223 585.0 High Pressure Washer Operator Manual Overview... 2 Precautions... 2-4 Assembly Instructions... 4 Operating Instructions... 5 GFCI Instructions... 6 Using the Accessories...
More informationK 2.90 M. Specifications Operating pressure, max PSI Water volume GPM Voltage V Amp draw AMPS
K 2.90 M High Pressure Washer Operator Manual Overview... 2 Important Precautions... 3-4 Assembly Instructions... 4 Operating Instructions... 5 GFCI Instructions... 6 Using the Accessories... 6 Working
More informationIFU 005 CLEANING / PREPARATION OF OUTDOOR HEAT EXCHANGE SURFACES & COILS. Date Approved
CLEANING / PREPARATION OF OUTDOOR HEAT EXCHANGE SURFACES & COILS Document Type / Category Information for Use (IFU) / Clean & Prepare Outdoor Heat Exchange Coils & Surfaces Document Number 09-06-005 Document
More informationPlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS
AIR COMFORT AIR TREATMENT 9933 GB 2016.05.25 PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN» INSTALLATION AND MAINTENANCE INSTRUCTIONS contents Page Installation options...... 2 Checks to be
More informationApplication note. LCD Module. Precautions for LCM handling. LCM handling V 1.1
LCD Module Precautions for LCM handling Application note LCM handling V 1.1 admatec GmbH Wendenstrasse 29, 20097 Hamburg, Germany Tel.: +49-40-238533-0, Fax: +49-40-238533-11 Internet: www.admatec.de,
More informationA. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.
SECTION 23 70 00- CENTRAL HVAC EQUIPMENT PART 1: GENERAL 1.1 PURPOSE: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.
More informationUnits for suspended ceilings
X X testregistrierung Units for suspended ceilings Type, hinged induced air grille, water connections Active chilled beam with two-way air discharge and horizontal heat exchanger, suitable for grid ceilings
More informationRycroft Supapac Plate Heat Exchangers
Rycroft Supapac Plate Heat Exchangers Installation Operation & Maintenance Manual Ormandy Rycroft Duncombe Road Bradford BD8 9TB England TEL +44 (0)1274 490911 FAX +44 (0)1274 498580 www.rycroft.com 1.
More informationINSTRUCTION MANUAL W-400
USE and MAINTENANCE INSTRUCTION MANUAL Bellaria WBX WB GRAVITY SPRAY GUN Series LPH-400 WB en it fr es pt de se TECHNICAL DATA Classic Plus Series LPH-400 (LVLP) Classic Plus Nozzle_Needle set Combination
More informationK Specifications. Max. Water Volume
K 2.35 High Pressure Washer Operator Manual Overview... 2 Precautions... 2-4 Assembly Instructions... 4 Operating Instructions... 5 Using the Accessories... 6 Working with Detergents... 7 Shut Down and
More informationCompact. Efficient. TROX.
Compact. Efficient. TROX. The art of handling air TROX understands the art of handling air like no other company. Since its foundation in 1951, TROX has been developing and manufacturing sophisticated
More informationK 3.97 M. Specifications or visit our website: In USA call: Part No
K 3.97 M High Pressure Washer Operator Manual Overview... 2 Precautions... 2-4 Assembly Instructions... 4-5 Operating Instructions... 5-6 GFCI Instructions... 6 Using the Accessories... 6 Working with
More informationUSE and MAINTENANCE INSTRUCTION MANUAL GRAVITY. WS-400 EVO LS-400 Entech. SPRAY GUN Series. en it fr es pt de se
USE and MAINTANCE INSTRUCTION MANUAL WS-400 EVO LS-400 Entech GRAVITY SPRAY GUN Series en it fr es pt de se TECHNICAL DATA WS-400 WS-400 EVO WS-400 Clear WS-400 Base WS-400-1301 EVO 1.3 170 365 260 WS-400-1401
More informationINSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD
TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system
More informationINSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X
INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...
More informationTable of Contents. Specifications... page 2. Installation... page 3. Customizing... page 4. Reversing door swing... page 5
Introduction The Scotsman Compact Refrigerator is a unique product, capable of being built into a cabinet because of its front vented, forced-air cooling system. It s also designed to be a companion to
More informationModel K 5800 G Part No
K5800G Manual 11/30/01 5:02 PM Page 1 Model K 5800 G Part No. 1.194-103.0 High Pressure Washer Operator Manual Overview..................................1 Precautions...............................1-2
More informationModel HD 3000 Part No High Pressure Washer Operator Manual
Model HD 3000 Part No. 1.187-116 High Pressure Washer Operator Manual Overview..................................1 P recautions...............................1-2 Assembly Instructions.........................3
More informationINSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD
TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system
More informationLiquid-coupled heat exchanger LQRT ECONET
ECONET includes the following: 1. Functional components with heat exchanger on the supply air side and the exhaust air side. 2. Pump unit (not installed). 3. Control unit for liquid circuit (not installed).
More informationG Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton
G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1
More informationAnnual Tune-Up Procedure
Annual Tune-Up Procedure SOLVENT SAVER RECYCLER MODELS SC (9711) AND HC (9725) 1 TABLE OF CONTENTS PAGE SPECIFICATIONS... 3 SAFETY & WARNINGS... 4-6 OVERVIEW... 7 CLEANING THE BOILER... 8-9 CHANGING THE
More informationCleaning and Sanitation Procedures Module Deli
Deli Triple Sink System (Clean, Rinse, Sanitize) A. Preparation 1) Wash your hands with anti-microbial soap before and after cleaning and whenever hands are dirty. 2) Dawn appropriate PPE s 3) Place safety
More informationDouble Skin Casing Air Handling Units
Double Skin Casing Air Handling Units Double wall with 25 mm insulation Modular design for clean process application flexibility all the requirements 2,000 40,000 CFM AUTUMN Air Handling Units incorporate
More informationModel K 520 M Part No
Model K 520 M Part No. 1.069-680.0 High Pressure Washer Operator Manual Overview... 2 Precautions... 2-4 Assembly Instructions... 4 Operating Instructions... 5 Using the Accessories... 6 Working with Detergents...
More information20-GALLON MOBILE PARTS WASHER OWNER S MANUAL
20-GALLON MOBILE PARTS WASHER OWNER S MANUAL WARNING: Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions may result in
More informationINSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH
TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system
More informationINSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X
INSTALLATION INSTRUCTIONS Cased N, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,
More informationThis appliance has been CE-marked on the basis of compliance with the Low Voltage and EMC Directives for the voltages stated on the data plate.
DOMINATORPLUS ELECTRIC RANGE APPLIANCES INSTALLATION and SERVICING INSTRUCTIONS IMPORTANT The installer must ensure that the installation of the appliance is in conformity with these instructions and National
More informationVEX250H with rotary heat exchanger and EXact control system
3003433-2014-04-11 VEX250_EXact VEX250H with rotary heat exchanger and EXact control system Unit supplied with (factory fitted): Compact filter FP Filter bag FB Trim damper and blowout zone,tb250 The following
More informationHigh Pressure Washer Operator Manual. Specifications Model HD 2700 DH/DB
Model HD 2700 DB Part No. 1.194-116 Model HD 2700 DH Part No. 1.194-117 Model HD 3000 DH Part No. 1.187-115 Model HD 3500 DH Part No. 1.810-997 Model HD 3500 DB Part No. 1.810-998 High Pressure Washer
More informationLONGONI ENGINEERING SRL
INDEX 1.1 Classification of heat exchanger and components 1.1.2 Type of heat exchanger and components 1.2 Purpose and scope of the manual 1.3 General instruction 1.4 Warning installation 1.5 Notes for
More informationINSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X
INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Modular Crescent Cuber Models KM-900MAH50 KM-900MRH50 A Superior Degree of Reliability INSTRUCTION MANUAL www.hoshizaki.com Issued: 6-25-2008 IMPORTANT Only qualified service technicians
More informationInstallation Instructions
40MBCQ Cassette Ductless System Sizes 09 to 8 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS INDOOR... 5 CLEARANCES INDOOR...
More informationINSTALLATION, OPERATION AND MAINTENANCE MANUAL IFB HEATING COILS
IOMIFB-6 INSTALLATION, OPERATION AND MAINTENANCE MANUAL IFB HEATING COILS ATTENTION: READ THIS MANUAL AND ALL LABELS ATTACHED TO THE UNIT CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE
More informationBrown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS
SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett
More informationCurb Inlet Filter INSTALLATION MANUAL. Bio Clean Environmental Services, Inc. 398 Via El Centro Oceanside, CA 92058
Curb Inlet Filter INSTALLATION MANUAL Bio Clean Environmental Services, Inc. 398 Via El Centro Oceanside, CA 92058 www.biocleanenvironmental.com p: 760.433.7640 f: 760.433.3176 INSTALLATION PROCEDURES
More informationSOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59
SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery
More informationPVA Clean Sponge. for Clean Room, Pharmaceutical. and Laboratory. Applications SUPER PVA SPONGE
PVA Clean Sponge for Clean Room, Pharmaceutical and Laboratory Applications SUPER PVA SPONGE PVA Sponge for wiping, cleaning and absorbing liquids www.pvasponge.com For both end-users and OEMs. Custom
More informationThe Role of Air Handling Units in Combating the Spread of Infectious Disease
The Role of Air Handling Units in Combating the Spread of Infectious Disease Goal To identify those areas within an air handler which poses risk to the healthcare industry and recommended four solutions
More informationTopMaster Air Handling unit. Installation instructions
Installation instructions Safety Instructions Operation of Air Handling units and accessories WARNING Installation may only be carried out by qualified personnel. Before taking the air handling unit into
More informationEnglish BT3600
www.blackanddecker.com 3 English BT3600 FIG. 1 FIG. 2 150mm BENCH GRINDER BT3600 GENERAL SAFETY RULES WARNING: Read all instructions. Failure to follow all instructions listed below may result in electric
More informationNOTICE: The information contained on the following page(s) was produced prior to May 1, On that date Reznor became part of Nortek, Inc.
NOTICE: The information contained on the following page(s) was produced prior to May 1, 2014. On that date Reznor became part of Nortek, Inc. References to any other company affiliations are no longer
More informationProcessing (cleaning, disinfection and sterilization) of instruments from Smith & Nephew Orthopaedics AG
Guide Processing (cleaning, disinfection and sterilization) of instruments from Smith & Nephew Orthopaedics AG Acceptance Cleaning, Disinfection Inspection, Packing Use T Sterilization t Storage Return
More informationIf a peak space temperature to about 28ºC is acceptable to the occupants then a naturally ventilated solution is a viable option.
Air handling units Aesthetic Not to add significantly to the existing ambient noise levels. Functional requirements If a peak space temperature to about 28ºC is acceptable to the occupants then a naturally
More informationModel HD 3501 Part No High Pressure Washer Operator Manual
0 15 25 40 25 Nozzle Identification SOAP HD3501 Manual 4/22/02 6:57 PM Page 1 Model HD 3501 Part No. 1.810-999.0 High Pressure Washer Operator Manual Overview..................................1 Precautions...............................1-2
More informationMIST MAX MODEL MM800. Important: Installation and Operation Manual
MIST MAX MODEL MM800 Installation and Operation Manual TM Important: This manual contains specific cautionary statements relative to worker safety. Read this manual thoroughly and follow as directed. It
More informationOperating instructions
ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-74673 Mulfingen Phone +49 (0) 793-0 Fax +49 (0) 793-0 info@de.ebmpapst.com www.ebmpapst.com CONTENTS. SAFETY REGULATIONS AND NOTES. Levels of hazard warnings.
More informationHygiene Product Range
INDUSTRIAL WASHING MACHINES Hygiene Product Range Your one source for hygiene equipment visit us at www.indwash.co.uk CONTENTS Sterilisers 4 Handbasins 6 Washers 11 Disinfection 16 Passage wash/disinfection
More informationInstallation Instructions
Evaporator Coil A Coil --- Cased Multipoise NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...
More informationJet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance
916503-0 GB Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 1. Main components 2. Application 3. Handling 3.1 Marking 3.2 Weight 3.3 Transport 4. Storage 1. Main components: Types ARC,
More informationAir Handling Units. T F E.
Air Handling Units Extract from BS EN ISO 15138:2007 Petroleum & natural gas industries- Offshore production installations-heating, ventilation & air-conditioning. A.12.1 Function Installations provided
More informationnew HYGIENE AND COMFORT FOR HOSPITALS AND PUBLIC BUILDINGS HYGIENIC AIR HANDLING UNITS HYGIENIC AHU N o : Range: AmberAir
new HYGIENIC AIR HANDLING UNITS WWW.SALDA.LT AHU N o : 16.11.005 Range: AmberAir HYGIENIC HYGIENE AND COMFORT FOR HOSPITALS AND PUBLIC BUILDINGS HYGIENE AND COMFORT FOR HOSPITALS AND PUBLIC BUILDINGS The
More informationBLAST-IT-ALL BUMPER BLASTER
LARRY HESS AND ASSOCIATES, INC 185 PIPER LANE / SALISBURY, NC 28147 PHONE: 1-800-535-2612 / FAX: 1-704-638-9311 WWW.BLAST-IT-ALL.COM BLAST-IT-ALL BUMPER BLASTER SUCTION BLAST CABINET NOTE: It is the responsibility
More informationInstallation Instructions
CNPHP Cased N Coils Horizontal Heating --- Cooling NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...
More informationInstructions for Operation and Maintenance of Containers
Instructions for Operation and Maintenance of Containers Container Handling 1. Containers are designed for transport on a flat loading area that is 2.5 m wide, which enables support of the load-bearing
More informationDOMINATORPLUS ELECTRIC RANGE APPLIANCES INSTALLATION and SERVICING INSTRUCTIONS
DOMINATORPLUS ELECTRIC RANGE APPLIANCES INSTALLATION and SERVICING INSTRUCTIONS IMPORTANT The installer must ensure that the installation of the appliance is in conformity with these instructions and National
More informationRead this entire manual before operation begins.
Read this entire manual before operation begins. Record below the following information which is located on the serial number data plate. Serial No. Model No. Date of Installation Contents Important Information........
More informationINSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER
INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL T Edition 0 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 88 STRATFORD, CT 0665
More informationAir Handling Unit eq and eq PLUS. Technical Data june 2010
Air Handling Unit eq and eq PLUS Technical Data june 2010 Contents Introduction... 9 Unit configuration... 12 eq Energy Solution... 13 eq Hygiene... 15 eq Top... 17 Flow chart... 19 Unit configuration...
More informationCS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A
CS 2 Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual Form No. 6120A TABLE OF CONTENTS Page Inspection... 2 Shipment of Units... 2 Handling... 2 Installation...
More informationTABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation.
Installation NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION... 2 Inspect Equipment... 2 Select
More informationLo-Carbon T-series Window & Roof Models
Lo-Carbon T-series Window & Roof Models Installation & User Instructions WIRED 456165A (9 WW) 456168A (9 RF) 456173A (12 WW) 456176A (12 RF) WIRELESS 456169A (9 WW) 456172A (9 RF) 456177A (12 WW) 456180A
More informationMARUYASU INDUSTRIES CO.,LTD.
Instruction Manual MARUYASU INDUSTRIES CO.,LTD. TUBE CORE HEAT EXCHANGER Thank you very much for your purchasing our tube core heat exchanger. Read this instruction manual carefully before using our products.
More informationUnits for suspended cei lings
. X X testregistrierung Units for suspended cei lings Type, hinged induced air grille, water connections Chilled Beams No. 09.2.432 Eurovent certification HYGIENISCH GETESTET V DI 6022 Tested to VDI 6022
More informationInstructions for the BASIC Air Handling System, Sizes General 1.1 Description of the System
Instructions for the BASIC Air Handling System, Sizes 004 055 1. General 1.1 Description of the System The BASIC System is a complete modular air handling unit. The unit consists of blocks, i.e. a number
More informationInstallation Instructions
CNPHP Cased N s Horizontal Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION...
More informationINSTALLATION INSTRUCTIONS
,1,_2008 Lennox Industries Inc, Dallas, Texas, USA INSTALLATION INSTRUCTIONS CR33 Series Coils EVAPORATOR COILS _ Technical 505,056M LL.L[ Publications 04108 Litho U.S.A. Supersedes 05/05 CR33 Series Coils...
More informationBall Float Controlled. Thermo Dynamic(TD) Trap Safety Valve Condensate Pump Flash Vessel Moisture Separators Deaerator Head Steam Injector Sight Glass
Product of Quality Best Performance Ball Float Controlled Steam Traps Auto Drain Traps Float Valve Air Vent Valves Feed Control Valve Drain Control Valve Thermo Dynamic(TD) Trap Safety Valve Condensate
More informationPortable Vacuum System Operating Manual
Reorder No. PD04.21 Portable Vacuum System Operating Manual 61300 (9.9 gal./36 ltr.) 120v-60Hz (US) 61301 (17 gal./64 ltr.) 120v-60Hz (US) 61302 (9.9 gal./36 ltr.) 230v-50Hz (UK) 61303 (17 gal./64 ltr.)
More informationHEAT EXCHANGE IN GENERAL
XXXX F28 HEAT EXCHANGE IN GENERAL Note(s) (1) In this class, the following expressions are used with the meanings indicated: heat exchange means the heating or cooling of a fluid or fluent solid by direct
More informationA. Set-Up with gravel
A. Set-Up with gravel Set-up tank 10 days before eggs arrive to condition the water and ensure all equipment is working. 1 Gravel Dust-free epoxy-coated gravel is recommended. For 20 gallon tanks use 5kg
More informationCeiling diffusers. Type DLQL
X X testregistrierung Type Horizontal one-way air discharge Horizontal two-way air discharge Horizontal four-way air discharge Horizontal duct connection For horizontal one-way to four-way air discharge,
More informationEnglish. Your Model Number is: HD1500 IMPORTANT
Your Model Number is: HD1500 IMPORTANT Attention Valued Customer: The serial number of your machine and date of purchase is necessary information to facilitate warranty claims and the ordering of replacement
More informationOPERATORS GUIDE Solvent Saver Recyclers. Technical Assistance call (800)
OPERATORS GUIDE 9711-9725 Solvent Saver Recyclers Technical Assistance call (800) 655-5649 Oct. 2003, V 1.2 BECCA INC. Operators Guide Workstations 1 TABLE OF CONTENTS Section 1 PAGE Safety.. 3 Section
More informationCRISTAL Built-in Dish Sterilizer Instruction Manual
CRISTAL Built-in Dish Sterilizer Instruction Manual Model No.: D36DSS Version Number: 01 Revision Date: September 2014 Dear user: Thank you for your purchase of CRISTAL built-in dish sterilizer! Please
More informationbreeze easytm model # F100-1W
DewStop breeze easytm model # F100-1W Installation Guide Read and Save These Instructions LISTED Questions, Problems, Missing Parts? Please Call 1-360-876-2974 or E-Mail info@dewstop.com please retain
More informationVEX280H with rotary heat exchanger and EXact control system
3003206-2014-04-15 VEX280_EXact VEX280H with rotary heat exchanger and EXact control system Unit supplied with (factory fitted): VEX280-1 VEX280-2 FP compact filter FB filter bag TB280 trim damper and
More informationEBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL
EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 700 Thimble Shoals Boulevard Newport News VA 23606-2575 Telephone (757) 873-6800 Fax (757) 873-3632 Website: www.ebacusa.com INTRODUCTION
More informationCONTENTS DESCRIPTION UNPACKING DIMENSIONS
INSTALLATION INSTRUCTIONS Ventilating Fan ModelNo.FV-08VRE CONTENTS GENERAL SAFETY INFORMATION DESCRIPTION UNPACKING SUPPLIED ACCESSORIES DIMENSIONS WIRING DIAGRAM INSTALLATION (BETWEEN JOISTS MOUNTING)
More informationTopVent Design Handbook
TopVent Design Handbook Recirculation Units and Supply Air Units for Heating and Cooling High Spaces TopVent Content TopVent DHV Recirculation unit for heating high spaces TopVent NHV Recirculation unit
More informationOPERATOR S MANUAL FOR YOUR SAFETY. 4 Gallon / Liter Part No. PB408SV
120 VOLT WET / DRY VAC 4 Gallon / 15.14 Liter Part No. PB408SV FOR YOUR SAFETY Read and understand this manual before use. Keep this manual for future reference. OPERATOR S MANUAL TABLE OF CONTENTS SECTION
More informationInstallation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers
OM010 Installation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers The operating and maintenance instructions contained within this package are for ThermaFlex gasketed
More informationHYGIENE EQUIPMENT INTRODUCTION HYGIENE
EDITION 2015/2016 INTRODUCTION HYGIENE EU directive 64/433 introduced in the food plants the obligation to produce food in a safe way. To meet the requirements regarding hygiene for staff, machinery, equipment
More information