1 NYC Department of Education Building Assessment Survey Asset: P.S QUEENS, TH AVENUE, New York, Inspection Id Inspection Type Time In Last Edited EE : Electrical :35 AM :36 AM Asset Data Type of Service Does Interactive Whiteboard (IWB) Exist? Water Penetration in Electrical Room? Have any Systems/Major Building Components been upgraded? DEDICATED INTERCOMS IN FIRE RESCUE AREAS Are there any Life Rescue Assistance Areas, Fire Rescue Areas, and/or Holding Rooms in your building? Answer Below Ground Systems: Years: 2015 Systems: Years: 2013 Systems: Years: 2003 Systems: Years: 1997 Systems: Years: 1993 Telephone System Auditorium (Projection System, Local Sound System), Cafeteria (Local Sound System) Emergency Light/Exit Light Panel, Intrusion Alarm System, IPDVS/CCTV System Interior Public Address System, Most Molded Case Circuit Breaker Panel Board, Partial Security Lights, Fire Alarm System (Sub-Panel, Fan Shutdown Control, Duct Smoke a Detector, Area Smoke Detector, Heat Detector) Priority Priority Priority Exist Category Last Year? Description Component Affected Location Description Person(s) tified Person(s) Title Status PhotoImage Fire Alarm System - Defective Sub Panel for Strobes FIRE ALARM SYSTEM Sub-Panel Fire Alarm Control Panel (Electronic) ROBERT CANON Custodian Sent to DSF Water Penetration in Electrical Room N/A Electrical Equipment Electrical Room ROBERT CANON Custodian Sent to DSF Fire Alarm System - Components Missing N/A FIRE ALARM SYSTEM Tamper Flow Switch/Chain Room B24 ROBERT CANON Custodian Sent to DSF Fire Alarm System - Defective Sub Panel for Fan Shutdown Controls FIRE ALARM SYSTEM Sub-Panel Fire Alarm Control Panel (Electronic) ROBERT CANON Custodian Sent to DSF Inspection Electrical AUDITORIUM House PB/A&W Page 1 of 14

2 Building Assessment Survey AUDITORIUM House Does a Chandelier exist? Fixture - Fluorescent Fixture - HID LIGHTING FIXTURE BALLAST DEFECTIVE Quantity 1 REPLACE BALLAST Urgency of Action PRIORITY 3 Photo1 Fixture - Incandescent Fixture - LED Local Sound System Installation Year 2013 Custodial Staff 2 - Between Good and Fair Projection System Is the projector on a cart or installed on the ceiling? Ceiling 1 - Good Theater System Dimming System PB/A&W Page 2 of 14

3 Building Assessment Survey AUDITORIUM Theater System Dimming System Theater LIGHTING FIXTURE BEYOND USEFUL LIFE Quantity 48 REPLACE-UPGRADE Urgency of Action PRIORITY 1 Photo1 CAFETERIA Fixture - Fluorescent Fixture - HID Fixture - Incandescent Fixture - LED Local Sound System Installation Year 2013 Projection System Theater System CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE Custodial Staff 2 - Between Good and Fair PB/A&W Page 3 of 14

4 Building Assessment Survey CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE Does a Chandelier exist? Fixture - Fluorescent LIGHTING FIXTURE BALLAST DEFECTIVE Quantity 4 REPLACE BALLAST Urgency of Action PRIORITY 3 Photo1 LIGHTING FIXTURE BALLAST DEFECTIVE Quantity 2 REPLACE BALLAST Urgency of Action PRIORITY 3 Photo1 Fixture - HID Fixture - Incandescent Fixture - LED COMPUTER LAB Power Panel Fixture - Fluorescent Fixture - HID Fixture - Incandescent Fixture - LED PB/A&W Page 4 of 14

5 COMPUTER LAB Raceway With Receptacles GYMNASIUM KITCHEN Fixture - Fluorescent Fixture - HID Fixture - Incandescent Fixture - LED LIBRARY LOCKER ROOM MULTIPURPOSE ROOM SCIENCE DEMO ROOM SCIENCE LAB Power Panel Alternative use Fixture - Fluorescent Fixture - HID NYC Department of Education Building Assessment Survey PB/A&W Page 5 of 14

6 SCIENCE LAB Fixture - HID Fixture - Incandescent Fixture - LED Emergency Gas Shut-Off Valve Emergency Shut-Off Power Power Supply Projection System SCIENCE PREP ROOM A Power Panel Alternative use A Fixture - Fluorescent A A A A Fixture - HID A Fixture - Incandescent A Fixture - LED A Emergency Gas Shut-Off Valve A Emergency Shut-Off Power Power Supply A A SWIMMING POOL TOILET ROOM - STAFF Fixture - Fluorescent NYC Department of Education Building Assessment Survey PB/A&W Page 6 of 14

7 Building Assessment Survey TOILET ROOM - STAFF Fixture - Fluorescent Fixture - HID Fixture - Incandescent Fixture - LED TOILET ROOM - STUDENT Fixture - Fluorescent Fixture - HID Fixture - Incandescent Fixture - LED AUXILIARY SIGNAL/BELL SYSTEM Replacement Quantity 46,000 Replacement Uom EMERGENCY DC STANDBY BATTERY POWER EMERGENCY GENERATOR SET EMERGENCY LIGHT/EXIT LIGHT PANEL 2 - Between Good and Fair LESS THAN 20% SPARE CIRCUIT BREAKERS Location/Instance Quantity 1 INSTALL NEW PANEL BOARD Urgency of Action PRIORITY 5 Photo1 EMERGENCY LIGHTING Battery Pack n Battery Pack EXIT LIGHT PB/A&W Page 7 of 14

8 Building Assessment Survey EXIT LIGHT Battery Pack FIXTURE NOT OPERATIONAL Location/Instance Ground Floor by Stairway C Quantity 1 REPLACE Urgency of Action PRIORITY 5 Photo1 n Battery Pack Location/Instance Quantity 2 FIXTURE LAMP NOT OPERATIONAL MAINTENANCE Urgency of Action PRIORITY 5 Photo1 EXIT/EMERGENCY LIGHT CITY FIRE ALARM SYSTEM FIRE ALARM SYSTEM Replacement Quantity 46,000 Replacement Uom Bell/Horn Strobe Manual Pull Station Fan Shutdown Control Duct Smoke Detector Area Smoke Detector PB/A&W Page 8 of 14

9 Building Assessment Survey FIRE ALARM SYSTEM CO Detector Heat Detector Elevator Recall Magnetic Door Holder/Contactor Fused Cutout Panel Fire Alarm Digital Communicator Main Panel Bell At Panel Fire Alarm Control Panel (Electronic) Fire Alarm Control Panel (Standard) Instance Instance Instance Quantity 1 Instance Instance Manufacturer ACME Equipment Fire Alarm Control Board Capacity/Size Quantity 6 Capacity/Size UOM Circuits Source of Capacity/Size Inspector Estimate Installation Year 1960 Inspector Estimate BEYOND USEFUL LIFE Location/Instance Quantity 46,000 REPLACE Urgency of Action PRIORITY 1 Photo1 Sub-Panel Bell At Panel Fire Alarm Control Panel (Electronic) Instance Instance Instance Quantity 1 Instance Instance Manufacturer Equipment Model 4 - Between Fair and Poor Cerberus Pyrotronics Fire Alarm Control Panel PB/A&W Page 9 of B

10 Building Assessment Survey FIRE ALARM SYSTEM Sub-Panel Fire Alarm Control Panel (Electronic) Capacity/Size Quantity 8 Capacity/Size UOM Zones Source of Capacity/Size Inspector Estimate Installation Year 1993 Documented PANEL DEFECTIVE Quantity 1 REPAIR Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Instance Instance Instance Quantity 1 Instance Instance Manufacturer Equipment 4 - Between Fair and Poor Edwards GS Fire Alarm Panel Model System 3 Capacity/Size Quantity 10 Capacity/Size UOM Source of Capacity/Size Zones Installation Year 1993 Quantity 1 Inspector Estimate Documented PANEL DEFECTIVE REPAIR Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Fire Alarm Control Panel (Standard) Remote Annunciator Sprinkler Flow/Air Pressure Switch Tamper Flow Switch/Chain Location/Instance Quantity Between Fair and Poor CHAIN MISSING Room B24 INSTALL CHAIN Urgency of Action PRIORITY 5 PB/A&W Page 10 of 14

11 Building Assessment Survey FIRE ALARM SYSTEM Tamper Flow Switch/Chain Purpose of Action LEVEL 6 Photo1 GROUNDING SYSTEM INTERCOM SYSTEM LAN Local Distribution Frame (I/LDF) Main Equipment Rack (MDF) LIGHTNING PROTECTION MOTOR CONTROL CENTER MOTOR STARTER/CONTACTOR PANEL BOARD Fused Disconnect Switch Type Location/Instance Quantity 2 PANEL BOARD BEYOND USEFUL LIFE Original Building Attic Fan Room, Auditorium Crawlspace Mechanical Room REPLACE-UPGRADE Urgency of Action PRIORITY 1 Photo1 Fused Knife Switch Type Fused Toggle Switch Type Location/Instance Quantity 1 PANEL BOARD BEYOND USEFUL LIFE Electrical Room REPLACE-UPGRADE Urgency of Action PRIORITY 1 Photo1 Molded Case Circuit Breaker Type PANEL BOARD COVER IS MISSING PB/A&W Page 11 of 14

12 Building Assessment Survey PANEL BOARD Molded Case Circuit Breaker Type Location/Instance By Room 213 Quantity 1 MAINTENANCE Urgency of Action PRIORITY 3 Photo1 Location/Instance Quantity 9 PANEL BOARD BEYOND USEFUL LIFE By Rooms (G13, G15, 116, 130, 213, 230),, Auditorium REPLACE-UPGRADE Urgency of Action PRIORITY 1 Photo1 PUBLIC ADDRESS SYSTEM Replacement Quantity 46,000 Replacement Uom SECURITY Instance Instance Instance Quantity 1 Instance General Office Model Biamp MPA 250 Installation Year 1993 Location/Instance Quantity 8 Documented CLOCK NOT OPERATIONAL Classrooms and Corridors REPLACE Urgency of Action PRIORITY 3 Photo1 IPDVS/CCTV System Replacement Quantity 46,000 Replacement Uom Installation Year 2003 Intrusion Alarm System Documented Replacement Quantity 46,000 Replacement Uom PB/A&W Page 12 of 14

13 Building Assessment Survey SECURITY Intrusion Alarm System Central Control Panel Instance Custodian's Office Instance Instance Quantity 1 Instance Model Vista - 128B Installation Year 2003 Documented Infrared Sensor Panic Switch Remote Annunciator Siren/Strobe Ultrasonic Sensor - Security Inaccessible SERVICE SWITCH Instance Electrical Room Instance Instance Quantity 1 Instance Instance Manufacturer Federal Pacific Electric Equipment Main Service SW Capacity/Size Quantity 800 Capacity/Size UOM Amps Source of Capacity/Size Nameplate Installation Year 1972 Inspector Estimate BEYOND USEFUL LIFE Location/Instance Quantity 46,000 REPLACE Urgency of Action PRIORITY 1 Photo1 SWITCHBOARD Number of Spares 4 Air Circuit Breaker Type PB/A&W Page 13 of 14

14 Building Assessment Survey SWITCHBOARD Fused Disconnect Switch Type Instance Electrical Room Instance Instance Quantity 1 Instance Instance Manufacturer Federal Pacific Electric Equipment N/A Capacity/Size Quantity 800 Capacity/Size UOM Amps Total Capacity/Size2 Quantity 2 Capacity/Size2 UOM Section(S) Source of Capacity/Size Service Switch Size Installation Year 1972 Inspector Estimate BEYOND USEFUL LIFE Location/Instance Quantity 46,000 REPLACE Urgency of Action PRIORITY 1 Photo1 Fused Knife Switch Type Molded Case Circuit Breaker Type TELEPHONE SYSTEM PBX/Intercom Standard TRANSFORMER TV SYSTEM Cable System Exist? Operational? Main Equipment Rack 1 - Good 1 - Good PB/A&W Page 14 of 14

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 184 - QUEENS, 163-15 21 ROAD, New York, 11357 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-05 11:46

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: I.S. 364 - BROOKLYN, 1426 FREEPORT LOOP, New York, 11239 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-16

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 5 - BROOKLYN, 820 HANCOCK STREET, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-25 8:54 AM 2018-06-04 10:18 AM Asset Data Type of Service Does Interactive

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: PS 152 ANNEX -BROOKLYN, 1087 OCEAN AVENUE, New York, 11210 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 174 - QUEENS, 65-10 DIETERLE CRESCENT, New York, 11374 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-01-25

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 81 ANNEX (OLD 75) - QUEENS, 511 SENECA AVENUE, New York, 11385 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 371 (OLD 615) - BROOKLYN, 355 37 STREET, New York, 11232 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-23

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 310 - BRONX, 260 WEST KINGSBRIDGE RD, New York, 10463 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-07

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 138 AX (CROWN HGTS ECC 1)-K, 960 PROSPECT PLACE, New York, 11216 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 59 ANNEX - BRONX, 2120 QUARRY RD, New York, 10457 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-02-12

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: NEW SCH FOR ARTS AND SCIENCE - X, 965 LONGWOOD AVENUE, New York, 10459 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-01 8:13 AM 2017-12-01

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 86 - BROOKLYN, 220 IRVING AVENUE, New York, 11237 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-14

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 90 MINISCHOOL - BRONX, 1116 SHERIDAN AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 47 - QUEENS, 9 POWER ROAD, New York, 11693 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-20 12:40

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: HS OF AMERICAN STUDIES - BRONX, 2925 GOULDEN AVENUE, New York, 10468 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 127 - BROOKLYN, 7805 7 AVENUE, New York, 11209 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-30

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 69 PORTABLE - QUEENS, 77-02 37TH AVENUE, New York, 11372 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-24 8:36 AM 2018-05-16

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 135 - QUEENS, 207-11 89TH AVENUE, New York, 11427 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: HS FOR MATH, SCI & ENGINEERING-M, 240 CONVENT AVENUE, New York, 10031 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-20 11:37 AM 2018-01-09

More information

NYC Department of Education

NYC Department of Education Asset: LEARNING SUPPORT CENTER - K, 1665 ST. MARKS AVENUE, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-07 1:06 PM 2018-05-10 12:20 PM Asset Data Type of Service

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: PRE-K CENTER @ 107-17 NORTHERN BOULEVARD - QUEENS, 107-17 NORTHERN BOULEVARD, New York, 11368 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 314 - BROOKLYN, 330 59 STREET, New York, 11220 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-23

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 80 AX(PETR COMPL-BLDG E)-S.I., 715 OCEAN TERRACE, New York, 10301 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 16 - BROOKLYN, 157 WILSON STREET, New York, 11211 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-30

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: I.S. 260 - MANHATTAN, 425 WEST 33RD STREET, New York, 10001 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-16

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: FORT HAMILTON HS MODULAR UNIT - K, 8301 SHORE ROAD, New York, 11209 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 152 - MANHATTAN, 93 NAGLE AVENUE, New York, 10040 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-05

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 56 - STATEN ISLAND, 250 KRAMER AVE., New York, 10309 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-20

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: TERS PREP HS(OL REDIRECTION)-K, 226 BRISTOL STREET, New York, 11212 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: DIV. COMPUTER INFO-DATA CENTER-K, 2 METROTECH CENTER, New York, 11211 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: FRANCIS LEWIS HS TRANSPORTABLE - Q, 58-20 UTOPIA PARKWAY, New York, 11365 Inspection Id Inspection Type Time In Last Edited EE :

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 23 - BROOKLYN, 545 WILLOUGHBY AVENUE, New York, 11206 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-05-31 8:47 AM 2018-06-05 3:45 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 104 - BROOKLYN, 9115 5TH AVENUE, New York, 11209 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-02-21 8:55 AM 2018-02-21 1:09 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 224 ANNEX - QUEENS, 221-21 CORBETT ROAD, New York, 11361 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-28 12:27 PM 2018-04-04 5:15 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 19 - STATEN ISLAND, 780 POST AVENUE, New York, 10310 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-10-26 8:58 AM 2017-11-14 1:37 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 7 - MANHATTAN, 160 EAST 120 STREET, New York, 10035 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-02 8:44 AM 2018-03-12 10:45 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 73 - BRONX, 1020 ANDERSON AVENUE, New York, 10452 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-16 8:29 AM 2017-11-28 10:59 AM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: UNIVERSITY NEIGHBORHOOD - M, 200 MONROE STREET, New York, 10002 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-02-05 11:56 AM 2018-03-02 7:14 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 146 - BRONX, 968 CAULDWELL AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-01 8:57 AM 2018-05-31 2:59 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 22 - STATEN ISLAND, 1860 FOREST AVENUE, New York, 10303 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-08 8:51 AM 2017-12-18 4:14 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 198 - BRONX, 1180 TINTON AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-24 8:14 AM 2018-01-24 9:32 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 163 - BRONX, 2075 WEBSTER AVENUE, New York, 10457 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-22 8:33 AM 2018-03-22 3:13 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 2 - MANHATTAN, 122 HENRY STREET, New York, 10002 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-05 9:21 AM 2018-01-16 12:15 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 205B (ECF) - BRONX, 2375 SOUTHERN BLVD, New York, 10460 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-12 12:29 PM 2018-01-12 3:14 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 253 - BROOKLYN, 601 OCEAN VIEW AVENUE, New York, 11235 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-22 8:34 AM 2018-05-31 5:42 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: J. K. ONASSIS HS FOR INT CAREERS-M, 120 WEST 46 STREET, New York, 10036 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-11 11:37 AM 2017-12-26 12:18 PM Asset Data Are there

More information

NYC Department of Education

NYC Department of Education Mechanical Inspection Asset: P.S. 1 - MANHATTAN, 8 HENRY STREET, New York, 10038 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-09-28 8:39 AM 2017-10-12 5:28 PM Asset Data Are there

More information

NYC Department of Education

NYC Department of Education Asset: BAYSIDE AF - QUEENS, 204-29 29TH AVENUE, New York, 11361 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-10-31 9:42 AM 2017-11-20 4:21 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: MORRISANIA SEC ED COMPLEX-X, 1365 FULTON AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-03 8:53 AM 2017-11-03 5:47 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 29 - STATEN ISLAND, 1581 VICTORY BLVD, New York, 10314 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-10 11:28 AM 2018-01-17 11:37 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 161 - MANHATTAN, 499 WEST 133 STREET, New York, 10027 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-15 8:26 AM 2018-06-08 1:37 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 841- QUEENS, 48-25 37TH STREET, New York, 11104 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-02 12:54 PM 2018-05-14 12:28 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 128 - MANHATTAN, 560 WEST 169 STREET, New York, 10032 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-07 8:50 AM 2018-06-14 1:16 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 11 - MANHATTAN, 320 WEST 21 STREET, New York, 10011 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-23 8:27 AM 2018-01-23 3:21 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 183 - QUEENS, 2-45 B 79 STREET, New York, 11693 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-02 8:32 AM 2018-05-16 1:44 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 78 - QUEENS, 48-09 CENTER BLVD., New York, 11109 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-02 11:40 AM 2018-04-19 9:04 AM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: J.H.S. 216 - QUEENS, 64-20 175 STREET, New York, 11365 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-06 8:51 AM 2017-11-22 10:04 AM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 157 - BRONX, 757 CAULDWELL AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-01 8:48 AM 2017-12-06 5:36 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 160 - BROOKLYN, 5105 FORT HAMILTON PARKWAY, New York, 11219 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-03 8:01 AM 2018-05-18 1:45 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: I.S. 45 - BRONX, 2502 LORILLARD PLACE, New York, 10458 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-05 9:14 AM 2017-12-20 11:42 AM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 92 - BROOKLYN, 601 PARKSIDE AVENUE, New York, 11226 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-13 8:31 AM 2017-11-27 11:43 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S./I.S. 194 - BRONX, 2365 WATERBURY AVENUE, New York, 10462 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-24 8:34 AM 2018-02-01 10:02 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: LEARNING SUPPORT CENTER - M, 333 7TH AVENUE, New York, 10001 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-23 8:46 AM 2018-01-30 10:47 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 111 - MANHATTAN, 440 WEST 53 STREET, New York, 10019 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-16 8:47 AM 2018-03-21 8:02 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 199 ANNEX (@ ST. TERESA'S) - QUEENS, 50-15 44TH STREET, New York, 11377 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-18 11:39 AM 2018-05-14 12:27 PM Asset Data

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 194 - MANHATTAN, 244 WEST 144 STREET, New York, 10030 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-12 10:48 AM 2018-01-29 10:54 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 32 - BRONX, 690 EAST 183 STREET, New York, 10458 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-13 9:25 AM 2017-11-16 5:46 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: I.S. 131 - BRONX, 885 BOLTON AVENUE, New York, 10473 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-10-17 8:54 AM 2017-12-05 5:41 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 310 - BRONX, 260 WEST KINGSBRIDGE RD, New York, 10463 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-07 8:42 AM 2017-12-13 12:31 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: HS FOR MATH, SCI & ENGINEERING-M, 240 CONVENT AVENUE, New York, 10031 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-20 12:04 PM 2018-01-05 5:32 PM Asset Data Are there

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 69 - STATEN ISLAND, 144 KEATING PLACE, New York, 10314 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-19 8:39 AM 2018-01-23 4:33 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 4 - MANHATTAN, 500 WEST 160TH STREET, New York, 10032 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-08 8:29 AM 2017-12-08 3:44 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 188 - MANHATTAN, 442 EAST HOUSTON STREET, New York, 10002 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-08 8:52 AM 2018-06-13 5:06 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: PRE-K CENTER @ 7401 FORT HAMILTON PARKWAY - BROOKLYN, 7401 FORT HAMILTON PARKWAY, New York, 11228 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-27 11:12 AM 2017-11-27

More information

NYC Department of Education

NYC Department of Education Asset: MID MAN ADULT LRNG CTR (81) - M, 212 W 120TH ST, New York, 10027 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-17 8:16 AM 2018-01-17 8:17 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 86 ANNEX - BRONX, 124 EAMES PLACE, New York, 10468 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-05 1:03 PM 2018-04-27 1:35 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: FORSYTH HS (AUXSVC-OLD 91) - M, 198 FORSYTH STREET, New York, 10002 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-09-28 8:07 AM 2018-03-20 4:47 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: I.S. 2 - BROOKLYN, 655 PARKSIDE AVE, New York, 11226 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-05-11 9:35 AM 2018-05-22 3:53 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: JEFFERSON AF - BROOKLYN, 125-08 FLATLANDS AVENUE, New York, 11208 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-05-07 8:39 AM 2018-05-08 2:04 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: NEW UTRECHT AF - BROOKLYN, 1601 80 STREET, New York, 11214 Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior 2017-10-31 4:06 PM 2018-06-13 10:51 AM AA : Architectural

More information

NYC Department of Education

NYC Department of Education Architectural Inspection Building Assessment Survey 2017-2018 Asset: LEHMAN AF - BRONX, 3000 EAST TREMONT AVENUE, New York, 10461 Inspection Id Inspection Type Time In Last Edited SA : Architectural -

More information

NYC Department of Education

NYC Department of Education Asset: W.E.B. DUBOIS HS - BROOKLYN, 402 EASTERN PARKWAY, New York, 11225 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-04 1:02 PM 2017-12-27 4:16 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: A. PHILLIP RANDOLPH HS - MANHATTAN, 443 WEST 135 STREET, New York, 10031 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-02-02 8:11 AM 2018-06-14 1:21 PM Asset Data Are there

More information

NYC Department of Education

NYC Department of Education Asset: AUTOMOTIVE TRADES VOC HS - K, 50 BEDFORD AVENUE, New York, 11222 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-05-01 8:09 AM 2018-05-10 2:18 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: ACHIEVEMENT FIRST ENDEAVOR CHARTER SCHOOL- BROOKLYN, 510 WAVERLY AVENUE, New York, 11238 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-14 8:42 AM 2018-03-23 10:17 AM

More information

NYC Department of Education

NYC Department of Education Asset: CLINTON AF - BRONX, 100 W. MOSHOLU PKWY S, New York, 10468 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-20 8:24 AM 2017-12-31 2:04 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: LIBERTY HS - MANHATTAN, 250 WEST 18 STREET, New York, 10011 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-29 11:32 AM 2018-02-01 10:16 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: COLUMBUS AF - BRONX, 925 ASTOR AVENUE, New York, 10469 Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior 2017-10-31 9:21 AM 2017-11-29 8:45 AM AA : Architectural - Associate

More information

NYC Department of Education Building Condition Assessment Survey :49AM :00PM

NYC Department of Education Building Condition Assessment Survey :49AM :00PM School: InspectionId Asset Data Inspection Type Building Assessment Survey 05-06 P.S. 70 - BROOKLYN, 4 EMERSON PLACE, BROOKLYN, NY, 05 Time In Last Edited 476 MECHANICAL 05-- 08:49AM 05-- 03:00PM Have

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. The present fire alarm system manufactured by Gamewell was installed with the 1982 renovation. It is a non addressable, zoned system. It includes

More information

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 No. Discipline Sent to Name Item Date Noted Date Resolved How item was resolved SCO # 1Punch listed items were noted below on

More information

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL DISTRIBUTION SYSTEM:?? The existing electrical service consists of an underground primary service originating at a utility pole on Cedar Street,

More information

PLATTEVILLE MIDDLE SCHOOL

PLATTEVILLE MIDDLE SCHOOL Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. Description of the building system The school is equipped with a hard wired fire alarm control panel, and automatic dialer. The fire alarm

More information

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School MOUNT PLEASANT MIDDLE SCHOOL HVAC M-01 Heating Plant: The existing boilers have recently been upgraded. (3) steam boilers (8660 mbh each) manufactured by Weil- McLain have been installed. Newer hot water

More information

Florence High School / Middle School Page 1 of 3 Florence, WI

Florence High School / Middle School Page 1 of 3 Florence, WI Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15 ELECTRICAL DESIGN CRITERIA TABLE OF CONTENTS I GENERAL...2 II CRITERIA...2 A. POWER DISTRIBUTION SYSTEMS...2 1. NORMAL POWER:...2 2. EMERGENCY POWER...3 B. LIGHTING...4 1. GENERAL...4 2. AVERAGE MAINTAINED

More information

ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING

ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING Mechanical Systems Information The mechanical system at Reed Middle School is comprised of seventy six Trane DX/Gas rooftop units (RTUs). The recommended useful life for DX equipment is 15 years. Seventy

More information

Sprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS

Sprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS EXISTING MECHANICAL CONDITIONS SUMMARY The items listed below are based on our site visit on Nov 10, 2016. Our review is based on current conditions and anticipated future use of these building. In the

More information