1 DIXON UNIFIED SCHOOL DISTRICT DIGITAL INTERCOM / CLOCK & BELL SYSTEM PART 1 GENERAL 1. SECTION INCLUDES a. Furnish and install a complete computer based and controlled voice communications system with all wire, outlets, and equipment as may be required, as shown on the drawings, and as specified herein to provide a complete and operational sound and voice communications system. b. Provide all labor, engineering, design, testing, materials, components and supervision necessary to provide a complete operating sound and voice communications system. 2. Provide District training per District requirements 3. RELATED SECTIONS a. Drawings and general provisions of the Contract, General and Special Conditions and Division Sections apply to this. b. Basic Electrical Methods and Materials: Intercom & Clock systems infrastructure 4. SYSTEM DESCRIPTION AND SCOPE OF WORK a. The work provided herein consists of furnishing and installing all equipment, cabling and labor required for a complete, operable, new computer based administrative communication and control system as shown on the plans and specifications. b. The system shall provide a communications path to all classrooms, workrooms, multi-purpose rooms, offices and corridor speaker locations and all exterior speaker locations. The communications path shall be separate from voice processing system allowing simultaneous use of classroom telephone and receipt of intercom pages to the speaker without interruption. c. If a telephone system is provided by owner, the system shall be interfaced to the telephone system allowing any telephone location, with the entry of a password, to initiate a page, call a specific room or zone, or initiate an emergency or time tone. d. The equipment specified herein and shown on the drawings is based upon equipment as manufactured by Teradon/ThreeSixty Industries. The intent is to establish a standard of quality, function, and features. It is the responsibility of the bidder to insure that the system meets or exceeds all standards set forth in these specifications. e. The contractor shall provide all support to the District to interface the system to other communication devices. f. The contractor shall have a factory trained service department on call 24 hours a day, 365 days a year, to service the specified product. The systems contractor must be able to provide a 4 hour response time. g. The installation contractor shall be factory authorized to install, program and maintain the voice communication system. h. The contractor shall maintain adequate stock of potential replacement parts including clocks, speakers, exterior hom speakers, back boxes, grilles, remote speaker cards, Raptor V laptop computer and power supplies to service the system should component failure occur. It is recommended that the contractor maintain a stock Raptor Intercom system. This will provide all of the required parts. The purpose of this is to have sufficient stock to never allow any system to be down more than 24 hours due to any catastrophic failure such as lightning damage, flooding, etc. 5. SUBMITTALS a. Contractor is to submit the following prior to construction for Contractor and District approval. b. Contractor will provide, prior to installation, a current letter of recommendation from the manufacturer, addressed to the District. Letter of recommendation must be given to General Contractor at time of bid. Contractor must be certified with the manufacturer at least twelve (12) months prior to letter of recommendation. Please reference project number. c. Contractor will provide data of factory certified installers experience and qualifications, which shall include three (3) years on projects of similar complexity. Include names and locations of two (2) projects successfully completed using a Teradon/ThreeSixty Voice Communications & Sound System. Include written certification from users that systems have performed satisfactorily for not less than 18 months. d. Provide documentation stating you have been in the telecommunication contracting business for a minimum of five (5) years under the same name and are located within a four (4) hour response time of the District. e. Product Data: i. Manufacturer's data, user and installation manuals for all equipment and software programs including computer equipment and any other equipment required for the Voice Communications & Sound System ii. Preparation instructions and recommendations iii. Storage and handling requirements and recommendations iv. Installation methods v. Labeling and schematic for cabling and components. Voice Communications & Sound System contractor must coordinate with Electrical contractor for labeling of cable. vi. Parts list and quantity of each part

2 f. Shop drawings shall provide details of proposed system and the work to be provided. Include point-to-point drawings of systems and wiring diagrams of individual devices. i. Detailed wiring diagrams and system description ii. System device locations on architectural floor plans iii. Full Schematic of system, including wiring information for all devices g. Training Schedule to provide details for the District staff. Include time line with class types and descriptions and amount of people that can attend along with location. 6. CLOSE OUT a. Documentation to be submitted by the Contractor upon completion of system installation: i. Upon completion of installation, the Contractor shall prepare "As Builts" drawings of the system. These As Builts shall be 30 inches by 42 inches (76 cm by 107cm) format Mylar reproducible drawings of each floor plan indicating exact device locations, cable routes and wire numbers as tagged on the cable tag. ii. As Builts shall be submitted to the contractors for approval prior to the system acceptance walk through. iii. Operation and maintenance manuals: three sets of operating manuals shall be provided electronically and in written binder format explaining the operation and maintenance of the system. iv. Maintenance required and maintenance schedule v. The system contractor shall generate a list of call stations and their associated rooms to be given to the school. 7. DELIVERY STORAGE AND HANDLING a. Deliver materials in manufacturers original new, unopened, undamaged containers; and unharmed original identification labels. b. Store products in manufacturers unopened packaging until ready for installation c. Protect and store materials from environmental and temperature conditions following manufacturer s instructions. d. Handle and operate products and systems according to manufacturer's instructions 8. MANUFACTURER a. Raptor V Intercom by Teradon/ThreeSixty, Inc. or District approved equal. 9. SYSTEM DESCRIPTION a. The system shall consist of a central equipment cabinet, system server running computer based intercom operations software, power supply, zone cards, Executive Handsets, amplifiers, classroom loudspeaker assemblies, and all associated material, hardware, wiring, and options as described herein to provide a complete working system which shall meet the specified requirements. b. The system shall provide the following communication paths and functions: i. Executive control to a single classroom loudspeaker. ii. Executive control to executive control. iii. Executive control to classroom phone. iv. Simultaneous program distribution directed from an executive control without interrupting the intercom channel. v. Executive control or classroom telephone (with pass code) to any of the system programmable 999 paging zones. vi. Executive control or classroom telephone (with pass code) to any of the 999 emergency alerts in the system. vii. Executive control to Teradon/ThreeSixty IP softphone from any Windows based computer viii. Expandable up to 255 simultaneous intercom and 255 simultaneous paging channels c. The system shall provide the facilities for: i. Paging ii. Sounding emergency signals iii. Timed event signals iv. Control and distribute multiple program channels to individual classrooms, selected groups, or all classroom speakers. v. Programmable input and output events without the need for additional hardware d. The system computer shall include the capabilities to act as the master clock and will be capable of correcting compatible brands of analog and digital secondary clocks. The system clock shall be capable of being automatically updated with the atomic clock on the Internet or the Districts time server via LAN or WAN connection. e. The system shall use standard 25-volt technology. f. The system shall also be capable of providing standard Telephone functions as the PBX/ phone system in the school connected to external trunk lines provided by telecom provider. The system will supply the school with the following features on the telephone system: i. Capability to accommodate up to 999 telephone extensions without the addition of another PBX/system. Systems that require an additional PBX/system to be tied into the intercom is not considered equal. ii. SIP Compliant iii. Caller ID iv. Voice mail for each user with notification when mailbox approaches maximum size.

3 v. Automated attendant vi. Call forwarding vii. Call waiting viii. Conference calling g. The system shall provide for Remote Addressable Units (RAU) connected to the Central Equipment cabinet via new copper cabling or a single pair of multimode or single mode fiber optic in a star topology. All RAU's to be located at or near IDF's. All local room wiring for speaker, call-in and VOIP or Analog Telephone should be cabled via existing or new CAT6 homerun to each local RAU. Must be able to accommodate RAU's in both single building and multi-building complexes with only a single connection between the head-end and the RAU. Individual homeruns to the head-end are unacceptable. The use of punch downs and 25, 50 or 100 pair wire runs back to head end are not considered equal. The purpose of this system design is to add modular expandability at each IDF closet location in the school. Systems that require master control cards found in the head end rack to also be located in RAU's for communication are not considered equal. 10. SYSTEM FUNCTION a. The system shall provide a minimum of the following: i. Provide computer-based equipment of plug and play design, utilizing plug in connections between the system control computer and the system cards. ii. Ability to interconnect multiple Raptor V Systems for global emergency communication iii. Provide SIP gateway to owner furnished SIP compliant telephone systems iv. Ability to perform district wide or site to site paging v. Ability to perform site to site intercom calls vi. Utilize the latest in EVO technology for Video override of Teradon/ThreeSixty's Trilo digital signage solutions vii. Ability to perform page, intercom, manual audio event, or music call from any Windows based computer running Teradon/ThreeSixty softphone program viii. Emergency calls shall be set to take precedence over all routine calls. ix. Optional ipad testing app x. Optional UPS (uninterruptible power supply) shall be provided to maintain system integrity in instances of power loss. xi. Distribution of paging announcements via any Executive control handset, telephone interface, or system computer. xii. System shall be capable of accommodating 999 Executive Handsets, Teradon/ThreeSixty SIP softphones, or classroom phones in any combination. xiii. Classroom loudspeakers are user programmable to any of 999 paging or class change zones. Systems not capable of handling a minimum of 75 zones shall not be acceptable. xiv. Each Room/Call-in can be designated as either an Intercom Call-in or a Special Event function. 1. Call-in: Each Call-in Shall be capable of producing a 'Normal' Call-in event, an 'Emergency' Call-in event or a special event. a. Special Event: Each Room/Call-in shall be capable of being redefined for a special event on Callin. The Special event will generate any system- defined tone for the specified duration to any programmed paging zone xv. System shall be capable of utilizing standard.wav or.mp3 files for sound generation. System shall come equipped with a minimum of 30 sound selections, including multiple bells, custodial, and emergency tones. xvi. Programmable tones such as warble, siren, chime, etc shall be available. 30 different tones shall come on the system. The owner shall have the ability, without requiring a service call to the Contractor, to add unlimited additional tones or unlimited pre-recorded messages and announcements to the system. xvii. The system shall be able to handle unlimited owner provided.way or.mp3 file imports for tones. xviii. The system shall be able to provide 2 auxiliary contact closures per speaker card that are triggered on any of the following events: 1. Bells 2. All Page 3. Special Events 4. Timed Correction for external systems such as mechanical clock correction or lighting control xix. Last number redial xx. Speed dial access to specific functions. xxi. User Programmable "soft-keys" to initiate action such as emergency, all-page, and bells with a single touch of a button. xxii. Clear all registered calls xxiii. Calls shall repeat until ring count is reached for each Executive Handset. xxiv. The system shall come equipped with 2 Executive Handsets, with built in microphone, Caller Id, speaker, and hands free speakerphone. xxv. The system shall have the following station design: xxvi. Each classroom shall be considered one station and shall have a dedicated audio circuit to the central equipment cabinet or RAU.

4 xxvii. All outside horns shall be zoned separately. xxviii. Each grade level shall be independently grouped into its own zone separately. xxix. All zones shall be verified with District Representatives. xxx. Capability for an Executive Handset or telephone interface with the system to direct a program to any one, group of, or all remote stations. xxxi. Programmable system functions, including: digit user programmable room dialing 2. Caller Id to the Executive Handset, as well as classroom phones if equipped. 3. Systems that must have separate caller ID modules will not be accepted. 4. Unlimited user events and user tones. 5. Unlimited bell schedules. 6. Ring up to 3 simultaneous event/bell schedules multi-purpose zones on systems installed. Systems that require multiple Master Control Units to be networked together to accomplish this number of zones are not considered equal. 8. Automatic distribution of user programmable time events activated by the internal clock. 9. School programmable room stations, zones, or multiple zones to receive the program source on a selected basis. School shall be able to access the computer and assign room, zone, and events with a single point and click. 10. Compatible with standard Bellcore Caller Id Remote Display Units for display of incoming calls. 11. System is to be compatible with DTMF phone system and be able to use touch tone phones to make and receive call from within the system. 12. System is to have a user-programmable, UPS backed master clock. 13. System shall be able to drive a combination of both digital and analog clocks on the same circuit from within the system 14. System capacity shall be up to 4096 remote stations and call points with a minimum capacity of2 Executive Handsets expandable up to Handsets can be either analog, SIP/IP, or any combination of both. 16. The system must be able to accept unlimited system inputs to integrate to external special systems, which the school wishes to generate an event or tone on the intercom. 17. The system shall support ''remote speaker cards" allowing for speaker cards/stations to be located throughout the building or buildings. 18. Systems that require all speakers and call switches be home run to the head-end and that do not support the placement of "remote speaker cards" are not acceptable. b. Remote Access and Programming i. Web Interface: The system shall provide password protected web programming from any internet connection. The web interface shall include the minimum functions: 1. Bell Schedule creation and modification 2. Zone configuration and management 3. Extension programming 4. Tone Configuration 5. Ability to create, upload and distribute audio files a single site or to multiple systems at the same time. Audio files to include voice recording, site created or downloaded audio files. 6. Upload audio files or create 'on the fly' announcements 7. Multiple levels of access for local site level access and district wide access. h. Ability to view system log files. 8. Systems that do not provide a constant, web based and web accessible programming option for the end user will not be accepted. ii. Configuration: The system shall provide password protected Remote Configuration features via a TCP/IP network based LAN or WAN including: 1. Speaker card configuration 2. Room configurations 3. System Diagnostics iii. Assistance: The system shall provide password protected Remote Assistance features via a TCP/IP network based LAN or WAN including: 1. Operating System trouble shooting/diagnostics 2. Database maintenance 3. File transfers c. Remote Addressable Unit (RAU) i. Remote Addressable Units shall consist of: 1. Rack mount 120w amplifiers located in Central System Equipment

5 2. Rack Audio Bridge in 1 U fully enclosed chassis located in Central System Equipment 3. Up to 254 Speaker/Call-in Modules in 1 U fully enclosed chassis located in Remote System Equipment 4. Fiber Transmitters and Receivers (if fiber is used) or copper connections (if copper is used) ii. Remote System Equipment shall be connected in a star topology to the Head end via: 1. Copper: CAT6 cable; and three (3) individually shielded pair18awg Stranded cable - Belden 9369 or equal. a. All speaker cards connected via copper must be equipped with EVO Emergency Voice override to allow for emergency paging in the event of a power failure. Part# IC1100RC 2. Fiber: 2 strands fiber-optic cabling between head-end and each RAU iii. Local room wiring for speaker and call-in should be cabled in CAT 5/6 or 18AWG stranded cable homerun to each local Remote System Equipment. 11. WARRANTY AND TRAINING a. The system contractor shall warrant any equipment installed under this specification to be free from defect for a period of one (1) year from the date of final acceptance. b. The system contractor shall provide a minimum of 20 hours training for the school district personnel on proper operating procedures for the system after completion per campus. This will include a follow up "advanced" training no later than three (3) months after initial training up to four (4) separate site visits. i. Initial Training will cover use of all telephones both executive and classroom. In addition, contractor is required in initial training to provide instruction to district personnel on bell schedule, music playing, zone creation and back up procedures to ensure that the district can control their system without a service call to change bell schedules, create zones or back up any changes that they make. 12. EQUAL REQUESTS To be considered equal to the Teradon/ThreeSixty Raptor V intercom, the proposed system must be capable of the following key features to the owner. Documentation shall be provided to owner/engineer to prove claims of equality. a. System shall provide for programming both on and off site via LAN/WAN connection. b. Equal proposing systems shall provide for complete programming by the owner including a computer for each site as well as lifetime licensed software to the owner. The purpose of this is to reduce the service calls required for simple schedule changes, bell tone imports, zone changes etc. System computer provided shall be rack mounted with the following minimum capabilities: i. Standard Windows 7 embedded OS (or newer) Rack Mounted computer with minimum of (2) 60G solid state hard drive in a raid 1 CONFIGURATIONS, Xeon processor, 4G RAM minimum ii. Optional Monitor and Keyboard shall be provided with computer and shall be industry standard rack mounted equipment. Non Rack mount equipment will not be acceptable. c. System installed in each school shall be capable of 999 paging zones not dependent upon wiring configuration. Systems that require multiple Master controlling Cards must provide sufficient quantity of cards to accomplish this minimum number of zones. d. System must be capable of unlimited available schedules. e. System shall have capabilities for 999 manually activated bell tones. f. System shall be capable of importing.wav or.mp3 files for use as emergency tones or bell tones. g. System shall provide for capabilities of up to 999 analog, IP or combination of the two. These can be either classroom and or executive. h. System must be capable of "On the Fly" Recorded massaging at master pc. i. System must be capable of3 Active simultaneous event/bell schedules. j. System to be installed shall be capable of up to 13 phones without additional equipment Management: The system shall provide password protected Remote Management features via a TCP/IP network based LAN or WAN including: i. Bell Schedule adjustment ii. Tone Configuration iii. System Time Adjustment 13. EXAMINATION a. Examine areas to receive devices and notify adverse conditions affecting installation or subsequent operation b. Do not begin installation until unacceptable conditions are corrected c. If preparation is the responsibility of another installer, notify General Contractor of unsatisfactory preparation before proceeding d. Ensure selected location is secure and offers protection from accidental damage. e. Location shall provide reasonable temperature and humidity conditions, free from sources of electrical and electromagnetic interference. f. Ensure power source is protected against accidental shutoff g. The contractor shall provide the following services as part of the contract: i. Supervision of sub-contractors

6 ii. Coordination of other contractors for system related work (electrical contractor, finish hardware contractor, general contractor and District representative) iii. Attending site construction/coordination meetings iv. Keeping updated construction drawings at the construction site v. Meeting construction deadlines per the construction schedule PART 2 PRODUCTS 1. SYSTEM COMPONENTS a. Central System Equipment i. Teradon/ThreeSixty AR1000 Series Raptor V intercom computer. ii. Standard Windows 7 embedded OS (or newer) Rack Mounted computer with minimum of (2) 60G solid state hard drive in a raid 1 CONFIGURATIONS, Xeon processor, 4G RAM minimum. Teradon/ThreeSixty T9008R-R iii. Amplifier: 120 Watt Modular Amplifier; provide minimum (2) amplifiers sufficient to provide 1 Watt per interior speaker and 12 Watt per exterior speaker. Teradon/ThreeSixty T-1S120 iv. Communication Card: Teradon/ThreeSixty IC1110R-8 Rack Mount Converter Card with 8 Ports v. VOX Card: Teradon/ThreeSixty IC1130R Rack Mount VOX Card vi. 4 Channel Mixer Card: Teradon/ThreeSixty IC1150R Rack Mount 4 Channel Mixer Card vii. Optional Rack Mount CD player Teradon/ThreeSixty part number T6221 viii. Optional Monitor, Keyboard and Mouse: Teradon/ThreeSixty RMM425B Rack Mount 15" TFT Monitor, Keyboard & Mouse Ensemble ix. Rack Mounted UPS I Battery Back-up: TUPS VA Uninterruptible Power Supply x. Cabinet: Teradon/ThreeSixty 6622 Stand Alone Cabinet with 22 Rack Units of Vertical Space or larger depending upon size of system. b. Executive Control Handset i. Teradon/ThreeSixty A9007 Executive Phone ii. Color: Charcoal iii. Executive Control Phones shall be installed as determined by District staff c. Classroom Clock I Speaker Combo i. Clock: Teradon/ThreeSixty wired or wireless clock ii. Volume Control: integrated w/speaker, recessed d. Classroom and Corridor Speakers for suspended ceilings i. Speaker/Grille/Back Box: Teradon/ThreeSixty S8054W25/70-CW, A5000, A5050 e. 2X2 Lay in speaker for suspended ceilings: Teradon/ThreeSixty TQS12 f. Exterior Speakers i. Teradon/ThreeSixty TQH16T g. Remote System Equipment i. Speaker Card: Teradon/ThreeSixty IC11OORC Speaker Card ii. Speaker Card Power Supply: Teradon/ThreeSixty IC11OOPS iii. Amplifier: Teradon/ThreeSixty models T-1S Watt, TA Watt per requirements. iv. Vox Card: Teradon/ThreeSixty IC1130R H. Telephone Interface Device h. Telephone Interface Device i. Telephone interface to existing telephone system is provided in the IC2000 Audio Conference Bridge i. Miscellaneous i. Call-in Switch: Teradon/ThreeSixty A2001 Call-In Switch ii. Executive Analog Phone: A9007 iii. Executive VOIP Phone: A9002 iv. Classroom Analog Phone:A9006 v. Classroom VOIP Phone: A9004 vi. Remote Access Software: provide the capability to install at owners request (2) copies of Remote Access Software PART 3 EXECUTION 1. INSTALLATION a. Install per manufacturers specifications b. Speakers on the drawings are shown in their approximate location and for quantities needed. The Contractor shall coordinate exact locations and quantities of all clock and speaker locations with the District's Representative. Installation of all ceiling speakers shall be coordinated with these plans. In general: Corridor speakers shall be centered and spaced 20 feet apart. Classroom speakers shall be centered in the room, or centered on the wall where wall mounting is required. Gym, Media Center,

7 Auditorium, Cafeteria, etc. speakers shall be positioned for proper sound coverage, avoiding ceiling sound panels and include appropriate protective wire guards. 2. WIRING a. Size and quantity of conductors shall be in accordance with manufacturer's requirement for cabling. Cables may be run in conduit or in return air plenums provided the cable is UL listed for Plenum use. b. CAT6 or 18AWG stranded cabling shall be utilized for speaker, call-ins, and Executive Handsets. c. The number of clocks on each run and the distance for the clock runs will determine secondary clock wiring. d. Cable manufactures i. 18 AWG: West Penn, Belden, or equivalent ii. CAT6 CommScope or Amp Netconnect 1. CommScope or Amp Netconnect for indoor/outdoor- rated cabling

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

GAI-Tronics Corporation. Serverless Page Party (SP2) Publication : SP2 Intelligent Intra-Plant Communication and Emergency Notification System

GAI-Tronics Corporation. Serverless Page Party (SP2) Publication : SP2 Intelligent Intra-Plant Communication and Emergency Notification System GAI-Tronics Corporation Serverless Page Party (SP2) Publication 160501: SP2 Intelligent Intra-Plant Communication and Emergency Notification System Guide Specification for NEC Standards Contents 1. General...

More information

_5120_School_Intercom_Rack_Spec.doc 09/21/04

_5120_School_Intercom_Rack_Spec.doc 09/21/04 ****************************************************************************************** 16720-3 Simplex TrueCom 5120 Inter Communication System Advanced 360 Station, Rack Mounted, Intercom / Paging

More information

POPE FRANCIS HIGH SCHOOL SPRINGFIELD, MA BID SPECIFICATION PUBLIC ADDRESS AND INTERCOM SYSTEM

POPE FRANCIS HIGH SCHOOL SPRINGFIELD, MA BID SPECIFICATION PUBLIC ADDRESS AND INTERCOM SYSTEM POPE FRANCIS HIGH SCHOOL SPRINGFIELD, MA BID SPECIFICATION PUBLIC ADDRESS AND INTERCOM SYSTEM 1.1 SUMMARY REQUIREMENTS A. The Public Address and Intercom, and Clock systems shall provide the school with

More information

5120_School_Intercom_Rack_Spec.doc 10/10/07

5120_School_Intercom_Rack_Spec.doc 10/10/07 ****************************************************************************************** 16720-3 Simplex TrueCom 5120 Inter Communication System Advanced 360 Station, Rack Mounted, Intercom / Paging

More information

STATEMENT OF WORK. System Description:

STATEMENT OF WORK. System Description: STATEMENT OF WORK Scope of Work: To install a paging/sound system throughout the Rapid City Swim Center (RCSC). This work shall includes all labor, material equipment and related services necessary to

More information

PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION

PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION Section 00000 SECURITY PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION PART 1 GENERAL A. The intent of this document is to specify the minimum criteria for the design,

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

ACTIVE INFRARED BARRIER

ACTIVE INFRARED BARRIER Although PROTECH provides high security indoor intrusion sensors for the military and government markets, our specialty is outdoor protection. Since we first introduced our PIRAMID outdoor dual technology

More information

BSD Technical Standard. Division 28: Electronic Safety & Security

BSD Technical Standard. Division 28: Electronic Safety & Security Division 28: Electronic Safety & Security I. PURPOSE This Technical Standard is a narrative describing Beaverton School District s (BSD s) basis of design for electronic safety and security in BSD facilities.

More information

SECTION INTERCOMMUNICATION SYSTEM 1. GENERAL 1.1 DESCRIPTION

SECTION INTERCOMMUNICATION SYSTEM 1. GENERAL 1.1 DESCRIPTION SECTION 27 51 23 INTERCOMMUNICATION SYSTEM 1. GENERAL 1.1 DESCRIPTION A. The requirements of the contract documents, including the General and Supplementary General Conditions and Division 1 - General

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

TrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description

TrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description TrueCom Building Communications Systems 5115-Series 5115-9001, -9002 Area of Rescue Communications System Description The Simplex 5115-9001 and -9002 Area of Rescue Communications System provides buildings

More information

CRESTRON MEDIAMANAGER INTELLICLASS

CRESTRON MEDIAMANAGER INTELLICLASS CRESTRON MEDIAMANAGER INTELLICLASS Crestron IntelliClass systems provide educators with a simplified yet comprehensive classroom presentation solution that saves time and money. Designed to deliver the

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

Architect s Project Number of 12 Intercom Systems District Master Specs 2013 Edition

Architect s Project Number of 12 Intercom Systems District Master Specs 2013 Edition PART 1 GENERAL 1.1 SECTION INCLUDES A. Intercom equipment B. Intercom cable C. Accessories D. Surge Protection 1.2 REGULATORY REQUIREMENTS A. System: Listed by UL, ETL, or FM 1.3 SYSTEM DESCRIPTIONS SECTION

More information

SECTION VIDEO SECURITY COMMUNICATION SYSTEM. Logo. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

SECTION VIDEO SECURITY COMMUNICATION SYSTEM. Logo. Display hidden notes to specifier by using Tools / Options / View / Hidden Text. SECTION 13702 VIDEO SECURITY COMMUNICATION SYSTEM Logo Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Video security communication

More information

SECTION Mass Notification Systems

SECTION Mass Notification Systems Specifier Notes: This product guide specification is written according to the Construction Specifications Institute (CSI) 3-Part Format, including MasterFormat, SectionFormat, and PageFormat, as described

More information

Appendix 1 LACCD Districtwide Security Performance Requirements

Appendix 1 LACCD Districtwide Security Performance Requirements Appendix 1 LACCD Districtwide Security Performance Requirements SECTION LISTING 28 01 10 Overview 28 13 00 Access Control System 28 13 01 Access Control System Installation 28 13 26 Access Control Remote

More information

Gmini 100. User Guide INTELEC SYSTEMS Intelligent Electronic Systems. Web:

Gmini 100. User Guide INTELEC SYSTEMS Intelligent Electronic Systems. Web: Gmini 100 User Guide INTELEC SYSTEMS Intelligent Electronic Systems 2014-2015 Web: www.intelec-systems.com Copyright Copyright cc, South Africa November 2014, February 2015, October 2015. Revision 4.1

More information

Fire Protection Systems FST 209. COURSE SYLLABUS Fire Protection Systems FST 209 [Semester] CRN 3 Credits

Fire Protection Systems FST 209. COURSE SYLLABUS Fire Protection Systems FST 209 [Semester] CRN 3 Credits COURSE SYLLABUS Fire Protection Systems [Semester] CRN 3 Credits Instructor Name: Instructor Email: Instructor Phone: Office Hours: Class Meeting Dates/Location/Time: Location: Class Days: Class Times:

More information

TELECOMMUNICATION. Telecommunication. Wireless Phone

TELECOMMUNICATION. Telecommunication. Wireless Phone TELECOMMUNICATION Telecommunication Wireless Phone Talkback System CCTV PAGA TV Distribution LAN / WAN System 25 Telecommunication Telecommunication projects in the Oil & Gas industry are often large,

More information

telecommunication systems

telecommunication systems special purpose telecommunication systems custom made, to solve customer specific needs 1 FITRE S.p.A. 100% Italian Company Since 1943 designs and manufactures Telecommunication Systems and Products for:

More information

EN ASTRO-PA/GA System. ASTRO-PAGA Digital IP Public Address & General Alarm SYSTEM for INDUSTRIAL SAFETY APPLICATIONS

EN ASTRO-PA/GA System. ASTRO-PAGA Digital IP Public Address & General Alarm SYSTEM for INDUSTRIAL SAFETY APPLICATIONS ASTRO-PA/GA System EN 54-16 SISTEMA QUALITÀ CERTIFICATO ISO 9001 ISO 9001 CERTIFIED SYSTEM QUALITY F I T R E S.p.A. 20142 MILANO ITALIA via Valsolda, 15 tel.: +39.02.8959.01 fax: +39.02.8959.0400 e-mail:

More information

Section PERIMETER SECURITY SYSTEMS

Section PERIMETER SECURITY SYSTEMS Section 28 16 43 PERIMETER SECURITY SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide and install a perimeter security system as herein specified for the purpose of detecting entry into a designated security

More information

Architectural and Engineering Specification for a Real-Time Locating System Flare

Architectural and Engineering Specification for a Real-Time Locating System Flare Architectural and Engineering Specification for a Flare AE-T1-IN-R3-E-0617 Page 1 of 14 This document is intended to provide performance specifications and operational requirements for the Flare. It is

More information

SECTION PUBLIC ADDRESS SYSTEMS

SECTION PUBLIC ADDRESS SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Amplifier and control equipment B. Input equipment C. Raceways and communications cable D. List of equipment for gym PA system E. List of equipment for cafeteria

More information

Solutions for Mass Notification Systems

Solutions for Mass Notification Systems Solutions for Mass Notification Systems Emergency Voice Alarm Systems with Paging and Background Music Functions 8 decades of Sound & Communication and 4 decades of Voice Alarm Experience Boutique Passage

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM. ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM February 2017

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM. ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM February 2017 SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM February 2017 PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes

More information

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. Description of the building system The school is equipped with a hard wired fire alarm control panel, and automatic dialer. The fire alarm

More information

3226 Trunk Port FXO Doorphone

3226 Trunk Port FXO Doorphone 3226 Trunk Port FXO Doorphone Installation and User Guide Algo Communication Products Ltd., Burnaby, BC Canada V5J 5L2 www.algosolutions.com - 1 - Document #: 90-00040F Important Safety Notice The 3226

More information

SMART. FLEXIBLE. RELIABLE.

SMART. FLEXIBLE. RELIABLE. SMART. FLEXIBLE. RELIABLE. Life Safety Communications for Education, Healthcare, Correctional, and Industrial/Commercial Applications. WWW.CAREHAWK.COM THE CH1000(LT) PLATFORM The CH1000(LT), a life safety

More information

SECTION INTERCOM SYSTEMS

SECTION INTERCOM SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Intercom equipment. B. Intercom cable. C. Accessories. D. Surge Protection 1.2 REGULATORY REQUIREMENTS A. System: Listed by U.L. or E.T.L. or F.M. 1.3 SYSTEM DESCRIPTIONS

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

AlertWave Smart Wireless Solutions for Today s Campus Whether you are a large university

AlertWave Smart Wireless Solutions for Today s Campus Whether you are a large university Introduction AlertWave Smart Wireless Solutions for Today s Campus Whether you are a large university seeking a comprehensive packaged solution or a community college looking for a detailed solution on

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO Prepared For: Public Schools Facilities Authority State of New Mexico 2019 Galisteo, Suite

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1 GREEN LIGHT ARCHITECTURAL DIMMING CONTROLS (GLPD) Crestron Green Light and Green Light Express Network Dimming Control Systems are web accessible, network connected dimming control systems that receive

More information

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,

More information

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System 1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering

More information

RFP Addendum 2 March 31, 2016

RFP Addendum 2 March 31, 2016 RFP Addendum 2 March 31, 2016 For Best Value Procurement Option Three Security Upgrades Ph 1 UT Health Science Center SBC No. 540/013-04-2015 This Addendum forms a part of the Request for Proposals (RFP)

More information

University. NewVoice. San Francisco Paris Geneva Zurich Linz Mainz Shanghai Brisbane Hong Kong São Paulo Dubai

University. NewVoice. San Francisco Paris Geneva Zurich Linz Mainz Shanghai Brisbane Hong Kong São Paulo Dubai University Case Study University - Message Broadcast Powerful messaging scenarios to persons and groups, voice and text, dynamic and predefined. Messaging can be triggered via phone or web. With or without

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

Vocia VACIE. Reference Guide

Vocia VACIE. Reference Guide Vocia VACIE Reference Guide Document Revision 1.2.3, August 2015 Biamp Systems 9300 SW Gemini Drive Beaverton, Oregon 97008, U.S.A. (503) 641-7287 www.biamp.com INTRODUCTION... 3 SECTION 1... 4 VACIE CONFIGURATION...

More information

For Dealers / Integrators / Architects. IS Series. Video Intercom. Building Communication. Controlling Security.

For Dealers / Integrators / Architects. IS Series. Video Intercom. Building Communication. Controlling Security. For Dealers / Integrators / Architects IS Series Video Intercom Building Communication. Controlling Security. IS Series helps save money Control multiple functions from any location to help reduce overall

More information

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Page 2 of 16 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Contents 1. Introduction... 4 2. Product Features... 4 3. Package

More information

Architectural and Engineering Specification for a. Flash / Flare

Architectural and Engineering Specification for a. Flash / Flare Architectural and Engineering Specification for a Flash / Flare June 27, 2014 Page 1 of 12 T1DA0115-001 Rev D This document is intended to provide performance specifications and operational requirements

More information

SECTION HEALTHCARE COMMUNICATION AND MONITORING SYSTEM (NURSE CALL)

SECTION HEALTHCARE COMMUNICATION AND MONITORING SYSTEM (NURSE CALL) SECTION 27 52 23 HEALTHCARE COMMUNICATION AND MONITORING SYSTEM (NURSE CALL) PART 1 - GENERAL 1.1 SECTION INCLUDES A. Basic System Requirements B. Stations C. Master Stations/Consoles D. Annunciators,

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

B. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator.

B. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator. SECTION 281300 - ACCESS CONTROL SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Minimum standards for Access Control Systems. B. Related Requirements: 1. Section 087100 Door Hardware. 1.2 REFERENCES

More information

Standard Specifications for Rice University Traction and Hydraulic Elevator(s) Revision 04/28/2017

Standard Specifications for Rice University Traction and Hydraulic Elevator(s) Revision 04/28/2017 Summary: 14 20 00 Standard Specifications for Rice University Traction and Hydraulic Elevator(s) Revision 04/28/2017 Work for this section includes providing equipment, incidental material and labor required

More information

AlertWave. visiplex. From a Public Address System to an Emergency Communication System... The AlertWave system advantages:

AlertWave. visiplex. From a Public Address System to an Emergency Communication System...  The AlertWave system advantages: AlertWave From a Public Address System to an Emergency Communication System... The AlertWave offers facility managers an easy way to implement an on-site wireless public address, emergency control and

More information

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

Attendees/Absentees. Derek Gallagher DG. Delano Secondary School Additions and Renovations June 6, 2016 Technology User Group Meeting Minutes

Attendees/Absentees. Derek Gallagher DG. Delano Secondary School Additions and Renovations June 6, 2016 Technology User Group Meeting Minutes MEMORANDUM To: From: Attendees/Absentees Derek Gallagher DG Date: June 14, 2016 Comm. No: 152235 Subject: Independent School District #879 Delano Secondary School Additions and Renovations June 6, 2016

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

East Central College

East Central College SECTION 260923 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Innovative protection that combines power and flexibility

Innovative protection that combines power and flexibility Innovative protection that combines power and flexibility Desigo Fire Safety Modular outpaces industry standards and includes cutting-edge detection and communication capabilities usa.siemens.com/desigo-fs-modular

More information

STATEMENT OF WORK ELECTRICAL REPAIR / MAINTENANCE BUILDING PROJECT FDC RACCOON CREEK STATE PARK (BEAVER COUNTY)

STATEMENT OF WORK ELECTRICAL REPAIR / MAINTENANCE BUILDING PROJECT FDC RACCOON CREEK STATE PARK (BEAVER COUNTY) STATEMENT OF WORK ELECTRICAL REPAIR / MAINTENANCE BUILDING PROJECT FDC-213-100797 RACCOON CREEK STATE PARK (BEAVER COUNTY) I. SCOPE OF WORK: The Commonwealth of Pennsylvania, Department of Conservation

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

Unified Fire Authority - Fire Prevention Bureau

Unified Fire Authority - Fire Prevention Bureau Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance

More information

16 Zone Voice Evacuation VA & PA Sound System

16 Zone Voice Evacuation VA & PA Sound System 16 Zone Voice Evacuation VA & PA Sound System 4 Channel Main Amp VA-MP4120 PC Server & Software VA-2000ST T-565 Zone 1-4 One Channel Standby Amp VA-2000RM VA-2000MA T-565 Zone 5-8 LAN CAT5 Cable CAT5 Data

More information

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.

More information

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1 Operation Manual Fighter ProVision Software Version: 0.0 Revision: 1 TABLE OF CONTENTS 1. Introduction 5 2. Software Installation 5 3. PC Users 6 3.1 Introduction 6 3.2 Default Code 6 3.3 Edit PC User

More information

Alarm Tone Generator Model AG17

Alarm Tone Generator Model AG17 Alarm Tone Generator Installation & Operation P005089 Rev. C 150930 9/30/2015 12:25 PM Ph: 403.258.3100 \ email:info@guardiantelecom.com \ www.guardiantelecom.com Table of Contents Package Contents...

More information

CLASSROOM INTERCOM SPECIFICATIONS

CLASSROOM INTERCOM SPECIFICATIONS 1. General This section and associated drawings define a communications system for an intercom, public address, and master clock system. The bidder shall provide infrastructure, cable, hardware, and equipment,

More information

Comprehensive Solutions for School Communication Amplified Learning Public Address Emergency Notification Intercom Bell Schedule Clock

Comprehensive Solutions for School Communication Amplified Learning Public Address Emergency Notification Intercom Bell Schedule Clock Comprehensive Solutions for School Communication Amplified Learning Public Address Emergency Notification Intercom Bell Schedule Clock Synchronization Innovative Electronic Designs - Over 30 Years of Mass

More information

DONALD H. BERG, ARCHITECT

DONALD H. BERG, ARCHITECT DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:

More information

Call stations and extensions

Call stations and extensions Novigo Call stations and extensions PT2001-A1, PT2002-A1, PT2008-A1, PT2009-A1, PTO2001-A1, PTO2002-A1, PTO2003-A1, PTO2004-A1, PTO2005-A1, PTO2006-A1, PTO2008-A1 EN 54-16-certified alarm and business

More information

DOOR MONITORING/DURESS SYSTEM

DOOR MONITORING/DURESS SYSTEM SECTION PART 1 - GENERAL 1.1 RELATED SECTIONS A. Comply with the requirements of Section 27 05 00 Common Work Results for Communications. 1.2 DEFINITIONS A. Not used. 1.3 DESCRIPTION OF SYSTEM: A. Provide

More information

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM DIVISION 26 ELECTRICAL SECTION 26 09 26 PART 1 GENERAL 1.01 DESCRIPTION A. The intent of this set of specifications is to provide a complete, functional, intelligent, lowvoltage lighting control system

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 27 COMMUNICATIONS SECTION PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 27 COMMUNICATIONS SECTION PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS SECTION 275116 - PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Preamplifiers. 2. Power amplifiers. 3. Microphones. 4. Control console. 5. Loudspeakers.

More information

Notice... 1 Trademarks... 1 US Patent Numbers... 1 Technical Services Contact Information... 2 Document Conventions... 2 Warranty...

Notice... 1 Trademarks... 1 US Patent Numbers... 1 Technical Services Contact Information... 2 Document Conventions... 2 Warranty... Table of Contents Preface 1 Notice... 1 Trademarks... 1 US Patent Numbers... 1 Technical Services Contact Information... 2 Document Conventions... 2 Warranty... 2 Chapter 1 Radius Overview 6 1.1 About

More information

VACIE REFERENCE GUIDE REVISION 1.2.6

VACIE REFERENCE GUIDE REVISION 1.2.6 VACIE REFERENCE GUIDE REVISION 1.2.6 November 2016 INTRODUCTION... 3 SECTION 1... 4 VACIE CONFIGURATION... 4 Communications... 4 Vocia VACIE Devices... 4 Vocia Support devices:... 5 Power Supply and Network

More information

Electronic Safety and Security

Electronic Safety and Security 28 Electronic Safety and Security NOTE: This is a new section, which includes content from previous sections of the KU Design Standards, along with appropriate revisions and updates. Significant revisions

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 RELATED SECTIONS: Refer to Section 15300 for requirements regarding fire protection systems. 1.2 SCOPE OF SECTION: This section contains the requirements for equipment and installation

More information

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.

More information

A. Provide a complete microprocessor controlled intercom and clock/bell system as shown on the drawings and as specified herein.

A. Provide a complete microprocessor controlled intercom and clock/bell system as shown on the drawings and as specified herein. 13745 INTERCOM AND CLOCK SYSTEM ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 27 51 16 An optional

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCESA / NASA UFGS-27 41 00.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 41 00.00 10 (November 2002) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

N-8000 SERIES IP INTERCOM SYSTEM

N-8000 SERIES IP INTERCOM SYSTEM N-8000 SERIES IP INTERCOM SYSTEM IP Network-Compatible Intercom System with Packet Audio Technology developed with cutting-edge TOA technological strengths for greater versatility and improved sound quality

More information

FI6000 INSTRUCTION MANUAL. Thank you for choosing another quality product from Amperes Electronics. Fire Alarm Interface

FI6000 INSTRUCTION MANUAL. Thank you for choosing another quality product from Amperes Electronics. Fire Alarm Interface INSTRUCTION MANUAL FI6000 Fire Alarm Interface Thank you for choosing another quality product from Amperes Electronics. FI6000 is a phase evacuation controller which can be integrated with various Amperes

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel ACC-25/50ZST Zoned System Voice with Telephone Evacuation Control Panel General The AUDIO COMMAND CENTER 25/50 Zone System with FireFighters Telephone (ACC-25/50ZST) is a state-of-the-art Emergency Voice

More information

NetworX Series NX-4V2 Control Panel Installation and Startup

NetworX Series NX-4V2 Control Panel Installation and Startup NetworX Series NX-4V2 Control Panel Installation and Startup 2005 GE Security All rights reserved. These instructions do not purport to cover all details or variations in equipment nor to provide every

More information

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 STUDY AND TEST MATERIAL FOR THE FA2 and FA4 ASSESSMENTS (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 This document contains sample questions to help participants study for the FA2 and FA4

More information

IP-based Building Management Control

IP-based Building Management Control IP-based Building Management Control Core Control - IP-based Building Management Control Software Core Control is a professional Building Management Control application for scheduling and triggering IP-connected

More information

Courthouse East vision and policy plan

Courthouse East vision and policy plan August 2017 Courthouse East vision and policy plan Virginia Beach, Virginia 2017 URBAN DESIGN ASSOCIATES SITE PLANNING APPROACH 10-minunte walk from the Courthouse COURTHOUSE EAST IN THE ITA VICINITY Site

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY

DIVISION 28 ELECTRONIC SAFETY AND SECURITY 281300 - ACCESS CONTROL A. General DIVISION 28 ELECTRONIC SAFETY AND SECURITY At the beginning of the project, schedule a meeting with the Facilities Access/Maintenance Coordinator with questions and concerns.

More information

SECTION COMMUNICATIONS PATCH CORDS, STATION CORDS AND CROSS CONNECT WIRE

SECTION COMMUNICATIONS PATCH CORDS, STATION CORDS AND CROSS CONNECT WIRE SECTION 27 16 19 COMMUNICATIONS PATCH CORDS, STATION CORDS AND CROSS CONNECT WIRE PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

INTERCOM/CLOCK/PUBLIC ADDRESS SYSTEM

INTERCOM/CLOCK/PUBLIC ADDRESS SYSTEM 277000 INTERCOM/CLOCK/PUBLIC ADDRESS SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This section includes a fully operational school internal Record Version 20140728 communications and clock incorporating safety

More information