Munters Heat Exchangers
|
|
- Piers Fowler
- 5 years ago
- Views:
Transcription
1 Munters Heat Exchangers Brad Perdew Applications Engineer 8/27/12 DOAS Configurations Cheryl Hughes Regional Sales Manager October 11, 2016
2 Munters DOAS Configurations Presentation Purpose of Dedicated Outside Air Systems Review Building Loads Talking Dew Point is Critical How DOAS is Applied Munters Core Components Munters DOAS Configurations Munters Cost to Operate Spreadsheet
3 Purpose of DOAS ASHRAE recommends decoupling sensible and latent loads ASHRAE recommends lower delivered dew points Lower than the original Neutral Air Unit Lower than standard packaged DX or chilled water can deliver Outside air is good, but consumes a lot of energy to treat 90.1 wants to reduce energy LEED makes you prove you have reduced energy
4 Sensible Loads Have Reduced Less Cooling Required, Less Reheat Available = Reduced Lighting Load = Reduced Solar Load = Improved Envelope
5 Outdoor Air People Infiltration Operations No Reduction in Moisture Load Requires Active Dehumidification
6 Typical Buildings Design Dew Points Building Space Served Dew Point Control Meeting Space Single F Loose Grocery Store Single F Medium Pharmaceuticals Single F Tight Hotel/Condo Multiple F Loose Office Multiple F Loose Classrooms Multiple F Loose Healthcare Depends F Depends
7 Supply Air at the Correct Dew Point SPACE DEW POINT VS. OUTDOOR AIR CFM DELIVERED PER PERSON SPACE DEW POINT O/A CFM DELIVERED PER PERSON 40 DP 45 DP 50 DP 55 DP 60 DP Chart accounts for internal latent load of occupants at 200 Btu/hr/person
8 Multiple DOAS Options Different DOAS technologies Different system combos and methods of laying out DOAS Standard or custom solutions for every application EVAPORATIVE COOLING SENSIBLE ENERGY RECOVERY EVAPORATIVE COOLING & SENSIBLE ENERGY RECOVERY DEHUMIDIFICATION & TOTAL ENERGY RECOVERY
9 Munters Products Core Components Focus on Humidity Control Over-Cool & Reheat Wringer Cycle Cooling Coil Surrounded by Single Heat Exchanger Active Desiccant Reactivated by external source of heat Reactivated using site recovered energy Focus on Energy Recovery Wheels Enthalpy or Sensible Heat pipes Plates Counter-flow or Crossflow EPX Polymer Tubes
10 Munters DOAS Products Without Exhaust Air Energy Recovery Cool-Reheat Wringer DryCool / HCU DDS (Config 1,2 & 5) HCD ICA With Exhaust Air Energy Recovery Sensible Heat Recovery Total Heat Recovery Sensible Wringer Plus Total Wringer Plus DryCool ERV DDS (Config 3 & 4)
11 Old Version of Neutral air to space 75 F at 55 F dewpoint = 50% rh 55 F 75 F DX Cooling Coil Hot Gas Reheat Compressors Supply Fan OA S/A
12 Now DOAS Should Deliver Over Dried Air to Space 75 F at 45 F dewpoint = 35% rh 45 F 75 F DX Cooling Coil Hot Gas Reheat Compressors Supply Fan OA S/A
13 Cool-Reheat (Brute Force) Cool air to desired leaving dew point and then reheat it to Space Neutral temperature Reheat must not be a "new" energy source per 90.1 Packaged DX unit (with Hot Gas Reheat) Highly competitive, Munters rarely sells Outside Air SA Cool Reheat
14 Over-Cool & Reheat (Common Selection) 60 ton CU 47.5F dp
15 Wringer Introduced by Des Champs in 1980 as a patented process surrounding a dehumidification coil with a single energy recovery device First pass across energy recovery device pre-cools humid air before coil... Reducing refrigeration requirements Second pass across energy recovery device reheats leaving air, reducing or eliminating the need for supplemental reheat Achievable dew point limited by coil temperature Sensible Heat Exchanger Outside Air SA Cool Reheat
16 Wringer 50 ton CU 46.4F dp
17 Exhaust Air Energy Recovery Pre-conditions OA with energy recovery device before cooling to desired dew point and then reheat it to space neutral temperature EA Return/Exhaust Air Reheat Outside Air SA Energy Recovery Device CW Coil DX (AC/WC/WSHP)
18 Special WARNING About Energy Recovery System Performance! TAG MODEL NUMBER AIR CAPACITY RETURN AIR TEMP CFM SUMMER WINTER SUPPLY AIR FAN EXHAUST AIR FAN SUPPLY EXHAUST (db/rh, F) (db/rh, F) ESP TSP HP ESP TSP HP RTU-1 PVR-12 11,600 11,600 75/50% 72/ RTU-2 PVR-6 6,100 6,100 75/50% 72/ RTU-3 PVR-4 4,450 4,450 75/50% 72/ SUPPLY AIR, SUMMER SUPPLY AIR, WINTER ROTARY HXR DX COIL HEAT EXCHANGER Ind. Gas Supply E.A.T. L.A.T. E.A.T L.A.T. TOTAL E.A.T L.A.T. Heat MBH Air (db/w b, F) (db/w b, F) (db/w b, F) (db/w b, F) MBH (db/w b, F) (db, F) (Output) (db, F) Accessories 90/ / / / / / / / / / / / / / / Critical Relationship
19 Exhaust Air Energy Recovery 50 ton CU 46.5F dp
20 Wringer Plus Adds exhaust air energy recovery, sensible or total, to a Wringer Enthalpy Wheel Heat Pipe, Plate or EPX Sensible Wheel Heat Pipe or Plate EA Return/Exhaust Air Outside Air SA Cool Reheat
21 Wringer Plus 30 ton CU 46.2F dp
22 DryCool Hybrid Cooling plus Active Desiccant DH Outside air first passes the pre-cool coil to < 60 F saturated The pre-cooled air then passes thru the desiccant wheel to continue drying the air to ~45 Fdp, the dehumidification process simultaneously raises the dry bulb temperature to ~75 F Combining pre-cooling with active desiccant dehumidification reduces refrigeration requirements by ~40% Outside air for reactivation is heated by a condenser coil, the rest of the condenser heat is rejected to atmosphere EA EA Outside Air Outside Air SA Cool Desiccant DH Wheel
23 DryCool Standard / HCU 40 tons precooling 43.6 F dp
24 no. 24
25 DryCool Chilled Water One 10 ton DX ckt 45.3 F dp
26 DryCool ERV Adds exhaust air energy recovery to DryCool unit Suitable for indoor installations Condenser Coil B Return/ Exhaust Air React Condenser Coil A Outside Air Outside Air SA Energy Recovery Wheel Cool Desiccant DH Wheel
27 DryCool ERV 26 ton CU 43.7 F dp
28 Enthalpy Wheel + Desiccant
29 Cost to Operate Comparison
30 Munters DOAS Presentation Recap Dedicated Outside Air Systems should be considered for all occupied spaces to provide adequate ventilation and meet codes Properly conditioning outside air takes a lot of energy, it makes sense to consider all ways to reduce operating costs Sizing and operating DOAS to maintain proper humidity control is crucial to occupant comfort and integrity of the building envelope Munters experience in humidity control plus Des Champs experience in energy recovery provide customers with a wide range of product options and expertise Each Munters system design has advantages and limitations to consider and can be compared side by side to aid in the decision making process
31 Questions
HCU Systems for Industrial Applications. Rob Smith National Accounts Manager March 7, 2011
HCU Systems for Industrial Applications Rob Smith National Accounts Manager Origins of the HCU The Humidity Control Unit (HCU) Hybrid Desiccant DX System Humidity Control Unit - DryCool HCU Introduced
More informationDedicated Outdoor Air Systems: AHRI 920, ISMRE & ASHRAE 90.1
Dedicated Outdoor Air Systems: AHRI 920, ISMRE & ASHRAE 90.1 1 Peter Teige, Application Engineering Manager, AHRI Member Technical Training, October 12, 2016 AHRI 920: Establishes Efficiency Metric for
More informationDesigning Energy Efficient Outdoor Air Systems
Designing Energy Efficient Outdoor Air Systems Joseph Thorndal Applied Products Sales Manager Greenheck, Schofield, Wisconsin 1 Joseph Thorndal BS Industrial Engineering North Dakota State University Work
More informationSection 4 of 6 DOAS Core Technologies
Section 4 of 6 DOAS Core Technologies Desiccant dehumidification Air-to-air energy recovery Evaporative cooling 1 Desiccant dehumidification Industrial Desiccant Dehumidifier Hybrid DX + Desiccant Dehumidifier
More informationDEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks
DEHUMIDIFICATION: Ice Arena Application & Product Guide Design, construct and operate to control indoor humidity in ice rinks Munters is the world leader in dehumidification Munters is the largest manufacturer
More informationStandards and Guidelines. Presented by: Aric Murray December 12, 2014
TDSHS Ventilation Standards and Guidelines Presented by: Aric Murray December 12, 2014 Agenda 1. What are the TDSHS ventilation 1. What are the TDSHS ventilation requirements? 2. Pressure relationships.
More informationTo Keep Docs Cool, Dry and Happy
To Keep Docs Cool, Dry and Happy David N. Schurk DES., CEM., LEED-AP., CDSM., SFP., CWEP. Director of Healthcare Accounts for Heat Transfer Solutions in Houston, TX. Learning Objectives 1. Understand the
More information100% Outdoor Air Dehumidification Methods
Technical Bulletin 16 100% Outdoor Air ehumidification Methods I NTROUCTION As consulting engineers and end users implement the ASHRAE 6 ventilation code, they are faced with selecting an appropriate method
More informationNON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING
NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING Danny Hall, National Sales Manager, Desert Aire Corp., Milwaukee, WI USA Traditionally, a heat pump has relied on a reversing valve system
More informationAir Conditioning for and-humid Climates:
Air Conditioning for Hot-and and-humid Climates: Commercial Technologies ACEEE Market Transformation Conference Emerging Technologies March 21, 2007 Hugh I Henderson, Jr., P.E. CDH Energy Corp. Cazenovia,
More informationIntroduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN
Introduction to HVAC Agenda Psychrometrics Human Comfort Heat Transfer Refrigeration Cycle HVAC Terminology HVAC Systems Introduction to HVAC Psychrometrics 2000 TRG-TRC002-EN Properties of Air Dry-bulb
More informationRT-OA TM Rooftop Outdoor-Air (DOAS)
RT-OA TM Rooftop Outdoor-Air (DOAS) A/C s & HEAT PUMPS Dedicated Outside-Air System (DOAS) Solutions Office Buildings, Schools, Hospitals, Restaurants, Gyms & Fitness Centers, Hotels, Retail Stores...!
More informationEnergy Recovery with Cooling and Heating
Energy Recovery with Cooling and Heating VersiVent - Model VER Commercial Institutional 2,000-10,000 cfm 3.0 in. wg external static pressure Configurable September 2008 Page The VersiVent Header Model
More informationDehumidification: Energy Efficiency Comparisons
Fourth Annual Energy Management Workshop Cocoa, Florida February 10-11, 2003 Dehumidification: Energy Efficiency Comparisons Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting,
More informationASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes
ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes In Humid Climates BY DAVID A. JOHN, P.E., MEMBER ASHRAE; DREW ELSBERRY, MEMBER ASHRAE Designing g a building s HVAC system requires designers
More informationThe Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc.
The Basics - B Practical Psychrometrics Jerry Cohen President Jacco & Assoc. Who is Jacco Established 1968 Hudson, Ohio Columbus, Ohio Toledo, Ohio Focused on the Engineered Environment Systems Knowledgeable
More informationHVAC 101. H V A C S y s t e m s
H V A C 1 0 1 S y s t e m s Introduction & Overview Should you care? Mechanical System Types Components & operation Popular Application Key Issues and Design Considerations System Comparisons First Cost
More informationDehumidifying with Dedicated Outdoor Air
Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,
More informationAHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency
Application Note 24 AHRI 920 Performance Rating and Comparisons I NTRODUCTION In 2015, the Air-Conditioning, Heating, and Refrigeration Institute (AHRI) introduced a performance rating for dedicated outside
More informationRT-OA TM Rooftop Outdoor-Air (DOAS)
RT-OA TM Rooftop Outdoor-Air (DOAS) A/C s & HEAT PUMPS (DX - Air Source Data) Dedicated Outside-Air System (DOAS) Solutions Office Buildings, Schools, Hospitals, Restaurants, Gyms & Fitness Centers, Hotels,
More informationDES CHAMPS PRODUCTS. Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling
DES CHAMPS PRODUCTS Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling DES CHAMPS PRODUCTS Packaged Heat Recovery Systems Micro-Z
More informationDesign Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationD-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency
Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)
More informationTrane CDQ Desiccant Dehumidification
Engineering Bulletin Trane CDQ Desiccant Dehumidification September 2004 CLCH-PRB020-EN Preface This engineering bulletin presents the Trane CDQ desiccant dehumidification system. It explains the features
More informationDADANCO Technical Paper
DADANCO Technical Paper 260 North Elm Street Westfield, MA 01085 Phone: (413) 564-5657 Fax: (413) 568-2969 March 2013 CLASSROOM SOLUTION USING ACTIVE CHILLED BEAMS (Note: This technical paper assumes the
More informationSR SERIES WATER SOURCE HEAT PUMP SYSTEM SELECTION AND OPTIMIZATION GUIDE
SR SERIES WATER SOURCE HEAT PUMP SYSTEM SELECTION AND OPTIMIZATION GUIDE Fresh Access Pro http://freshaccesspro.com/erep/ This guide is intended for use by qualified professionals to assist in properly
More informationPRODUCT SERIES. VPR Series VPRX Series VPRE Series VPRP Series VPRC Series
PRODUCT SERIES VPR Series VPRX Series VPRE Series VPRP Series VPRC Series Valent Air Management Products Valent Air Management Systems designs and manufactures reliable, high-outdoor-air ventilators. Our
More information7. MECHANICAL SYSTEM DESIGN
7. MECHANICAL SYSTEM DESIGN The second primary topic of this thesis is to investigate the application of a dedicated outdoor air system (DOAS) to the SLCC. The stated goals for this thesis of improved
More informationEnergy Recovery with Cooling and Heating Model ERCH
Energy Recovery with Cooling and Heating Model ERCH 100% Outdoor Air System Dedicated Outdoor Air System 1,000-10,000 cfm 1.75 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating,
More informationDES CHAMPS PRODUCTS 85% 4,400 CFM
DES CHAMPS PRODUCTS Saves up to 85% of the heat from exhaust airstream Removes pollutants before they accumulate Transfers heat energy in winter/cool energy in summer Low cost Capacities up to 4,400 CFM
More informationEarthWise System Seminar
EarthWise System Seminar Tim Gasper, P.E. Solutions Engineer Brady-Trane Services, Inc. EarthWise Systems? Energy Efficiency Emissions Buildings use 39% of the Primary Energy Consumed in the United States
More informationPINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION
ENERGY EFFICIENT DEHUMIDIFICATION PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM Provides a very high degree of latent cooling using only a minimal amount of conventional cooling input Substantial energy
More informationHumidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President
Humidity Control Design Tips R. Mark Nunnelly, PE, CxA, LEED AP President AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects
More informationFundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer
Fundamentals of Psychrometrics By James L. Murphy, Colorado Building Environments Sales Engineer Let s s Start with Air Air is Made up of Two Main Gases Nitrogen (77%) Oxygen (23%) If that is all there
More informationMulti-Path RTU-TYPE 2
ALDI # CITY, STATE SUPERMARKET MultiPath RTUTYPE 2 (RTU1) CESMPU025RHVAV2 Date: February 17, 201 2013 Consolidated Energy Solutions, Inc. UNIT FEATURES CES TYPE VAV2 Unit features include: 25 Ton MultiPath
More informationTDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013
TDSHS Air Change Requirements and the Basics of Psychrometrics Presented by: Aric Murray December 06, 2013 Agenda 1. What are the air change requirements and how do you calculate them? 2. Why are air change
More informationHumidity Control & Psychrometrics
Humidity Control & Psychrometrics Iowa Chapter of ASHRAE March 22, 2017 R. Mark Nunnelly, P.E., CxA, LEED AP Nunnelly & Associates, Inc. Commissioning & Humidity Control Consulting Birmingham, AL mnunnelly@nunnellyengineering.com
More informationAHRI 920 & ASHRAE 90.1
AHRI 920 & ASHRAE 90.1 Optimizing Solutions through Superior Dehumidification Technology SM 1 About the Presenter Paul Stewart Education: BSGE University of Illinois Work History: Johnson Controls Inc.
More informationEnergy Recovery Ventilators
Energy Recovery Ventilators Models ERM, MiniVent, ERV and ERVe Untempered Preconditioners September 2016 Energy Recovery Ventilators Greenheck offers a complete line of energy recovery ventilators to reduce
More informationSPLIT SYSTEMS SELECTION & OPTIMIZATION GUIDE
SPLIT SYSTEMS SELECTION & OPTIMIZATION GUIDE www.addison-hvac.com Creating a New Project 1. Open the ACE Interface within the web browser. ACE performs best using the Google Chrome browser. Do not use
More informationIAQ VENTILATORS. FRESH AIR REQUIREMENTS. Applications ASHRAE 62.1, 90.1 & School / university / day care.
FRESH AIR REQUIREMENTS ASHRAE 62.1, 90.1 & 189.1 Applications Health / beauty / spa Pet shop / veterinary clinic ice / conference room School / university / day care Medical / pharmaceutical Museum / library
More informationPhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi
PhEn-602 Pharmaceutical Facility Design Notes #7 J. Manfredi 1 HVAC Design and the Psychrometric Chart 2 HVAC Considerations Pharmaceutical Facility Design Process 1. SPACE REQUIREMENTS Temperature Humidity
More informationHAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001
This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.
More informationAchieving Dry Outside Air in an Energy-Efficient Manner
AT-01-7-2 Achieving Dry Outside Air in an Energy-Efficient Manner Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE Kurt M. Shank Student Member ASHRAE ABSTRACT The central thrust of this paper is to develop
More informationPsychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International
Psychrometrics: The Science of Moisture in Air Presented by Tom Peterson, CEO and Founder Climate by Design International www.cdihvac.com Owatonna, MN 507-451-2198 4 02/2014 1 Psychrometrics or psychrometry
More informationBenefits Offered by Passive Dehumidification Wheel Speed Control
Benefits Offered by Passive Dehumidification Wheel Speed Control White paper By John Fischer Benefits Offered by Passive Dehumidification Wheel Speed Control The most significant advantage of the Pinnacle
More informationINTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings
INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,
More informationMechanical System Redesign. Dedicated Outdoor Air System. Design Criteria
Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed
More informationASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES
INTRODUCTION ASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES Tom Brooke MBA, PE, CEM May 25, 212 On April 19, 212, ASHRAE conducted a webcast to publicize the concept of Dedicated
More informationDesiccant Dehumidification in Air Conditioning for a Large Commercial Building
2333 Desiccant Dehumidification in Air Conditioning for a Large Commercial Building Hyun W Kim, Kamal Abou-Khamis Youngstown State University Abstract A case study was done to investigate the performance
More informationWall Mounted Air Conditioners with Gas Heat Models AVGA
PRODUCT DATA SHEET Wall Mounted Air Conditioners with Gas Heat Models AVGA24-30-36-42-48-60 General Description The Marvair GPac wall mounted air conditioner with gas heat is designed for use on a variety
More informationUTAH ASHRAE CHAPTER ENERGY EFFICIENCY
UTAH ASHRAE CHAPTER ENERGY EFFICIENCY PROGRAM IDEC SYSTEMS SAVE ENERGY WHILE REDUCING DEMAND ON GRID November 2, 2012 Presented by Tom Colvin, P.E., LEED AP, DBIA EVAPORATIVE COOLING BENEFITS ENERGY CONSERVATION
More informationEfficient energy recovery in AHU. DOHA, Qatar Timo Schreck Enventus AB, Sweden
Efficient energy recovery in AHU DOHA, Qatar 11.04.2010 Timo Schreck Enventus AB, Sweden Main principles for cooling and dehumidification process in AHU 1. With cooling coil and reheater 2. Energy recovery
More informationASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering
ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.
More informationCARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.
Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using
More informationCHAPTER 4. HVAC DELIVERY SYSTEMS
CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer
More informationMT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS
CARROLL COUNTY PUBLIC SCHOOLS LIFE CYCLE COST ANALYSIS SUMMARY DGS PROCEDURES FOR THE IMPLEMENTATION OF LIFE CYCLE COST ANALYSIS AND ENERGY CONSERVATION OCTOBER, 2010 G.A.I.#09090 GIPE ASSOCIATES, INC.
More informationSystem Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.
System Components with ` Emphasis on Packaged Rooftop Application and Installation Jerry Cohen President Jacco & Assoc. Agenda Define and relate in practical terms the following components: System Effect
More informationThe ultimate fresh air solution.
Fresh Access The ultimate fresh air solution. Introducing Fresh Access TM. Expertly designed, our innovative energy recovery ventilator (ERV) unit, split dedicated outside air system (DOAS), and packaged
More informationEconomical, Flexible, Advanced Performance. Ventilation and Dehumidification for Healthy IAQ
Economical, Flexible, Advanced Performance Ventilation and Dehumidification for Healthy IAQ CompleVent the Energy Conserving, Cost-Efficient Way to Meet ASHRAE Standards Today s focus on indoor air quality
More informationMystery of Sustainable Heat Exchange Material Heat Recovery Ventilator(HRV)
Mystery of Sustainable Heat Exchange Material Heat Recovery Ventilator(HRV) 1 Contents Why Heat Recovery Ventilator(HRV) is required Type of Heat Recovery Ventilator Feature of MITSUBISHI ELECTRIC Lossnay
More informationA New Dedicated Outdoor Air System with Exhaust Air heat recovery
12 th IEA HEAT PUMP Conference Paper number O1.2.4 A New Dedicated Outdoor Air System with Exhaust Air heat recovery GREATLAB Zi-Yang Zhang, Xiang Cao, Zhi Yang, Liang-Liang Shao, Chun-Lu Zhang, Yue Yu
More informationState of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney
Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled
More informationTwo essential attributes of mechanical systems intended to
This pairing can represent a great strategy if you choose your tactics wisely. When is passive or active the better desiccant approach? When is one out of the question? We ll discuss how to control the
More informationGreenPac & GreenPac HGR Heat Pumps & Air Conditioners Models AVP
MANUFACTURER CERTIFIED TO ARI AS COMPLYING WITH R EQUIPMENT ARI STANDARD 210 ARI STANDARDS GreenPac & GreenPac HGR Heat Pumps & Air Conditioners Models AVP24-30-36-42-48-60 General Description The Marvair
More informationAlpha Aire. Dedicated Outdoor Air System, VAV, Air-Source Heat Pump with Energy Recovery. Engineering Guide Effective February 2018
Alpha Aire Dedicated Outdoor Air System, VAV, Air-Source Heat Pump with Energy Recovery Engineering Guide Effective February 018 CONTENTS PRODUCT FEATURES.......................... OPTIONS.....................................
More informationInnovative and energy efficient humidity control. Peter Lau Application Manager Ingersoll Rand
Innovative and energy efficient humidity control Peter Lau Application Manager Ingersoll Rand CDQ (Cool Dry Quiet) : Dehumidification Innovative and energy efficient humidity control 2 CDQ (Cool Dry Quiet)
More informationBill McCullough. Director ERV Products. Dallas, TX
Bill McCullough Director ERV Products Dallas, TX TOPICS 1. ERV Definition & Benefit 2. Indoor Air Quality 3. Energy Efficiency 4. ERV Technology & Operation 5. Stand-Alone ERVs 6. Compact ERVs What is
More informationThe School District of Philadelphia Administration Headquarters Shell and Core Renovations 440 North Broad Street Philadelphia, PA
2.0 Depth Work - Alternative Mechanical Designs 2.1 Objectives The goal of designing alternative systems is to compare energy usage, system costs, emissions, lost rentable space, and constructability.
More informationTechnical Development Program
Technical Development Program PRESENTED BY: James Parker Insert your logo here AIR HANDLERS Coils: Direct Expansion Chilled Water and Heating Menu Section 1 Introduction Section 2 Typical Coil Applications
More informationMSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)
MSP WRAP-ARUND MULTIPLE SMALL PLATE DEHUMIDIFICATIN TECHNLGY VS. CNVENTINAL DEHUMIDIFICATIN IN DEDICATED UTDR AIR SYSTEMS (DAS) ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
More informationCARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems
Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.
More informationHVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS
HVAC Systems What the Rater Needs to Know in the Field This presentation used CASE* studies from the following *CASE Copy And Steal Everything HVAC Systems - What the Rater Needs to Know in the Field This
More informationEnergy Recovery Ventilation
Published on Business Energy Advisor (https://oncor.bizenergyadvisor.com) Home > Energy Recovery Ventilation Energy Recovery Ventilation Proper ventilation is essential for maintaining good indoor-air
More informationAppendices. Included in this section are
Appendices Included in this section are Appendix A Building Overview Appendix B Alternative Mechanical Designs Appendix C Integration of Structural System and Constructability 68 Appendix A Building Overview
More informationBOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:
4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XRT INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This
More informationA/C Cooling Load calculation and measurement
Testo Inc. 40 White Lake Rd. Sparta NJ 07871 (800) 227-0729 A/C Cooling Load calculation and measurement When we talk about sizing an air conditioning appliance (tons of cooling, BTU/h or KW), we are specifying
More informationFeasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to
More informationASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee
ASHRAE WILL GIVE YOU THE WORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique CTTC
More informationVentilation in Humid Climates: Data from Field Experiments
Gaylord Texan Resort & Convention Center October 20-23, 2004 - Dallas, Texas Ventilation in Humid Climates: Data from Field Experiments Neil Moyer FSEC Yearly Housing Starts Past 3 Years Source: NAHB x
More informationFAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney
FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1
More informationExecutive Summary. OA/person (cfm/p) Private and open offices, Classrooms, Building as designed
Observations, ref ASHRAE May 2013 Journal article Vol. 55, NO 5, pg. 18 VAV Reheat vs. Active Chilled Beams & DOAS. Also published at: http://escholarship.org/uc/item/1jh193x3 Prepared by: S. A. Mumma,
More informationSummary Comparison of Simulation Program Features
Summary Comparison of Simulation Program Features FEATURE DOE2.2 equest TRACE 700 HAP Public/Proprietary Public Domain Proprietary Proprietary Proprietary Simulation Method 8760 hours 8760 hours 8760 hours
More informationProduct Catalog. Horizon Outdoor Air Unit For 100% Outdoor Air Applications Model: OADG OAU-PRC004A-EN. November 2017
Product Catalog Horizon Outdoor Air Unit For 100% Outdoor Air Applications Model: OADG November 2017 OAU-PRC004A-EN Introduction The Horizon Outdoor Air Unit... The Trane DX Horizon Outdoor Air Unit for
More informationHVAC Psychrometric Analysis to Avoid Moisture Problems
PDHonline Course M9 (3 PDH) HVAC Psychrometric Analysis to Avoid Moisture Problems Instructor: Fred W. Dougherty, P.E., B.A.E., M.M.E. 11 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 230-68
More informationDehumidification for Industrial Coating Applications. By: Jay Kranker Munters MCS
Dehumidification for Industrial Coating Applications By: Jay Kranker Munters MCS Reasons for Using Dehumidification Construction/Coating Schedules New VOC Regulations Paint Specifications Adverse Weather
More informationSIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA
Ninth International IBPSA Conference Montréal, Canada August 15-18, 25 SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS Chaoqin Zhai 1, Xiaohong
More informationPrinciples of Active Desiccant Operation. Presented by Tom Peterson, CEO and Founder. Climate by Design International
Principles of Active Desiccant Operation Presented by Tom Peterson, CEO and Founder Climate by Design International www.cdihvac.com Owatonna, MN 507-451-2198 4 02/2014 1 Dehumidification CDI is the Premier
More informationBy MIKE WEST, PHD, PE Advantek Consulting Inc. Melbourne, Fla.
Specifying S P E C I F I C A T I O N G U I D E 2 0 0 4 Dehumidifiers By MIKE WEST, PHD, PE Advantek Consulting Inc. Melbourne, Fla. Desiccant Desiccant dehumidifiers are used for lower-dew-point (below
More informationAn Hourly Building Simulation Tool to Evaluate Hybrid Desiccant System Configuration Options
An Hourly Building Simulation Tool to Evaluate Hybrid Desiccant System Configuration Options ASHRAE Summer Meeting June 29, 2003 Hugh I Henderson, Jr. P.E. CDH Energy Corp. Cazenovia, NY James R. Sand,
More informationHeat pump and energy recovery systems
SBS5311 HVACR II http://ibse.hk/sbs5311/ Heat pump and energy recovery systems Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Oct 2017 Contents Basic concepts Air-to-air
More informationBOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:
4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XIN INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This
More informationEnergy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE
This article was published in ASHRAE Journal, March 20145 Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
More informationAvailable online at Energy Procedia 6 (2011) MEDGREEN 2011-LB
Available online at www.sciencedirect.com Energy Procedia 6 (2011) 759 768 MEDGREEN 2011-LB Comparison of two methods of improving dehumidification in air conditioning systems: hybrid system (refrigeration
More informationENGINEERING AND CONSTRUCTION BULLETIN
ENGINEERING AND CONSTRUCTION BULLETIN No. 2016-15 Issuing Office: CECW-CE Issued: 23 May 16 Expires: 23 May 18 CATEGORY: Guidance 1. References: Jesse Dean, Lesley Herrmann, Eric Kozubal, and Jesse Geiger
More informationDOAS UNITS. ReznorHVAC.com MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR
MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR KITCHENS HOTEL CORRIDORS LABORATORIES CONFERENCE CENTERS SCHOOLS PAINT BOOTHS MALLS/SHOPPING CENTERS DOAS UNITS Capacities 5-30 Tons 50-800 MBH 30-120 kw 650-9,000
More informationDehumidification System Enhancements
2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal, (Vol. 48, February 2006). For personal use only. Additional distribution
More informationTHE ULTIMATE ROOFTOP SOLUTION
Configured Packaged Rooftop Solutions Specializing in Dedicated Outdoor Air Systems (DOAS) Capacities from 6 to 90 Tons Available in 208, 230, 460 and 575 Volts THE ULTIMATE ROOFTOP SOLUTION Service Friendly
More informationChilled Ceilings / Beams Working Principles & Applications
5 th International Conference on Energy Sustainable Energy Polices and Technologies 15-17 October 2014 Chilled Ceilings / Beams Working Principles & Applications Francis W H Yik ATAL Building Services
More informationHEALTHCARE SURGERY VENTILATION HUMIDITY CONTROL
EFFECTIVE LOW DEW POINT EFFICIENT HEALTHCARE SURGERY VENTILATION HUMIDITY CONTROL HVAC systems have a major impact on: Specialized solution for the high demands of healthcare applications HVAC systems
More information