THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6
|
|
- Barrie Neal
- 5 years ago
- Views:
Transcription
1 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1
2 QUESTIONS How To Ask a Question: POLLING There will be occasional interactive poll questions. 2
3 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 JOINT COMMISSION TOP FINDINGS 3
4 CMS TOP FINDINGS. 1. K0056 Automatic Sprinkler Systems 2. K0062 Sprinkler System Maintenance 3. K0144 Generators Inspection/Testing 4. K0038 Exit Accessible at All Times 5. K0029 Hazardous Area Separation 6. K0025 Smoke Partition Construction K0056 Automatic Sprinkler Systems K0029 Hazardous Area Separation K0062 Sprinkler System Maintenance K033 Exit Components K0144 Generators Inspection/Testing K0038 Exit Accessible at All Times 7. K0050 Fire Drills K0025 Smoke Partition Construction K0062 Sprinkler System Maintenance K0056 Automatic Sprinkler Systems K0050 Fire Drills K0029 Hazardous Area Separation K0052 Fire Alarm System Testing K0144 Generators Inspection/Testing K0025 Smoke Partition Construction 8. K0067 HVAC K020 Vertical Shafts K0071 Laundry Chutes 9. K0071 Laundry Chutes K0050 Fire Drills K0147 Electrical Wiring and Equipment 10. K0018 Corridor Doors K0018 Corridor Doors K069 Cooking Equipment SPRINKLER SYSTEM INSTALLATION K56 K351 4
5 SPRINKLER SYSTEM MAINTENANCE K62 K353 NFPA 25, 2011 Edition EXIT CORRIDORS K39 K232 Corridor clutter / storage 30 minute rule 5
6 HAZARDOUS AREAS K29 K321 EXISTING 1 hour enclosure ¾ hour door Sprinkler protection Smoke partition Self closing door 50 SF or greater with storage NEW 1 hour enclosure ¾ hour door Sprinkler protection Self closing door 100 SF or greater with storage SMOKE BARRIERS K25 K372(wall), K379(doors) Outside wall to outside wall Floor to deck All penetrations sealed Doors smoke resisting Doors self closing HINT: INSPECT IN THE LESS OBVIOUS LOCATIONS...NOT JUST ABOVE THE CORRIDOR DOORS 6
7 CONSTRUCTION TYPE / PROTECTION K12 K161 FIRE DRILLS K50 K712 Varying times Varying conditions Each shift quarterly Knowledge of procedures and competence of staff as observed in drills 7
8 ELECTRICAL K50 K511 NFPA 70 (NEC) LIFE SAFETY FEATURES Rated fire / smoke barrier walls 30 min corridor walls Rated enclosures / shafts Exits Exterior Stairs Passageways Horizontal 8
9 WHY DRAWINGS CLARIFICATIONS 9
10 WHY DRAWINGS LIFE SAFETY FEATURES 10
11 HAZARDOUS AREAS Existing Hazardous Areas Sprinklered Non-sprinklered New Hazardous Areas Ambulatory & Business HAZARDOUS AREAS 11
12 SUITES Suite Type Sleeping suite Non-sleeping suite Non-patient care suite Suite Size SMOKE COMPARTMENTS Compartment Boundaries Compartment Size 22,500sq.ft. Sprinkler Protection 12
13 SUITES & SMOKE COMPARTMENTS COVER PAGE GENERAL BLDG. INFO LOGO 13
14 ALTERNATE APPOACHES WAIVERS Fire Safety Evaluation System (FSES) Time Limited Waiver Permanent Waiver Categorical Waiver 14
15 FIRE SAFETY EVALUATION SYSTEM (FSES) NFPA 101A (guide) Addresses Alternate Approaches to Life Safety Accepted method by TJC and CMS Calculations and process by occupancy type Evaluates each smoke zone Factors include Occupancy risk factors Safety parameters OCCUPANCY RISK PARAMETERS HEALTHCARE 15
16 OCCUPANCY SAFETY PARAMETERS HEALTHCARE Construction Interior Finish Corridor Partitions Corridor Doors Zone Dimensions Vertical Openings Hazardous Areas Smoke Control Egress Routes Fire Alarm Detection Sprinkler Protection OCCUPANCY SAFETY PARAMETERS HEALTHCARE 16
17 OCCUPANCY SAFETY PARAMETERS HEALTHCARE OCCUPANCY SAFETY PARAMETERS HEALTHCARE All Zones Must be Zero (0) or Greater 17
18 FSES CERTIFICATION Registered Architect Licensed PE CFPS Local AHJ (fire marshal, building official, etc.) COMMON FSES APPLICATIONS Construction issues Travel distance issues Deficient egress components 18
19 TIME LIMITED WAIVERS A detailed written request outlining a time period in which the facility will become in prescriptive compliance with a Life Safety Code provision. Deficiencies eliminated in future Code editions Temporary issues Issues identified in survey taking longer than 60 days to remediate. WAIVER SUBMISSION Executive Summary / Overview Building Overview Construction info Building height Sprinkler protection Smoke detection Other pertinent info Detailed Deficiency Description Code / Standard References TJC Life Safety Chapter Life Safety Code chapter and section Intent of the Requirement 19
20 WAIVER DOCUMENTATION / SUBMISSION Hardship Assessment Cost (provide specifics when possible) Operational disruption Negative affect on patients Waiver Justification Deficiency What off sets the deficiency New or existing features above what is required Cost, source & commitment for alternative solution Interim Life Safety Measures (ILSM) Clarify that ILSMs have been reviewed and applied Patient Safety Assessment / Field Verification Alternative Clarify that the request will not negatively impact patient safety Statement clarifying an on site review & assessment WAIVER DOCUMENTATION / SUBMISSION Supporting documentation / descriptive drawings Organization Name & Logo 20
21 WAIVER DOCUMENTATION / SUBMISSION Supporting / descriptive photographs COMMON PITFALLS Why are Requests Commonly Returned or Rejected Substance Proposal does not constitute an equivalent or better situation Administrative Missing information in submission Request form not provided or incomplete No certifying letter FSES not completed accurately FSES drawings not included 21
22 QUESTIONS Next Session Referenced Codes & Standards 22
23 THANK YOU Dave Hood President Nick Gabriele Vice President 23
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationDeveloping a Healthcare Facility Fire Door Inspection Program
Developing a Healthcare Facility Fire Door Inspection Program WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio QUESTIONS How To Ask a Question: 1 POLLING There will be occasional interactive
More informationBuilding Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1
Building Codes & Standards for Healthcare Building Codes and Standards AHJs Codes Defend in Place Walls Sprinklers Fire Alarm Important Dates for Healthcare Facilities 7/5/16 NFPA Life Safety Code 101
More informationJOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015
JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015 AGENDA INTRODUCTION OF PRESENTERS SOC VS. FIRE & LIFE SAFETY DRAWINGS HAZARDOUS AREAS VS. INCIDENTAL
More informationInterim Life Safety Measures. Healthcare Construction Certificate - Level 1
Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained
More informationLIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE
California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments
More information2017 Accreditation Updates
2017 Accreditation Updates Tennessee Healthcare Engineers Association 2017 Spring Conference Pickwick Landing State Park Counce, Tennessee 38326 Presented May 17, 2017 By Ken Gregory Vice President, Accreditation
More informationFIRE/SMOKE BARRIER FUNDAMENTALS
FIRE/SMOKE BARRIER FUNDAMENTALS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire OBJECTIVE Identify the different
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during
More informationChanges to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)
Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for
More informationTaming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.
Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago
More informationLife Safety Code Comparison
ASHE Monograph Life Safety Code Comparison Michael A. Crowley, PE, SASHE Jeffery E. Harper, PE ASHE Monograph Life Safety Code Comparison Michael A. Crowley, PE, SASHE Jeffery E. Harper, PE Chicago 2013
More informationOther EC and LS documents may be requested by surveyors, as needed, throughout the survey.
Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the
More informationMeasures (ILSM) Process
Managing the Interim Life Safety Measures (ILSM) Process 1 A Program for The Texas Association of Healthcare Facility Management Monday, April 30, 2012 Robert H. Bartels, CHFM CHSP CHEP SASHE President,
More informationChanges to NFPA 101A 2013 Edition for Health Care Facilities
2017 NFPA Conference & Expo Changes to NFPA 101A 2013 Edition for Health Care Facilities Presented by: William Koffel, P.E, FSFPE Lennon Peake, P.E. Koffel Associates Koffel Associates President Manager
More informationPresented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC
Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC Changes to Life Safety Compliance Healthcare leaders will have to deal with many changes in Life Safety compliance when
More informationTHE HEALTHCARE ENVIRONMENT UPDATE. Anne M. Guglielmo, Engineer Engineering Department The Joint Commission. Copyright, The Joint Commission
2013 THE HEALTHCARE ENVIRONMENT UPDATE Anne M. Guglielmo, Engineer Engineering Department The Joint Commission Standard/NPSG 2012 Non Compliance 2013 Non Compliance (1 st Six Months) RC.01.01.01 61% 55%
More informationAre there any policies regarding outlets that contain USB ports?
Answers to the Questions Mark J. Blackburn, P.E., CFPS February, 2016 Question 1 Are there any policies regarding outlets that contain USB ports? There is no direct reference in code about these types
More informationLife Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 AGENDA: Life Safety Code Referenced Publications Overview Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99
More informationNew DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE
DEPARTMENT OF HEALTH & HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - AMBULATORY SURGICAL CENTERS Medicare 1. (A) PROVIDER NUMBER Identifying information as shown in
More informationNFPA 101 Code Update from 2012 Edition to the 2015 Edition
NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls
More informationLIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN
Title/Description: Life Safety & Fire Prevention Management Department: Facilities Management Personnel: All Effective Date: 5/97 Revised: 7/00, 7/01, 7/02, 7/03, 7/04, 7/05, 7/08 LIFE SAFETY & FIRE PREVENTION
More informationCenter for Clinical Standards and Quality /Survey & Certification Group
DEPARTMENT OF HEALTH & HUMAN SERVICES Centers for Medicare & Medicaid Services 7500 Security Boulevard, Mail Stop C2-21-16 Baltimore, Maryland 21244-1850 Center for Clinical Standards and Quality /Survey
More informationNFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering
NFPA 101 and NFPA 99, 2012 Editions Code Update where art meets engineering Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC NFPA 101 and NFPA 99 where art meets
More informationHealth Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &
More informationJanuary 1, 2014 Mandatory Effective Date
2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective
More informationFACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)
FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT
More information2016 Joint Commission Update
2016 Joint Commission Update Bert M. Gumeringer, MBA, CHFM, FASHE Asst. Vice President-Facilities Operations Texas Children s Hospital August 12, 2016 11:30am-12:30pm Top 10 Findings Comparison-2015 vs.2016
More informationThe Physical Environment Portal: Module 5, LS Leadership
The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings
More informationM E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect
M E M O R A N D U M To: From: Approved: All Licensed Assisted Living Facilities Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect Henry Fry, Deputy Assistant Secretary
More informationFACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS
FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS Presented by: Alise Howlett, Assoc. AIA,CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT PHYSICAL ENVIRONMENT
More informationAgency for Health Care Administration
Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER
More informationProcedure DESCRIPTION/OVERVIEW
Applies To: UNMH Responsible Department: Life Safety Revised: 07.08.16 Procedure Patient Age Group: (X ) N/A ( ) All Ages ( ) Newborns ( ) Pediatric ( ) Adult DESCRIPTION/OVERVIEW To assure the safety
More information<< COMPANY LETTERHEAD >>
Healthcare Facilities Accreditation Program Attn: Engineering Department 142 E. Ontario Street Chicago, IL 60611 > < Date > RE: Request for Code Equivalency ABC General Hospital,
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT N.A GARMENTS PLOT # 36, ROAD # 46, GULSHAN NORTH C/A, DHAKA OTHER FACTORIES: SIDKO LIMITED, SIDKO APPARELS LIMITED, DELTA TIES LIMITED April 17, 2014 Page 2 SUMMARY was surveyed
More informationFirst Aspen Federal Regulation Set: K LSC 2000 Health Existing
First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall
More informationSTATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT
STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR3002 SAF-HEA (18.1.3.2) Recommendation: 18.1.3.2 Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies
More informationNFPA 101 Life Safety Code Culture change 2012
NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted
More informationChanges to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates
Issued June 28, 207 Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Nursing Care Center (NCC) Accreditation Program Standard
More informationAgency for Health Care Administration
Page 1 of 130 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC
More informationBeth Israel Deaconess Medical Center BIDMC Manual
Beth Israel Deaconess Medical Center BIDMC Manual Title: Life Safety/Fire Safety Management Plan Policy #: EOC-04 Purpose: The BIDMC Life Safety Management Plan defines the program to minimize the probability
More informationAgency for Health Care Administration
Page 1 of 75 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER
More informationAgency for Health Care Administration
Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other
More informationCommon Building Code Misinterpretations
Common Building Code Misinterpretations Presented by: Ron Melucci, P.E. Technical Manager, FP Division Engineering Planning and Management, Inc. rbm@epm inc.com www.epm inc.com 508 875 2121 Engineering
More informationFIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group
FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway AIA Healthcare Group Introductions Presenters Coffman Engineers Scott M. Twele, P.E. Operations Manager,
More informationEC 5.10 FIRE PREVENTION MANAGEMENT
EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively
More informationAccreditation Program: Hospital
ccreditation Program: Hospital Life Safety 2008 The Joint ommission on ccreditation of Healthcare Organizations ccreditation Program: Hospital hapter: Life Safety Standard LS.0001 The [organization] designs
More informationDanilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services
Life Safety Code Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services danilo.concepcion@stjoe.org 714-771-8944 The findings and conclusions in this presentation are
More informationAgency for Health Care Administration
Page 1 of 133 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - Y1001 - Awareness of the
More information3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials
AMCA International Design Tips For Fire and Smoke Barriers William E. Koffel, P.E., FSFPE President, Koffel Associates, Inc. www.koffel.com Air System Engineering & Technology (ASET) Conference US San
More informationThis policy may also be used for routine work orders that are Life Safety in nature and cannot be completed within 45-days.
Policy: It is the policy of the St. Joseph Mercy Health System (SJMHS- Ann Arbor, Oakland, Livingston, Brighton, Chelsea and St. Mary Mercy Hospital- Livonia) and associated satellite facilities to assure
More informationEmergency Planning for Institutional Facilities
Emergency Planning for Institutional Facilities Pacific ADA Emergency Preparedness Webinars Presented by: Kimberly Paarlberg, ICC Based on the 2015 edition of the International Building Code (IBC) and
More informationLife Safety Codes for Assisted Living Facilities
Life Safety Codes for Assisted Living Facilities Doug Hohbein Chief Plans Examiner Nebraska State Fire Marshal s Office doug.hohbein@nebraska.gov 402-471-9474 Assisted Living Facilities Receive annual
More informationLauzon Life Safety Consulting
Welcome to This Presentation By The WHEA Education & Professional Development Committee WHEA Lunch & Learn April 13, 2017 Lauzon Life Safety Consulting FIRE PLANS & DRILLS 1 Agenda Lauzon Life Safety Consulting
More informationAgency for Health Care Administration
Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationAssisted Living Facilities
Life Safety Codes for Assisted Living Facilities Doug Hohbein Chief Plans Examiner Nebraska State Fire Marshal s Office doug.hohbein@nebraska.gov 402-471-9474 Assisted Living Facilities Receive annual
More informationChapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.
3610 COMMERCE DR SUITE 817 BALTIMORE MD 21227 P 410.737.8677 F 410.737.8688 www.haifire.com May 5, 2014 Review of Regulations 42 CFR Parts 403, 416, 418, 460, 482, 483 and 485 Medicare and Medicaid Programs;
More informationThe Surveyor s Perspective. Understanding How The Joint Commission Surveyors Conducts Surveys
The Surveyor s Perspective Understanding How The Joint Commission Surveyors Conducts Surveys Tim Markijohn MBA\MHA, CHFM, CHE Field Director, Life Safety Learning Objectives At the conclusion of this presentation,
More informationPERFORMANCE COMPLIANCE METHODS
CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,
More informationASCs & LSC. Alice Epstein, DFASHRM, FNAHQ
, DFASHRM, FNAHQ Disclaimer The purpose of this presentation is to provide information, rather than advice or opinion. It is accurate to the best of the speaker's knowledge as of the date of the presentation.
More informationLife Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved
Life Safety Code Common Discepancies Course# LSC102 EZpdh.com All Rights Reserved 1. K147 Electrical - Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code. 9.1.2
More informationAgency for Health Care Administration
Page 1 of 98 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC surveyor's determination
More informationTIPS FOR BETTER JOINT COMMISSION SURVEYS
TIPS FOR BETTER JOINT COMMISSION SURVEYS Washington Society for Healthcare Engineering September 21, 2011 Yakima, Washington The BASICS Most Failed Standards. Scoring. Electronic S. O. C. I.L.S.M. Building
More informationM E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter
More informationInterim Life Safety Measures (ILSM)
1 Interim Life Safety Measures (ILSM) Frank D. Rudilosso P.E., M.Eng, CHSP Manager Facilities Regulatory Life Safety Compliance frr9035@nyp.org Tom Singh MPH, MHA, CHSP Field Director Facilities Regulatory
More informationFHCA 2014 Annual Conference & Trade Show
FHCA 2014 Annual Conference & Trade Show CE Session #5 Preparing for the Upcoming Code Changes Don t Look Back Tuesday, July 8 8:15 to 9:15 a.m. Canary 3 Operations/Quality Improvement Upon completion
More information4/9/2014. Life Safety Code. Nursing Facility Life Safety Code Today and Tomorrow. Kenneth Daily, LNHA.
Nursing Facility Life Safety Code Today and Tomorrow Kenneth Daily, LNHA kenn@qissurvey.com April 2014 Life Safety Code Life Safety Code 101 (2000 Ed.) Promulgated by the National Fire Protection Association
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance
More informationCodes and Standards FFP1510, BFST1510, ATCP1510
DEPARTMENT OF FINANCIAL SERVICES Division of State Fire Marshal Bureau of Fire Standards & Training Title: Master Syllabus Date: July, 2017 Codes and Standards FFP1510, BFST1510, CP1510 Course Title Codes
More informationInterim Life Safety Assessments and Infection Prevention Assessments
Interim Life Safety Assessments and Infection Prevention Assessments 1 Healthcare Construction ILSM and ICRAs PRESENTED BY Bob Dubiel, CHFM, CHC -Mayo Clinic Health System NWWI -Projects and Construction
More informationThe Residences at Christina Landing Wilmington, DE
5.0 FIRE PROTECTION EXISTING CONDITIONS 5.1 Project Specific Fire Protection Data Codes, Regulations, and Standards Building Officials and Code administrators (BOCA) National Building Code [1996] with
More informationLABELING OF FIRE-RATED GLAZING STUDY GROUP REPORT TO CTC MEETING CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES
LABELING OF FIRE-RATED GLAZING STUDY GROUP REPORT TO CTC MEETING CHICAGO, IL - OCTOBER 3-4, 20 CODE CHANGES Issue : Clarification of when 703.6 can be used rather than 76. 76.2 --rated glazing. --rated
More informationSPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.
STATE OF LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BOULEVARD, BATON ROUGE, LA 70806 800-256-5452 225-925-4920
More informationPRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING
SUMMARY PROVER'S PLAN OF CORRECTION K 000 INITIAL COMMENTS K 000 A Life Safety Code Survey was conducted by the State Fire Marshal beginning on May 9th, 2017 and ending on May 10th, 2017. Adair Acute Care
More informationMedical Gas Inspections and Maintenance Programs. HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson
Medical Gas Inspections and Maintenance Programs HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson Mathis Carlson I have worked for the last 15+ years in the Medical
More informationASHE Advocacy Team. Q4 ASHE Advocacy Liaison Webinar 12/7/16 12/7/16. Tim Adams, FASHE, CHFM, CHC Director of Leadership Development
Q4 ASHE Advocacy Liaison Webinar 12/7/16 ASHE Advocacy Team Chad E. Beebe, AIA, CHFM, CFPS, CBO, SASHE Deputy Executive Director of Advocacy cbeebe@aha.org Tim Adams, FASHE, CHFM, CHC Director of Leadership
More informationFIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)
INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-
More informationLife Safety Crosswalk
The Life Safety 2008 2009 Crosswalk is an easy-to-use reference tool that crosswalks The Joint Commission s 2009 Life Safety with the 2008 and National Fire Protection Association s This crosswalk excerpt
More informationDEALING WITH FIRE SAFETY
DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February
More informationH BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION
STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H
More informationCOMPLIANCE ALTERNATIVES
CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare
More informationC. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - 2000 LIFE SAFETY CODE Intermediate Care Facilities for the Mentally Retarded LARGE PART I Figure
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More informationLife Safety - Means of Egress/Exits NFPA 101
Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all
More informationCOMPLIANCE ALTERNATIVES
CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 2 New Eskaton Road, Mogbazar, Dhaka Dhaka Dhaka Bangladesh 15 Jun 2013 The Alliance for Bangladesh Worker Safety Page 1/10 Factory Name: 15 Jun 2013
More informationNarrative Reports As Regulated by 780 CMR, Section 903.0
EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for
More informationTHE HEALTHCARE ENVIRONMENT UPDATE. George Mills, Director Engineering Department The Joint Commission. Copyright, The Joint Commission
2013 THE HEALTHCARE ENVIRONMENT UPDATE George Mills, Director Engineering Department The Joint Commission Standard/NPSG 2012 Non Compliance 2013 Non Compliance (1 st Six Months) RC.01.01.01 61% 55% LS.02.01.20
More informationK SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Form Approved OMB No. 0938-0242 1. (A) PROVER NUMBER 1. (B) MEDICA I.D. NO. 1. HOSPITAL
More informationPresented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com
Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com 1 Wis Professional Engineer Experienced Facility Director Experienced AHJ WHEA Code
More informationField Guide for Healthcare Facilities
Field Guide for Healthcare Facilities Jennifer L. Frecker James K. Lathrop Written by industry experts Jennifer L. Frecker and James K. Lathrop and using an easy-to-digest format, The New Life Safety Code
More informationRenovation Program. Renovation Program GENERAL
Renovation Program GENERAL This program provides guidance and protocols for renovation projects in occupied, operational acute hospitals. Team building is essential to quality control and HFD Services
More informationPERFORMANCE COMPLIANCE METHODS
CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,
More informationEC EP 14 All other electrical K-920 equipment in patient care vicinity NFPA , Chapter 10
MSL Healthcare Partners, Inc. Wild Card EPs Paraphrase K-tag # EC.02.04.03 EP 14 All other electrical K-920 equipment in patient care vicinity NFPA 992012, Chapter 10 K-924 K-928 K-931 K-tag Description
More informationCOURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE
COURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE 100126 The course is organized into three bands. Band A covers HVACrelated building components and other types
More information