ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

Size: px
Start display at page:

Download "ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS"

Transcription

1 ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered fire suppression system using branded agent FM200 manufactured by Dupont and can be operated with a flexible pneumatic, thermally sensitive tubing used as a detection device, or with a manual release device. The thermally sensitive tubing is designed to burst at approximately 110 C, releasing suddenly the pressure inside the tubing. The sudden release of pressure activates the indirect low pressure (ILP) valve and floods the protected area with extinguishing agent. The preengineered fire suppression system shall be used to protect enclosed hazard such as electrical cabinets, CNC machines and other enclosed compartment containing electrical or mechanical components. II. APPLICABLE STANDARDS AND PUBLICATIONS The FireDETEC pre-engineered system shall be designed, installed, inspected, maintained, tested and recharged only by fire protection personnel qualified and trained by CEODEUX Extinguisher Valves Technology S.A. in accordance with existing regulations, rules and guidelines including requirements of the Governmental and/or Local authority and other regulatory authorities, in accordance with applicable requirements set forth in the latest edition of the following codes and standards: A. NFPA 2001 Clean Agent Fire Extinguishing Systems B. FM Factory Mutual Approval Guide C. UL Fire Protection Equipment Directory

2 D. Department of Transportation (DOT) Title 49 Code of Federal Regulations E. Local Authorities Having Jurisdiction (AHJ) The standards listed, as well as all other applicable codes, standards, and good engineering practices shall be used as minimum design standards. III. REQUIREMENTS The suppression system installation shall be made in accordance with the drawings, specifications and applicable standards. Should a conflict occur between the drawing and specifications, the specifications shall prevail. IV. EXCLUSIONS The work listed below shall be provided by others, or under other sections of this specification: A. 120 VAC or 220 VAC power supply to the system control panel. B. Interlock wiring and conduit for shutdown of Heating, Ventilation and Air-Conditioning (HVAC), dampers and/or electric power supplies, relays or shunt trip breakers. C. Connection to local/remote fire alarm systems or listed central alarm station(s). V. QUALITY ASSURANCE A. MANUFACTURER 1. The valves, cylinders, detection tubing, ends of line, discharge tubing, fittings and nozzles shall be supplied by CEODEUX-EXTINGUISHER VALVES TECHNOLOGY S.A. or one of its direct representatives. 2. The name of the brand FireDETEC or the Rotarex three-star logo shall appear on all major components. 3. All devices, components and equipment shall be approved by the CEODEUX- EXTINGUISHER VALVES TECHNOLOGY S.A. 4. All devices, components and equipment shall be new, standard products of the manufacturer s latest design and suitable to perform the functions intended.

3 5. All devices and equipment shall be validated by UL and FM during the certification process of complete systems. B. INSTALLER 1. The installing contractor shall be trained by the supplier to design, install, test and maintain fire suppression systems and be in possession of the corresponding training certificate (valid 3 years). 2. The installing contractor shall be an experienced firm regularly engaged in the installation of automatic Clean Agent, or similar, fire suppression systems in strict accordance with all applicable codes and standards. 3. The contractor shall specifically prepare plans according to the common standards and easily reproducible. These plans will show the quantity, location, and marking of all system components. Included shall be a description and routing of all piping / tubing. Care should be taken to locate all agent storage containers as close to the protected area as possible to ensure complete liquid discharge of the suppression agent within 10 seconds. 4. The installing contractor shall have access to a Clean Agent recharging station. The installing contractor shall provide proof of this ability to recharge the largest Clean Agent system within 24 hours. This section is to be adapted to the specific local conditions of each country. 5. The installing contractor shall be an authorized stocking distributor of the Clean Agent system equipment so that immediate replacement parts are available from inventory. This section is to be adapted to the specific local conditions of each country. SECTION 2 TECHNICAL REQUIREMENTS I. SYSTEM DESCRIPTION AND OPERATION A. The FireDETEC indirect pre-engineered clean agent extinguishing system is used for total flooding applications. Total flooding protection is applicable to enclosed special hazards such as rooms or space containing flammable liquid, electrical equipment, records, or other combustibles where the agent may be used for extinguishment. The hazard area must have no outside air flow present in order to successfully achieve the extinguishing concentration within the enclosure.

4 B. The system shall provide a minimum agent design concentration, as defined by NFPA 2001, in all areas and/or protected spaces, at the minimum anticipated temperature within the protected area. The system should be designed to discharge its contents in 10 seconds or less. Final concentration shall not exceed 9% for normally occupied spaces. Concentration may vary depending on the Authorities Having Jurisdiction (AHJ) but may never be less than the one defined by NFPA C. The system shall be complete according to the design manual. It shall include all mechanical, and electrical installation, all detection and control equipment, agent storage cylinders, branded FM200 agent, discharge nozzles, pipe and fittings, manual release and abort stations, audible and visual alarm devices, auxiliary devices and controls, shutdowns, alarm interface, caution/advisory signs, functional checkout and testing, training and all other operations necessary for a functional, UL Listed and/or FM Approved Clean Agent Suppression System for use with branded FM200 agent. D. The FireDETEC systems are indirect automatic type systems which utilize flexible, pneumatic, thermally sensitive tubing to activate the system. This tubing is connected to the top of the discharge valve assembly and is pressurized with nitrogen along with the cylinder contents. When the pressure in this tubing is vented, the valve piston moves up, the valve opens and the extinguishing agent is discharged through a separate piping network. There are three ways of venting the pressure in the tubing in order to actuate the system: - Manual operation by use of end of line manual actuator - Electrical operation by use of end of line solenoid actuator - Automatic operation when a sufficient temperature is reached to burst the tubing Note: The thermally sensitive tubing is not considered as an acceptable mean of fire detection by FM and was not tested as such. An FM Approved system shall require the use of an FM Approved smoke/heat detector and control panel. Therefore, for an FM approved system the solenoid actuator must be installed on all units and wired to a control panel connected to FM approved sensors. The manual actuator must also be installed to provide an independent means of manual actuation, as per FM 5600 section Both actuators may be installed at the end of the tubing line by use of a tee connector. E. The Rotarex FireDETEC Indirect Low Pressure (ILP) Pre-Engineered Fire Suppression Systems Featuring Linear Pneumatic Tubing Design, Installation, and Maintenance Manual, p/n , describes the design, installation, usage, maintenance, and limitations for these systems. These systems are to be designed, installed, used, and maintained explicitly as described in the system manual identified above.

5 II. MATERIAL AND EQUIPMENT A. GENERAL REQUIREMENTS 1. The FireDETEC pre-engineered fire suppression system materials and equipment shall be standard products of the supplier s latest design and suitable to perform the functions intended. When one or more pieces of equipment must perform the same function(s), they shall be duplicates produced by one manufacturer. 2. All devices and equipment shall be validated by UL and FM during the certification process of complete systems. 3. The fire suppression agent shall be branded FM200 agent manufactured by Dupont. The agent shall be suitable for use in normally occupied spaces. Agent shall be listed as Acceptable on the US Environmental Protection Agency s Significant New Alternatives Policy (SNAP) list. 4. All exposed parts of an extinguishing system, including the finishes on coated or painted parts, the assemblies of moving parts, the nameplates as secured in place, the mounting bracket, or other similar parts, shall be resistant to commonly encountered atmospheric corrosive influences, and to galvanic corrosion as determined by the Salt Spray Corrosion Tests performed by UL and FM. 5. When the deterioration, breakage or other malfunction of a material for an extinguishing system unit presents a risk of causing the extinguishing system to become inoperable, the material shall not be susceptible to stress cracking, as determined by 10- Day Moist Ammonia Tests performed by UL and FM. 6. The extinguishing system unit shall be designed to operate between 32 F (0 C) and 130 F (54.4 C). B. CLEAN AGENT STORAGE 1. Each system has its own supply of clean agent. 2. Systems shall be designed in accordance with the manufacturer s guidelines. 3. Each supply shall be located out of the hazard area, as near as possible, to reduce the amount of pipe and fittings required to install the system. 4. The FireDETEC indirect pre-engineered clean agent extinguishing system is suitable for applications where the cylinder ambient storage temperature is between 32 F and 130 F (0 C to 54 C). 5. The extinguishing agent used in these systems is branded FM200, chemically identified as 1,1,1,2,3,3,3 Heptafluoropropane. This extinguishing agent currently holds

6 component FM Approval under multiple manufacturers and is listed in the Approval Guide as part of the Fire Protection Division under the heading Fixed Extinguishing Systems Clean Extinguishing Agents. The extinguishing agent is superpressurized with dry nitrogen to the nominal working pressure of 240 psi (16.5 bar) at 70 F (21 C) for use in this system. 6. The FireDETEC indirect pre-engineered extinguishing system is available in three capacities, each having its own article number. Details are provided in the table below. System Model Number Cylinder Part Number Max. Fill, lbs. (kg) Discharge Valve Part Number Discharge Valve Outlet, In. Maximum Protected Volume, Ft 3 (m 3 ) B (1.4) B ¼ NPT 92.2 (2.61) B (3.2) B ½ NPT (6.09) B (6.4) B ½ NPT (12.19) Note: Maximum protected volume is given for a completely enclosed area according to NFPA calculation guidelines. C. VALVE 1. The valve is nickel plated brass, equipped with a pressure gauge to monitor the system pressure, with a ball valve interfacing the tubing and the cylinder, and with a burst disc. 2. The valves are equipped with 2 discharge ports. Each discharge port shall be fitted with a safety plug for safety purposes during transportation and intended to prevent uncontrolled discharge of a cylinder in the event of accidental system activation. 3. All valves are delivered with a safety clip preventing from unauthorized manipulation of the ball valve when sealed. D. MOUNTING BRACKETS 1. The cylinder wall mounting brackets are epoxy powder coated and must be used to mount the cylinder in vertical position. 2. Cylinders and brackets shall be arranged to allow cylinder removal and cylinder weighing (maintenance procedure). E. BURST DISC Burst disc is provided to protect the cylinders against overpressure. F. PRESSURE GAUGE

7 1. Pressure gauge is provided and used to indicate internal cylinder pressure. The pressure gauge is color coded to display the acceptable operating range, under and over pressure range. 2. Each system shall have a pressure switch plugged on its detection line to provide electrical supervision of the cylinder pressure. The low pressure switch shall be wired to a control panel to provide an audible and visual supervisory condition signal in the event the cylinder pressure drops below 90% of working pressure. 3. Pressure switch shall be easily assembled and disassembled when the cylinder is pressurized. G. END OF LINE (EOL) 1. The End of Line (EOL) shall be required to pressurize the thermal activation tubing. 2. EOL Manual Release shall be used where the system shall be manually activated and without external power require. 3. EOL Solenoid Actuator (an electro mechanical device) shall be used where the system required relay signal to actuate electrically from control panel or other electric signal. 4. A manual means of operation shall be provided with a seal or other device to minimize the potential for accidental discharge. H. LINEAR THERMAL DETECTOR AND ACTUATION TUBING 1. Linear Thermal Detector and Actuation Tubing shall be designed to meet the following requirement: - Max. Working pressure 20 bar (at 20 C) - Internal diameter 4 mm - Outside diameter 6 mm - Min. Bending radius 100 mm - Temperature range - 30 C C - Life time 5 years (under normal conditions) 2. All devices and equipment shall be tested and validated by UL and FM during the certification process of complete systems. 3. The Linear Thermal Detector shall be validated and considered as a mean of detection by UL. This section is to be adapted depending on the type of tubing used. I. DISCHARGE NOZZLE

8 1. The discharge nozzle used to control the flow of and distribute the agent into the hazard area shall be brass construction, 360 dispersal patterns and is FM and UL approved. 2. The 3 lb. cylinders shall be used with a one nozzle setup, while the 7 lb. and 14 lb. cylinders can be used with two nozzles, balanced setups as well. These nozzles have a pre-determined design which was performance tested, as identified in the table below. Nozzle Part System Thread Size Orifice Quantity Orifice Diameter Number lb./1 nozzle 1/ lb./1 nozzle 3/ lb./2 nozzles 3/ lb./1 nozzle 1/ lb./2 nozzles 1/2" J. PIPING REQUIREMENT 1. Piping must be Schedule 40 steel pipe, either galvanized or black steel. Specifications ASTM A-53 or A-106, ANSI B36.10 must be used for steel pipe or tube. 2. Distribution piping and fittings shall be installed in accordance with the manufacturer s requirements, NFPA 2001 and approved piping standards and guidelines. All distribution piping shall be installed by qualified individuals using accepted practices and quality procedures. All piping shall be adequately supported and anchored at all directional changes and before nozzle locations. The piping shall be laid out to give maximum flow and to avoid possible mechanical, chemical or other damage. Installation shall follow drawings as closely as possible. System designer must be consulted for anything other than minor deviations in pipe routing. 3. The discharge line shall be connected to the ground to avoid the accumulation of static electricity during discharge. K. PIPE FITTINGS 1. Piping joints shall be Malleable Iron 300 pound class only - ASTMA-197 and have a minimum working pressure of 620 psi (42 bars). Temperature ratings of the fittings must not be exceeded. All threaded joints must be in accordance with ANSI B-20.1 Ductile Iron 300-pound class or higher ASTM A-395, or Steel ASTM-234 is acceptable. Piping, fittings, and pipe supports shall be in accordance with the latest edition of NFPA Also consult ANSI B 31.1, The Power Piping Code. The method of joining all pipe must be in accordance with the latest requirements listed in NFPA Acceptable fittings include screwed, flanges, welded.

9 III. SEQUENCE OF OPERATION The system shall be designed and installed such that it activated the discharge valve by any one of the following: A. MANUAL ACTUATION VIA MANUAL RELEASE VALVE The pre-engineered Fire suppression system can be manually activated by installing the manual release device at the end of the linear sensor tubing. The manual release device shall depressurize the linear sensor tube and open the valve to activate the Clean Agent discharge through the discharge nozzle installed within the protected area. Pressure switch is activated and opens (or closes) electric contacts to switch on/switch off electric devices. B. ELECTRIC ACTUATION VIA ELECTRIC RELEASE DEVICE The pre-engineered Fire suppression system can be electrically activated by installing the solenoid actuator at the end of the linear sensor tube. The electro-mechanical device allows actuation of the pre-engineered Fire suppression system from control panel or other electronic sensor. C. AUTOMATIC ACTUATION VIA TEMPERATURE SENSITIVE TUBING The system automatically operates when the thermal temperature sensitive tubing installed as linear detection capability bursts because of heating. Heat or direct flame impingement during a fire situation will cause the tubing to rupture. The tubing ruptures at the hottest point along its entire length, and then the Clean Agent (FM-200 ) is discharged through the piping network and nozzles to extinguish fire. Pressure switch is activated and opens (or closes) electric contacts to switch on/switch off electric devices. SECTION 3 DOCUMENTATION AND TESTING I. SYSTEM INSPECTION AND CHECKOUT Upon completion of installation, a meeting shall be held at the site with the contractor. Equipment supplier and owner personnel shall be present. The contractor shall familiarize owner s personnel with system components, system functions, and recommend procedures. The contractor will provide the owner with a complete operation and maintenance manual as well as written summary of any functional tests conducted.

10 The check-out procedures is intended to represent the minimum requirement for the extinguishing portion of the system. Additional procedures may be required by the applicable governmental or regulatory authorities. A. COMPARTMENT (HAZARD) AREA CHECK A good review of the hazard area shall be made. Certain aspects about the hazard may have changed, or been overlooked, which could affect overall system performance. B. AREA CONFIGURATION The hazard area dimensions shall be checked against those shown on the system plan(s). If the area volume or geometry has changed, the agent weight shall be recalculated and compared with the agent weight supplied. The area shall also be checked for bulkheads or movable partitions, which have been added or changed. If partitions have been added, installer shall check to see that all areas within the compartment still receive adequate agent distribution. C. AREA LEAKAGE The hazard area shall be checked for openings which could allow agent leakage after system discharge. Openings, such as cable, pipe and duct penetrations into the area shall be permanently sealed. Other sources of leakage shall be checked for and sealed. Doors entering and access panels in the hazard area shall be checked for tightness. Seals and door sweeps shall be installed to minimize leakage. Wall switch and receptacle boxes shall be sealed. All penetrations between walls and side panels must be sealed. D. CONTAINERS 1. Installer must check to ensure all cylinders and brackets are securely fastened. 2. Installer must check all pressure gauges. They shall display 240 PSIG at 70 F (16.6 bar at 21 C). 3. Installer must verify that cylinders of correct weight and pressure are installed in accordance with the design drawings. E. AUXILIARY FUNCTIONS Operation of auxiliary functions such as door closures, damper closures, air handling shutdown, etc. shall be verified when the pressure switch is activated. II. TRAINING REQUIREMENTS

11 Prior to final acceptance, the installing contractor shall provide operational training to each shift of the owner s personnel. Each training session shall include control panel operation, manual and (optional) abort functions, trouble procedures, supervisory procedures, auxiliary functions and emergency procedures. The following shall be included in the contractor s quotation: A. Duration of training B. Location of training (on site if feasible) C. Material covered and training aids available III. MAINTENANCE The maintenance procedures and intervals are indicated in the Design, Installation and maintenance manual for DuPont FM-200 Pre-engineered fire suppression systems, art. nb. PR-EN-xxxx, and are meant to represent the minimum requirements for FireDETEC FM-200 systems. These procedures do not preclude those required by NFPA 2001 and or the applicable governmental or regulatory authority. More frequent service intervals may be necessary if systems are installed in more severe service applications. A regular maintenance program must be established for the continuous operation of all FM- 200 fire suppression systems. A periodic maintenance program shall be established and followed. A maintenance log must be maintained for ready reference. The log must include the following accumulated data: A. Inspection Interval B. Inspection procedure performed C. Maintenance performed as a result of the inspection D. Name of inspector performing the task Any time rust or corrosion is found on a fire suppression cylinder it should be taken out of service and replaced. IV. INSTALLATION Installation procedures shall be performed in accordance with Design, Installation and maintenance manual for DuPont FM-200 Pre-engineered fire suppression systems, art. nb. PR-EN-xxxx, by fire protection personnel qualified and trained by CEODEUX Extinguisher Valves

12 Technology S.A. in accordance with existing regulations, rules and guidelines including requirements of the Governmental and/or Local authority and other regulatory authorities. V. WARRANTY System shall be warranted for parts and labour for not less than a period of one (1) year from date of installation. The contractor shall specify the maintenance to be performed during the warranty period to maintain warranty conditions. The standard life time for the tube must be (5) years under the normal operating condition and within the stated specification of the tubing.

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition. 1. GENERAL SPECIFICATION 1.1 A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection 1. GENERAL SPECIFICATION 1.1 A total flooding, Novec 1230 fluid, fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in

More information

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1. A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125

More information

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System 1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering

More information

SPECIFICATION: ARGONITE Engineered Fire Suppression System

SPECIFICATION: ARGONITE Engineered Fire Suppression System 1. GENERAL SPECIFICATION 1.1 A total flooding, clean agent, fire suppression system, filled with Argonite agent shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125 as the fire extinguishing agent

More information

FM-200 In-Cabinet Series

FM-200 In-Cabinet Series 1. GENERAL SPECIFICATION 1.1 A total flooding, In-Cabinet fire suppression system, employing FM-200 superpressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by

More information

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND 1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation

More information

SECTION FM-200 FIRE SUPPRESSION SYSTEM

SECTION FM-200 FIRE SUPPRESSION SYSTEM SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to

More information

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL SECTION 1 GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing FK-5-1-12 as the fire extinguishing agent and with a

More information

Hospitals and Major Medical Centers

Hospitals and Major Medical Centers Hospitals and Major Medical Centers INERGEN Fire Suppression Systems AUTOPULSE Detection and Control Equipment SENTRY Hand Portable Fire Extinguishers Medical centers have special concerns for fire safety

More information

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 An Engineered Carbon Dioxide Fire Suppression System shall be installed to meet a minimum design concentration of %, by volume in all designated spaces/areas to be protected.

More information

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL SECTION 1 GENERAL CONDITIONS I. SCOPE: SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing

More information

TOTALPAC2 Integrated Fire Protection System

TOTALPAC2 Integrated Fire Protection System TOTALPAC2 Integrated Fire Protection System Page 1 of 8 General 1. Applicable Standards The TOTALPAC2 Surefire complies with the following standards: - NFPA-13 Sprinkler Systems; - NFPA-15 Water Spray

More information

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM SECTION 13966 TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Total

More information

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. Page 1 of 9 1. (Refer to Figures 1-3.) Viking Electric/Pneumatic Double Interlocked Preaction Systems utilize a Viking deluge valve controlled by a pneumatic actuator (E.1), normally held closed by supervisory

More information

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi CONTROL PANEL SECTION 1 GENERAL CONDITIONS I. SCOPE: SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing

More information

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA. 319a. January 27, 2012 January 27, 2012 319a 1. DEsCrIpTIoN (Refer to Figures 1-3.) Viking Electric/Pneumatic Double Interlocked Preaction Systems utilize a Viking deluge valve controlled by a pneumatic actuator (E.1), normally

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE January 27, 2012 311a 1. DEsCrIpTIoN (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system.

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 2400CA - CLEAN AGENT CHEMICAL SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE Page 1 of 12 1. (Refer to Figures 1-7.) Viking supervised Single-Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system piping

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary

More information

Copyright 2013 Fike 12/13 SECTION CLEAN-AGENT FIRE-EXTINGUISHING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Copyright 2013 Fike 12/13 SECTION CLEAN-AGENT FIRE-EXTINGUISHING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 212200 - CLEAN-AGENT FIRE-EXTINGUISHING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL DRY CHEMICAL SELF-CONTAINED AUTOMATIC EXTINGUISHER UNIT

DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL DRY CHEMICAL SELF-CONTAINED AUTOMATIC EXTINGUISHER UNIT DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR DRY CHEMICAL SELF-CONTAINED AUTOMATIC EXTINGUISHER UNIT Models: 940202-2.5 lbs 940502-5 lbs 941002-10 lbs 942002-20 lbs P/N 800010 U.L. EX5323

More information

BERMAD Fire Protection

BERMAD Fire Protection Model: 400E-3M Bermad Electro-Pneumatically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with

More information

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories.

More information

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE Page 1 of 12 1. DESCRIPTION (Refer to Figures 1-6.) Viking Electric/Pneu-Lectric Double Interlocked Preaction Systems utilize a Viking deluge valve, pneumatic supervision of the automatic sprinkler system,

More information

FIREDETEC PRODUCT TECHNOLOGY: DIRECT & INDIRECT

FIREDETEC PRODUCT TECHNOLOGY: DIRECT & INDIRECT FIREDETEC TECHNOLOGY: DIRECT & INDIRECT PROPERTIES DIRECT SYSTEM (< 1m 3 ) DETECTION TUBE : FIRE DETECTION & EXTINGUISHING AGENT DISCHARGE IDEAL APPLICATION: Small and hard to reach enclosures (< 1m 3

More information

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types: Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Preaction Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-21 21 03.00 10 February 2009) ---------------------------------- Preparing Activity: USACE Superseding UFGS-21 21 03.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

CONSTRUCTION REQUIREMENTS

CONSTRUCTION REQUIREMENTS CONSTRUCTION REQUIREMENTS Note: The buildings on the UCCS campus are divided into two categories: General Fund and Auxiliaries. General Fund Buildings include academic and administrative functions. Auxiliary

More information

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses PART 1 - GENERAL 1.1 SCOPE A. Through Class III Commodity Classification, up to 12.2m of single, double or multiple row rack storage, up to 14.6m building height (VanQuish Fire Sprinkler System). Cartoned

More information

Liberty Township Fire Department Fire Prevention Bureau. Clean Agent Fire Protection Plan Submittal Checklist

Liberty Township Fire Department Fire Prevention Bureau. Clean Agent Fire Protection Plan Submittal Checklist Liberty Township Fire Department Fire Prevention Bureau Clean Agent Fire Protection Plan Submittal Checklist Project Name: Date: Project Address: Designers Name: Company Name: Phone Number: Email: Fax:

More information

Worldwide Contacts.

Worldwide Contacts. Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

Committee Input No. 9-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement

Committee Input No. 9-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement Committee Input No. 9-NFPA 2001-2016 [ Global Input ] Incorporate revisions per the attached file. Supplemental Information File Name 2001-CI_9.pdf Description Data and specific revisions presented at

More information

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types: Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Preaction Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E Advanced Integrated Fire Protection Systems TOTALPAC 2 Owner's Operation and Maintenance Manual FIRECYCLE III September 2009 FM-086G-0-5E TOTALPAC2 OWNER'S OPERATION & MAINTENANCE MANUAL Manufactured by

More information

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5 Page 1 of 5 1. SYSTEM DESCRIPTION Viking supervised, single interlocked preaction pre-primed systems utilize a Viking Deluge Valve (A.1) and a hydraulically pressurized automatic sprinkler system. The

More information

Data/ Specification Sheet

Data/ Specification Sheet Data/ Specification Sheet MONARCH Dry Chemical Automotive Paint Spray Booth Fire Suppression System TM 1. Fixed temperature mechanical or thermal detectors 2. Electrical conduit protecting stainless steel

More information

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This section outlines the requirements for the nitrogen-generating sprinkler corrosion inhibiting system. The work

More information

Industrial Dry Chemical Fire Suppression System

Industrial Dry Chemical Fire Suppression System Industrial Dry Chemical Fire Suppression System INSTALLATION, OPERATION AND MAINTENANCE MANUAL, P/N 15040 Revision B, April 9, 2013 AMEREX CORPORATION INC. - 7595 GADSDEN HIGHWAY - TRUSSVILLE, AL 35173

More information

Deluge & Preac tion Systems

Deluge & Preac tion Systems Deluge & Preaction Systems Deluge Systems are normally used in special hazard installations where water must be applied to an entire area for protection. They use open sprinklers or spray nozzles attached

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

More information

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT 1. GENERAL SPECIFICATION 1.1 This specification outlines the requirements for a pre-engineered fire extinguishing system comprising Kidde Fire Systems WHDR Wet Chemical Fire Suppression System, Kidde APC

More information

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar) Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

STR-Series Indirect-Fired Air Turnover Units

STR-Series Indirect-Fired Air Turnover Units STR-Series Indirect-Fired Air Turnover Units Equipment Specifi cations 1.800.589.3691 www.weather-rite.com GAS/OIL HEATING ONLY INDIRECT-FIRED AIR TURNOVER UNIT GUIDE SPECIFICATIONS PART 1 GENERAL [Gas][Oil][Gas/Oil

More information

Basic Vehicle Fire Protection Manual

Basic Vehicle Fire Protection Manual Basic Vehicle Fire Protection Manual Basic Vehicle Fire Protection Manual TABLE OF CONTENTS Introduction... 3 System Operation...... 5 Component Overview.... 7 Operator Controls Control Panel.........

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

More information

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL NO. 05602 FOR AMEREX STORED PRESSURE, HAND PORTABLE DRY CHEMICAL FIRE EXTINGUISHERS. ABC (Ammonium Phosphate Base)

More information

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE ANSUL INSTALLATION OPERATION AND MAINTENANCE MANUAL ANSUL AUTOMAN II-C RELEASING DEVICE 001799 This manual is intended for use with the ANSUL AUTOMAN II-C Releasing Device. Those who install, inspect,

More information

D. Reference Standards (Utilize latest editions available):

D. Reference Standards (Utilize latest editions available): 1.01 Scope of Standard A. This standard provides general requirements of The Sam Houston State University for fireextinguishing systems other than water-based fire suppression systems. This document is

More information

TECHNICAL DATA. Wet 26a. February 22, 2009

TECHNICAL DATA. Wet 26a. February 22, 2009 February 22, 2009 Wet 26a 1. DESCRIPTION The Viking Alarm Check Valve serves as a check valve by trapping pressurized water above the clapper and preventing reverse flow from sprinkler piping. The valve

More information

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS ANSUL Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50-B, 450/100-B, 900/100-B INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,

More information

Twin-Agent Fire Fighting/Securing Systems Specifications

Twin-Agent Fire Fighting/Securing Systems Specifications Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50, 450/100, 900/100 & 1350/200 INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,

More information

esfr dry pendent sprinkler Vk501 (k14.0)

esfr dry pendent sprinkler Vk501 (k14.0) September 13, 2012 Sprinkler 122a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK501 is a fast response fusible element type sprinkler designed for use in storage

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.

More information

CHAPTER THREE SPRINKLER SYSTEM AND FM-200 AGENT SYSTEM

CHAPTER THREE SPRINKLER SYSTEM AND FM-200 AGENT SYSTEM CHAPTER THREE SPRINKLER SYSTEM AND FM-200 AGENT SYSTEM 10 Chapter Three Sprinkler System and FM-200 Agent System 3.1. Background National Fire Protection Association (NFPA 13), Standard for the installation

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS HI DELTA, TYPE WH - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 3500.932A Effective: 04-01-17 Replaces: 10-31-16 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY A.

More information

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE HD FIRE PROTECT TECHNICAL DATA SIZE DELUGE VALVE CHECK VALVE SPRINKLER ALARM RELEASE PANEL 50, 80, 100, 150 & 200 NB Model H3, UL Listed

More information

Sinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea

Sinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea s Data Sheet Fire Safety Products Sinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea ARCHITECT AND ENGINEER SPECIFICATIONS System Overview Sinorix

More information

Gravity and Pneumatic Waste and Linen Handling Systems NFPA 82 Inspection Form

Gravity and Pneumatic Waste and Linen Handling Systems NFPA 82 Inspection Form Gravity and Pneumatic Waste and Linen Handling Systems NFPA 82 Inspection Form PART 1 GRAVITY CHUTES CHUTE DESIGN AND INSTALLATION INTAKE OPENINGS LIMITED ACCESS OFFSETS DIMENSIONS VENTING CONSTRUCTION

More information

Replacement of pneumatic actuators on Ruskin negator spring dampers with Belimo FSxx Series

Replacement of pneumatic actuators on Ruskin negator spring dampers with Belimo FSxx Series WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. See NFPA checklists below. Contents Replacement of pneumatic actuators on Ruskin negator spring dampers

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Instructions for Installation, Operation, Care and Maintenance Bulletin 733 Rev. F Model DDX PrePaK, Type D Preaction System 4 (100mm), 6 (150mm) & 8 (200mm) Single Interlock - Electric Release Double

More information

Types of Detection. Fusible Link Detection - Most Common

Types of Detection. Fusible Link Detection - Most Common Types of Detection Fusible Link Detection - Most Common Types of Detection Electric Detection Types of Detection Pneumatic Detection-Tubing Pneumatic Tubing 3 Year Service life Survey Hazard 1) List all

More information

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description FIREFLEX VACTEC description This FIREFLEX VACTEC integrated fire protection system consists of a vacuum system trim totally pre-assembled, prewired and factory tested. All electrical and mechanical components

More information

GASEOUS HYDROGEN SYSTEMS

GASEOUS HYDROGEN SYSTEMS CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall

More information

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description FIREFLEX VACTEC description This FIREFLEX VACTEC integrated fire protection system consists of a vacuum system trim totally pre-assembled, prewired and factory tested. All electrical and mechanical components

More information

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES DIVISION 21 FIRE SUPPRESSION PART 1 GENERAL 1.01 DESCRIPTION A. Provide UL listed, FM approved listed fire protection specialties or accessories as required by either the equipment manufacturer or the

More information

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock Bulletin 740 Rev. A Model DDX PrePaK, Type D Preaction System 2 (50mm), 2-1/2" (65mm) & 3 (80mm) Sizes Instructions for Single Interlock Installation, Operation, Double Interlock Care and Maintenance 10

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

TJERNLUND PRODUCTS, INC.

TJERNLUND PRODUCTS, INC. TJERNLUND PRODUCTS, INC. 1601 Ninth Street White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 (651) 426-2993 FAX (651) 426-9547 Visit our web site www.tjernlund.com PRESSURE SWITCH AND INSTALLATION WITH

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS DELTA LIMITED, TYPE WH - MODELS 399B-899B SUGGESTED SPECIFICATIONS Catalog No.: 3500.97B Effective: 04-01-17 Replaces: 11-15-08 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

DESIGN, INSTALLATION AND MAINTENANCE MANUAL

DESIGN, INSTALLATION AND MAINTENANCE MANUAL DESIGN, INSTALLATION AND MAINTENANCE MANUAL PART NUMBER 027650010. RELEASE DATE: REVISION 07/16 LISTED FIRE PROTECTION SYSTEMS INSTALLATION MANUAL Minimax SSP 1230 Clean Agent Fire Suppression Systems

More information

USER INSTRUCTIONS FOR FLANGE IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS

USER INSTRUCTIONS FOR FLANGE IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS USER INSTRUCTIONS FOR FLANGE IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS APPLICATION INDEECO Explosion proof Electric Immersion Heaters for Hazardous Locations are ccsaus Certified for use in areas (external

More information

Engineering Specifications

Engineering Specifications Engineering Specifications ANSUL INERGEN Clean Agent Fire Suppression System with AUTOPULSE Control System 2012-AUG-20 FIRE DETECTION / INERGEN FIRE SUPPRESSION SYSTEM ENGINEERING SPECIFICATIONS Tyco

More information

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCESA / NASA UFGS-21 21 00.00 40 (August 2010) --------------------------------- Preparing Activity: NASA Superseding UFGS-21 21 00.00 40 (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

SERVICE MANUAL (v1) UL / ULC. WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK

SERVICE MANUAL (v1) UL / ULC. WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK STRIKE FIRST CORPORATION AKC SERVICE MANUAL (v1) UL / ULC WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK All fire extinguishers should be installed, inspected

More information

OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE

OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE FOAM FIRE EXTINGUISHERS MODEL 254-6 LITER AFFF FOAM WITH SPRAY NOZZLE Model 250 2 ½ GAL.LON AFFF FOAM WITH ASPIRATED NOZZLE MODEL 252 2 ½ GAL.LON FFFP (ALCOHOL RESISTANT) FOAM WITH ASPIRATED NOZZLE OWNER'S

More information

TotalPac 3 Firecyle III Deluge Remote controlled system

TotalPac 3 Firecyle III Deluge Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical

More information

esfr dry pendent sprinkler Vk502 (k14.0)

esfr dry pendent sprinkler Vk502 (k14.0) Page 1 of 11 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual

ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual 001799 This manual is intended for use with the ANSUL AUTOMAN Il-C Explosion-Proof Releasing Device.

More information

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16 (42,7 mm) CROSS SECTION Worldwide Contacts www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K and Pendent Extended Coverage Light and Ordinary Hazard General Description Extended Coverage and Pendent Sprinklers

More information

FIRE SUPPRESSION SYSTEM

FIRE SUPPRESSION SYSTEM FIRE SUPPRESSION SYSTEM An effective fire suppression systems work fundamentally in three ways; The corner stone has to be an efficient means of early warning/detection. Followed by either an Oxygen reduction

More information

PAFSS Fire Suppression Systems from Jactone. Automatic Fixed Fire Suppression Systems. JACTONE.COM/PAFSS +44 (0)

PAFSS Fire Suppression Systems from Jactone. Automatic Fixed Fire Suppression Systems. JACTONE.COM/PAFSS +44 (0) PAFSS Fire Suppression Systems from Jactone Automatic Fixed Fire Suppression Systems JACTONE.COM/PAFSS +44 (0)1902 357777 pafss@jactone.com Protect your assets from fire with PAFSS JACTONE.COM/PAFSS +44

More information

FireFlex DUAL Double Interlock, Self-contained system

FireFlex DUAL Double Interlock, Self-contained system FireFlex DUAL description The FireFlex DUAL integrated system consists of an integrated Double interlock preaction automatic sprinkler system combined with a clean agent fire extinguishing system, factory-assembled

More information