PLATTEVILLE MIDDLE SCHOOL

Size: px
Start display at page:

Download "PLATTEVILLE MIDDLE SCHOOL"

Transcription

1 Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle School was originally built in The original building was remodeled in 1997 along with a major addition which added the commons area, the IMC and several new classrooms. The Technology classroom, Art room and the Vocals room were all remodeled in The current band room was remodeled in The school is located at 40 E. Madison Street. It has approximately 112,347 square feet and sets on 11.9 acres of land. There is an outdoor play area to the northwest corner of the building and two large parking lots to the south and southwest. Bus drop off is along 2 nd Street with students entering the eastern entry near the gymnasium, thru doors E2. See photo 1 Photo 2-Awning Type Aluminum Windows The main entry doors, S3 are located to the south of the building, facing the parent drop off area. See photo 3. There is also a pair of doors, S4 facing south from the east corridor. See photo 4. Both sets of exterior doors are painted hollow metal and are showing some signs of rust and should be repaired and painted or replaced as a priority 3 renovation. See photo 5. Photo 1-Student Entry Along 2nd Street. The main school district offices are located within the middle school. They currently occupy rooms 132 thru 135. The middle school main office is located along the south side of the building between entry doors S2 and S3. The occupants of the school office must rely on security cameras to see the student entry at doors E2 and the parent drop off doors, S3. The main school office area seemed difficult to find when we entered the building through S3 doors. The relationship between the main entry and the school offices should be reviewed for better options and security reasons. This should be reviewed as a priority 1 renovation. Photo 3-Main entry is located along the right side of the student drop off area. Existing Facilities Survey Page 45

2 Photo 4-Doors S4 Photo 7-Exterior play area to northwest of the existing building. There are several areas where the caulking in the masonry joints needs to be replaced. These are primarily where the new additions were built next to the existing building. This work should be done as priority 2 repair work. See photos 8, 9 and 10. Photo 5-Hollow metal doors are showing signs of rust and should be repaired and painted or replaced. The outdoor play are to the northwest appears to be in good shape. See photos 6 and 7. Photo 8-Exterior caulking needs to be replaced. Photo 6-Current outdoor play area to the northwest of the building. Photo 9-Exterior flashing/caulking needing repair. Page 46 Existing Facilities Survey

3 Photo 10-Exterior caulking needs to be replaced. The existing roof was snow covered during our visit so no inspection was performed. The student entry, at doors E2 have an aluminum framed vestibule which provides an air lock to the interior of the building. The landing distance between the top riser of the terrazzo steps and the actual aluminum doors does not appear to meet the current code for stair landing widths and should be investigated and corrected as a priority 1 renovation. See photo 11. Photo 12-There are areas where the existing VCT flooring is damaged due to movement in the concrete slab. During our walkthrough we noticed that several of the existing toilet rooms do not meet the current ADA/ANSI code for accessibility. These restrooms should be renovated to meet the current codes as priority 1 renovations. See photos 13, 14 and 15. Photo 13-The current toilet partitions do not provide the proper clearances to meet ANSI requirements. Photo 11-Aluminum framed vestibule at entry doors E2. There are several areas where the existing VCT flooring is showing damage due to movement in the concrete slab below. These areas should be repaired as priority 3 repairs. See photo 12. Photo 14-Existing toilet partitions do not meet current ANSI requirements. Existing Facilities Survey Page 47

4 There are several areas where the ceiling tiles are showing signs of humid damage and should be replaced as a priority 3 renovation. See photo 18. Photo 15-ANSI requires proper clearances on the latch sides of doors leading to and from corridors. The entry doors to and from some of the restrooms do not meet this requirement. There are several locations where the existing wood doors and frames have been damaged. These should be repaired or replaced as priority 3 repairs. See photos 16 and 17. Photo 18-There are several areas where the existing ceiling tile is sagging & shows damage. The wood floor and ceramic tile walls in the gymnasium have visible signs of wear, movement and damage. The flooring and tile should be repaired or replaced and as a priority 3 renovation. See photos 19 and 20. Photo 16-Existing wood doors have been damaged & need to be repaired or replaced. Photo 19-Wood flooring & wall damage needs to be repaired or replaced. Photo 17-Existing wood doors and frames have been damaged & should be replaced or repaired. Page 48 Existing Facilities Survey

5 Photo 20-Wood flooring in the gymnasium needs to be repaired or replaced. Photo 22-The terrazzo steps and flooring in the east gymnasium entry are in need of repair. There are several areas within the older section of the building where walls and doors have been damaged. These repairs could be done as priority 3 repairs. See photo 21. Photo 23, The east entry terrazzo flooring should be repaired. Photo 21-There are numerous areas in the older section of the building that are in need of wall and door repairs. The lockers in the older section of the building could be replaced or repaired and painted as an upgrade to this area. This work should be considered as a priority 3 renovation. See photo 24. The terrazzo flooring and steps in the east entry to the gymnasium area are showing signs of damage and cracking. This repair work should be considered as a priority 3 repair. See photos 22 and 23. Photo 24-The existing lockers in the older portion of the building have some minor damage. Existing Facilities Survey Page 49

6 The existing band room appears to have damaged ceiling tiles, below average lighting levels and a general need for repairs, painting and increased storage. This work should be considered as a priority 3 renovation. See photos 25, 26 and 27. Heating, Ventilating and Air Conditioning Systems Heating: The facility s unit ventilators, terminal equipment and reheat are served by a primary-secondary pumping system and three Patterson-Kelley hot water boilers installed in Expected Useful Life (based on ASHRAE published data): Boilers: years Terminal Equipment: years Unit ventilators: years Pumps: years Photo 25-Band Room The pumps, terminal equipment and associated piping and accessories are at or nearing the end of their useful life and should be considered for replacement. The boilers appear to be in good working condition and have approximately 10 years remaining in their useful life. Photo 26-Band Room Photo 28-Existing Boilers Cooling is provided by packaged DX rooftop units. Refer to Ventilation/Overhead Air section for additional information. Photo 27-Band Room A majority of the building s ventilation and overhead air is provided through packaged DX rooftop air handling units. A majority of the units were installed in 1998 except the Trane unit serving the band area and the Carrier unit serving D Section. Air is distributed to reheat coils and then distributed to spaces. The gym is served by two heating only indoor air handling units, only one of which is functional. Page 50 Existing Facilities Survey

7 Expected Useful Life (based on ASHRAE published data): Packaged rooftop air handling units: years Indoor air handling units: years Unit ventilators: years The air-handling units are approaching the end of their useful life and should be considered for replacement. Plumbing System There are two gas fired water heaters located in the main mechanical room to serve the building and two gas fired water heaters located near the kitchen to serve the kitchen, all were installed in All water to the building is softened. The water softener was installed in 1998 along with the remainder of the plumbing equipment. Plumbing fixtures throughout the building are original. Expected Useful Life (based on ASHRAE published data): Water Heater: years Water Softener: years The water softener and water heaters are in good working condition but are nearing the end of their useful lives and should be considered for replacement. The plumbing fixtures installed as part of the original building appear to be at the end of their useful life. Photo 29-Existing Building & Kitchen Water Heaters Photo 30-Existing Building & Kitchen Water Heaters Fire Protection System None existing. If renovations are pursued, the addition of fire protection should be considered. Electrical Systems General lighting in the building consists of fluorescent 2x4 acrylic troffers and surface direct fixtures in corridors, office spaces and classrooms, fluorescent in utility spaces, and miscellaneous specialty/decorative lighting in some spaces. Some of the specialty lighting and stage lighting is incandescent. It appears that most classrooms and offices have multi-level switching installed. All fixtures are in working condition, but a few older fixtures are nearing the end of their useful life. Light levels throughout the building appear to meet IES recommendations for this type of building. Lighting control consists of wall switches and occupancy sensors in a few areas such as the library, corridors and stairways. Although the corridors have automatic control via occupancy sensors, current energy code has requirements for turning lights off automatically in most office and classroom spaces that are not met in this building. The angled corridors north of the IMC do not have proper exit sign coverage. The elevator machine room does not have an emergency light fixture provided; this is a safety concern. Outdoor lighting consists of building mounted and pole mounted light fixtures controlled via photocell and time clock. Existing Facilities Survey Page 51

8 Expected Useful Life Remaining: Newer lighting: 10+ years Older lighting: 5+ years Exterior lighting: 5+ years Replace fixtures that are near the end of their useful life. Replace incandescent lighting with LED can lights and review stage lighting for possible alternative lamping. Add automatic lighting control via occupancy sensors to spaces required by energy code. moderate condition. The kitchen is well maintained and has the majority of the code requirements met, including a hood suppression system. However, the equipment under the hood is currently not served by shunt-trip breakers, which is a code violation. Many of the receptacles in areas where janitor mop basins are located are not GFCI protected, which is a code violation. One classroom appeared to previously have a kitchen with particular kitchen equipment that would require an exhaust hood with fire protection as mentioned above. Although the range is currently removed, the power receptacle remains, so a code official could interpret this as a kitchen, and therefore could require fire protection requirements to be met in this classroom. A simple solution would be to remove the receptacle and circuit entirely from the classroom. Expected Useful Life Remaining: Pit equipment: Past useful life. Original building panels: Past useful life. Other equipment: 25+ years Photo 31-Exterior Building Mounted HID Lamp Power Distribution: The building is fed with a 480V, 3 phase, 1200A electrical service from an outdoor utility owned transformer. The service is fed into an existing Square-D switchboard in the lower level boiler room. This gear is in good condition and has spare capacity. However, the current service entrance also back-feeds the original building service entrance in a room below the lower level boiler room accessible only by a ladder. The original service equipment located in this pit area is not in good condition and should be removed. It is recommended to remove all equipment from the pit for multiple reasons, accessibility, maintenance, and equipment past its useful life. The majority of the rest of the electrical equipment is neatly labeled and appears to be in good working condition with some spare breaker capacity for future panels. However, utility demand values should be studied prior to any upgrades or additions to the system. The majority of the electrical branch panels are still in good working condition with the exception of approximately 10 branch panels that are original to the building. These panels are damaged and will be difficult to get service parts for in the future. Electrical receptacles and connections appear to be in Keep existing electrical equipment in place until a complete renovation occurs. If a complete remodel is not in the near future, then an upgrade to the older buildingoriginal panels is recommended to replace outdated, difficult-to-service equipment. Replace receptacles near sinks with GFCI receptacles. Photo 32-Pit Electrical Equipment Page 52 Existing Facilities Survey

9 The building does not have emergency power. Emergency lighting is accomplished from emergency battery packs throughout the building. Most of these appear to be in good condition. Expected Useful Life: Battery wall pack lighting has a typical life-span of 5 to 7 years for a battery. The lighting heads will last longer as long as the batteries are replaced. Keep up maintenance of battery back-up lighting, add some battery ballasts to provide additional egress lighting as necessary to meet code requirements. It is not code required but a building of this size and use could be costeffective to have a generator. It is recommended to install an emergency generator, transfer switch, and branch panel to feed emergency lighting and the fire alarm panel, access control and security. The fire alarm system is served by a Simplex 4020 hornstrobe addressable system. The fire alarm system generally consists of some smoke detection, pull stations at exits, and notification throughout the building. Some of the fire alarm has been installed using surface mounted conduit due to remodeling. Approximately 15% of notification coverage is lacking to meet code requirements. Expected Useful Life Remaining: 20+ years Photo 34-Existing Fire alarm Annunciator Existing integrated Paging and Clock system is a Rauland multi-zone two-way paging and communication system with speakers and located throughout corridors and public areas, speakers and call stations in classrooms, and a control panel and microphone at the reception desk. Clocks are located throughout corridors and public areas, and in classrooms; some clocks are stand-alone clocks. Many of the stand-alone clocks are not equipped with any provision for automatic synchronization, either with each other or with an external master time signal (such as GPS). Other than the stand-alone clocks that have no provision for synchronization, the system seems to be in fair general condition and functioning as intended. Update all clocks to a district-wide synchronized clock system. Continue to maintain the fire alarm system regularly. When renovations occur, verify smoke detection and notification coverage meets current code standards and upgrade only as necessary. Add an LCD annunciator at the main fire department entrance point. Photo 33-Simplex 4020 Panel with Notification Extender Panels Existing Facilities Survey Page 53

10 Priority 1 Recommendations Recommended upgrades/replacements in the near future due to life safety, code compliance, or security. 1. Review main entry and the school offices for better options for security reasons. 2. Upgrade toilet rooms to meet the ANSI requirements for ADA accessibility 3. Upgrade door hardware to meet current ADA and accessibility guidelines. 4. Correct width between the top riser of the terrazzo steps and the actual aluminum doors as it does not appear to meet the current code for stair landing widths at doors E2. Priority 2 Recommendations Recommended upgrades/replacements due to maintenance, energy, or end-of-life 12. Replace caulking in masonry joints between new addition and original building. 13. Replace 1998 or older DX rooftop units, boilers, pumps and corresponding piping and accessories. 14. Eliminate use of corridor as a return plenum by providing code compliant return and transfer ductwork. 15. Add emergency generator and power system. 16. Replace original building electrical panels. 5. Provide emergency gas shutoffs in boiler rooms. 6. Eliminate use of corridor as a return plenum by providing code compliant return and transfer ductwork. 7. Add shunt-trip breakers for kitchen equipment under the hood. 8. Provide GFCI receptacles within 6 of sinks and mop basins. 9. Add automatic shut-off via occupancy sensors. 10. Record video from video door entry stations via existing video surveillance system. 11. Review code required fire alarm notification locations and provide additional as needed. Page 54 Existing Facilities Survey

11 Priority 3 Recommendations Recommended infrastructure upgrades/replacements. 17. Repair or replace rusting hollow metal main entry doors S3 and S Repair or replace damaged VCT flooring due to movement in the concrete slab below. 19. Repair or replace damaged wood doors and frames. 20. Repair or replace damaged ceiling tiles. connectivity and quad-shielded RG-6 coaxial cabling for CATV distribution (quad-shielded RG-11 coaxial cabling for runs over 180 ft.). Install rack-mounted RJ- 45 patch panels for UTP cabling terminations. 31. Update fiber optic computer network backbone cabling to OM4 50-micron multimode fiber optic cable and/or OS2 singlemode fiber optic cable. 32. Update all clocks to a district-wide synchronized clock system. 21. Repair or replace damaged ceramic tile walls in the gymnasium. 22. Repair or replace damaged wood flooring in the gymnasium. 23. Repair damaged walls and doors in the older section of the building. 24. Repair or replace damaged and cracking terrazzo flooring and steps in the east entry to the gymnasium. 25. Repair, replace or paint lockers in the older section of the building as an upgrade in that area. 26. Band Room: Repair or replace damaged ceiling tiles. Upgrade below average lighting levels. General need for repairs and painting. Additional storage needed. 27. Replace reheat coils with variable air volume boxes to conserve energy and comply with current energy codes. 28. Upgrade any remaining old halogen, incandescent and fluorescent lighting indoors and outdoors to high performance fluorescent and LED. 29. Create dedicated Technology rooms to house structured cabling terminations, telephone and computer network active electronics and equipment; video surveillance and access control cabling terminations and active electronics and equipment; and clock and overhead paging system cabling terminations and active electronics and equipment. 30. Update structured cabling to include Category 6 UTP cabling for VoIP telephone and computer network Existing Facilities Survey Page 55

12 Page 56 Existing Facilities Survey

13 Existing Facilities Survey Page 57

14 Page 58 Existing Facilities Survey

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District HOLUM EDUCATION CENTER Architectural The existing building has approximately 41,823 square feet and sets on a lot about 4.14 acres in size. Parking lots are located along the east and west sides of the

More information

Facilities Master Planning

Facilities Master Planning Facilities Master Planning DeForest Area School District DeForest, WI PRA Project #130343-01 January 13, 2014 DRAFT Table of Contents DeForest Area School District PRA Project # 130217-01 Section 1 Existing

More information

Florence High School / Middle School Page 1 of 3 Florence, WI

Florence High School / Middle School Page 1 of 3 Florence, WI Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October

More information

2 Main Office Building BLDG-955A Building Purpose Building Area Administration offices. Training room 7,610 SF Inspection Date August 16, 2016 Inspect

2 Main Office Building BLDG-955A Building Purpose Building Area Administration offices. Training room 7,610 SF Inspection Date August 16, 2016 Inspect 1 Site Summary Address 7200 Bluff Springs Road Austin, TX 78744 Number of Permanent Campus Facilities 2 Original Year of Construction 2014 Total Campus Building Area (combined) 25,314 SF Introduction The

More information

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School MOUNT PLEASANT MIDDLE SCHOOL HVAC M-01 Heating Plant: The existing boilers have recently been upgraded. (3) steam boilers (8660 mbh each) manufactured by Weil- McLain have been installed. Newer hot water

More information

MUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY

MUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY ARCHITECTURE ROLLING HILLS ELEMENTARY SCHOOL Rolling Hills Elementary was built in 1999 and is the newest addition to the Mukwonago Area School District. The building contains approximately 64,900 gross

More information

S AGE E NGINEERING A SSOCIATES, LLP

S AGE E NGINEERING A SSOCIATES, LLP S AGE E NGINEERING A SSOCIATES, LLP 1211 Western Avenue Albany, NY (518) 453 6091 F (518) 453 6092 Kingston Library Mechanical and Electrical Systems Field Report Date of Visits: Mechanical - September

More information

Appendix B. Facilities Assessment Report

Appendix B. Facilities Assessment Report Mile Lane Army Reserve Center Redevelopment Plan September 2008 Appendix B Facilities Assessment Report RKG Associates, Inc. Mile Lane Army Reserve Base Middletown, CT MEP System Evaluation For RKG Associates

More information

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Facility Condition Assessment Summary Report British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Submitted by: VFA Canada Corp. Burnaby Centre 4211 Kingsway Burnaby, BC V5H 1Z6

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL DISTRIBUTION SYSTEM:?? The existing electrical service consists of an underground primary service originating at a utility pole on Cedar Street,

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. The present fire alarm system manufactured by Gamewell was installed with the 1982 renovation. It is a non addressable, zoned system. It includes

More information

VOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED

VOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED Ashton Elementary School 1 Masonry Repair $ 42,781.50 2 Replace HVAC $ 375,000.00 3 Replace SAT @ Various Locations $ 92,364.00 3 Recoat & Resurface Exterior Paved Play Area $ 135,978.30 3 Various Technological

More information

MARY CRAPO CENTER Miller Road, Swartz Creek, Michigan

MARY CRAPO CENTER Miller Road, Swartz Creek, Michigan MARY CRAPO CENTER 8197 Miller Road, Swartz Creek, Michigan MARY CRAPO CENTER 8197 Miller Road, Swartz Creek General Information: - Instructional, Child Care Development Center (West Wing) o (2) Infant/Toddler

More information

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

Currently, all electrical upgrades would be voluntary, but there are situations in which upgrades would be required.

Currently, all electrical upgrades would be voluntary, but there are situations in which upgrades would be required. Executive Summary The current electrical system is functional but requires some understanding in order to avoid overloading circuits. Certain outlets can be used for space heaters while others cannot and

More information

MUKWONAGO SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY

MUKWONAGO SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY MUKWONAGO SCHOOL DISTRICT ARCHITECTURE PARK VIEW MIDDLE SCHOOL The original school building was dedicated in 1954 as the High School, with an addition in 1959, a library addition in 1970, and an addition/renovation

More information

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN September 30, 2015 PBA Project No. 2015.0140.00 PETER BASSO ASSOCIATES INC. CONSULTING ENGINEERS 5145 LIVERNOIS ROAD,

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 16 - BROOKLYN, 157 WILSON STREET, New York, 11211 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-30

More information

Ashland School District Facility & Capacity Assessment Report 2005

Ashland School District Facility & Capacity Assessment Report 2005 Ashland School District Facility & Capacity Assessment Report 2005 Briscoe Elementary School (Closed Facility) Address: 265 N Main Street Area: 33,980 square feet Buildings: Original Building 1948 Music

More information

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1 Page 1 TABLE OF CONTENTS 1 ELECTRICAL 2 Summary Sustainability Electrical Distribution Lighting Detection and Alarm Communication Systems Lightning Protection Clock Systems Access Control Housekeeping

More information

NORTH CENTRAL MICHIGAN COLLEGE PETOSKEY CAMPUS. Facilities Conditions Assessment Mechanical And Electrical Petoskey, Michigan

NORTH CENTRAL MICHIGAN COLLEGE PETOSKEY CAMPUS. Facilities Conditions Assessment Mechanical And Electrical Petoskey, Michigan NORTH CENTRAL MICHIGAN COLLEGE PETOSKEY CAMPUS Facilities Conditions Assessment Mechanical And Electrical Petoskey, Michigan PBA Project No. 2014.0137.00 Prepared By: Wayne Kerbelis Terry Cleis September

More information

2015 Building Condition Survey Summary Mosaic Associates Architects 02/19/16

2015 Building Condition Survey Summary Mosaic Associates Architects 02/19/16 1. General: This summary is offered as a supplement to the 2015 Building Condition Survey being filed with SED on behalf of the District. All cost estimates are preliminary, and should be re-evaluated

More information

CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN

CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN 04.13.2017 1 MONTICELLO INTERIOR FINISHES PAINT MOULDING WALLS ACCENT DOORS DOOR TRIM/STAIRS

More information

Sprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS

Sprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS EXISTING MECHANICAL CONDITIONS SUMMARY The items listed below are based on our site visit on Nov 10, 2016. Our review is based on current conditions and anticipated future use of these building. In the

More information

PLAN REVIEW SUBMITTAL GUIDE

PLAN REVIEW SUBMITTAL GUIDE PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide

More information

Facility Improvements

Facility Improvements AP-SI-03 BICYCLE RACK ADDITION AP-SI-05 EXTERIOR BENCH ADDITIONS Installation of bike rack will allow for designated and secure storage of bicycles. Installation of exterior benches will provide an outdoor

More information

DRAFT. Widen Elementary School Site Summary 74,523 SF. Introduction

DRAFT. Widen Elementary School Site Summary 74,523 SF. Introduction 1 Widen Elementary School Site Summary Address 5605 Nuckols Crossing Austin, TX 78744 Number of Permanent Campus Facilities 2 Original Year of Construction 1986 Total Campus Building Area (combined) 74,523

More information

New High School Concept

New High School Concept Approved Bond Projects for Alamance-Burlington Schools In November 2018, Alamance County citizens approved a $150 million bond project proposal. Bond funds will pay to construct a new high school and provide

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES 2.07 ELECTRICAL GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.07 It is expected that the electrical design professional will conform to accepted good engineering design practices.

More information

Siemens Building Technology MEP Existing Conditions

Siemens Building Technology MEP Existing Conditions Electrical Existing Conditions Report Executive Summary: The electrical systems for the are generally of the original vintage. The site is primary metered with the meter located in the main Electric Room.

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 174 - QUEENS, 65-10 DIETERLE CRESCENT, New York, 11374 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-01-25

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. Description of the building system The school is equipped with a hard wired fire alarm control panel, and automatic dialer. The fire alarm

More information

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15 ELECTRICAL DESIGN CRITERIA TABLE OF CONTENTS I GENERAL...2 II CRITERIA...2 A. POWER DISTRIBUTION SYSTEMS...2 1. NORMAL POWER:...2 2. EMERGENCY POWER...3 B. LIGHTING...4 1. GENERAL...4 2. AVERAGE MAINTAINED

More information

Chariho Regional School District Five-Year Capital Facilities Improvement Plan (2/10/15)

Chariho Regional School District Five-Year Capital Facilities Improvement Plan (2/10/15) Chariho Regional School District Five-Year Capital Facilities Improvement Plan (2/10/15) School/Department FY 16 FY 17 FY18 FY19 FY20 Chariho Regional High School FY 16 FY 17 FY18 FY19 FY20 *Repair Bleachers

More information

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 No. Discipline Sent to Name Item Date Noted Date Resolved How item was resolved SCO # 1Punch listed items were noted below on

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 56 - STATEN ISLAND, 250 KRAMER AVE., New York, 10309 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-20

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: I.S. 260 - MANHATTAN, 425 WEST 33RD STREET, New York, 10001 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-16

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 131 - QUEENS, 170-45 84TH AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-18

More information

SPACE TYPE: JUDICIAL CHAMBER

SPACE TYPE: JUDICIAL CHAMBER SPACE TYPE: JUDICIAL CHAMBER Construction Criteria The unit costs for Judicial Chamber space types are based on the construction quality and design features in the following table. This information has

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 135 - QUEENS, 207-11 89TH AVENUE, New York, 11427 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20

More information

Joseph Brennemann Elementary School

Joseph Brennemann Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Appendix E: Photo Documentation

Appendix E: Photo Documentation Appendix E: Photo Documentation Brown County Library Central Branch Building Assessment Appendix E: Photo Documentation Architectural and Structural Brown County Library Central Branch Building Assessment

More information

2014 Bond Project Guide

2014 Bond Project Guide 2014 Bond Project Guide Bush Elementary School Page 1 Instructional Technology Computers, Projectors, Mobile Carts, Document Cameras and Printers Wireless Connectivity New Construction New Tech Center

More information

Related Sections: TBD. Effective Date: January 1, 2016

Related Sections: TBD. Effective Date: January 1, 2016 Description: The purpose of the section is to highlight the current applicable UMCP Design Standards for the design, selection and, installation of lighting fixtures within buildings. Related Sections:

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: HS OF AMERICAN STUDIES - BRONX, 2925 GOULDEN AVENUE, New York, 10468 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

F. GENERAL REQUIREMENTS Electrical Design Criteria 2009 Edition 11/23/2009 School District Palm Beach County Page-1 of 17

F. GENERAL REQUIREMENTS Electrical Design Criteria 2009 Edition 11/23/2009 School District Palm Beach County Page-1 of 17 ELECTRICAL DESIGN CRITERIA TABLE OF CONTENTS I GENERAL...2 II CRITERIA...2 A. POWER DISTRIBUTION SYSTEMS...2 1. NORMAL POWER:... 2 2. EMERGENCY POWER... 3 B. LIGHTING...4 1. GENERAL... 4 2. AVERAGE MAINTAINED

More information

Briar Crest Elementary

Briar Crest Elementary Promises Kept This document includes partial lists of major projects completed at Pattonville Schools since 1986 as part of past bond issues approved by the Pattonville community. Briar Crest Elementary

More information

Genevieve Melody Elementary School

Genevieve Melody Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: PS 152 ANNEX -BROOKLYN, 1087 OCEAN AVENUE, New York, 11210 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20

More information

3. 21st Century Learning A. Districtwide Flexible Learning - Allowance for Flexible Furniture $600,000 Subtotal $600,000

3. 21st Century Learning A. Districtwide Flexible Learning - Allowance for Flexible Furniture $600,000 Subtotal $600,000 1. Safety and Security A. Additional Cameras District Wide $382,000 B. Interior Locks Upgrades Allowance $300,000 C. Tilden Entrance Upgrades D. Door and Glass Improvements Allowance $500,000 E. Alert

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: NEW SCH FOR ARTS AND SCIENCE - X, 965 LONGWOOD AVENUE, New York, 10459 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-01 8:13 AM 2017-12-01

More information

DEERFIELD SCHOOL DISTRICT REFERENDUM Committed to Excellence and Equity in Educating Our Students

DEERFIELD SCHOOL DISTRICT REFERENDUM Committed to Excellence and Equity in Educating Our Students DEERFIELD SCHOOL DISTRICT REFERENDUM Committed to Excellence and Equity in Educating Our Students FACILITY NEEDS THE CHALLENGE Deerfield Middle School/High School building has served the community for

More information

CAPITAL OUTLAY REQUEST - IDENTIFIED AND EMERGING PROJECTS - RANKED 3-Jun-14

CAPITAL OUTLAY REQUEST - IDENTIFIED AND EMERGING PROJECTS - RANKED 3-Jun-14 2014-2015 CAPITAL OUTLAY REQUEST - IDENTIFIED AND EMERGING PROJECTS - RANKED 3-Jun-14 School Item Amount a. Classroom A/R (Increase CR capacity to 804, add l Resource and tutoring spaces needed. Teacher

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 314 - BROOKLYN, 330 59 STREET, New York, 11220 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-23

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

Calmeca Academy of Fine Arts and Dual Language

Calmeca Academy of Fine Arts and Dual Language Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Francis M McKay Elementary School

Francis M McKay Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010

An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010 An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010 Putnam County Planning & Development Services Building & Zoning Division Compliance Section PO Box 1486 Palatka, FL 32178 1486 Office

More information

Master Facility Planning Update School Board Meeting May 26, 2016

Master Facility Planning Update School Board Meeting May 26, 2016 Master Facility Planning Update School Board Meeting May 26, 2016 Master Facilities Committee Overview Reflection of Committee Work Review of District Wide Facility Issues Identified District Wide Facility

More information

Telecommunications Survey

Telecommunications Survey Victor Valley College Telecommunications Survey Victor Valley College 18422 Bear Valley Road Victorville, CA 92395 November 30, 2010 Submitted by P2S Engineering, Inc. Executive Summary Background and

More information

Greenwood Elementary School 5550 South Holly Street Greenwood Village, Colorado 80111

Greenwood Elementary School 5550 South Holly Street Greenwood Village, Colorado 80111 Greenwood Elementary School 5550 South Holly Street Greenwood Village, Colorado 80111 Year Opened 1958 Current Square Footage 50,504 Site Acreage 8.53 greenwood.cherrycreekschools.org $220,720 Electrical

More information

HVAC / Boilers / Hot Water. Expected Life Span. very rough estimates Condition/Issue Age. Athletics / Gyms

HVAC / Boilers / Hot Water. Expected Life Span. very rough estimates Condition/Issue Age. Athletics / Gyms $4,013,500.00 $4,013,500.00 $ 1,155,000.00 $ 1,000,000.00 $ 205,000.00 $ 275,000.00 $ 300,000.00 $ 360,000.00 $ 438,500.00 $ 280,000.00 School Status Item HS Boilers boiler controls replaced 2017 2002

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 310 - BRONX, 260 WEST KINGSBRIDGE RD, New York, 10463 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-07

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 152 - MANHATTAN, 93 NAGLE AVENUE, New York, 10040 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-05

More information

Springpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp.

Springpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp. Volume 1 Bidding Requirements, Contract Forms, Conditions of the Contract, Division 1, Architectural and Site Specifications 000107 Certification Page 000110 Table of Contents DIV00 PROCUREMENT AND CONTRACTING

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 5 - BROOKLYN, 820 HANCOCK STREET, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-25 8:54 AM 2018-06-04 10:18 AM Asset Data Type of Service Does Interactive

More information

NYC Department of Education

NYC Department of Education Asset: LEARNING SUPPORT CENTER - K, 1665 ST. MARKS AVENUE, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-07 1:06 PM 2018-05-10 12:20 PM Asset Data Type of Service

More information

ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING

ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING Mechanical Systems Information The mechanical system at Reed Middle School is comprised of seventy six Trane DX/Gas rooftop units (RTUs). The recommended useful life for DX equipment is 15 years. Seventy

More information

Alessandro Volta Elementary School

Alessandro Volta Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Electrical Inspection Lighting & Power

Electrical Inspection Lighting & Power 0921 Light Fixtures & Controls Fixtures, controls, conduit, wiring, etc. Interior classroom and corridor lighting consists of T12 fluorescent lamps with magnetic ballasts. In the classrooms the luminaires

More information

Preliminary Study Document. Horicon. Horicon, Wisconsin

Preliminary Study Document. Horicon. Horicon, Wisconsin Preliminary Study Document Horicon School District Horicon, Wisconsin Monday table of contents i 1 2 Introduction Section One: Van Brunt Elementary School a. Building Evolution b. Existing Site Plan c.

More information

Edward Jenner Elementary Academy of the Arts

Edward Jenner Elementary Academy of the Arts Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

ALLISON ELEMENTARY SCHOOL 4315 Don Julio Blvd., North Highlands, CA 95660

ALLISON ELEMENTARY SCHOOL 4315 Don Julio Blvd., North Highlands, CA 95660 ALLISON ELEMENTARY SCHOOL 4315 Don Julio Blvd., North Highlands, CA 95660 Year Built 1960 // Age 58 years Building Area 31,688 Square Feet Student Capacity 389 Current Enrollment (2017-2018) 466 Priority

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 371 (OLD 615) - BROOKLYN, 355 37 STREET, New York, 11232 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-23

More information

School District of Milton 5- Year Capital Maintenance and Improvement Plan

School District of Milton 5- Year Capital Maintenance and Improvement Plan Updated - 02/21/17 School District of Milton 5- Year Capital Maintenance and Improvement Plan 101 East Elementary 1 Parking Lot/Traffic Flow Project 615,175 Includes Construction and Engineering 2 Bathroom

More information

RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan

RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan ADDENDUM NO. 2 RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan TO: All Bidders Gentlemen: You are hereby directed to make the following changes in the Project Manual and/or

More information

Josefa Ortiz De Dominguez Elementary School

Josefa Ortiz De Dominguez Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: HS FOR MATH, SCI & ENGINEERING-M, 240 CONVENT AVENUE, New York, 10031 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-20 11:37 AM 2018-01-09

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton RCSSD #7 Bishop Savaryn Catholic Elementary School B58A Edmonton Report run on: July 10, 2008 3:31 PM Building Name: Address: Location: Building Id: Gross Area

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 90 MINISCHOOL - BRONX, 1116 SHERIDAN AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

Meadow Point Elementary School East Grand Avenue Aurora, Colorado 80015

Meadow Point Elementary School East Grand Avenue Aurora, Colorado 80015 Meadow Point Elementary School 17901 East Grand Avenue Aurora, Colorado 80015 Year Opened 1982 Current Square Footage 53,100 Site Acreage 7.48 meadowpoint.cherrycreekschools.org $2,081,600 Electrical system,

More information

Forest Hills Facilities Plan

Forest Hills Facilities Plan Forest Hills Facilities Plan Extensive updates to 8 of our 9 schools Replace Wilson Elementary Enhance learning environments across the district Build additional classrooms to accommodate gradual implementation

More information

Richard Henry Lee Elementary School

Richard Henry Lee Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 127 - BROOKLYN, 7805 7 AVENUE, New York, 11209 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-30

More information

Agustin Lara Elementary Academy

Agustin Lara Elementary Academy Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

John Palmer Elementary School

John Palmer Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Massachusetts School Building Authority

Massachusetts School Building Authority Massachusetts School Building Authority School District Revere District Contact Paul Dakin TEL: (781) 286-8226 Name of School Submission Date 3/6/2007 The following Priorities have been included in the

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Lakeland Roman Catholic Separate School District No. 1 Ecole Notre Dame High School B266A Bonnyville Report run on: January 26, 2 : PM Bonnyville - Ecole Notre Dame High

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 69 PORTABLE - QUEENS, 77-02 37TH AVENUE, New York, 11372 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-24 8:36 AM 2018-05-16

More information

Page 1 of General

Page 1 of General Page 1 of 8 16.1 General 1. This section covers items common to sections of CSI s Master Format - Division 16. 2. Dalhousie University is certified by IBEW for new construction and all electrical contractors

More information

Mechanical Inspection Plumbing

Mechanical Inspection Plumbing 0811 Fixtures Sinks, drinking fountains, water closets, showers, etc. Classroom Sinks. Classroom sinks (19) are enameled cast iron self rimming side ledge with gooseneck faucet trim with index handles,

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Oscar DePriest Elementary School

Oscar DePriest Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Bethlehem University 2008 Projects Summary

Bethlehem University 2008 Projects Summary 2008 Projects Summary 2008 Projects Summary In Addition to following up daily engineering related issues and supervising the Maintenance and Security Departments the University Engineer is involved in

More information

Electrical Inspection Service & Distribution

Electrical Inspection Service & Distribution 0911 Distribution Panels & Switchgear Equipment, conduit, feeders, and grounding 480 Volt Switchboard: This switchboard contains the utility meter and two main, service, circuit breakers. One circuit breaker

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: TERS PREP HS(OL REDIRECTION)-K, 226 BRISTOL STREET, New York, 11212 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

Attendees/Absentees. Derek Gallagher DG. Delano Secondary School Additions and Renovations June 6, 2016 Technology User Group Meeting Minutes

Attendees/Absentees. Derek Gallagher DG. Delano Secondary School Additions and Renovations June 6, 2016 Technology User Group Meeting Minutes MEMORANDUM To: From: Attendees/Absentees Derek Gallagher DG Date: June 14, 2016 Comm. No: 152235 Subject: Independent School District #879 Delano Secondary School Additions and Renovations June 6, 2016

More information