Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Size: px
Start display at page:

Download "Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM"

Transcription

1 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No ] All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors, moisture, environmental contaminants, or other foreign materials into the piping. Submittal Date: Fri Apr 15 14:53:33 EDT 2016 Response Message: The deletion of this language is editorial as the exact language is already provided in Section Public Comment No. 25-NFPA 17A-2015 [Section No ]

2 2 of 14 6/22/2016 3:15 PM Second Revision No. 2-NFPA 17A-2016 [ Section No ] The protection device shall blow off, blow open, or blow out upon agent discharge. Submittal Date: Fri Apr 15 14:55:19 EDT 2016 Response Message: The deletion of this language is editorial as the exact language is already provided in Section Public Comment No. 26-NFPA 17A-2015 [Section No ]

3 3 of 14 6/22/2016 3:15 PM Second Revision No. 7-NFPA 17A-2016 [ Section No ] * A placard shall be conspicuously placed near each Class K extinguisher that states that the fire protection system shall be activated prior to using the fire extinguisher. [ 96: ] Submittal Date: Fri Apr 15 17:44:48 EDT 2016 Response Message: "Class K" was added to this requirement to clearly state which extinguishers need a placard.

4 4 of 14 6/22/2016 3:15 PM Second Revision No. 6-NFPA 17A-2016 [ New Section after ] Shutoff Devices On actuation of any cooking equipment fire extinguishing system, all sources of fuel and electric power that produce heat to all equipment protected by the system shall be shut down Gas appliances not requiring protection but located under the same ventilation equipment shall also be shut off Steam supplied from an external source shall not be required to be shut down Solid fuel cooking operations shall not be required to be shut down If the expellant gas is used to pneumatically operate these devices, the gas connection shall be prior to entry into the wet chemical tank Shutoff devices shall require manual resetting prior to fuel or power being restored A hood exhaust fan(s) shall continue to operate after the extinguishing system has been activated unless fan shutdown is required by a listed component of the ventilation system or by the design of the extinguishing system. [96: ] When the fire-extinguishing system activates, makeup air supplied internally to a hood shall be shut off. [96:8.3.2] Submittal Date: Fri Apr 15 17:36:00 EDT 2016 After reconsideration, and at the advice of the Task Group assigned to review this material, requirements , , , and (of the current NFPA 17A 2013 edition text) are needed for proper operation of a wet chemical system. Response Message: Public Comment No. 10-NFPA 17A-2015 [New Section after ]

5 5 of 14 6/22/2016 3:15 PM Public Comment No. 11-NFPA 17A-2015 [New Section after ] Public Comment No. 12-NFPA 17A-2015 [New Section after ] Public Comment No. 13-NFPA 17A-2015 [New Section after ] Public Comment No. 14-NFPA 17A-2015 [New Section after ]

6 6 of 14 6/22/2016 3:15 PM Second Revision No. 11-NFPA 17A-2016 [ Section No ] 4.6.1* The wet chemical used in the system shall be listed for the particular system, and the system manufacturer shall be required to specify that particular chemical in the manufacturer s design, installation, and maintenance manual. Submittal Date: Mon May 09 22:04:48 EDT 2016 Response Message: Removing the struck text from FR-6 clarifies that it is the system manufacturer, not the wet chemical manufacturer, that specifies the appropriate wet chemical.

7 7 of 14 6/22/2016 3:15 PM Second Revision No. 4-NFPA 17A-2016 [ Section No ] Wet chemical containers and expellant gas assemblies shall be located and arranged so that inspection, testing, recharging, and other maintenance activities are facilitated. Submittal Date: Fri Apr 15 17:17:23 EDT 2016 Response Message: Section was removed to eliminate redundancy with Section which provides more concise language to clarify the intent of the requirement. Public Comment No. 28-NFPA 17A-2015 [Section No ]

8 8 of 14 6/22/2016 3:15 PM Second Revision No. 3-NFPA 17A-2016 [ Section No ] A Any equipment installed in the path of exhaust products that provides secondary filtration or air pollution control unit, whether or not it includes an ignition source, shall be protected either provided with a separate an approved automatic fire-extinguishing suppression system, installed in accordance designed to operate simultaneously with the activation of the automatic fire-extinguishing suppression system protecting the ventilation hood(s) being served or with a single automatic fire suppression system that protects both the secondary filtration or air pollution control unit and the hood(s) being served. manufacturer s instructions. [ 96: 9.3.3] Submittal Date: Fri Apr 15 17:09:20 EDT 2016 Response Message: The ICC Codes do not adopt NFPA 96 and in order for this requirement to be recognized, it must stay in NFPA 17A. The extracted text from Section of the 2017 edition of NFPA 96 provides concise language to address the intent of this requirement. Public Comment No. 15-NFPA 17A-2015 [Section No ] Public Comment No. 23-NFPA 17A-2015 [Section No ]

9 9 of 14 6/22/2016 3:15 PM Second Revision No. 12-NFPA 17A-2016 [ Section No [Excluding any Sub-Sections] ] Parts that are found during maintenance that could cause an impairment or failure of operation of the system shall be replaced by listed components as required by Section 4.1 in accordance with the manufacturer's instructions. Submitter Full Name: Jacqueline Wilmot Organization: National Fire Protection Assoc Submittal Date: Wed May 18 11:45:01 EDT 2016 : Some manuals don't recognize components described in NFPA 17A, section 4.1. Response Message: Public Comment No. 29-NFPA 17A-2015 [Section No [Excluding any Sub-Sections]]

10 10 of 14 6/22/2016 3:15 PM Second Revision No. 8-NFPA 17A-2016 [ Section No ] Fusible links manufactured more than 2 years prior to the installation date shall not be permitted to be installed. Submittal Date: Fri Apr 15 17:47:52 EDT 2016 Response Message: After reconsideration of the First Draft Report, there is no evidence that fusible links have a finite shelf life. This revision removes Section from the standard. See SR. No. 9 (which revises associated annex language.).

11 11 of 14 6/22/2016 3:15 PM Second Revision No. 10-NFPA 17A-2016 [ Section No. A ] A Pre-engineered systems protect hazards posed by the duct, plenum, and cooking surfaces of appliances and are defined by the manufacturer s design, installation, and maintenance manual. Fires that start outside the protected area might not be extinguished by the pre-engineered system. An example is shown in Figure A Figure A Nozzle location and area protected. Submittal Date: Fri Apr 15 18:00:52 EDT 2016 Response Message: The figure does not correctly illustrate the protected area and the annex language can stand on it's own. In addition, this figure is a proprietary reference and should not be included in the standard.

12 12 of 14 6/22/2016 3:15 PM Second Revision No. 9-NFPA 17A-2016 [ Section No. A ] A The date of manufacture marked on fusible metal alloy temperature-sensing elements does not limit when they can be used. The intent of is to require replacement of fusible metal alloy temperature-sensing elements that have been installed for up to 6 months in environments subjecting them to contaminant loading, such as grease in restaurant hoods and ducts, that could adversely affect their proper operation. Submittal Date: Fri Apr 15 17:56:36 EDT 2016 Response Message: There is no shelf life as indicated in the annex for multiple editions of the standard. Mandating a maximum 2 year life is excessive for enforcement.see SR. No. 8 (which revises associated language in the body of the standard).

13 13 of 14 6/22/2016 3:15 PM Second Revision No. 5-NFPA 17A-2016 [ New Section after B.11 ] Annex C Systems for Protection of Residential Stoves When Used in Other than Commercial Cooking Operations This annex is not a part of the requirements of this NFPA document but is included for informational purposes only. C.1 Only pre-engineered wet chemical extinguishing systems, including piping and detection, that have been listed by a nationally recognized testing laboratory to ANSI/UL 300, Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment, or UL 300A, Outline of Investigation for Extinguishing System Units for Residential Range Top Cooking Surfaces, should be installed to protect residential stoves where used in other than commercial cooking operations. C.2 The area to be protected should be the cook top surface of a residential stove within the dimensions listed in the manufacturer s design, installation, and maintenance manual. C.3 Each protected cook top should be provided with a listed fire detection device or devices specified in the manufacturer s design, installation, and maintenance manual to automatically actuate the extinguishing system. C.4 Manual actuation should be provided in the path of egress as per the manufacturer s design, installation, and maintenance manual. C.5 Only the type of hose/pipe and fittings listed in the manufacturer s design, installation, and maintenance manual and provided as part of the pre-engineered extinguishing system should be used. C.6 All discharge nozzles should be located to minimize damage or misalignment and within the limitations and constraints of the manufacturer s design, installation, and maintenance manual. C.7 The location of the agent container should be within the limitations and constraints of the manufacturer s design, installation, and maintenance manual and in accordance with Section 5.4. C.8 The system should shut off the fuel (gas/electric) to the residential stove being protected. C.9 The system should be provided with an audible or visual indicator to show that the system has operated, that personnel response is needed, and that the system is in need of recharge. C.10 The extinguishing system should be connected to the fire alarm system, if provided, in accordance with the requirements of NFPA 72 so that the actuation of the extinguishing system will sound the fire alarm. Supplemental Information File Name ANNEX_C_MTL.docx Description New Annex C Material

14 14 of 14 6/22/2016 3:15 PM Submittal Date: Fri Apr 15 17:31:32 EDT 2016 Response Message: The Technical developed this annex language to be used as a model enabling document for these types of systems to be used in the field for appropriate applications. The language was developed with considerations from public inputs #s 87, 83, 80, 86, 85, 82 and committee input # 21.

15 ANNEX C SYSTEMS FOR PROTECTION OF RESIDENTIAL STOVES WHEN USED IN COMMERCIAL OCCUPANCIESOTHER THAN COMMERCIAL COOKING OPERATIONS This annex is not part of the requirements of this NFPA document but is included for informational purposes only. C.1 Only pre-engineered wet chemical extinguishing systems, including piping and detection, that have been listed by a nationally recognized testing laboratory to UL 300 OR Subject 300A should be installed to protect residential stoves when used in other than commercial occupancies.cooking operations. C.2 The area to be protected should be the cook top surface of a residential stove within the dimensions listed in the manufacturer s design, installation, and maintenance manual. C.3 Each protected cook top should be provided with a listed fire detection device or devices specified in the manufacturer s design, installation, and maintenance manual to automatically actuate the extinguishing system.

16 C.4 Manual actuation should be provided in the path of egress as per the manufacturer s design, installation, and maintenance manual. C.5 Only the type of hose/pipe and fittings listed in the manufacturer s design, installation, and maintenance manual, and provided as a part of the pre- engineered extinguishing system should be used. C.6 All discharge nozzles should be located to minimize damage or misalignment and within the limitations and constraints of the manufacturer s design, installation, and maintenance manual. C.7 The location of the agent container should be within the limitations and constraints of the manufacturer s design, installation, and maintenance manual and in accordance with NFPA 17A, section 5.4. C.8 The system should shut off the fuel (gas/electric) to the residential stove being protected. C.9 The system should be provided with an audible or visual indicator to show that the system has operated, that personnel response is needed, and that the system is in need of recharge.

17 C.10The extinguishing system should be connected to the fire alarm system, if provided, in accordance with the requirements of NFPA 72, National Fire Alarm and Signaling Code, so that the actuation of the extinguishing system will sound the fire alarm.

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

NFPA 96, 2017 REVIEW SUMMARY

NFPA 96, 2017 REVIEW SUMMARY NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments: Second Revision No. 3-NFPA 31-2015 [ Section No. 10.5.1 ] 10.5.1* Oil burners, other than oil stoves with integral tanks, shall be provided with some means for manually stopping the flow of oil to the

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 FREQUENTLY ASKED QUESTIONS CONCERNING COMMERCIAL COOKING PROTECTION Published by FIRE ENGINEERING DIVISION

More information

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Second Revision No. 2-NFPA [ Section No ]

Second Revision No. 2-NFPA [ Section No ] Page 1 of 8 Second Revision No. 2-NFPA 410-2014 [ Section No. 10.2 ] 10.2* Fire Extinguishers. In addition to extinguishers required by NFPA 409, extinguishers shall be provided for aircraft maintenance

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

Page 1 of 12 Input No. 62-NFPA 409-2013 [ Section No. 3.3.9 ] 3.3.9 Hangar Building Cluster. A group of buildings with more than one area for the storage and servicing of aircraft and all attached or contiguous

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-21 21 03.00 10 February 2009) ---------------------------------- Preparing Activity: USACE Superseding UFGS-21 21 03.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 496-2014 [ Section No. 5.2.2 ] 5.2.2 Where When the enclosure has been opened or if the protective gas supply has failed to maintain the required positive pressure, the enclosure

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting.

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting. Input No. 7-NFPA 80-2013 [ Section No. 3.3.8 ] 3.3.8 Automatic Fire Detector. A device designed to detect the presence of a fire signature and to initiate action. For the purpose of this standard, automatic

More information

Page 1 of 126 First Revision No. 113-NFPA 45-2013 [ Global Input ] Change all references to Material Safety Data Sheets (MSDS) to Safety Data Sheets (SDS) Submittal Date: Thu May 09 11:40:44 EDT 2013 Response

More information

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Second Revision No. 3-NFPA [ Section No. 2.3 ] Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler

More information

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM of 66 5/18/2015 1:01 PM Second Revision No. 36-NFPA 32-2015 [ Detail ] 6.5 Solvents (See Annex C for additional information on solvents) Submittal Date: Tue Mar 17 17:20:03 EDT 2015 Committee Statement:

More information

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

WORKING DRAFT OF COMMITTEE MEETING OUTPUT WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF SECOND DRAFT REPORT Document: NFPA 221 Revision Cycle: A2014 Meeting Date: 5/20/2013

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

Types of Detection. Fusible Link Detection - Most Common

Types of Detection. Fusible Link Detection - Most Common Types of Detection Fusible Link Detection - Most Common Types of Detection Electric Detection Types of Detection Pneumatic Detection-Tubing Pneumatic Tubing 3 Year Service life Survey Hazard 1) List all

More information

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,

More information

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN) 4 of 326 11/21/2013 1:03 PM First Revision No. 161-NFPA 72-2013 [ Section No. 3.3.11 ] 3.3.11 Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

NFPA 37 Public Comment Responses Page 1 of 32

NFPA 37 Public Comment Responses Page 1 of 32 of 30 11/4/2016 3:05 PM Public Comment No. 6-NFPA 37-2016 [ New Section after 1.6 ] TITLE OF NEW CONTENT Type your content here... 1.7 Pressure Measurement. All pressures expressed in this document are

More information

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25

More information

Report on Proposals F2007 Copyright, NFPA Report of the Committee on Dry and Wet Chemical Extinguishing Systems

Report on Proposals F2007 Copyright, NFPA Report of the Committee on Dry and Wet Chemical Extinguishing Systems Report of the Committee on Dry and Wet Chemical Extinguishing Systems Edward J. Kaminski, Chair Schirmer Engineering Corporation, NV [I] Paul E. Buchhofer, Building Inspection Underwriters, Inc., PA [E]

More information

ISO INTERNATIONAL STANDARD. Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment

ISO INTERNATIONAL STANDARD. Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment INTERNATIONAL STANDARD ISO 15371 Second edition 2009-03-15 Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment Navires et technologie maritime Systèmes d'extinction

More information

Page 1 of 9 First Revision No. 2-NFPA 99B-2012 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard for Portable

More information

Committee Input No. 60-NFPA [ Sections , ]

Committee Input No. 60-NFPA [ Sections , ] Page 1 of 15 Committee Input No. 60-NFPA 34-2013 [ Sections 3.3.7.1, 3.3.7.2 ] Sections 3.3.7.1, 3.3.7.2 3.3.7.1 Combustible Liquid. A Any liquid that has a closed-cup flash point at or above 100 F (37.8

More information

CORE Protection Fire System Specification

CORE Protection Fire System Specification CORE Protection Fire System Specification The CORE restaurant fire suppression system is a pre-engineered, duct and plenum water spray system in conjunction with a wet chemical, cartridge-operated, regulated

More information

Second Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 6/23/ :34 AM

Second Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 6/23/ :34 AM of 56 6/23/2016 11:34 AM Second Revision No. 1-NFPA 96-2016 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM

More information

First Revision No. 7-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 7-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 29 6/9/2016 1:42 PM First Revision No. 7-NFPA 289-2016 [ Global Input ] Add comman between "reconstruction or research" throughout the document as follows: "reconstruction, or research" Submittal Date:

More information

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52

More information

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

WORKING DRAFT OF COMMITTEE MEETING OUTPUT WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF FIRST DRAFT REPORT Document: NFPA 110 (EPS-AAA) Revision Cycle: A2018 Meeting Date(s):

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 1410-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 1500, Standard on Fire Department

More information

Second Revision No. 11-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement

Second Revision No. 11-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement Second Revision No. 11-NFPA 16-2014 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 11, Standard for Low-, Medium-, and High-Expansion Foam, 2010 2015 edition. NFPA 13, Standard

More information

Project Name: Project Address: Installer Name: Installer Address: Date of Inspection:

Project Name: Project Address: Installer Name: Installer Address: Date of Inspection: FIRE DEPARTMENT Kitchen Range Hood Fire Suppression System Acceptance Test Project Name: Project Address: Installer Name: Installer Address: Date of Inspection: DOCUMENTATION NO Plans have been reviewed

More information

SERVICE VERSUS REMOVAL OF OBSOLETE COMMERCIAL KITCHEN PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

SERVICE VERSUS REMOVAL OF OBSOLETE COMMERCIAL KITCHEN PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SERVICE VERSUS REMOVAL OF OBSOLETE COMMERCIAL KITCHEN PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS The members of the Fire Equipment Manufacturers Association (FEMA) are in the business of providing the very

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Public Comment No. 2-NFPA 16-2013 [ Section No. 3.3.6 ] 3.3.6* Foam-Water Sprinkler System. A piping network connected to a source of foam concentrate and to a water supply. The piping network is equipped

More information

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ] 8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.

More information

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.

More information

First Revision No. 20-NFPA [ Section No ]

First Revision No. 20-NFPA [ Section No ] of 25 7/15/2015 8:30 AM First Revision No. 20-NFPA 56-2015 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by NFPA

More information

COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET

COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET Colorado Springs Fire Department Division of the Fire Marshal October 2013 Table of Contents PURPOSE... 3 SCOPE... 3 DEFINITIONS... 3 GUIDELINES...

More information

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM of 28 11/18/2016 2:25 PM First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] 1.6 Units and Formulas. 1.6.1 The units of measure in this standard are presented first in U.S. customary units (inch-pound

More information

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM 1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling

More information

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS June 20, 2011 TO: PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS SUBJECT: New Acceptance Criteria for Fixed Condensed Aerosol Fireextinguishing Systems, Subject AC432-0611-R1

More information

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM 2 of 326 11/21/2013 1:03 PM First Revision No. 82-NFPA 72-2013 [ Section No. 2.3.4 ] 2.3.4 ISO Publications. International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56, CH-1211

More information

Public Input No. 107-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 107-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification of 123 7/30/2015 1:48 PM Public Input No. 107-NFPA 96-2014 [ Section No. 1.3.2 ] 1.3.2 The authority having jurisdiction shall determine compliance with this standard and authorize equivalent deviations

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

Public Comment No. 22-NFPA [ New Section after 1.4 ] Statement of Problem and Substantiation for Public Comment

Public Comment No. 22-NFPA [ New Section after 1.4 ] Statement of Problem and Substantiation for Public Comment of 25 5/14/2015 2:32 PM Public Comment No. 22-NFPA 14-2014 [ New Section after 1.4 ] A.1.4 A.1.4 It is the intent of the Commi ee to recognize that future edi ons of this standard are a further refinement

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

NFPA 30 FLC-SWC First Revisions Page 1 of 10 11/6/2015 9:21 AM. First Revision No. 208-NFPA [ Section No ]

NFPA 30 FLC-SWC First Revisions Page 1 of 10 11/6/2015 9:21 AM. First Revision No. 208-NFPA [ Section No ] of 46 11/6/2015 9:21 AM First Revision No. 208-NFPA 30-2015 [ Section No. 9.3.3.1 ] 9.3.3.1 Storage of liquids shall not physically obstruct a means of egress. Submittal Date: Wed Sep 09 18:24:20 EDT 2015

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical self-closing device

More information

XRRS Specification Fire Ready Hood

XRRS Specification Fire Ready Hood XRRS Specification Fire Ready Hood ************************************************************************************************************************ Note to User: This document is subject to copyright

More information

The distances in shall be reduced to 130 ft (39.7 m) when manual dry standpipes are installed in open parking garages.

The distances in shall be reduced to 130 ft (39.7 m) when manual dry standpipes are installed in open parking garages. of 123 6/10/2014 9:07 AM First Revision No. 117-NFPA 14-2014 [ Global Input ] 7.3.2.7.5 The distances in 7.3.2.2 shall be reduced to 130 ft (39.7 m) when manual dry standpipes are installed in open parking

More information

MEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Initiating Devices for Fire

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

Ships and marine technology Fireextinguishing. of galley cooking equipment

Ships and marine technology Fireextinguishing. of galley cooking equipment INTERNATIONAL STANDARD ISO 15371 Third edition 2015-11-15 Ships and marine technology Fireextinguishing systems for protection of galley cooking equipment Navires et technologie maritime Systèmes d extinction

More information

Public Comment No. 7-NFPA 30A-2013 [ Section No ]

Public Comment No. 7-NFPA 30A-2013 [ Section No ] Page 1 of 13 Public Comment No. 7-NFPA 30A-2013 [ Section No. 6.4.2 ] 6.4.2 Additional Proposed Changes Each pump shall have installed on the discharge side a listed leak detection device that will provide

More information

Page 1 of 10 Second Revision No. 8-NFPA 600-2014 [ Section No. 3.3.17 ] 3.3.17* Incident Management System (IMS). A system that defines the roles and responsibilities to be assumed by responders and the

More information

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification Public Comment No. 2-NFPA 73-2014 [ Section No. 4.1.3 ] 4.1.3 Unused Openings. 4.1.3.1 Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or

More information

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND 1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical on Fluidized Bed Boilers AGENDA Web/Teleconference 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of Members and Guests 3. Approval of Minutes from

More information

Fire Suppression Installation (R-102) for AVI Hoods & XLT Ovens

Fire Suppression Installation (R-102) for AVI Hoods & XLT Ovens XD 9011E ABGKSWBGHAE 10/16/2017 Fire Suppression Installation (R-102) for AVI Hoods & XLT Ovens CAUTION This appliance is for professional use by qualified personnel. This appliance must be installed by

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

2012 International Mechanical Code Significant Changes. About the Significant Changes

2012 International Mechanical Code Significant Changes. About the Significant Changes Significant Changes to the International Mechanical Code and the International Fuel Gas Code With Louisiana Amendments Copyright Materials This presentation is protected by US and International Copyright

More information

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application. 1.3.1 This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ]

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ] of 71 6/11/2014 8:20 AM First Revision No. 36-NFPA 76-2014 [ Section No. 1.1 [Excluding any Sub-Sections] ] This standard provides requirements for fire protection of telecommunications facilities where

More information

Page 1 of 31 Second Revision No. 1-NFPA 80-2014 [ Section No. 2.3.2 ] 2.3.2 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM A36/A36M,

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

First Revision No. 106-NFPA [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 106-NFPA [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 106-NFPA 86-2012 [ Chapter NFPA ] 7.4.10.2* The number of safety shutoff valve cycles shall be determined by one of the following ways: (1) Counting of actual safety shutoff valve open-closed

More information

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS FIRE EXTINGUISHER REQUIREMENTS 1. All commercial cooking operations require at least one 2A10BC rated (5 or 6 pound size) fire extinguisher.

More information

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities

More information

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Guy R. Colonna, PE Division Manager, NFPA Combustible Dust Symposium Detroit, MI September 20, 2011 1 Objectives

More information

The Committee updated the edition dates for the reference sources for extracted text within the standard per the NFPA Manual of Style.

The Committee updated the edition dates for the reference sources for extracted text within the standard per the NFPA Manual of Style. Second Revision No. 51-NFPA 86-2013 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 54, National Fuel Gas Code, 2009 2015 edition. NFPA 69, Standard on Explosion Prevention

More information

Chapter One Commercial Kitchen Fires

Chapter One Commercial Kitchen Fires Table of Contents Table of Contents Chapter One Commercial Kitchen Fires COMMERCIAL KITCHEN FIRES... 2 The Commercial Kitchen Fire Problem... 2 Unreported Fires... 2 Cooking By-Products... 3 Grease Accumulation

More information

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Water Additives

More information

First Revision No. 339-NFPA [ Section No. 2.2 ]

First Revision No. 339-NFPA [ Section No. 2.2 ] 8 of 326 11/21/2013 1:03 PM First Revision No. 339-NFPA 72-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard

More information

Page 1 of 40 First Correlating Revision No. 15-NFPA 72-2014 [ Global Input ] 10.5.4 Plans Examiners and Inspectors. 10.5.4.1 Fire alarm system and emergency communications system plans and specifications

More information

SECTION COMMERCIAL-KITCHEN HOODS

SECTION COMMERCIAL-KITCHEN HOODS SECTION 23 38 13 COMMERCIAL-KITCHEN HOODS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement 10/20/ :03 AM

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement 10/20/ :03 AM of 496 10/20/2016 11:03 AM First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value 0.0375 lumens/ft 2 is used the metric equivalent shall be

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

Report on First Revision June 2014 NFPA 101

Report on First Revision June 2014 NFPA 101 101- Log #62 SAF-BSF Final Action: (9.2.3) Submitter: Doug Hohbein, Northcentral Regional Fire Code Development Committee Recommendation: Revise to read: 9.2.3 Commercial Cooking Equipment Operations.

More information

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

Public Comment No. 32-NFPA 90A-2016 [ Section No ] Statement of Problem and Substantiation for Public Comment

Public Comment No. 32-NFPA 90A-2016 [ Section No ] Statement of Problem and Substantiation for Public Comment of 53 11/9/2016 9:07 AM Public Comment No. 32-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA

More information