BC-R10 Series. Burner Controllers

Size: px
Start display at page:

Download "BC-R10 Series. Burner Controllers"

Transcription

1 No. CP-SS-1885E BC-R10 Series Burner Controllers Summary BC-R10 Series burner controllers are combustion safety controllers specifically designed for batch operation (systems which start and stop at least once within 24 hours). They ensure safety by automatically controlling the ignition, combustion monitoring, and fuel shutoff of oil burners. BC-R10 burner controllers can be used with AFD100/110 series visible light flame detectors. They are also equipped with a 7-segment display that can be used in maintenance, a trial operation mode that is convenient for trial operation and adjustment, and other features. Features Compliant with JIS standards Safe construction of combustion systems and equipment - Uses prepurge and ignition timing in compliance with JIS B 8407:2012 (forced-air burners) and JIS B 8415:2008 (combustion equipment in compliance with the safety principles for industrial incinerators) JIS-compliant burner controller safety design - Safety design in compliance with JIS C 9730 (automatic electrical controls for household and similar use) - EN 298 compliance (certification pending) Easy mounting and replacement DIN rail mounting - Easily mountable in the same way as other control devices and control relays Uses a sub-base structure - Structure separates the sub-base from the main unit It is possible to change only the main unit, leaving the wired-in sub-base in place Precautions on equipment instrumentation Extensive communications with external devices Equipped with a 7-segment display - 7-segment display for sequence codes and warning codes - Press the DISP switch to display the flame voltage. External status output - States such as ignition failure, flame failure, and combustion detected are output digitally (and used as panel displays) Warning reset by contact input (1) The equipment used in the combustion safety system was designed with careful consideration of laws, standards, safety guidelines, and the like. If the system is designed to a foreign specification, refer to laws and standards in the relevant country. Main Safety Standards in Japan - Technical Policy on Safety Standards for Equipment in Industrial Furnaces: Ministry of Health, Labour and Welfare - equipment in compliance with the safety principles for industrial incinerators - JIS B Forced Draught Burners - Part 1: Gas Burners - JIS B Forced Draught Burners - Part 2: Oil Burners - JIS B The index of safety technology of industrial gas combustion equipment: Japan Gas Association - Index of safety technology of gas boiler combustion facilities: Japan Gas Association (2) This device monitors for failures in the relay contacts used for combustion load (IG, PV, MV) output. An E09 error is output if a voltage occurs at a load terminal, due to a ground fault or wiring error, when this device is not outputting a load. If an E09 error occurs when this device is installed, recheck the wiring and eliminate the factors causing the error. (3) If the wiring from this device exceeds the recommended length, prevent malfunction due to the effects of external noise by running wires from the control panel to the casing through a conduit, keeping a distance between power lines and input lines, and other measures. Check the operation of the system on installation. (4) A reset signal must always be input near the equipment (burner, etc.), not remotely. If a reset is input while it is not possible to confirm safety, there is the risk of explosion. 1

2 Specifications Application Item Compatible flame detector Batch-operated combustion systems burning oil Visible light flame detector AFD100/110 series Sequence Sequence timing Please refer to the model number composition table. Electrical specifications Transportation and storage conditions Operating conditions General specifications Flame response timing Warning detection timing monitoring Operation at ignition failure Operation at flame failure Rated power supply Allowable power supply voltage Voltage resistance Voltage resistance Please refer to the model number composition table. Description 1 s or longer (main unit reset switch or contact reset input) False flame (1) *1 (2) *1 Interlock error 5 s 1 s 180 s 1 s max Please refer to the model number composition table. Please refer to the model number composition table. 100 Vac or 230 Vac, 50 Hz or 60 Hz 85 to 110 % of rated power supply 10 W or less 1500 Vac for 1 min, or 1800 Vac for 1 s Between each terminal and ground (the DIN rail clamp), except for combustion sensor connection terminals (terminals 14, 15) Insulation resistance At least 50 MΩ, 500 Vdc megger Between each terminal and ground (the DIN rail clamp), except for combustion sensor connection terminals (terminals 14, 15) Contact rating Blower motor Warning (electromagnetic breaker) 100 VA 300 VA 200 VA 200 VA 75 VA s 4, maximum 30 ma each When ignition is detected: 1.3 Vdc or less detection level When detected as extinguished: 0.5 Vdc or over Flame voltage output Flame voltage output range: 0.2 to 4.8 Vdc Startup, lockout interlock, contact reset, airflow switch * Each input is a non-voltage contact input, with allowable contact resistance up to 500 Ω Lifespan 10 years when used for eight hours per day, or 100,000 start/stop cycles (at 25 C, constant temperature, rated voltage) Ambient temperature -20 to +70 C Ambient humidity 5 to 95 % RH (no condensation) Vibration 0 to 9.8 m/s 2 (10 to 150 Hz, 1 octave/minute, 10 cycles, in each of XYZ directions) Shock 0 to 300 m/s 2 Packaged drop test 60 cm drop height (free drop onto 1 corner, 3 edges, 6 sides) Ambient temperature -20 to +60 C Ambient humidity 10 to 90 % RH (no condensation) Vibration 0 to 3.2 m/s 2 (10 to 150 Hz, 1 octave/minute, 10 cycles, in each of XYZ directions) Shock 0 to 9.8 m/s 2 Mounting angle Reference plane +/-10 Dust 0.3 mg/m 3 or less Protective structure IP40 (with a sideboard ( ) attached to the sub-base (BC-R05)) IP10 (sub-base (BC-R05) only) Excess voltage II category Pollution degree PD2 Case color Black Case material Denatured PPE resin (UL 94-V0 PTI material group IIIa) Structure Sub-base and main unit Mounted orientation Vertical or horizontal However, for horizontal attachment, 7 segment display can only be mounted so that it faces directly overhead (DIN rail mounting or direct mounting through base screw holes) Dimensions W95 H105 D110mm Weight Approximately 600 g (incl. sub-base) Wiring types and max. wiring - Start, airflow switch, lockout interlock length Copper IV wire with 600 V vinyl insulation, 1.25 mm 2, recommended condition: 20 m or less, maximum wiring length: 100 m - Contact reset Copper IV wire with 600 V vinyl insulation, 1.25 mm 2, maximum wiring length: 10 m - AFD100 Series (F, G) Copper IV wire with 600 V vinyl insulation, 1.25 mm 2, maximum wiring length: 100 m - Signal line for flame voltage output IV wire, 0.75 mm 2 or larger, max. wiring length 10 m *1 monitoring model only 2

3 Model number composition (Note: The dedicated sub-base and sideboard are not provided with the BC-R10 series controller. Order them separately.) Model Number BC-R10A7G004_ observation Pre-purge type Pre-ignition *3 Pre-purge time Ignition trial time Postignition *2 Operation at flame failure 4.5±0.5 s 11±1.5 s 2 s max BC-R10A7H003_ Pre-ignition *3 4.5±0.5 s 11±1.5 s Recycling *4 1 s max BC-R10A7H005_ Yes Pre-ignition *3 4.5±0.5 s 15±1.5 s Recycling *4 1 s max BC-R10A7J002_ Pre-purge 4.5±0.5 s 7±1 s 2 s max BC-R10A7K007_ Pre-purge 7±1 s 7±1 s Recycling *4 1 s max 20±2 s BC-R10A7L004_ Pre-ignition *3 4.5±0.5 s 11±1.5 s 2 s max BC-R10A7M003_ Pre-ignition *3 4.5±0.5 s 11±1.5 s Recycling *4 1 s max BC-R10A7M005_ No *1 Pre-ignition *3 4.5±0.5 s 15±1.5 s Recycling *4 1 s max BC-R10A7N002_ Pre-purge 4.5±0.5 s 7±1 s 2 s max BC-R10A7P007_ Pre-purge 7±1 s 7±1 s Recycling *4 1 s max _ 0 : No additional function D : With inspection record (with data) Flame failure Post-purge response time time *1 It must be used for burners that are configured for use without an airflow rate detector, as specified in JIS B , Forced Draught Burners, Part 2: Oil Burners. *2 It proceeds to post-ignition after the end of ignition trial. *3 The ignition transformer is ON during pre-purge. *4 When flame failure occurs, after the flame failure response time,the recycling model proceed to pre-purge after 5 s of inter-waiting time and 2 s of start check time elapse. Recycling is done once. If there is second time of flame failure, it proceeds to lock-out. 0 s Compatible flame detector (sold separately) Visible light flame detector Model number Name Notes AFD100A0700 Visible light flame detector Light reception direction: front, top-view type AFD100B0700 AFD110A0000 Light reception direction: side, side-view type G3/4-inch flange mounting type Options (sold separately) Model number Name Notes BC-R05A100 Dedicated BC-R sub-base Required for all products in the BC-R10 series Connector for front wiring Weidmueller BL3.5/11F Compatible wire: mm 2 (AWG28-14) Connector for front wiring (for right side wiring) Weidmueller BL3.5/11/270F Compatible wire: mm 2 (AWG28-14) Side boards Contains two. Not included in the sub-base. FSP136A100 Analog flame meter Jack cover Includes mounting screw Front connector cover Packaged with mounting screws (Included with the controller.) BC-R models that replace R4424 and older models Current/old model R4424C104-A, R4424C104-1, R4313C R4424C204-A, R4424C204-1, R4313C R4424D1001-A, R4424C1001-1, R4313D1005 R4424D1019-A, R4424C1019-1, R4313D1013 R4424D121-A, R4424C121-1, R4313B1009 R4424D221-A, R4424C221-1, R4313B1017 R4424E104-A, R4424C104-1, R4313E1002 R4424E204-A, R4424C204-1, R4313E1010 Rated power supply 100 Vac 200 Vac 100 Vac 200 Vac 100Vac 200 Vac 100 Vac 200 Vac Operation at flame failure Recycling Recycling Pre-purge type Pre-purge Pre-ignition Pre-purge Pre-ignition Pre-purge Pre-purge Replacement BC-R model BC-R10A7P0070 (BC-R10A7K0070) * BC-R10A7L0040 (BC-R10A7G0040) * BC-R10A7M0050 (BC-R10A7H0050) * BC-R10A7N0020 (BC-R10A7J0020) * * Note: monitoring is available for models in parentheses. Sequence timing and tolerances of the replacement may differ from those of the replaced model. For details, see the individual speciations sheet. 3

4 Terminal numbers, front panel item names Front Display Sub-base (sold separately) switch Display switch Front connector cover (connector is behind cover) Jack * * Used for inspection and adjustment during production. Not for Smart Loader Package use. DIN rail clamp Terminal board Terminal numbers Front connector terminals No. Function No. Function 25 Flame voltage output (+) 31 for monitor output 26 Flame voltage output (-) 32, combustion 27 NC 33, ignition failure 28 NC 34, flame failure 29 NC 35, lockout 30 NC interlock input Sub-base terminals No. Function No. Function 1 Blower motor output (electromagnetic breaker) 13 2 AC power supply (L1) 14 Flame detector (F) 3 AC power supply (L2 (N)) 15 Flame detector (G) 4 common 1 16 common 1 5 common 2 17 common 2 6 output 18 NC 7 ) 19 NC 8 ) 20 9 NC 21 input *1 10 NC 22 input 11 NC 23 NC 12 NC 24 Contact reset input *1 Only for models with airflow switch observation. 4

5 7-segment display, LED display, switches If this device detects a flame failure etc., it isolates the load and applies a lockout. During lockout, the relevant diagnostic function code is displayed on the 7-segment display. Part Name 7-segment LED (green) When normal: sequence code/ flame voltage When an error occurs: Warning code/ flame voltage Switch Flame voltage/ sequence code Flame voltage/ warning code display switch Flame LED (green) Lit when flame signal is detected. Off when flame signal is off. Loader jack Used for inspection and adjustment during production. Not for Smart Loader Package use. BC-R main unit fastening screw switch Switch to cancel lockout (Press and hold for approximately 1s) ALARM LED (red) Lit during lockout. Off when there is no lockout. Front connector Flame voltage output (0-5V) (semiconductor relay output) BC-R main unit fastening screw Warning codes Display Name Meaning E0 Interlock error E 1 False flame signal was detected for 5s during start check and prepurge E2 error 1 *1 The airflow switch turned Off during combustion E3 error 2 *1 The airflow switch stayed On for 3 minutes during start check The airflow switch did not turn On for 3 minutes after the start of prepurge E6 Ignition failure Ignition could not be detected with main trial E7 Flame failure The flame signal disappeared in the sequence after main trial E9 + Sub-code (2 digits) Device error Voltage error detected in output from the ignition transformer, ), or Hi solenoid valve), etc. *1 Only for models with airflow switch observation. Sequence codes Display Status content P 1 P2 Pre-purge P4 Iignition trial P5 Post ignition P8 Run Pr Inter-waiting -- Controlled shutdown Examples of sequence codes and warning codes Warning code: E1 to E7 Warning code: E9 + sub-code (2 digits) Switches every 0.8s (Sub-code) Switches every 0.8s 5

6 Internal block circuit, external connection terminals (1-24 on sub-base, on front connector) L1 L2(N) Blower motor (Electromagnetic breaker) common K10 10A circuit K2 K5 K3 K4 NC K1 DC24V safety control circuit K6 Flame detector circuit circuit (24Vdc) 13 F 14 G NC 18 NC Warning Flame detector common Start *2 10 NC NC NC NC 24 Contact reset Display FLAME ALARM Flame voltage circuit NC 27 NC 28 NC 29 FV+ FV- DISP switch Loader jack *1 switch Monitor output circuit NC Interlock for monitor output (100/200 Vac or 24 Vdc) Note - Use reset (terminal 24) input in isolation. It cannot be used in conjunction with other BC-R contact reset inputs. - common (terminals 4, 5) and input common (terminal 16, 17) cannot be used in conjunction with other BC-R. *1 The loader jack is used for inspection and adjustment during production. *2 Only for models with airflow switch observation 6

7 External Dimensions BC-R10 Burner Controller (Unit: mm) Sub-base (sold separately) BC-R main unit fastening screw Connector for front wiring Sub-base (sold separately) BC-R main unit fastening screw A DIN rail clamp Model number A Sub-base BC-R05A100 (sold separately) Knockout hole 16 Knockout hole 64 M3.5 (terminal screw) ø12 knockout hole ø12 knockout hole Sub-base mounting hole Sub-base mounting hole DIN rail clamp 7

8 Sideboard (sold separately) (Unit: mm) Sub-base 30.7 Sub-base ø19 knockout hole Sideboard Sideboard ø19 knockout hole 23.9 Precautions on installation (1) Allow 50mm above and below, 50mm to the left and right, and 80mm to the front as space for removal, wiring, and maintenance. Also, do not install this device close to electric power devices or other sources of heat. 50mm Front 50mm 50mm 50mm 80mm 50mm 50mm Wiring, ducts, etc. (2) This device must be grounded within a grounded and conductive control panel to ensure safety. (3) Do not pull the wiring while it is attached to the device. Doing so can cause failure of the connectors or the unit itself. Installation orientation Install the device in the orientation shown below. Display area BC-R Main unit OK BC-R Main unit OK Do not install it in the orientations illustrated below. BC-R Main unit Mounting in a Panel [1] Drill two M4 screw holes into the panel. [2] Use screws to mount the sub-base on the panel. (Maximum tightening torque: 1.2 N m) 62.5 M4 (2 locations) (Unit: mm) 8

9 Operation Sequence 1-1. Normal Operation (Pre-purge with airflow switch) signal Prepurge Post ignition Steady combustion -- P1 P2 P4 P5 P8 -- time time Post ignition time 1-2. Normal Operation (Pre-purge without airflow switch) signal Prepurge Post ignition Steady combustion -- P1 P2 P4 P5 P8 -- time time Post ignition time 9

10 1-3. Normal Operation (Pre-ignition pre-purge with airflow switch) signal Pre-ignition Pre-purge Post ignition Steady combustion -- P1 P2 P4 P5 P8 -- time time Post ignition time 1-4. Normal Operation (Pre-ignition pre-purge without airflow switch) signal Pre-ignition Pre-purge Post ignition Steady combustion -- P1 P2 P4 P5 P8 -- time time Post ignition time 10

11 2. (Pre-purge with airflow switch) signal Prepurge -- P1 P2 P4 P4/E6 time time 11

12 3-1. (Non-recycling model) signal Prepurge Post ignition Steady combustion -- P1 P2 P4 P5 P8 P8/E7 Flame response Post ignition time time time 3-2. (Recycling model) signal Prepurge Post ignition Steady combustion Inter-waiting Prepurge -- P1 P2 P4 P5 P8 Pr P1 P2 P4 Flame response Post ignition time time time Inter-waiting time Approximately 5 s time 12

13 4. Interlock error(pre-purge model) signal Prepurge Steady combustion -- P1 P2 P4 P5 P8 P8/E0 -- time Post ignition time time 5. does not turn ON when pre-purge starts.(common to both pre-purge and preignition models) signal Prepurge -- P1 P2 P2/E3 time Approximately 3 m 13

14 6. False flame signal before startup -- P1 P1/E1 signal 5 s 7. False flame occurred during pre-ignition prepurge(pre-ignition model) (False flame occurrence time: less than 5 s) signal Pre-ignition Pre-purge False flame occurrence False flame extinguished Post ignition Steady combustion -- P1 P2 P4 P5 P8 -- Less than 5 s * Flame response time Post ignition time time * Note: If the false flame signal continues for five seconds or longer, lockout occurs. 14

15 Trial-run operation mode Warning In trial operation mode, loads (blower, ignition transformer, control motor, etc.) operate. They should be operated by a person with expert knowledge and an understanding of the functions. There is a risk of a major accident. Transition to trial operation mode [1] Press and hold the DISP switch for approximately 5 s or more during the stop sequence (when the start switch is Off). The 7-segment display changes to [ C2 ] and the system goes into trial operation mode. The central dot of the 7-segment display starts blinking (a 1 s cycle). [1] [2] [3] [4] [3] Trial operation setup [2] Each time the DISP switch is pressed, the display changes through the cycle [ C2 C3 C4 C5 C6 ] Display C2 C3 C4 C5 C6, flame, ignition failure, flame failure, lockout interlock Blower motor output Meaning n Trial-run operation mode selection [3] Select trial operation type using the DISP switch. When C2 ~ C6 is selected 1 Press the button to enter selection mode. The 7-segment display displays [ Cx/OF ]. 2 When the DISP switch is pressed in this situation, the display toggles between [ Cx/ OF ] and [ Cx/On ], and trial operation runs according to the On/Off selection. * C6 only becomes [ C6/On ]. To turn the blower off, press the switch when in this state. 3 When the switch is pressed to stop trial operation, the display for selecting types of trial operation ([2] above) is displayed. Exit [4] Press and hold the DISP switch for 5 s or more to end trial operation mode. Trial operation mode also ends in the following situations. The power supply is turned Off. 1.1 Forced output of the Flame monitor output ( c2 ) Allows checking of indicators etc. connected to the monitor output terminal. Turns the flame monitor output ON or OFF. 1.2 Forced ignition failure monitor output ( c3 ) Allows checking of indicators etc. connected to the monitor output terminal. Turns the ignition failure monitor output ON or OFF. 1.3 Forced flame failure monitor output ( c4 ) Allows checking of indicators etc. connected to the monitor output terminal. Turns the flame failure monitor output ON or OFF. 1.4 Forced lockout interlock monitor output ( c5 ) Allows checking of indicators etc. connected to the monitor output terminal. Turns the lockout interlock monitor output ON or OFF. 1.5 output On ( c6 ) This is a function to force blower motor (electromagnetic breaker) output and check the air volume. 15

16 Customer Specification Check Sheet, BC-R10 Series This sheet is for selecting the optimum BC-R10 Series product to suit the customer s specification. Use it to facilitate communications with our sales staff. Equipment name Equipment summary Flame detector used Visible light flame detector AFD100/110 sires Ignition method voltage 100 to 230 Vac Sequence Pre-purge Seconds or minutes Ignition standby Post-ignition Flame response s s s (Write whether or not there is input, the specification, etc.) input Contact reset input input MEMO 16 1st Edition: Issued in Mar nd Edition: Issued in July 2014

AUR300C, AUR350C. Advanced Ultraviolet Burner Controller

AUR300C, AUR350C. Advanced Ultraviolet Burner Controller No. CP-SS-7E Overview The AUR300C is a burner controller with a dynamic selfchecking function and is used in combination with the AUD300C or AUD00C Advanced Ultraviolet Flame Detector. This AUR300C controls

More information

Advanced Ultraviolet Burner Controller

Advanced Ultraviolet Burner Controller No. CP-SS-7E Advanced Ultraviolet Burner Controller Model AUR300C/AUR30C Overview The AUR300C Advanced Ultraviolet Burner Controller and AUR30C Advanced Ultraviolet Burner Controller with Communication

More information

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD Corona Corporation This instruction manual contains important information for safe use of this device. Keep this instruction manual

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION R SERIES 35-61 24 VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay F-35-61 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge

More information

AUR300C. Advanced Ultraviolet Burner Controller

AUR300C. Advanced Ultraviolet Burner Controller No. CP-SS-1807E AUR300C Advanced Ultraviolet Burner Controller Overview The AUR300C is a burner controller with a dynamic selfchecking function and is used in combination with the AUD300C or AUD500C Advanced

More information

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION R SERIES 35-703 120 VAC Microprocessor-Based Intermittent Pilot Ignition Control F-35-703 July 2016 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

SERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS

SERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS SERIES 35-63J INSTALLATION INSTRUCTIONS FOR REPLACING JOHNSON CONTROLS G77X AND OTHER MODELS WITH FENWAL SERIES 35-63J IP IGNITION CONTROL APPLICATIONS The Fenwal 35-63J series Intermittent Pilot Ignition

More information

SLATE. Burner Control Module INSTALLATION INSTRUCTIONS R8001B2001

SLATE. Burner Control Module INSTALLATION INSTRUCTIONS R8001B2001 SLATE Burner Control Module R8001B2001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform

More information

LFL Series Burner Flame Safeguard Control

LFL Series Burner Flame Safeguard Control LFL Series Burner Flame Safeguard Control Technical Instructions Document No. 74US LFL Rev. 2 November, 2004 The LFL is a compact electro-mechanical primary flame safeguard control designed to provide

More information

7800 SERIES RM7888A Relay Module

7800 SERIES RM7888A Relay Module 7800 SERIES RM7888A Relay Module SPECIFICATION DATA FEATURES APPLICATION The Honeywell RM7888A Relay Module is a microprocessor-based integrated burner control for industrial process semi-automatically

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! 50V64-743 Integrated Furnace Control for Furnaces with Variable Fan Speed INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY

More information

Model 60200FR Gas Primary Control Data Sheet

Model 60200FR Gas Primary Control Data Sheet Programmable, Microprocessor Based Gas Burner Primary Controls On-Board LCD Screen Easy to Understand Icons for Inputs and Outputs Displays micro-amp Flame reading Display operational information Fault

More information

INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL

INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL Figure 1 Series 9 Intermittent Pilot Ignition Control Application The Series 9 Intermittent Pilot Ignition Control is a microprocessor

More information

7800 SERIES RM7840E,G,L,M; EC7840L Relay Module

7800 SERIES RM7840E,G,L,M; EC7840L Relay Module 7800 SERIES RM7840E,G,L,M; EC7840L Relay Module SPECIFICATION DATA Valve Proving features including: VPS test time When (Never, Before, After, Split or Both) FEATURES APPLICATION The Honeywell RM7840 is

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA) R SERIES 35-70 120 VAC Microprocessor-Based Direct Spark Ignition Control F-35-70 November 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

MBCE-110/230UV Flame Sensor Module

MBCE-110/230UV Flame Sensor Module MBCE-1002 FEBRUARY 3, 2017 MBCE-110/230UV Flame Sensor Module DESCRIPTION The MBCE-110/230UV modules provide visual indication and electrical outputs that signal the user regarding flame presence in a

More information

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS SERIES 35-65 24 VAC Microprocessor-Based Hot Surface Ignition Control F-35-65 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings* 120/240

More information

7800 SERIES RM7888A Relay Module

7800 SERIES RM7888A Relay Module 7800 SERIES RM7888A Relay Module FEATURES SPECIFICATION DATA APPLICATION The Honeywell RM7888A Relay Module is a microprocessor-based integrated burner control for industrial process semi-automatically

More information

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY AUTOMATIC BURNER CONTROL SYSTEM The burner control unit Quad400 is suitable for the control of direct ignition burners up to 350 kw, pursuant to EN 746-2. Flame control by means of UV scanner or ionization

More information

NXM2G Installation and Operating Manual

NXM2G Installation and Operating Manual NXM2G-1001 MARCH 26, 2014 NXM2G Installation and Operating Manual (-1 UL version shown) 40VG This manual must be affixed on or adjacent to the boiler or kept with boiler operating manual or other information.

More information

7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules

7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules 7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules SPECIFICATION DATA FEATURES APPLICATION The Honeywell EC7895/RM7895/RM7896 is a microprocessor based integrated burner control for automatically

More information

BGH Series Hot Surface Ignition Control

BGH Series Hot Surface Ignition Control Installation Instructions BGH Series Issue Date April 14, 2011 BGH Series Hot Surface Ignition Control Application The BASO Gas Products BGH Series Hot Surface Ignition (HSI) control is microprocessor

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 50A55-286 Integrated Furnace Control INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR

More information

Operating Manual MS220KA and MSR220KA

Operating Manual MS220KA and MSR220KA Temperature Relays and MINIKA, Mains Monitoring, Digital Panel meters MINIPAN, Switching Relays and Controls Operating Manual MS220KA and MSR220KA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße

More information

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001 SLATE Base Module R8001A1001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform can

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! 031-01284-000/50A55-241 Integrated Furnace Control INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR

More information

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS 50M56-743 Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD

More information

Model Universal Oil Primary Control

Model Universal Oil Primary Control Model 70200 Universal Oil Primary Control Installation and Operating Instructions For Use By Qualified Service Technicians Only Universal Replacement for Carlin, Beckett, Honeywell and ICM Controls On-Board

More information

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) T M 1 isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) Technical Bulletin NAE1012372 / 03.2015 isopv

More information

7800 SERIES: EC7895A,C; RM7895A,B,C,D; RM7896A,B,C,D RM7897A,C and RM7898A Relay Modules

7800 SERIES: EC7895A,C; RM7895A,B,C,D; RM7896A,B,C,D RM7897A,C and RM7898A Relay Modules 7800 SERIES: EC7895A,C; RM7895A,B,C,D; RM7896A,B,C,D RM7897A,C and RM7898A Relay Modules SPECIFICATION DATA The RM7897A1002 offers selectable pilot operation, intermittent on terminal 8 or interrupted

More information

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

DEB71. Earth Leakage Monitoring Relay. Benefits. Description Earth Leakage Monitoring Relay Benefits Adjustable trip level. Adjustable leakage threshold from 30mA to 5A or from 300mA to 30A. 2 outputs. Two relay outputs provide, besides the alarm signal an additional

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! 50A65-843 Universal Integrated Furnace Control INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING

More information

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products 7 418 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of small to medium capacity (without fan) in intermittent operation. The LGA... and this

More information

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl enproteko.com Temperature Monitoring Relay K8AB-TH Compact and Slim Relay Ideal for Temperature Alarms and Monitoring Excessive increases can be prevented and abnormal s can be monitored. Temperature monitoring

More information

50A Integrated Furnace Control

50A Integrated Furnace Control Goodman White-Rodgers 0130F00005 PCBBF110 PCBBF123 50A55-743 0130F00005S PCBBF110S PCBBF123S 50A55-289 B1809926 PCBBF112 50T55-289 B1809926S PCBBF112S 50A55-743 Integrated Furnace Control INSTALLATION

More information

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler ClearFire Model CFH Horizontal Steam Boiler Startup Guide 750-293 www.cleaverbrooks.com Improper installation, adjustment, service, or maintenance can cause equipment damage, personal injury, or death.

More information

UV Flame Supervision System

UV Flame Supervision System 7 783 UV Flame Supervision System DETACTOGYR LFE50 Series 02 ISO 9001 The LFE50 is a self-checking UV flame supervision system designed for use with continuously operating burners or for burners running

More information

MBCE-110/230FR Flame Sensor Module

MBCE-110/230FR Flame Sensor Module MBCE-1001 APRIL 13, 2012 MBCE-110/230FR Flame Sensor Module DESCRIPTION The MBCE-110/230FR modules provide visual indication and electrical outputs that signal the user regarding flame presence in a combustion

More information

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification SCC Inc. LMV51 Control Product Description February 7, 2017 The LMV51 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft

More information

SLATE. Rectification Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001V1031

SLATE. Rectification Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001V1031 SLATE Rectification Ampli-Check Flame Amplifier R8001V1031 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single

More information

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE Cat. N STOP & GO automatic resetting 87045 LIMOGES Cedex - FRANCE Telephone : + 33 5 55 06 87 87 Fax: + 33 5 55 06 88 88 Cat. N (s) : 4 062 88 / 4 062 89 CONTENTS PAGE 1. Description - Use... 1 2. Product

More information

STEAMPAK Series BurnerPAK BMS Burner Management Systems

STEAMPAK Series BurnerPAK BMS Burner Management Systems BurnerPAK BMS Burner Management Systems Sequence of operation, ignition and control of burners Meets NFPA 85 safety standard MFT alarming with manual reset, first-out indication Optional enhanced alarming

More information

R7120M 7800 SERIES Relay Modules

R7120M 7800 SERIES Relay Modules R7120M 7800 SERIES Relay Modules INSTALLATION INSTRUCTIONS APPLICATION The R7120M are microprocessor-based integrated burner controls for automatically fired gas, oil, or combination fuel single burner

More information

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR..

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR.. EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR.. AUTOMATIC OIL BURNER CONTROL SYSTEMS APPLICATION This range of electronic oil burner controls has been specifically designed for oil burners for non

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 50A55-474 & 50A55-571 Integrated Furnace Controls INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE

More information

7800 SERIES RM7840E,G,L,M Relay Module

7800 SERIES RM7840E,G,L,M Relay Module 7800 SERIES RM7840E,G,L,M Relay Module APPLICATION SPECIFICATION DATA The Honeywell RM7840 is a microprocessor based integrated burner control for automatically fired gas, oil or combination fuel single

More information

YP7999A1000 ControLinks Fuel Air Ratio Control Panel

YP7999A1000 ControLinks Fuel Air Ratio Control Panel YP7999A1000 ControLinks Fuel Air Ratio Control Panel FEATURES INSTALLATION INSTRUCTIONS Pre-wired and ready to install Includes the R7999A control, wiring subbase and S7999D1048 touchscreen display Commission,

More information

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners certified Qualitysystem ISO 9001 / EN 29001 Reg. Nr. 10529 Gas Burner Safety Control A Honeywell Company For 2-stage forced draught and combi oil/gas burners Possible flame detectors: - Ionisation probe

More information

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit A Honeywell Company Gas Burner Safety Control For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit Possible flame detectors: - Ionisation probe - Infrared flicker

More information

Interrupted Ignition Series Oil Primary Control

Interrupted Ignition Series Oil Primary Control Interrupted Ignition Series Oil Primary Control Application Guide & Installation Instruction for ICM1511*, ICM1512*, ICM151*, ICM1514* For more information on our complete range of American-made products

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

Oil Burner Controls LMO24... LMO44...

Oil Burner Controls LMO24... LMO44... 7 130 Oil Burner Controls LMO14... LMO24... LMO44... Microcontroller-based oil burner controls for the startup, supervision and control of forced draft oil burners in intermittent operation. Standard versions

More information

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products 7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! 50A66-743 Integrated Furnace Control Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL

More information

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION M-4000 JANUARY 29, 200 FIREYE M4RT1 FLAME SAFEGUARD CONTROLS WARNING: Selection of this control for a particular application should be made by a competent professional, licensed by a state or other government

More information

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division 7 8 ISO 900 LOA2... LOA... Oil Burner Controls LOA2... LOA... Oil burner controls for the supervision, startup and control of single- or twostage oil burners with an oil throughput of up to 0 kg/h in intermittent

More information

Oil Burner Controls LMO24... LMO44...

Oil Burner Controls LMO24... LMO44... 7 130 Oil Burner Controls LMO14... LMO24... LMO44... Microcontroller-based oil burner controls for the startup, supervision and control of forced draft oil burners in intermittent operation. Standard versions

More information

R7910A SOLA (Hydronic Control) and R7911 SOLA (Steam Control) Systems

R7910A SOLA (Hydronic Control) and R7911 SOLA (Steam Control) Systems R7910A SOLA (Hydronic Control) and R7911 SOLA (Steam Control) Systems APPLICATION The R7910 SOLA hydronic boiler and the R7911 SOLA steam control systems provide heat control, flame supervision, circulation

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! 21M51U-843 Universal Integrated Two-Stage 120Volt Hot Surface Ignition Control Kit INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals Technical Information RTA421 Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals Application Plant and machine construction Panel builders Process monitoring Process

More information

LC3000 Level Controller Installation and Maintenance Instructions

LC3000 Level Controller Installation and Maintenance Instructions 4025550/12 IM-P402-36 AB Issue 12 LC3000 Level Controller Installation and Maintenance Instructions 1. General safety information LC3000 NORM ALARM TEST 2. General product information 3. Installation 4.

More information

CAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS

CAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS 50T35-743 Integrated Furnace Control INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY

More information

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit certified Qualitysystem ISO 9001 / EN 29001 Reg. Nr. 10529 Gas Burner Safety Control A Honeywell Company For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit Possible

More information

Quickheat 30 weather compensated boiler control

Quickheat 30 weather compensated boiler control Quickheat 0 weather compensated boiler control A compact and sophisticated heating controller The compact KM controller is designed for the control of fan assisted boilers with modulating burners. The

More information

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products 7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication

More information

Eclipse Self-Check UV Scanner

Eclipse Self-Check UV Scanner 856 Instruction Manual 10/18/2010 Eclipse Self-Check UV Model 5602-91 Version 1 Introduction The self-check UV is used for continuous gas or oil flames. A mechanical shutter in the scanner closes briefly

More information

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification LMV52 Control Product Description February 3, 2017 The LMV52 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft burners.

More information

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 0804 L2 Revised 05 05 2008 G71MPP G71MPP SERIES UNITS G71MPP series units are high efficiency multi position (upflow, downflow, horizontal right and left) gas furnaces equipped

More information

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15 with coupling device AGH675-7 and AGH675-7MV15 Device combination for insulation monitoring in unearthed AC, AC/DC and DC power systems (IT systems) IRDH275BM-7_D00123_03_D_XXEN/01.2017 with coupling device

More information

7800 SERIES EC7885A/RM7885A Relay Module

7800 SERIES EC7885A/RM7885A Relay Module 7800 SERIES EC7885A/RM7885A Relay Module SPECIFICATION DATA 1. Torch-ignited main burner using the S445A Start-Stop Station, or any conventional knee or foot operated start-stop station. 2. Torch-ignited

More information

Flame Safeguard Fault Code Diagnostics

Flame Safeguard Fault Code Diagnostics Vino s Vine Tech Tips Series 02/2013 Flame Safeguard Fault Code Diagnostics As manager of Tech Services, it probably comes as no surprise I spend some time discussing fault codes and corresponding corrective

More information

Honeywell Primary Control Cross Reference

Honeywell Primary Control Cross Reference Honeywell Primary Control Cross Reference Page Pages, Page, Page Page Page Pages 9, 0 Page Pages, Page Pages, Page Page Pages 9,0 R, R0, R, R90B, RA90B, R90C, R, R90B RA90B, R90C, RA90C, RA90XB,XC, RA90D

More information

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies HVAC Products

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies HVAC Products ISO 900 LOA2... LOA... Oil Burner Controls LOA2... LOA... Oil burner controls for the supervision, startup and control of single- or 2-stage forced draft oil burners in intermittent operation. Oil throughput

More information

Dual Column Dehydrating Breather Manual

Dual Column Dehydrating Breather Manual Dual Column Dehydrating Breather Manual DCB-MANUAL 1.6 Read and understand this manual prior to operating or servicing the products. SPX Transformer Solutions, Inc., Service & Components Division U.S.

More information

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products Distribuitor: FLAME POWER SRL 021-3121727 ; 0744-340566 contact@arzatoare.ro ; www.arzatoare.ro 7 128 Oil Burner Control LOA44.252A27 Oil burner control for the supervision, startup and control of 1- or

More information

EW 40 Wireless Fan Control

EW 40 Wireless Fan Control Installation & Operating Manual EW 40 Wireless Fan Control USA CAN Product Information... Chapters 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration...

More information

24 VAC Intermittent Pilot Gas Ignition Control

24 VAC Intermittent Pilot Gas Ignition Control C610U Universal 24 VAC Intermittent Pilot Gas Ignition Control Issue Date: 08/24/2016 Quick Reference Guide The C610U Universal Intermittent Pilot Gas Ignition Control module replaces many popular flame

More information

RM7897A,C 7800 SERIES Relay Modules

RM7897A,C 7800 SERIES Relay Modules RM7897A,C 7800 SERIES Relay Modules INSTALLATION INSTRUCTIONS APPLICATION The RM7897A,C are microprocessor-based integrated burner controls for automatically fired gas, oil, or combination fuel single

More information

Forced draught gas burner

Forced draught gas burner Installation, use and maintenance instructions Forced draught gas burner Code Model Type 3751982 GAS 3 519T80 291 (3) - 02/2010 DECLARATION Declaration of conformity in accordance with ISO / IEC 17050-1

More information

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02 7 783 ISO 9001 DETACTOGYR Flame Safeguard Series 02 The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil

More information

50M56U-843 INSTALLER MUST READ DESCRIPTION PRECAUTIONS WARNING CAUTION

50M56U-843 INSTALLER MUST READ DESCRIPTION PRECAUTIONS WARNING CAUTION 50M56U-843 Universal Single Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS INSTALLER MUST READ PAGE 3 CONTAINS WIRING HARNESS AND BLOWER CONNECTION INSTRUCTIONS FOR ALL APPLICATIONS

More information

7800 SERIES EC7810A, EC7820A Relay Module

7800 SERIES EC7810A, EC7820A Relay Module 7800 SERIES EC780A, EC780A Relay Module PRODUCT DATA GENERAL The Honeywell EC780A or EC780A Relay Module is a microprocessor based integrated burner control for automatically fired gas, oil, or combination

More information

FIREYE NXF4000 ADVANCED BURNER MANAGEMENT SYSTEM with INTERNAL FLAME SAFEGUARD

FIREYE NXF4000 ADVANCED BURNER MANAGEMENT SYSTEM with INTERNAL FLAME SAFEGUARD BURNER MANANGEMENT SYSTEM NXF4000-SPEC AUGUST 5 2017 PRODUCT GUIDE SPECIFICATION FIREYE NXF4000 ADVANCED BURNER MANAGEMENT SYSTEM with INTERNAL FLAME SAFEGUARD GENERAL OVERVIEW 1.1.1. Each burner shall

More information

R7910A SOLA (Hydronic Control) and R7911 SOLA (Steam Control) Systems

R7910A SOLA (Hydronic Control) and R7911 SOLA (Steam Control) Systems R7910A SOLA (Hydronic Control) and R7911 SOLA (Steam Control) Systems INSTALLATION INSTRUCTIONS APPLICATION The R7910 SOLA hydronic boiler and the R7911 SOLA steam control systems provide heat control,

More information

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System. The Fireye EP260, EP270 (early spark termination), or EP265 (pilot stabilization) programmer modules are used with the FLAME-MONITOR Burner Management Control System (P/N E110). Several operational characteristics

More information

Eclipse Trilogy Flame Safeguards

Eclipse Trilogy Flame Safeguards Instruction Manual 835 11/11/2014 Eclipse Trilogy Flame Safeguards T600 Series Version 2 Copyright Copyright 2012 by Eclipse, Inc. All rights reserved worldwide. This publication is protected by federal

More information

Specification , July 2015

Specification , July 2015 Technical Information PrecisionLine Controllers EDC21 / EDC22 / EDC23 EASYSET DIGITAL CONTROLLERS Specification 51-52-3-48, July 215 Introduction The EDC21, EDC22 and EDC23 controllers provide precise

More information

Process Alarm Module RTA 421

Process Alarm Module RTA 421 Technical Information TI 074R/24/ae Process Alarm Module RTA 421 Alarm module and power supply for monitoring current or voltage signals Application Areas Plant and machine construction Panel builders

More information

A-1106 ACCESSORY KIT INSTALLATION INSTRUCTIONS IGNITION CONTROL P/N S , S , S

A-1106 ACCESSORY KIT INSTALLATION INSTRUCTIONS IGNITION CONTROL P/N S , S , S ACCESSORY KIT INSTALLATI INSTRUCTIS IGNITI CTROL P/N S1-33101972200, S1-37326083000, S1-43101972100 FOR USE WITH THE FOLLOWING FURNACE MODELS: GY9, GF9, GM9, P1UK, PAKU, P2MP, P2MPV, P9MP, P2UR, PBLU,

More information

LAE10 LFE10. Use. Series 02

LAE10 LFE10. Use. Series 02 ISO 00 Flame Safeguards 7 7 LAE L Series 02 Supplementary data sheets 772 and 773 Flame safeguards for burners with intermittent operation. For safety reasons - self-test of flame supervision circuit,

More information

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc. MODEL 3200-Plus Temp Limit / LWCO Control with Thermal Targeting for Water Boilers 120 VAC Input / 24 VAC Burner Circuit PATENT. 8,931,708; 8,844,834; 7,891,572; others pending INSTALLATION INSTRUCTIONS

More information

DIGITAL INDICATOR JIR-301-M

DIGITAL INDICATOR JIR-301-M DIGITAL INDICATOR JIR-301-M Instruction Manual Preface Thank you for purchasing our digital indicator JIR-301-M. This manual contains instructions for the mounting, functions, operations and notes when

More information

TEMPERATURE CONTROLLER

TEMPERATURE CONTROLLER TEMPERATURE CONTROLLER E5CX(-H) DIN-sized super-compact (48 x 48-mm) Temperature Controller Featuring Advanced PID Control Advanced PID control with two degrees of freedom improves stability and response

More information

7800 SERIES EC7890A,B; RM7890A,B,C Relay Module

7800 SERIES EC7890A,B; RM7890A,B,C Relay Module 7800 SERIES EC7890A,B; RM7890A,B,C Relay Module SPECIFICATION DATA EC7890 APPLICATION RM7890 The Honeywell EC7890A,B/RM7890 is a microprocessor based integrated burner control for automatically fired gas,

More information

Single stage operation oil burner

Single stage operation oil burner Installation & Operating Manual Single stage operation oil burner WARNING NON-RETROFIT APPLICATIONS If this burner is being installed in a packaged unit (ie. burner comes with a boiler or furnace), follow

More information

SLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071

SLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071 SLATE UV Ampli-Check Flame Amplifier R8001S1071 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform.

More information

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR 7 783 DETACTOGYR Flame Safeguard The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil or gas burners or

More information

MBCE-110/230FR Flame Sensor Module

MBCE-110/230FR Flame Sensor Module MBCE-1001 FEBRAURY 6, 2017 MBCE-110/230FR Flame Sensor Module exida FMEDA SIL2 SEE NOTE 1 ON PAGE 4 DESCRIPTION The MBCE-110/230FR modules provide visual indication and electrical outputs that signal the

More information

RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES Relay Modules

RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES Relay Modules RM79A,B,C,D/EC79A,C; RM796A,B,C,D 700 SERIES Relay Modules INSTALLATION INSTRUCTIONS APPLICATION The RM79A,B,C,D/EC79A,C; RM796A,B,C,D are microprocessor-based integrated burner controls for automatically

More information