P.C. Simonton & Associates, Inc. Consulting Engineers. Paul C. Simonton

Size: px
Start display at page:

Download "P.C. Simonton & Associates, Inc. Consulting Engineers. Paul C. Simonton"

Transcription

1 P.C. Simonton & Associates, Inc. Consulting Engineers 309 North Main Street 1050 Parkside Commons Post Office Box 649 Suite 101 Hinesville, Georgia Greensboro, Georgia Addendum No. One Date: November 7, 2018 Project: Pre-Packaged Fire Pump Skid City of Hinesville PCS No Engineer: P.C. Simonton & Associates, Inc. Greensboro, Georgia The original plans, specifications, and bid documents are amended to include the following: Specifications: Replace the previous Section with the enclosed Section Paul C. Simonton END- Hinesville, Georgia Phone: (912) Fax (912) Greensboro, Georgia Phone: (706) Fax (706)

2 SECTION PRE-PACKAGED FIRE PUMP SKID PART 1 - GENERAL 1.01 SCOPE A. This specification covers the manufacturing and supplying 1 (qty.) packaged fire pump system including a vertical inline fire pump complete with motor, vertical inline electric fire pump, controller(s), ATS, jockey pump, jockey pump controller, tank recirculation pump and control, and all other accessories as outlined and/or shown on drawing. The equipment supplier shall provide for the contractor to install a pre-packaged fire pump system, designed in accordance with the requirements of N.F.P.A. Pamphlet #20. The fire pump shall be listed by Underwriters Laboratories and/or approved by Factory Mutual for fire pump service at the specified rating. The system manufacturer will assume unit responsibility for the proper operation of the entire packaged system as specified herein. The system packager should be the original equipment manufacturer of the UL listed and FM approved fire pump(s) used on equipment skid. Should potential bidders choose to use a packager that is not the OEM of UL listed and FM approved fires pumps, prior approval is required and must be presented with bid. B. The Fire Pump Skid manufacturer shall have a quality management system in place and shall be ISO 9001 Certified. C. Skid size shall not exceed 11 L x 5 W and shall include all items listed above as part of the system. D. Suction / Discharge connection shall be made through the floor of the proposed bldg. enclosure DESIGN A. Fire Pump shall be designed to deliver 750 GPM when operating against a TDH of 161 ft. The pump shall also deliver not less than 150% of rated capacity at a pressure not less than 65% of rated head. The pump shut off head shall not exceed 140% of the rated head PART 2 - PRODUCTS 2.01 ELECTRIC DRIVEN FIRE PUMP A. The vertical in-line pump shall have a rated capacity of 750 GPM when operating against at 70 psi. The pump shall also deliver not less than 150% of rated capacity at a pressure not less than 65% of rated pressure. Motor and pump speed shall not exceed 3575 RPM. Unit provided under provision NFPA-20, 2007, paragraph #1-5. Unit pressure shut-off head shall not exceed 140% of rated pressure. 1. The pump(s) shall be listed by Underwriters Laboratories (UL). The unit shall meet all the requirements outlined in National Fire Protection Association Pamphlet /

3 and shall be a Patterson Series VIP or A-C Fire Pump Series 1580 comparable and shall be 6" X 6" skid with system to meet all of the following requirements, or approved equal. 2. The pump(s) shall be constructed so that the rotating elements and motor can be removed without disturbing the piping fittings, and shall be of the back pull-out type and design. The suction and discharge flanges shall be on the same center line plain, 180 degrees apart. 3. Rotation shall be CW (clockwise) when viewed from the driver end. The casing shall be radially split with suitable connections supplied for gauges, priming, venting, and draining. The suction and discharge flanges shall be 125 lbs. ASA standard. 4. The pump shall be hydrostatically tested to 1.5 times the maximum working pressure or 250 psi minimum. The stuffing box shall be designed for long packing life. A water seal (lantern) ring shall be located near the center of the stuffing box. 5. Sealing water injection shall be through a precision drilled passage in the volute cover to the seal ring, eliminating external lines. The stuffing box gland shall exert uniform pressure on the packing. A replaceable shaft sleeve shall be locked into position by the impeller key. The impeller shall be precision cast machined and balanced for optimum pump life. 6. The pump casting shall be smooth, free of scale, lumps, cracks, sand holes and defects of any nature which may make it unfit for the use for which it is intended. The pump shall have an integrally cast easily accessible clean-out port located at the bottom of the casing. 7. The bolting of pressure-holding castings shall be such that the maximum stress on any bolt will not exceed one-fourth the elastic limit of the material as computed by using the stress area and on the basis of the water pressure equivalent to the shutoff pressure effective over the area out of the center line of the bolts. 8. The pump bearings shall have a L-10 rating of not less than 5000 hours based on load ratings and fatigue life ELECTRIC MOTOR A. The shall be 100 HP motor maximum and shall be a 286JPV, open drip-proof, ball bearing, squirrel cage, induction motor. B. The motor shall be designed for 3-phase, 60-cycle, 208 volts operation with a 1.15 service factor. The motor shall be close coupled and is an integral part of the pump ELECTRIC FIRE PUMP CONTROLLER A. The fire pump controller shall be Firetrol Mark IIXG Electric Fire Pump Controller, or equal, designed and built strictly in accordance with the latest requirements of the National Fire Protection Association's Pamphlet No. 20. B. The main fire pump controller with integrated transfer switch shall be factory assembled, wired and tested as a single unit with reduced voltage solid state starter, /

4 NEMA contactor bypass. It shall be listed and approved for fire protection service by Underwriters Laboratories and Factory Mutual Research. C. The controller short circuit current rating shall be 100,000 RMS symmetrical amps. D. The enclosure shall be floor mounted and shall not exceed 64 inches in height, 24 inches in width, or 13 inches in depth. All enclosure doors shall be equipped with safety mechanical interlocks to prevent all doors from being opened until the isolating switch is opened. E. The controller shall be provided in a dust-tight, NEMA 12 enclosure with a driphood. The finish shall be a baked on fire engine red paint. F. The Isolating Switch and Circuit Breaker shall be vertically mounted to separate any incoming line terminals from any circuit breaker terminals by at least 12 inches, no exception. The Isolating Switch and Circuit breaker shall each be provided with an operating handle. They shall be interlocked so the Isolating switch cannot be opened until the Circuit Breaker is opened. G. The controller shall utilize a pressure transducer based digital pressure switch. It shall have start and reset settings that can be set to the nearest 1.0 psi. These settings shall be readable through the door. H. All transducers, pressure switches, and all related pressurized wet parts shall all be mounted externally to the side of the controller, no exception. They shall also be mechanically protected from damage, no exception. No water pressure connection of any kind shall be provided inside the controller enclosure. I. The controller shall be rated to operate in a 50C ambient environment. J. All printed circuit boards shall be conformal coated to operate in a high humidity environment where the humidity is 95% and non-condensing. K. The control unit shall be comprised of a control board enclosed in a protective metal chassis, no exceptions. All plug-in cables shall be securely latched or locked in place. Insulation displacement connectors are not acceptable. L. Control power shall be 24 VDC and shall be derived from 3 independent, control power transformers with redundant isolated rectifier circuits. M. The controller shall have a dielectric strength of 5000 Vac for increased immunity to voltage surges. N. Power for the circuit breaker DC shunt trip solenoid shall be derived from any of the three transformers and shall be completely independent of any one single phase A.C. voltage. O. 30 mm mechanical start and stop pushbuttons shall be mounted on the door flange. They shall start and stop the pump independent of the HMI. P. An input shall be provided for a normally closed remote start contact. Q. A separate input shall be provided for a normally closed deluge valve start contact /

5 R. A test valve solenoid shall be provided on the outside of the enclosure to facilitate local pressure drop testing or auto testing. It shall include a y-strainer to protect the valve from debris. S. Anytime the test valve is operated, either through the local pressure drop test button or through the auto testing function, the transducer shall be tested. If the pressure reads greater than 10 psi while the valve is open, a Transducer/DVS failure alarm shall activate. If the transducer is disconnected, the pump shall start. T. A Failure to Start alarm shall provide an alarm when motor current is not measured within 15 seconds of the pump start demand signal. U. Motor Overload logic shall provide an alarm when motor current exceeds 120% of the motor s full load rated current. It shall not shutdown the pump. V. Precise Low Voltage logic shall provide an alarm when any phase to phase voltage is less than 85% of the controller rated voltage. W. PhaseSmart logic shall be provided to assure that the controller will not start the fire pump under single phase conditions when the voltage on any phase is lower than 65% of the rated motor voltage. However, if the motor is already running when a phase loss occurs, the Phase Smart logic shall keep the motor running. X. A Human Machine Interface (HMI) shall be provided to set up the controller and display the status but shall not be relied on for the controller operation. The accuracy of the display shall be 2 percent or 2 digits and shall be traceable to the National Institute of Standards and Technology. Y. The starting and running functions controller shall operate independently of the HMI and shall even operate with the HMI damaged or disconnected. Z. The HMI shall be a 5.7 inch, 64 K color touch screen interface that simultaneous displays all 3 phase voltages and currents, the System Pressure, Start/Reset settings, Manual/Auto Stop setting, and the Weekly/Monthly test setting. It shall also display the starting sequence and pump running status. AA. In addition, the HMI shall be capable of enabling or disabling remote or deluge start, auto testing, minimum run timing, setting sequence timing, and acceleration timing. BB. Further, it shall display the following alarms: AC Volts Low, AC Failure, CB Trip, Fail to Start, Load Shed, Lockout, Low Discharge Pressure, On Demand, Motor Overload, Over Pressure, Phase Reversal, PhaseSmart, 8 Pump House Trouble inputs, Pump Run, Single Phase Running, and Transducer Failure. CC. A password protected Setup Assistant screen is provided to quickly access the pressure start/reset settings, the sequence, accelerate time settings, the remote/deluge start settings, and the weekly/monthly test settings. DD. A Setup summary screen accessible to anyone is available to view all the controller settings. EE. A Remote alarm contact testing screen shall be provided to operate each remote alarm contact individually to facilitate remote alarm testing /

6 FF. The Alarm Silence shall be provided with a 24 hour auto re-sounding function. GG. The internal Data Recorder shall download directly through an external USB waterproof adapter to a USB drive. No codes, settings, or menu operations shall be required. Once the USB is inserted, the data recorder shall recognize the USB drive and indicate USB Active. The file shall then be automatically transferred and indicate USB OK. The USB drive can then be removed. HH. The Data Recorder shall record the system pressure every hour or every time the pressure changes by 5 psi. It shall also record all 3 phase voltages and currents on every alarm event and every 5% change from the previous reading. In addition, all active alarms and the starting sequence shall be recorded. II. Voltage Free Remote Contacts shall be provided for Pump Running (2 sets), AC Failure, Phase Reversal, System Trouble, and On Demand. JJ. Additionally, 8 programmable inputs and 8 programmable relay outputs shall be provided for any of the displayed alarms. The Voltage Free Contacts shall be rated for 6 amps at 30 vdc, 6 amps at 250 vac and have a UL pilot duty ratings of R300 and B300. KK. For building automation systems and site monitoring, an additional waterproof adapter shall be provided for external Ethernet access with the Modbus TCP/IP protocol. LL. It is intended that the manufacturer of the specified equipment shall be a business regularly engaged in the manufacture, assembly, construction, start up, and maintenance of fire pump controllers. The manufacturer shall have at least three (3) years of successful experience in providing this equipment. MM. The manufacturer's published warranty certificate for the entire controller shall be submitted to show that it covers parts and labor for a period of 2 years and parts for a period of 5 years. In addition, a guarantee shall be provided to cover parts damaged by transient voltage surges, including lightning, up to a maximum of $5,000 for a period of 5 years. NN. Certified factory test data shall be provided, if requested, to verify that the following tests have been performed: 1) A complete visual inspection; 2) A complete operational test; 3) A plumbing leakage test done at the maximum system pressure; 4) A pressure transducer accuracy test; 5) A 5000 volt dielectric voltage withstand test; and 6) A power path voltage drop test. OO. The controller shall be manufactured in the United States of America /

7 JOCKEY PUMP A. The jockey pump shall be a GRUNDFOS CR Series or A-C Fire Pump brand, centrifugal close-coupled vertical inline pump with mechanical seal, cast iron suction and discharge flanges, with stainless steel intervals or suitable equivalent. B. Designed for PSI 3450 RPM 1.5 HP, 3 Phase, 60 Cycle, 208 Volt operation JOCKEY CONTROLLER A. The jockey pump controller shall be a UL Approved Jockey Pump Controller complete with fusible disconnect, "HANDOFF-AUTOMATIC" selector switch and a pressure switch. The minimum enclosure rating shall be NEMA Type 2, drip tight. B. Controller shall have the following options, 1. Restart Time Delay 2. Running Period Timer PART 3 - INSTALLATION 3.01 FACTORY PREFABRICATION A. All of the above equipment (except the test header, hose valves, and muffler) shall be mounted on an open structural steel I-beam skid. All piping, pressure sensing lines, bypass with check valve, and shut-off valves, as well as approved suction and discharge valves shall be firmly anchored to the steel base by means of structural steel supports. All electrical wiring between controllers and drivers shall be completed and tested at the factory. The entire package will require one power connection by the electrical contractor. THE FIRE PUMP SYSTEM PACKAGER MUST BE AN ORIGINAL EQUIPMENT MANUFACTURER OF UL LISTED AND FM APPROVED, NFPA 20 FIRE PUMP 3.02 FACTORY TEST A. All equipment will be factory tested in accordance with the requirements of N.F.P.A., U.L., and F.M. Additionally, the entire package system will be hydrostatically tested by the system manufacturer prior to shipment SUBMITTAL DATA A. The submittal data for the pumping system shall include, but not limited to: pump curves, individual computer data sheets, system drawings, and complete description of control panel, with wiring diagram, sequencing data, instrumentation, alarms, and copy of certificate of $1,000, minimum liability insurance /

8 3.04 GUARANTEE A. The Pre-Packaged fire pumping system shall be guaranteed in writing by the manufacturer for a period of one year from date of shipment against defect in design, material, or construction. In addition to paragraph 2.03 Section MM FIELD ACCEPTANCE TEST AND START-UP SERVICE A. The service of a factory trained representative shall be made available on the jobsite to check installation, field acceptance testing, start-up, and instruct operating personnel. B. In order to ensure the fire pump unit is properly coordinated and will function in accordance with the intent of these specifications, all the equipment required to comprise the fire pump unit will be supplied by the fire pump manufacturer in whom shall be vested unit responsibility for the proper function of the complete fire pump unit, including the fire pump, motor or engine, base plate, control equipment and other required accessories(when applicable prepack fire pump package systems including fire pump skid and/or housed units). C. To verify compliance with this requirement of the fire pump manufacturer will be required to submit a notarized Certificate of Compliance certifying that all components of the fire pump unit were in fact supplied by the fire pump manufacturer and acknowledging its responsibility for the proper function of the unit INSTALLATION OF PRE-PACKAGED PUMP SKID A. Place, assemble, install and place into operational readiness complete pumping system and building as specified in this section, in accordance with Pre-Packaged Pump manufacturer recommendations, Drawings, FM and NFPA 20. B. FIELD QUALITY CONTROL 1. Manufacturer s field representative shall supervise installation of all items and equipment as specified in this section 2. Manufacturer s field representative and/or Contractor shall inspect job site conditions 72 hours before shipment of packaged pump module to assure field conditions compatible with system layout. 3. Manufacturer s field representative shall conduct and document acceptance tests and startup of equipment specified in this section and shall ensure conformance to acceptance requirements of NFPA 20 and FM Data Sheet 3-7N/13-4N. 4. Manufacturer s representative shall instruct Owners personnel in proper system operation and maintenance /

9 5. Manufacturer s representative shall commission equipment and certify to Owner in writing that all installation, maintenance instruction, tests, adjustments, repairs and startup are complete and that all components are ready for continuous operation /

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps Note: The A/E must choose all design values in brackets below before using in project specifications 1 General 1.1 Provide UL listed and FM approved fire pump complete with pump, driver, controller and

More information

SECTION FIRE PUMP AND CONTROLS

SECTION FIRE PUMP AND CONTROLS SECTION 15320 FIRE PUMP AND CONTROLS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Fire pump, jockey pump, and controls including necessary accessories as shown in Construction Documents, specified

More information

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL SECTION 21 30 00 FIRE PROTECTION PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00,

More information

SECTION Fire Pumps

SECTION Fire Pumps SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.

More information

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps. Issued 2006/08/01 Section 13920 Packaged Fire Pumps and Controllers Page 1 of 7 PART 1 GENERAL 1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

SECTION PACKAGED HEAT TRANSFER SYSTEM

SECTION PACKAGED HEAT TRANSFER SYSTEM PACKAGED HEAT TRANSFER SYSTEM Page 1 of 6 SECTION PACKAGED HEAT TRANSFER SYSTEM 1 GENERAL 1.1 SUMMARY A. Packaged steam-to-water heat transfer system 1.2 REFERENCES A. ASHRAE American Society of Heating,

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES SECTION 21 30 00 FIRE PUMPS GENERAL This standard provides general requirements of The University of South Alabama in Mobile Alabama for fire pumps. This document is not intended to serve as a guide specification.

More information

Soft Start Series MP700 Solid State, Reduced Voltage

Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s

More information

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU with Automatic Power Transfer Switch Contents: NOTE: The drawings included in this package are for controllers covered under our standard

More information

SECTION FIRE PUMPS 1.00 PART 1 & GENERAL Description of Work. A. Provide pumps for fire suppression Section Includes

SECTION FIRE PUMPS 1.00 PART 1 & GENERAL Description of Work. A. Provide pumps for fire suppression Section Includes SECTION 210200 Formatted 1.00 PART 1 & GENERAL 1.01 Description of Work A. Provide pumps for fire suppression. 1.02 Section Includes A. Single Stage, Double Suction, 8100 Series Horizontal Splitcase Fire

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

Drawing Submittal Package

Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch

More information

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model

More information

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass Project: Customer: Engineer: Pump Manufacturer: Submittal Document Model VPS Pressure Limiting (VFD) with Soft Start Bypass Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections Note:

More information

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE SBP1000-61 FTA1000 Full Voltage Starting Electric Fire Pump Controllers Product Description Description Firetrol FTA1000 Full Voltage Fire Pump Controllers

More information

Drawing Submittal Package

Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch

More information

SECTION PLUMBING EQUIPMENT Piping (Plumbing). 2. Division 16 - Electrical Wiring and Connections.

SECTION PLUMBING EQUIPMENT Piping (Plumbing). 2. Division 16 - Electrical Wiring and Connections. SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15410 - Piping (Plumbing). 2. Division 16 - Electrical Wiring and Connections. 1.02 SUBMITTALS A. Submit properly identified

More information

Variable Frequency Drive SERIES MP800 VFD

Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controls and Accessories Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for

More information

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

FDF Foam Pump Controllers Features

FDF Foam Pump Controllers Features FDF100 Diesel Engine Foam Pump Controllers 1-1 Product Description The FDF Series of Foam Pump Controllers are designed for use with foam concentrate injection, foam transfer and water mist systems for

More information

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS SECTION 23 22 23 - STEAM CONDENSATE PUMPS PART I - GENERAL 1.1 SECTION INCLUDES A. Steam Condensate Return Units, Gravity Return Type 1. Receiver 2. Pumps 3. Control Panel 4. Accessories Note to PSC: Although

More information

SECTION HEATING BOILER FEEDWATER EQUIPMENT

SECTION HEATING BOILER FEEDWATER EQUIPMENT SECTION 23 53 00 HEATING BOILER FEEDWATER EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes boiler feedwater pumps, de-aerators, accessories, controls and tanks. 1.2 REFERENCES A. ASME (American

More information

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Specification General The Powerex Laboratory Scroll Enclosed Air Compressor System is designed to provide clean, dry air for

More information

Model VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch

Model VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model VPS + VPU Pressure Limiting (VFD) with Soft Start Bypass with Automatic Transfer Switch Contents: Data Sheets Dimensional

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

SECTION DOMESTIC WATER PUMPS

SECTION DOMESTIC WATER PUMPS SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,

More information

DualPak Series FILE NO: DATE: Feb. 15, 1999 SUPERSEDES: DATE: Sept. 28, DualPak 6900 Series Booster System

DualPak Series FILE NO: DATE: Feb. 15, 1999 SUPERSEDES: DATE: Sept. 28, DualPak 6900 Series Booster System DualPak Series 6900 FILE NO: 62.11 DATE: Feb. 15, 1999 SUPERSEDES: 62.11 DATE: Sept. 28, 1995 DualPak 6900 Series Booster System D U A L P A K 6 9 0 0 Armstrong proudly presents the Series 6900 DualPak

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps...

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps... PUMPS FOR INDUSTRY CONTENTS: The Vertical Pump Specialists Introduction & User List Product Overview Vertical Process Pumps... Series 600 Vertical Sewage Pumps... Series 700 Vertical Sump Pumps... Series

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

SECTION ELECTRIC-DRIVEN, FIRE PUMPS

SECTION ELECTRIC-DRIVEN, FIRE PUMPS SECTION 21 30 13 ELECTRIC-DRIVEN, FIRE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between // --- // if not applicable to the project. Also delete any other item or paragraph including

More information

SERIES 1600 Quality Design Features Assure Long, Trouble-Free Service

SERIES 1600 Quality Design Features Assure Long, Trouble-Free Service Vortex End Suction SERIES 1600 Quality Design Features Assure Long, Trouble-Free Service WIDE RANGE OF APPLICATIONS: Food Processing Solids Waste Water Treatment Pollution Control Slurries Industrial Process

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to define the general installation and minimum product

More information

Mission Critical. Fuel Supply Systems

Mission Critical. Fuel Supply Systems Fuel Supply Systems Insight Onsite Fuel Supply Systems Page 2 Simplex Mission Critical Fuel Supply Systems are comprehensive, integrated, project-matched fuel management systems for diesel and turbine

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features September 007 DIESEL Engine Fire Pump Controllers Features FD0 Diesel Engine Controllers 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller.

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional

More information

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals. SECTION 23 21 23 - HYDRONIC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Pipe and Pipe Fittings. B. Air compressor. C. Air receiver and accessories. D. Aftercooler. E. Refrigerated air dryer. F. Pressure reducing station. 1.02 RELATED

More information

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016 SECTION 23 21 23 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section.

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

LMR Electric Fire Pump Controllers Features

LMR Electric Fire Pump Controllers Features 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps...

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps... PUMPS FOR INDUSTRY CONTENTS: The Vertical Pump Specialists Introduction & User List Product Overview Vertical Process Pumps... Series 600 Vertical Sewage Pumps... Series 700 Vertical Sump Pumps... Series

More information

Technical Data Submittal Document

Technical Data Submittal Document Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPL + GLU Limted Service Full Voltage Across the Line Start Electric Fire Pump Controller Contents: Data Sheets Dimensional

More information

LMR Electric Fire Pump Controllers Features

LMR Electric Fire Pump Controllers Features 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status

More information

Transfer Switch Features

Transfer Switch Features 1-1 Product Description The Automatic Transfer Switch Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer

More information

SECTION CHILLERS

SECTION CHILLERS SECTION 15650 PART I - GENERAL 1.01 WORK INCLUDED A. Extent of work shall be as indicated on Drawings and provisions of this section, including schedules and equipment lists associated with either Drawings

More information

.2 Section Waste Management and Disposal..5 Section Motors, Drives and Guards for Mechanical Systems.

.2 Section Waste Management and Disposal..5 Section Motors, Drives and Guards for Mechanical Systems. Issued 2006/08/01 Section 15131 Pumps Hydronic Systems Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal.3 Section 01780

More information

HHA Lyerly Apartments 75 Lyerly Houston, Texas J. Allen Management Managing Agent

HHA Lyerly Apartments 75 Lyerly Houston, Texas J. Allen Management Managing Agent HHA Lyerly Apartments 75 Lyerly Houston, Texas 77022 J. Allen Management Managing Agent Scope of Work: 1.) Boiler Replacement with Double Vertical Boiler System (1 Million btu each) 2.) Water Pump Replacement

More information

30 F to 300 F Process Temperatures* 1/2 to 7.5 HP Centrifugal Pumps ( GPM) 3/8-1 Solenoid Cooling Valves (VE & 300 F models)

30 F to 300 F Process Temperatures* 1/2 to 7.5 HP Centrifugal Pumps ( GPM) 3/8-1 Solenoid Cooling Valves (VE & 300 F models) Temperature Control Units Water & Oil - 00 F Portable Chillers Air & Water-Cooled 0-70 F Central Chillers Air & Water-Cooled Packages & Modules 0-70 F Pump Tank Stations Chilled or Tower Water 00-00 gallons

More information

PUMP CONTROL CENTER (PCC)

PUMP CONTROL CENTER (PCC) PART 1 SUMMARY A. In accordance with the plans and specifications, the Contractor shall provide and install a complete pre-fabricated, pre-tested ArcSafe Pump Control Center including all required equipment,

More information

Transfer Switch Features

Transfer Switch Features 1-1 Product Description The Automatic Transfer Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer and

More information

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials. B B11.0 DIVISION 08 - OPENINGS SECTION 08 17 00 INTEGRATED DOOR OPENING ASSEMBLIES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

HHA Bellerive Apartments 7225 Bellerive Houston, Texas J. Allen Management Managing Agent

HHA Bellerive Apartments 7225 Bellerive Houston, Texas J. Allen Management Managing Agent HHA Bellerive Apartments 7225 Bellerive Houston, Texas 77036 J. Allen Management Managing Agent Scope of Work: 1.) Water Heater Replacement with Vertical Boiler System 2.) Water Conditioning System (Softener)

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

TECHNICAL. Series 18. Pump Packages

TECHNICAL. Series 18. Pump Packages TECHNICAL S Y S T E M S Series 18 Pump Packages Series 18 Pump Packages Standard Features Close-coupled, end-suction, centrifugal pumps Mounted and wired pump starters Hand-Off-Auto switch for each pump

More information

SECTION WASTEWATER PUMPING STATION DESCRIPTION

SECTION WASTEWATER PUMPING STATION DESCRIPTION SECTION 33 3200 WASTEWATER PUMPING STATION DESCRIPTION The contractor shall furnish and install one submersible sewage lift station with concrete wet well and valve vault, pumps, 4 piping and valves, and

More information

B. Section Transfer Switches: Automatic transfer switch.

B. Section Transfer Switches: Automatic transfer switch. SECTION 263213 - ENGINE GENERATORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Packaged engine generator set. B. Exhaust silencer and fittings. C. Remote control panel. D. Battery and charger. E. Weatherproof

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP DS series Industrial End Suction Pumps ISO/DP 5199 www.sterlingpumps.com.au DS series Capacities from: Heads from: 340 to 5,680 m3/h (1,500 to 25,000 USPGM) 21 to 106 metres (70 to 350 feet) Power range

More information

A. Product Data: Include rated capacities, furnished specialties and accessories.

A. Product Data: Include rated capacities, furnished specialties and accessories. BASE BID: SECTION 15542 FUEL-FIRED RADIANT HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install a Co-Ray-Vac Low Intensity Vented Infrared Radiant Vacuum Gas Heating System. System must be certified

More information

Full-line Product Overview

Full-line Product Overview Full-line Product Overview End Suction Centrifugal Pumps This general purpose pump can be configured in frame-mounted and close-coupled, semi-open and enclosed impeller configurations. They are available

More information

Casey Craft

Casey Craft SmartWash Locomotive Wash Whiting Systems, Inc. 9000 Highway 5 North Alexander, Arkansas 72002 800-542-9031 501-847-0074 fax Casey Craft cc@rmsi.net 1 Whiting Systems, Inc. 9000 Highway 5 North Alexander,

More information

CITY OF MEXICO BEACH REQUEST FOR QUOTES: LIFT STATION PANELS REPLACEMENT

CITY OF MEXICO BEACH REQUEST FOR QUOTES: LIFT STATION PANELS REPLACEMENT CITY OF MEXICO BEACH REQUEST FOR QUOTES: LIFT STATION PANELS REPLACEMENT The City of Mexico Beach is requesting quotes for replacement of 18 lift station control panels. The lift stations range from 2

More information

Ruhrpumpen Fire Systems

Ruhrpumpen Fire Systems FIRE SYSTEMS RP FIRE SYSTEMS Ruhrpumpen Fire Systems Fire pumps play a vital role as the first response to a fire situation, saving countless lives and property from destruction. They are usually found

More information

FTA550 JOCKEY PUMP CONTROLLERS

FTA550 JOCKEY PUMP CONTROLLERS FTA550 JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP550E (A) FTA550E XG Jockey Pump Controllers Product Description Failed to start indication Main switch not in Auto alarm Pressure recording

More information

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

WET AUTOMATIC FIRE SPRINKLER SYSTEMS SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,

More information

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming.

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming. SECTION 260943 SPECIFICATIONS - Wireless Network Lighting Controls. PART 1 - GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY AND KEY SYSTEM DIFFERENTIATORS A. The lighting control system specified herein shall

More information

MASTER DIESEL FIRE PUMP CONTROLLER

MASTER DIESEL FIRE PUMP CONTROLLER MASTER DIESEL FIRE PUMP CONTROLLER Model - DEC Innovation G4 INSTRUCTION MANUAL C 2013 Master Control Systems, Inc MASTER - Diesel Fire Pump Controller TABLE OF CONTENTS Important Safety Information. Page

More information

DUPLEX CONDENSATE TANK SYSTEM

DUPLEX CONDENSATE TANK SYSTEM DUPLEX CONDENSATE TANK SYSTEM PROJECT NAME: 7 EAST 54TH STREET CONTRACTOR: PRO PUMP CORP ENGINEER: KEVAN WOODWORTH SUBMITTED BY: NISSIM ISAACSON DATE: 2.20.205 DESIGN DATA Model GPM TDH HP Volt Phase RPM

More information

FUEL OIL DAY TANKS. SST Level Controller: UL 508 LISTED

FUEL OIL DAY TANKS. SST Level Controller: UL 508 LISTED FUEL OIL DAY TANKS SST Series - Engineering Submittal SST Series - Advanced Line Day Tanks Construction: UL 142 aboveground steel tank all seam welded, square, atmospheric tank of heavy gauge steel with

More information

FD30 Full Voltage - Across the Line July 2011

FD30 Full Voltage - Across the Line July 2011 Must Be Installed Per Applicable Code and Manufacturers Recommendations Electric Fire Pump Controllers Features 1-1 FD30 Full Voltage - Across the Line July 2011 Power I/O Board Transformers Incoming line

More information

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR SECTION 08 71 13 LOW ENERGY AUTOMATIC OPERATORS Specifier Note: Coordinate and edit articles

More information

DIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers

DIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers DIESEL Engine Fire Pump Controllers Features FD120 Diesel Engine Controllers 1-1 March 2013 Diesel Product Description The DIESEL Plus Fire Pump Controllers from Eaton Corporation are designed to control

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS SECTION 23 22 23 STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable in the

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15684 ROTARY SCREW WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236423 An optional

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

3020/3120 Series DEMING PUMPS. Frame-mounted and close-coupled Enclosded and semi-enclosed impeller Capacities to 4,000 GPM Heads to 780 feet

3020/3120 Series DEMING PUMPS. Frame-mounted and close-coupled Enclosded and semi-enclosed impeller Capacities to 4,000 GPM Heads to 780 feet 3020/3120 Series Frame-mounted and close-coupled Enclosded and semi-enclosed impeller Capacities to 4,000 GPM Heads to 780 feet A Crane Co. Company DEMING PUMPS Introducting Deming 3020/3120 Series End-Suction

More information

Moss MOSS TRAY DEAERATOR ECONOMICAL INDUSTRIAL DEAERATOR SYSTEMS

Moss MOSS TRAY DEAERATOR ECONOMICAL INDUSTRIAL DEAERATOR SYSTEMS Moss MOSS TRAY DEAERATOR ECONOMICAL INDUSTRIAL DEAERATOR SYSTEMS MOSS TRAY DEAERATOR DESIGNS WHY DEAERATE? Removal of corrosive oxygen and carbon dioxide from boiler feedwater Reduction in the use of oxygen

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

Laboratory Open Scroll Air Compressor System with Premium NFPA Controls

Laboratory Open Scroll Air Compressor System with Premium NFPA Controls Laboratory Open Scroll Air Compressor System with Premium NFPA Controls Specification General The Powerex Laboratory Open Scroll Air Compressor System is designed to provide clean, dry air for applications

More information

FT60 Reduced Voltage - Autotransformer

FT60 Reduced Voltage - Autotransformer 1-1 Product Description The Automatic Transfer Switch Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer

More information

Customer Connection Terminals Connection terminals for external customer connections, are located at the top of the Power I/O board.

Customer Connection Terminals Connection terminals for external customer connections, are located at the top of the Power I/O board. Must Be Installed Per Applicable Code and Manufacturers Recommendations Electric Fire Pump Controllers Features 1-1 FD80 Reduced Voltage - Wye Delta (Star-Delta) Closed Transition Power I/O Board Transformers

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S.

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. NAME OF TENDER: CONSTRUCT, DELIVER AND COMMISSION 3 (THREE) LIFT STATION ELECTRICAL LOCATION OF WORK: 3 Separate work sites in

More information

SENTRA Series Water Unit

SENTRA Series Water Unit SENTRA Series Water Unit Standard Unit: F to 0 F Process Fluid Temperatures* Optional High Temperature Configuration to 0 F Direct Injection Cooling 0 to kw Heaters to 7. HP Centrifugal Pumps (0-00 GPM)

More information