LevelSET S GSM Functionalities Instructions for Commissioning and Use

Size: px
Start display at page:

Download "LevelSET S GSM Functionalities Instructions for Commissioning and Use"

Transcription

1 Labkotec Oy Myllyhaantie 6 FI Pirkkala, Finland Tel: Fax: Internet: LevelSET S GSM Functionalities Instructions for Commissioning and Use Copyright 2010 Labkotec Oy 1/33 Labkotec reserves the right to any changes

2 CONTENTS 1 GENERAL Copyright Target group Symbols Safety instructions Ambient conditions INTRODUCTION GSM modem operation LevelSET S and LabkoNet Mobile phone numbers COMMISSIONING LEVELSET S GSM Placing the SIM card Commissioning the GSM modem SETTING AND READING THE PHONE NUMBERS Command syntax Mobile phone numbers for end users and administrators Setting an end-user phone number Reading an end-user phone number Setting an administrator phone number Reading an administrator phone number Deleting an end-user phone number Deleting an administrator phone number BASIC SETTINGS AFTER COMMISSIONING Setting the device or target name Reading the device or target name Specifying the probe input Reading the probe input Setting the time and date Querying the signal strength ALARM SETTINGS Setting the alarm texts Reading the alarm texts Setting the interval for the maintenance alarm Reading the maintenance alarm interval Setting the measurement interval for a battery-operated device Reading the measurement interval of a battery-operated device Querying the alarm status FEATURE SETTINGS OF THE DEVICE Setting the operating voltage alarm limit Reading the operating voltage alarm limit Querying the battery voltage Querying the software version Resetting the message counter MESSAGES TO END USERS SENT BY THE DEVICE Alarm message Test alarm TROUBLESHOOTING Device responses in error situations Changing the device settings in problem situations Changing the device PIN code Resetting an administrator phone number Copyright 2010 Labkotec Oy 2/33 Labkotec reserves the right to any changes

3 1 GENERAL 1.1 Copyright Copyright 2010 Labkotec Oy. All rights reserved. Copying, distributing, or saving this document entirely or partly is prohibited without the written authorisation of Labkotec. Labkotec develops their products continuously and, therefore, reserves the right to make changes and improvements to any product mentioned in this document without any prior notice. Labkotec is not liable for direct or indirect damages, including the loss of information or income. The contents of this document are provided "as is". No direct or indirect guarantee is given for its accuracy, reliability, or the contents, or a specific guarantee for its marketability or suitability to a specific purpose, unless otherwise stipulated by law. Labkotec reserves the right to modify this document or remove it from distribution without any prior notice. LabkoNet is a registered trademark of Labkotec Oy. 1.2 Target group In regards to commissioning GSM functionalities and their use, this document provides additional instructions to the LevelSET S Operation and Installation Manual. 1.3 Symbols The following symbols are used to warn the user of a possible hazardous situation, or to remind the user of an important aspect. Symbol Warning / Note To be carefully considered especially when installing in potentially explosive atmospheres. The device is protected with either double insulation or reinforced insulation. 1.4 Safety instructions The LevelSET S measurement centre must not be installed in potentially explosive atmospheres, but a probe connected to it may be installed in potentially explosive atmosphere zones 0, 1, or 2. In potentially explosive atmosphere installations, the national regulations and the appropriate standards IEC/EN Intrinsically safe electrical systems i and/or IEC/EN Explosive atmospheres - Electrical installations must be observed. In case static electricity can cause hazards in the measurement environment, the equipotential bonding must be attended according to the regula- Copyright 2010 Labkotec Oy 3/33 Labkotec reserves the right to any changes

4 tions concerning potentially explosive atmospheres. Equipotential bonding is done by connecting all conductive parts to the same potential, for example, in a junction box. The equipotential bonding system must be grounded. The device is not equipped with a mains switch of its own and, therefore, the supply voltage wires, near the device, should be fitted with a disconnecting coupler (250 VAC/1 A), which disconnects both wires (L1, N) to facilitate maintenance and repair actions. The switch is to be marked as the disconnecting coupler of the device. When performing maintenance, inspections or repairs in potentially explosive atmospheres, standards IEC/EN and IEC/EN in regards to Ex devices inspection and maintenance should be observed. 1.5 Ambient conditions LevelSET S GSM Dimensions Enclosure Operating temperature Supply voltage Power consumption Probes Data communication (only with LevelSET S GSM) 175 mm x 125 mm x 75 mm (w x h x d) IP 65, material: polycarbonate -30ºC +50ºC 230 VAC ± 10%, 50/60 Hz Fuse 5 x 20 mm 160 mat (EN /3) The device is not equipped with a mains switch 4.5 VA Digital Labkotec SET probes GSM text messages (SMS) Built-in GSM modem 900/1800 MHz LevelSET S is suitable to be used as a power source for probes located in potentially explosive atmosphere zones 0, 1, and 2. The inputs of the device are naturally intrinsic safety structures. LevelSET S must be installed to a safe area. Copyright 2010 Labkotec Oy 4/33 Labkotec reserves the right to any changes

5 2 INTRODUCTION LevelSET S is a versatile measurement and control centre for monitoring liquid levels. The most common applications are: alarms for oil and sand separators high level and low level alarms for tanks alarms for condensation water level control These instructions provide information on commissioning and using the GSM version of the LevelSET S measurement centre. The instructions also describe the GSM functionalities. The device sends the alarms as text messages either directly to the GSM phone of the user, or to the LabkoNet server to be stored and shared with other appropriate parties. The user settings of the GSM version can be changed using the user's own mobile phone. The indicator lights, buttons, and interfaces of the device are illustrated in figure 1. Figure 1. LevelSET S level switch features Copyright 2010 Labkotec Oy 5/33 Labkotec reserves the right to any changes

6 Figure 2. Application example: Separator system 2.1 GSM modem operation LevelSET S GSM sends the alarm data as text messages either directly to the GSM phone of the user, or to the LabkoNet server. The device continuously reads the status of the digital SET probes connected to it and, if the alarm status changes, sends a notification. Also a probe fault creates an alarm of its own. With the help of the GSM modem, the user can: specify the time when the alarm data is sent to the server. order the data using a text message. change the device settings using a text message. Figure 3 illustrates the message exchange between the user and the LevelSET S central unit. Copyright 2010 Labkotec Oy 6/33 Labkotec reserves the right to any changes

7 Figure 3. Message exchange between the user and LevelSET S GSM All messages are sent as text messages. These are detailed later on in chapters 4, 5, 6, and 7 of this document. 2.2 LevelSET S and LabkoNet LevelSET S can be connected to the web-based LabkoNet monitoring system. Using the LabkoNet system alongside mobile phones brings various advantages, including constant connection monitoring as well as storing alarm data and providing visual presentations. The alarm and measurement data sent from measurement points is transferred to the LabkoNet server through a communication unit via GSM network. The server receives the data sent by the communication unit and stores the data into a database, from which it can be later accessed, for example, for reporting purposes. In addition to checking the probe-specific data sent by the device, it checks for possible alarm threshold violations. If the server detects any violations, it sens alarms to the predefined addresses as messages and phone numbers as text messages. Using their user credentials, end users can also view the alarm data in numerical or graphical format at Mobile phone numbers You can store two types of phone numbers into the LevelSET S GSM device: 1. End-user phone numbers to which messages regarding changes in alarm status are sent. Using these phone numbers, you can also request for the alarm status but not change the settings. 2. Administrator phone numbers can be used to change the device settings. No alarm data is sent to these numbers, but they can be used for sending alarm status queries. NOTE: If you wish to receive the alarm data to the same phone number from which the device settings are also changed, you must specify the phone number in question both as an end-user and administrator number. Copyright 2010 Labkotec Oy 7/33 Labkotec reserves the right to any changes

8 3 COMMISSIONING LevelSET S GSM NOTE: To commission the GSM feature, the device needs a SIM card. 3.1 Placing the SIM card Make sure that the device is not energized. 1. Open the front panel of the device. 2. Slide the SIM card holder of the device, and the holder opens up. Figure 4: Placing the SIM card into the LevelSET S GSM device 3.2 Commissioning the GSM modem 3. Place the SIM card into the holder with the metal contact surface pointing downwards. 4. Press the holder down. 5. Re-attach the front panel. Commissioning the GSM modem takes place by mere text messages, if the modem has been first selected into use with the S4 switch of the top card of the device (see chapter 5.7 Commissioning the GSM modem of the LevelSET S Level Switch for Separator Systems manual). If the device has been delivered with a modem, the modem is activated by default. After this, commissioning a new device takes place in the following order: 1. Set the end-user phone numbers. 2. Set the administrator phone numbers. 3. Set a name for the device and the parameters for the probe inputs. 4. Set the time (clock). 5. Set the alarm texts. The commissioning-related functions are described in chapters 4, 5, and 6. Copyright 2010 Labkotec Oy 8/33 Labkotec reserves the right to any changes

9 4 SETTING AND READING THE PHONE NUMBERS 4.1 Command syntax The following message descriptions apply the following syntax: A parameter marked with <> suggests that the user or the device enters the value to that specific field. Between the marks <> there is a short description of the setting. The text given in bold is an example message entered by the user. In terms of commands, the protocol recognises both upper and lower case letters. Example: Fields TEL <number1> <number5> Command End-user phone number in international format 4.2 Mobile phone numbers for end users and administrators The device can be programmed to five end-user phone numbers (TEL), to which the device sends alarm messages and from which alarm status queries can be made. These phone numbers cannot be used for changing the device settings. The device also includes five memory slots for administrator phone numbers (OPTEL), from which it is possible to change the settings, but to which alarm messages are not sent. However, administrator phone numbers can be used for requesting the alarm status data of the device. In terms of setting administrator numbers for the first time, the numbers can be set from any phone number. Once administrator phone numbers have been stored into the memory of the device, adding and deleting is possible only from those stored phone numbers. NOTE: If you wish to receive the alarm data to the same phone number from which the device settings are also changed, you must specify the phone number in question both as an end-user and administrator number Setting an end-user phone number NOTE: The maximum number of administrator/enduser phone numbers is 5, and 1-5 numbers can be set at a time. The number is always stored to the first available memory slot. Copyright 2010 Labkotec Oy 9/33 Labkotec reserves the right to any changes

10 TEL <number1> <number2> <number3> <number4> <number5> Fields TEL <number1> <number5> Command End-user phone number in international format For example: TEL <device name if specified> TEL 1: <phone number of memory slot 1>.. n: <phone number of memory slot n> TEL The response is the phone numbers set to the device. The response is only TEL, if no number has been stored. Example 1: No name has yet been specified for the device, and the following command is given: TEL TEL 1: : : Example 2: Copyright 2010 Labkotec Oy 10/33 Labkotec reserves the right to any changes

11 The memory already contains the phone numbers set in the previous example 1, and the following command is given: TEL TEL 1: : : : Reading an end-user phone number TEL <device name if specified> TEL 1: <phone number of memory slot 1>. n: <phone number of memory slot n> TEL The response is the phone numbers set to the device. The response is only TEL, if no number has been stored Setting an administrator phone number NOTE: The maximum number of administrator/enduser phone numbers is 5, and 1-5 numbers can be set at a time. The number is always stored to the first available memory slot. OPTEL <number1> <number2> <number3> <number4> <number5> Fields OPTEL Command Copyright 2010 Labkotec Oy 11/33 Labkotec reserves the right to any changes

12 <number1> <number5> End-user phone number in international format For example: OPTEL <device name if specified> OPTEL 1: <phone number of memory slot 1>.. n: <phone number of memory slot n> OPTEL The response is the phone numbers set to the device. The response is only OPTEL, if no number has been stored. Example 1: No name has yet been specified for the device, and the following command is given: OPTEL OPTEL 1: : : Example 2: The memory already contains the phone numbers set in the previous example 1, and the following command is given: OPTEL OPTEL 1: : Copyright 2010 Labkotec Oy 12/33 Labkotec reserves the right to any changes

13 3: : NOTE: After setting administrator numbers, the device settings can only be changed from the numbers in question. Remember to add your own phone number to the administrator phone number list, if you continue making device settings even after this phase Reading an administrator phone number OPTEL <device name if specified> OPTEL 1: <phone number of memory slot 1>.. n: <phone number of memory slot n> OPTEL The response is the phone numbers set to the device. The response is only OPTEL, if no number has been stored Deleting an end-user phone number NOTE: Administrator/end-user phone numbers can be deleted 1-5 at a time. DELTEL <n1> <n2> <n3> <n4> <n5> Fields DELTEL <n1> <n5> Command Memory slot number to be deleted Copyright 2010 Labkotec Oy 13/33 Labkotec reserves the right to any changes

14 For example: DELTEL 2 <device name if specified> TEL 1: <phone number of memory slot 1>... Command presents the remaining memory slots. n: <phone number of memory slot n> <device name>tel Response, if no number has been stored. Example 1: A phone number has been stored in every memory slot, but the device name has not yet been specified. The following command is given: DELTEL 2 TEL 1: : : : Example 2: The remaining phone numbers from example 1 are in the memory, and the following command is given: DELTEL TEL 4: In this case, only the phone number in memory slot 4 is an end-user phone number and other memory slots are empty. Copyright 2010 Labkotec Oy 14/33 Labkotec reserves the right to any changes

15 4.2.6 Deleting an administrator phone number NOTE: Administrator/end-user phone numbers can be deleted 1-5 at a time. DELOPTEL <n1> <n2> <n3> <n4> <n5> Fields DELOPTEL <n1> <n5> Command Memory slot number to be deleted For example: DELOPTEL 2 <device name if specified> TEL 1: <phone number of memory slot 1>... Command presents the remaining memory slots. n: <phone number of memory slot n> <device name> TEL Response, if no number has been stored. Example 1: A phone number has been stored in every memory slot, but the device name has not yet been specified. The following command is given: DELOPTEL 2 TEL 1: : Copyright 2010 Labkotec Oy 15/33 Labkotec reserves the right to any changes

16 4: : Example 2: The remaining phone numbers from example 1 are in the memory, and the following command is given: DELOPTEL TEL 4: In this case, only the phone number in memory slot 4 is an end-user phone number and other memory slots are empty. Copyright 2010 Labkotec Oy 16/33 Labkotec reserves the right to any changes

17 5 BASIC SETTINGS AFTER COMMISSIONING 5.1 Setting the device or target name It is recommended to specify a unique name for the device/target, as this gives direct indication of the device from which the alarm has been sent. NAME <device/target name> Fields NAME Command <device/target name> Name selected by the user. Max. 25 characters. Can also include spaces. For example: NAME Pirkkala Asematie1 NAME <device/target name> Command presents the device name. NAME Response is only NAME, if no name has been specified. Example 1: The following command is given: NAME Pirkkala Asematie1 5.2 Reading the device or target name NAME Pirkkala Asematie1 Copyright 2010 Labkotec Oy 17/33 Labkotec reserves the right to any changes

18 NAME NAME <device/target name> Command presents the device name. NAME Response is only NAME, if no name has been specified. 5.3 Specifying the probe input You can give descriptive names for the probes to facilitate understanding of alarm messages. NOTE: The factory settings of probe inputs are: Probe1, Probe2 and Probe3. DI <x>: <name of probe x>. <y>: <name of probe y>. <z>: <name of probe z> NOTE: In commands, dots between the probe names separate the names. NOTE: You can also specify only one or two probe inputs if, for example, you later wish to change the name of an already specified probe input. Fields DI Command <x/y/z> Probe input number 1 3 <name of probe x/y/z> Probe input must be specified, max. 20 characters. Note: In case one command is used to specify more than one probe input, the names must be separated by a dot. Copyright 2010 Labkotec Oy 18/33 Labkotec reserves the right to any changes

19 For example: DI 1: backwater probe. 2: grease probe. 3: sludge probe <device name> DI <x>: <name of probe input x> <y>: <name of probe input y> Command presents the probe input names. <z>: <name of probe input z> Example 1: The following command is given: DI 1: backwater probe. 2: grease probe. 3: sludge probe Pirkkala Asematie1 DI 1: backwater probe 2: grease probe 3: sludge probe Example 2: The name of probe input 2 should be changed, and the following command is given: DI 2: oil probe Pirkkala Asematie1 DI 1: backwater probe 2: oil probe 3: sludge probe 5.4 Reading the probe input DI Copyright 2010 Labkotec Oy 19/33 Labkotec reserves the right to any changes

20 <device name> DI <x>: <name of probe input x> <y>: <name of probe input y> Command presents the probe input names and the device name. <z>: <name of probe input z> 5.5 Setting the time and date NOTE: The time must be set only if the device sends messages to the Labkonet server. CLOCK <dd.mm.yyyy> <hh:mm> Fields CLOCK <dd.mm.yyyy > <hh:mm> Command Day, month and year, separated by dots. Hours and minutes separated by a colon. <device name> CLOCK <dd.mm.yyyy> <hh:mm> Command presents the device name and the time and date. Example 1: The following command is given: CLOCK :00 Copyright 2010 Labkotec Oy 20/33 Labkotec reserves the right to any changes

21 NOTE: The command can also be given in the following format: CLOCK :00. Pirkkala Asematie1 CLOCK : Querying the signal strength You can also query for the signal strength of the GSM modem. The signal strength can vary between 0 and 31. NOTE: If the value is below 11, the connection may be insufficient for sending messages. CSQ <device name> CSQ <value> Command presents the device name and the signal strength as value between 0 and 31. Example 1: The device name was already specified as Pirkkala Asematie1, and the following command is given: CSQ Pirkkala Asematie1 CSQ 25 Copyright 2010 Labkotec Oy 21/33 Labkotec reserves the right to any changes

22 6 ALARM SETTINGS 6.1 Setting the alarm texts The device can also be specified with alarm texts, which it sends when an alarm is triggered and cleared. You can use a different text for both cases. NOTE: The factory settings of alarm texts are: Alarm on and Alarm off. NOTE: In a fault alarm situation, the texts are Fault on and Fault off. These texts cannot be changed. ALTXT <x>: <probe x alarm on txt>. <probe x alarm off txt>. <y>: <probe y alarm on txt>. <probe y alarm off txt>. <z>: <probe z alarm on txt>. <probe z alarm off txt>. NOTE: In commands, dots between the probe names separate the names. Fields ALTXT Command <x/y/z>: Probe input number 1 3 <alarm on txt>. <alarm off txt>. Message to be sent when an alarm is triggered, max. 20 characters. Message to be sent when the alarm is cleared, max. 20 characters. NOTE: You can also specify the alarm texts for only one or two inputs at a time if, for example, you later wish to change some already specified alarm text. For example: ALTXT 1: alarm on. alarm off. 2: alarm on. alarm off. 3: alarm on. alarm off. Copyright 2010 Labkotec Oy 22/33 Labkotec reserves the right to any changes

23 ALTXT <x>: <probe x alarm on txt>. <probe x alarm off txt>. <y>: <probe y alarm on txt>. <probe y alarm off txt>. Command presents the specified alarm texts by probe inputs. <z>: <probe z alarm on txt>. <probe z alarm off txt>. Example 1: The following command is given: ALTXT 1: alarm on. alarm off. 2: alarm on. alarm off. 3: alarm on. alarm off. ALTXT 1: alarm on. alarm off 2: alarm on. alarm off 3: alarm on. alarm off 6.2 Reading the alarm texts ALTXT ALTXT <x>: <probe x alarm on txt>. <probe x alarm off txt>. <y>: <probe y alarm on txt>. <probe y alarm off txt>. Command presents the specified alarm texts by probe inputs. <z>: <probe z alarm on txt>. <probe z alarm off txt>. Copyright 2010 Labkotec Oy 23/33 Labkotec reserves the right to any changes

24 6.3 Setting the interval for the maintenance alarm The device can be set with a maintenance alarm with certain intervals to remind the user of the required maintenance actions and inspections. Maintenance alarms are indicated by the MAINTENANCE indicator light on the cover of the device. To use this function, switch S7/6 must be in position ON. See chapter 5.6 of the LevelSET S Level Switch for Separator Systems manual. NOTE: The factory setting for the alarm limit is 180. NOTE: The maintenance interval counter is reset when setting the interval. SI <nnn> Fields SI <nnn> Command Interval for the maintenance alarm in days. Max. 3 digits. <device name> SI: <mmm>/<nnn> <position of switch S7/6> <mmm> = current value of counter <nnn> = counter value to alarm (interval) <position of switch S7/6> = maintenance alarm in use when SERVIVE ALARM ENABLED, not in use when SERVICE ALARM DISABLED. Command presents the device name, the current value of the counter, the counter value to an alarm, and information on whether the maintenance alarm is in use (SERVICE ALARM ENABLED = in use, SERVICE ALARM DISABLED = not in use). Example 1: The device name was already specified as Pirkkala Asematie1, and the following command is given: Copyright 2010 Labkotec Oy 24/33 Labkotec reserves the right to any changes

25 SI Reading the maintenance alarm interval Pirkkala Asematie1 SI 0/150. SERVICE ALARM ENABLED SI <device name> SI: <mmm>/<nnn> <position of switch S7/6> <mmm> = current value of counter <nnn> = counter value to alarm (interval) <position of switch S7/6> = maintenance alarm in use when SERVIVE ALARM ENABLED, not in use when SERVICE ALARM DISABLED. Command presents the device name, the current value of the counter, the counter value to an alarm, and information on whether the maintenance alarm is in use (SERVICE ALARM ENABLED = in use, SERVICE ALARM DISABLED = not in use). 6.5 Setting the measurement interval for a battery-operated device A measurement interval can be specified for the device. When the interval limit is reached, the device reads the probes and sends the alarm data, if necessary. The device also starts the GSM modem and reads the possible set messages and queries sent to it. After this, it returns back to sleep mode. NOTE: The factory setting for the measurement interval is 60. MI <nnn> Fields MI Command Copyright 2010 Labkotec Oy 25/33 Labkotec reserves the right to any changes

26 <nnn> Measurement interval in minutes. Max. 3 digits. <device name> MI: <nnn> <position of switch S4/5> <nnn> = measurement interval in minutes <position of switch S4/5> = sleep mode in use when SLEEP MODE ENABLED, not in use when SLEEP MODE DISABLED. Command presents the device name, the position of switch S4/5, the measurement interval in minutes, and information on whether the sleep mode is in use (SLEEP MODE ENABLED = in use, SLEEP MODE DISABLED = not in use). Example 1: The device name was already specified as Pirkkala Asematie1, and the following command is given: MI 60 Pirkkala Asemati1 MI 30. SLEEP MODE ENABLED 6.6 Reading the measurement interval of a battery-operated device MI <device name> MI: <nnn> <position of switch S4/5> <nnn> = measurement interval in minutes <position of switch S4/5> = sleep mode in use when SLEEP MODE ENABLED, not in use when Command presents the device name, the position of switch S4/5, the measurement interval in minutes, and information on whether the sleep mode is in use (SLEEP MODE ENABLED = in use, SLEEP MODE DISABLED = not in Copyright 2010 Labkotec Oy 26/33 Labkotec reserves the right to any changes

27 SLEEP MODE DISABLED. use). 6.7 Querying the alarm status You can also query for the alarm status of probe inputs. M <device name> <name of probe x> <alarm or fault alarm text of probe x>.. Command presents the device name, the probe name, and the alarm and fault alarm text. In the response message, the status of each probe input is in its own row. s for the fields are given in the following table: Field <device name> <name of probe input> If you have specified a name for the device, it is written to the beginning of the message. User may have specified a descriptive name for the probe input. By default: probe 1/probe 2/probe 3 <alarm text> User may have specified alarm texts for the probe input. By default: Alarm on / Alarm off <fault alarm text> Alarm text for triggering or clearing a fault alarm. Cannot be changed. By default: Fault on / Fault off. Copyright 2010 Labkotec Oy 27/33 Labkotec reserves the right to any changes

28 NOTE: The information is not presented if the input in question has been disabled via central unit switch S4. By factory setting, all inputs are in use. Example 1: Pirkkala Asematie1 Oil probe Oil alarm 7 FEATURE SETTINGS OF THE DEVICE 7.1 Setting the operating voltage alarm limit The LevelSET S GSM device monitors its operating voltage. In the 12 VDC version, the device directly monitors the operating voltage received, for example, from the battery and, in the 230 VAC version, it monitors the voltage after the transformer. The device sends an alarm when the limit value for low voltage level is reached. NOTE: The factory setting for the alarm limit is 0.0 V (= alarm not in use). VLIM <xx.x> Fields VLIM <xx.x> Command Desired voltage value in volts and with one decimal. A dot separates the integer and the fraction. NOTE: There is a 1 V hysteresis for alarm off. In other words, the alarm is cleared 1 V higher from the limit. The hysteresis value cannot be changed. <device name> VLIM: <xx.x> V Command presents the set alarm limit for the operating Copyright 2010 Labkotec Oy 28/33 Labkotec reserves the right to any changes

29 voltage (in volts). Example 1: The device name was already specified as Pirkkala Asematie1, and the following command is given: VLIM 15.0 Pirkkala Asemati1 VLIM 15.0 V 7.2 Reading the operating voltage alarm limit VLIM <device name> VLIM: <xx.x> V Command presents the set alarm limit for the operating voltage (in volts). 7.3 Querying the battery voltage You can also use the LevelSET S GSM device for querying the battery voltage of the device. The return value of a mains supplied device is the rectified voltage after the transformer. BATVOLT 2. Send the text message command to the phone number of the device. <device name> BATVOLT: <value> V Command presents the battery voltage level in volts. Copyright 2010 Labkotec Oy 29/33 Labkotec reserves the right to any changes

30 7.4 Querying the software version Example 1: The device name was already specified as Pirkkala Asematie1, and the following command is given: BATVOLT Pirkkala Asematie1 BATVOLT 17.5 V You can also use the LevelSET S GSM device for querying the software version of the device. VER <device name> VER: <vx.xx> Command presents the software version of the device. Example 1: The device name was already specified as Pirkkala Asematie1, and the following command is given: VER Pirkkala Asematie1 VER V Resetting the message counter Per 24 hours, the number of messages sent by the device is limited to Reset the counter by sending the following text message command to the phone number of the device: rstc Copyright 2010 Labkotec Oy 30/33 Labkotec reserves the right to any changes

31 8 MESSAGES TO END USERS SENT BY THE DEVICE 8.1 Alarm message The LevelSET S GSM device sends an alarm message to the end-user phone numbers, when the alarm or fault status changes, and as a response to an alarm query message. Alarm messages contain the following fields, separated by a space: <device name> <probe name> <alarm text or fault alarm text> Data only for the used probe inputs is presented (see chapter 5.1 Selecting the probes in use of the LevelSET S Level Switch for Separator Systems manual). Field <device name> <name of probe input> If you have specified a name for the device, it is written to the beginning of the message. User may have specified a descriptive name for the probe input. By default: probe 1/probe 2/probe 3 <alarm text> User may have specified alarm texts for the probe input. By default: Alarm on / Alarm off <fault alarm text> Alarm text for triggering or clearing a fault alarm. Cannot be changed. By default: Fault on / Fault off. 8.2 Test alarm A test alarm can be triggered by continuously pressing the TEST button on the cover of the device for over 5 seconds until the device blinks all of the ACTIVE and ALARM indicator lights for a few seconds. In a test alarm, the device sends a message similar to the response for an alarm message query (querying alarm data), but the message includes the text "Test" after the device name. Copyright 2010 Labkotec Oy 31/33 Labkotec reserves the right to any changes

32 9 TROUBLESHOOTING 9.1 Device responses in error situations The LevelSET S GSM device sends a text message response to the queries received. Occasionally, the text message command sent by the user is incorrect, in which case the device responds by sending an error message to the mobile phone number of the user. Error situation/message No response COMMAND ERROR COMMAND SYNTAX ERROR Number from which the setting is made is not an OPTEL number. See chapter Setting an administrator phone number. Command was written incorrectly. Parameter error. The reason for the error varies command-specifically. The possible reasons are: a dot missing between the numbers too many numbers in respect to the available memory slots the number is too long (over 15), or letters are included too many characters a dot or a colon is missing the probe input number is not 1 3 the separator marks are missing or incorrect the entered date/time cannot exist a number with over 3 digits, letters included Solution: Write a new text message command and, before sending it, verify that it is written correctly. 9.2 Changing the device settings in problem situations In case the device does not respond in spite of messages sent to it, a so-called SOPTEL command must be given. Using this command, it is possible to change the device data. However, the PIN code of the device must be known. Copyright 2010 Labkotec Oy 32/33 Labkotec reserves the right to any changes

33 9.2.1 Changing the device PIN code The LevelSET S GSM device has a device-specific PIN code, which is not the same as the SIM card PIN code for the device. If you have forgotten the administrator phone number or specified an incorrect one, you can change it using the 4-digit PIN code of the device. NOTE: The factory setting for the PIN code is PIN <old PIN> <new PIN> Example message: PIN Resetting an administrator phone number changes the PIN code from the factory setting of 1234 to SOPTEL <PIN> <your phone number> This authorises your phone number to change the device data. Example message: SOPTEL grants the change rights to phone number Send the text message command to the phone number of the device. 3. Set the administrator phone number. Setting the administrator phone number takes place with a regular OPTEL message as described in chapter Setting an administrator phone number, by setting your phone number as an administrator phone number for the device. Copyright 2010 Labkotec Oy 33/33 Labkotec reserves the right to any changes

34

Labcom 200. Installation and User s Guide (230 VAC) Communication Unit

Labcom 200. Installation and User s Guide (230 VAC) Communication Unit Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel. +358 29 006 260 Fax +358 29 006 1260 E-mail: info@labkotec.fi Internet: www.labkotec.fi 16.7.2014 30 pages Labcom 200 Communication Unit Copyright

More information

SolarSET GSM SolarSET GSM with a Beacon

SolarSET GSM SolarSET GSM with a Beacon Labkotec Oy Myllyhaantie 6 FI-33960 Pirkkala FINLAND Tel. +358 29 006 260 Fax +358 29 006 1260 13.08.2009 Internet: www.labkotec.fi SolarSET GSM SolarSET GSM with a Beacon Solar Powered Oil Separator Alarm

More information

SET Installation and Operating Instructions. Level switch for one sensor

SET Installation and Operating Instructions. Level switch for one sensor Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel.: +358 29 006 260 Fax: +358 29 006 1260 7.11.2013 Internet: www.labkotec.fi 1/14 SET-1000 Level switch for one sensor Copyright 2013 Labkotec Oy

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

OilSET Installation and Operating Instructions. Oil Separator Alarm Device Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 18.11.2010 Internet: www.labkotec.fi 1/10 OilSET-1000 Oil Separator Alarm Device Copyright 2010 Labkotec

More information

Labkotec SET. Labkotec separator alarm system protecting our environment. Measure your success

Labkotec SET. Labkotec separator alarm system protecting our environment. Measure your success Labkotec SET Labkotec separator alarm system protecting our environment Designed to comply EN858-1&2 and PPG3 norms Warns of excessive levels of oil, sludge & liquids Prevents pollution incidents Fail-safe

More information

AND INSTALLATION MANUAL

AND INSTALLATION MANUAL Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel. +358 29 006 260 Fax +358 29 006 1260 Internet: www.labkotec.fi 10.10.2013 SET/DM3AL Level sensor OPERATION AND INSTALLATION MANUAL 1(5) SYMBOLS

More information

OilSET-1000 (12 VDC)

OilSET-1000 (12 VDC) Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 Internet: www.labkotec.fi 20.03.2009 1/11 OilSET-1000 (12 VDC) Oil Separator Alarm Device Copyright 2009

More information

SET-2000 Oil/Sludge 12 VDC

SET-2000 Oil/Sludge 12 VDC Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 12.2.2015 Internet: www.labkotec.fi 1/14 SET-2000 Oil/Sludge 12 VDC Alarm Device for Oil Separators with

More information

GSM WIRELESS ALARM SYSTEM Model: GSM-0308W

GSM WIRELESS ALARM SYSTEM Model: GSM-0308W GSM WIRELESS ALARM SYSTEM Model: GSM-0308W Table of Contents Application..... 3 Instructions. 4 Installation Diagram....5 Device Design... 5 Technical Parameter....6 Setup Instruction.6 1 Administrator

More information

Labkotec automatic warning devices for separators protecting the environment

Labkotec automatic warning devices for separators protecting the environment Labkotec automatic warning devices for separators protecting the environment ENG Labkotec SET warning devices SolarSET S warning systems OMS-1 warning device for light liquid separators GA-1 and GA-2 warning

More information

Mobeye CM2410 GSM fire alarm communicator

Mobeye CM2410 GSM fire alarm communicator PORTAL USER MANUAL Mobeye CM2410 GSM fire alarm communicator Accessory for Ei Electronics fire detector SW version 5.n Incl. CM2400 Attention! Very important This user manual contains important guidelines

More information

SET-2000 Hi Level/Oil

SET-2000 Hi Level/Oil Labkotec Oy Labkotie 1 FI-36240 KANGASALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 13.03.2008 Internet: www.labkotec.fi Alarm Device for Oil Separators Copyright 2008 Labkotec Oy We reserve

More information

USER MANUAL Mobeye ThermoGuard CM2200

USER MANUAL Mobeye ThermoGuard CM2200 USER MANUAL Mobeye ThermoGuard CM2200 SW version 1.n Attention! Very important This user manual contains important guidelines for the installation and usage of the Mobeye device as described in this manual.

More information

Trident User s Manual

Trident User s Manual Labkotec Oy Myllyhaantie 6 33960 Pirkkala FINLAND Tel. +358 (0)29 006 260 18.05.2017 Fax +358 (0)29 006 1260 Internet: www.labkotec.fi 34 pages Trident Copyright 2017 Labkotec Oy 1/34 TABLE OF CONTENTS

More information

PORTAL USER MANUAL. Mobeye WaterGuard-FS. Float sensor CM2300FS. SW version 5.n

PORTAL USER MANUAL. Mobeye WaterGuard-FS. Float sensor CM2300FS. SW version 5.n SW version 5.n PORTAL USER MANUAL Mobeye WaterGuard-FS Float sensor CM2300FS Attention! Very important This user manual contains important guidelines for the installation and usage of the Mobeye device

More information

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions SET-000 Oil/Sludge Alarm Device for Oil Separators Copyright 007 Labkotec Oy We reserve the right for changes without notice TABLE OF CONTENTS GENERAL... INSTALLATION... 4. SET-000 Oil/Sludge Control Unit...

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor Labkotec UK Ltd Adminicle House 1 Lumb Lane Audenshaw Manchester M34 5WH GREAT BRITAIN Tel: 0844 3350 477 Fax: 0161 4281 179 E-mail: info@labkotec.co.uk 10.8.2012 Internet: www.labkotec.co.uk 1/13 OilSET-1000

More information

SCAN200E USER S MANUAL

SCAN200E USER S MANUAL SCAN200E USER S MANUAL Code No. 2071 1052 rev. 1.4 Code No. 2071 1052 Rev. 1.4 Page 2/16 SCAN200E User s Manual Foreword This manual is for SCAN200E Controller running software version 2.03 or later. We

More information

USER S MANUAL HOME ENERGY SAVINGS REMOTE CAMERA INTERNET USER INTERFACE TEMPERATURE ALARMS BURGLARY PROTECTION DOOR SECURITY FIRE SAFETY

USER S MANUAL HOME ENERGY SAVINGS REMOTE CAMERA INTERNET USER INTERFACE TEMPERATURE ALARMS BURGLARY PROTECTION DOOR SECURITY FIRE SAFETY + USER S MANUAL 1.0 HOME ENERGY SAVINGS REMOTE CAMERA INTERNET USER INTERFACE TEMPERATURE ALARMS BURGLARY PROTECTION DOOR SECURITY FIRE SAFETY SECURITY KEYPAD WITH PROXIMITY TAGS PREVENTION OF WATER DAMAGES

More information

1. User features of the GSM dialer

1. User features of the GSM dialer 1. User features of the GSM dialer The JA60GSM dialer offers many useful features described in detail below. The installer should properly demonstrate the use of the system to the user after installation

More information

EZY SWITCH. SMS-IRR-4 System Monitor Installation Manual

EZY SWITCH. SMS-IRR-4 System Monitor Installation Manual EZY SWITCH SMS-IRR-4 System Monitor Installation Manual Table of Contents COMMANDS Getting Started Setting Up Initial User 7 Adding a User 8 Removing a User 8 Adding an Administrator 8 Removing the Administrator

More information

SC-F3G User Manual 1.0

SC-F3G User Manual 1.0 SC-F3G User Manual 1.0 Table of Contents 1. Introduction... 3 2. Functions... 3 3. Features... 3 4. Package Contents... 3 5. Device Configuration... 4 6. Status LED signals... 5 7. Before You Start...

More information

Other trade names mentioned in this document may be registered trademarks or trademarks of respective product manufacturers or vendor products.

Other trade names mentioned in this document may be registered trademarks or trademarks of respective product manufacturers or vendor products. Attention! Read this user manual carefully. Representative of the company installing the alarm system will explain which security module SP231 functions needs to be activated to ensure proper security

More information

OSA 3. Level alarm for oil separator. Afriso Ema AB. Kilvägen 2 SE Arlöv Sweden T +46-(0) F +46-(0)

OSA 3. Level alarm for oil separator. Afriso Ema AB. Kilvägen 2 SE Arlöv Sweden T +46-(0) F +46-(0) Level alarm for oil separator CONTENTS: Functional description... 2 Component parts... 3 Spare parts... 5 Safety regulations... 6 Checklist... 7 Installation... 8 Commissioning... 11 Operation... 14 Maintenance...

More information

ECO601 OPERATING INSTRUCTIONS ME04

ECO601 OPERATING INSTRUCTIONS ME04 RAK 72.2 9.11.2010 1 2 3 4 5 6 7 8 9 0 # ECO601 OPERATING INSTRUCTIONS ME04 PRESENTATION The ECO601 is intended for the simple control and surveillance of premises. This device can be controlled locally

More information

3G GSM AUTO DIALER. Remote monitoring & Control using your mobile phone. MODEL NUMBER 3GAD1

3G GSM AUTO DIALER. Remote monitoring & Control using your mobile phone.   MODEL NUMBER 3GAD1 3G GSM AUTO DIALER Remote monitoring & Control using your mobile phone www.gsm-activate.co.uk MODEL NUMBER 3GAD1 PAGE 1 Product Information Our 3G GSM Auto Dialer is a versatile unit which can be attached

More information

SCAN20 Series Gas Detection Controller

SCAN20 Series Gas Detection Controller SCAN20 Series Gas Detection Controller USER S MANUAL Code Number 2071 1022 SCAN20 USER S MANUAL Code no. 2071 1022 Page 1/14 Foreword This manual is made for SCAN20 Controllers equipped with the software

More information

GSM 3G AUTO DIALLER. Remote monitoring & Control using your mobile phone. MODEL NUMBER 3GAD1

GSM 3G AUTO DIALLER. Remote monitoring & Control using your mobile phone.   MODEL NUMBER 3GAD1 GSM 3G AUTO DIALLER Remote monitoring & Control using your mobile phone www.gsm-activate.co.uk MODEL NUMBER 3GAD1 PAGE 1 Product Information Our GSM 3G Auto Dialer is a versatile unit which can be attached

More information

1. Functions of GPS locator ETLOC-30S 3

1. Functions of GPS locator ETLOC-30S 3 Contents 1. Functions of GPS locator ETLOC-30S 3 1.1 Direct view of the vehicle position on the map 3 1.2 Vehicle security 3 1.2.1 Vehicle protection 3 1.2.1.1 GPS protection 3 1.2.1.2 GPS higher level

More information

IP & SMS Alarm Communicator

IP & SMS Alarm Communicator Models: WGSMSC You deserve to feel safe, secure & protected IP & SMS Alarm Communicator Quick Start Guide Thank you for purchasing a Watchguard IP & SMS Alarm Communicator This Quick Start Guide covers

More information

with internal sensor (channel 1) with an external sensor (channel 2) A-Editor software, Professional AK20 version (not for version AK4)

with internal sensor (channel 1) with an external sensor (channel 2) A-Editor software, Professional AK20 version (not for version AK4) Examples of use Example Creating an SMS-based alarm with confirmation A project file must first be created using the A-Editor software. This project file is then stored in the alarm modem. The alarm modem

More information

COMMUNICATOR ET08 / ET081

COMMUNICATOR ET08 / ET081 COMMUNICATOR ET08 / ET081 User Manual v1.2 Safety instructions Please read and follow these safety guidelines in order to maintain safety of operators and people around: GSM communicator ET08 / ET081 (further

More information

SMART SWITCH TECHNOLOGIES. SmartSwitch Yacht-Guard Model SMS-8 Vessel System Monitor Installation Manual

SMART SWITCH TECHNOLOGIES. SmartSwitch Yacht-Guard Model SMS-8 Vessel System Monitor Installation Manual SMART SWITCH TECHNOLOGIES SmartSwitch Yacht-Guard Model SMS-8 Vessel System Monitor Installation Manual Table of Contents System / Connections 4 Outputs 5 Inputs 6 COMMANDS Getting Started Setting Up Initial

More information

Any additional devices linked to the system ET08 (computer, sensors, relays etc.) must be approved by LST EN standard.

Any additional devices linked to the system ET08 (computer, sensors, relays etc.) must be approved by LST EN standard. COMMUNICATOR ET08 User Manual v1.0 Safety instructions Please read and follow these safety guidelines in order to maintain safety of operators and people around: GSM communicator (gateway) ET08 (further

More information

2G & 3G GSM Door Contact Alarm

2G & 3G GSM Door Contact Alarm 2G & 3G GSM Door Contact Alarm www.gsm-activate.co.uk MODEL RF - PIR PAGE 1 Product Information Our 2G/3G GSM Door Contact Alarm is a standalone alarm system for smaller rooms inside properties. It will

More information

Version 1.03 January-2002 USER S MANUAL

Version 1.03 January-2002 USER S MANUAL Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...

More information

User Manual & Setting Instructions

User Manual & Setting Instructions WT-9001 IP65 GSM Remote Controll And Allarm System User Manual & Setting Instructions WW II TT UU RR AA CC OO RR PPOO RR AA TT II OO NN SS DDNN BB HH DD WT-9001 IP65 GSM REMOTE CONTROL AND ALARM SYSTEM

More information

Snitcher. Installation Instructions

Snitcher. Installation Instructions Snitcher Installation Instructions IMPORTANT: Register your Snitcher Text alert system onboard SIM before installing and/or powering up the system (see setup and operating instructions). The system must

More information

Ontech GSM 9040/50. Reference Manual English -1 -

Ontech GSM 9040/50. Reference Manual English -1 - Ontech GSM 9040/50 Reference Manual English -1 - Content Welcome... 5 This manual... 5 Text styles... 5 Support... 5 Disclaimer... 5 Overview... 6 Accessories... 6 External temperature sensor 9901... 7

More information

GSM AUTO DIALLER WIRELESS ALARM SYSTEM MODEL AD-SD MODEL AD-SD-W www.gsm-activate.co.uk Model AD-SD & Model AD-SD-W PAGE 1 Product Information Our AD-SD Auto Dialler is a versatile unit which can be attached

More information

Labkotec Level Instruments Protecting our environment

Labkotec Level Instruments Protecting our environment Labkotec Level Instruments Protecting our environment Labko SET Alarm Devices SolarSET Alarm Unit LID-3300IP Ice Detector LOKASET R Wireless Alarm Device POP-22 EX Level Controller LabkoMax and LabkoFlex

More information

PERMACONN PM1030 Includes DI300. Installation Manual

PERMACONN PM1030 Includes DI300. Installation Manual PERMACONN PM1030 Includes DI300 Installation Manual Radio Data Comms Unit 5/20-30 Stubbs Street Silverwater NSW 2128 Telephone: 02 9352 1777 Facsimile: 02 9352 1700 Introduction The PERMACONN system provides

More information

DualCom GradeShift UDL QUICK GUIDE & INSTRUCTION MANUAL

DualCom GradeShift UDL QUICK GUIDE & INSTRUCTION MANUAL DualCom GradeShift UDL QUICK GUIDE & INSTRUCTION MANUAL The most trusted brand in Alarm Signalling www.csldual.com @CSLDualCom CSL DualCom Limited Figure 1 - GradeShift UDL SIM card slot Service LED Aerial

More information

Watchguard WGAP864 User Manual

Watchguard WGAP864 User Manual Watchguard WGAP864 User Manual v1.0 Issued September 2016 1 2 Table of Contents Glossary... 5 1. Introduction to your Watchguard WGAP864... 6 2. Before Operating your Alarm System... 6 3. Understanding

More information

Sintrol Snifter A2 EX. Manual. Version 1.2.3

Sintrol Snifter A2 EX. Manual. Version 1.2.3 Sintrol Snifter A2 EX Manual Version 1.2.3 Table of Contents 1 INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 4 1.3 How does it work?... 4 2 INSTALLATION... 4 2.1 Selecting the installation

More information

Contents 1 Set Up 2 Gateway information 3 Operation of the App 4 Troubleshooting Description of sensors. 1 Set Up. 1.1 Connect the Gateway

Contents 1 Set Up 2 Gateway information 3 Operation of the App 4 Troubleshooting Description of sensors. 1 Set Up. 1.1 Connect the Gateway Contents 1 Set Up 2 Gateway information 3 Operation of the App 4 Troubleshooting Description of sensors 1 Set Up After downloading the Weatherhub app, follow these steps: 1.1 Connect the Gateway Connect

More information

Memcom Emergency Telephone

Memcom Emergency Telephone Memcom Emergency Telephone Installation Guide Ref No. 450 900 (GB) Version 2 + + Simple wiring for quick installation + + Integrated LCD display shows you what you have programmed + + All code based programming

More information

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47) DIESEL ENGINE CONTROL UNIT DCU 205 - USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) 64 84 52 00 Fax: (+47) 64 84 52 12 office@auto-maskin.no - 1 - TABLE OF CONTENTS 1. INTRODUCTION TO THE DCU 205...4

More information

ECO N DATE DESCRIPTION OF CHANGE CHG

ECO N DATE DESCRIPTION OF CHANGE CHG Model Number: M21E-24-DIN Description: The product is a loop powered device which controls an unsupervised dual pole output channel suitable to manage 24VAC loads. The M21E-24-DIN is micro-controller operated,

More information

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE isocket Smart Relay is a complex Smart House system which is installed in the fuse cabinet (electric cabinet) in the house. We therefore assume that

More information

Remote monitoring for technical condition of buildings and constructions

Remote monitoring for technical condition of buildings and constructions Remote monitoring for technical condition of buildings and constructions Tieto-Oskari Oy Syväojankatu 3 B, FI-87700 Kajaani, Finland www.tieto-oskari.fi AKKE S-MEASURE automated monitoring system is developed

More information

Universal Monitoring System. Model IMEC8A. User Manual Version 1.10 Software version 2.3.1

Universal Monitoring System. Model IMEC8A. User Manual Version 1.10 Software version 2.3.1 Unit 7/8, Heathrow Causeway Estate, Ariel Way, Hounslow Middlesex, TW4 6JW +44 (0) 208 6302270 www.cpcuk.co.uk Universal Monitoring System Model IMEC8A User Manual Version 1.10 Software version 2.3.1-1

More information

DigiAir QUICK GUIDE & INSTRUCTION MANUAL

DigiAir QUICK GUIDE & INSTRUCTION MANUAL DigiAir QUICK GUIDE & INSTRUCTION MANUAL The most trusted brand in Alarm Signalling www.csldual.com @CSLDualCom CSL DualCom Limited Figure 1 - DigiAir Yellow Comms LED Red Fault LED Yellow Service LED

More information

2G & 3G GSM Portable PIR Alarm

2G & 3G GSM Portable PIR Alarm 2G & 3G GSM Portable PIR Alarm www.gsm-activate.co.uk MODEL RF - PORTABLE-PIR PAGE 1 Product Information Our 2G/3G Portable PIR Alarm is a standalone alarm system suitable for indoors or outside usage.

More information

PROTECTION CABINETS SUPERVISION CABINETS FOR AUTOMATIC EXTERNAL DEFIBRILLATORS (AEDs)

PROTECTION CABINETS SUPERVISION CABINETS FOR AUTOMATIC EXTERNAL DEFIBRILLATORS (AEDs) PROTECTION CABINETS SUPERVISION CABINETS FOR AUTOMATIC EXTERNAL DEFIBRILLATORS (AEDs) FEATURES OF AIVIA PROTECTION MODELS H : 423 mm The Aivia range has been designed and manufactured by the French company

More information

EWP2WIRELESS MOTION DETECTOR

EWP2WIRELESS MOTION DETECTOR EN EWP2WIRELESS MOTION DETECTOR User manual v1.2 Compatible with: ESIM364 v02.08.00 and up. EPIR3 v1.2.0 and up EPIR2 v01.03.02 and up Main features: Built-in dual element passive infrared (PIR) sensor.

More information

Getting Started with Live Exceptions

Getting Started with Live Exceptions Getting Started with Live Exceptions Live Exceptions provides alarm reporting by identifying problems that include delay, errors, failures, security, or configuration changes. The Live Exceptions Browser

More information

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use! Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 74363 Güglingen Telefon +49 7135-102-0 Service +49 7135-102-211 Telefax +49 7135-102-147 info@afriso.de

More information

Thank you for buying a DEVI product. With this purchase you have obtained a product of the highest quality, designed to give long lasting comfort at

Thank you for buying a DEVI product. With this purchase you have obtained a product of the highest quality, designed to give long lasting comfort at Devireg 550 INT Thank you for buying a DEVI product. With this purchase you have obtained a product of the highest quality, designed to give long lasting comfort at a minimum of environmental impact. 2

More information

Labkotec Ice Detector

Labkotec Ice Detector Labkotec Ice Detector LID 3300IP Level and flow know-how since 1964 Benefits of using Ice Detector Stops wind turbine to prevent icethrow Safety first of all! Safety device Authorities / construction licence

More information

0KITMGSM00 KIT FOR BOILER CONTROL THROUGH GSM FOR ITACA - FORMENTERA INSTALLATION USE AND MAINTENANCE

0KITMGSM00 KIT FOR BOILER CONTROL THROUGH GSM FOR ITACA - FORMENTERA INSTALLATION USE AND MAINTENANCE 0KITMGSM00 KIT FOR BOILER CONTROL THROUGH GSM FOR ITACA - FORMENTERA INSTALLATION USE AND MAINTENANCE Dear Sirs, thank you for choosing and buying our GSM kit. Please read these instructions carefully

More information

Monitoring Operator Guide. Access Control Manager Software Version

Monitoring Operator Guide. Access Control Manager Software Version Monitoring Operator Guide Access Control Manager Software Version 5.10.10 2018, Avigilon Corporation. All rights reserved. AVIGILON, the AVIGILON logo, ACCESS CONTROL MANAGER, ACM, ACM VERIFY AND TRUSTED

More information

Monitoring Solutions

Monitoring Solutions GSM Systems Monitor: Temperature, Humidity, Power, Water, Smoke, Carbon Monoxide and More September 2016 Table of Contents GSM Systems... 3 Argon 100 GSM... 3 Ares 12 & 14 GSM... 4 Poseidon2 4002... 5

More information

Avigilon Control Center 5 System Integration Guide

Avigilon Control Center 5 System Integration Guide Avigilon Control Center 5 System Integration Guide with Hirsch Velocity INT-HIRSCH-B-Rev1 2012 2014 Avigilon Corporation. All rights reserved. Unless expressly granted in writing, no license is granted

More information

Avigilon System Integration Guide. Avigilon Control Center with AMAG Symmetry Security Management System 7.0

Avigilon System Integration Guide. Avigilon Control Center with AMAG Symmetry Security Management System 7.0 Avigilon System Integration Guide Avigilon Control Center with AMAG Symmetry Security Management System 7.0 2013-2016, Avigilon Corporation. All rights reserved. AVIGILON, the AVIGILON logo, HDSM, HIGH

More information

2G & 3G GSM Wireless Beam Alarm

2G & 3G GSM Wireless Beam Alarm 2G & 3G GSM Wireless Beam Alarm www.gsm-activate.co.uk MODEL RF - BEAM PAGE 1 Product Information Our 2G/3G GSM Wireless Beam Alarm is a standalone alarm system suitable for indoor and outside use. It

More information

Heating is great when you control it. USER MANUAL. Wireless Programmable Room Thermostat. Model No.: LS Scan for App

Heating is great when you control it. USER MANUAL. Wireless Programmable Room Thermostat. Model No.: LS Scan for App Heating is great when you control it. USER MANUAL Wireless Programmable Room Thermostat Model No.: LS99111010 Scan for App Contents 1. Overview... 01 2. System Installation... 02 2.1 Install and Wiring

More information

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English Rectifier RC-series Manual RC-series English Manual Wall and 19 English Presentation The RC-series is a rectifier for either directly powering the load or for use together with batteries. It is designed

More information

SAFETY INFORMATION AND WARNINGS

SAFETY INFORMATION AND WARNINGS This manual refers to the Model SST-3 control panel manufactured since October 31, 2013, which uses a universal (100 277 VAC; 50/60 Hz) power supply. Older units use a voltage-specific power supply and

More information

Ion Gateway Cellular Gateway and Wireless Sensors

Ion Gateway Cellular Gateway and Wireless Sensors Page 1 of 9 Account & Network Setup If this is your first time using the Ion Gateway online system site you will need to create a new account. If you have already created an account you can skip to the

More information

PitBoss User Manual. Version /24/2013 Copyright 2013 PumpAlarm.com, LLC

PitBoss User Manual. Version /24/2013 Copyright 2013 PumpAlarm.com, LLC PitBoss User Manual Version 1.5 10/24/2013 Copyright 2013 PumpAlarm.com, LLC www.pumpalarm.com 1 CONTENTS Introduction... 4 How Does the PitBoss Work... 4 What Comes With Your PitBoss... 5 Getting to Know

More information

Fitting instructions

Fitting instructions Fitting instructions Ver. 02_English 02. 11. 2017 CONTENT 1 INTRODUCTION... 3 2 FITTING THE PATRIOT EU... 3 2.1 Electronic diagram... 3 2.2 Fitting instructions... 4 2.3 Final placement... 4 2.4 Alarm

More information

SCHMIDT LED Measured Value Display MD Instructions for Use

SCHMIDT LED Measured Value Display MD Instructions for Use SCHMIDT LED Measured Value Display MD 10.010 Instructions for Use Table of Contents 1 Important Information... 3 2 Application range... 4 3 Mounting instructions... 4 4 Electrical connection... 6 5 Signalizations...

More information

USER S MANUAL 1.0. Read this manual carefully and keep it together with the unit.

USER S MANUAL 1.0. Read this manual carefully and keep it together with the unit. USER S MANUAL 1.0 Read this manual carefully and keep it together with the unit. Contents 1. INTRODUCTION... 3 1.1 FIRST STEPS... 4 1.1.1 Deciding on the GSM Subscription... 4 1.1.2 Switching PIN Code

More information

Сontrol panel Contact GSM-9N

Сontrol panel Contact GSM-9N Сontrol panel Contact GSM-9N Data sheet Device identification number 2 1. General Information The Contact GSM-9N control panel (hereinafter referred to as the device) is designed for setting up security

More information

IRIS Touch Firmware Enhancements and Additions from Version to Version

IRIS Touch Firmware Enhancements and Additions from Version to Version Overview IRIS Touch Firmware Enhancements and Additions from Version 1.14.3 to Version 1.19.1 This document details enhancements to the feature set of the IRIS Touch from firmware Version 1.14.3 to Version

More information

RMS Monitoring Software System Startup

RMS Monitoring Software System Startup System Startup 2017 ROTRONIC AG Bassersdorf Switzerland 2017 ROTRONIC AG Bassersdorf Switzerland Page 2 of 53 Contents Contents... 3 1 Overview... 5 1.1 System Requirements... 5 1.1.1 Browser... 5 2 Create

More information

USER MANUAL S203. Controller for three circuits. - control for 2 heating circuits - 1 domestic hot water control. Saving energy, creating comfort

USER MANUAL S203. Controller for three circuits. - control for 2 heating circuits - 1 domestic hot water control. Saving energy, creating comfort USER MANUAL S203 Controller for three circuits - control for 2 heating circuits - 1 domestic hot water control Saving energy, creating comfort This user manual consists of two parts. Issues that are intended

More information

Security System. User s Guide for the Text Command Center

Security System. User s Guide for the Text Command Center User s Guide for the Text Command Center MY ALARM COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY CONTROL PANEL IS CONNECTED TO THE PHONE JACK LOCATED:

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

EKB3W WIRELESS LED KEYPAD

EKB3W WIRELESS LED KEYPAD EKB3W WIRELESS LED KEYPAD User manual v1.6 Compatible with: ESIM364 all versions. EPIR v05.06.02 and up + EWT2 v16.17 and up. EPIR2 all versions. EPIR3 all versions. Main features: Alarm system arming

More information

V1.0. Smart Home Alarm System. User Manual. APP download via QR Code scanning. Please read the manual carefully before using.

V1.0. Smart Home Alarm System. User Manual. APP download via QR Code scanning. Please read the manual carefully before using. V1.0 Smart Home Alarm System User Manual APP download via QR Code scanning Please read the manual carefully before using. Content FUNCTION PROFILE 2 THE SCHEMATIC GRAPH OF HOST 3 PROCESS OF BOOTING 6 OPERATION

More information

1. Introduction. 2. Product overview

1. Introduction. 2. Product overview 1. Introduction The AG400011 GSM Alarm panel is a control panel that is compatible with other H-net security devices from Everspring, such as wireless sensors, remote keyfobs, tags, and keypad. With this

More information

SCS311 / SCS317 Installation Instructions

SCS311 / SCS317 Installation Instructions SCS311 / SCS317 Installation Instructions SCS311 or SCS317 Wireless Programmable Room Thermostat Programmable room thermostats are widely recognised as one of the best ways in which to control central

More information

Avigilon Control Center System Integration Guide

Avigilon Control Center System Integration Guide Avigilon Control Center System Integration Guide with Velocity INT-HIRSCH-A-Rev3 Copyright 2013 Avigilon. All rights reserved. No copying, distribution, publication, modification, or incorporation of this

More information

FCD-wire Contents. List of Figures

FCD-wire Contents. List of Figures FCD-wire Contents FCD-X21 Configuration 1 Introduction... 1 2 Opening the FCD Application... 1 3 FCD Window... 2 4 FCD LEDs... 3 5 Configuration Operations... 4 FCD Info...4 FCD System Info...5 FCD Interface

More information

Milestone SMI Intrepid II Perimeter Module 1.1 User s Manual

Milestone SMI Intrepid II Perimeter Module 1.1 User s Manual Milestone SMI Intrepid II Perimeter Module 1.1 User s Manual Target Audience for this Document This document is aimed at system users and provides descriptions on how to install and maintain the Milestone

More information

Ref. 1067/024 Ref. 1067/032A Ref. 1067/052A

Ref. 1067/024 Ref. 1067/032A Ref. 1067/052A DS1067-062C Mod. 1067 LBT20063 REMOTE CONTROLLABLE ALARM CONTROL PANELS Ref. 1067/024 Ref. 1067/032A Ref. 1067/052A USER MANUAL TABLE OF CONTENTS INTRODUCTION... 6 1 CONTROL DEVICES... 7 1.1 1067/022 keypad

More information

Preface. Thank you for purchasing our GSM Security Alarm System ( The System )! The System will keep your home and property safe around the clock.

Preface. Thank you for purchasing our GSM Security Alarm System ( The System )! The System will keep your home and property safe around the clock. Preface Thank you for purchasing our GSM Security Alarm System ( The System )! The System will keep your home and property safe around the clock. The GSM Security Alarm ( The Alarm ) adopts the most advanced

More information

3D_ISS. Integrated Software System. User Guide Manual

3D_ISS. Integrated Software System. User Guide Manual 3D Digital Design & Development LTD 58/60 Edward Road Tribec House New Barnet EN4 8AZ 020 8440 7060 3D_ISS Integrated Software System User Guide Manual Copyright 2014 3D Digital Design and Development

More information

Elderly Care Alarm System

Elderly Care Alarm System Introduction 24/7 Peace of mind for your family The GSM Elderly Care Alarm System is a new released smart solution for take care of senior, aged, elder or disabled people on their daily life. Big LED display

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

MAKING MODERN LIVING POSSIBLE INT INT EFIT 550. User Guide and Installation Manual. Danfoss Heating

MAKING MODERN LIVING POSSIBLE INT INT EFIT 550. User Guide and Installation Manual. Danfoss Heating MAKING MODERN LIVING POSSIBLE EFIT 550 User Guide and Installation Manual Danfoss Heating Thank you for buying a Danfoss product. With this purchase you have obtained a product of the highest quality,

More information

D3D Wi-Fi GSM Smart Alarm System -User Manual

D3D Wi-Fi GSM Smart Alarm System -User Manual D3D Wi-Fi GSM Smart Alarm System -User Manual D3D Wi-Fi / GSM Smart Alarm system (Model : D10). Please read all instructions carefully & follow steps for easy home installation. 1 P a g e D3D Wi-Fi / GSM

More information

To activate using remote control: press [ ] key once. To activate using keyboard: on panel keyboard [ ] keys once.

To activate using remote control: press [ ] key once. To activate using keyboard: on panel keyboard [ ] keys once. Table of Content 1.1General Description----------------------------------------------------------------------2 2.2System Setup-----------------------------------------------------------------------------3

More information

User manual and installation guide

User manual and installation guide User manual and installation guide 31046005 Copyright Phason Inc. All rights reserved. Printed in Canada About the manual The manual describes the features of your control and how to use them; it does

More information

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0 User s Guide SUB-MA7240O-0001.OG.Solution40-111.doc Created: 6/05/03 Last Updated: 23/09/03 MA7240AO-0001 Version 1.0 2 Table Of Contents User List...6 Quick Reference..7 Features...7 Keypad User's Guide...8

More information

Alarms Updated 03/26/2018

Alarms Updated 03/26/2018 Updated 03/26/2018 Table of Contents Alarms Alarms in OneView...1 Types of Alarms...1 Setting up Alarms...2 Alarm Configuration...4 Customize Alarm Parameters...5 List of Configured Alarms...7 Acknowledging

More information

Making the Most of Alarms

Making the Most of Alarms Making the Most of Alarms Leverage the alarm management features of MPA to address network performance problems more effectively. Blueprint to Leverage Alarms and Alerts Using Mitel Performance Analytics

More information

Products no longer available

Products no longer available Technical data sheet MONICO-.. Turnkey automation station MONICO-.. Forms an efficient fire protection system together with the motorisation sets BF(G)24MP Completely wired controller in matching control

More information