M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

Size: px
Start display at page:

Download "M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing"

Transcription

1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic Materials Processing Joanne Goyette, Administrator, Technical Projects DATE: November 7, 2014 SUBJECT: NFPA 664 First Draft TC FINAL Ballot Results (A2016) According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. 25 Members Eligible to Vote 5 Not Returned (S. Francis, J. Lysy, A. Mattos, Jr., B. Noe, and D. VanderHyde, Jr.) 14 Members Voting Affirmative (10 with Comment on one or more First Revisions: B. Chastain, J. Cholin, A.Dastidar, D. Guaricci, P. Levitt, K. Mayeaux, B. McLelland, T. Myers, F. Tanguay, and E. Ural) 6 Members Voting Negative on one or more First Revisions (B. Chastain, J. Cholin, K. Mayeaux, T. Myers, F. Tanguay, and E. Ural) 0 Members Voting to Abstain on one or more First Revisions The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each first revision. There are two criteria necessary for each first revision to pass ballot: (1) simple majority and (2) affirmative 2 /3 vote. The mock examples below show how the calculations are determined. (1) Example for Simple Majority: Assuming there are 20 vote eligible committee members, 11 affirmative votes are required to pass ballot. (Sample calculation: 20 members eligible to vote 2 = = 11) (2) Example for Affirmative 2 /3: Assuming there are 20 vote eligible committee members and 1 member did not return their ballot and 2 members abstained, the number of affirmative votes required would be 12. (Sample calculation: 20 members eligble to vote 1 not returned 2 abstentions = 17 x 0.66 = = 12 ) As always please feel free to contact me if you have any questions.

2 Results by Revision NFPA 664 CMD WOO (A2016) First Draft Ballot Final Results November 7, 2014 FR 62, Global Input, See FR 62 FR 65, Global Input, See FR 65 FR 1, Sections 1.1.1, 1.1.2, See FR 1 Affirmative 17 Affirmative with Comment 2 Peter Levitt An AHJ could interpret that the standard only applies to product woodworking shops and not maintenance or school shops. I believe we do want all dust collectors greater than 1500 cfm outdoors, with explosion vents, etc. I suggest "but not limited to" should be deleted. "production type" should be replaced by "other types of". An appendix item should be added to clarify that the other types of shops include, but are not limited to maintenance and school instructional wood shops. Ken J. Mayeaux Negative 1 Erdem A. Ural Basically agree with P. Levitt. Replace "production type" with "other types of," and add clarification in the appendix. Section worries me deeply. One can have an operation in < 5000 ft2 area and dust collection (system air) flow rate < 1500 cfm and have a severe explosion hazard. A much more important factor, dust generation rate, is completely ignored in this exception. Another change in this section, not addressed in committee statement, is to bring these excepted operations into the standard but not letting important chapters apply to them. Normally, we would rely on 652 to catch the problems. However, the way FR 1 is worded, along with the latest scope statement in 652, will prevent owner/operator or AHJ from identifying and addressing dangerous conditions in the workplace. FR 2, New Section after 1.4.3, See FR 2 Affirmative 17

3 Erdem A. Ural Negative 2 Timothy J. Myers Francois Tanguay This section is not clear. Add the committee statement as annex material. This language is not clear and needs further revision or explanation in an annex. Does the standard retroactively apply to all existing areas and process of the facility OR only to the process changes? Ex: The MEC criteria for pneumatic conveying changed from 75% to 25% (2007 edition to 2012 edition). Existing systems that are operating at 60% of the MEC are now deemed to have a deflagration hazard. If that process doesn't change but another one inside the mill does, it would still affect it? FR 3, Chapter 2, See FR 3 FR 35, New Section after , See FR 35 Affirmative 18 Dan A. Guaricci Distance needs to be defined? Negative 1 Francois Tanguay Safe location as defined is not all inclusive of all the articles where it is currently being used. Article uses 'safe location' with the intent of a safe area outside the building. FR 28, Section No , See FR 28 Affirmative 15 Affirmative with Comment 3 Timothy J. Myers As written this is unclear. Is all wood that is less than 5 mm and 25% moisture content deflagrable, even if testing demonstrates otherwise? Or can testing be used to show that specific material less than 5 mm and 25% moisture content is not deflagrable? Ashok Ghose Dastidar Erdem A. Ural Comments: 1/20" is not 5mm. This is a mathematical error. it should be ~1/5" The text should not read"5 mm (1/20) or smaller". It would be beneficial to say "5 mm (1/5 in.) or smaller. Material passing through a No.4 Taylor mesh screen" Commercial 5 mm screens are not available. the closest is a No.4 Taylor mesh screen which is 4.76 mm. This definition is confusing. The first part ending with "regardless of particle size or shape" is good. The rest may belong to Annex with additional explanation. Didn't we delete ? It contradicts Negative 2 Francois Tanguay In recent years, the criteria for combustible dust has jumped from 420 microns to 500 microns to 5000 microns (5mm), 10x bigger in size. Additional clarification is needed. Also, there doesn't seems to be consistency, as FR 8 (section ) is revised using 500 microns as the criteria to define protection requirements for dust conveying.

4 Ken J. Mayeaux The fairly recent dust testing that was presented during the 2014 TC meeting in Chicago was basis for this change. At that meeting, a subcommittee was developed to further review the various parameters associated with those tests. Perhaps additional testing can (should) be done to further refine the definition. I suggest we hold off on accepting the definition until we hear back from the subcommittee. FR 29, New Section after 4.1, See FR 29 Affirmative 18 Affirmative with Comment 2 Dan A. Guaricci Why have an industry standard if you refer to a general standard. With this statement both apply everywhere. a user has to now read both. Confusing for the user. Francois Tanguay The requirement to comply with NFPA 652 should not be in this standard. If specific articles of 664 refer to 652, then there is a clear path of which requirement are to be complied with. Suggest to remove those last few words: 'and NFPA 652'. FR 30, New Section after 4.1, See FR 30 FR 14, Section No , See FR 14 Affirmative 16 Negative 4 Francois Tanguay That article isn't clear for the user. Why not refer to article of NFPA 654 edition The way NFPA 654 defines how to determine both Dust Explosion Hazard and Dust Flash Fire Hazard is much clearer. So either refer to NFPA 654 or copy it into 664. Ken J. Mayeaux I believe the 5% area limitation was incorporated from the appendix of the which was also later incorporated into the body of 654 where it remains. The validity of the 5% area has been a question for some time and has been a rule of thumb used. However, I agree with J. Cholin, it should be validated and perhaps it's time for a research project. Relocating it to the appendix would seem to be appropriate, but it would also not be consistent with 654 and perhaps even 652. Erdem A. Ural Delete the expression "upward facing." Move this section after the bulk density correction section. Replace 1/8" with the term "allowable thickness" Delete section as it is redundant with section

5 John M. Cholin The 5% area limitation was brought from the annex, where it was advisory, to the body where it is mandatory in the last revision cycle with absolutely no loss data or research to support the need to or legitimacy of this limitation. the area limitation should be returned to the annex unless and until loss history of validated research can substantiate the need for this to be mandatory text. Secondly, the proposed language for seems self evident. the reference to Section 4.3 and 652 should be in the annex. FR 31, Section No , See FR 31 Negative 1 Erdem A. Ural Make the bulk density correction mandatory for all bulk densities. 1/8" thick layer of denser layers present a greater hazard, which is currently ignored by 664. FR 33, Section No , See FR 33 FR 32, New Section after 6.3, See FR 32 FR 11, New Section after 6.3.2, See FR 11 FR 34, Section No , See FR 34

6 FR 36, Section No. 7.1, See FR 36 FR 16, Section No , See FR 16 Affirmative 17 Negative 3 Erdem A. Ural replace "wood" with "wood and wood dust layers" Change temperature criteria to 165 C (329 F), to account for material that dehydrates or carbonizes. Francois Tanguay OSB Press are heated process equipment which are in contact with wood and are exceeding 356oF. That article as written would prohibit the use of those equipment. Many mills will have to shutdown. Ken J. Mayeaux Agree with F. Tanguay regarding OSB presses. Should add a subsection that states high temperatures are acceptable for processes protected in accordance with Chapters 8 and 9. FR 37, Section No , See FR 37 Affirmative 18 Negative 2 Erdem A. Ural Change temperature criteria to 165 C (329 F), to account for material that dehydrates or carbonizes. Francois Tanguay Some furnaces installed in Southern climate would have an outside metal temperature above 356oF even when properly insulated, as that metal temperature is depending on the ambient conditions. FR 17, Section No , See FR 17

7 FR 38, Section No , See FR 38 FR 60, Section No , See FR 60 Erdem A. Ural A GENERAL COMMENT ON CHAPTER 8 Chapter 8 lacks deflagration isolation requirements for ducts and interconnected equipment per NFPA 69. This is a dangerous deficiency that must be fixed. FR 19, Section No , See FR 19 FR 18, Section No , See FR 18 Dan A. Guaricci FR 39, Section No , See FR 39 During operation so called green material areas have had fires and events where material does not clear the process and dry's out. "In green material areas good housekeeping shall prevent material from drying out and being retained by the process." A study is going on in Europe on this very subject.

8 FR 40, Section No , See FR 40 Erdem A. Ural Must add deflagration isolation requirements per 69. FR 41, Section No , See FR 41 FR 20, Section No (A), See FR 20 FR 6, Sections , , , , See FR 6 Affirmative 16 Affirmative with Comment 4 Dan A. Guaricci NFPA 68 does cover venting between vessels if the duct is over 12". Plus the venting of ducts is hard inside considering the need for a vent ducts. Suggest this section be removed. 3 Metal ducts shall be located indoors and shall be equipped with adequate deflagration relief vents that have relief pipes, not exceeding 6 m (20 ft) in length, extending to safe areas outside the building and that have a design strength exceeding the maximum reduced deflagration pressure.and vent ducts designed, installed, and maintained in accordance with NFPA 68 and shall have a design strength exceeding the maximum reduced deflagration pressure. Bruce McLelland Sections , subsections (2),(3),(4) and (5) are confusing and in some cases incorrect. the sections should be rewritten.

9 Francois Tanguay John M. Cholin I agree with Mr. Cholin comments about the rewriting of sub section (2): '... that limits deflagration pressure within the duct to the limits established in NFPA 69'. Sub Section (2) should be reconsidered and edited. A deflagration suppression system cannot have a "design strength exc3eeding the maximum reduced deflagration pressure". It should read "...that limits the deflagration pressure within the duct to the limits established in NFPA 69." FR 42, Section No , See FR 42 FR 8, Section No , See FR 8 FR 21, New Section after , See FR 21 FR 43, Section No , See FR 43 FR 44, Section No , See FR 44

10 FR 22, Section No , See FR 22 FR 25, Section No , See FR 25 Affirmative 18 Affirmative with Comment 2 Peter Levitt If we are going to allow a 5000 cfm & less outdoor cyclone & indoor enclosureless dust collector without the requirement of a a spark detection & extinguishing or abort gate, we should state that, so it is clear to AHJ's. Bruce McLelland Clarification needs to be made that isolation provisions are still required to protect from flame and pressure propagation from the cyclone to the inside enclosureless AMS. Add the following sentence. "When a deflagration hazard exists in the cyclone, isolation provisions shall be made to prevent deflagration flame and pressure propagation from the cyclone back into the building and to the enclosureless dust collector. FR 45, Section No , See FR 45 FR 46, Section No , See FR 46 Bruce McLelland add clarification to the provision. "...meeting the design and application provisions of NFPA 68." With the information presented, it implies the designer is not obligated to any other provisions. The reader should be notified that the vent design criteria can not overlook the performance and application requirements of NFPA 68.

11 FR 23, Section No , See FR 23 FR 24, Section No , See FR 24 FR 61, Section No [Excluding any Sub Sections], See FR 61 Negative 1 Francois Tanguay Removing will make section 8.3 unclear, as it is not written in the same manner as chapters 6 or 7. Section is the equivalent to a performance based design and section contains the prescriptive requirements. Without article the reader won't understand what is required. FR 47, Section No , See FR 47 FR 48, Section No , See FR 48

12 FR 49, Section No , See FR 49 FR 50, Section No , See FR 50 FR 51, Section No , See FR 51 FR 52, Section No , See FR 52 FR 53, Section No , See FR 53

13 FR 54, Section No , See FR 54 FR 55, Section No , See FR 55 FR 56, Section No , See FR 56 FR 57, Section No , See FR 57 Affirmative 17 Francois Tanguay Change 'handling' for 'storing' so it is inline with the intent of which relates to dry fines storage. So it would read like this: 'Any areas storing dry wood particulate shall...'. Also, the word 'detached' has been added to I believe the intent of that article was only to differentiate between 'green' and 'dry' particulate storage, within the same type or area. So should be rewriting like this: 'Any areas that store only green wood particulate shall be permitted to have electrical equipment suitable for Class II Division 2 in accordance with article 500 of NFPA 70'. Negative 2 Brice Chastain Ken J. Mayeaux This requirement should be revised to: Any areas storing dry wood waste particulate shall have Class II, Division 1 electrical equipment. "Storing" should be used instead of "handling" in the requirement. Handling is a broad term; storage is a limiting term and is appropriate in this requirement. Note: All other areas "handling" combustible dusts shall be classified in accordance with Article 500 of NFPA 70. Electrical classification of all combustible dusts is required by regulation to be classified under NFPA 70 Article 500. Agree with B. Chastain. Electrical classification of areas handling dry wood particulate should be evaluated individually in accordance with Article 500 of NFPA 70. FR 58, Section No , See FR 58

14 FR 59, New Section after 10.1, See FR 59 FR 12, Section No , See FR 12 Brice Chastain This requirement should include "flash fire" FR 15, Section No. A.4.3, See FR 15 Brice Chastain The example in the second sentence should be revised to include "flash fire hazards". Suggest the example sentence be revised to: For example in a woodworking facility it would include where fire hazards exist, where flash fires exist, where explosion hazards exist, and what protective measures are in place to protect the personnel and property from those hazards. FR 27, Section No. A (2), See FR 27

15 FR 26, Section No. A , See FR 26 FR 63, Section No. A , See FR 63 FR 10, Section No. A , See FR 10 FR 66, Chapter B, See FR 66 Dan A. Guaricci B1 Add Statement to indicate one or more of the methods might be required. B.4.1 Add Flame less vent as an option. B 6 Section limits applicability to ducts of less then 1' or requires an isolation method to be used. Suggest eliminating this statement. "Although NFPA 68, Standard on Explosion Protection by Deflagration Venting, indicates venting as an option for interconnections, venting is valid only when interconnected equipment is protected from explosions." B.6.1 Mechanical Isolation. Should be expanded to include the many Passive Mechanical Isolation Devices available. The only once listed are the higher cost quick sliding valve or chemical isolation. Lower cost isolation methods are available. FR 67, Chapter C, See FR 67 Affirmative 18 Affirmative with Comment 2

16 Dan A. Guaricci The examples indicate the use of an explosion vent. This considers the hazard to require and explosion isolation system if the air is returned to the building. If venting is shown with a spark detection and extinguishing system then isolation should also be shown. This is a common misconception with users as they apply an abort gate and think it protects against the deflagrations propagation. While they can the construction of most won't stop a deflagrations pressure. It must be clear that Spark systems are a great first step to prevent explosions explosion protection is not provided by them. Peter Levitt In illustrations C & C.2.2 the spark detectors are located after the dust collector. Is this the required/preferred location for the detectors? I thought they should be located before the dust collector. FR 68, Chapter D, See FR 68 Dan A. Guaricci Figure D.1 Figure indicates a cyclone and dust collector both having a deflagration hazard. But the isolation between the two only shows isolation required from the DC to the cyclone considering the device shown is a single direct device. Since the cyclone has isolation on the inlet it should have it on the outlet. Venting of duct work shown between DC and Cyclone only applicable per NFPA 68 if duct size is under 12+" and shorter then 20' which does not fit most process ducts. FR 69, Chapter E, See FR 69 FR 13, Chapter F, See FR 13

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Correlating Committee on Combustible Dusts Susan

More information

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Building Service and

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Portable Fire Extinguishers

More information

MEMORANDUM. NFPA Technical Committee on Handling and Conveying of Dusts, Vapors, and Gases. NFPA 654 Second Draft TC FINAL Ballot Results (A2016)

MEMORANDUM. NFPA Technical Committee on Handling and Conveying of Dusts, Vapors, and Gases. NFPA 654 Second Draft TC FINAL Ballot Results (A2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Handling and Conveying

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018) M EM O RA N D UM TO: FROM: DATE: SUBJECT: Correlating Committee on Combustible Dusts Yiu Lee, Project Administrator January 27, 2017 NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

MEMORANDUM. Technical Committee on Fundamentals of Combustible Dusts. NFPA 652 First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Fundamentals of Combustible Dusts. NFPA 652 First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Combustible

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

Prevention of Fires and Explosions in Wood Pellet Facilities. Allen Wagoner, FLAMEX, Inc.

Prevention of Fires and Explosions in Wood Pellet Facilities. Allen Wagoner, FLAMEX, Inc. Prevention of Fires and Explosions in Wood Pellet Facilities Allen Wagoner, FLAMEX, Inc. Wood Dust The smaller the particles the more dangerous Particle size of 420 microns or less (NFPA Code 664)

More information

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Guy R. Colonna, PE Division Manager, NFPA Combustible Dust Symposium Detroit, MI September 20, 2011 1 Objectives

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

COMBUSTIBLE DUST AN EXPLOSIVE ISSUE NFPA 654

COMBUSTIBLE DUST AN EXPLOSIVE ISSUE NFPA 654 COMBUSTIBLE DUST AN EXPLOSIVE ISSUE NFPA 654 NFPA 654-2006 What is NFPA 654- Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, Handling of Combustible Particulate

More information

Industrial Explosion Suppression Technology

Industrial Explosion Suppression Technology 88 th Annual Michigan Safety Conference 2018 Tuesday April 17 th 2018-10:45 AM Industrial Division Lansing Center, Lansing, MI Industrial Explosion Suppression Technology Presenter: Rob Markle Phone: (309)

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

TECHNICAL COMMITTEE ON FIRE CODE

TECHNICAL COMMITTEE ON FIRE CODE TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2

More information

NFPA Technical Committee on Fire Tests

NFPA Technical Committee on Fire Tests National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Tracy

More information

M E M O R A N D U M. The Technical Correlating Committee on Boiler and Combustion Systems Hazards

M E M O R A N D U M. The Technical Correlating Committee on Boiler and Combustion Systems Hazards M E M O R A N D U M TO: FROM: The Technical Correlating Committee on Boiler and Combustion Systems Hazards Jeanne Moreau DATE: June 22, 2010 SUBJECT: NFPA 85 TCC Report on Comments Letter Ballot (F10)

More information

First Revision No. 1-NFPA [ Chapter 2 ]

First Revision No. 1-NFPA [ Chapter 2 ] First Revision No. 1-NFPA 499-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this recommended practice

More information

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fundamentals of Fire

More information

Dust Explosions. health & environmental sciences failure analysis & prevention

Dust Explosions. health & environmental sciences failure analysis & prevention health & environmental sciences failure analysis & prevention Dust Explosions Timothy Myers 9 Strathmore Road Natick, MA 01760 tmyers@exponent.com (508) 652-8572 December 7, 2016 A leading engineering

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: DATE: Technical Committee on Handling and Conveying

More information

Circulation Report for SIG-TMS Comments Document # 72

Circulation Report for SIG-TMS Comments Document # 72 1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15

More information

3/20/2017. The Impact & Implications of NFPA 652 NFPA s Newest Combustible Dust Standard. Jason Reason. Jason Reason

3/20/2017. The Impact & Implications of NFPA 652 NFPA s Newest Combustible Dust Standard. Jason Reason. Jason Reason The Impact & Implications of NFPA 652 NFPA s Newest Combustible Dust Standard Jason Reason, CIH, CSP, CHMM Senior Vice President / Consultant Jason Reason Education & Certifications B.S. Industrial Hygiene

More information

Second Revision No. 14-NFPA [ Global Comment ] Submitter Information Verification. Committee Statement 8/25/ :39 AM

Second Revision No. 14-NFPA [ Global Comment ] Submitter Information Verification. Committee Statement 8/25/ :39 AM of 36 8/25/2015 10:39 AM Second Revision No. 14-NFPA 664-2015 [ Global Comment ] Add the following statement to the begining of Chapter 10 and Chapter 11 - The provisions of this Chapter shall be applied

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Road Tunnel and Highway

More information

Combustible Dust Issues

Combustible Dust Issues Combustible Dust Issues Dust Collector Requirements J Kirt Boston IAF Programs Manager Donaldson Company, Inc. Combustible Dust Impact on Collectors Rules or Requirements Discussed by Customers What areas

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Residential Occupancies Kelly

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 17 From: Kimberly Shea, Project Administrator

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Residential

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

The element is closed at one end and open at the other, and it s bolted onto the explosion vent opening on the equipment so that its open end overlaps

The element is closed at one end and open at the other, and it s bolted onto the explosion vent opening on the equipment so that its open end overlaps Meeting explosion safety requirements with flameless venting Jef Snoeys Fike Corp. Flameless venting is a recently developed technology for protecting indoor equipment from dust explosions. This technology

More information

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Alternative Approaches to

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

National Fire Protection Association

National Fire Protection Association National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M (AMENDMENT) TO: FROM: Technical Committee on Mercantile

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

Before proceeding with the selection process, let s briefly look at the various explosion protection options:

Before proceeding with the selection process, let s briefly look at the various explosion protection options: Explosion Protection System Selection Guide By Emre Ergun, MS, MBA New Product Development Manager, FENWAL Explosion Protection Systems A UTC Fire & Security Company 400 Main Street, Ashland MA 01721 Tel:

More information

COMBUSTIBLE DUST HAZARD MITIGATION

COMBUSTIBLE DUST HAZARD MITIGATION COMBUSTIBLE DUST HAZARD MITIGATION February 2014 GUIDE FOR FRONT LINE SUPERVISORS AND MANAGEMENT TABLE OF CONTENTS P a g e 1 A] Combustible Dust Hazard Mitigation... 4 A.1] Why Are We Here?... 4 A.2]

More information

First Revision No. 15-NFPA [ Chapter 2 ]

First Revision No. 15-NFPA [ Chapter 2 ] Page 1 of 28 First Revision No. 15-NFPA 91-2013 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard

More information

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Correlating Committee on Signaling Systems for

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017)

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Code Kelly Carey,

More information

Correlating Committee on Combustible Dusts (CMD-AAC)

Correlating Committee on Combustible Dusts (CMD-AAC) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org Correlating Committee on Combustible Dusts (CMD-AAC) Drury Plaza Hotel

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

Conducting a NFPA 652 Dust Hazard Analysis (DHA): Practical Tips & Approaches

Conducting a NFPA 652 Dust Hazard Analysis (DHA): Practical Tips & Approaches Conducting a NFPA 652 Dust Hazard Analysis (DHA): Practical Tips & Approaches Pulp & Paper Safety Association Safety & Health Conference June 18, 2018 Mike Snyder PE CSP CFPS Executive Vice President,

More information

Combustible Dust Hazard Recognition and Control NFPA Standards for Combustible Dusts

Combustible Dust Hazard Recognition and Control NFPA Standards for Combustible Dusts Combustible Dust Hazard Recognition and Control NFPA Standards for Combustible Dusts Guy R. Colonna, PE Division Manager, NFPA Pellet Fuels Institute Conference Asheville, NC July 20, 2010 1 Objectives

More information

Industrial Dust Explosions Causes & Case Studies. Presented by Geof Brazier at Expocorma, Concepcion, Chile 10th November 2017

Industrial Dust Explosions Causes & Case Studies. Presented by Geof Brazier at Expocorma, Concepcion, Chile 10th November 2017 Industrial Dust Explosions Causes & Case Studies Presented by Geof Brazier at Expocorma, Concepcion, Chile 10th November 2017 Introduction Increased global demand for Wood products = increased industrial

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES INTERNATIONAL MARITIME ORGANIZATION E IMO SUB-COMMITTEE ON FIRE PROTECTION 46th session Agenda item 5 FP 46/5 30 November 2001 Original: ENGLISH UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED

More information

Understanding. Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations

Understanding. Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations Understanding Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations Michigan Safety Conference April 11, 2017 Mike Snyder PE CSP CFPS Vice President Organizational

More information

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the

More information

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, 2014 9:00 AM - 5:00 PM EST Web/Teleconference Meeting 1. Welcome. George Seuss, Chair 2. Introductions and Update

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 1-NFPA 36-2013 [ Global Input ] Revise the document to eliminate the use of "Exception" text. The use of "Exception" text is inconsistent with the Manual of Style. Exception text should

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 14 From: Kimberly Shea, Project Administrator

More information

Our Statement is not a problem - we are encouraging continuation of the standard as it is written without substantive changes.

Our Statement is not a problem - we are encouraging continuation of the standard as it is written without substantive changes. of 69 10/3/2016 2:09 PM Public Input No. 25-NFPA 652-2016 [ Global Input ] This standard was approved on September 7, 2015, less than one year ago. We believe this standard as written generally provides

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Furnishings

More information

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Standpipes Elena

More information

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12.

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12. 2/18/2016 National Fire Protection Association Report Committee Input No. 70 NFPA 54 2015 [ Section No. 12.5 ] This was a First Revision that failed ballot. 12.5 Type of Venting System to Be Used. 12.5.1

More information

Technical Committee on Electrical Equipment Evaluation. ROC Meeting Agenda September 28-29, 2010 Providence, RI

Technical Committee on Electrical Equipment Evaluation. ROC Meeting Agenda September 28-29, 2010 Providence, RI Technical Committee on Electrical Equipment Evaluation ROC Meeting Agenda September 28-29, 2010 Providence, RI Item 10-09-1 Call to Order Item 10-09-2 Introductions Item 10-09-3 Staff Remarks Item 10-09-4

More information

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Pumps Patti

More information

TECHNICAL COMMITTEE ON WOOD AND CELLULOSIC MATERIALS PROCESSING. NFPA 664 CMD-WOO (A2016) First Draft Meeting

TECHNICAL COMMITTEE ON WOOD AND CELLULOSIC MATERIALS PROCESSING. NFPA 664 CMD-WOO (A2016) First Draft Meeting TECHNICAL COMMITTEE ON WOOD AND CELLULOSIC MATERIALS PROCESSING NFPA 664 (A2016) First Draft Meeting Hilton Garden Inn Chicago, IL August 19-21, 2014 8 AM 5 PM AGENDA 1. Meeting is called to order at 8

More information

NFPA Overview. International Titanium 2014 Conference Chicago Kevin L. Kreitman

NFPA Overview. International Titanium 2014 Conference Chicago Kevin L. Kreitman NFPA 484 - Overview International Titanium 2014 Conference Chicago Kevin L. Kreitman Disclaimer This presentation is for informational purposes only. In preparing and making this information available,

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

MEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Initiating Devices for Fire

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

Requirements for ships carrying hydrogen and compressed natural gas vehicles

Requirements for ships carrying hydrogen and compressed natural gas vehicles Lloyd's Register briefing IMO FP 55 Summary report for clients Overview The 55 th session of the IMO Fire Protection Sub Committee (FP) was held from 25 th to 29 th July 2011, at the IMO headquarters in

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Tuesday, March 10; All Day Wednesday, March 11; All Day DRURY PLAZA HOTEL San Antonio Riverwalk 0. Administrative. A. Meeting Schedule.

More information

Page 1 of 9 First Revision No. 2-NFPA 99B-2012 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard for Portable

More information

Jason Reason. NFPA Technical Committees

Jason Reason. NFPA Technical Committees Jason Reason Education & Certifications B.S. Industrial Hygiene Purdue University MBA University of Indianapolis CIH, CSP, CHMM Experience 12.5 years as OSHA Compliance Officer Performed over 50 combustible

More information

Diane D. Matthews, Administrator, Technical Projects. The September 19, 2013 date for receipt of the NFPA 5000 Second Draft Ballot has passed.

Diane D. Matthews, Administrator, Technical Projects. The September 19, 2013 date for receipt of the NFPA 5000 Second Draft Ballot has passed. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Fire Protection Features Diane D. Matthews,

More information

Public Input No. 3-NFPA [ Chapter 2 ]

Public Input No. 3-NFPA [ Chapter 2 ] Public Input No. 3-NFPA 655-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 14 FROM: Kimberly Shea DATE:

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 2 FROM: Kimberly Shea, Administrator,

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Construction

More information

Aluminum Dust Management in a Metallizing Facility

Aluminum Dust Management in a Metallizing Facility Aluminum Dust Management in a Metallizing Facility Safety and Regulatory Concerns William James Barlow, Jr., Product Development Engineer, National Accounts Division Printpack, Inc., Villa Rica, GA Overview

More information

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ] 8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.

More information

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Supervising Station

More information

WHITE PAPER Dust Hazard Analysis for Simple Dust Collection Systems

WHITE PAPER Dust Hazard Analysis for Simple Dust Collection Systems WHITE PAPER Dust Hazard Analysis for Simple Dust Collection Systems By Mike Walters Combustible dusts are a recognized hazard for industrial facilities everywhere, and performing a hazard analysis is the

More information

Committee on NFPA 664

Committee on NFPA 664 Committee on NFPA 664 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic Materials Processing Jeanne Moreau DATE: March 19, 2010 SUBJECT: NFPA 664 A11 ROP Letter Ballot The ROP

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Fire Alarm

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.

More information