Public Input No. 107-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Size: px
Start display at page:

Download "Public Input No. 107-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification"

Transcription

1 of 123 7/30/2015 1:48 PM Public Input No. 107-NFPA [ Section No ] The authority having jurisdiction shall determine compliance with this standard and authorize equivalent deviations from it in all applications. Delete the entire section The text in is already addressed by 1.5 Submitter Full Name: RAYMOND WALKER Organization: Bolton Fire Dept Affilliation: Executive Board of International Fire Marshal's Assoc. Submittal Date: Fri Dec 26 16:43:37 EST 2014 Resolution: The current statement provides clarity of responsibility.

2 of 123 7/30/2015 1:48 PM Public Input No. 27-NFPA [ Section No. 2.3 ] 2.3 Other Publications ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2012b ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, 2012a. ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C, 2009b ASTM E 814, Standard Test Method for Fire Tests of Through-Penetration Fire Stops, 2011a 2013a. ASTM E 2336, Standard Test Methods for Fire Resistive Grease Duct Enclosure Systems, 2004, re-approval (2009) reapproved ASTM E 2652, Standard Test Method for Behavior of Materials in a Tube Furnace with a Cone-shaped Airflow Stabilizer, at 750 C, EPA Publication. Environmental Protection Agency, Ariel Rios Bldg., 1200 Pennsylvania Avenue, NW, Washington, DC EPA Test Method 202, Determination of Condensable Particulate Emissions for Stationary Sources, UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/ UL 197, Standard for Commercial Electric Cooking Appliances, 2010, revised ANSI/ UL 263, Standard for Fire Tests of Building Construction and Materials, 2011, Revised ANSI/ UL 300, Standard for Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment, 2005, revised UL 710, Standard for Exhaust Hoods for Commercial Cooking Equipment, 1995, revised ANSI/ UL 710B, Standard for Recirculating Systems, 2011, Revised UL 710C, Outline of Investigation for Ultraviolet Radiation Systems for Use in the Ventilation Control of Commercial Cooking Operations, ANSI/ UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, revised UL 762, Outline of Investigation for Power Roof Ventilators for Restaurant Exhaust Appliances, ANSI/ UL 1046, Standard for Grease Filters for Exhaust Ducts, 2010, revised ANSI/ UL 1479, Standard for Fire Tests of Through-Penetration Firestops, 2003, revised ANSI/ UL 1978, Standard for Grease Ducts, 2005, revised UL 2221, Standard for Tests of Fire Resistive Grease Duct Enclosure Assemblies, Other Publications. Merriam-Webster s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, Updated edtitions. Related Public Inputs for This Document Related Input Relationship

3 of 123 7/30/2015 1:48 PM Public Input No. 26-NFPA [Section No. B.1.2] New standard editions Submitter Full Name: Aaron Adamczyk Organization: [ Not Specified ] Submittal Date: Mon Jun 09 16:45:38 EDT 2014 Resolution: FR-55-NFPA Statement: Updated references to the latest edition in accordance with the NFPA Manual of Style.

4 of 123 7/30/2015 1:48 PM Public Input No. 93-NFPA [ Section No ] ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2012b ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, 2012a ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C, 2009b ASTM E 814, Standard Test Method for Fire Tests of Through-Penetration Fire Stops, 2011a 2013a. ASTM E 2336, Standard Test Methods for Fire Resistive Grease Duct Enclosure Systems, 2004, re-approval (2009) ASTM E 2652, Standard Test Method for Behavior of Materials in a Tube Furnace with a Cone-shaped Airflow Stabilizer, at 750 C, date update Submitter Full Name: Marcelo Hirschler Organization: GBH International Submittal Date: Tue Dec 16 21:51:20 EST 2014 Resolution: FR-55-NFPA Statement: Updated references to the latest edition in accordance with the NFPA Manual of Style.

5 of 123 7/30/2015 1:48 PM Public Input No. 108-NFPA [ Section No ] UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/UL 197, Standard for Commercial Electric Cooking Appliances, 2010, revised ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, ANSI/UL 300, Standard for Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment, 2005, revised UL 710, Standard for Exhaust Hoods for Commercial Cooking Equipment, 1995, revised ANSI/UL 710B, Standard for Recirculating Systems, UL 710C, Outline of Investigation for Ultraviolet Radiation Systems for Use in the Ventilation Control of Commercial Cooking Operations, ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, revised UL 762, Outline of Investigation for Power Roof Ventilators for Restaurant Exhaust Appliances, ANSI/UL 1046, Standard for Grease Filters for Exhaust Ducts, 2010, revised ANSI/UL 1479, Standard for Fire Tests of Through-Penetration Firestops, 2003, revised ANSI/UL 1978, Standard for Grease Ducts, 2005, revised UL 2221, Standard for Tests of Fire Resistive Grease Duct Enclosure Assemblies, UL Standards were updated. Submitter Full Name: Ronald Farr Organization: UL LLC Submittal Date: Mon Dec 29 13:09:07 EST 2014 Resolution: FR-55-NFPA Statement: Updated references to the latest edition in accordance with the NFPA Manual of Style.

6 of 123 7/30/2015 1:48 PM Public Input No. 30-NFPA [ Section No ] UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/UL 197, Standard for Commercial Electric Cooking Appliances, 2010, revised ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, ANSI/UL 300, Standard for Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment, 2005, revised UL 710, Standard for Exhaust Hoods for Commercial Cooking Equipment, 1995, revised ANSI/UL 710B, Standard for Recirculating Systems, UL 710C, Outline of Investigation for Ultraviolet Radiation Systems for Use in the Ventilation Control of Commercial Cooking Operations, UL KNLZ, Outline of investigation for Commercial Cooking Appliances with Integral Systems for Limiting the Emmission of Grease laden Air. ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, revised UL 762, Outline of Investigation for Power Roof Ventilators for Restaurant Exhaust Appliances, ANSI/UL 1046, Standard for Grease Filters for Exhaust Ducts, 2010, revised ANSI/UL 1479, Standard for Fire Tests of Through-Penetration Firestops, 2003, revised ANSI/UL 1978, Standard for Grease Ducts, 2005, revised UL 2221, Standard for Tests of Fire Resistive Grease Duct Enclosure Assemblies, IMC 2012 section exception 2, and section make reference to direct exhaust hood exemptions for performance tested cooking operations where effluent emissions as measured by an approved laboratory are less than or equal to the 5mg/m3 particulate matter (including condensible vapor/gas phase) of as stated in Chapter 13 of NFPA 96 with its reference to chapter 17 or EPA Test Method 202. The performance certification for commercial cooking operations with effluent emissions less than or equal to the above referenced threshold limit value (TLV) where a Type I hood would be required, is UL KNLZ which is titled: Commercial Cooking Appliances with Integral Systems for Limiting the Emission of Grease-laden Air. It is important to include the KNLZ performance certification test method in NFPA 96 for clarity purposes. Submitter Full Name: Organization: Affilliation: Street Address: THOMAS JOHNSON JOHNSON DIVERSIFIED PROD INC On my behalf; though I am a voting member of UL 710, 710B, 710C, KNLZ; ASHRAE TC5.10, AHSRAE SPC 154, an active member of EHEDG, the NSF JC food Equipment and Council III of the Conference for Food Protection. (CFP)

7 of 123 7/30/2015 1:48 PM Submittal Date: Wed Jun 11 09:02:21 EDT 2014 Resolution: Many of the requirements in this public input are outside the scope of NFPA 96. Consideration should be given to approaching NFPA 1 on this topic. Section currently addresses temporary and mobile cooking operations.

8 of 123 7/30/2015 1:48 PM Public Input No. 22-NFPA [ New Section after ] Commercial Cooking Operations. Cooking operations that are concerned with or engaged in commerce. Application of this Standard is difficult when the core term of the document is not defined. It is understood that the Standard can be applied to commercial and residential cooking equipment, but the cooking equipment has nothing to do with the question of whether or not the cooking operations are considered commercial. How can section for residential cooking equipment be enforced if the enforcer does not know what commercial cooking is? If the committee does not agree with the proposed definition, we would ask the committee to provide one. Submitter Full Name: Doug Hohbein Organization: Northcentral Fire Code Develop Submittal Date: Tue Apr 22 16:35:23 EDT 2014 Resolution: Section and and identifies the scope of this document.

9 of 123 7/30/2015 1:48 PM Public Input No. 115-NFPA [ New Section after ] TITLE OF NEW CONTENT Add a definition as follows: Mobile or Temporary Cooking. Any cooking facility, apparatus or equipment, being operated on a one-time or interim basis, or for less than 90 days in the same location, other than at a fixed location, building or structure which has been inspected and permitted under another section of this code, regulation or statute, inclusive of self-propelled trucks and vehicles, trailered units, push carts, equipment located under cover of awnings, canopies or pop-up tents, or other structures for which a building permit has not been issued. Substantiation:This new proposed definition references the proposed chapter 16 submitted as a separate input and similarly results from the IFMA and Task Group work referred to in the Chp 16 submittal. Submitter Full Name: RAYMOND WALKER Organization: Bolton Fire Dept Affilliation: Executive Board of IFMA and the Task Group and the membership Submittal Date: Tue Dec 30 19:35:32 EST 2014 Resolution: Many of the requirements in this public input are outside the scope of NFPA 96. Consideration should be given to approaching NFPA 1 on this topic. Section currently addresses temporary and mobile cooking operations. PI-114 related.

10 0 of 123 7/30/2015 1:48 PM Public Input No. 138-NFPA [ New Section after ] TITLE OF NEW CONTENT Type your content here Water-wash system. A system that employs a water spray to clean grease from the plenum and portions of the ductwork on an intermittent or continuous basis Water-wash fire extinguishing system. A water-wash system that is listed and in compliance with ANSI/UL 300 or other equivalent standard and installed in accordance with the listing. Not all water-wash systems are listed water-wash fire extinguishing systems. There is a need to add definitions to the standard to distinguish the two. Related Public Inputs for This Document Related Input Public Input No. 139-NFPA [Section No ] Public Input No. 140-NFPA [Section No ] Public Input No. 144-NFPA [Section No ] Relationship Submitter Full Name: Russell Fleming Organization: National Fire Sprinkler Association Affilliation: Correlating Committee on Automatic Sprinklers Submittal Date: Mon Jan 05 13:58:56 EST 2015 Resolution: FR-5-NFPA Statement: The Technical Committee added these definitions for terms used in the standard.

11 1 of 123 7/30/2015 1:48 PM Public Input No. 29-NFPA [ Section No ] * Cooking equipment that has been listed in accordance with ANSI/UL 197 or an equivalent standard for reduced emissions shall by UL to UL KNLZ, the performance certification test for Commercial Cooking Appliances with Integral Systems for Limiting the Emission of Grease-laden Air shall not be required to be provided with an exhaust system. a secondary mechanical system in the from of any tyoe of hood, duct and/or exhaust fan that discharges captured air to the out doors. The performance certification test for commercial cooking appliances featuring integral grease limiting devices, such as heavy metal catalytic combustion systems, is UL KNLZ. If a appliance process test using the same reference test method standard required in NFPA 96 Chapter 13 measures effluents to be the same or less than that allowed in of NFPA 96, then no exhaust hood or make up air system should be required. Submitter Full Name: Organization: Affilliation: Street Address: Submittal Date: THOMAS JOHNSON JOHNSON DIVERSIFIED PROD INC On my own behalf. I am a voing member of of several UL STP's icluding UL710, ANSI UL710B, UL KNLZ and ANSI UL 1046, in addition to ASHRAE TC5.10 and the SPC 154 along with NSF JC on Food Equipment and council III of the Conference for Food Protection. Wed Jun 11 08:46:11 EDT 2014 Resolution: FR-12-NFPA Statement: The Technical Committee created a clearer explanation of UL197 and UL 710B for appliances with limited grease emissions.

12 2 of 123 7/30/2015 1:48 PM Public Input No. 99-NFPA [ Section No ] All airflows shall be maintained as required by the appliance listing, this standard or the code adopted by the authority having jurisdiction. It may be unnecessary for constant operation of air handling systems for replacement air especially for appliances that are not in continuous operation. See Sections and This may be particularly beneficial in areas of climate extremes and my assist with compliance with other adopted codes such as energy conservation codes. Submitter Full Name: Jim Muir Organization: Building Safety Division, Clark County, Washington Affilliation: NFPA's Building Code Development Committee (BCDC) Submittal Date: Mon Dec 22 20:32:31 EST 2014 Resolution: The requirements for air flows are provided elsewhere in the standard.

13 3 of 123 7/30/2015 1:48 PM Public Input No. 124-NFPA [ Section No ] The responsibility for inspection, testing, maintenance, and cleanliness of the ventilation control and fire protection of the commercial cooking operations shall, including cooking appliances, shall ultimately be that of the owner of the system, provided that this responsibility has not been transferred in written form to a management company, tenant, or other party. Numerous fires in commercial cooking operations are caused by ignition of grease in and around appliances, particularly in places that are not within the zone of protection of the extinguishing system. Section 11.7 specifies requirements for cleaning appliances of accumulated grease. Adding the proposed text emphasizes that the responsibility for assuring that this cleaning gets done, is that of the owner. Note: the process does not appear to be working correctly and is duplicating the word "shall". Related Public Inputs for This Document Related Input Public Input No. 128-NFPA [New Section after A ] Relationship Submitter Full Name: David de Vries Organization: Firetech Engineering Inc. Submittal Date: Sun Jan 04 17:16:25 EST 2015 Resolution: FR-6-NFPA Statement: Numerous fires in commercial cooking operations are caused by ignition of grease in and around appliances, particularly in places that are not within the zone of protection of the extinguishing system. Section 11.7 specifies requirements for cleaning appliances of accumulated grease. Adding the proposed text emphasizes that the responsibility for assuring that compliance with this requirement is that of the owner.

14 4 of 123 7/30/2015 1:48 PM Public Input No. 137-NFPA [ Section No ] The responsibility for inspection, testing, maintenance, and cleanliness of the ventilation control and fire protection of, cooking appliances and fire protection of the commercial cooking operations shall ultimately be that of the owner of the system, provided that this responsibility has not been transferred in written form to a management company, tenant, or other party. Fires initiating outside the "zone of protection" due to leaking grease from fryer vats accumulating near and about the fryer's burners, poor housekeeping practices beneath and behind heat generating cooking appliances have become way to common. Some restaurant operators/ kitchen staff seem oblivious to the risk of fire associated with poor housekeeping practices. 96 needs to be clear on these type issues...no ambiguity or wiggle room for interpretation, please. Submitter Full Name: ROBERT SCHROEDER Organization: Schroeder Fire Inc Affilliation: None...lessons from the front line...root cause/ post fire analysis Submittal Date: Mon Jan 05 13:05:01 EST 2015 Resolution: FR-6-NFPA Statement: Numerous fires in commercial cooking operations are caused by ignition of grease in and around appliances, particularly in places that are not within the zone of protection of the extinguishing system. Section 11.7 specifies requirements for cleaning appliances of accumulated grease. Adding the proposed text emphasizes that the responsibility for assuring that compliance with this requirement is that of the owner.

15 5 of 123 7/30/2015 1:48 PM Public Input No. 106-NFPA [ Section No ] * Cooking equipment used in fixed, mobile, or temporary concessions, such as trucks, buses, trailers, pavilions, tents, or any form of roofed enclosure, shall comply with this standard. unless otherwise exempted by the authority having jurisdiction in accordance with of this standard. Insert period after the word standard in line 2 and delete remainder of section from "unless otherwise" to "of this standard". Substantiation: The deleted wording is not needed as and 1.5 already lets the AHJ approve alternate methods os complying with the standard. The deleted wording is not needed as and 1.5 of this standard already lets the AHJ approve alternative methods of complying with this standard. Submitter Full Name: RAYMOND WALKER Organization: Bolton Fire Dept Affilliation: Executive Board of International Fire Marshals Assoc. Submittal Date: Fri Dec 26 16:04:32 EST 2014 Resolution: FR-7-NFPA Statement: The deleted wording is not needed as Sections and already allows the AHJ to determine equivalency.

16 6 of 123 7/30/2015 1:48 PM Public Input No. 125-NFPA [ Section No ] * Where enclosures are not required, hoods, grease removal devices, exhaust fans, and ducts shall have a clearance of at least 457 mm (18 in.) to combustible material, 76 mm (3 in.) to limited-combustible material, and 0 mm (0 in.) to noncombustible material. See the proposed Annex note A Related Public Inputs for This Document Related Input Public Input No. 126-NFPA [New Section after A.4.2] Relationship Submitter Full Name: David de Vries Organization: Firetech Engineering Inc. Submittal Date: Sun Jan 04 17:25:01 EST 2015 Resolution: FR-8-NFPA Statement: Add annex material. The committee added annex material to provide further clarification for measurement purposes.

17 7 of 123 7/30/2015 1:48 PM Public Input No. 32-NFPA [ Section No ] Where a clearance reduction system consisting of a listed and labeled field-applied grease duct enclosure material, system, product, or method of construction specifically evaluated for such purpose in accordance with ASTM E 2336, the required clearance shall be in accordance with the listing. There are currently factory-built and field-applied ASTM E 2336 tested and listed assemblies. Submitter Full Name: Gerry Saieva Organization: DuraSystems Barriers Inc Submittal Date: Thu Jul 10 14:30:24 EDT 2014 Resolution: FR-41-NFPA Statement: This revision addresses the type of duct systems that are available in the industry.

18 8 of 123 7/30/2015 1:48 PM Public Input No. 31-NFPA [ Section No ] The factory-built grease duct protection system shall be listed in accordance with UL 2221 or ASTM E Factory-built assemblies are currently tested and listed to the ASTM E 2336 standard. The current wording of implies only UL 2221 tested and listed systems are acceptable to be factory-fabricated. Submitter Full Name: Gerry Saieva Organization: DuraSystems Barriers Inc Submittal Date: Thu Jul 10 14:25:39 EDT 2014 Resolution: UL 2221 is the minimum standard for factory-built grease duct protection systems. Factory built assemblies can be also classified for compliance with ASTM E 2336, in addition to listing in accordance with UL2221.

19 9 of 123 7/30/2015 1:48 PM Public Input No. 121-NFPA [ Section No ] Listed grease filters and grease removal devices that are removable but not an integral component of a specific listed exhaust hood shall be listed in accordance with ANSI/UL 1046, and shall be clearly so designated on the face of the filter as to be visible as to be visible with the filter installed.. NFPA 96 requires all grease removal devices to be listed to ANSI/UL 1046 however non-listed filters are readily available in the marketplace, and are commonly found employed in the field. These filters are inexpensive, and are being sold to unsuspecting end users in lieu of the 1046 listed filters that are required. Having the grease removal devices clearly marked on the front will allow inspecting authorities and end users to easily identify that the employed grease removal devices align with the requirements of the standard. Submitter Full Name: Bernard Besal Organization: Besal Services, Inc. Affilliation: International Kitchen Exhaust Cleaning Association (IKECA) Submittal Date: Fri Jan 02 15:59:21 EST 2015 Resolution: FR-9-NFPA Statement: NFPA 96 requires all grease removal devices to be listed to ANSI/UL 1046 however non-listed filters are readily available in the marketplace, and are commonly found employed in the field. These filters are inexpensive, and are being sold to unsuspecting end users in lieu of the 1046 listed filters that are required. Having the grease removal devices clearly marked will allow inspecting authorities and end users to easily identify that the employed grease removal devices align with the requirements of the standard.

20 0 of 123 7/30/2015 1:48 PM Public Input No. 100-NFPA [ Section No ] Where grease removal devices are used in conjunction with charcoal solid fuel or charcoal solid fuel -type broilers, including gas or electrically heated charbroilers, a minimum vertical distance of 1.22 m (4 ft) shall be maintained between the lower edge of the grease removal device and the cooking surface. As written in the code, this seems to miss wood-fired cooking appliances. The term "solid fuel" is used in lieu of "charcoal" in the charging statement to capture both charcoal and wood or any other solid fuels, which would need a 4 ft clearance. Submitter Full Name: Jim Muir Organization: Building Safety Division, Clark County, Washington Affilliation: NFPA's Building Code Development Committee (BCDC) Submittal Date: Mon Dec 22 20:35:04 EST 2014 Resolution: FR-10-NFPA Statement: The term "solid fuel" is used in lieu of "charcoal" in the charging statement to capture both charcoal and wood or any other solid fuels, which would need a 4 ft clearance.

21 1 of 123 7/30/2015 1:48 PM Public Input No. 120-NFPA [ Section No ] Grease Filter Orientation. Grease filters that require a specific orientation to drain grease shall be clearly so designated on the face of the filter as to be visible with the filter installed, or the hood shall be constructed so that filters cannot be installed in the wrong orientation. Authorities having jurisdiction, inspection entities, and end users will have clear indication on the required orientation of the grease removal devices without having to remove the grease removal devices from the exhaust hood. Submitter Full Name: Bernard Besal Organization: Besal Services, Inc. Affilliation: International Kitchen Exhaust Cleaning Association (IKECA) Submittal Date: Fri Jan 02 15:42:55 EST 2015 Resolution: FR-11-NFPA Statement: UL 1046 requires a visible mark on the face of the filter to show the filter orientation. As an option, users will have clear indication on the required orientation of the grease removal devices without having to remove the grease removal devices from the exhaust hood.

22 2 of 123 7/30/2015 1:48 PM Public Input No. 71-NFPA [ New Section after ] TITLE OF NEW CONTENT Exception: Factory-built listed grease ducts shall be permitted to be installed at a slope lower than that specified in 7.1.4, in accordance with the lower slope specified in the manufacturer's installation instructions. This exception would permit installation of factory-built listed grease duct at a slope lower than that specified in this standard. Recently revised UL 1978 (the standard used for listing grease duct) allows for duct installation at lesser slope than that specified in section 7.1.4, when the lesser slopes have been shown through analysis, tests, or both to provide equivalent or better flow characteristics, as compared to field-installed (which are rectangular) grease ducts with code prescribed minimum slopes (as specified in 7.1.4), and the manufacturer's installation instructions include a statement regarding the installation at not less than the lesser duct slope which is approved by the listing agency. The installation instructions, which are a required part of a factory-built grease duct listing, of manufacturers of such grease ducts include a statement regarding installation of their grease ducts at not less than the lesser duct slope that the listing agency has approved. Submitter Full Name: Jayendra Parikh Organization: Compliance Solutions International Inc Affilliation: Self Submittal Date: Tue Dec 02 19:12:51 EST 2014 Resolution: FR-14-NFPA Statement: The previous edition did not refer to a lesser slope.

23 Public Input No. 73-NFPA [ Section No ] Delete "or listed grease duct drains," from this section, so it reads: Where provided, drains shall be continuously welded to the exhaust duct or listed grease duct drains, in accordance with the terms of the listing and the manufacturer's installation manual. The proposed change will clarify this requirement. The phrase that is proposed to be deleted does not make sense, as it is written/included in this section. Also, grease duct drains are not listed. If the drains are provided with listed grease duct, they are components of that grease duct. Submitter Full Name: Jayendra Parikh Organization: Compliance Solutions International Inc Affilliation: Self Submittal Date: Mon Dec 15 19:02:31 EST 2014 Resolution: FR-15-NFPA Statement: The proposed change will clarify this requirement. The phrase that is proposed to be deleted does not make sense, as it is written/included in this section. Also, grease duct drains are not listed. If the drains are provided with listed grease duct, they are components of that grease duct. 3 of 123 7/30/2015 1:48 PM

24 4 of 123 7/30/2015 1:48 PM Public Input No. 40-NFPA [ Section No ] Access Panels. Must be installed by a licensed sheet metal installer Access panels shall be of the same material and thickness as the duct Access panels shall have a gasket or sealant that is rated for 815.6ºC (1500ºF) and shall be greasetight Fasteners, such as bolts, weld studs, latches, or wing nuts, used to secure the access panels shall be carbon steel or stainless steel and shall not penetrate duct walls Listed grease duct access door assemblies (access panels) shall be installed in accordance with the terms of the listing and the manufacturer's instructions. I was notified recently by MA State Fire Marshal office that only a licensed sheet metal contractor could install access panels and hinge kits. I cannot find anywhere in NFPA 96 which states this. Is this accurate? Submitter Full Name: Raymond Zakarian Organization: UNI-SERVE USA / UNDER PRESSURE INC. RAYMOND K ZAKARIAN UNDER PRESSURE Affilliation: INC Submittal Date: Sat Oct 11 09:43:39 EDT 2014 Resolution: The AHJ is responsible for local licensing requirements.

25 5 of 123 7/30/2015 1:48 PM Public Input No. 123-NFPA [ New Section after ] TITLE OF NEW CONTENT Type your content here Factory-built grease duct systems shall conform to the accessibility requirements specified in section 7.4. Factory-built grease duct systems consist of components and fittings and access to the interior of the exhaust duct is provided by installation of wyes and tees. Adding access to factory-built duct systems after assembly of the sections is impossible due to impact on the listings of the assembly. Factory-built ductwork is often installed with less frequency of access, and many installations are found where the tees and wyes intended for use as access points have interferences. On smaller diameter factory-built ducts, the frequency and placement of the access is critical to facilitate long term fire-protective cleaning. The proposed change aligns access requirements for fabricated and factory-built ducts. Submitter Full Name: Bernard Besal Organization: Besal Services, Inc. Affilliation: International Kitchen Exhaust Cleaning Association (IKECA) Submittal Date: Fri Jan 02 18:44:10 EST 2015 Resolution: Language for accessibility is currently adequate.

26 Public Input No. 23-NFPA [ Sections , ] Sections , Buildings less Enclosures less than four stories levels in height shall have an enclosure with a fire resistance rating of not less than 1 hour Buildings Enclosures four stories levels or more in height shall have an enclosure with a fire resistance rating of not less than 2 hours. It is unclear if the intent is to provide a fire rated enclosure based on the height of the building or the number of stories penetrated by the exhaust duct. If a duct penetrates only one floor of a six-story building, is the enclosure required to be two-hour fire rated? If the intent is number of levels in the building, should basements or lower levels that are not considered stories be counted? Submitter Full Name: Doug Hohbein Organization: Northcentral Fire Code Develop Submittal Date: Tue Apr 22 16:36:55 EDT 2014 Resolution: The current language is consistent with other industry standard terms. 6 of 123 7/30/2015 1:48 PM

27 7 of 123 7/30/2015 1:48 PM Public Input No. 101-NFPA [ Section No ] Rooftop terminations shall be arranged with or provided with the following: (1) A minimum of 3 m (10 ft) of horizontal clearance from the outlet to adjacent buildings, property lines, and air intakes (2) A minimum of 1.5 m (5 ft) of horizontal clearance from the outlet (fan housing) to any combustible structure (3) A vertical separation of 0.92 m (3 ft) below above any exhaust outlets for air intakes within 3 m (10 ft) of the exhaust outlet (4) The ability to drain grease out of any traps or low points formed in the fan or duct near the termination of the system into a collection container that is noncombustible, closed, rainproof, and structurally sound for the service to which it is applied and that will not sustain combustion (5) A grease collection device that is applied to exhaust systems that does not inhibit the performance of any fan (6) Listed grease collection systems that meet the requirements of (4) and (5) (7) A listed grease duct complying with Section 4.4 or ductwork complying with Section 4.5 (8) A hinged upblast fan supplied with flexible weatherproof electrical cable and service hold-open retainer to permit inspection and cleaning that is listed for commercial cooking equipment with the following conditions: (9) Where the fan attaches to the ductwork, the ductwork is a minimum of 0.46 m (18 in.) away from any roof surface, as shown in Figure (10) The fan discharges a minimum of 1.02 m (40 in.) away from any roof surface, as shown in Figure (11) Other approved fan, provided it meets all of the following criteria: (12) The fan meets the requirements of (3) and (13) Its discharge or its extended duct discharge meets the requirements of (2). (See ) (14) Exhaust fan discharge is directed up and away from the roof surface. Figure Upblast Fan Clearances.

28 8 of 123 7/30/2015 1:48 PM Item (3) is confusing as written. The change clarifies the provision in a more precise manner. Submitter Full Name: Jim Muir Organization: Building Safety Division, Clark County, Washington Affilliation: NFPA's Building Code Development Committee (BCDC) Submittal Date: Mon Dec 22 20:38:38 EST 2014 Resolution: FR-16-NFPA Statement: Item (3) is confusing as written. The change clarifies the provision in a more precise manner.

29 9 of 123 7/30/2015 1:48 PM Public Input No. 153-NFPA [ Section No ] Lower exhaust air volumes shall be permitted during no-load cooking conditions, provided they are sufficient to capture and remove flue gases and residual vapors from cooking equipment Retrofits of existing installations using mesh filters shall include testing to insure adequate exhaust capacity. Retrofits place taxation on existing exhaust blowers which were sized prior to the adding of resistance from other sources. Smoke loss, poor capture and unsafe condition result from the absence of adjusting blowers to accomodate the resistance. Submitter Full Name: Bernard Besal Organization: Besal Services, Inc. Affilliation: International Kitchen Exhaust Cleaning Association (IKECA) Submittal Date: Mon Jan 05 16:38:43 EST 2015 Resolution: Adequate airflow is addressed in Section and

30 0 of 123 7/30/2015 1:48 PM Public Input No. 59-NFPA [ Section No ] The hood exhaust fan shall not be required to start shall start upon activation of the extinguishing system if the exhaust fan and all cooking equipment served by the fan have been shut down, unless fan shutdown is required by a listed component of the ventilation system or by the listing of the extinguishing system. If a fire event causes the extinguishing system to activate, the hood exhaust fans should activate to remove the products of combustion from the immediate area and aid in the cooling of heated surfaces to facilitate controlling and extinguishment of the fire. There is very little additional expense for this requirement. The conditional statement for exemption was carried over from Submitter Full Name: Kelly Nicolello Organization: Western Regional Fire Code Dev Submittal Date: Tue Oct 21 16:20:20 EDT 2014 Resolution: FR-56-NFPA Statement: If a fire event causes the extinguishing system to activate, the hood exhaust fans should activate to remove the products of combustion from the immediate area and aid in the cooling of heated surfaces to facilitate controlling and extinguishment of the fire. There is very little additional expense for this requirement. The conditional statement for exemption was carried over from

31 1 of 123 7/30/2015 1:48 PM Public Input No. 122-NFPA [ Section No ] The exhaust fan shall be provided with a means so that the fan is activated when any heat producing cooking appliance under the hood is turned on. Other appliances reside beneath cooking hoods in conjunction with cooking appliances. As currently written, the exhaust blower would be required to operate when non-heat producing appliances are operated. This proposed change would allow clearer guidance for the authority having jurisdiction, and would be more suitable for commonly applied heat detection devices which are used to activate the exhaust system blowers. Submitter Full Name: Bernard Besal Organization: Besal Services, Inc. Affilliation: International Kitchen Exhaust Cleaning Association (IKECA) Submittal Date: Fri Jan 02 18:13:25 EST 2015 Resolution: FR-18-NFPA Statement: This proposed change would allow clearer guidance for the authority having jurisdiction, and would be more suitable for commonly applied heat detection devices which are used to activate the exhaust system blowers.

32 2 of 123 7/30/2015 1:48 PM Public Input No. 113-NFPA [ Section No ] Fume incinerators, thermal recovery units, air pollution control devices, and/or other devices installed in ducts or hoods shall comply with the following: (1) The clearance requirements of Section 4.2 (2) Hood construction requirements in Section 5.1 (3) Exhaust duct construction complying with Chapter 7 (4) Simultaneous Other equipment installed in a hood shall meet the simultaneous operation requirements in (5) Access panels or doors complying with Chapter 7 (6) In-line fans complying with (7) Other equipment installed in a duct shall comply with (new ) (make this #(5) and renumber remaining) Additional Proposed Changes File Name Description Approved PCU_Illistration.docx Typical Filter Type Pollution Control Unit (PCU) Currently fire extinguishing systems installed in a pollution control unit, as and example, must discharge at the same time the hood system discharges. This makes sense if the pollution control equipment is installed within the hood, but is not logical if installed in the duct. Consider a hood with a pollution control unit installed in the duct. If a fire started in the hood the fire extinguishing equipment would discharge chemical not only within and under the hood but within the pollution control unit, over various series of filters (see illustration), aluminum electrostatic cells in some cases, and possibly odor control media. Now consider that this fire extends into the pollution control unit. Will the fire be extinguished by the chemical that has sprayed onto the filters etc. or will it prevent the filters etc. from catching fire. To my knowledge there is no test data showing that the fire will be extinguished or not allowed to ignite the filters etc. It is our recommendation (our proposed new ) that a pollution control unit or other devices installed in the duct should have its own independent fire extinguishing system so if the fire reached the unit it would then discharge and extinguish the fire. Submitter Full Name: PHILIP MORTON Organization: [ Not Specified ] Affilliation: Gaylord Industries Submittal Date: Tue Dec 30 14:50:51 EST 2014

33 3 of 123 7/30/2015 1:48 PM Resolution: FR-20-NFPA Statement: A pollution control unit or other devices installed in the duct should have its own independent fire extinguishing system.

34 4 of 123 7/30/2015 1:48 PM Public Input No. 78-NFPA [ Section No [Excluding any Sub-Sections] ] Any equipment, listed or otherwise, installed in the path of exhaust products that provides secondary filtration or air pollution control and that is installed in the path of travel of exhaust products shall be provided with an approved automatic fire-extinguishing system, installed in accordance with the fire-extinguishing system manufacturer's instructions, for the protection of the The fire extinguishing system required by shall provide protection for the component sections of the equipment, and shall include protection of the ductwork downstream of the equipment, whether or not the equipment is provided with a damper. To improve correlation between NFPA 96 and 17A. The current text contains errors and unnecessary text. The new requirement wording is much easier to enforce. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 13:51:25 EST 2014 Resolution: FR-25-NFPA Statement: To improve correlation between NFPA 96 and 17A. The current text contains errors and unnecessary text. The new requirement wording is much easier to enforce.

35 5 of 123 7/30/2015 1:48 PM Public Input No. 156-NFPA [ New Section after ] TITLE OF NEW CONTENT Type your content here...add a section on requiring a Carbon Monoxide detector in the kitchen if the operating fuel non electric If the heating fuel is non-electric and open flames are used a Carbon Monoxide detector shall be installed in both the kichen and dining area. Carbon Monoxide has been a problem in restaurants, with occupants evacuated and a death in one instance. Submitter Full Name: LEE DEVITO Organization: FIREPRO INCORPORATED Submittal Date: Mon Jan 05 17:41:27 EST 2015 Resolution: FR-19-NFPA Statement: The installation of a carbon monoxide detector enhances the life safety within a commercial cooking establishment.

36 6 of 123 7/30/2015 1:48 PM Public Input No. 102-NFPA [ Section No ] Equipment commissioning report(s) shall be provided for other the kitchen hood exhaust system and other equipment installed. The commissioning report for other equipment should include the kitchen hood exhaust system as well since it s operation would have an effect on performance of other equipment. Submitter Full Name: Jim Muir Organization: Building Safety Division, Clark County, Washington Affilliation: NFPA's Building Code Development Committee (BCDC) Submittal Date: Mon Dec 22 20:42:16 EST 2014 Resolution: This requirement is covered by Section

37 7 of 123 7/30/2015 1:48 PM Public Input No. 117-NFPA [ Section No ] 10.1 General Requirements Fire-extinguishing equipment for the protection of grease removal devices, hood exhaust plenums, and exhaust duct systems shall be provided * Cooking equipment that produces grease-laden vapors and that might be a source of ignition of grease in the hood, grease removal device, or duct shall be protected by fire-extinguishing equipment (New) Fume incinerators, thermal recovery units, air pollution control devices, or other devices installed in the exhaust, shall be protected by an independent fire extinguishing system with its own detection system. Currently fire extinguishing systems installed in a pollution control unit, as and example, must discharge at the same time the hood system discharges. This makes sense if the pollution control equipment is installed within the hood, but is not logical if installed in the duct. Consider a hood with a pollution control unit installed in the duct. If a fire started in the hood the fire extinguishing equipment would discharge chemical not only within and under the hood but within the pollution control unit, over various series of filters (see illustration), aluminum electrostatic cells in some cases, and possibly odor control media. Now consider that this fire extends into the pollution control unit. Will the fire be extinguished by the chemical that has sprayed onto the filters etc. or will it prevent the filters etc. from catching fire. To my knowledge there is no test data showing that the fire will be extinguished or not allowed to ignite the filters etc. It is our recommendation that a pollution control unit or other devices installed in the duct should have its own independent fire extinguishing system so if the fire reached the unit it would then discharge and extinguish the fire. Submitter Full Name: PHILIP MORTON Organization: [ Not Specified ] Affilliation: Gaylord Industries Submittal Date: Thu Jan 01 18:12:43 EST 2015 Resolution: FR-21-NFPA Statement: A pollution control unit or other devices installed in the duct should have its own independent fire extinguishing system.

38 8 of 123 7/30/2015 1:48 PM Public Input No. 127-NFPA [ Section No ] * Fire-extinguishing equipment for the protection of grease removal devices, hood exhaust plenums, and exhaust duct systems shall be provided. See proposed Annex note A Related Public Inputs for This Document Related Input Public Input No. 128-NFPA [New Section after A ] Relationship Source for annex note Submitter Full Name: David de Vries Organization: Firetech Engineering Inc. Submittal Date: Sun Jan 04 17:33:57 EST 2015 Resolution: FR-22-NFPA Statement: Added explanatory material to describe the hazard created by not complying with this requirement.

39 9 of 123 7/30/2015 1:48 PM Public Input No. 103-NFPA [ Section No ] Effective January 1, 2014, all existing fire-extinguishing systems shall meet the requirements of January 1, 2014 has passed. The charging statement in requires it for all existing systems now. Submitter Full Name: Jim Muir Organization: Building Safety Division, Clark County, Washington Affilliation: NFPA's Building Code Development Committee (BCDC) Submittal Date: Mon Dec 22 20:45:35 EST 2014 Resolution: The 2014 date was a specific date that was chosen that was 24 years after UL/300 passed which was 2 full hydrostatic testing cycles.

40 0 of 123 7/30/2015 1:48 PM Public Input No. 139-NFPA [ Section No ] Grease A water-wash fire extinguishing system installed in accordance with its listing can be used to satisfy the requirement of for the protection of grease removal devices, hood exhaust plenums, and exhaust ducts requiring protection in accordance with shall be permitted to be protected by a listed fixed baffle hood containing a constant or fire-actuated water-wash system that is listed and in compliance with ANSI/UL 300 or other equivalent standards and shall be installed in accordance with the requirements of their listing for the areas covered by such system. In combination with new definitions proposed for Chapter 3, this would make it clear that the listed water-wash systems can provide protection for the areas covered. The wording of the current makes it necessary to make a reference to "areas" covered. Related Public Inputs for This Document Related Input Public Input No. 138-NFPA [New Section after ] Relationship Definitions referenced Submitter Full Name: Russell Fleming Organization: National Fire Sprinkler Association Affilliation: Correlating Committee on Automatic Sprinklers Submittal Date: Mon Jan 05 14:05:30 EST 2015 Resolution: FR-42-NFPA Statement: Committee is eliminating redundancy in these sections and using new terminology for clarification. The heading of covers all hoods and the modified language clarifies the difference between a basic water wash system and one listed as a fire extinguishing system. The committee added the word fire to Section , as this section addresses water wash fire extinguishing systems. In Section , the technical committee clarified terminology used in this section of the standard.supervision is addressed in section

41 1 of 123 7/30/2015 1:48 PM Public Input No. 140-NFPA [ Section No ] Each such area not provided with a listed water-wash fire extinguishing system shall be provided with a fire-extinguishing system listed for the purpose. Consistency with new term and definition. Related Public Inputs for This Document Related Input Public Input No. 138-NFPA [New Section after ] Relationship New definition Submitter Full Name: Russell Fleming Organization: National Fire Sprinkler Association Affilliation: Correlating Committee on Automatic Sprinklers Submittal Date: Mon Jan 05 14:12:20 EST 2015 Resolution: FR-42-NFPA Statement: Committee is eliminating redundancy in these sections and using new terminology for clarification. The heading of covers all hoods and the modified language clarifies the difference between a basic water wash system and one listed as a fire extinguishing system. The committee added the word fire to Section , as this section addresses water wash fire extinguishing systems. In Section , the technical committee clarified terminology used in this section of the standard.supervision is addressed in section

42 2 of 123 7/30/2015 1:48 PM Public Input No. 141-NFPA [ Section No ] The water for listed fixed baffle hood assemblies supply for water-wash fire extinguishing systems shall be permitted to be supplied from the domestic water supply when the minimum water pressure and flow are provided in accordance with the terms of the listing. This requirement is only applicable to water-wash systems that are listed as fire extinguishing systems. Water-wash systems installed only for cleaning purposes should not be required to prove minimum flows and pressures other than as needed for customer satisfaction. Submitter Full Name: Russell Fleming Organization: National Fire Sprinkler Association Affilliation: Correlating Committee on Automatic Sprinklers Submittal Date: Mon Jan 05 14:16:33 EST 2015 Resolution: FR-42-NFPA Statement: Committee is eliminating redundancy in these sections and using new terminology for clarification. The heading of covers all hoods and the modified language clarifies the difference between a basic water wash system and one listed as a fire extinguishing system. The committee added the word fire to Section , as this section addresses water wash fire extinguishing systems. In Section , the technical committee clarified terminology used in this section of the standard.supervision is addressed in section

43 3 of 123 7/30/2015 1:48 PM Public Input No. 142-NFPA [ Section No ] The water supply for water-wash fire extinguishing systems shall be controlled by a supervised water supply control valve. listed indicating valve and shall be supervised open by one of the following methods: (capture from existing ). The intent is to apply to water-wash systems that are listed water-wash fire extinguishing systems. With this addition, present section can be deleted. Related Public Inputs for This Document Related Input Public Input No. 147-NFPA [Section No ] Public Input No. 151-NFPA [Section No ] Relationship Submitter Full Name: Russell Fleming Organization: National Fire Sprinkler Association Affilliation: Correlating Committee on Automatic Sprinklers Submittal Date: Mon Jan 05 14:19:59 EST 2015 Resolution: FR-42-NFPA Statement: Committee is eliminating redundancy in these sections and using new terminology for clarification. The heading of covers all hoods and the modified language clarifies the difference between a basic water wash system and one listed as a fire extinguishing system. The committee added the word fire to Section , as this section addresses water wash fire extinguishing systems. In Section , the technical committee clarified terminology used in this section of the standard.supervision is addressed in section

44 4 of 123 7/30/2015 1:48 PM Public Input No. 144-NFPA [ Section No ] The A water wash in a fixed baffle hood specifically listed to extinguish a fire -wash fire extinguishing system shall be activated by the cooking equipment fire extinguishing system. Consistency with proposed new definitions. Related Public Inputs for This Document Related Input Public Input No. 138-NFPA [New Section after ] Relationship Proposed definitions Submitter Full Name: Russell Fleming Organization: National Fire Sprinkler Association Affilliation: Correlating Committee on Automatic Sprinklers Submittal Date: Mon Jan 05 14:25:34 EST 2015 Resolution: FR-42-NFPA Statement: Committee is eliminating redundancy in these sections and using new terminology for clarification. The heading of covers all hoods and the modified language clarifies the difference between a basic water wash system and one listed as a fire extinguishing system. The committee added the word fire to Section , as this section addresses water wash fire extinguishing systems. In Section , the technical committee clarified terminology used in this section of the standard.supervision is addressed in section

45 5 of 123 7/30/2015 1:48 PM Public Input No. 145-NFPA [ Section No ] A water-wash system approved to be used for protection of the grease removal device(s), hood exhaust plenum(s), exhaust duct(s), or combination thereof shall include instructions and appropriate electrical interface for simultaneous activation of the water-wash system from an automatic fire-extinguishing system, where the automatic fire-extinguishing system is used for cooking equipment protection only. This section can be deleted. The previous section contains the performance requirement. Submitter Full Name: Russell Fleming Organization: National Fire Sprinkler Association Affilliation: Correlating Committee on Automatic Sprinklers Submittal Date: Mon Jan 05 14:32:25 EST 2015 Resolution: FR-42-NFPA Statement: Committee is eliminating redundancy in these sections and using new terminology for clarification. The heading of covers all hoods and the modified language clarifies the difference between a basic water wash system and one listed as a fire extinguishing system. The committee added the word fire to Section , as this section addresses water wash fire extinguishing systems. In Section , the technical committee clarified terminology used in this section of the standard.supervision is addressed in section

46 Public Input No. 146-NFPA [ Section No ] Where the fire-extinguishing system provides protection for the cooking equipment, hood, and duct, activation of the water wash shall not be required Where the automatic fire extinguishing system in accordance with NFPA 17A provides protection for the hood and duct in a fixed baffle hood containing a water-wash system, the water-wash system shall be made inoperable or delayed for a minimum of 60 seconds upon operation of the automatic fire-extinguishing system. Present is not needed, since a reorganization of material and new definitions would make the intent clear. It is proposed to move present to become the new subsection and renumber other subsections accordingly, since this subsection applies to water-wash systems that are not listed fire extinguishing systems, It is more general and should be presented first. Submitter Full Name: Russell Fleming Organization: National Fire Sprinkler Association Affilliation: Correlating Committee on Automatic Sprinklers Submittal Date: Mon Jan 05 14:37:26 EST 2015 Resolution: FR-42-NFPA Statement: Committee is eliminating redundancy in these sections and using new terminology for clarification. The heading of covers all hoods and the modified language clarifies the difference between a basic water wash system and one listed as a fire extinguishing system. The committee added the word fire to Section , as this section addresses water wash fire extinguishing systems. In Section , the technical committee clarified terminology used in this section of the standard.supervision is addressed in section of 123 7/30/2015 1:48 PM

47 Public Input No. 147-NFPA [ Section No ] Water-Based Fire-Extinguishing System The water required for listed automatic fire-extinguishing systems shall be permitted to be supplied from the domestic water supply where the minimum water pressure and flow are provided in accordance with the terms of the listing. The water supply shall be controlled by a supervised water supply control valve. 8.9 Where the water supply is from a dedicated fire protection water supply in a building with one or more fire sprinkler systems, separate indicating control valves and drains shall be provided and arranged so that the hood system water-wash fire extinguishing systems and sprinkler systems can be controlled individually. The current requirement of can be sufficiently covered in , specifically the proposed changes to It is proposed that current become the last subsection of current Related Public Inputs for This Document Related Input Public Input No. 142-NFPA [Section No ] Relationship relocation of valve supervision requirement Submitter Full Name: Russell Fleming Organization: National Fire Sprinkler Association Affilliation: Correlating Committee on Automatic Sprinklers Submittal Date: Mon Jan 05 14:41:24 EST 2015 Resolution: FR-42-NFPA Statement: Committee is eliminating redundancy in these sections and using new terminology for clarification. The heading of covers all hoods and the modified language clarifies the difference between a basic water wash system and one listed as a fire extinguishing system. The committee added the word fire to Section , as this section addresses water wash fire extinguishing systems. In Section , the technical committee clarified terminology used in this section of the standard.supervision is addressed in section of 123 7/30/2015 1:48 PM

48 8 of 123 7/30/2015 1:48 PM Public Input No. 151-NFPA [ Section No ] Water Valve Supervision. Valves controlling the water supply to listed fixed baffle hood assemblies, automatic fire-extinguishing systems, or both shall be listed indicating type of valve and shall be supervised open by one of the following methods: (1) Central station, proprietary, or remote station alarm service (2) Local alarm service that will cause the sounding of an audible signal at a constantly attended point (3) Locking valves open (4) * Sealing of valves and approved weekly recorded inspection Thsi section can be deleted if the details of valve supervision are moved to Related Public Inputs for This Document Related Input Public Input No. 142-NFPA [Section No ] Relationship New located for valve supervision details Submitter Full Name: Russell Fleming Organization: National Fire Sprinkler Association Affilliation: Correlating Committee on Automatic Sprinkklers Submittal Date: Mon Jan 05 14:51:18 EST 2015 Resolution: FR-43-NFPA Statement: The Technical Committee revised the section to use new terminology for clarification.

49 Public Input No. 118-NFPA [ Sections , ] Sections , Hoods installed end to end, back to back, or both, or sharing a common ductwork, not exceeding 75 feet in distance from the farthest hood, and having a grease-producing appliance(s) located under one or more of the hoods shall be considered a single hazard area requiring simultaneous automatic fire protection in all hoods and ducts (New) Hoods installed end to end, back to back, or both, sharing a common ductwork, the ductwork beyond 75 feet from the farthest hood shall be protected by an independent fire-extinguishing system with its own detection system and shall not require simultaneous activaton with the hoods fire extinguishing systems Hoods installed end to end, back to back, or both that do not share a common exhaust duct and are separated by a wall(s) or other means to ensure that grease-laden vapors exhausted under one hood cannot propagate to the other hoods, the hoods fire extinguishing system(s) shall be independent and shall not simultaneosly discharge. Common ductwork beyond 75 feet from the farthest hood shall be protected by an independent fire extinguishing system with its own detection system (New) Fume incinerators, thermal recovery units, air pollution control devices, or other devices installed in the exhaust systems duct shall not be required to comply with and New UL Test Standard 300 conduct a test to ensure that chemical spray nozzles located at the exhaust duct entrance will extinguish a fire in duct work 75 feet beyond the hood duct collar. Passing this test gives the fire system an "unlimited protection" Listing. We are involved in projects where the duct work is several hundred feet long, sometimes going straight up and others with horizontal ducts and making many turns before reaching the exhaust fan. There is no data, that I am aware of, that ensures a fire beyond 75 feet will be extinguished. Requiring an independent system, with its own detection system, will the system to discharge when needed and extinguish the system Hoods that share a common exhaust duct but are separated by walls should have their own independent fire extinguishing systems. We recently had a project where there were 43 hoods, most separated by walls or located in different rooms and all on one common exhaust duct. Because of current it was required that all 43 hoods had to simultaneously discharge. Even if it was just 2 hoods, installed in different rooms, there is still a problem. The following is rational for our proposal: For an example, assume there are 3 hoods separated by walls and there is a fire in Hood # 1, the fire is detected and all three fire systems simultaneously discharge; 1. If the fire spreads to Hood #2, will the chemical that has already sprayed all over the cooking appliances, hood plenum, and up the duct, extinguish the fire or prevent grease or other material from igniting. We are not aware of any tests or data proves this. 2. The personnel around Hood #1, will certainly be aware of the fire and will deal with it, even anticipating the fire extinguishing system discharging. The personnel around Hoods #2 and #3 may have no idea that Hood #1 is involved in a fire, and so when their Hoods fire extinguishing system discharges it's a complete surprise. If anyone is cooking under the hood, will the chemical harm their skin, or worse yet what if they happen to be looking up when the system discharges. What if maintenance, such as removing filters, replacing light bulbs etc. were being conducted when the system discharged. We believe simultaneous discharge is actually a hazard. Why not just allow the fire extinguishing system to react when there is a fire under the hood it serves (New) The rational for this proposal is the same as our proposal for and (New) and is as 9 of 123 7/30/2015 1:48 PM

50 0 of 123 7/30/2015 1:48 PM follows: Currently fire extinguishing systems installed in a pollution control unit, as and example, must discharge at the same time the hood system discharges. This makes sense if the pollution control equipment is installed within the hood, but is not logical if installed in the duct. Consider a hood with a pollution control unit installed in the duct. If a fire started in the hood the fire extinguishing equipment would discharge chemical not only within and under the hood but within the pollution control unit, over various series of filters (see illustration), aluminum electrostatic cells in some cases, and possibly odor control media. Now consider that this fire extends into the pollution control unit. Will the fire be extinguished by the chemical that has sprayed onto the filters etc. or will it prevent the filters etc. from catching fire. To my knowledge there is no test data showing that the fire will be extinguished or not allowed to ignite the filters etc. It is our recommendation that a pollution control unit or other devices installed in the duct should have its own independent fire extinguishing system so if the fire reached the unit it would then discharge and extinguish the fire. Submitter Full Name: PHILIP MORTON Organization: [ Not Specified ] Affilliation: Gaylord Industries Submittal Date: Thu Jan 01 18:22:32 EST 2015 Resolution: FR-45-NFPA Statement: The modification in Section mandates separate independent fire systems for multiple hoods on a single duct system and does not require those systems to simultaneously discharge. Section was added to comply with new section

51 1 of 123 7/30/2015 1:48 PM Public Input No. 152-NFPA [ Section No ] Where an automatic sprinkler system is used in conjunction with a water-wash system or water- based fire-extinguishing system served by the same water supply, hydraulic calculations shall consider both systems operating simultaneously. The water demands of a water-wash system can affect available water supply even if it is not a listed water-wash fire extinguishing system. Submitter Full Name: Russell Fleming Organization: National Fire Sprinkler Association Affilliation: Correlating Committee on Automatic Sprinklers Submittal Date: Mon Jan 05 14:56:24 EST 2015 Resolution: FR-42-NFPA Statement: Committee is eliminating redundancy in these sections and using new terminology for clarification. The heading of covers all hoods and the modified language clarifies the difference between a basic water wash system and one listed as a fire extinguishing system. The committee added the word fire to Section , as this section addresses water wash fire extinguishing systems. In Section , the technical committee clarified terminology used in this section of the standard.supervision is addressed in section

52 2 of 123 7/30/2015 1:48 PM Public Input No. 79-NFPA [ New Section after ] Solid fuel cooking operations shall not be required to be shut down. To improve correlation between NFPA 96 and 17A. This requirement currently appears as in NFPA 17A. It should be moved to NFPA 96 as shown. All requirements relating to shutdown should only appear on one standard and they are more appropriate in NFPA 96. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:03:35 EST 2014 Resolution: FR-23-NFPA Statement: To improve correlation between NFPA 96 and 17A. This requirement currently appears as in NFPA 17A. It should be moved to NFPA 96 as shown.

53 3 of 123 7/30/2015 1:48 PM Public Input No. 80-NFPA [ Section No [Excluding any Sub-Sections] ] A readily accessible means for manual activation shall be located between 1067 mm and 1219 mm (42 in. and 48 in.) above the floor, be accessible in the event of a fire, be located in a path of egress, and clearly identify the hazard protected. To improve correlation between NFPA 96 and 17A. There is similar text in NFPA 17A, The requirement should only appear in one standard. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:09:41 EST 2014 Resolution: FR-46-NFPA Statement: To improve correlation between NFPA 17A and NFPA 96, the revised text is applicable to all types of extinguishing systems.

54 4 of 123 7/30/2015 1:48 PM Public Input No. 69-NFPA [ Section No ] * At least one manual actuation device shall be located a minimum of 3 m (10 ft) and a maximum of 6 m (20 ft) from the protected hood exhaust system(s) within a located within a path of egress or at an alternative location acceptable to the AHJ. Given the design of any particular cooking area, meeting this spacing requirement is often difficult and impractical. By requiring the manual activator to be between 10 ft. and 20 ft. from the protected hood often requires building a structure for the sole purpose of mounting the manual activator. In some instances the kitchen door is right next to the cooking area and the manual activator should be located at that point of egress. Although the current wording does allow for flexibility by the AHJ, often times this is viewed as an absolute requirement. Removing this requirement will give the AHJ more discretion to assure the manual activator is located in a practical location in the path of egress. The location recommendation will be moved to the Annex, A , a separate proposal has been submitted to cover this new annex material. Submitter Full Name: Jennifer Boyle Organization: Bill Vegso, Buckeye Fire Equipment Company Affilliation: Fire Equipment Manufacturers Association (FEMA) Submittal Date: Tue Dec 02 13:15:32 EST 2014 Resolution: FR-46-NFPA Statement: To improve correlation between NFPA 17A and NFPA 96, the revised text is applicable to all types of extinguishing systems.

55 5 of 123 7/30/2015 1:48 PM Public Input No. 81-NFPA [ Section No ] At least one manual actuation device shall be located a minimum of 3 m (10 ft) and a maximum of 6 m (20 ft) from the protected hood exhaust system(s) within a path of egress or at an alternative location acceptable to the AHJ. To improve correlation between NFPA 96 and 17A. This requirement should appear in NFPA 17A. The requirement should be deleted from NFPA 96 and NFPA 17A, needs to be updated. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:11:13 EST 2014 Resolution: FR-46-NFPA Statement: To improve correlation between NFPA 17A and NFPA 96, the revised text is applicable to all types of extinguishing systems.

56 6 of 123 7/30/2015 1:48 PM Public Input No. 82-NFPA [ Section No ] Manual activation using a cable-operated pull station shall not require more than 178 N (40 lb) of force, with a pull movement not to exceed 356 mm (14 in.) to activate the automatic fire-extinguishing equipment. To improve correlation between NFPA 96 and 17A. The pull station requirements should only appear in NFPA 17A. This requirement appears in NFPA 17A, and Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:21:59 EST 2014 Resolution: FR-46-NFPA Statement: To improve correlation between NFPA 17A and NFPA 96, the revised text is applicable to all types of extinguishing systems.

57 7 of 123 7/30/2015 1:48 PM Public Input No. 83-NFPA [ Section No ] The automatic and manual means of system activation external to the control head or releasing device shall be separate and independent of each other so that failure of one will not impair the operation of the other except as permitted by To improve correlation between NFPA 96 and 17A. Similar text appears in NFPA 17A, The requirement should only appear on one standard. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:25:14 EST 2014 Resolution: FR-46-NFPA Statement: To improve correlation between NFPA 17A and NFPA 96, the revised text is applicable to all types of extinguishing systems.

58 8 of 123 7/30/2015 1:48 PM Public Input No. 84-NFPA [ Section No ] The manual means of system activation shall be permitted to be common with the automatic means if the manual activation device is located between the control head or releasing device and the first fusible link. To improve correlation between NFPA 96 and 17A. This is a system installation requirement which should appear in the installation standard, NFPA 17A, section 5.2. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:27:30 EST 2014 Resolution: FR-46-NFPA Statement: To improve correlation between NFPA 17A and NFPA 96, the revised text is applicable to all types of extinguishing systems.

59 9 of 123 7/30/2015 1:48 PM Public Input No. 85-NFPA [ Section No ] The means for manual activation shall be mechanical or rely on electrical power for activation in accordance with To improve correlation between NFPA 96 and 17A. Allowance for manual actuation to rely on electrical power is already covered in NFPA 17A, and Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:34:52 EST 2014 Resolution: FR-46-NFPA Statement: To improve correlation between NFPA 17A and NFPA 96, the revised text is applicable to all types of extinguishing systems.

60 0 of 123 7/30/2015 1:48 PM Public Input No. 86-NFPA [ Section No ] Electrical power shall be permitted to be used for manual activation if a standby power supply is provided or if supervision is provided in accordance with Section To improve correlation between NFPA 96 and 17A. Allowance for manual actuation to rely on electrical power is already covered in NFPA 17A, and Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:36:38 EST 2014 Resolution: FR-46-NFPA Statement: To improve correlation between NFPA 17A and NFPA 96, the revised text is applicable to all types of extinguishing systems.

61 1 of 123 7/30/2015 1:48 PM Public Input No. 130-NFPA [ Section No ] * Instruction shall be documented and shall be provided by the management to new employees on hiring and to all employees semi-annually regarding the proper use of portable fire extinguishers and the manual activation of fire-extinguishing equipment. Experience finds that many commercial cooking operations employees have not been instructed or have forgotten their training, resulting in inappropriate response to a fire. Providing instructions at regular intervals after initial instruction will reduce the likelihood of inappropriate response. Related Public Inputs for This Document Related Input Public Input No. 131-NFPA [New Section after A (4)] Relationship Submitter Full Name: David de Vries Organization: Firetech Engineering Inc. Submittal Date: Sun Jan 04 17:43:43 EST 2015 Resolution: FR-48-NFPA Statement: The revision is more appropriate in Chapter 11 where posting instructions is already required. Experience finds that many commercial cooking operations employees have not been instructed or have forgotten their training, resulting in inappropriate response to a fire. Providing instructions at regular intervals after initial instruction will reduce the likelihood of inappropriate response.

62 2 of 123 7/30/2015 1:48 PM Public Input No. 87-NFPA [ Section No ] Upon activation of an automatic fire-extinguishing system, an audible alarm or visual indicator shall be provided to show that the system has activated. To improve correlation between NFPA 96 and 17A. Audible or visual indicator for system operation is covered in NFPA 17A, Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:37:35 EST 2014 Resolution: These requirements should reside in NFPA 96 and be recommended for extraction into NFPA 17A and other installation standards as appropriate.

63 3 of 123 7/30/2015 1:48 PM Public Input No. 88-NFPA [ Section No ] Where a fire alarm signaling system is serving the occupancy where the extinguishing system is located, the activation of the automatic fire-extinguishing system shall activate the fire alarm signaling system. To improve correlation between NFPA 96 and 17A. Connection to the building fire alarm system is covered in NFPA 17A, This requirement should only appear in one standard. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:38:50 EST 2014 Resolution: These requirements should reside in NFPA 96 and be recommended for extraction into NFPA 17A and other installation standards as appropriate.

64 4 of 123 7/30/2015 1:48 PM Public Input No. 119-NFPA [ Section No ] Where electrical power is required to operate the fixed automatic fire-extinguishing system, the system shall be provided with a reserve power supply and be monitored by a supervisory alarm except as permitted in (New. Renumber existing to and remaining sections of 10.7.) Fixed automatic fire-extinguishing systems shall have a visual means to indicate that the propellant vessel is pressurized to its required pressure. Many chemical fire extinguishing systems use a pressurized gas cartridge, that when mechanically punctured, propels the chemical through the piping and then discharging through the nozzles. The problem is that this cartridge is not monitored. The fire extinguishing system may be cocked and ready, but the cartridge may not be pressurized or not in place. Without monitoring, the kitchen staff has no idea that the system in not ready to discharge if there is a fire. We have many service agencies that are also fire extinguishing systems contractors, and we have heard many instances of cartridges laying in the bottom of the system cabinet, or in place but previously punctured. Without the gas propellent the system is useless. Submitter Full Name: PHILIP MORTON Organization: [ Not Specified ] Affilliation: Gaylord Industries Submittal Date: Thu Jan 01 18:55:54 EST 2015 Resolution: This public input has been referred to the correlation task group for NFPA 17A and NFPA 96 for recommended resolution.

65 5 of 123 7/30/2015 1:48 PM Public Input No. 89-NFPA [ Section No ] Where electrical power is required to operate the fixed automatic fire-extinguishing system, the system shall be provided with a reserve power supply and be monitored by a supervisory alarm except as permitted in To improve correlation between NFPA 96 and 17A. Reserve power and supervision for systems that are electrically operated is covered in NFPA 17A, This requirement should only appear in one standard. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:40:33 EST 2014 Resolution: FR-47-NFPA Statement: To improve correlation between NFPA 17A and NFPA 96, the requirements are more appropriate in an installation standard.

66 6 of 123 7/30/2015 1:48 PM Public Input No. 90-NFPA [ Section No ] Where fixed automatic fire-extinguishing systems include automatic mechanical detection and actuation as a backup detection system, electrical power monitoring and a reserve power supply shall not be required. To improve correlation between NFPA 96 and 17A. Delete requirement for electrical power monitoring and a reserve power not being required for systems that include automatic mechanical detection and actuation as a backup detection system as this is already covered in NFPA 17A, The requirement should only appear in one standard. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:41:56 EST 2014 Resolution: FR-47-NFPA Statement: To improve correlation between NFPA 17A and NFPA 96, the requirements are more appropriate in an installation standard.

67 7 of 123 7/30/2015 1:48 PM Public Input No. 91-NFPA [ Section No ] System supervision shall not be required where a fire-extinguishing system(s) is interconnected or interlocked with the cooking equipment power source(s) so that if the fire-extinguishing system becomes inoperable due to power failure, all sources of fuel or electrical power that produce heat to all cooking equipment serviced by that hood shall automatically shut off. To improve correlation between NFPA 96 and 17A. Delete requirement that supervision is not required where a system is interconnected to turn off cooking equipment power if the fire extinguishing system becomes inoperable due to power failure as this is already covered in NFPA 17A, The requirement should only appear in one standard. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:43:00 EST 2014 Resolution: FR-47-NFPA Statement: To improve correlation between NFPA 17A and NFPA 96, the requirements are more appropriate in an installation standard.

68 8 of 123 7/30/2015 1:48 PM Public Input No. 41-NFPA [ Section No ] Hoods containing automatic fire-extinguishing systems are protected protecting all appliances and spaces under the hood are considered protected areas; therefore, these hoods are not considered obstructions to overhead sprinkler systems and shall not require floor additional sprinkler coverage underneath. This has been submitted to 96 and 13. This better clarifies the intent of this section. Commercial cooking hoods that have total fire protection beneath them are not considered obstructions to ceiling-installed sprinklers. This has been a confusing issue and unclear to some AHJs. It is not uncommon to find areas under the hood without protection, such as when there are no appliances or where the appliances do not require protection (e.g. they do not produce grease-laden vapors examples include ovens, warming equipment, and steam tables). Another example is a pizza restaurant with a large commercial cooking hood. While the hood may / may not need a suppression system based on what is cooked and the production of grease-laden vapors, there are often large areas under the hood with no protection and it is common to find cardboard pizza boxes stored there. Also the term floor coverage is deleted and replaced with additional sprinkler coverage ; floor coverage is a concept in NFPA 13 but not an actual objective. Except for similar text extracted from NFPA 96, the term floor coverage does not exist in NFPA 13. Submitter Full Name: Doug Hohbein Organization: Northcentral Fire Code Develop Submittal Date: Tue Oct 14 12:48:22 EDT 2014 Resolution: FR-28-NFPA Statement: This better clarifies the intent of this section. Commercial cooking hoods that have total fire protection beneath them are not considered obstructions to ceiling-installed sprinklers. This has been a confusing issue and unclear to some AHJs. It is not uncommon to find areas under the hood without protection, such as when there are no appliances or where the appliances do not require protection (e.g. they do not produce grease-laden vapors examples include ovens, warming equipment, and steam tables). Another example is a pizza restaurant with a large commercial cooking hood. While the hood may / may not need a suppression system based on what is cooked and the production of grease-laden vapors, there are often large areas under the hood with no protection and it is common to find cardboard pizza boxes stored there. The term floor coverage is deleted and replaced with additional sprinkler coverage ; floor coverage is a concept in NFPA 13 but not an actual objective. Except for similar text extracted from NFPA 96, the term floor coverage does not exist in NFPA 13.

69 9 of 123 7/30/2015 1:48 PM Public Input No. 92-NFPA [ Section No ] A single detection device, listed with the extinguishing system, shall be permitted for more than one appliance where installed in accordance with the terms of the listing. To improve correlation between NFPA 96 and 17A. A single link is permitted for multiple appliances should be moved to NFPA 17A, This requirement should only appear in one standard. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 14:44:19 EST 2014 Resolution: FR-24-NFPA Statement: To improve correlation between NFPA 96 and 17A. A single link is permitted for multiple appliances should be moved to NFPA 17A, This requirement is more appropriate in an installation standard.

70 0 of 123 7/30/2015 1:48 PM Public Input No. 155-NFPA [ New Section after ] TITLE OF NEW CONTENT Class "B" gas-type clean agent extinguishers shall not be permitted in kitchen cooking areas. The technical committee needs to again address this specific fire extinguisher reference within commercial kitchens. The prohibited placement of clean agent types of portable fire extinguishers within commercial kitchens has been a long standing requirement, that was inadvertently removed from the 2011 edition of NFPA-96. Clean agent fire extinguishers have a history of attempted use on cooking appliance fires, prior to activating fire suppression systems. Activation of the fire supression system prior to the utilization of any extinguisher, is essential to address hidden fire typically present within the hood and exhaust duct, as well as shut down of all heat sources under the hood. The premature removal of heat generated from cooking applance fires with an extinguisher, can essentially disable the automatic detection and activation of such systems until the building structure is severely involved. Existing extinguisher requirements within NFPA-10 and NFPA-96 specifically restrict the use of installed class K extinguishers till after the suppression system has been activated. Reference the existing equipment labeling and placard requirements within commercial kitchen applications. The suggested "clean agent" term was added for additional clarification of the specific type of extinguishers being addressed. Submitter Full Name: J. Nerat Organization: UTC/Badger Fire Protection Affilliation: NFPA Industrial Section Representative Submittal Date: Mon Jan 05 17:24:35 EST 2015 Resolution: FR-29-NFPA Statement: Carbon dioxide extinguishers shall not be used in kitchen fires.

71 1 of 123 7/30/2015 1:48 PM Public Input No. 132-NFPA [ Section No ] Instructions for manually operating the fire-extinguishing system shall be posted conspicuously in the kitchen and shall be reviewed with employees by the management in accordance with Section This proposed additional text ties this section back to the requirement for instruction in Related Public Inputs for This Document Related Input Public Input No. 131-NFPA [New Section after A (4)] Relationship Same subject Submitter Full Name: David de Vries Organization: Firetech Engineering Inc. Submittal Date: Sun Jan 04 17:54:32 EST 2015 Resolution: This revision is addressed by FR-48.

72 2 of 123 7/30/2015 1:48 PM Public Input No. 61-NFPA [ Section No ] * Fusible links of the metal alloy type and automatic sprinklers of the metal alloy type shall be replaced at least semiannually except as permitted by and No longer apply to section & Submitter Full Name: MICHAEL LADEROUTE Organization: GLOBE TECHNOLOGIES CORP. Submittal Date: Wed Nov 19 09:46:13 EST 2014 Resolution: FR-30-NFPA Statement: Reference to and are not necessary as they do not address metal alloy types.

73 3 of 123 7/30/2015 1:48 PM Public Input No. 62-NFPA [ Section No ] Detection devices that are other than bulb-type automatic sprinklers and fusible links other than the metal alloy type shall be examined and cleaned or replaced annually or as per the manufacturer's instructions. There are other types of detection and they require their own maintenance instructions. Submitter Full Name: MICHAEL LADEROUTE Organization: GLOBE TECHNOLOGIES CORP. Submittal Date: Wed Nov 19 09:48:07 EST 2014 Resolution: It is reasonable to permit glass bulbs to be cleaned.

74 4 of 123 7/30/2015 1:48 PM Public Input No. 63-NFPA [ Section No ] Fixed temperature-sensing elements other than the fusible metal alloy type shall be permitted to remain continuously in service, provided they are inspected and cleaned or replaced if necessary in accordance with the manufacturer's instructions, every 12 months or more frequently to ensure proper operation of the system. Previous changes to this standard no longer make this section needed. Also, agrees with NFPA 17A proposed changes. Submitter Full Name: MICHAEL LADEROUTE Organization: GLOBE TECHNOLOGIES CORP. Submittal Date: Wed Nov 19 09:51:44 EST 2014 Resolution: Glass bulb links can be cleaned.

75 5 of 123 7/30/2015 1:48 PM Public Input No. 28-NFPA [ New Section after ] Inspection and maintenance records, including certificates of inspection and maintenance, shall be permitted to be stored and accessed electronically. The permission of electronic storage and access of inspection and maintenance documentation is now granted by NFPA 10, 25, 72, 80, 731, and, pending final adoption next year, NFPA 12A and NFPA 96, like those other documents, has inspection and maintenance requirements that call for documentation. This PI will bring NFPA 96 in line with these other documents that permit electronic storage and access of inspection and maintenance documentation, while still allowing for documentation in hardcopy format. Submitter Full Name: Joe Scibetta Organization: BuildingReports Submittal Date: Tue Jun 10 21:00:44 EDT 2014 Resolution: FR-31-NFPA Statement: The permission of electronic storage and access of inspection and maintenance documentation is now granted by NFPA 10, 25, 72, 80, 731, and, pending final adoption next year, NFPA 12A and NFPA 96, like those other documents, has inspection and maintenance requirements that call for documentation. This PI will bring NFPA 96 in line with these other documents that permit electronic storage and access of inspection and maintenance documentation, while still allowing for documentation in hardcopy format.

76 6 of 123 7/30/2015 1:48 PM Public Input No. 77-NFPA [ Section No ] 11.4 * Inspection for Grease Buildup. The entire exhaust system shall be inspected for grease buildup by a properly trained, qualified, and certified person(s) acceptable to the authority having jurisdiction and in accordance with Table Table 11.4 Schedule of Inspection for Grease Buildup Type or Volume of Cooking Systems serving solid fuel cooking operations * Systems serving high-volume cooking operations, such as 24-hour cooking, charbroiling, or wok cooking Systems serving moderate-volume cooking operations Inspection Frequency Monthly Quarterly Semiannually ** Systems serving low-volume cooking operations, such as Annually *High-volume cooking operations include 24-hour cooking, charbroiling, and wok cooking. **Low-volume cooking operations, include churches, day camps, seasonal businesses, or and senior centers. Annually The examples more appropriately belong as notes to the table. Alternately, the could appear in the annex. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 13:37:01 EST 2014 Resolution: FR-32-NFPA Statement: The examples more appropriately belong as notes to the table.

77 7 of 123 7/30/2015 1:48 PM Public Input No. 143-NFPA [ Section No ] * If, upon inspection, the exhaust system is found to be contaminated with deposits from grease-laden vapors, the contaminated portions of the exhaust system shall be cleaned by a properly trained, qualified, and certified person(s) in accordance with IKECA/ANSI Standard C-10 or, other equivalent standard acceptable to the authority having jurisdiction. Since the last revision cycle, IKECA/ANSI Standard C-10 has been adopted by The International Code Council/International Fire code (ICC/IFC). Adoption by NFPA 96 would allow greater harmony in guidance for local Authorities Having Jurisdiction (AHJs). Local AHJs have long voiced their desire for greater clarity on methodology in support of standards. IKECA/ANSI Standard C-10 is currently in mid revision as per typical cycle requirement. Some revisions to C-10 are in keeping with a formal agreement between The IKECA/ANSI Standards Committee and, NFPA. When these revisions are finalized, a current copy of the standard shall be provided to the NFPA 96 Committee. We expect this revision to be complete before the May, 2015 NFPA 96 Committee meeting. Submitter Full Name: W. Dilg Organization: Nelbud Services Group Submittal Date: Mon Jan 05 14:20:38 EST 2015 Resolution: FR-33-NFPA Statement: ANSI/IKECA C-10 provides reasonable guidance on cleaning.

78 8 of 123 7/30/2015 1:48 PM Public Input No. 74-NFPA [ Section No ] * If, upon inspection, the exhaust system is found to be contaminated with deposits from grease-laden vapors, the contaminated portions of the exhaust system shall be cleaned by a properly trained, qualified, and certified person(s) acceptable to the authority having jurisdiction Hoods, grease removal devices, fans, ducts, and other appurtenances shall be cleaned to remove combustible contaminants to a minimum of 50 μm (0.002 in.) A grease depth gauge comb shown in Figure shall be scraped along the duct surface to measure grease depth Where a measured depth of 2000 μm (0.078 in.) is observed, the surfaces shall be cleaned in accordance with Where a measured depth of 3175 μm (0.125 in.) is observed in a fan housing, the surfaces shall be cleaned in accordance with Insert Figure A here and renumber as Figure The use of the grease comb depth gauge should be required. The text is being moved from the annex to the body. Related Public Inputs for This Document Related Input Public Input No. 76-NFPA [Section No. A ] Public Input No. 75-NFPA [Section No ] Relationship Moved A to body of standard. Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 13:26:16 EST 2014 Resolution: FR-34-NFPA Statement: The grease comb should be used to determine cleanliness and should appear as a requirement. The annex text was moved to the body of the standard.

79 9 of 123 7/30/2015 1:48 PM Public Input No. 75-NFPA [ Section No ] * If, upon inspection, the exhaust system is found to be contaminated with deposits from grease-laden vapors, the contaminated portions of the exhaust system shall be cleaned by a properly trained, qualified, and certified person(s) acceptable to the authority having jurisdiction Delete text and renumber accordingly. Hoods, grease removal devices, fans, ducts, and other appurtenances shall be cleaned to remove combustible contaminants to a minimum of 50 μm (0.002 in.). This text should appear as a subparagraph to Related Public Inputs for This Document Related Input Relationship Public Input No. 74-NFPA [Section No ] New cleaning criteria added to Submitter Full Name: Mark Conroy Organization: Brooks Equipment Company Submittal Date: Tue Dec 16 13:28:17 EST 2014 Resolution: FR-34-NFPA Statement: The grease comb should be used to determine cleanliness and should appear as a requirement. The annex text was moved to the body of the standard.

80 0 of 123 7/30/2015 1:48 PM Public Input No. 24-NFPA [ Section No ] When an exhaust cleaning service system is used cleaned, a certificate showing the name of the servicing company, the name of the person performing the work, and the date of inspection or cleaning shall be maintained on the premises. The proposed revision clarifies that whoever cleans the system a record is maintained on site. Submitter Full Name: Doug Hohbein Organization: Northcentral Fire Code Develop Submittal Date: Tue Apr 22 16:38:43 EDT 2014 Resolution: FR-35-NFPA Statement: The revision clarifies that whoever inspects or cleans the system must provide a record to be maintained on site.

81 1 of 123 7/30/2015 1:48 PM Public Input No. 133-NFPA [ New Section after ] Grease Drip Collectors Metal containers used to collect grease drippings as required by Section shall be inspected at least weekly, and then emptied and cleaned as needed to limit the accumulation of grease. The metal grease drip collectors within the hood sometimes become involved in fire before the fire extinguishing system operates. Typically no agent discharges into these devices, thus a fire on an appliance and within the hood that is successfully extinguished by the system can subsequently spread from a fire that is fueled from the grease collector into the exhaust system, since the grease collector is outside the zone of protection. Related Public Inputs for This Document Related Input Public Input No. 128-NFPA [New Section after A ] Relationship Same subject Submitter Full Name: David de Vries Organization: Firetech Engineering Inc. Submittal Date: Sun Jan 04 17:58:05 EST 2015 Resolution: FR-36-NFPA Statement: The metal grease drip collectors within the hood sometimes become involved in fire before the fire extinguishing system operates. Typically no agent discharges into these devices, thus a fire on an appliance and within the hood that is successfully extinguished by the system can subsequently spread from a fire that is fueled from the grease collector into the exhaust system, since the grease collector is outside the zone of protection.

82 2 of 123 7/30/2015 1:48 PM Public Input No. 109-NFPA [ Section No ] Listing evaluation shall include the following: (1) Capture and containment of vapors at combustible particulate matter at published and labeled airflows (2) Grease discharge at the exhaust outlet of the system not to exceed an average of Effluent emissions from a thermal food and food equipment process shall not exceed 2. 5 mg/m 3 ( oz/ft 3 ) of exhausted air sampled combustable particulate matter in process air sampled from that equipment at maximum amount of product that is capable of being processed over a continuous 8 2 -hour test per EPA Test Method 202 5, with with the system operating at its minimum listed airflow (3) Listing and labeling of clearance to combustibles from all sides, top, and bottom (4) Electrical connection in the field in accordance with NFPA 70 (5) Interlocks on all removable components that lie in the path of airflow within the unit to ensure that they are in place during operation of the cooking appliance Additional Proposed Changes File Name Description Approved EFFLUENT_REPORT.docx GOOGLE SEARCH ENGINE USING TITLE OF ASRAE PUBLICATION RETURNS DTATA FROM A PEER REVIEWED PUBLICATION CHARACTERIZING VARIOUS RATIONS OF H2O MEASURED BY EPA 202 TEST METHOD. H2O - IS ANTAGONISTIC TO FIRE NAD INCLUDING THESE VALUES IN FIRE RISK ASSESSMENT/MEASUREMENT IS BAD SCIENCE The ASHRAE 745 RP IS A PEER REVIEWED ASHRAE PUBLICATION COMPRISING THE VERY FIRST FUNDAMENTAL RESEARCH TO CHARATERIZE EFFLUENT PARTICULATE MATTER AS MEASURED USING EPA 202. THE SELECTION OF EPA 202 FOR THE APPROPRIATE RISK ANALYSIS METHOD WAS PRECIPITATED WITH THE SOUTH COAST AIR MANAGEMENT DISTRICT IN SOUTHERN CALIFORNIA IN UNFORTUNATELY, AS THE DATA AND REPORT DOCUMENT, WATER IS MEASURED AS A PARRT OF THE OVERALL VALUE OF "CONDENSABLE" PARTICULATE. PRIVATE STUDIES HAVE SHOWN THAT BOILING WATER WITH LARGE SURFACE AREAS WILL ENABLE THE NPA 96 CHAPTER 13 IMPOSED TLV OF 5MG/M3 AS NOMINAL EXHAUST RATE OF 500CFM TO BE EXCEEDED. WHAT FIRE RISK DOES WATER VAPOR COMPRISE? NFPA 96 IS ABOUT FIRE SAFETY, NOT EXCESSIVE HUMIDITY, MOLD AND SICK BUILDING SYNDROME. EPA TEST METHOD 5 IS A MORE APPRIPROATE TEST FOR COMBUSTIBLE PARTICULATE MATTER FROM STATIONARY SOURCES. FURTHER RESEARCH IS NEEDED TO PROCESS REASONABLE VALIDATE TOTAL MASS EMISSIONS GIVEN SPOECIFIC CHARACTERISTICS OF THE SPACE IN WHICH THE THERMAL FOOD PROCESS IS PERFORMED. Submitter Full Name: THOMAS JOHNSON Organization: JOHNSON DIVERSIFIED PROD INC Affilliation: on my own

83 3 of 123 7/30/2015 1:48 PM Submittal Date: Tue Dec 30 08:03:30 EST 2014 Resolution: Lack of substantiation for the change.

84 PEER REVIEWED RESEARCH PUBLICATION. USE THE GOOGLE SEARCH ENGINE FOR: New Rules For Kitchen Exhaust - ASHRAE

85 4 of 123 7/30/2015 1:48 PM Public Input No. 110-NFPA [ Section No ] Listing evaluation shall include the following: (1) Capture and containment of vapors partuculate matter at published and labeled airflows (2) Grease discharge Combustilbe particulate matter discharged at the exhaust outlet of the system is not to exceed an average of 5 mg 2.5mg /m 3 ( oz/ft 3 ) of exhausted air sampled from that equipment at maximum amount of product that is capable of being processed over a continuous 8 2 -hour test per EPA Test Method 202 5, with the system operating at its minimum listed airflow (3) Listing and labeling of clearance to combustibles from all sides, top, and bottom (4) Electrical connection in the field in accordance with NFPA 70 (5) Interlocks on all removable components that lie in the path of airflow within the unit to ensure that they are in place during operation of the cooking appliance Condensible water vapor is measured using EPA test method 202. Any H2O measured in the sample is antagonistic to fire, and cannot logically be used as an risk measurement additive or contributing factor to a fire hazard. The use of the word "vapors" is misapplied in this standard. condensible particulates are instantly condensed when they come in contact with room air. The mean temperature of exhaust air even over high temperature cooking operations rarely exceeds 200F. Combustible particulate matter at these temperatures are not in a gas phase. Accordingly, cooking operations are outside of the scope of EPA test method 202. EPA 202 is the appropriate test for power plants smoke stacks and other industrial processes where gasses from various industrial processes are captured and exhausted from stacks. Such is not the case where exhaust air streams are always below the boiling point of water at atmospheric pressure. Submitter Full Name: THOMAS JOHNSON Organization: JOHNSON DIVERSIFIED PROD INC Affilliation: On my own Submittal Date: Tue Dec 30 08:40:29 EST 2014 Resolution: The submitter did not provide adequate substation.

86 5 of 123 7/30/2015 1:48 PM Public Input No. 134-NFPA [ Section No ] * Gas-operated equipment utilizing solid fuel for flavoring that meets all the following conditions shall not be required to have a separate exhaust system: (1) * The solid fuel holder (smoker box) shall be listed with the gas-operated equipment. (2) The solid fuel holder shall be located underneath the gas burners. (3) Spark arresters conforming with shall be provided. (4) * The maximum quantity of solid fuel consumed shall not exceed 2.45 kg ( lb) per hour per kw 3kW (100,000 Btu/hr) of gas burner capacity. (5) The gas-operated equipment shall be protected by a fire suppression system listed for the equipment, including the solid fuel holder. (6) Gas-operated equipment with integral solid fuel holder(s) intended for flavoring, such as radiant charbroiler(s), shall comply simultaneously with the requirements of ANSI/UL 300 that address that gas radiant charbroiler(s) and mesquite wood wood charbroiler(s). (7) A fire suppression system nozzle(s) shall be installed to protect the solid fuel holder. (8) The fire suppression system shall be designed and installed to protect the entire cooking operation. (9) Each solid fuel holder shall be limited to a size of L ( in. 3 ), with no dimension to exceed 51 cm (20 in.). (10) A maximum of one solid fuel holder for each 29.3 kw (100,000 Btu/hr), or portion thereof, of burner capacity shall be permitted. (11) Solid fuel shall be immersed in water for a continuous period of at least 24 hours immediately prior to being placed in the cooking equipment. (1 1 2) The inspection frequency shall be the same as for solid fuel cooking operations in Table Gas-operated equipment utilizing solid fuel for flavoring that meets shall be inspected, cleaned, and maintained in accordance with Section During the last cycle of this standard, a proposal was made to allow solid fuel (wood) to be utilized in char broilers for flavoring, and to treat that operation differently than cooking with solid fuel, specifically to delete the requirement for a separate hood system for these operations. The original proposal was to limit the amount of wood to an amount that would contribute less than five percent of the total amount of heat used for cooking. The proposal was based upon a study conducted by the proponent and the policies and procedures of a major restaurant chain. The committee accepted the proposal in principle, but invoked a series of requirements to address concerns expressed by the committee and others. The results of the committee s revisions of the original proposal are that the amount of fuel allowed is far more than what was used in the study, and more than is used by the major restaurant chain. This comment addresses that issue by revising the maximum amount of fuel permitted to the same amount used in the study. To allow greater amounts of fuel is to increase the hazard without justification; this change simply adheres to the parameters of the study.

87 6 of 123 7/30/2015 1:48 PM The other change is to require that the wood be soaked in water prior to being placed in the broiler. This is consistent with the study used to justify the original change, and is consistent with the procedures used by the major restaurant change. This proposal should not be controversial; it is simply bringing the language that was inserted into the standard in line with the justification provided for the proposed change. Submitter Full Name: Jennifer Boyle Organization: Jim Tidwell, Tidwell Code Consulting Affilliation: Fire Equipment Manufacturers Association (FEMA) Submittal Date: Mon Jan 05 08:57:40 EST 2015 Resolution: FR-37-NFPA Statement: This revision brings the fuel volumes in line with the original test data.

88 7 of 123 7/30/2015 1:48 PM Public Input No. 68-NFPA [ Section No [Excluding any Sub-Sections] ] For fire-extinguishing equipment on downdraft appliance ventilation systems, the following shall apply: (1) Cooking surface, duct, and plenum protection shall be provided. (2) At least one fusible link or heat detector shall be installed within each exhaust duct opening in accordance with the manufacturer's listing. (3) A fusible link or heat detector shall be provided above for each protected cooking appliance and in located in the plenum area of that appliance or in accordance with the extinguishing system manufacturer s listing. (4) A manual activation device shall be provided as part of each appliance at a height acceptable to the authority having jurisdiction. (5) Portable fire extinguishers shall be provided in accordance with Section Downdraft appliances do not have an overhead hood where detectors can be placed. The exhaust from these appliances does not go up into an overhead hood but rather down into the downdraft plenum. Placing a detector above a downdraft appliance is impractical and would not provide timely system activation because the heat generated by a fire on the cooking surface is drawn into the downdraft plenum. This is where the detector should be placed. Additionally, NFPA requires that an interlock be provided on downdraft cooking appliances so the appliance cannot operate unless the ventilation system is activated. Submitter Full Name: Jennifer Boyle Organization: Bill Vegso, Buckeye Fire Equipment Company Affilliation: Fire Equipment Manufacturers Association (FEMA) Submittal Date: Tue Dec 02 13:10:45 EST 2014 Resolution: FR-38-NFPA Statement: It is not practical to place a detector above a downdraft ventilation appliance.

89 8 of 123 7/30/2015 1:48 PM Public Input No. 114-NFPA [ New Section after 15.4 ] TITLE OF NEW CONTENT Type your content here... Additional Proposed Changes File Name Description Approved Proposed_Chapter_16.pdf Proposed new section concerning mobile cooking Substantiation: IFMA developed a Task Group to look into mobile and temporary cooking operations after recent events involving them along with what seems to be a lack of regulation for the increasing number of units. Currently there is no one place to find all the requirements for mobile and temporary cooking operations this proposal brings requirements from NFPA 1 and 58 to aid the user of the document. The remaining text brings in common requirements for an operation i.e. permits, portable fire extinguishers, training and other. Submitter Full RAYMOND WALKER Name: Organization: Bolton Fire Dept Executive Board of IFMA on behalf of the Task Group and Affilliation: membership. Submittal Date: Tue Dec 30 19:19:00 EST 2014 Resolution: Many of the requirements in this public input are outside the scope of NFPA 96. Consideration should be given to approaching NFPA 1 on this topic. Section currently addresses temporary and mobile cooking operations.

90 Chapter 16 Mobile and Temporary Cooking Operations 16.1 General Mobile and temporary cooking operations shall comply with Section 16.1 and the applicable section for the type of cooking being performed Where required by the AHJ, permits shall be required for the location, design, construction and operation of mobile and temporary cooking operations Portable fire extinguishers Portable fire extinguishers shall be provided per NFPA 96 for cooking operations A minimum of one 2A:10BC portable fire extinguishers shall be provided when a generator or other fuel fired appliance is used When wood or charcoal is being used a minimum of one 2A portable fire extinguisher or an approved hose line shall be provided Mobile or temporary cooking operations shall be separated from buildings or structures, combustible materials, vehicle and other cooking operations by a minimum of 10 ft (3 m) Tents Mobile or temporary cooking shall not take place within tents occupied by the public Tents shall comply with NFPA Seating for the public shall not be located within any mobile or temporary cooking vehicle Mobile or temporary cooking operations shall not block fire department access roads, fire lanes, fire hydrants or other fire protection devices and equipment Communications. A method of communication to emergency personnel shall be accessible to all employees Training Prior to performing mobile or temporary cooking operations workers shall be trained in emergency response procedures including: (a) proper use of portable fire extinguishers and extinguishing systems (b) proper method of shutting off fuel sources

91 (c) proper procedure for notifying the local fire department (d) proper refueling, (e) how to perform leak detection (f) fuel properties Refresher training shall be provided every year Initial and refresher training shall be documented and made available to the AHJ upon request Internal Combustion Power Sources Electric generator and internal combustion power sources used for mobile or temporary cooking shall comply with this section Fueling. Fuel tanks shall be of adequate capacity to permit uninterrupted operation during normal operating hours. (1: ) Refueling. Refueling shall be conducted only when not in use. (1: ) Protection. Internal combustion power sources shall be isolated from contact with the public by either physical guards, fencing, or an enclosure. (1: ) Fueling from a container shall be permitted when the engine is shut down and engine surface temperature is below the autoignition temperature of the fuel Portable generators shall be positioned so that the exhaust is directed as follows: (1) At least 5 ft (1.5 m) in any direction away from any openings or air intakes and means of egress (2) Away from any building (3) Away from any mobile or temporary cooking vehicle or operation Where applicable, electrical appliances, fixtures, equipment or wiring shall comply with NFPA Charcoal/wood burning Mobile or temporary cooking operations that utilize wood or charcoals shall comply with NFPA 96 Section An approved carbon monoxide detector shall be installed where mobile cooking operations are performed in an enclosed area.

92 16.2 Mobile cooking Mobile cooking operations and equipment shall comply with NFPA 96, 16.1 and this section LP-Gas Systems Cylinders shall be secured in an upright position to prevent tipping over Gas systems on mobile cooking vehicles shall comply with NFPA 58 and this section Leak Detection Gas systems shall be inspected prior to each use by a worker trained in accordance with training Leak detection testing shall be documented and made available to AHJ upon request Where a gas detection system has been installed it shall be tested every month Leak detection shall be performed every time a new connection or a change in cylinder is made to any gas system LP-Gas Systems on Vehicles (Other Than Engine Fuel Systems) * Application. Section shall apply to the following: (1)Nonengine fuel systems on all vehicles (2)Installations served by exchangeable (removable) cylinder systems and by permanently mounted containers. (58:6.24.1) Nonapplication. Section shall not apply to the following: (1)Systems installed on mobile homes (2)Systems installed on recreational vehicles (3)Cargo tank vehicles, including trailers and semitrailers, and similar units used to transport LP-Gas as cargo, which are covered by Chapter 9 (4)LP-Gas engine fuel systems on the vehicles, which are covered by Chapter 11 of NFPA 58, (58:6.24.2) Container Installation Requirements Containers shall comply with (A) through (D). (A) ASME mobile containers shall be in accordance with one of the following: (1)A MAWP of 312 psig (2.2 MPag) or higher where installed in enclosed spaces of vehicles. (2)A MAWP of 312 psig (2.2 MPag) or higher where installed on passenger vehicles

93 (3)A MAWP of 250 psig (1.7 MPag) or higher for containers where installed on the exterior of nonpassenger vehicles (B) LP-Gas fuel containers used on passenger-carrying vehicles shall not exceed 200 gal (0.8 m3) aggregate water capacity. (C) The capacity of individual LP-Gas containers on highway vehicles shall be in accordance with Table (C). Table (C) Maximum Capacities of Individual LP-Gas Containers Installed on LP- Gas Highway Vehicles (D) Containers designed for stationary service only and not in compliance with the container appurtenance protection requirements of of NFPA 58 shall not be used. (58:6.24.3) ASME containers and cylinders utilized for the purposes covered by Section shall not be installed, transported, or stored (even temporarily) inside any vehicle covered by Section , except for ASME containers installed in accordance with (I), Chapter 9, or DOT regulations. (58: ) The LP-Gas supply system, including the containers, shall be installed either on the outside of the vehicle or in a recess or cabinet vaportight to the inside of the vehicle but accessible from and vented to the outside, with the vents located near the top and bottom of the enclosure and 3 ft (1 m) horizontally away from any opening into the vehicle below the level of the vents. (58: ) Containers shall be mounted securely on the vehicle or within the enclosing recess or cabinet. (A) Containers shall be installed with road clearance in accordance with of NFPA 58. (B) Fuel containers shall be mounted to prevent jarring loose and slipping or rotating, and the fastenings shall be designed and constructed to withstand, without permanent visible deformation, static loading in any direction equal to four times the weight of the container filled with fuel. (C) Where containers are mounted within a vehicle housing, the securing of the housing to the vehicle shall comply with this provision. Any removable portions of the housing or cabinet shall be secured while in transit. (D) Field welding on containers shall be limited to attachments to nonpressure parts such as saddle plates, wear plates, or brackets applied by the container manufacturer.

94 (E) All container valves, appurtenances, and connections shall be protected to prevent damage from accidental contact with stationary objects; from loose objects, stones, mud, or ice thrown up from the ground or floor; and from damage due to overturn or similar vehicular accident. (F) Permanently mounted ASME containers shall be located on the vehicle to provide the protection specified in (E). (G) Cylinders shall have permanent protection for cylinder valves and connections. (H) Where cylinders are located on the outside of a vehicle, weather protection shall be provided. (I) Containers mounted on the interior of passenger-carrying vehicles shall be installed in compliance with Section 11.9 of NFPA 58. Pressure relief valve installations for such containers shall comply with of NFPA 58. (58: ) Installation of Container Appurtenances Container appurtenances shall be installed in accordance with the following: (1)Pressure relief valve installation on ASME containers installed in the interior of vehicles complying with Section 11.9 of NFPA 58 shall comply with of NFPA 58. (2)Pressure relief valve installations on ASME containers installed on the outside of vehicles shall comply with of NFPA 58 and (3)Main shutoff valves on containers for liquid and vapor shall be readily accessible. (4)Cylinders shall be designed to be filled in either the vertical or horizontal position, or if they are the universal type, they are permitted to be filled in either position. (5)All container inlets, outlets, or valves installed in container inlets or outlets, except pressure relief devices and gauging devices, shall be labeled to designate whether they communicate with the vapor or liquid space. (6)Containers from which only vapor is to be withdrawn shall be installed and equipped with connections to minimize the possibility of the accidental withdrawal of liquid. (58: ) Regulators shall be installed in accordance with of NFPA 58 and (A) through (E). (A) Regulators shall be installed with the pressure relief vent opening pointing vertically downward to allow for drainage of moisture collected on the diaphragm of the regulator. (B) Regulators not installed in compartments shall be equipped with a durable cover designed to protect the regulator vent opening from sleet, snow, freezing rain,ice, mud, and wheel spray. (C) If vehicle-mounted regulators are installed at or below the floor level, they shall be installed in a compartment that provides protection against the weather and wheel spray. (D) Regulator compartments shall comply with the following: (1)The compartment shall be of sufficient size to allow tool operation for connection to and replacement of the regulator(s). (2)The compartment shall be vaportight to the interior of the vehicle. (3)The compartment shall have a 1 in.2 (650 mm2) minimum vent opening to the exterior located within 1 in. (25 mm) of the bottom of the compartment. (4)The compartment shall not contain flame or spark-producing equipment. (E) A regulator vent outlet shall be at least 2 in. (51 mm) above the compartment vent opening. (58: )

95 Piping Piping shall be installed in accordance with of NFPA 58 and (A) through (M). (A) Steel tubing shall have a minimum wall thickness of in. (1.2 mm). (B) A flexible connector shall be installed between the regulator outlet and the fixed piping system to protect against expansion, contraction, jarring, and vibration strains. (C) Flexibility shall be provided in the piping between a cylinder and the gas piping system or regulator. (D) Flexible connectors shall be installed in accordance with of NFPA 58. (E) Flexible connectors longer than the length allowed in the code, or fuel lines that incorporate hose, shall be used only where approved. (F) The fixed piping system shall be designed, installed, supported, and secured to minimize the possibility of damage due to vibration, strains, or wear and to preclude any loosening while in transit. (G) Piping shall be installed in a protected location. (H) Where piping is installed outside the vehicle, it shall be installed as follows: (1)Piping shall be under the vehicle and below any insulation or false bottom. (2)Fastening or other protection shall be installed to prevent damage due to vibration or abrasion. (3)At each point where piping passes through sheet metal or a structural member, a rubber grommet or equivalent protection shall be installed to prevent chafing. (I) Gas piping shall be installed to enter the vehicle through the floor directly beneath or adjacent to the appliance served. (J) If a branch line is installed, the tee connection shall be located in the main gas line under the floor and outside the vehicle. (K) Exposed parts of the fixed piping system either shall be of corrosion-resistant material or shall be coated or protected to minimize exterior corrosion. (L) Hydrostatic relief valves shall be installed in isolated sections of liquid piping as provided in Section 6.13 of NFPA 58.

96 (M) Piping systems, including hose, shall be pressure tested and proven free of leaks in accordance with Section 6.14 of NFPA 58. (58: ) There shall be no fuel connection between a tractor and trailer or other vehicle units. (58: ) Equipment Installation. Equipment shall be installed in accordance with Section 6.18 of NFPA 58, , and (58:6.24.6) Installation shall be made in accordance with the manufacturer's recommendations and, in the case of approved equipment, as provided in the approval. (58: ) Equipment installed on vehicles shall be protected against vehicular damage as provided for container appurtenances and connections in (E). (58: ) Appliance Installation on Vehicles Subsection shall apply to the installation of all appliances on vehicles. It shall not apply to engines. (58: ) All appliances covered by installed on vehicles shall be approved. (58: ) Where the device or appliance, such as a cargo heater or cooler, is designed to be in operation while the vehicle is in transit, means, such as an excess-flow valve, to stop the flow of gas in the event of a line break shall be installed. (58: ) Gas-fired heating appliances shall be equipped with shutoffs in accordance with (A) of NFPA 58, except for portable heaters used with cylinders having a maximum water capacity of 2.7 lb (1.2 kg), portable torches, melting pots, and tar kettles. (58: ) Gas-fired heating appliances, other than ranges and illuminating appliances installed on vehicles intended for human occupancy, shall be designed or installed to provide for a complete separation of the combustion system from the atmosphere inside the vehicle. (58: ) * Where unvented-type heaters that are designed to protect cargo are used on vehicles not intended for human occupancy, provisions shall be made to provide air from the outside for combustion and dispose of the products of combustion to the outside. (58: ) Appliances installed in the cargo space of a vehicle shall be readily accessible whether the vehicle is loaded or empty. (58: )

97 Appliances shall be constructed or otherwise protected to minimize possible damage or impaired operation due to cargo shifting or handling. (58: ) Appliances shall be located so that a fire at any appliance will not block egress of persons from the vehicle. (58: ) A permanent caution plate shall be affixed to either the appliance or the vehicle outside of any enclosure, shall be adjacent to the container(s), and shall include the following instructions: CAUTION: (1)Be sure all appliance valves are closed before opening container valve. (2)Connections at the appliances, regulators, and containers shall be checked periodically for leaks with soapy water or its equivalent. (3)Never use a match or flame to check for leaks. (4)Container valves shall be closed when equipment is not in use. (58: ) Gas-fired heating appliances and water heaters shall be equipped with automatic devices designed to shut off the flow of gas to the main burner and the pilot in the event the pilot flame is extinguished. (58: ) General Precautions Mobile units including mobile kitchens and catering vehicles that contain hot plates and other cooking equipment shall be provided with at least one approved portable fire extinguisher rated in accordance with NFPA 10, Standard for Portable Fire Extinguishers, at not less than 10-B:C. (58: ) Where fire extinguishers have more than one letter classification, they shall be considered as meeting the requirements of each letter class. (58: ) Parking, Servicing, and Repair Where vehicles with LP-Gas fuel systems used for purposes other than propulsion are parked, serviced, or repaired inside buildings, the requirements of through shall apply. (58: )

98 The fuel system shall be leak-free, and the container(s) shall not be filled beyond the limits specified in Chapter 7 of NFPA 58. (58: ) The container shutoff valve shall be closed, except that the container shutoff valve shall not be required to be closed when fuel is required for test or repair. (58: ) The vehicle shall not be parked near sources of heat, open flames, or similar sources of ignition, or near unventilated pits. (58: ) Vehicles having containers with water capacities larger than 300 gal (1.1 m3) shall comply with the requirements of Section 9.7 of NFPA 58. (58: ) * Containers shall be designed, fabricated, tested, and marked (or stamped) in accordance with the regulations of the U.S. Department of Transportation (DOT); the ASME Code, Section VIII, Rules for the Construction of Unfired Pressure Vessels ; or the API-ASME Code for Unfired Pressure Vessels for Petroleum Liquids and Gases, except for UG-125 through UG-136. (A) Used containers constructed to specifications of the Association of American Railroads shall not be installed. (B) Adherence to applicable ASME Code case interpretations and addenda that have been adopted and published by ASME 180 calendar days prior to the effective date of this code shall be considered as compliant with the ASME Code. (C) Where containers fabricated to earlier editions of regulations, rules, or codes listed in of NFPA 58, and of the Interstate Commerce Commission (ICC) Rules for Construction of Unfired Pressure Vessels, prior to April 1, 1967, are used, the requirements of Section 1.4 of NFPA 58 shall apply. (58: ) Containers that show excessive denting, bulging, gouging, or corrosion shall be removed from service. (58: ) Where a hose or swivel-type piping is used for liquid transfer, it shall be protected as follows: (1)An emergency shutoff valve shall be installed at the railroad tank car end of the hose or swivel-type piping where flow into or out of the railroad tank car is possible. (2)An emergency shutoff valve or a backflow check valve shall be installed on the railroad tank car end of the hose or swivel-type piping where flow is only into the railroad tank car. (3)*Where a facility hose is used at a LP-Gas bulk plant or industrial plant to transfer LP-Gas liquid from a cargo tank vehicle in non-metered service to a bulk plant or industrial plant, the facility hose or the facility shall be equipped with an emergency discharge control system that provides a means to shut down the flow of LP-Gas caused by the complete separation of the facility hose within 20 seconds and without the need for human intervention. (58: )

99 After installation or modification, piping systems (including hose) shall be proven free of leaks by performing a pressure test at not less than the normal operating pressure. (58: ) General Location of Cylinders Cylinders in storage shall be located to minimize exposure to excessive temperature rises, physical damage, or tampering. (58: ) Cylinders in storage having individual water capacity greater than 2.7 lb (1.1 kg) [nominal 1 lb (0.45 kg) LP-Gas capacity] shall be positioned so that the pressure relief valve is in direct communication with the vapor space of the cylinder. (58: ) Cylinders stored in buildings in accordance with Section 8.3 of NFPA 58 shall not be located near exits, near stairways, or in areas normally used, or intended to be used, for the safe egress of occupants. (58: ) If empty cylinders that have been in LP-Gas service are stored indoors, they shall be considered as full cylinders for the purposes of determining the maximum quantities of LP-Gas permitted by 8.3.1, , and of NFPA 58. (58: ) Cylinders shall not be stored on roofs. (58: ) Protection of Valves on Cylinders in Storage Cylinder valves shall be protected as required by and of NFPA 58. (58: ) Screw-on-type caps or collars shall be in place on all cylinders stored, regardless of whether they are full, partially full, or empty, and cylinder outlet valves shall be closed. (58: ) Valve outlets on cylinders less than 108 lb (49 kg) water capacity [nominal 45 lb (20 kg) propane capacity] shall be plugged, capped, or sealed in accordance with of NFPA 58. (58: ) Transportation of Cylinders Cylinders having an individual water capacity not exceeding 1000 lb (454 kg) [nominal 420 lb (191 kg) propane capacity], when filled with LP-Gas, shall be transported in accordance with the requirements of Section 9.3 of NFPA 58. (58: )

100 Cylinders shall be constructed as provided in Section 5.2 of NFPA 58 and equipped in accordance with Section 5.7 of NFPA 58 for transportation as cylinders. (58: ) The quantity of LP-Gas in cylinders shall be in accordance with Chapter 7 of NFPA 58. (58: ) Cylinder valves shall comply with the following: (1)Valves of cylinders shall be protected in accordance with of NFPA 58. (2)Screw-on-type protecting caps or collars shall be secured in place. (3)The provisions of of NFPA 58 shall apply. (58: ) The cargo space of the vehicle shall be isolated from the driver's compartment, the engine, and the engine's exhaust system. (A) Open-bodied vehicles shall be considered to be in compliance with this provision. (B) Closed-bodied vehicles having separate cargo, driver, and engine compartments shall be considered to be in compliance with this provision. (C) Closed-bodied vehicles, such as passenger cars, vans, and station wagons, shall not be used for transporting more than 215 lb (98 kg) water capacity [nominal 90 lb (41 kg) propane capacity], but not more than 108 lb (49 kg) water capacity [nominal 45 lb (20 kg) propane capacity] per cylinder, unless the driver and engine compartments are separated from the cargo space by a vaportight partition that contains no means of access to the cargo space. (58: ) Cylinders and their appurtenances shall be determined to be leak-free before being loaded into vehicles. (58: ) Cylinders shall be loaded into vehicles with flat floors or equipped with racks for holding cylinders. (58: ) Cylinders shall be fastened in position to minimize the possibility of movement, tipping, and physical damage. (58: ) Cylinders being transported by vehicles shall be positioned in accordance with Table (58: ) View Large

101 Vehicles transporting cylinders where the total weight is more than 1000 lb (454 kg), including the weight of the LP-Gas and the cylinders, shall be placarded as required by DOT regulations or state law. (58: ) 16.3 Temporary Cooking Temporary cooking operations and equipment shall comply with NFPA 96, 16.1 and this section Temporary cooking equipment and installations shall comply with NFPA Deep fat fryers, fry-o-laters, or other appliances having combustible liquids heated by LP Gas, solid fuels or electricity shall be protected by an approved hood fire suppression system, or other approved means of extinguishment in the event of fire.

102 Public Input No. 72-NFPA [ Chapter A ] Annex A Explanatory Material Annex A is not a part of the requirements of this NFPA document but is included for informational purposes only. This annex contains explanatory material, numbered to correspond with the applicable text paragraphs. 9 of 123 7/30/2015 1:48 PM

103 0 of 123 7/30/2015 1:48 PM A These requirements include, but are not limited to, all manner of cooking equipment, exhaust hoods, grease removal devices, exhaust ductwork, exhaust fans, dampers, fire-extinguishing equipment, and all other auxiliary or ancillary components or systems that are involved in the capture, containment, and control of grease-laden cooking effluent. A This judgment should take into account the type of cooking being performed, the items being cooked, and the frequency of cooking operations. Examples of operations that might not require compliance with this standard include the following: (1) Day care centers warming bottles and lunches (2) Therapy cooking facilities in health care occupancies (3) Churches and meeting operations that are not cooking meals that produce grease-laden vapors (4) Employee break rooms where food is warmed A This standard cannot provide safe design and operation if parts of it are not enforced or are arbitrarily deleted in any application.

104 A Approved. The National Fire Protection Association does not approve, inspect, or certify any installations, procedures, equipment, or materials; nor does it approve or evaluate testing laboratories. In determining the acceptability of installations, procedures, equipment, or materials, the authority having jurisdiction may base acceptance on compliance with NFPA or other appropriate standards. In the absence of such standards, said authority may require evidence of proper installation, procedure, or use. The authority having jurisdiction may also refer to the listings or labeling practices of an organization that is concerned with product evaluations and is thus in a position to determine compliance with appropriate standards for the current production of listed items. A Authority Having Jurisdiction (AHJ). The phrase authority having jurisdiction, or its acronym AHJ, is used in NFPA documents in a broad manner, since jurisdictions and approval agencies vary, as do their responsibilities. Where public safety is primary, the authority having jurisdiction may be a federal, state, local, or other regional department or individual such as a fire chief; fire marshal; chief of a fire prevention bureau, labor department, or health department; building official; electrical inspector; or others having statutory authority. For insurance purposes, an insurance inspection department, rating bureau, or other insurance company representative may be the authority having jurisdiction. In many circumstances, the property owner or his or her designated agent assumes the role of the authority having jurisdiction; at government installations, the commanding officer or departmental official may be the authority having jurisdiction. A Listed. The means for identifying listed equipment may vary for each organization concerned with product evaluation; some organizations do not recognize equipment as listed unless it is also labeled. The authority having jurisdiction should utilize the system employed by the listing organization to identify a listed product. A Appliance Flue Outlet. There might or might not be ductwork attached to the opening(s). A Certified. Certification can be provided by the manufacturer of the listed equipment being serviced or an independent third party. A Construction. See Figure A Figure A Examples of Open and Closed Combustible Construction. A Continuous Weld. Welding is a fabrication technique for joining metals by heating the materials to the point that they melt and flow together to form an uninterrupted surface of no less strength than the original materials. For the purpose of the definition, it specifically includes the exhaust compartment of hoods and welded joints of exhaust ducts yet specifically does not include filter support frames or appendages inside hoods. 1 of 123 7/30/2015 1:48 PM

105 A Solid Fuel Cooking Equipment. This equipment includes ovens, tandoori charcoal pots, grills, broilers, rotisseries, barbecue pits, and any other type of cooking equipment that derives all or part of its heat source from the burning of solid cooking fuel. A Grease Filter. Filters should limit the projection of flames after grease loading, in accordance with ANSI/UL 1046, Standard for Grease Filters for Exhaust Ducts, to a maximum of 457 mm (18 in.) downstream when attacked by flame on the upstream side. They are expected to maintain their strength, shape, and integrity when exposed to the anticipated rough handling, cleaning, and service found in the field. A Grease. Grease might be liberated and entrained with exhaust air or might be visible as a liquid or solid. A Hood. The term hoods as used in this document often refers to Type I hoods, meaning those applied to grease exhaust applications. They are built in various styles, for example, single- or double-island canopy, wall-mounted canopy, noncanopy, backshelf, high sidewall, eyebrow, and pass-over style. All such type and style hoods are applicable to this document, provided they meet all the material and performance requirements of this document. (See Figure A ) Figure A Styles of Hoods. The following are types of hoods: (1) Type I. Hoods designed for grease exhaust applications. (2) Type II. Hoods designed for heat and steam removal and other nongrease applications. These hoods are not applicable to the standard. 2 of 123 7/30/2015 1:48 PM

106 A Material. Materials subject to increase in combustibility or flame spread index beyond the limits herein established through the effects of age, moisture, or other atmospheric condition should be considered combustible. See Table A Table A Types of Construction Assemblies Containing Noncombustible, Limited-Combustible, and Combustible Materials Classifications for Determining Hood and Grease Duct Clearance* Type of Assembly Noncombustible Limited- Combustible Combustible Wall assemblies Brick, clay tile, or concrete masonry products Plaster, ceramic, or quarry tile on brick, clay tile, or concrete masonry products Plaster on metal lath on metal studs X X X Gypsum board on metal studs Solid gypsum board X X Plaster on wood or metal lath on wood studs Gypsum board on wood studs Plywood or other wood sheathing on wood or metal studs X X X Floor-ceiling or roof-ceiling assemblies Plaster applied directly to underside of concrete slab X Suspended membrane ceiling With noncombustible mineral wool acoustical material With combustible fibrous tile X X Gypsum board on steel joists beneath concrete slab X Gypsum board on wood joists X Notes: (1) Wall assembly descriptions assume same facing material on both sides of studs. (2) Categories are not changed by use of fire retardant treated wood products. (3) Categories are not changed by use of Type X gypsum board. (4) See definitions in of combustible material, limited-combustible material, and noncombustible material. *See clearance requirements in Section 4.2. Solid gypsum walls and partitions, 50.8 mm (2 in.) or mm (2 1 4 in.) thickness, are described in the Gypsum Association publication Fire Resistance Design Manual. A Noncombustible Material. Materials that are reported as passing ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C, should be considered noncombustible materials. A Trained. Formal and/or technical training can be administered by the employer or a recognized training program. 3 of 123 7/30/2015 1:48 PM

107 4 of 123 7/30/2015 1:48 PM A See ANSI/UL 710B, Standard for Recirculating Systems. A When solid fuel is burned in cooking operations, increased quantities of carbon, creosote, and grease-laden vapors are produced that rapidly contaminate surfaces, produce airborne sparks and embers, and are subject to significant flare-ups. Also, solid fuel cooking requires fuel storage and handling and produces ash that requires disposal. For these reasons, solid fuel cooking operations are required to comply with Chapter 14. A The authority having jurisdiction can exempt temporary facilities, such as a tent, upon evaluation for compliance to the applicable portions of this standard. Although it might not be practical to enforce all requirements of this standard in temporary facilities, the authority having jurisdiction should determine that all necessary provisions that affect the personal safety of the occupants are considered.

108 5 of 123 7/30/2015 1:48 PM A.4.2

109 6 of 123 7/30/2015 1:48 PM See Figure A.4.2(a) through Figure A.4.2(h) for clarification of the appropriate clearances required in Section 4.2. Figure A.4.2(a) Typical Section View for Building with Two Stories or More with Fire-Rated Floor- Ceiling Assembly. Figure A.4.2(b) Typical Section View for One-Story Building with Fire-Rated Roof-Ceiling Assembly. (Clearances given in Figure A.4.2(a) apply also to this drawing.) Figure A.4.2(c) Typical Section View for Building with Two Stories or More with Non-Fire-Rated Ceiling and Fire-Rated Floor. (Clearances given in Figure A.4.2(a) apply also to this drawing.)

110 7 of 123 7/30/2015 1:48 PM Figure A.4.2(d) Typical Section View for One-Story Building Without Fire-Rated Roof-Ceiling Assembly. Figure A.4.2(e) Detail Drawings Showing Hoods Penetrating Ceilings.

111 8 of 123 7/30/2015 1:48 PM Figure A.4.2(f) Wall-Mounted Fan.

112 9 of 123 7/30/2015 1:48 PM Figure A.4.2(g) Example of Clearance Reduction System: 229 mm (9 in.) Clearance to Combustible Material. Figure A.4.2(h) Example of Clearance Reduction System: 76 mm (3 in.) Clearance to Combustible Material.

113 00 of 123 7/30/2015 1:48 PM A The intent of this paragraph is to maintain the systems and their function in accordance with the requirements of the edition of NFPA 96 under which the systems were designed and installed. A Protection should be steel outer casing [minimum 0.46 mm (0.018 in.) thick] or equivalent. A The provisions of do not require inherently noncombustible materials to be tested in order to be classified as noncombustible materials. [5000: A ] A (1) Examples of such materials include steel, concrete, masonry and glass. [5000: A (1)]

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

NFPA 96, 2017 REVIEW SUMMARY

NFPA 96, 2017 REVIEW SUMMARY NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

Throughout standard remove references to the following and replace with the following:

Throughout standard remove references to the following and replace with the following: of 35 12/3/2015 7:13 AM Public Input No. 1-NFPA 90A-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/UL and replace with UL. (2) ANSI/ASHRAE

More information

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Second Revision No. 3-NFPA [ Section No. 2.3 ] Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document 1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two

More information

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input Public Input No. 4-NFPA 111-2016 [ Section No. 1.1.4.1 ] 1.1.4.1 * This standard shall not cover the following: (1) Application of the SEPSS (2) Distribution wiring (3) Systems having total outputs less

More information

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.

More information

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard

More information

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application. 1.3.1 This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

Second Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 6/23/ :34 AM

Second Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 6/23/ :34 AM of 56 6/23/2016 11:34 AM Second Revision No. 1-NFPA 96-2016 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 1-NFPA 36-2013 [ Global Input ] Revise the document to eliminate the use of "Exception" text. The use of "Exception" text is inconsistent with the Manual of Style. Exception text should

More information

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ] 8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.

More information

Remove the "Exception" text to be consistent with direction provided in the MOS.

Remove the Exception text to be consistent with direction provided in the MOS. of 37 1/11/2017 7:38 AM Public Input No. 9-NFPA 88A-2015 [ Global Input ] Remove the "Exception" text to be consistent with direction provided in the MOS. The current language in 88A has numerous section

More information

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM 1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling

More information

Public Input No. 3-NFPA [ Chapter 2 ]

Public Input No. 3-NFPA [ Chapter 2 ] Public Input No. 3-NFPA 655-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

12/21/2015 National Fire Protection Association Report

12/21/2015 National Fire Protection Association Report http://submittals.nfpa.org/terraviewweb/viewerpage.jsp?id=232 2012.ditamap&toc=false&draft=true 1/9 Public Comment No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents

More information

Jacqueline Wilmot Fire Protection Engineer NFPA. Road Map for Mobile Food Truck Regulation

Jacqueline Wilmot Fire Protection Engineer NFPA. Road Map for Mobile Food Truck Regulation Jacqueline Wilmot Fire Protection Engineer NFPA Road Map for Mobile Food Truck Regulation Mobile Food Trucks Mobile Food Trucks Mobile Food Trucks Mobile Food Trucks Mobile Food Trucks Hazards Multiple

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification Public Comment No. 2-NFPA 73-2014 [ Section No. 4.1.3 ] 4.1.3 Unused Openings. 4.1.3.1 Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or

More information

Public Input No. 48-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 48-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 62 8/4/17, 2:42 PM Public Input No. 48-NFPA 45-2017 [ Section No. 1.1.2 ] 1.1.2 This standard shall apply to all educational laboratory units and instructional laboratory units in which any quantity

More information

Public Comment No. 32-NFPA 90A-2016 [ Section No ] Statement of Problem and Substantiation for Public Comment

Public Comment No. 32-NFPA 90A-2016 [ Section No ] Statement of Problem and Substantiation for Public Comment of 53 11/9/2016 9:07 AM Public Comment No. 32-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 FREQUENTLY ASKED QUESTIONS CONCERNING COMMERCIAL COOKING PROTECTION Published by FIRE ENGINEERING DIVISION

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

Change all instances of flame resistant (hypobaric) to Limited-Combustible (material) in all instances in the document. 1 of 9 10/21/2015 1:22 PM First Revision No. 3-NFPA 99B-2015 [ Global Input ] Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

More information

"Spray area" is the term that is used throughout the document. This change is for consistency.

Spray area is the term that is used throughout the document. This change is for consistency. of 78 5/30/2014 2:08 PM Public Comment No. 39-NFPA 33-2013 [ Global Input ] For Chapter 18, replace "spray paint area" with "spray area". "Spray area" is the term that is used throughout the document.

More information

Public Comment No. 1-NFPA [ Section No ]

Public Comment No. 1-NFPA [ Section No ] Page 1 of 7 Public Comment No. 1-NFPA 556-2014 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA, 19428-2959. ASTM D2859, Standard

More information

First Revision No. 1-NFPA [ Chapter 2 ]

First Revision No. 1-NFPA [ Chapter 2 ] First Revision No. 1-NFPA 499-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this recommended practice

More information

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 496-2014 [ Section No. 5.2.2 ] 5.2.2 Where When the enclosure has been opened or if the protective gas supply has failed to maintain the required positive pressure, the enclosure

More information

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input of 201 1/13/2014 12:51 PM Public Input No. 88-NFPA 20-2013 [ New Section after 3.3.38.10 ] Add New Defination 3.3.28.11 Multiple Stage Multiple Port Pump. A single driver pump with multiple impellers operating

More information

Reference to the Smoke Damage Index (SDI) is needed as it is part of the test method.

Reference to the Smoke Damage Index (SDI) is needed as it is part of the test method. Public Input No. 4-NFPA 287-2014 [ Section No. 1.2.3.2 ] 1.2.3.2 Indices resulting from the test methods include critical heat flux (CHF), thermal response parameter (TRP), fire propagation index (FPI),

More information

Page 1 of 126 First Revision No. 113-NFPA 45-2013 [ Global Input ] Change all references to Material Safety Data Sheets (MSDS) to Safety Data Sheets (SDS) Submittal Date: Thu May 09 11:40:44 EDT 2013 Response

More information

Page 1 of 190 Public Input No. 22-NFPA 55-2013 [ Global Input ] Throughout the document, delete ANSI from ANSI/ASME B31.3. Current Text: (multiple locations) ANSI/ASME B31.3 (found in Subsections: 2.3.2

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

NFPA 101 SAF-RES PUBLIC COMMENTS

NFPA 101 SAF-RES PUBLIC COMMENTS Page 134 of 195 Public Comment No. 3-NFPA 101-2013 [ Section No. 28.7.6.1 ] 28.7.6.1 New draperies, curtains, and other similar loosely hanging furnishings and decorations shall be flame resistant as demonstrated

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document National Fire Protection Association Report of 113 http://submittals.nfpa.org/terraviewweb/contentfetcher?commentpara... 2/9/2016 10:50 AM Public Input No. 1-NFPA 87-2015 [ Global Input ] Throughout standard

More information

CHAPTER 5: EXHAUST SYSTEMS

CHAPTER 5: EXHAUST SYSTEMS MOTORS, FANS AND FILTERS 503.1 General. Motors and fans shall be sized to provide the required air movement. Motors in areas that contain flammable vapors or dusts shall be of a type approved for such

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

First Revision No. 1-NFPA 30A-2015 [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

First Revision No. 1-NFPA 30A-2015 [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement of 35 1/21/2016 7:56 AM First Revision No. 1-NFPA 30A-2015 [ Section No. 1.1.3 ] 1.1.3* This code shall not apply to those motor fuel dispensing facilities where only liquefied petroleum gas (LP-Gas),

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting.

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting. Input No. 7-NFPA 80-2013 [ Section No. 3.3.8 ] 3.3.8 Automatic Fire Detector. A device designed to detect the presence of a fire signature and to initiate action. For the purpose of this standard, automatic

More information

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input Public Input No. 2-NFPA 259-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D 5865, Standard Test Method

More information

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference Matthews, Diane Subject: Location: Start: End: Show Time As: Recurrence: Meeting Status: Organizer: Required Attendees: Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference http://nfpa.adobeconnect.com/rpbmeet/

More information

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ]

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ] of 71 6/11/2014 8:20 AM First Revision No. 36-NFPA 76-2014 [ Section No. 1.1 [Excluding any Sub-Sections] ] This standard provides requirements for fire protection of telecommunications facilities where

More information

First Revision No. 15-NFPA [ Chapter 2 ]

First Revision No. 15-NFPA [ Chapter 2 ] Page 1 of 28 First Revision No. 15-NFPA 91-2013 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

NFPA 37 Public Comment Responses Page 1 of 32

NFPA 37 Public Comment Responses Page 1 of 32 of 30 11/4/2016 3:05 PM Public Comment No. 6-NFPA 37-2016 [ New Section after 1.6 ] TITLE OF NEW CONTENT Type your content here... 1.7 Pressure Measurement. All pressures expressed in this document are

More information

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

Throughout standard remove references to the following and replace with the following:

Throughout standard remove references to the following and replace with the following: of 105 1/21/2016 7:49 AM Public Input No. 2-NFPA 30A-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/UL and replace with UL. (2) ANSI

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

JOINT CODE INTERPRETATION

JOINT CODE INTERPRETATION JOINT CODE INTERPRETATION May 2018 Mobile/Temporary Cooking Equipment 14-FCI-003 Page 1 of 8 PURPOSE The purpose of this interpretation is to assist owners/operators of mobile cooking operations and safety

More information

Chapter One Commercial Kitchen Fires

Chapter One Commercial Kitchen Fires Table of Contents Table of Contents Chapter One Commercial Kitchen Fires COMMERCIAL KITCHEN FIRES... 2 The Commercial Kitchen Fire Problem... 2 Unreported Fires... 2 Cooking By-Products... 3 Grease Accumulation

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information

Public Comment No. 16-NFPA 13D-2014 [ Section No ]

Public Comment No. 16-NFPA 13D-2014 [ Section No ] of 52 9/22/2014 9:20 AM Public Comment No. 16-NFPA 13D-2014 [ Section No. 2.3.3 ] 2.3.3 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

First Revision No. 20-NFPA [ Section No ]

First Revision No. 20-NFPA [ Section No ] of 25 7/15/2015 8:30 AM First Revision No. 20-NFPA 56-2015 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by NFPA

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Public Comment No. 2-NFPA 16-2013 [ Section No. 3.3.6 ] 3.3.6* Foam-Water Sprinkler System. A piping network connected to a source of foam concentrate and to a water supply. The piping network is equipped

More information

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS FIRE EXTINGUISHER REQUIREMENTS 1. All commercial cooking operations require at least one 2A10BC rated (5 or 6 pound size) fire extinguisher.

More information

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM of 66 5/18/2015 1:01 PM Second Revision No. 36-NFPA 32-2015 [ Detail ] 6.5 Solvents (See Annex C for additional information on solvents) Submittal Date: Tue Mar 17 17:20:03 EDT 2015 Committee Statement:

More information

Page 1 of 198 Public Input No. 88-NFPA 20-2013 [ New Section after 3.3.38.10 ] Add New Defination 3.3.28.11 Multiple Stage Multiple Port Pump. A single driver pump with multiple impellers operating in

More information

Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101

Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101 Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101 For the Florida Building Commission And the Fire Code Advisory Council Introduction The scope

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

Resolution: FR-1-NFPA Statement: When tests are conducted for fire reconstruction or research the items excluded above can be included.

Resolution: FR-1-NFPA Statement: When tests are conducted for fire reconstruction or research the items excluded above can be included. of 29 4/12/2016 9:32 AM Public Input No. 11-NFPA 289-2016 [ New Section after 1.1.5 ] 1.1.6 When tests are conducted for the purpose of forensic fire reconstruction or research, this test standard shall

More information

Second Revision No. 1 NFPA [ Chapter 2 ]

Second Revision No. 1 NFPA [ Chapter 2 ] Second Revision No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

Page 1 of 13 Second Revision No. 1-NFPA 326-2014 [ Section No. 2.3.1 ] 2.3.1 ACGIH Publications. American Conference of Governmental Industrial Hygienists, 1330 Kemper Meadow Drive, Cincinnati, OH 45240-1634.

More information

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments: Second Revision No. 3-NFPA 31-2015 [ Section No. 10.5.1 ] 10.5.1* Oil burners, other than oil stoves with integral tanks, shall be provided with some means for manually stopping the flow of oil to the

More information

Public Comment No. 7-NFPA 30A-2013 [ Section No ]

Public Comment No. 7-NFPA 30A-2013 [ Section No ] Page 1 of 13 Public Comment No. 7-NFPA 30A-2013 [ Section No. 6.4.2 ] 6.4.2 Additional Proposed Changes Each pump shall have installed on the discharge side a listed leak detection device that will provide

More information

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, 2014 9:00 AM - 5:00 PM EST Web/Teleconference Meeting 1. Welcome. George Seuss, Chair 2. Introductions and Update

More information

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

Public Input No. 23-NFPA [ Section No. 1.1 [Excluding any

Public Input No. 23-NFPA [ Section No. 1.1 [Excluding any of 222 1/26/2017 2:37 PM Public Input No. 23-NFPA 86-2016 [ Section No. 1.1 [Excluding any Sub-Sections] ] This standard shall apply to Class A, Class B, Class C, and Class D ovens, dryers, and furnaces;

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L )

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L ) NCEHSA Conference Carbon Monoxide Detector Regulations for Lodging Establishments (S.L. 2013-413) 1 Purpose of this session The purpose of this session is to review the provisions of Session Law 2013-413

More information

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement 1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by

More information

Are Your Kitchen Hood Filters Compliant?

Are Your Kitchen Hood Filters Compliant? Are Your Kitchen Hood Filters Compliant? Do your kitchen hood filters comply with the current Australian Standards for fire safety? Why Install Kitchen Exhaust Hood Filters? The purpose of a kitchen exhaust

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN) 4 of 326 11/21/2013 1:03 PM First Revision No. 161-NFPA 72-2013 [ Section No. 3.3.11 ] 3.3.11 Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

More information

CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES to 2003

CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES to 2003 CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES 2000 to 2003 The following pages contain comments regarding the changes to the 2000 edition of the UNIFORM MECHANICAL CODE (UMC ) that were made to

More information

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement First Revision No. 1-NFPA 259-2016 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D5865, Standard Test Method

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Industrial and Medical Gases

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Construction

More information

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS 1 Ventilation and Exhaust 2 Seminar Introduction Seminar addresses key concepts

More information

Public Comment No. 22-NFPA [ New Section after 1.4 ] Statement of Problem and Substantiation for Public Comment

Public Comment No. 22-NFPA [ New Section after 1.4 ] Statement of Problem and Substantiation for Public Comment of 25 5/14/2015 2:32 PM Public Comment No. 22-NFPA 14-2014 [ New Section after 1.4 ] A.1.4 A.1.4 It is the intent of the Commi ee to recognize that future edi ons of this standard are a further refinement

More information