Operating Manual. Gasgard 100 Control System. Order No.: /00. MSAsafety.com

Size: px
Start display at page:

Download "Operating Manual. Gasgard 100 Control System. Order No.: /00. MSAsafety.com"

Transcription

1 Operating Manual Gasgard 100 Control System Order No.: /00 MSAsafety.com

2 Warning! THIS MANUAL MT BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR ING OR SERVICING THE PRODUCT. Like any piece of complex equipment, this instrument will perform as designed only if it is used and serviced in accordance with the manufacturer s instructions. OTHERWISE, IT COULD FAIL TO PERFORM AS DESIGNED AND PERSONS WHO RELY ON THIS PRODUCT FOR THEIR SAFETY COULD STAIN SEVERE PERSONAL INJURY OR DEATH. The warranties made by Mine Safety Appliances Company with respect to the product are voided if the product is not used and serviced in accordance with the instructions in this manual. Please protect yourself and others by following them. We encourage our customers to write or call regarding this equipment prior to use or for any additional information relative to use or service. IN NORTH AMERICA: MSA-INST or FAX (724) IN CANADA: or FAX (416) MSA INTERNATIONAL: (724) MINE SAFETY APPLIANCES COMPANY All Rights Reserved This manual is available on the internet at MSA NORTH AMERICA 1000 Cranberry Woods Drive Cranberry Township, Pennsylvania 16066

3 Contents Contents 1. MSA Permanent Instrument Warranty Warranty Exclusive Remedy Exclusion of Consequential Damage Safety Regulations Warnings System Overview System Component Overview System Configuration Preconfigured Features System Operational Relay Horn Acknowledge and Latched Alarm Reset Option Sensor Fault Relay Setup Installation and Configuration Check List Specifications Appendix Gasgard 100 Control System 3

4 MSA Permanent Instrument Warranty 1. MSA Permanent Instrument Warranty 1.1. Warranty Seller warrants that this product will be free from mechanical defect or faulty workmanship for a period of 18 months from date of shipment, or one year from installation, whichever occurs first, provided it is maintained and used in accordance with Seller's instructions and/or recommendations. This warranty does not apply to expendable or consumable parts whose normal life expectancy is less than one year such as, but not limited to, nonrechargeable batteries, filament units, filter, lamps, fuses etc. The Seller shall be released from all obligations under this warranty in the event repairs or modifications are made by persons other than its own or authorized service personnel or if the warranty claim results from physical abuse or misuse of the product. No agent, employee or representative of the Seller has any authority to bind the Seller to any affirmation, representation or warranty concerning the goods sold under this contract. Seller makes no warranty concerning components or accessories not manufactured by the Seller, but will pass on to the Purchaser all warranties of manufacturers of such components. THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED, IMPLIED OR STATUTORY, AND IS STRICTLY LIMITED TO THE TERMS HEREOF. SELLER SPECIFICALLY DISCLAIMS ANY WARRANTY OF MERCHANT ABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE Exclusive Remedy It is expressly agreed that Purchaser's sole and exclusive remedy for breach of the above warranty, for any tortious conduct of Seller, or for any other cause of action, shall be the repair and/or replacement at Seller's option, of any equipment or parts thereof, which after examination by Seller is proven to be defective. Replacement equipment and/or parts will be provided at no cost to Purchaser, F.O.B. Seller's Plant. Failure of Seller to successfully repair any non-conforming product shall not cause the remedy established hereby to fail of its essential purpose Exclusion of Consequential Damage Purchaser specifically understands and agrees that under no circumstances will seller be liable to purchaser for economic, special, incidental or consequential damages or losses of any kind whatsoever, including but not limited to, loss of anticipated profits and any other loss caused by reason of nonoperation of the goods. This exclusion is applicable to claims for breach of warranty, tortious conduct or any other cause of action against seller. 4 Gasgard 100 Control System

5 Safety Regulations 2. Safety Regulations 2.1. Warnings The Controller described in this manual must be installed, operated and maintained in strict accordance with its labels, cautions, warnings, instructions, and within the limitations stated. Misuse can result in death or serious injury. If a portion of the system fails, remaining system functions may not operate properly. In this case, do not use the system until proper repairs are made. This device uses custom firmware developed by YOKOGAWA and is identified as S22 or S7 at the end of the main unit model code. Do not modify firmware. Doing so may render the device inoperable. S7 version of the MW100 is the only Class 1 Division 2 approved rack offered with the Gasgard 100 Control System. Failure to use the correct rack can result is death or serious injury. The Gasgard 100 Control System comes preconfigured with relay assignments for indication of a variety of faults, as outlined in the manual. Do not modify settings. Modifying these settings will compromise the unit s ability to notify the user of an inoperable system which can result in death or serious injury. Gasgard 100 Control System 5

6 System Overview 3. System Overview Thank you for purchasing the Gasgard 100 Control System. The Gasgard 100 Control System utilizes the MW100 Data acquisition system by YOKOGAWA. This manual covers useful information about the instruments functions, installation and wiring procedures and operating procedures that are specific to the Gasgard 100 Control System operation. The standard features of the MW100 Data acquisition system can be found in the YOKOGAWA User Manuals referenced below. Please visit the website of YOKOGAWA Corporation of America at to access all available MW100 manuals. The MW100 User Manual and Viewer Software User Manual are available on the MW100 CD that ships with the product. Manual Title Manual No. Description MW100 User Manual IM MW100-01E Describes information about the instrument s functions, installation and wiring procedures, operating procedures, and handling precautions. MW100 Data Acquisition Unit Operation Guide MW100 Communication Command Manual MW100 Connecting Ethernet and Checking the Connection Precautions on the Use of the MX100/MW100 MX100/MW100 Data Acquisition Unit Installation and Connection Guide IM MW100-02E IM MW100-17E IM MW100-71E IM MX100-71E IM MX100-72E Describes the handling of the MW100 Data Acquisition Unit and the basic operations of the MW100 Viewer Software. Describes the communication command of the MW100 main module. Explains the procedure to check the Ethernet connection. Summarizes the precautions regarding the use of the MW100 Data Acquisition Unit. Describes the installation procedures and wiring procedures of the MW100 Data Acquisition Unit. MW100 Viewer Software IM MW E Describes the functions and operations of the MW100 Viewer Software that comes standard with the MW100 main modules. The Gasgard 100 Control System is a fully integrated measurement and recording system with webenabled Ethernet connectivity for shared, real-time trend monitoring using a web browser. The Gasgard 100 Control System offers many advanced features, including the following: Communicate with both analog and Modbus field devices Interface with PLCs and other control devices through Modbus/TCP and Modbus/RTU Ethernet provides easy connection to allow modification to your system. Configure, save and view data remotely from a PC A highly flexible system architecture allowing one to configure a system with combinations of analog input, relays and analog outputs Create customized viewing screen on a PC by choosing bar graphs, digital read outs, trending analysis and more Delivers access for multiple users to monitor and share measured data by simply connecting the Gasgard 100 Control System simultaneously to multiple PCs 6 Gasgard 100 Control System

7 System Overview Create customized hourly, daily, weekly and monthly reports that can be saved to the system s compact flash (CF) media and automatically uploaded to an FTP server for further processing and review Built-in trigger function allows data recording to be started based on alarm values, time, external contact input or other parameters Data thinning function allows portions of measured data to be omitted at regular intervals during measurement, before data is recorded 3.1. System Component Overview The Gasgard 100 Control System consists of the YOKOGAWA MW100 data acquisition rack, a set of DIN rail mounted terminal blocks for custom wiring, an optional 240 W power supply for powering field devices, and an optional horn relay and alarm acknowledge kit. The Gasgard 100 Control System is offered in two sizes: a system with expansion capabilities to a total of six (6) I/O modules and a system with up to three (3) I/O modules. The following YOKOGAWA MW100 content is offered with the Gasgard 100 Control System. Main Module The main module is equipped with power supply connectors, Ethernet ports, and other devices facilitating supply of power to and control of the input/output modules, and connection to networks. Data acquisition via serial communication is also possible through use of the RS-422A/485 serial communication function. I/O Modules The following three modules are available with the Gasgard 100 Control System. YOKOGAWA offers ten additional I/O modules that are not supported by MSA. Contact YOKOGAWA for more information on these modules. 10-CH, Medium-Speed Universal Input Module (MX110-UNV-M10) 8-CH, Medium-Speed Analog Output Module (MX120-VAO-M08) 10-CH, Medium-Speed Digital Output Module (MX125-MKC-M10) Base Plate The base plate is equipped with connectors for connecting the main module and input/output modules. Two different base plates are available to hold from one to six input/output modules. The offering is a six I/O module plate for the large system and a 3 I/O plate for the small system. By attaching the DIN rail mounting brackets that came with the product to the base plate, you can rack-mount or panel-mount the Gasgard 100 Control System main unit. Gasgard 100 Control System 7

8 System Overview PC Software The Gasgard 100 Control System comes with the Viewer software program that allows users to view measured data acquired by the Gasgard 100 Control System. The Viewer consists of the two software components described below. MW 100 IP Config Software Sets the IP address on the Gasgard 100 Control System. This software is used when setting an IP address for the first time, or if the current IP address needs to be changed. The default IP address is set to at the factory. MW 100 Viewer Enables you to (1) display measured, computed, and thinning data that has been stored, (2) read values and perform computation over an area using cursors, and (3) convert the measured and computed data into various formats such as Excel. Gasgard 100 Control System Reference Guides The following references are available to support Gasgard 100 Control System installation and configuration. Quick-Start Map Available on our website: Videos Configuration videos are available on MSA TV (msatv.msasafety.com) or through AR codes on the quickstart map. Videos cover topics including configurations of inputs, alarms and relays, among others. Installation Outline Drawing Available on our website: The I/O drawing covers all installation and wiring details. 8 Gasgard 100 Control System

9 System Configuration 4. System Configuration The Gasgard 100 Control System is a highly configurable system. System configuration is facilitated through the use of the on-board Ethernet connection. To access the Gasgard 100 Control System viewing and configuration screens, perform the following: (1) Attach the Gasgard 100 Control System to your PC through the use of a cross over cable or to your network. (2) The Gasgard 100 Control System comes preconfigured with an IP address of If another IP address is to be used, run the IP configuration tool found on the MW100 CD that comes with the product. Details on how to use this tool can be found in the YOKOGAWA User Manual or by watching the Gasgard 100 Control System configuration videos found on Step Configuration Descriptions Reference Materials 1 Installation and Wiring YOKOGAWA User s Manual Chapter 2 Installation and Wiring I/O Drawing SK Configuring the Network Connection YOKOGAWA User s Manual Chapter 2 Connecting the Ethernet Cable YOKOGAWA User s Manual Chapter 3 Communication Settings 3 Initial Setup YOKOGAWA User s Manual Chapter 3 System Settings 4 Setting Up an Analog Input YOKOGAWA User s Manual Chapter 1 Functions of the 10-CH, Medium Speed Universal Input Module YOKOGAWA User s Manual Chapter 3 Setting Measurement Conditions Appendix, Scaling Values for Range and Alarm Levels for instructions 5 Configuring Alarms YOKOGAWA User s Manual Chapter 1 Alarms YOKOGAWA User s Manual Chapter 3 Setting Alarms Appendix, Scaling Values for Range and Alarm Levels for instructions 6 Configuring the Relay Settings YOKOGAWA User s Manual Chapter 1 Functions of the 10-CH, Medium Speed Digital Output Module YOKOGAWA User s Manual Chapter 3 Digital Output Settings 7 Configuring Analog Output Settings YOKOGAWA User s Manual Chapter 1 Functions of the 8-CH, Medium Speed Analog Output Module YOKOGAWA User s Manual Chapter 3 Analog/PWM Output Settings Gasgard 100 Control System 9

10 System Configuration Step Configuration Descriptions 8 Configuring Modbus Master Settings Reference Materials YOKOGAWA User s Manual Chapter 3 Communication Settings 9 Configuring the Display Screens YOKOGAWA User s Manual Chapter 3 Measured Data Monitor Display/Settings 10 Configuring Acknowledge and Horn Silence Feature YOKOGAWA User s Manual Chapter 4 Troubleshooting and Maintenance 11 Troubleshooting YOKOGAWA User s Manual Chapter 4 Troubleshooting and Maintenance 10 Gasgard 100 Control System

11 Preconfigured Features 5. Preconfigured Features The system is preconfigured to facilitate indication of faults as well as to activate the optional horn and alarm acknowledge feature. These configurations set by the factory for these features are outlined below System Operational Relay For proper system fault notification, the factory has configured multiple relays to supply notification of various system faults to an on-board PLC. This PLC then provides a common, normally closed system fault dry contact. Review the I/O Drawing for customer wiring point. The configuration of these relays was accomplished by setting the items listed below. The relays configured in this example are relays # (6 position rack). For a three position rack, these are replaced with Warning! Do not modify any of the listed settings listed below. Modifying these settings will compromise the unit s ability to notify the user of an inoperable system which can result in death or serious injury. System Setting -> Timer Setting Fig. 1 Timer Setting Gasgard 100 Control System 11

12 Preconfigured Features System Setting -> Event Action Setting Fig. 2 Event Action Setting Channel Setting -> Math Channel Setting Fig. 3 Math Channel Setting 12 Gasgard 100 Control System

13 Preconfigured Features Channel Setting -> DO Channel Setting Fig. 4 DO Channel Setting Gasgard 100 Control System 13

14 Preconfigured Features Channel Setting -> Alarm Setting (MATH) Fig. 5 Alarm Setting (MATH) 14 Gasgard 100 Control System

15 Preconfigured Features 5.2. Horn Acknowledge and Latched Alarm Reset Option The factory has configured the settings listed below for proper operation of the Horn Acknowledge and latched alarm reset options. When this option is purchased, the factory will mount and connect two pushbuttons to perform these operations. The horn will be controlled by system relay 056 (026 on a three position rack). The user must configure alarm levels to control this relay for the horn to activate. The Latched Alarm reset button is connected and configured to operate on input 001. Warning! The user must configure alarms to control the appropriate relay for proper horn operation. Do not modify any of the highlighted settings listed below. Modifying these settings will compromise the functionality of the horn relay and latched relay reset feature. Channel Setting -> AI/DI Channel Setting Fig. 6 AI/DI Channel Setting Gasgard 100 Control System 15

16 Preconfigured Features System Setting -> Event Action Setting Fig. 7 Event Action Setting Channel Setting -> DO Channel Setting Fig. 8 DO Channel Setting 16 Gasgard 100 Control System

17 Preconfigured Features 5.3. Sensor Fault Relay Setup An alarm level must be configured for each sensor attached to the system to determine if that sensor is in a fault condition. These alarm levels must be configured for relay 057 (027 on a three position rack) which has been allocated as the sensor fault relay. The Alarm type should be L for Low alarm, the alarm will trip when the reading drops below the assigned value. The sensor fault alarm value depends upon the full scale sensor range and milliamp level of the alarm. To configure this alarm, refer to the table in Appendix to find the appropriate value to set the alarm level. Channel Setting -> Alarm Setting (AI/DI) or Channel Setting Alarm Setting (MATH) Fig. 9 Alarm Setting (AI/DI) or Channel Setting Alarm Setting (Math) Warning! The user must configure alarms to control the appropriate relay for proper sensor fault detection. Failure to properly configure and monitor the sensor fault relay can compromise the unit s ability to notify the user of an inoperable sensor which can result in death or serious injury. Gasgard 100 Control System 17

18 Installation and Configuration Check List 6. Installation and Configuration Check List Ensure that all wiring connections were made in accordance with all applicable code. Reference the installation outline drawing and wiring label located on the inside door of the device for details. It is a best practice to perform a system level test of your gas detection system once all field transmitters and output devices such as strobes and horns are wired and operating. This check should be performed after all configuration of the Gasgard 100 controller has been completed. The following is a suggested test procedure for ensuring proper operation of your gas detection system. (1) Apply test gas to each field sensor. Verify that outputs such as LEDs, relays and milli-amp signal function correctly. (2) Check channel reading for the transmitter receiving gas. Ensure the reading is accurate. (3) Check the alarm status of the Gasgard 100 Control System. Verify that the correct channel alarms activate. (4) Check that the Gasgard 100 Control System relays are appropriately assigned. Verify that the relays activate when the associated alarm is enabled Make any necessary configuration and/or wiring adjustments to ensure your system is operating as intended. 18 Gasgard 100 Control System

19 Specifications 7. Specifications Power Supply Operating Temperature W/O internal 240 W Power Supply Option 12 to 28 VDC W/ internal 240 W Power Supply Option 100 to 240 VAC 50/60 Hz Rack -20 C to 50 C (-4 F to 122 F) Enclosure -20 C to 45 C (-4 F to 113 F) 24 x 24 Fiberglass enclosure (accepts up to 6 I/O), no internal power supply. -20 C to 35 C (-4 F to 95 F) 24 x 24 Fiberglass enclosure (accepts up to 6 I/O), with a 240 W Internal power supply. Types of Measurement Connection Modes Terminal Connections Relay Contact Ratings Enclosure Dimensions Ingress Protection Approvals (Rack Only) -20 C to 45 C (-4 F to 113 F) 16 x 20 small enclosure (accepts up to 3 I/O), no internal power supply. ma (standard), DC Voltage, DI (non-voltage contact), level (5 V logic) 2 wire or 3 wire, ma; RS485 (Modbus) Max 2.5 m² (12 AWG) stranded wire Configurable Rack Relays SPST (Form A), Normally Energized/De-energized 250 VDC/0.1 A, 250 VAC/2 A, or 30 VDC/2 A (resistance load) Horn Relay SPST (Form A), Normally De-energized 240 VAC/5 A, or 24 VDC/5 A System Fault Relay SPST (Form A), Normally Energized 240 VAC/4 A, or 24 VDC/2 A 24.6" L x 24,1" W x 9.0" D (accepts up to 6 I/O) or 20.2" L x 16.2" W x 9.0" D (accepts up to 3 I/O) Supplied with NEMA 4X Components CSA: CSA22.2 No , overvoltage category II, measurement category II, pollution degree 2 UL: Conforms to UL61010B-1 (CSA NRTL/C) CE: EMC directive; EN61326 Class A; EN ; EN Low voltage directive; EN ; overvoltage category II, measurement category II, pollution degree 2 FM: Class I Division 2 Groups A, B, C, D For additional, module specific specifications please see YOKOGAWA User Manual Chapter 5. Gasgard 100 Control System 19

20 Appendix 8. Appendix Full Scale Range Lower Scale Upper Scale Scaled Fault Alarm Level based on ma Fault Level Designated by Gas Transmitter (Fault Levels are 10 % high to account for any meaurement errors) ma Volts Gasgard 100 Control System

21 Appendix Defining a fault condition for a channel in the Gasgard 100 Control System unit requires extending the measurement range beyond the normal measurement range. For example the measurement range of the transmitter output is 4 to 20 ma. Most fault conditions are transmitted as milliamp values between the range of 0 to 4 ma. The 4 to 20 ma range can be related to more meaningful engineering units; for example: 0 to 100 % LEL or 0 to 25 % O 2. The alarm setpoints on the Gasgard 100 Control System unit are configured using engineering units; for example, to alarm at 8 ma on a 0 to 100 % LEL output sensor, the alarm is set to a value of 25 % LEL. Setting fault alarms is done in a similar manner. The fullscale range of the channel in the Gasgard 100 Control System unit is set to appropriate engineering units as shown in the Table above. The lower scale takes into account the extension of the engineering units beyond the measurement range of 4 to 20 ma to the full milliamp range of 0 to 20. To set the fault alarm value, find the intersecting value in the Table above after selecting your fullscale (FS) engineering unit range and milliamp fault value sent by the transmitter. For example, on a transmitter with a milliamp output of 0 to 20 ma, engineering units of 0 to 100 % LEL and fault level of 3 ma, the Gasgard 100 Control System is configured as follows: Lower scale: -25 Upper scale: 100 Fault alarm value: Gasgard 100 Control System 21

22 MSA in the World For local MSA contacts please go to our web site MSAsafety.com

GasGard 100 Control System

GasGard 100 Control System GasGard 100 Control System Because every life has a purpose... MSA Providing Fixed Gas and Flame Detection Solutions. It is critical for plant managers and personnel to have a proactive and diagnostic

More information

Remote Relay Module (RRM)

Remote Relay Module (RRM) Remote Relay Module (RRM) Instruction Manual WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like

More information

Instruction Manual WARNING

Instruction Manual WARNING Controllers Instruction Manual WARNING THIS MANAUL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like any piece of

More information

Controllers. Instruction Manual WARNING

Controllers. Instruction Manual WARNING Controllers Instruction Manual WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like any piece of

More information

Beacon 800 Gas Monitor Operator s Manual

Beacon 800 Gas Monitor Operator s Manual Beacon 800 Gas Monitor Operator s Manual Part Number: 71-0037RK Revision: F Released: 4/18/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be

More information

IT COULD FAIL TO PERFORM AS DESIGNED AND PERSONS WHO RELY ON THIS PRODUCT FOR THEIR SAFETY COULD SUSTAIN SEVERE PERSONAL INJURY OR DEATH.

IT COULD FAIL TO PERFORM AS DESIGNED AND PERSONS WHO RELY ON THIS PRODUCT FOR THEIR SAFETY COULD SUSTAIN SEVERE PERSONAL INJURY OR DEATH. Chillgard LC Control Module Instruction Manual "! WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING, MAINTAINING OR SERVICING

More information

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL. Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH AND LOW LEVEL ALARM 2.2 PUMP DOWN CONTROLLER 2.3

More information

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08 GasScanner 4C Four Channel Monitor Operator s Manual MINT-0280-XX Rev. A 02/25/08 Product Warranty Matheson Tri-Gas., warrants gas alarm equipment sold by us to be free from defects in materials, workmanship,

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector CAUTION & SYMBOL DEFINITIONS: CAUTION: Gives detailed description of different situations to avoid or not avoid for the proper operation of the

More information

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL GASGUARDIAN 2 3 2-Channel Controller OPERATING & INSTALLATION MANUAL GasGuardian 2 3 Operating and Installation Manual Table of Contents General description.... 3 Installation. 3 Locating the GasGuardian-2..

More information

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL Installation and Operation Manual 2 GG-2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm Ion Endeavor Controller Digital Level Control with Alternation Page 1 of 8 General Overview The Ion Endeavor is a pump controller that senses a water level of up to 72", has a configurable water level/pump

More information

Beacon 410A Gas Monitor Operator s Manual

Beacon 410A Gas Monitor Operator s Manual Beacon 410A Gas Monitor Operator s Manual Part Number: 71-0397 Revision: F Released: 12/5/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be

More information

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08 GasScanner 8C Eight Channel Monitor Operator s Manual MINT-0281-XX Rev. A 01/29/08 Product Warranty Matheson Tri-Gas, Inc., warrants gas alarm equipment sold by us to be free from defects in materials,

More information

PodView Level Indicator LI40 Series Manual

PodView Level Indicator LI40 Series Manual PodView Level Indicator LI40 Series Manual Flowline Inc. 10500 Humbolt Street Los Alamitos, CA 90720 Tel: (562) 598 3015 Fax: (562) 431 8507 www.flowline.com Rev A MN204260 1 of 16 INTRODUCTION / TABLE

More information

THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR USING, MAINTAINING OR SERVICING THIS PRODUCT.

THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR USING, MAINTAINING OR SERVICING THIS PRODUCT. Chillgard RT Instruction Manual "! WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR USING, MAINTAINING OR SERVICING THIS PRODUCT. Like any piece

More information

RAM3 Remote Alarm Module

RAM3 Remote Alarm Module RAM3 Remote Alarm Module INSTRUCTIONS Installation and Operation of the AMC-RAM3 with AMC Monitors IMPORTANT: Please read this installation and operating instructions completely and carefully before starting.

More information

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12 PAGE 1 OF 12 TABLE OF CONTENTS PAGE 1. SAFETY PRECAUTIONS 1.1. Electrical shock 3 2. APPLICATION 3 3. INSTALLATION 3.1. Mount indoor alarm display 3.2. Mount the outdoor junction box 3.3. Install interconnecting

More information

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual Read and understand this material before operating or servicing these heating tapes. Failure to understand

More information

Model 9010 and 9020 Monitoring Systems

Model 9010 and 9020 Monitoring Systems Model 9010 and 9020 Monitoring Systems Instruction Manual "! WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR USING OR SERVICING THE PRODUCT. Like

More information

ion Genesis Pump Controller

ion Genesis Pump Controller High Water Alarm Document No.: IONG_OM Page 1 of 7 Table of Contents Safety Precautions.......................... 1 General Overview.......................... 1 Installation.................................2

More information

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

GG-EM ENTRANCE MONITOR. Installation and Operation Manual GG-EM ENTRANCE MONITOR Installation and Operation Manual 2 GG-EM Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information

Beacon 110 Gas Monitor Operator s Manual

Beacon 110 Gas Monitor Operator s Manual Beacon 110 Gas Monitor Operator s Manual Part Number: 71-0110RK Revision: H Released: 12/5/17 RKI Instruments, Inc. www.rkiinstruments.com Product Warranty RKI Instruments, Inc., warrants gas alarm equipment

More information

Installation and Operations Manual

Installation and Operations Manual Installation and Operations Manual H-IM-LLC February 2018 Part No. 25092501 Replaces H-IM-LLC (01/2014) Lead Lag Control System Table of Contents General Safety Information 2 Inspection 2 Warranty Statement

More information

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm Page 1 of 8 General Overview Thank you for purchasing an Ion Genesis controller. Take the time to read the instructions carefully before using this appliance. We strongly recommend that you keep this instruction

More information

Module de relais Relay Module. Manuel de l utilisateur 301RW. User Manual ERP /07

Module de relais Relay Module. Manuel de l utilisateur 301RW. User Manual ERP /07 Module de relais Relay Module Manuel de l utilisateur 301RW User Manual ERP 511397 02/07 Relay Module 301R User Manual ERP 511397 2/07 Notices and Trademarks Copyright by Honeywell International Inc.

More information

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products: Model 2102 Gas Alarm Panel APPLICABILITY & EFFECTIVITY This manual provides instructions for the following Sierra Monitor products: Model Description 2102-00 Alarm Panel 2 Channel 2102-01 Alarm Panel 2

More information

HotPoly Tote Tank / IBC Heaters (TTH Series)

HotPoly Tote Tank / IBC Heaters (TTH Series) HotPoly Tote Tank / IBC Heaters (TTH Series) Instruction Manual Read and understand this material before operating or servicing these heaters. Failure to understand how to safely operate these heaters

More information

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control Installation and Operation Manual Temperature and Pressure Monitoring for Heating and Cooling Applications Temperature Monitoring Control VALVE OPEN ALARM System= 128 o F Alarm At= 130 o F RESET /BACK

More information

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL. Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH Liquid Level Alarm 2.2 LOW Liquid Level Alarm 3. INSTALLATION...

More information

VA301C CONTROLLER WITH BACnet OPTION

VA301C CONTROLLER WITH BACnet OPTION ORDERING INFORMATION VA301C Controller VA301C-DLC VA301C-DLC-BIP Gas detection controller with data logging, display and plastic housing. Gas detection controller with data logging and display, BACnet/IP

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

(HSTAT Series) Instruction Manual

(HSTAT Series) Instruction Manual Silicone Rubber Heating Tapes with Adjustable Thermostat Control (HSTAT Series) Instruction Manual Read and understand this material before operating or servicing these heating tapes. Failure to understand

More information

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A GasScanner 1C Single Channel Monitor Operator s Manual MINT-0278-XX Rev A Product Warranty Matheson Tri-Gas, Inc., warrants gas alarm equipment sold by us to be free from defects in materials, workmanship,

More information

PLL Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

PLL Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual Installation and Operation Manual Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control PLL Pump-Lead-Lag Warning This Heat-Timer control is strictly an operating control; it

More information

PLL. Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

PLL. Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual Installation and Operation Manual Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control Pump-Lead-Lag Warning This Heat-Timer control is strictly an operating control; it should

More information

Wrap-Around TOTE Tank / IBC Heaters (TOTE and TOT Series)

Wrap-Around TOTE Tank / IBC Heaters (TOTE and TOT Series) Wrap-Around TOTE Tank / IBC Heaters (TOTE and TOT Series) Instruction Manual Read and understand this material before operating or servicing these heating tapes. Failure to understand how to safely operate

More information

TRIGARD Gas Monitor. Instruction Manual "! WARNING

TRIGARD Gas Monitor. Instruction Manual ! WARNING TRIGARD Gas Monitor Instruction Manual "! WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR USING OR SERVICING THE PRODUCT. Like any piece of complex

More information

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector IMPORTANT READ THIS FIRST....3 CAUTIONS... 3 AVOIDING NUISANCE ALARMS... 3 STANDARD FEATURES... 4 AVAILABLE OPTIONS... 4 PARTS DESCRIPTION... 5 FRONT PANEL

More information

Model 9010 and 9020 Monitoring Systems

Model 9010 and 9020 Monitoring Systems Model 9010 and 9020 Monitoring Systems Instruction Manual " WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR USING OR SERVICING THE PRODUCT. Like

More information

Safe T Net 210. Instruction Manual Part Number Mar2010

Safe T Net 210. Instruction Manual Part Number Mar2010 Safe T Net 210 Instruction Manual Part Number 71-0012 31Mar2010 2007 Thermo Fisher Scientific Inc. All rights reserved. Specifications, terms and pricing are subject to change. Not all products are available

More information

Pioneer-R16 Gas Monitor Operator s Manual

Pioneer-R16 Gas Monitor Operator s Manual Pioneer-R16 Gas Monitor Operator s Manual Edition 7/2/97 RKI INSTRUMENTS, INC RKI Instruments, Inc. 33248 Central Ave, Union City, CA 94587 (510) 441-5656 Chapter 1: Description About the Pioneer-R16 Gas

More information

FW-RA-LED Remote Multiplex Annunciator Panels

FW-RA-LED Remote Multiplex Annunciator Panels FW-RA-LED Remote Multiplex Annunciator Panels WIRING and INSTALLATION INSTRUCTION LNOTICE All information, documentation, and specifications contained in this manual are subject to change without prior

More information

LV-5 Direct Contact Low Voltage Detector and LV-5/K01 Kit including LV-PT Tester, Holster and Available Accessories

LV-5 Direct Contact Low Voltage Detector and LV-5/K01 Kit including LV-PT Tester, Holster and Available Accessories LV-5 Direct Contact Low Voltage Detector and LV-5/K01 Kit including LV-PT Tester, Holster and Available Accessories Operating & Instruction Manual 1475 Lakeside Drive Waukegan, Illinois 60085 U.S.A. 847.473.4980

More information

Isolated Thermocouple Module

Isolated Thermocouple Module User Manual for the HE693THM665, HE693THM666, HE693THM667, HE693THM668 Isolated Thermocouple Module Twelfth Edition 19 April 2004 PREFACE 19 APR 2004 PAGE 3 PREFACE This manual explains how to use the

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

Air Pump Up to 800 gallons

Air Pump Up to 800 gallons Air Pump Up to 800 gallons REMINDER CALL 1-888-755-6750 BEFORE RETURNING TO STORE. PACKAGE CONTENTS ITEM #PBPAPK40W Questions, problems, missing parts? Before returning to your retailer, call our customer

More information

RF SCOUT PLUS INSTRUCTION MANUAL. Dielectric, LLC 22 Tower Rd. Raymond, ME Phone: January 2015, Rev B 1

RF SCOUT PLUS INSTRUCTION MANUAL. Dielectric, LLC 22 Tower Rd. Raymond, ME Phone: January 2015, Rev B 1 RF SCOUT PLUS INSTRUCTION MANUAL Dielectric, LLC 22 Tower Rd. Raymond, ME 04071 Phone: 800.341.9678 www.dielectric.com 21 January 2015, Rev B 1 WARNING Powering RF sensors above +30dBm (1W) will cause

More information

SECTION Fluorescent Dissolved Oxygen Measuring System

SECTION Fluorescent Dissolved Oxygen Measuring System SECTION 40 75 43 Fluorescent Dissolved Oxygen Measuring System PART 1 General 1.01 SUMMARY A. Requirements for a high-performance, digital fluorescence sensor for measurement of dissolved oxygen in liquid.

More information

Expanded Backup Control Installation & Operator s Instruction Manual

Expanded Backup Control Installation & Operator s Instruction Manual Installation & Operator s Instruction Manual March 2004 CTB Inc. Warranty CTB Inc. Warranty CTB Inc. warrants each new Chore-Tronics product manufactured by it to be free from defects in material or workmanship

More information

Section PERIMETER SECURITY SYSTEMS

Section PERIMETER SECURITY SYSTEMS Section 28 16 43 PERIMETER SECURITY SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide and install a perimeter security system as herein specified for the purpose of detecting entry into a designated security

More information

Intrinsically Safe Transmitters, Option Code 2n

Intrinsically Safe Transmitters, Option Code 2n Installation Manual for Intrinsically Safe Transmitters, Option Code 2n ATEX PERSONAL INJURY WARNING DO NOT USE these products as safety or emergency stop devices or in any other application where failure

More information

Ethernet to Serial Bridge Owners Manual Circuit Board: AB Converter: Digi Connect ME

Ethernet to Serial Bridge Owners Manual Circuit Board: AB Converter: Digi Connect ME Circuit Board: AB-2552-006 Converter: Digi Connect ME American LED-gible Inc. 1776 Lone Eagle St. Columbus, OH 43228 (614) 851-1100 Phone (614) 851-1121 Fax www.ledgible.com www ledgible@ledgible.com e-mail

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Instrumentation, Inc. 11390 Amalgam Way Gold River, CA 95670 T: 800-876-1172 Int l: (916) 638-3429, F: (916) 638-3270 High Water Alarm WA400-DC WA400-AC WA400-BU WA400-FS WA400-AL 10/23/06 P/N: 01-527

More information

Alarm Tone Generator Model AG17

Alarm Tone Generator Model AG17 Alarm Tone Generator Installation & Operation P005089 Rev. C 150930 9/30/2015 12:25 PM Ph: 403.258.3100 \ email:info@guardiantelecom.com \ www.guardiantelecom.com Table of Contents Package Contents...

More information

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12 AUTOMATION P R O D U C T S GROUP, INC. Operator s Manual RST-5000 Series Web Enabled Input Module Rev. A2, 1/12 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com RST-5000

More information

Notice... 1 Trademarks... 1 US Patent Numbers... 1 Technical Services Contact Information... 2 Document Conventions... 2 Warranty...

Notice... 1 Trademarks... 1 US Patent Numbers... 1 Technical Services Contact Information... 2 Document Conventions... 2 Warranty... Table of Contents Preface 1 Notice... 1 Trademarks... 1 US Patent Numbers... 1 Technical Services Contact Information... 2 Document Conventions... 2 Warranty... 2 Chapter 1 Radius Overview 6 1.1 About

More information

MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL

MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL 95 Methodist Hill Drive Rochester, NY 14623 Phone: US +1.585.321.5800 Fax: US +1.585.321.5219 www.spectracomcorp.com Part Number 8143-5000-0050

More information

AMC-RAM-4. Refrigerant Alarm Module USER MANUAL. Please read the installation and operating instructions completely and carefully before starting.

AMC-RAM-4. Refrigerant Alarm Module USER MANUAL. Please read the installation and operating instructions completely and carefully before starting. AMC-RAM-4 Refrigerant Alarm Module USER MANUAL IMPORTANT: Please read the installation and operating instructions completely and carefully before starting. Filename: 3310405B, DOC, AMC_RAM4_Manual.doc

More information

External Wireless Sounder

External Wireless Sounder External Wireless Sounder Model: WL RWS401 Installation and Programming Instructions Table of Contents Introduction... 3 Operational Functions... 3 Alarm / Tamper Indication... 3 Low Battery Indication...

More information

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual Replace the following pages of Document Number 50734 (I56-993-01/D770-19-00), Revision B with the corresponding revised

More information

Chore-Tronics Load Cell Indicator

Chore-Tronics Load Cell Indicator Chore-Tronics Load Cell Indicator June 2008 CTB Inc. Warranty Load Cell Indicator CTB Inc. Warranty CTB Inc. warrants each new product manufactured by it to be free from defects in material or workmanship

More information

CT2 Retro Box Installation Instruction Manual

CT2 Retro Box Installation Instruction Manual ` CT Retro Box Installation Instruction Manual November 007 CTB Inc. Warranty CT Retro Box CTB Inc. Warranty CTB Inc. warrants each new product manufactured by it to be free from defects in material or

More information

Frequently asked questions: Intelligent Transmitter Series

Frequently asked questions: Intelligent Transmitter Series Frequently asked questions: Intelligent Transmitter Series The Wilcoxon family of Intelligent Transmitters, relay alarms, and communication modules can be used to implement low-cost online vibration monitoring

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

SEC 2000 Millenium Infrared Gas Detector

SEC 2000 Millenium Infrared Gas Detector SEC 2000 Millenium Infrared Gas Detector Instruction and Operation Manual Sensor Electronics Corporation 5500 Lincoln Drive Minneapolis, Minnesota 55436 USA (952) 938-9486 Fax (952) 938-9617 Email: sales@sensorelectronic.com

More information

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required. TTSIM-1A TraceTek Sensor Interface Module with Relay Installation Items (not supplied) General Information Installation/Operation Instructions Please read these instructions and keep them in a safe place.

More information

NXM2G Installation and Operating Manual

NXM2G Installation and Operating Manual NXM2G-1001 MARCH 26, 2014 NXM2G Installation and Operating Manual (-1 UL version shown) 40VG This manual must be affixed on or adjacent to the boiler or kept with boiler operating manual or other information.

More information

Beacon 200 Gas Monitor Operator s Manual

Beacon 200 Gas Monitor Operator s Manual Beacon 200 Gas Monitor Operator s Manual Part Number: 71-0059RK Revision: J Released: 1/31/18 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be

More information

ES2-HB. Ordering Information. Dimensions. Specifications. Humidity Sensor Temperature/Humidity Sensor

ES2-HB. Ordering Information. Dimensions. Specifications. Humidity Sensor Temperature/Humidity Sensor Humidity Sensor Temperature/Humidity Sensor ES2-THB CSM ES2-THB_DS_E_3_2 Detect Humidity within an Accuracy of ±3% in a Compact Body. Set Provides Superior Humidity Control and Temperature/ Humidity Control.

More information

Model 4001 Series Single Channel Controller

Model 4001 Series Single Channel Controller Model 4001 Series Single Channel Controller Sierra Monitor Corporation 1991 Tarob Court, Milpitas, CA 95035 (408) 262-6611 (800) 727-4377 (408) 262-9042 - Fax E-Mail: sales@sierramonitor.com Web site:

More information

Instruction Bulletin

Instruction Bulletin Instruction Bulletin 435-54-26A 9/99 Monroe, NC, USA MODEL 98 Digital Temperature Controller For Medium Voltage Transformers Class 3, 4 Retain for future use. NOTICE Read these instructions carefully and

More information

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System SYSTEM MANUAL FT1-SB Single Zone Fire Alarm System DOCUMENT HISTORY Issue Date Description Written By Checked By Draft 0 2/9/2008 Original Document. A. Shenouda C. Orr Issue 1 4/11/2011 Update drawing

More information

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...

More information

Installation Manual COPYRIGHT NOTICE

Installation Manual COPYRIGHT NOTICE Installation Manual COPYRIGHT NOTICE Copyright 2007 by Quest Controls Inc (QUEST). The material discussed in this publication is the proprietary property of QUEST. QUEST retains all rights to reproduction

More information

Series: MBC1-TC Mini Benchtop Temperature Controller

Series: MBC1-TC Mini Benchtop Temperature Controller User s Guide Series: MBC1-TC Mini Benchtop Temperature Controller Imagine Instruments LLC:: 4500 Williams Drive, Ste 212-318 :: Georgetown, TX 78633 :: p. 855.574.6243 e-mail: info@imagineinstruments.com

More information

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

Combustible Gas and Hydrogen Sulfide Beacon 200 Rig Monitor Operator s Manual

Combustible Gas and Hydrogen Sulfide Beacon 200 Rig Monitor Operator s Manual Combustible Gas and Hydrogen Sulfide Beacon 200 Rig Monitor Operator s Manual Part Number: 71-0243RK Revision: E Released: 12/11/17 www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

SECTION Process and Immersion Turbidity and Total Suspended Solids Sensor

SECTION Process and Immersion Turbidity and Total Suspended Solids Sensor SECTION 40 75 53 Process and Immersion Turbidity and Total Suspended Solids Sensor PART 1 General 1.01 SUMMARY A. Requirements for a digital sensor for process turbidity or Total Suspended Solids (TSS)

More information

MODEL 4200-IR-2 (Up to 2 Sensors) MODEL 4200-IR-4 (Up to 4 Sensors) MODEL 4200-IR-6 (Up to 6 Sensors)

MODEL 4200-IR-2 (Up to 2 Sensors) MODEL 4200-IR-4 (Up to 4 Sensors) MODEL 4200-IR-6 (Up to 6 Sensors) MODEL 4200-IR-2 (Up to 2 Sensors) MODEL 4200-IR-4 (Up to 4 Sensors) MODEL 4200-IR-6 (Up to 6 Sensors) Refrigerant Monitor User Manual Technical Support Continental North America Toll Free 1-(800) 387-9487

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

MaxLite LED Vapor Tight Linear Fixture

MaxLite LED Vapor Tight Linear Fixture General Safety Information To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards read all warnings and instructions

More information

4 & 8-POINT ANNUNCIATORS Instruction Manual

4 & 8-POINT ANNUNCIATORS Instruction Manual 4 & 8-POINT ANNUNCIATORS Instruction Manual 8 Field Selectable Sequences All Common ISA Sequences 4 or 8-Point (Channel) Monitoring Free Replaceable Message Labels Type 4X, NEMA 4X, IP65 Front Universal

More information

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features. CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse

More information

Ultrasonic Reflective Sensor

Ultrasonic Reflective Sensor Ultrasonic Reflective with an Adjustable Sensing Distance of 0.3 to 3 m Under Stable Operation without Background Interference Ensures a stable operating range with minimal side-lobe areas. Built-in unstable

More information

Thermometer model 02059

Thermometer model 02059 Instruction Manual Thermometer model 02059 pm CONTENTS Unpacking Instructions... 2 Package Contents... 2 Product Registration... 2 Features & Benefits: Sensor... 2 Features & Benefits: Display... 3 Setup...

More information

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

Use this product according to this instruction manual. Please keep this instruction manual for future reference. 273 Branchport Avenue Long Branch, NJ 07740 (732) 222-6880 Thank you for using our products. INSTALLATION INSTRUCTIONS REMOTE MICROPHONE (SINGLE CIRCUIT) Use this product according to this instruction

More information

Protocol Station Remote Alarm

Protocol Station Remote Alarm ADI 5135-C Certified ISO 9001 Protocol Station Remote Alarm 529 5135-01-120 529 5135-01-220 INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Controls Corporation

More information

MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL

MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL TABLE OF CONTENTS Product Overview... 2 Operation... 3 Installation... 5 Troubleshooting... 9 Ordering Information, Warranty and Service...10

More information

Henny Penny Blast Chiller/Freezer Models BCC/BCR-140 Models BCC/BCR-175 Models BFR/BCR-350

Henny Penny Blast Chiller/Freezer Models BCC/BCR-140 Models BCC/BCR-175 Models BFR/BCR-350 Henny Penny Blast Chiller/Freezer Models BCC/BCR-140 Models BCC/BCR-175 Models BFR/BCR-350 TECHNICAL MANUAL Section TABLE OF CONTENTS Page Section 1. TROUBLESHOOTING... 1-1 1-1. Introduction... 1-1 1-2.

More information

TrueClean Compact CIP

TrueClean Compact CIP TrueClean Compact CIP Installation, Operation, and Maintenance Manual www.trueclean.us TrueClean Compact CIP Table of Contents Safety... 1 Important Safety Information.... 1 Introduction... 2 About This

More information

SECTION INDUCTIVE CONDUCTIVITY ANALYZERS

SECTION INDUCTIVE CONDUCTIVITY ANALYZERS SECTION 40 75 16 INDUCTIVE CONDUCTIVITY ANALYZERS PART 1 General 1.01 SUMMARY A. Requirements for a digital inductive conductivity sensor for standard, hazardous and hightemperature applications. The sensor

More information

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16 TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and

More information

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

Installation Instructions. Remanufactured Veeder-Root Overfill Alarm and. Acknowledgement Switch. Overfill Alarm PMP # OEM #

Installation Instructions. Remanufactured Veeder-Root Overfill Alarm and. Acknowledgement Switch. Overfill Alarm PMP # OEM # Manual Number: 01-62-768 Revision : 1.2 Date: 03/20/17 Installation Instructions Remanufactured Veeder-Root Overfill Alarm and Acknowledgement Switch Overfill Alarm PMP # 62625 OEM # 790091-001 Acknowledgement

More information

WDB2 Series Bearing Temperature Sensor

WDB2 Series Bearing Temperature Sensor WDB2 Series Bearing Temperature Sensor Dear 4B Customer: Congratulations on your purchase. 4B appreciates your business and is pleased you have chosen our products to meet your needs. Please read in its

More information

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS GENERAL INFORMATION Please read these instructions and keep them in a safe place. These instructions must

More information

Humidity Monitor model 01080

Humidity Monitor model 01080 Instruction Manual Humidity Monitor model 01080 Features & Benefits 19 18 1 2 3 4 12 11 10 17 16 5 9 RECORDS ºC/ºF 15 14 FRONT 6 7 8 1. Humidity Level Indicator Indicates a high, low or ideal humidity

More information