Installation Instructions Model CDC-4

Size: px
Start display at page:

Download "Installation Instructions Model CDC-4"

Transcription

1 Installation Instructions CDC-4 Conventional Card INTRODUCTION The SIEMENS CDC is a card that allows conventional detectors to be used on the FireFinder-XLS system. It provides four Class or Class B conventional detection zones. Each zone can support two-wire photoelectric or ionization compatible smoke detectors, and an unlimited number of normally open circuit closure devices. The module also supports flame and beam detectors. The relay base, remote lamp and audible base may also be used with the CDC-4. The CDC uses one network address on the FireFinder-XLS system. The card has diagnostic LED indicators showing module status and the status of each zone. Z O N E 1 Z O N E 2 Z O N E 3 CDC-4 RESET POWER CRD FIL HNET FIL GND FULT ZONE STTUS LRM TROUBLE CLSS OPEN LRM TROUBLE CLSS OPEN LRM TROUBLE CLSS OPEN OPERTION ctivation of any device on the circuit initiates a zone alarm and causes any previously programmed functions to operate. ny circuit in an alarm or trouble condition is displayed on the PMI.. Z O N E 4 LRM TROUBLE CLSS OPEN The CDC-4 is designed to function in a local degrade mode during failure of the FireFInder-XLS main processor or during the loss of the system communication network. While in the degrade mode, the CDC-4 can report both alarm and trouble conditions and can activate local outputs on other modules within the same enclosure. The CDC-4 initiating device circuit is not intended to handle more than one detector in alarm per circuit HNET Do not use shorting devices on circuits with accessories on them. The shorting devices will lower the zone voltage to a point where the accessories will not operate. Figure 1 CDC-4 Conventional Card P/N Building Tec echnologies

2 ny or all of the CDC-4 circuits may be programmed to operate with larm Verification. This allows the automatic verification of alarm conditions caused by smoke detectors in order to prevent nuisance alarms. For further information, refer to the FireFinder-XLS Manual, P/N Controls and Indicators The front panel of the CDC-4 contains one reset switch, sixteen LEDs, and one HNET address switch as shown in Figure 1 reset switch is located on the top of the front panel. Pushing the reset switch reinitializes the CDC-4 operation (similar to a cold boot). The LEDs follow the reset switch and their functions are defined as follows: POWER (Green) Normally ON. When illuminated, indicates that power for the CDC-4 is applied to the card. CRD FIL (Yellow) Normally OFF. When illuminated, indicates that the card microprocessor has failed. HNET FIL (Yellow) Normally OFF. When illuminated, indicates that the HNET communication with the CDC-4 has terminated and the card goes into degrade mode (applicable only when card resides in the HNET network). GND FULT (Yellow) Normally OFF. When illuminated, indicates that the CDC-4 has detected either a negative or positive ground fault. ZONE 1 LRM (Red) Normally OFF. When illuminated indicates that an alarm condition has been detected in Zone 1. It will stay on continuously until the system is reset. ZONE 1 TROUBLE (Yellow) Normally OFF. When illuminated, indicates that a trouble condition has been detected in Zone 1. It will stay on continuously until the condition is cleared. ZONE 1 CLSS OPEN (Yellow) Normally OFF. When illuminated, indicates that there is a break in the Class wiring in Zone 1. ZONE 2 LRM (Red) Normally OFF. When illuminated indicates that an alarm condition has been detected in Zone 2. It will stay on continuously until the system is reset. ZONE 2 TROUBLE (Yellow) Normally OFF. When illuminated, indicates that a trouble condition has been detected in Zone 2. It will stay on continuously until the condition is cleared. Building Technologies 2 P/N

3 ZONE 2 CLSS OPEN (Yellow) Normally OFF. When illuminated, indicates that there is a break in the Class wiring in Zone 2. ZONE 3 LRM (Red) Normally OFF. When illuminated indicates that an alarm condition has been detected in Zone 3. It will stay on continuously until the system is reset. ZONE 3 TROUBLE (Yellow) Normally OFF. When illuminated, indicates that a trouble condition has been detected in Zone 3. It will stay on continuously until the condition is cleared. ZONE 3 CLSS OPEN (Yellow) Normally OFF. When illuminated, indicates that there is a break in the Class wiring in Zone 3. ZONE 4 LRM (Red) Normally OFF. When illuminated indicates that an alarm condition has been detected in Zone 4. It will stay on continuously until the system is reset. ZONE 4 TROUBLE (Yellow) Normally OFF. When illuminated, indicates that a trouble condition has been detected in Zone 4. It will stay on continuously until the condition is cleared. ZONE 4 CLSS OPEN (Yellow) Normally OFF. When illuminated, indicates that there is a break in the Class wiring in Zone 4. three-position switch at the bottom of the front panel is used to set the HNET network address of the CDC-4. PRE-INSTLLTION The network address switch must be set prior to inserting the card into the CC-5 (refer to Figure 1): Network ddress Switch: Set the three-digit HNET network address for the CDC-4 using the three-position switch located near the bottom of the front panel. (Refer to Figure 1 for the location of the switch.) The address for the CDC-4 must be the same as the address selected for it in the Zeus Programming Tool. To increment each digit of the address, press the button above the desired digit; to decrement each digit, press the - button below the desired digit. The range of allowable addresses is from 001 to 251 (leading zeros must be used). Building Technologies 3 P/N

4 WIRING Disconnect BTTERY and C prior to working on equipment. ll device field wiring to the CDC-4 is connected to the terminal blocks of the CC-5 card cage slot in which it is installed. To Connect the External Wiring: ZONE 1 ZONE 2 1. Lift the WHITE cover on the CC-5 terminal block. 2. Loosen the screw of the terminal by turning it counterclockwise. 3. Insert the wire into the side of the terminal block 4. Tighten the screw of the terminal block by turning it clockwise. Connect 24V from PSC-12 to terminal 17 and -24V from PSC-12 to terminal 18 of the slot in the CC-5 where the CDC will be installed using WG (Refer to Fig.2). LINE (OUT) LINE (RETURN) LINE- (RETURN) LINE- (OUT) LINE (OUT) LINE (RETURN) LINE- (RETURN) LINE- (OUT) LINE (OUT) LINE (RETURN) LINE- (RETURN) LINE- (OUT) LINE (OUT) LINE (RETURN) LINE- (RETURN) LINE- (OUT) NOTES: 1. ll circuits can be Class or Class B. 2. ll circuits are power limited per NEC ll circuits are supervised. 4. Refer to the UL Compatible Two-Wire List for the maximum number of detectors per zone. 5. Do not mix smoke detectors with the PB Max resistance: ohms/ circuit, ohms/circuit if accessories (relay/audible bases) are used. 7. Do not use shorting devices on circuits with accessories on them. 8. Only one device accessory per circuit is guaranteed to activate on the CDC Do not mix different model smoke detectors on the same zone, with the exception of models. LINE (OUT) Refer to Figure 3. ll circuits are power limited to NFP per NEC 7. Each detector or group of detectors must use a two-wire circuit of at least 18 WG, thermoplastic fixture wire, enclosed in conduit. If permitted by local building codes, 18 WG limited energy, shielded cable without conduit may also be used. LINE (RETURN) ZONE 1 CLSS EOL 50uF, 50V P/N LINE- (RETURN) LINE- (OUT) LINE Figure 3 CDC-4 Zones ZONE 2 CLSS B* * IN CND, MOUNT USING MODEL EL-33 EOL 50uF, 50V P/N NC NC LINE- LINE- 24V 24V ZONE 3 TO 24VDC FROM PSC-12 Figure 2 Wiring 24V Power Lines LINE ZONE 4 ONE SLOT OF CC-5 FOR CDC _ PB-1191 _ EOLR 4.7K, 1/4W P/N ZONE 3 ZONE _ B C D E F DO NOT USE EOL 50uF, 50V P/N Building Technologies 4 P/N

5 Total circuit resistance must not exceed ohms ohms if accessories (relay/ audible bases) are used. Each detector zone can be wired Class or Class B individually. The EOL capacitor (50uF, 50V) is used for ionization and photoelectric detectors and EOL resistor (4.7K) for beam detectors. The screw terminals can accommodate one WG or two WG. ll unused zones must be terminated with a 50uF capacitor (Terminals 1 and 4 for Zone 1, Terminals 5 and 8 for Zone 2, Terminals 9 and 12 for Zone 3, and Terminals 13 and 16 for Zone 4). When there is a beam detector on the zone, as shown in Figure 3, terminate with a 4.7K resistor. INSTLLTION The CDC-4 plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin DIN connectors and can occupy any slot in the card cage. (Refer to Figure 4.) Insert the CDC-4 card into the card guides rightside up (lettering on the front panel is legible). Slide the card in until the card edge connectors contact the receptacles on the motherboard. Verify that the DIN connectors of the card and the cardcage aligned properly. The card can only plug in one direction to the card cage, if it does not align, DO NOT FORCE the card. Place thumbs on the front panel adjacent to the captive screws and gently apply even pressure on the card until the connectors seat in the receptacles on the motherboard. Secure with the captive screws. Figure 4 Installing The CDC -4 Power up the system and verify that the CDC-4 power LED turns ON. INITITING DEVICES Refer to the UL Compatible Two-Wire List for the number of detectors that may be used on a CDC-4 zone. Refer to Figure 3 for initiating device wiring. ll circuits are power limited to NFP per NEC 7. Each detector or group of detectors must use a two-wire circuit of at least 18 WG, thermoplastic fixture wire, enclosed in conduit. If permitted by local building codes, 18 WG limited energy, shielded cable without conduit may also be used. Total circuit resistance must not exceed ohms ohms if accessories (relay/ audible bases) are used. For specific wiring and installation information, read the instructions provided with each device. Building Technologies 5 P/N

6 ELECTRICL RTINGS Initiating Circuits Voltage range Supervisory Current larm Current VDC 4m per zone max 175m per zone max Power Supplies 24V Back Plane Current 0 Screw Terminal 24V Current Supervisory larm 110m 8m per zone max 110m 3m per zone max 6.2V Back Plane Current 0m max 24V Standby Current Supervisory larm 0m 8m per zone max 0m 3m per zone max UL COMPTIBLE TWO-WIRE DETECTORS The detectors listed in the following tables are compatible with the CDC-4 (UL identifier CDC). The CDC-4 and all detectors shown below are ULC listed. Contact the manufacturer for listing information on models other than. Manufacturer UL UL DI-3 DI-3H DI-3 DI-3H DI-3 DI-3H DI-3 DI-3H DI-B3 DI-B3H DI-B3 DI-B3H D-3I D-3I DI-4 DI-4 DB-4TS DB-4TF DB-4TS DB-4TF DI-6 DI-6 DB-4TS DB-4TF DB-4TS DB-4TF DT-11 DT-11 w/dpt PB-1191 PB-1191 PBB-1191 PBB PE-3 PE-3T PE-3 PE-3T PE-3 PE-3T PE-3 PE-3T D-3ILP D-3ILP PE-11 PE-11 D-11P D-11PR D-11P D-11PR PE-11T PE-11T w/dpt DT-3P-135 DT-3P-135 Unlimite d Building Technologies 6 P/N

7 Manufacturer UL UL ir Products and Controls ir Products and Controls RW-2W-N RW-2W-P RW-2W-N RW-2W-P Manufacturer UL UL pollo to to pollo pollo pollo Manufacturer UL UL System Sensor (BRK) System Sensor (BRK) 20T 20IT 1 1 Building Technologies 7 P/N

8 Manufacturer UL UL DCD-135 NS4-2 NS6-2 DCD-135 DCD-190 NS4-2 NS6-2 DCD-190 SIH-24F HS-22D YB-M22 SIH-24F HSB SIH-24F HSC-224R HB-73 SIH-24F HS-224D YB-M224 SIJ-24 NS4-2 NS6-2 SIJ-24 SLK-24F SLK-24FH HS-22D YB-M22 SLK-24F SLK-24FH HS-224D YB-M224 SLK-24F SLK-24FH HSB SLK-24F SLK-24FL HSC-224R HB-73 SLK-24FL HSB-2 HSB-2N 0 SLR-24H SLR-24V NS4-2 NS6-2 SLR-24H SLR-24V SLR-835 SLR-835W SLR-835 SLR-835W NS4-2 NS6-2 SLR-835H SLR-835HW HD-5 SLR-835H SLR-835HW HD-5 NS4-2 NS6-2 NS6-2W Building Technologies 8 P/N

9 Manufacturer UL UL 4C 4CR S11 4CRT S11 4CT 425C 425CR S11 425CRT S11 425CT 429C CT B/BXT (w/sw1 OFF) CRXT S U 611UD 1U 1U 611UD 9U10 611UT UD 1U 1U 1U 612UD 9U10 613U5 1U Building Technologies 9 P/N

10 Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 CN P/N

Installation Instructions Model DLC

Installation Instructions Model DLC Installation Instructions Model DLC Device Loop Card INTRODUCTION OPERATION The SIEMENS Model DLC Device Loop Card is the interface for connection of FireFinder-XLS smoke detectors, manual stations, monitor

More information

Installation Instructions Model HZM

Installation Instructions Model HZM Installation Instructions Model Remote Conventional Zone Module INTRODUCTION The Model from is an intelligent device that connects a single zone of conventional devices to a DLC (FireFinder-XLS System)

More information

Installation Instructions Model SSD-C-REM

Installation Instructions Model SSD-C-REM Installation Instructions Model SSD-C-REM Remote System Status Display with Control ON ALARM SUPERVISORY SECURITY TROUBLE AUDIBLES SILENCED INTRODUCTION The SIEMENS Model SSD-C-REM is an optional FireFinder

More information

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION Fire Safety Installation Instructions Model SMB- Main Control Board OPERATION The SIEMENS Model SMB- board in each MXL-IQ System controls operations and monitors input device identity, network communication,

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

Fire Safety. Installation Instructions Model D2300CPS Fiber Optic Interface INTRODUCTION MOUNTING ELECTRICAL CONNECTIONS. Figure 1 D2300CPS Module

Fire Safety. Installation Instructions Model D2300CPS Fiber Optic Interface INTRODUCTION MOUNTING ELECTRICAL CONNECTIONS. Figure 1 D2300CPS Module Fire Safety Installation Instructions Model Fiber Optic Interface INTRODUCTION The Model from Siemens uilding Technologies, Inc. (See Figure 1) is a Fiber Optic interface for the MXL s RS-485 network (MNET

More information

Installation Instructions Model ABHW-4S

Installation Instructions Model ABHW-4S Installation Instructions Model ABHW-4S Intelligent Audible Base for Sleeping Area with 520Hz Low Frequency Sounder Introduction Application note The Model ABHW-4S audible base from Siemens Industry, Inc.

More information

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER Installation Instructions Model AD-HR Air Duct Monitoring Housing INTRODUCTION The SIEMENS Model AD-HR is a sampling tube, air duct monitoring housing. When used with a compatible smoke detector, smoke

More information

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11 Fire Safety Installation Instructions Model ADBX11 Audible Base INTRODUCTION Model ADBX11 The SIEMENS Model ADBX11 Audible Base consists of a standard Series 11 base combined with an audible device. All

More information

INSTALLATION MANUAL: IDC-6 INITIATING DEVICE CIRCUIT EXPANDER

INSTALLATION MANUAL: IDC-6 INITIATING DEVICE CIRCUIT EXPANDER NOTICE TO THE INSTALLER This manual provides an overview and the installation instructions for the IDC-6 module. All terminals are power limited and should be wired in accordance with the requirements

More information

Air Duct Housings. Description

Air Duct Housings. Description Air Duct Housings Series IL, and Series 3 Ionization or Photoelectric Detectors Optional Relays for Supplementary Equipment Operation Optional Control Module for Self-contained Operation (Series 3 Detectors

More information

Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation.

Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation. Fire Safety nstallation nstructions Model MMB- Main ontrol Board OPERATON The SEMENS Model MMB- board in each MXL System controls operations and monitors input device identity, network communication, and

More information

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Fire Safety Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

Fire Safety. Installation Instructions. Model RCC-2/R and RSE-1 Remote Control Centers OPERATION INTRODUCTION INSTALLATION

Fire Safety. Installation Instructions. Model RCC-2/R and RSE-1 Remote Control Centers OPERATION INTRODUCTION INSTALLATION Fire Safety Installation Instructions Model RCC-/R and RSE- Remote Control Centers INTRODUCTI The SIEMENS Model RCC-/R Remote Command Center (See Figure ) provides the option to remotely annunciate and

More information

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS MODEL XR5FC/XR5SL COMMAND PROCESSOR INSTALLATION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and, if not installed

More information

Intelligent Detection Devices

Intelligent Detection Devices Intelligent Detection Devices Multi-Criteria Fire Detector [with ASAtechnology TM ] Advanced multi-criteria fire detector that has dual-optical and thermal sensors Differentiates between deceptive phenomena

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS SXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 4 Zones Expandable to 8 Zones Microprocessor Based Control Factory Programmed Field Configurable 2 Style Y Notification

More information

Fireray Application and. Installation Guide FEATURES. Range metres. 12V to 24V dc operation. Selectable alarm thresholds

Fireray Application and. Installation Guide FEATURES. Range metres. 12V to 24V dc operation. Selectable alarm thresholds Fireray 2000 pplication and FETURES Installation Guide Range 10-100 metres 12V to 24V dc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or automatic reset

More information

Model OOHC941 ARCHITECT AND ENGINEER SPECIFICATIONS Advanced multi-criteria fire detector that has optical, thermal and CO sensors

Model OOHC941 ARCHITECT AND ENGINEER SPECIFICATIONS Advanced multi-criteria fire detector that has optical, thermal and CO sensors Intelligent Detection Devices Multi-Criteria Fire / CO Detector [with ASAtechnology TM ] ARCHITECT AND ENGINEER SPECIFICATIONS Advanced multi-criteria fire detector that has optical, thermal and CO sensors

More information

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE Fire Door Release MODEL AR-D2 MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D2 GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

Fire Alarm Control Panels

Fire Alarm Control Panels Fire Alarm Control Panels Device Compatability Guide LT-1007SUM Rev.2 Compatability Guide Table of Contents SFC-500 Series Compatible Addressable Devices (UL Listed)... 1 Analog/Addressable Devices...

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS MXL-IQ Advanced Life Safety System ENGINEER AND ARCHITECT SPECIFICATIONS FirePrint Application Specific Fire Detection Capacity for up to 240 Intelligent Analog Detectors Expandable Up to a Stand Alone

More information

Conventional Releasing Control Panel

Conventional Releasing Control Panel s Data Sheet Fire Safety Products Conventional Releasing Control Panel Pre-Action Deluge Agent-Releasing Fire System Model TXR-320 Remote configurable Up to two (2) hazard areas Operable with the following:

More information

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep. 140 58th St. Brooklyn, NY Power Supply/Chargers Installation Guide Models Include: eflow4n/eflow4nx - 4 amp @ 12VDC or 24VDC eflow4n8/eflow4nx8 eflow4n8d/eflow4nx8d - 4 amp @ 12VDC or 24VDC - 4 amp @ 12VDC

More information

MANUAL RESET ALARM RELEASE BOX

MANUAL RESET ALARM RELEASE BOX MANUAL RESET ALARM RELEASE BOX (For 100~240VAC or 24VAC or 24VDC) INSTRUCTION MANUAL WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

FIREFINDER-XLS CONTROL PANEL

FIREFINDER-XLS CONTROL PANEL FIREFINDER-XLS CONTROL PANEL Installation, Operation and Maintenance Manual P/N 315-033744-3 Siemens Building Tec echnologies Fire Safety CAUTION ALL WIRING MUST BE DONE AS DESCRIBED BELOW TO OBTAIN SAFE

More information

F220-B6PS/M. Installation Guide. Addressable Detector Bases

F220-B6PS/M. Installation Guide. Addressable Detector Bases F220-B6PS/M EN Installation Guide Addressable Detector Bases F220-B6PS/M Installation Guide 1.0 Overview 1.0 Overview These instructions cover the installation of the B6PS/M Addressable Detector Bases

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

Conventional Smoke Detectors KFAPO

Conventional Smoke Detectors KFAPO Kingfisher Company, inc. Conventional Smoke Detectors KFAPO Features: Wide operating voltage, 9-33 VDC Advanced electronic technology Flashing LED Magnetic test switch Proven detection performance Designed

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Harrington Signal HS-3100/3200 Fire Alarm Control Unit

Harrington Signal HS-3100/3200 Fire Alarm Control Unit HARRINGTON SIGNAL INC. FIRE ALARM Harrington Signal HS-3100/3200 Fire Alarm Control Unit Installation Manual Revision 2 January 2009 Document # LT-2000HAR Table of Contents 1.0 Technical Information...

More information

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS PXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 12 Zone System Expandable to 32 10 Amp Base Power Supply Multiple Power Supplies Available - Local or Remote 4 Notification

More information

P/N Product Manual. Conventional Fire Alarm/Suppression System

P/N Product Manual. Conventional Fire Alarm/Suppression System P/N 10-063 Product Manual Conventional Fire Alarm/Suppression System Manual P/N: 06-297 Rev. 4, 03/2010 FIKE World Headquarters 704 SW 10 th Street P.O. Box 610 Blue Springs, Missouri 64013 U.S.A. Phone:

More information

B. The fire alarm system shall be manufactured by an ISO 9001 certified company and meet the requirements of BS EN9001: ANSI/ASQC

B. The fire alarm system shall be manufactured by an ISO 9001 certified company and meet the requirements of BS EN9001: ANSI/ASQC SECTION 28 31 00 ~ FIRE LRM SYSTEM PRT 1 -GENERL 1.1 DESCRIPTION. This section includes the furnishing, installation, and connection of the fire alarm equipment required to form a complete coordinated

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

D285DH. Installation Instructions Photoelectric Duct Smoke Detector

D285DH. Installation Instructions Photoelectric Duct Smoke Detector D85DH EN Installation Instructions Photoelectric Duct Smoke Detector D85DH Installation Instructions.0 Introduction FCC Notice The D85DH Photoelectric Duct Smoke Detector complies with Part 5 of the Federal

More information

Multiplex Eight Input Remote Modules

Multiplex Eight Input Remote Modules Multiplex Eight Input Remote Modules 1.0 Introduction These instructions cover the installation of the D7042/D7042B Eight Input Remote Modules in a fire system supervised by an FPD-7024 Fire Alarm Control

More information

Fire Safety. Installation Instructions Model NIM-1W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION NIM-1W

Fire Safety. Installation Instructions Model NIM-1W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION NIM-1W Fire Safety Installation Instructions Model NIM-W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION The SIEMENS Model NIM-W provides a new communication path for the following uses:

More information

ALK-V PHOTOELECTRIC SMOKE SENSOR

ALK-V PHOTOELECTRIC SMOKE SENSOR ALK-V PHOTOELECTRIC SMOKE SENSOR APPLICATION The HOCHIKI America ALK-V Photoelectric Smoke Sensor is particularly suited to detecting optically dense smoke typical of fires involving materials such as

More information

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors Hinge Edge of Door Hinge Edge of Door Wiring Instructions for the Sargent 0 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL

More information

Reflective Optical Beam Smoke Detector User Guide

Reflective Optical Beam Smoke Detector User Guide Reflective Optical Beam Smoke Detector User Guide 1. Installation IMPORTANT NOTE: The infrared beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the system initiating

More information

FIREFINDER-XLS CONTROL PANEL

FIREFINDER-XLS CONTROL PANEL FIREFINDER-XLS CONTROL PANEL Installation, Operation and Maintenance Manual P/N 315-033744-4 Siemens Building Technologies Fire Safety CAUTION ALL WIRING MUST BE DONE AS DESCRIBED BELOW TO OBTAIN SAFE

More information

AL600ULX Series. Power Supply/Charger. Installation Guide

AL600ULX Series. Power Supply/Charger. Installation Guide AL600ULX Series Power Supply/Charger Installation Guide Models Include: AL600ULX - Single Output AL600ULPD4 AL600ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs AL600ULPD8 AL600ULPD8CB - Eight

More information

SC-6 Six Supervised Control Module

SC-6 Six Supervised Control Module INSTALLATION AND MAINTENANCE INSTRUCTIONS SC-6 Six Supervised Control Module SPECIFICATIONS Normal Operating Voltage: Stand-By Current: Alarm Current: Temperature Range: Humidity: Dimensions: Accessories:

More information

SIGA-CC1 Single Input Signal Module Installation Sheet

SIGA-CC1 Single Input Signal Module Installation Sheet SIGA-CC1 Single Input Signal Module Installation Sheet Personality codes Use the personality codes described below to configure the SIGA-CC1 module. See Table 1 for listing information Table 1: Personality

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 042010 Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

Print Specification. Publication. Instructions. Specific requirements. General requirements

Print Specification. Publication. Instructions. Specific requirements. General requirements Print Specification Publication GSA-CC1 Single Input Signal Module Installation Sheet P/N P-047550-1802-EN REV 04 ISS 23JUN15 Instructions This page is the print specification for the publication. It is

More information

XR10/XR20 Command Processor Panels Installation Guide

XR10/XR20 Command Processor Panels Installation Guide XR10/XR20 Command Processor Panels Installation Guide 10/26 Zone Burglary/Fire/Access Control Panels with Built-in Communicator LT-0229 (5/97) MODEL XR10/XR20 COMMAND PROCESSOR INSTALLATION GUIDE FCC NOTICE

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

Operating Instructions MXL Multi-Line Keyboard/Display Panel

Operating Instructions MXL Multi-Line Keyboard/Display Panel Operating Instructions MXL Multi-Line Keyboard/Display Panel Local Mode Operation TRODUCTION When the MXL Keyboard/Display Panel is installed in a control panel, the components are behind a locked door.

More information

Remote NAC Power Supply D7038

Remote NAC Power Supply D7038 Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE Fire Door Release MODEL AR-D MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev Altronix Corp. 140 58th St. Brooklyn, NY AL1042ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 052313 Agency Listings: UL Listed for Control Units for

More information

Installation Instructions Model MDACT MXL/FireFinder-XLS Multi-Point Digital Alarm Communicator

Installation Instructions Model MDACT MXL/FireFinder-XLS Multi-Point Digital Alarm Communicator Installation Instructions Model MDACT MXL/FireFinder-XLS Multi-Point Digital Alarm Communicator INTRODUCTION The Model MDACT from Siemens Industry, Inc. is a multipoint serial dialer for use in MXL and

More information

Desigo TM Fire Safety System A comprehensive fire-protection system

Desigo TM Fire Safety System A comprehensive fire-protection system s Desigo TM Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the 252- point and 504-point systems One (1) or (2)

More information

Series. Access Power Controllers. Installation Guide

Series. Access Power Controllers. Installation Guide Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

Advanced Protection System

Advanced Protection System MXL-IQ Advanced Protection System FirePrint Application Specific Detection Capacity for up to 240 Intelligent Analog Detectors Expandable Up to a Stand Alone System Capacity of 998 Input and Output Points

More information

INSTALLATION AND MAINTENANCE

INSTALLATION AND MAINTENANCE INSTALLATION AND MAINTENANCE DH100ACDCIA & DH100ACDCPA Air Duct Smoke Detector Before Installing ULC standard CAN/ULC-S524-M91 Standard For The Installation Of Fire Alarm Systems should be referenced for

More information

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X AL1042ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 071508X Agency Listings: UL Listed for Control Units for Fire Protective Signaling Systems (UL

More information

ARCHITECT AND ENGINEER SPECIFICATIONS

ARCHITECT AND ENGINEER SPECIFICATIONS s Data Sheet Fire Safety Products Intelligent Detection Devices Multi-Criteria Fire / CO Detector [with ASAtechnology TM ] ARCHITECT AND ENGINEER SPECIFICATIONS Advanced multi-criteria fire detector that

More information

D250A/D253/D261AW/D280A/D290 Series

D250A/D253/D261AW/D280A/D290 Series D0A/D/D6AW/D80A/D90 Series EN Installation Instructions / Smoke/Heat Detector Bases EN. D0A/D/D6AW/D80A/D90 Series Installation Instructions.0 Trademarks M Weatherban is a trademark of M. All rights reserved.

More information

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Fire Safety FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

These instructions detail procedures to follow in order to avoid damage to equipment.

These instructions detail procedures to follow in order to avoid damage to equipment. D326A, D334A, D339A Point Contact Modules Installation Guide 1.0 Notice These instructions are for the installation of the D326A, D334A and D339A Point Contact Modules in an analog system controlled by

More information

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL400ULM Multi-Output Access Control Power Supply Charger R AL400ULM - Multi-Output Access Control Power Supply/Charger Rev. 072500 Overview: The AL400ULM multi-output access control

More information

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs AL300ULX Series Power Supply/Charger Installation Guide Models Include: AL300ULX - Single Output AL300ULPD4 AL300ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs AL300ULPD8 AL300ULPD8CB - Eight

More information

Control Relay Modules

Control Relay Modules TM INTERNATIONAL ANALOG ADDRESSABLE INPUT/OUTPUT DEVICES Control Relay Modules Model SIGA-CR, SIGA-MCR, SIGA-CRR, Features! Provides one no/nc contact (SIGA-CR/MCR) Form C dry relay contact can be used

More information

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to installing and/or servicing this product. As with all releasing device

More information

Building Name: Our Lady of Sorrows Date: July 10, 2013

Building Name: Our Lady of Sorrows Date: July 10, 2013 1 E1. FIRE ALARM SYSTEM ANNUAL TEST AND INSPECTION REPORT (Reference: 5.1.2) Building Name: Our Lady of Sorrows Date: July 10, 2013 Address 19 Mohns Avenue Petawawa, ON System Manufacturer: Siemens Model

More information

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs AL400ULX Series Power Supply/Charger Installation Guide Models Include: AL400ULX - Single Output AL400ULPD4 AL400ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs AL400ULPD8 AL400ULPD8CB - Eight

More information

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone: Cookson Company 1901 South Litchfield Road Goodyear, AZ 85338 Phone: 800-294-4358 www.cooksondoor.com O W N E R S M A N U A L MODEL FIREFLY III EXTENDED PERFORMANCE RELEASE DEVICE TABLE OF CONTENTS INTRODUCTION

More information

ZNS MICROPROCESSOR BASED CONVENTIONAL FIRE ALARM CONTROL PANEL. Installation & Operation Manual

ZNS MICROPROCESSOR BASED CONVENTIONAL FIRE ALARM CONTROL PANEL. Installation & Operation Manual ZNS MICROPROCESSOR BASED CONVENTIONAL FIRE ALARM CONTROL PANEL Installation & Operation Manual The Gamewell Company 60 Pleasant Street Part No. 71774 Ashland, MA 01721 Issue 4 12/4/98 PROPRIETARY MATERIAL

More information

IDP-Zone-6 Six Zone Interface Module

IDP-Zone-6 Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS IDP-Zone-6 Six Zone Interface Module BEFORE INSTALLING If the modules will be installed in an existing operational system, inform the operator and local authority

More information

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector Wiring Instructions for the 900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR

More information

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

FX Intelligent Analog Fire Alarm Control Panel. Installation and Operation Manual

FX Intelligent Analog Fire Alarm Control Panel. Installation and Operation Manual Advanced Life Safety Solutions Advanced Life Safety Solutions FX-2000 Intelligent Analog Fire Alarm Control Panel Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 Fax: 905-660-4113 U.S.A.

More information

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE SAFE A N D SECURE Cornell 100 Elmwood Ave. Crestwood Industrial Park Mountaintop, PA 18707 Tel 800.233.8366 Fax 800.526.0841 Email: cornell@cornelliron.com O W N E R S M A N U A L M O D E L F I R E G A

More information

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X AL1002ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 071508X Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).

More information

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION Fike s CyberCat 254 (P/N 10-066) is a state-of-the-art true intelligent digital peer-to-peer modular fire alarm control system.

More information

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi (P/N 10-068) is a state-of-the-art true intelligent digital peer-topeer modular suppression control system. It is ideal for

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow6na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow102na8-10a @ 12VDC - Eight

More information

9822 Marine Fire and Detection Equipment. Cerberus PRO. Cerberus PRO. Marine Fire and Detection Equipment. Models FH-2071-UM, BP-62 and USCG-HPLATE

9822 Marine Fire and Detection Equipment. Cerberus PRO. Cerberus PRO. Marine Fire and Detection Equipment. Models FH-2071-UM, BP-62 and USCG-HPLATE Cerberus PRO Marine Fire and Detection Equipment s FH-2071-UM, BP-62 and USCG-HPLATE Cerberus PRO Fire Safety Products ARCHITECT AND ENGINEER SPECIFICATIONS Marine equipment is used with Cerberus PRO 252-point

More information

Remote Booster Power Supplies

Remote Booster Power Supplies Remote Booster Power Supplies XLS-BPS6, XLS-BPS60, XLS-BPS6C, XLS-BPS0, XLS-BPS00, XLS-BPS0C FEATURES SPECIFICATION DATA Extends power available to Notification Appliance Circuits (NACs). Available in

More information

Signature Series Component

Signature Series Component Signature Series Component Installation Manual P/N 7097 Rev.0 06DEC99 DEVELOPED BY COPYRIGHT NOTICE Edwards Systems Technology 6 Parkland Drive Sarasota, FL (9) 79-00 Copyright 997-99 Edwards Systems Technology

More information

Model 4880 Status Output Display Module Manual

Model 4880 Status Output Display Module Manual Model 4880 Status Output Display Module Manual 1-2 150912 Section 1 Introduction The 4880 provides 16 switched outputs, 4 form C relay contacts, and an X10 module interface. See Table 2-1 for electrical

More information

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector D700DH EN Installation Instructions Multiplex Photoelectric Duct Smoke Detector D700DH Installation Instructions.0 Description Notices These instructions cover the installation of the D700DH Multiplex

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS The SensorNet I/O Module provides attachment for up to 32 alarms and up to 16 switched devices. An RS-232 or RS-422 communications port is also provided for receiving serial alarms.

More information

I NSTALLATION M ANUAL

I NSTALLATION M ANUAL MR-2900 Fire Alarm Control Unit I NSTALLATION M ANUAL September 2009 Document #: LT-2010 Rev.2 WARNING : This manual contains information on limitations regarding product use and function and information

More information

D2E Duct Smoke Detector

D2E Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS D2E Duct Smoke Detector Specifications Operating Temperature: 20 to 60 C Storage Temperature: 20 to 60 C Humidity: 0% to 93% Relative Humidity Non-condensing Air

More information

PULL STATION SERIES DIE-CAST METAL MANUAL PULL STATIONS

PULL STATION SERIES DIE-CAST METAL MANUAL PULL STATIONS PULL STATION SERIES DIE-CAST METAL MANUAL PULL STATIONS UL and cul Listed, FM Approved, CSFM Listed, MEA Approved, ADA Compliant Single or Dual Action Terminal connectors 10 Amp Snap Action Switch Gold

More information

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA CONVENTIONAL FIRE ALARM CONTROL UNITS MR-2300 SERIES Fire Alarm Control Units Description Secutron s MR-2300 Series fire alarm control panels consist of six and twelve zone models which are equipped with

More information