Measurement of Reliability of Evaporator used in Vapour Compression Refrigeration System (VCRS)
|
|
- Osborn Corey Cameron
- 5 years ago
- Views:
Transcription
1 Measurement of Reliability of Evaporator used in Vapour Compression Refrigeration System (VCRS) 1 VivekDwivedi,Dr. A. K.Bajpai 2 1 Research Scholar, College of Engineering,TeerthankarMahaveer University, Moradabad. 2 Principal/Professor, Mechanical Engineering Department, Sri RammurtiSmarak, College of Engineering & Technology,Lucknow. ABSTRACT In VapourCompresion Refrigeration System (VCRS) evaporator is the component where the actual cooling takes place. It is the space from which the actual COP of refrigeration system is calculated. Generally in evaporator heat transfers in the form of latent heat where a refrigerant in liquid state is converted into vapour state by absorbing heat in the form of latent heat[2]. Evaporator is also called chiller. In this research paper the technique to measure the reliability of evaporator for fifteen years if its life span is given on the basis of Modeling and Simulation on VENSIM-PLE Software. KeyWords:-VapourCompresion Refrigeration System, evaporator, Modeling and Simulation, VENSIM-PLE 1.INTRODUCTION The evaporators used in VCRS must fulfill the following requirements (a). The temperature difference between the refrigerant and cooling substance should be very small when refrigerant absorbs heat. For this purpose the surface area of evaporative/cooling coil is kept large in basic design[3]. (b). It should have sufficient space that the liquid refrigerant completely changes into vapour form. (c). The space provided inside the evaporator should be such that the refrigerant an flow easily even for very small pressure difference between evaporator inlet and evaporator outlet[1]. The amount of het transferred by evaporator can be given by the following equation; Q= U A (t 2 - t 1 ) Where; U = Overall Heat Transfer Coefficient A = Surface area of evaporator t 2 = Temperature of the medium to be cooled t 1 = Saturation Temperature of refrigerant at evaporator pressure Some important causes which can affect the performance of evaporator are: The material of High Conductivity Non corrosive with refrigerant Eg. Evaporators made of iron or steel can be used for any type of refrigerant. Evaporators made of brass or copper can be used for any refrigerant except ammonia. Evaporators made of aluminum can be used for any refrigerant except brass and Freon. The temperature difference between refrigerant and the product to be cooled should not increase to 8 0 C. The evaporator s performance is much affected by the velocity of refrigerant flowing inside the evaporator. On increasing the velocity of the refrigerant, the pressure difference between inlet and outlet also increases which may produce adverse effect. Therefore the velocity of different refrigerant should be optimized or according to the recommended in data book[4]. Even it is seen that the wall thickness of evaporative coil does not affect much more to the performance or heat transfer rate of evaporator because the material used for its manufacturing is already of high thermal conductivity. The contact surface area of evaporative coil is another important factor which affects the heat transfer capacity or effectiveness of evaporator. In the design of evaporator the exposure of coil surface area should be more as much as possible according to its physical shape and size[3]. Volume 3, Issue 5, May 2015 Page 71
2 2.MAJOR PROBLEMS ON EVAPORATOR 1. Blockage in evaporator due to valve damage, introduction of foreign materials. It affects the cooling capacity of the evaporator. 2. Leakage of refrigerant due to holes or damage inside it. 3. Choking of evaporative coil when defrosting switch is damaged or over freezing takes place[5] OBSERVATION TABLE This Observation is based on the complaints in evaporators of hundred vapour compression refrigeration systems that are used simultaneously before fifteen years. Table 1 : Practically observed data recorded for different types of problems in evaporator No. of complaints Where λi = (Max. Yr. No. )* 100 λi λ av (C) = λi λ av (L) = λ av (B) = λi 12 Volume 3, Issue 5, May 2015 Page 72
3 In modeling the reliability of components of evaporator is considered as it decays exponentially with time. 3.SYSTEM DYNAMIC MODELING Figure 1 :System Dynamic Modeling for reliability of evaporator 3.1. PROGRAMING DETAILS (1) BOEC= EXP(-0.003*Time) (2) CIEC= EXP(-0.011*Time) (3) FINAL TIME = 15 Units: Year The final time for the simulation. (4) INITIAL TIME = 0 Units: Year The initial time for the simulation. (5) LOR= EXP( *Time) (6) ROE= BOEC*CIEC*LOR (7) SAVEPER = TIME STEP Units: Year [0,?] The frequency with which output is stored. (8) TIME STEP = 1 Units: Year [0,?] The time step for the simulation. Volume 3, Issue 5, May 2015 Page 73
4 4.GRAPHICAL OUTPUTS (a). Figure 2 : Time dependent reliability for choaking in Evaporative Coil (b). Figure 3 : Time dependent reliability for leakage of refrigerant (C). Figure 4 : Time dependent reliability for blockage of Evaporative Coil Volume 3, Issue 5, May 2015 Page 74
5 (d). Figure 5 : Time dependent reliability for Evaporator 4.1. OBSERVATION TABLE Table 2 : Reliability of different components with respect to time 5.RESULTS AND DISCUSSION The reliability of evaporator mainly depends on three parameters as choking in evaporative coil, leakage of refrigerant and blockage of evaporative coil. Their reliability degradation rate with respect to time is calculated by experimentally collected data. From the above data it is confirmed that choking of evaporative coil is important parameter that considerably affects the reliability of evaporator. During modification in the functioning of evaporator we must concentrate towards the rectification in the choking of evaporative coil than the other two parameters. From the observation table it is found that at the end of fifteenth year the reliability of choking coil falls to 84.78% regarding to its choking. The reliability of other two parameters like leakage of refrigerant and blockage of evaporative coil falls to 95.02% and 95.59% at the end of fifteenth years which do not much affect the performance of evaporator. Overall reliability of evaporator decreases from 100% to 77.02% at the end of fifteenth year for starting. This percentage is not feasible for confident running of vapor compression refrigeration system for fifteen years. Hence at this stage of design modification is necessary. Volume 3, Issue 5, May 2015 Page 75
6 6. CONCLUSION It is confirmed from the above data recorded for last fifteen years that major problems arise in evaporator due to the choking of evaporative coil. Therefore the reliability of evaporator mainly depends on the proper and healthy functioning of evaporative coil. If there is a need of increase in the reliability of evaporator, first it is important to modify the evaporative coil. REFERENCES [1]. Cullimore, B; Optimization, Data Correlation, and Parametric Analysis Features in SINDA/FLUINT; SAE [2]. Cullimore, B; Reliability Engineering and Robust Design: New Methods for Thermal/Fluid Engineering; C&R White Paper, March [3]. Optimisation of Industrial Refrigeration Plants /ESL-IE pdf?sequence=1 [4]. [Pham, 2005] Pham, Q. T. (2005). Modelling heat and mass transfer in frozen foods: a review. Int. J. Refrigeration, 29: [5]. [Powell, 2002] Powell, P. (2002). In search of energy efficiency. Air Conditioning, Heating and Refrigeration News, 217(10):17. Volume 3, Issue 5, May 2015 Page 76
Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System
Enhancement of COP by Using Spiral and Microchannel instead of conventional of VCR System 1 P.G. Lohote, 2 Dr.K.P. Kolhe. 1 P.G. Student, 2 Professor. 1,2 Department of Mechanical Engineering, JSPM s,
More informationPerformance Assessment of Water Cooled Condenser Refrigeration System
Energy and Power 2017, 7(3): 70-74 DOI: 10.5923/j.ep.20170703.03 Performance Assessment of Water Cooled Condenser Refrigeration System Sheetal Narayan Shetty *, Prashanth Kamath Department of Mechanical
More informationTo Improve Cop of Domestic Refrigerator with the Help of Water Cooling Condenser
Vol. 4, Issue 3, March To Improve Cop of Domestic Refrigerator with the Help of Water Cooling Condenser Sukani Sunny 1, Savaj Jayesh 2, Cop Improver Group 3 Lecture of Mechanical Engineering Department,
More informationPerformance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers
e-issn 2455 1392 Volume 2 Issue 5, May 2016 pp. 108-116 Scientific Journal Impact Factor : 3.468 http://www.ijcter.com Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl
More informationNumerical Study on Improvement of COP of Vapour Compression Refrigeration System
Numerical Study on Improvement of COP of Vapour Compression Refrigeration System Sanath Kumar K H 1, Arun Kumara K S 2, Nissar Ahmed 3 Assistant Professor, Department of Mechanical Engineering, VVIT, Bangalore,
More informationCHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM
111 CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 7.1 INTRODUCTION Energy is the primary component to run any system in the world. According to
More informationPerformance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS
Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS Lalit Narayan, Abhishek Arya 2,2 M. Tech. Scholar, Associate Professor,,2 Scope College of Engineering, Bhopal, India Abstract: The
More informationII. OBJECTIVE OF RESEARCH
Enhancement of Coefficient of Performance of Vapor Compression Refrigeration System Using Diffuser at let of Condenser Mr. Nurul Seraj 1, Dr. S. C. Roy 2 1 Student, 2 Head of Department, Department of
More informationInternational Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN
ISSN 2229-5518 865 Abstract global warming and as a result, ambient temperature is rising significantly. Refrigeration and air- cooling systems are becoming necessary in almost all parts of India, even
More informationNew standard in compressed air treatment, providing Energy Savings up to 99%
PCM Series Specification for APAC Model Flow Capacity (Nm 3 /min) Pressure Dew Point ( ) Power Consumption (kw) Power Supply (V/Ph/Hz) Inlet/Outlet Connections Weight (kg) Dimensions (H x W x D mm) Refrigerants
More informationCFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology
IJIRST International Journal for Innovative Research in Science & Technology Volume 1 Issue 11 April 2015 ISSN (online): 2349-6010 CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology
More informationEXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS
International Journal of Scientific & Engineering Research Volume 3, Issue 7, July-2012 1 EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS Rahul ukey, Sharad chaudhary Abstract Electricity
More informationExperimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures
Experimental Study on Performance Parameters for Refrigerants, R41a and R44a at Various Air Outlet Temperatures P. Nagaraju P. G. Student Sanketika Institute of Technology and Management Ch. Kiran Kumar
More informationSECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
More informationPerformance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant
Performance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant Bukke Bhagyalathamma 1, Dr.Smt.G.Prasanthi 2 Department 1,2,Department of Mechanical Engineering,PG Scholor
More informationSimscape Refrigerant Loop Product
Aims The product is an easy to use simscape simulator with simple GUI or HMI allowing to define: - the different configurations of the physical system - the different operating modes: start, stop, load
More informationPerformance investigation of Air-conditioning system using ejector as expansion device
International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Performance
More informationAir Conditioning System with Modified Condenser Ducts and Evaporative Cooling
Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling Dr. Akash Langde 1, Zeeshan Jamal 2, Shahrukh Jamal 3, Mohammad Shumoil Ansari 4 1Professor, Department of Mechanical Engineering,
More informationCHAPTER 1 INTRODUCTION
1 CHAPTER 1 INTRODUCTION 1.1 Background The science which deals with creating a controlled climate in indoor space is called air conditioning. Earlier days the air-conditioning was treated as a luxury,
More informationAn Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters
An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters #1 Harshad D Kopurwar, #2 Pravin T Nitnaware, #3 Tapobrata Dey 1 harshvardhan1590@gmail.com #1 Mechanical
More information[Jhansi, 5(10): October 2018] ISSN DOI /zenodo Impact Factor
GLOBAL JOURNAL OF ENGINEERING SCIENCE AND RESEARCHES PERFORMANCE ANALYSIS OF VCR SYSTEM WITH TWISTED TAPE CONDENSER BY USING R134a REFRIGERANT Chidige Jhansi* 1 & Dr.Smt.G.Prasanthi 2 *1 PG Research Scholar
More informationGSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN
GSJ: VOLUME 6, ISSUE 6, JUNE 2018 189 GSJ: Volume 6, Issue 6, June 2018, Online: ISSN 2320-9186 ANALYSIS OF A VAPOUR ABSORPTION REFRIGERATION CYCLE POWERED BY A SOLAR SYSTEM Taiwo O. Oni Department of
More informationAnalysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant
Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET
More informationGlobal Journal of Engineering Science and Research Management
EXPERIMENTAL AND THEORETICAL STUDY OF MINIATURE VAPOR COMPRESSION CYCLE USING MICROCHANNEL CONDENSER Issam M. Ali Aljubury*, Ahmed Q. Mohammed, Marwa S. Neama * Mechanical Eng. Dept. College of Engineering,
More informationPerformance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical
More informationMath. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.
HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +
More informationLECTURE-18 Vapour Absorption Refrigeration System
Lecturer: -Dr. Esam Mejbil Abid Subject: Air Conditioning and Refrigeration Year: Fourth B.Sc. Babylon University College of Engineering Department of Mechanical Engineering LECTURE-18 Vapour Absorption
More informationPerformance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant
International Journal of Scientific and Research Publications, Volume 4, Issue 7, July 2014 1 Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170
More informationCapillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning
Journal of Physics: Conference Series PAPER OPEN ACCESS Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning To cite this article: Putu Wijaya Sunu et
More informationMAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR
MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR Santhosh Kumar Student(M.Tech), Mechanical Dept Gokul group of institutions Visakhapatnam, India M Karteek Naidu ASST PROFF, Mechanical
More informationPresentation on HVAC: Heating Ventilation Air Conditioning
Presentation on HVAC: Heating Ventilation Air Conditioning CHITKARA UNIVERSITY CHITKARA SCHOOL OF MECHANICAL ENGINEERING ;HARVINDER SINGH HVAC Heating, Ventilation and Air Conditioning Provides comfort
More informationISSN Vol.08,Issue.21, November-2016, Pages:
ISSN 2348 2370 Vol.08,Issue.21, November-2016, Pages:4164-4170 www.ijatir.org Thermal Analysis of Vapour Compression Cycle for Different Refrigerants ALI MOHAMMED ABDOULHA MASSOUD 1, DR. MOHAMMAD TARIQ
More informationCHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way
1 CHAPTER I INTRODUCTION In the modern life, electronic equipments have made their way in to practically every part, which is from electronic gadgets to high power computers. Electronic components have
More informationPressure Enthalpy Charts
Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance
More informationPERFORMANCE ENHANCEMENT OF AIR CONDITIONER *
PERFORMANCE ENHANCEMENT OF AIR CONDITIONER * K. B. Vijay, E. Naresh Kumar, T.Parameshwaran Pillai 1 Dept. of Mechanical Engineering. Anna University Chennai (BIT Campus), Tiruchirappalli 24 *corresponding
More informationPerformance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System
Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System Pawan Kumar Mishra #1, Amol Tripathi *2 # RIT Department of Mechanical Engineering Department,
More informationInternational Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015
International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015 ISSN: 2289-4152 Performance Evaluation of Vapour Compression Refrigeration System Using Double Effect Condensing
More informationPerformance of an Improved Household Refrigerator/Freezer
Performance of an Improved Household Refrigerator/Freezer D. O. Ariyo Department of Mechanical Engineering, School of Engineering, Federal Polytechnic, Offa, Nigeria Y. L. Shuaib-Babata Department of Mechanical
More informationREVIEW OF DESIGN OF SINGLE EFFECT SOLAR POWERED VAPOUR ABSORPTION AIR CONDITIONING SYSTEM
REVIEW OF DESIGN OF SINGLE EFFECT SOLAR POWERED VAPOUR ABSORPTION AIR CONDITIONING SYSTEM Mr. S. S. Mali 1, Prof.M.M.Wagh3 Prof. N. N. Shinde 2 1 M. Tech Scholar, Department Of Energy Technology, Shivaji
More informationOpen Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations
43rd ANZSES Conference Solar 24, Denedin (NZ), 28.11.-3.11.5, CD Abstract Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations M., W. Saman, K. Vajen* Sustainable
More informationComparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area
Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area MMS DEZFOULI, SOHIF MAT, K.SOPIAN Solar Energy Research Institute (SERI, Universiti
More informationPaper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration
Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration 11.1 Introduction Preservation of foods is a vital processing step in food processing. There are
More informationEnhancement of COP in Vapour Compression Refrigeration System
Enhancement of COP in Vapour Compression Refrigeration System M. Krishna Prasanna #1 M.E student, Heat Transfer studies in Energy Systems Department of Mechanical Engg., Andhra University Visakhapatnam-530003,
More informationExperimental Investigation of a Hybrid Evacuated Tube Solar Collector
International Conference on Mechanical, Industrial and Materials Engineering 2015 (ICMIME2015) 11-13 December, 2015, RUET, Rajshahi, Bangladesh Paper ID: ET-46 Experimental Investigation of a Hybrid Evacuated
More informationEXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM
EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM 1 RONANKI SURESH, 2 Dr. K. KALYANI RADHA 1 M.Tech, Mechanical Engineering, JNTUA College of Engineering
More informationFS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points
Name: Start time: End time: FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points 1. What are the units of the following quantities? (10 points) a. Enthalpy of a refrigerant b. Dryness fraction of
More informationPerformance Enhancement of Mini Refrigerator with Phase Change Materials
Performance Enhancement of Mini Refrigerator with Phase Change Materials Souptik Acharya 1, Manu Jose 2 and Risikesh Choudhury 3 Souptik Achraya,student at St. Martin s Engineering College Manu Jose T,
More informationPerformance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a
International Journal of Research in Engineering and Science (IJRES) ISSN (Online): 2320-9364, ISSN (Print): 2320-9356 Volume 4 Issue 6 ǁ June. 2016 ǁ PP. 52-57 Performance analysis of a vapour compression
More informationExperimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant
Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant Satish parmar 1, Ravindra Randa 2 1M.TECH. Scholar, Department Of Mechanical
More informationWORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM
WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM Sachin Kumar 1, Vicky Ranga 2 1Assistant Professor, Department of Mechanical Engineering, Jagan Nath University Jhajjar, Haryana, India. 2Scholar.
More informationEXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM
EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM Prof. S.V.Rao 1, Hitesh Sharma 2, Pankaj Kumar Gound 3, Tukaram Walgude 4, Shekhar Gavas 5 1 Prof.
More informationExperimental Study on Performance of Double pipe Length on Instantaneous Air Source Heat Pump Water Heater. Yin Shaoyou 1, a
International Symposium on Energy Science and Chemical Engineering (ISESCE 2015) Experimental Study on Performance of Double pipe Length on Instantaneous Air Source Heat Pump Water Heater Yin Shaoyou 1,
More informationDesign of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible
More informationFABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE
FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE PRESENTED BY J.SARAVANA PERUMAL 1 Saravananjsp005@gmail.com D.SATHEESH 2 Satheeshd123@gmail.com Contact no: 9789080381 DEPARTMENT
More informationLesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems
Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this lecture are to: 1. Importance of complete vapour compression refrigeration
More informationPerformance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Shoeb Inamdar 1, H. S. Farkade 2 P.G. Student, Department of Mechanical Engineering, Govt. College of Engg. Amravati. Maharashtra,
More informationVAPOR COMPRESSION HEAT PUMP USING LOW TEMPERATURE GEOTHERMAL WATER: A CASE STUDY OF NORTHERN THAILAND
VAPOR COMPRESSION HEAT PUMP USING LOW TEMPERATURE GEOTHERMAL WATER: A CASE STUDY OF NORTHERN THAILAND Fongsaward S. Singharajwarapan 1 and Nattaporn Chaiyat 2 1 Groundwater Technology Service Center, Chiang
More informationU.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India
DESIGN OF HYBRID AIR COOLER USING VAPOUR COMPRESSION REFRIGERATION SYSTEM Vimalkirti Shende 1, Sushil Borkar 2, Touseef Iqbal Qureshi 3 Asst. Prof. Nikhil Bhende 1 1,2,3 U.G. Student, Department of Mechanical
More informationA Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger
A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger Chetan Papade Department of Mechanical Engineering N.K.Orchid college of Engg.& Tech., Solapur, Maharashtra,
More informationIJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December
Performance Analysis of Eco-Friendly HC Mixture (R290/R600a) Refrigerant as an Alternative to in a Vapour Compression Refrigeration System for Sub-cooling using Heat Exchanger at Condenser Outlet and Diffuser
More informationHVAC Fundamentals & Refrigeration Cycle
HVAC Fundamentals & Refrigeration Cycle Change of State of Water & the Refrigeration Cycle Change of State Water The Basic Refrigeration Cycle Types of DX Systems The Chilled water System The Cooling Tower
More informationENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou
Condensers ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM A. Hadawey, Y. T. Ge, S. A. Tassou 4 7 8 5 3 2 6 1 Produced by: The Centre for Energy and Built Environment
More informationREPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER
REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER Alka Bani Agrawal* and A.C.Tiwari 1 Department of Mechanical Engineering, R.G.T.U., Bhopal M. P. (INDIA) *E-mail : alk_agr@yahoo.co.in
More information"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"
"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger" 1 Prof.Gaffar G.Momin, 2 Sagar B. Tupe, 2 Swapnil A. Parate 2 Omkar G. Yewale 2 Aakash P.
More informationEVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22
EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 Ameya P. Shrivastava 1, Choudhari Chandrakishor S. 2 1,2 Mechanical Department, AISSMS College of Engineering, Pune 411001, (India) ABSTRACT HCFC
More informationPerformance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System
Performance Evaluation of R29 as Substitution to & Mixture of Them in Vapour Compression System Pawan Kumar Mishra #1, Amol Tripathi *2 #RIT Department of Mechanical Engineering Department, RGPV,Bhopal
More informationPERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS
Int. J. Chem. Sci.: 14(S2), 2016, 665-674 ISSN 0972-768X www.sadgurupublications.com PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS J. THAVAMANI *, MARRIPUDAGALA KOMALI, SHAIK
More informationSubscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid
Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance
More informationCFD and Thermal Analysis of FIN Tube Evaporator
CFD and Thermal Analysis of FIN Tube Evaporator Kasireddy Tejashwi Ellenki College of Engineering and Technology, Patelguda(V), Hyderabad, Telangana, India. ABSTRACT: An evaporator is used in an air-conditioning
More informationFABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT
FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT Sivakumar.N a*, Agathiyan.V, Dhanush.S, Gokulnath.V, Jagadhesan.R b, c, d, e UG Scholar, Department of Mechanical Engineering, Gnanamani College
More informationInstitute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING
Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad- 500 043 B.Tech (III II SEM) MECHANICAL ENGINEERING REFRIGERATION AND AIR CONDITIONING Prepared by, Dr. CH V K N S N Moorthy, Professor
More informationComparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature
International Journal Of Computational Engineering Research (ijceronlinecom) Vol 3 Issue 3 Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature
More informationEXPERIMENTAL INVESTIGATION OF VAPOUR ABSORPTION SYSTEM
EXPERIMENTAL INVESTIGATION OF VAPOUR ABSORPTION SYSTEM AUTHOR 1.ME Student Mech Engg Dept,Godavari COE, Jalgaon,Maharashtra, India 2.Asso. Prof. & Head, Mech Engg Dept,Godavari COE, Jalgaon,Maharashtra,
More informationijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12
EXPERIMENTAL ANALYSIS OF THE EFFECT OF FIN GEOMETRY ON HEAT TRANSFER RATE THROUGH THE REFRIGERATOR CONDENSER ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12
More informationExperimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators
IJIRST International Journal for Innovative Research in Science & Technology Volume 3 Issue 11 April 2017 ISSN (online): 2349-6010 Experimental Investigations of Different Types of Condensers on the Performance
More informationEXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)
EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a) Abstract- With the recent government regulations, of banning the ozone depleting substances and Kyoto protocol
More informationSystem-CoolAC. Bharatividyapeeth College of Engineering, Deekshant Bharti Scholar, New Delhi, India
A Novel Design of Low Cost Domestic Cooling System-CoolAC Abhishek Gandhar Associate Prof., abhishek.gandhar@gmail.com Deekshant Bharti bravo9421@gmail.com Aditya Jain adityajn710@gmailcom Shiv Wadhwa
More informationRefrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 26 Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants Jit Guan
More informationME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3
ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes
More informationFabrication of Hot and Cold Water Dispenser
e-issn 2455 1392 Volume 2 Issue 7, July 2016 pp. 1 6 Scientific Journal Impact Factor : 3.468 http://www.ijcter.com Fabrication of Hot and Cold Water Dispenser Sana Shaikh 1, Priyanka Rawate 2 1,2 Bharati
More informationModelling the Performance of a Diffusion Absorption Refrigeration System
Modelling the Performance of a Diffusion Absorption Refrigeration System Noman Yousuf 1, Etienne Biteau 2, Timothy Anderson 1, Michael Gschwendtner 1 and Roy Nates 1 1 School of Engineering, Auckland University
More informationAIM: TO STUDY THE PERFORMANCE OF THE DOMESTIC REFRIGERATION RIG.
AIM: TO STUDY THE PERFORMANCE OF THE DOMESTIC REFRIGERATION RIG. Page1 CONTENT: 1. Product Description 2. Product Specifications 3. Operating Procedure 4. Observation Table 5. Calculations 6. Result Page2
More informationASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER
University of Maiduguri Faculty of Engineering Seminar Series Volume 6, december 5 ASSESSMENT OF REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R34A REFRIGERANT IN LARGE CAPACITY FREEZER S. Shodiya*, M.B. Oumarou
More informationPerformance Study of Triple Concentric Pipe Heat Exchanger
Performance Study of Triple Concentric Pipe Heat Exchanger #1 Pravin M. Linge, #2 A. B. Korane, #3 V. N. Kapatkar #123 Mechanical Engineering Department, Sinhgad College of Engineering, SPPU, Pune, India
More informationNUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A
ISSN: 2250-0138 (Online) NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A RANENDRA ROY a1, MADHU SRUTHI EMANI b AND BIJAN KUMAR MANDAL c abc Department
More informationExperimental Investigation on Domestic Refrigerator by Shell and Tube Heat Exchanger after the Condenser Using Sub Colling of Refregaring Fluid
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 12, Issue 2 Ver. V (Mar - Apr. 2015), PP 63-67 www.iosrjournals.org Experimental Investigation on
More informationAnalysis of Coefficient of Performance & Heat Transfer Coefficient on Sterling Cycle Refrigeration system.
RESEARCH ARTICLE OPEN ACCESS Analysis of Coefficient of Performance & Heat Transfer Coefficient on Sterling Cycle Refrigeration system. * Narendra.N.Wadaskar 1, Dr S.K.Choudhary 2, Dr R.D.Askhedkar 3 Ph.D.
More informationRole of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview
International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com
More informationDesign Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System
Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,
More informationOpen and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator
18 R. Saidur et al./journal of Energy & Environment, Vol. 6, May 2007 Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator R. Saidur, M. A. Sattar, M.
More informationThermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System
Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System A D Parekh, and P R Tailor Abstract Because of damaging effect of CFC refrigerants on stratospheric
More informationSTUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER
, Volume 6, Number 4, p.168-172, 2005 STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER Zhaohui Qi School of Energy Science and Engineering, Centralsouth University, Changsha,
More informationAnalysis of Vapour Compression Refrigeration System with Refrigerants R134a, R143a, R152a, R290 and R32
www.ijird.com June, 201 Vol Issue 6 ISSN 2278 0211 (Online) Analysis of Vapour Compression Refrigeration System with Refrigerants,,, and Ramesh P. Sah Assistant Professor, Department of Mechanical Engineering
More informationdeveloped, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos
Evaluation of A Plate Desiccant Outdoor Air-conditioning System Utilizing Cogenerated Hot Water Using A Numerical Model T. Baba 1, B. Park 1 1, *1, and T. Nagai 1 Department of Architecture, Tokyo University
More informationNumerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger
International Journal of ChemTech Research CODEN( USA) IJCRGG ISSN 0974-4290 Vol.5, No.2, pp 925-934, April-June 2013 ICGSEE-2013[14th 16th March 2013] International Conference on Global Scenario in Environment
More informationIJARI. 1. Introduction: Heat Pipes. Volume 3, Issue 3 (2015) ISSN International Journal of Advance Research and Innovation.
Thermodynamic Analysis of Heat Pipe Using Ammonia, Water and Ethanol with a View to Being Used in Refrigeration Ankit Dwivedi, R. S. Mishra Department of Mechanical Engineering, Delhi Technological University,
More information4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)
4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao
More informationRefrigerator and Heat Pump Objectives
10 CHAPTER Refrigeration Cycles 10-1 Refrigerator and Heat Pump Objectives The objective of a refrigerator is to remove heat (Q L ) from the cold medium; the objective of a heat pump is to supply heat
More informationRecent Advances in Energy, Environment and Economic Development
Experimental Investigation of Solar Hybrid Desiccant Cooling System in Hot and Humid Weather of Malaysia MM SALEHI DEZFOULI, Z HASHIM, MH RUSLAN, B BAKHTYAR, K SOPIAN, A ZAHARIM, S MAT, A RACHMAN, Solar
More informationOptimum Length of a Condenser for Domestic Vapor Compression refrigeration System
Optimum Length of a Condenser for Domestic Vapor Compression refrigeration System T. Mahaboob Basha 1, H.Ranganna 2,G. Maruthi Prasad Yadav 3 1.PG Student, Mechanical Engineering Dept, St Johns College
More information