Model VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch

Size: px
Start display at page:

Download "Model VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch"

Transcription

1 Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model VPS + VPU Pressure Limiting (VFD) with Soft Start Bypass with Automatic Transfer Switch Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections Note: The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package.

2 with Automatic Transfer Switch From Transfer Switch* 1R CR6 CR8 CR7 1R 4R 4R CR6 CR7 CR8 2R 3R FU1 SSS1 2R 3R LR1 VFD1 POWER MODULE Standard, Listings and Certifications Built to NFPA 20 Underwriters Laboratory (UL) New York City UL218 - Fire Pump Controllers UL Automatic power transfer switches for fire pump controllers Accepted for use in the City of New York by the Department of Buildings Enclosure Protection Rating Standard: NEMA 2 (IP31) Optional NEMA 12 NEMA 3 NEMA 3R IP54 Accessories Bottom entry gland plate Lifting lugs Keylock handle Paint Specifications Red RAL3002 Powder coating Glossy textured finish Shortcircuit Withstand Rating 200V to 208V 60Hz 220V to 240V 60Hz 380V to 416V 50 Hz / 60Hz 440V to 480V 60Hz 600V 60Hz HP Standard 100kA Optional 150kA Standard 50kA Optional 100kA n/a n/a n/a n/a n/a *Please see Disconnecting Means details on page 3. 2

3 with Automatic Transfer Switch Ambient Temperature Rating Operating Modes Surge Suppression Disconnecting Means Service Entrance Rating Standard: 5 C to 40 C / 41 F to 104 F The controller shall have the capability of running the pump motor in the following three (3) modes via a speed mode selector switch: Variable mode: Upon an automatic or manual start, the controller shall start the pump through the variable frequency drive (VFD) and instantly regulate the motor speed in reference to the discharge pressure Preset mode: Upon an automatic or manual start, the controller shall start the pump through the variable frequency drive (VFD) and run the pump motor at a pre-determined speed. This pre-determined speed shall be adjustable on the variable frequency drive (VFD) itself Bypass mode: Upon an automatic or manual start, the controller shall start the pump through the reduced voltage soft start bypass circuit. Surge arrestor rated to suppress surges above line voltage Isolating switch and circuit breaker assembly: - Door interlocked in the ON position - Isolating switch rated not less than 115% of motor full load current - Circuit breaker continuous rating not less than 115% of motor full load current - Overcurrent sensing non-thermal type, magnetic only - Instantaneous trip setting of not more than 20 times the motor full load current Common flange mounted operating handle Suitable as service entrance equipment Emergency Start Handle Flange mounted Pull and latch activation Integrated limit switch Across the line start (direct on line) Locked Rotor Protector Operate shunt trip to open circuit breaker Factory set at 600% of motor full load current Trip between 8 and 20 seconds Electrical Readings Pressure Readings Pressure and Event recorder Pressure Sensing Voltage phase to phase (normal power) Amperage of each phase when motor is running Continuous system pressure display Cut-in and Cut-out pressure settings Pressure readings with date stamp Event recording with date stamp The recorder will register and keep in memory pressure fluctuations over time that have occurred over the previous seven (7) days and events, alarms, general system information that have occurred over the previous fifteen (15) Information is retrievable through DB9 communication port accessible without having to open the controller door. Pressure transducers (2) for reading of discharge pressure Pressure sensing line connection (1/2 Female NPT) Rated for 0-600PSI working pressure Externally mounted with protective cover 3

4 Audible Alarm Visual Indications Alarm buzzer power available power available position position Technical Data with Automatic Transfer Switch Individual phase-to-phase voltage indication + Hz frequency (normal power) Individual phase current indication Pressure indication Elapsed run time Visual & Audible Alarms Visual only loss Motor run Phase reversal Phase unbalance Visual and Audible Overcurrent Undercurrent Fail to start Audible only Fault SSS (soft-start) Phase loss L1 Phase loss L2 Phase loss L3 Low System pressure Pressure transducer problem By-pass mode VFD Failure Undervoltage Overvoltage Locked rotor System trouble Remote Alarm Contacts DPDT-8A-250V.AC available Phase loss loss Overvoltage Undervoltage Phase unbalance Common motor trouble Overcurrent Undercurrent Fail to start Pressure transducer problem Phase reversal Bypass mode VFD Failure Motor run ***Can only be used if approved by the AHJ 4

5 Operator Interface Operation Technical Data with Automatic Transfer Switch Micro-processor based Accessible without opening main door Voltage and current indication Pressure settings and system pressure indication 15 day pressure and 15 day event Automatic Start Manual Start Stopping Timers Actuation Mode Start on pressure drop Start pushbutton Remote start from manual device Manual with Stop pushbutton Automatic after expiration of minimum run timer *** Field Adjustable & Visual Countdown Visual Indication Minimum run timer ***(off delay) Sequential start timer (on delay) Periodic test timer Pressure Automatic Non-automatic 5

6 with Automatic Transfer Switch Automatic Transfer Switch Surge Suppression Disconnecting Means Locked Rotor Protector Visual Indications Visual and Audible Alarms Surge arrestor rated to suppress surges above line voltage Isolating switch and circuit breaker assembly: - Door interlocked in the ON position - Isolating switch rated not less than 115% of motor full load current - Circuit breaker continuous rating not less than 115% of motor full load current - Overcurrent sensing non-thermal type, magnetic only - Instantaneous trip setting of not more than 20 times the motor full load current Common flange mounted operating handle Operate shunt trip to open circuit breaker Factory set at 600% of motor full load current Trip between 8 and 20 seconds (emergency) isolating switch in the OFF position (emergency) voltage phase to phase + frequency Transfer switch in normal or alternate position Isolating switch in OFF position Electrically operated and mechanically held in the normal or alternate position Provision for manual operation Remote Alarm Contacts SPDT-8A-250VAC Isolating switch in the OFF position Transfer switch in normal position Transfer switch in alternate (emergency) position Time Delays Momentary normal power outage override (factory set at 4 sec) (emergency) power available delay (factory set at 1 sec) Retransfer to normal (factory set at 5 min) Generator cooldown (factory set at 5 min) Voltage Sensing Transfer to alternate (normal power dropout) 85% of nominal Phase reversal transfer to alternate Retransfer to normal (normal power pickup) 90% of nominal Audible Alarm (AIS Open) Alarm buzzer Generator Start Connection SPDT-8A-250V.AC 6

7 with Automatic Transfer Switch A06B A07B A9 A10 A11 B11 B11B B19A B19B C1 C4 C7 C10 C14 C15 C18 C19 C21 C22 C23 C24 Cx Lockout Circuit from other VPx Interlock Circuit from other VPx Low zone pump control function Medium zone pump control function High zone pump control function Built in alarm panel (120V.AC supervisory power) providing indication for: Audible alarm & silence pushbutton for motor run, phase reversal, loss of phase. Pilot lights for loss of phase & supervisory power available Built in alarm panel same as B11 but VAC supervisory power High motor temperature c/w thermoster relay and alarm contacts (DPDT) High motor temperature c/w PT100 relay and alarm contacts (DPDT) Extra motor run alarm contact (DPDT) Periodic test alarm contact (DPDT) Low pump room temperature alarm contact (DPDT) Low water reservoir level alarm contact (DPDT) Pump on demand / automatic start alarm contact (DPDT) Pump fail to start alarm contact (DPDT) High water reservoir level c/w visual indication and alarm contact (DPDT) Emergency start alarm contact (DPDT) Deluge valve start alarm contact (DPDT) Remote automatic start alarm contact (DPDT) Remote manual start alarm contact (DPDT) High pump room temperature alarm contact (DPDT) Additional visual and alarm contact (Specify function) (DPDT) Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package. D1 D1A D13 D14 D14A D14B D15 D24 D26 D26A D27 D27A D28 D37 E1 E2 E3 F2 F2A F2B F6 F10 Low suction pressure transducer for fresh water rated at 0-300PSI with visual indication and alarm contact Low suction pressure transducer for sea water rated at 0-300PSI with visual indication and alarm contact High withstand rating for (normal power section) 208V to 480V = 150kA 600V = 100kA Anti-condensation heater & thermostat Anti-condensation heater & humidistat Anti-condensation heater & thermostat & humidistat Tropicalization Audible Alarm Modbus with RTU frame format and RS485 connection Modbus TCP / IP provision Motor heater connection (external single phase power source and heater on/off contact) Motor heater connection (internal single phase power source and heater on/off contact) Customized drawing set Window kit for operator interface Permanent load shedding contacts Temporary pump motor start period load shedding contacts Temporary & permanent load shedding contacts Anti condensation heater & thermostat (alternate power section) Anti condensation heater & humidistat (alternate power section) Anti condensation heater & thermostat & humidistat (alternate power section) High withstand rating for (model GPU only) : 208V to 480V=150kA 600V=100kA IP55 assembly 7

8 with Automatic Transfer Switch L01 L02 L03 Other language and English (bilingual) French Spanish Additional Options: Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package. 8

9 Operator Interface Technical Data with Automatic Transfer Switch Current / Time Pressure L1-L2 L2-L3 L3-L1 V. / Hz V. / Hz A. / Hr Available Position Phase Reversal Low System Pressure Altern. Available Position Isolating Switch in Off Position System Trouble Cut-out Cut-in Reset Test Print Paper Feed Trouble Legend : P : Pump Starting Failure O : Overcurrent Problem U : Undercurrent Problem T : Pressure Transducer Problem 9

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass Project: Customer: Engineer: Pump Manufacturer: Submittal Document Model VPS Pressure Limiting (VFD) with Soft Start Bypass Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections Note:

More information

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU with Automatic Power Transfer Switch Contents: NOTE: The drawings included in this package are for controllers covered under our standard

More information

Drawing Submittal Package

Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch

More information

Drawing Submittal Package

Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch

More information

Technical Data Submittal Document

Technical Data Submittal Document Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPL + GLU Limted Service Full Voltage Across the Line Start Electric Fire Pump Controller Contents: Data Sheets Dimensional

More information

LMR Electric Fire Pump Controllers Features

LMR Electric Fire Pump Controllers Features 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status

More information

Technical Data Submittal Documents

Technical Data Submittal Documents Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model PD - FM Diesel Engine Driven Fire Pump Controller Contents: Data Sheets Dimensional Data Wiring Schematics Field

More information

LMR Electric Fire Pump Controllers Features

LMR Electric Fire Pump Controllers Features 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status

More information

FDF Foam Pump Controllers Features

FDF Foam Pump Controllers Features FDF100 Diesel Engine Foam Pump Controllers 1-1 Product Description The FDF Series of Foam Pump Controllers are designed for use with foam concentrate injection, foam transfer and water mist systems for

More information

Model GPS + GPU Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller with Automatic Power Transfer Switch

Model GPS + GPU Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller with Automatic Power Transfer Switch Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPS + GPU Full Service Reduced Soft Start Soft Stop Electric Fire Pump ontroller with Automatic Transfer Switch ontents:

More information

Model GPS + GPU Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller with Automatic Power Transfer Switch

Model GPS + GPU Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller with Automatic Power Transfer Switch Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPS + GPU Full Service Reduced Soft Start Soft Stop Electric Fire Pump ontroller with Automatic Transfer Switch ontents:

More information

Model GPP Full Service Reduced Voltage Part Winding Electric Fire Pump Controller

Model GPP Full Service Reduced Voltage Part Winding Electric Fire Pump Controller Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model GPP Full Service Reduced Part Winding Electric Fire Pump ontroller ontents: Data Sheets Dimensional Data Wiring Schematics

More information

Model GPW + GPU Full Service Reduced Voltage Wye-delta Closed Electric Fire Pump Controller with Automatic Power Transfer Switch

Model GPW + GPU Full Service Reduced Voltage Wye-delta Closed Electric Fire Pump Controller with Automatic Power Transfer Switch Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPW + GPU Full Service Reduced Wye-delta losed Electric Fire Pump ontroller with Automatic Transfer Switch ontents:

More information

Model GPY + GPU Full Service Reduced Voltage Wye-delta Open Electric Fire Pump Controller with Automatic Power Transfer Switch

Model GPY + GPU Full Service Reduced Voltage Wye-delta Open Electric Fire Pump Controller with Automatic Power Transfer Switch Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPY + GPU Full Service Reduced Wye-delta Open Electric Fire Pump ontroller with Automatic Transfer Switch ontents:

More information

FT60 Reduced Voltage - Autotransformer

FT60 Reduced Voltage - Autotransformer 1-1 Product Description The Automatic Transfer Switch Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer

More information

Model GPS Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller

Model GPS Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model GPS Full Service Reduced Soft Start Soft Stop Electric Fire Pump ontroller ontents: Data Sheets Dimensional Data

More information

Model GPA Full Service Full Voltage Across the Line Start Electric Fire Pump Controller

Model GPA Full Service Full Voltage Across the Line Start Electric Fire Pump Controller Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model GPA Full Service Full Across the Line Start Electric Fire Pump ontroller ontents: Data Sheets Dimensional Data Wiring

More information

Transfer Switch Features

Transfer Switch Features 1-1 Product Description The Automatic Transfer Switch Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer

More information

Model GPW Full Service Reduced Voltage Wye-delta Closed Electric Fire Pump Controller

Model GPW Full Service Reduced Voltage Wye-delta Closed Electric Fire Pump Controller Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model GPW Full Service Reduced Wye-delta losed Electric Fire Pump ontroller ontents: Data Sheets Dimensional Data Wiring

More information

Transfer Switch Features

Transfer Switch Features 1-1 Product Description The Automatic Transfer Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer and

More information

FT40 Reduced Voltage - Part Winding. Electrically and Mechanically

FT40 Reduced Voltage - Part Winding. Electrically and Mechanically LMR PLUS Electric Fire Pump Controllers with Transfer Switch Features FT40 Reduced Voltage - Part Winding 1-1 January 2012 Product Description The Automatic Transfer Switch Option may be added to any FD

More information

Soft Start Series MP700 Solid State, Reduced Voltage

Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s

More information

FD30 Full Voltage - Across the Line July 2011

FD30 Full Voltage - Across the Line July 2011 Must Be Installed Per Applicable Code and Manufacturers Recommendations Electric Fire Pump Controllers Features 1-1 FD30 Full Voltage - Across the Line July 2011 Power I/O Board Transformers Incoming line

More information

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps. Issued 2006/08/01 Section 13920 Packaged Fire Pumps and Controllers Page 1 of 7 PART 1 GENERAL 1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

FT20 Full Voltage - Limited Service. Electrically and Mechanically

FT20 Full Voltage - Limited Service. Electrically and Mechanically LMR PLUS Electric Fire Pump Controllers with Transfer Switch FT20 Full Voltage - Limited Service 1-1 May 2014 Product Description The Automatic Transfer Switch Option may be added to any FD type Fire Pump

More information

Fire Pump Controllers Medium Voltage Controllers

Fire Pump Controllers Medium Voltage Controllers Fire Pump Controllers Medium Voltage Controllers Medium Voltage Controllers 1.5 Medium Voltage Fire Pump Controllers FDM Medium Voltage... Part Number / Options Selection Guide... Product Specifications

More information

Customer Connection Terminals Connection terminals for external customer connections, are located at the top of the Power I/O board.

Customer Connection Terminals Connection terminals for external customer connections, are located at the top of the Power I/O board. Must Be Installed Per Applicable Code and Manufacturers Recommendations Electric Fire Pump Controllers Features 1-1 FD80 Reduced Voltage - Wye Delta (Star-Delta) Closed Transition Power I/O Board Transformers

More information

Variable Frequency Drive SERIES MP800 VFD

Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controls and Accessories Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for

More information

DIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers

DIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers DIESEL Engine Fire Pump Controllers Features FD120 Diesel Engine Controllers 1-1 March 2013 Diesel Product Description The DIESEL Plus Fire Pump Controllers from Eaton Corporation are designed to control

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features 1-1 Product Description The FD100 Diesel Engine Controller is designed to control and monitor 12 or 24 volt, diesel fire pump engines. All models are listed by UL and ULC, and approved by Factory Mutual

More information

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE SBP1000-61 FTA1000 Full Voltage Starting Electric Fire Pump Controllers Product Description Description Firetrol FTA1000 Full Voltage Fire Pump Controllers

More information

Fire Pump Controllers Foam (Additive) Controllers

Fire Pump Controllers Foam (Additive) Controllers Fire Pump Controllers Foam (Additive) Controllers Diesel Additive (Foam) Pump Controllers 1.4 Foam (Additive) Fire Pump Controllers FDF20 Foam (Additive) - Limited Service... FDF30 Foam (Additive) - Across-the-Line...

More information

FDJ SERIES Jockey Pump Controllers Features

FDJ SERIES Jockey Pump Controllers Features 1-1 NEMA 2 Enclosures Enclosures have an oven baked powder paint finish and are supplied with NEMA 2 rating, unless otherwise ordered. Available options include: NEMA 1, 3R,, X, 12. Note: NEMA, X enclosures

More information

Technical Data Submittal Documents

Technical Data Submittal Documents Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model PD Diesel Engine Driven Fire Pump Controller Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps Note: The A/E must choose all design values in brackets below before using in project specifications 1 General 1.1 Provide UL listed and FM approved fire pump complete with pump, driver, controller and

More information

SECTION Fire Pumps

SECTION Fire Pumps SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.

More information

Options for Diesel Fire Pump Controllers

Options for Diesel Fire Pump Controllers Options for Diesel Fire Pump Controllers 2015-2016 This document describes our standard options. Please consult factory for any additional options / features / modifications if required. Modifications

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features September 007 DIESEL Engine Fire Pump Controllers Features FD0 Diesel Engine Controllers 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller.

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

SECTION FIRE PUMPS 1.00 PART 1 & GENERAL Description of Work. A. Provide pumps for fire suppression Section Includes

SECTION FIRE PUMPS 1.00 PART 1 & GENERAL Description of Work. A. Provide pumps for fire suppression Section Includes SECTION 210200 Formatted 1.00 PART 1 & GENERAL 1.01 Description of Work A. Provide pumps for fire suppression. 1.02 Section Includes A. Single Stage, Double Suction, 8100 Series Horizontal Splitcase Fire

More information

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

Fire Pump Controller. For Electric Motor Driven Fire Pumps. Wye Delta Reduced Current Types

Fire Pump Controller. For Electric Motor Driven Fire Pumps. Wye Delta Reduced Current Types Fire Pump Controller For Electric Motor Driven Fire Pumps Wye Delta Reduced Current Types Series MP430 and Series MP435 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

PUMP CONTROL CENTER (PCC)

PUMP CONTROL CENTER (PCC) PART 1 SUMMARY A. In accordance with the plans and specifications, the Contractor shall provide and install a complete pre-fabricated, pre-tested ArcSafe Pump Control Center including all required equipment,

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

MANUAL FOR MODEL MP600 HIGH VOLTAGE ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS

MANUAL FOR MODEL MP600 HIGH VOLTAGE ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS MANUAL FOR MODEL MP600 HIGH VOLTAGE ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS Starting Serial No. "LH" This manual provides General Information, Installation, Operation, Maintenance and System Set-Up

More information

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification February 11, 2019 Master Panel Product Description The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with LMV3 or LMV5

More information

FTA550 JOCKEY PUMP CONTROLLERS

FTA550 JOCKEY PUMP CONTROLLERS FTA550 JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP550E (A) FTA550E XG Jockey Pump Controllers Product Description Failed to start indication Main switch not in Auto alarm Pressure recording

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

Microprocessor Based Wye-Delta Reduced Current Type Starting

Microprocessor Based Wye-Delta Reduced Current Type Starting Metron Fire Pump Controls and Accessories NEW Microprocessor Based Wye-Delta Reduced Current Type Starting PRODUCT PILOT SERIES MPT430TS (Open Transition) - MPT435TS (Closed Transition) ONLY 32 WIDE WITH

More information

P.C. Simonton & Associates, Inc. Consulting Engineers. Paul C. Simonton

P.C. Simonton & Associates, Inc. Consulting Engineers. Paul C. Simonton P.C. Simonton & Associates, Inc. Consulting Engineers 309 North Main Street 1050 Parkside Commons Post Office Box 649 Suite 101 Hinesville, Georgia 31310 Greensboro, Georgia 30642 Addendum No. One Date:

More information

EATON LMR Plus Electric Fire Pump Controllers

EATON LMR Plus Electric Fire Pump Controllers O & M Manual IM05805020K EATON LMR Plus Description Page 1. INTRODUCTION... 3 2. INSTALLATION AND ELECTRICAL CONNECTIONS... 3 3. HARDWARE DESCRIPTION... 4 4. OPERATION...7 5. PROGRAMMING... 8 6. HISTORY,

More information

A. This Section includes transfer switches rated 600 V and less, including the following:

A. This Section includes transfer switches rated 600 V and less, including the following: SECTION 16415 - TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

PILOT SERIES MPT700TS

PILOT SERIES MPT700TS Metron Fire Pump Controls and Accessories Microprocessor Based Soft Start/Stop Solid State Reduced Voltage NEW PRODUCT PILOT SERIES MPT700TS ONLY 32 WIDE WITH ATS Available in Across-The-Line, Soft Start,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 3323 - CENTRAL BATTERY EQUIPMENT [for Evanston campus only] PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Remote Alarm Panels Features

Remote Alarm Panels Features Features 1-1 DFDAP-M / FDAP-M Remote Product Description Eaton s Remote s are designed to provide audible and visual alarms for Electric and Diesel Fire Pump Controllers. These remote panels are located

More information

SECTION 4000 LIFT STATIONS

SECTION 4000 LIFT STATIONS SECTION 4000 LIFT STATIONS LIFT STATIONS PART 1 GENERAL 1.01 Section Summary A. Lift station control panels. B. Related requirements include those established in the General Requirements Division 1, Division

More information

Commercial and Light Industrial Fire Alarm Control Panel

Commercial and Light Industrial Fire Alarm Control Panel FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel Features Easily expandable. All new plug-in board design Two supervised audible circuits Lamp and system trouble circuit test Ground

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

FTA550F JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA550F JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA550F JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP550F (A) FTA550F XG Jockey Pump Controllers Product Description Description Firetrol FTA550F XG Jockey Pump Controllers are intended for use

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014 January 16, 2014 Release Control Panel 290a 1. Description The Viking VFR400 is a microprocessor based releasing control panel for use on preaction, deluge, Surefire, Firecycle multicycle sprinkler systems,

More information

Table of Contents. Protective Relays

Table of Contents. Protective Relays Table of Contents KILOVAC WD Series, DIN Rail or Screw Mounted Introduction..........................................................11-2 KILOVAC WD25 Paralleling Relays........................................11-3

More information

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx:

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx: UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK 40 Dale Street West Babylon, NY 11704 Ph: 631-753-9550 Fx: 631-753-9560 www.unionconnector.com Emergency Automatic Transfer System STANDARD SPECIFICATIONS

More information

Moulded case circuit brakers

Moulded case circuit brakers Moulded case circuit brakers CONTENT Range 1 Protection Releases 2 Salient Features 5 Accessories 7 Widest Range 10 Time Current Characteristics 12 Overall Dimensions 14 SN4 SN3 SN2 SN1 3 RANGE SN1 Rated

More information

Model GPD Diesel Engine Driven Fire Pump Controller

Model GPD Diesel Engine Driven Fire Pump Controller Project: ustomer: Engineer: Pump Manufacturer: Submittal Document Model GPD Diesel Engine Driven Fire Pump ontroller ontents: Data Sheets Dimensional Data Wiring Schematics Field onnections Note: The drawings

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel PROTECTOWIRE FireSystems Features Easily expandable Two supervised audible circuits Lamp and system trouble circuit test Ground fault detection Initiating device circuit (IDC) alarm test Monitors up to

More information

TS Series. Technical Instructions. Document No. TS-4000 June 25, TS-CE Combustion Enclosures with LMV5. Description

TS Series. Technical Instructions. Document No. TS-4000 June 25, TS-CE Combustion Enclosures with LMV5. Description SCC Inc. TS Series TS-CE Combustion Enclosures with LMV5 June 25, 2018 Description TS-CE series combustion enclosure with Siemens LMV5 linkageless controller sets the standard for combustion control and

More information

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design TOTAL SOLUTIONS Liquid Level Control Product Guide MATELEC innovative by design Liquid Level Control Contents Dual Pump Controllers Section 1 The Range Common Features Operating Data Control Logic Setup

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES. READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION.

BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES. READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION. INSTALLATION INSTRUCTIONS FOR SYMCOM S CONTROL MODEL PC-05 BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES. READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION.!

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

SCC Inc. TS Series. Technical Instructions. Document No. TS 1000 June 25, TS Touchscreen Kits. Description. Touchscreen

SCC Inc. TS Series. Technical Instructions. Document No. TS 1000 June 25, TS Touchscreen Kits. Description. Touchscreen TS Touchscreen Kits for use with LMV3, LMV5 and RWF Controls June 25, 2018 Touchscreen Description Plate Kit Enclosure TS series touchscreen kits provide a human machine interface (HMI) with a Siemens

More information

Packaged Instantaneous Circulation Heater Full KW Selection In All Voltages, Single or Three Phase

Packaged Instantaneous Circulation Heater Full KW Selection In All Voltages, Single or Three Phase Features Heavy Duty Construction Constructed with high grade materials to ensure long operating life Turn-Key package is simple to specify and operate Factory wired electrical controls provide trouble-free

More information

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL SECTION 21 30 00 FIRE PROTECTION PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00,

More information

Model APD. Remote alarm panel for diesel motor driven fire pump. Drawing Submittal Package

Model APD. Remote alarm panel for diesel motor driven fire pump. Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Model APD Remote alarm panel for diesel motor driven fire pump Drawing Submittal Package Contents: Brochure Dimensional Data Wiring Schematics Field Connections

More information

Centro-Matic Automated Lubrication Systems System Controls

Centro-Matic Automated Lubrication Systems System Controls Selecting the right controls for your automated lubrication system is one of the last steps in the design process. Several different models may be chosen to control power-operated pumps, depending on the

More information

SCC Inc. TS Series. Technical Instructions. Document No. TS 5000 February 12, TS CE Combustion Enclosures with LMV3.

SCC Inc. TS Series. Technical Instructions. Document No. TS 5000 February 12, TS CE Combustion Enclosures with LMV3. TS CE Combustion Enclosures with LMV3 February 12, 2019 Description TS CE series combustion enclosure with Siemens LMV3 linkageless controller sets the new standard for combustion control and monitoring

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

FTA200-A REMOTE ALARM PANEL

FTA200-A REMOTE ALARM PANEL FTA200-A REMOTE ALARM PANEL (FOR USE WITH ELECTRIC FIRE PUMP CONTROLLERS) STANDARD SUBMITTAL PACKAGE SBP200A FTA200-A Remote Alarm Panels for Electric Fire Pump Controllers Product Description Type A -

More information

Conventional Releasing Control Panel

Conventional Releasing Control Panel s Data Sheet Fire Safety Products Conventional Releasing Control Panel Pre-Action Deluge Agent-Releasing Fire System Model TXR-320 Remote configurable Up to two (2) hazard areas Operable with the following:

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

R E C T I F I E R I N V E R T E R C O N V E R T E R SB7

R E C T I F I E R I N V E R T E R C O N V E R T E R SB7 SCR Battery Charger Product Specifications Description The is RIC Electronics premiere SCR battery charger/rectifier. The provides power to critical DC loads through a wide range of outputs and is engineered

More information

Heating Cable. Description

Heating Cable. Description ITLS Base Panel 10 VGA Touch Screen HMI 40 Amps/Loop @ 100 480 VAC 6 Loops to 72 Loops NEMA 4 or NEMA 4X Enclosure SCR Control Integral Circuit Panel with Circuit Breakers Optional Main Disconnect Soft

More information

ASCO Series 185 Power Transfer Switches

ASCO Series 185 Power Transfer Switches ASCO Series 185 Power Transfer Switches 24-hour protection no matter when trouble strikes ASCO Series 185 POWER TRANSFER SWITCHES An Automatic Transfer Switch helps prevent... Your business or home from

More information

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH CONTROL PANEL INTERFACE USING THE AUTO/OFF/MANUAL SWITCH With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting occurs when utility power source

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

7800 SERIES RM7840E,G,L,M; EC7840L Relay Module

7800 SERIES RM7840E,G,L,M; EC7840L Relay Module 7800 SERIES RM7840E,G,L,M; EC7840L Relay Module SPECIFICATION DATA Valve Proving features including: VPS test time When (Never, Before, After, Split or Both) FEATURES APPLICATION The Honeywell RM7840 is

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features. CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information