Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd
|
|
- Rosamund Melton
- 5 years ago
- Views:
Transcription
1 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) F : +44 (0) E : warrington@exova.com W: Title: Indicative fire test WF Report No: /A Prepared for: Hoody Speaker Hoods Ltd Link House Knight Rider Court Knight Rider Street Maidstone Kent ME15 6LU Date: 12 th November 2013
2 Page 2 of 16 Indicative Fire Test We have pleasure in enclosing the information obtained from the indicative fire test conducted, on your behalf, on the 9 th August The test results relate to an investigation, which utilised the heating and pressure conditions specified in BS EN : The information is provided for the test sponsor s information only and should not be used to demonstrate performance against any published fire test standard, nor compliance with a regulatory requirement. The test was not conducted under the requirement of UKAS accreditation. The purpose of the investigation was to provide an indication of the behaviour of a section of a timber floor protected on its underside by a plasterboard ceiling incorporating three speakers and associated covers, when subjected on its underside to the heating and pressure conditions specified by BS EN : The test assembly had overall nominal dimensions of 1700 mm wide by 2200 mm long and briefly comprised three sections of softwood timber joist at nominally 600 mm centres. The ends of the joists were closed with a section of the same softwood joist fixed across the ends on both edges. The floor construction was faced on its upper surface with a single layer of nominally 22 mm thick chipboard flooring. The underside of the floor was provided with a direct fixed ceiling formed from two layers of 12.5mm thick Lafarge Firecheck plasterboard. Three speakers with associated covers were fitted into the ceiling. The speakers were referenced A to C for the purpose of the test and were described by the sponsor as follows: Specimen A was referenced Monitor Audio CT165 Ceiling Speaker (Hoody 1). The specimen had a nominal diameter of 265 mm by 160 mm high and was installed within a cut out aperture within the ceiling 211 mm diameter by 114 mm high. Specimen B was referenced Monitor Audio CT180 Ceiling Speaker (Hoody 2). The specimen had a nominal diameter of 335 mm by 180 mm high and was installed within a cut out aperture within the ceiling 247 mm diameter by 121 mm high. Specimen C was referenced Monitor Audio CWT140R Ceiling Speaker (Hoody 5). The specimen had a nominal diameter of 185 mm by 145 mm high and was installed within a cut out aperture within the ceiling 149 mm diameter by 98.6 mm high. All three speakers were fitted with an Acoustic Fireproof Cover, provided by Hoody Speaker Hoods Ltd. The floor assembly was mounted such that it formed the top horizontal face of a 1.5 m by 2.0 m gas fired furnace chamber, the temperature rise of which was controlled to conform with the heating and pressure conditions specified in BS EN : The following information relating to the test is enclosed: Table 1 - Specified and actual furnace temperatures and percentage tolerances Table 2 - Individual and mean temperatures recorded on the unexposed surface of the floor (Thermocouples 20 to 24) Table 3 - Individual temperatures recorded on the unexposed surface of the floor adjacent to joints. (Thermocouples 25 and 26) Table 4 - At three positions mid-height of the air cavity, adjacent to the speaker assemblies (Thermocouples 27 to 29) Graph 1 - Graph showing the specified and actual furnace temperatures
3 Page 3 of 16 Graph 2 - Graph showing the individual and mean temperatures recorded on the unexposed surface of the floor. Observations on the general behaviour of the specimens during the test. Photographs taken before and after the test. The test was discontinued after a period of 90 minutes. We trust that the information obtained from the test will be useful to you. Yours faithfully, Responsible Officer D. Yates Testing Officer Fire Resistance Department Exova Warringtonfire This copy has been produced from a.pdf format electronic file that has been provided by Exova Warringtonfire to the sponsor of the report and must only be reproduced in full. Extracts or abridgements of reports must not be published without permission of Exova Warringtonfire. The pdf copy supplied is the sole authentic version of this document. All pdf versions of this report bear authentic signatures of the responsible Exova Warringtonfire staff.
4 Page 4 of 16 Table 1 Time Specified Actual Furnace Furnace Minutes Temperature Temperature Deg. C Deg. C
5 Page 5 of 16 Table 2 Time T/C T/C T/C T/C T/C Mean Number Number Number Number Number Minutes Temp Deg. C Deg. C Deg. C Deg. C Deg. C Deg. C
6 Page 6 of 16 Table 3 Time T/C T/C Number Number Minutes Deg. C Deg. C
7 Page 7 of 16 Table 4 Time T/C T/C T/C Number Number Number Minutes Deg. C Deg. C Deg. C
8 Page 8 of 16 Graph Temperature - Deg. C Specified Furnace Temperature Deg. C Actual Furnace Temperature Deg. C Time - Minutes
9 Graph 2 WF Test Report Page 9 of 16
10 Page 10 of 16 Test Observations Time All observations are from the unexposed face unless noted otherwise. mins secs The ambient air temperature in the vicinity of the test construction was 21ºC at the start of the test with a maximum variation of +4, -1ºC during the test The test commences Slight smoke release begins from the joints within the timber deck Viewed from the exposed face, the paper face of the plaster board ceiling has begun to burn away. The plastic speaker facing of Specimens A and B appears to have melted and fallen away Viewed from the exposed face, the plastic speaker facing of Specimen C appears to have melted and fallen into the furnace Slight smoke release continues from along the joints within the timber deck. Slight discolouration is evident at the same locations The ceiling board joints appear black in colour and slightly charred. The circular apertures within the ceiling appear blackened and slightly charred also The board joints within the first layer of ceiling board have opened up by approximately mm Viewed from the exposed face, a large section of the first layer of ceiling board has dropped downwards by approximately mm as it begins to detach from the ceiling along the joint Smoke release from the joints within the timber floor has increased slightly. Discolouration has become more evident at the same location Viewed from the exposed face, flames issue from the circular openings within the ceiling. The first layer of the ceiling board has dropped down further along the joint now by approximately 50 mm Smoke release from the joints within the timber deck has increased further Viewed from the exposed face, a large section of the first layer of ceiling board continued to pull away from the ceiling now by approximately mm A large section of the first layer of ceiling board has detached and fallen into the furnace chamber Smoke release has increased further along the timber deck joints A cotton pad is applied at the mid span of a timber deck joint but fails to ignite Viewed from the exposed face, large amounts of flaming issue from the circular apertures within the ceiling.
11 Page 11 of 16 Time mins secs Smoke release from the joints within the timber deck has increased significantly A large section of the second layer of board begins to drop downwards at the approximate centre of the ceiling Smoke release from the ceiling increases significantly and the test is discontinued at the sponsor s request.
12 Page 12 of 16 Test Photographs The exposed face of the ceiling prior to the test. The unexposed face of the ceiling prior to the test.
13 Page 13 of 16 The unexposed face of the ceiling after a test duration of 30 minutes The exposed face of the ceiling after a test duration of 30 minutes
14 Page 14 of 16 The unexposed face of the ceiling after a test duration of 60 minutes The exposed face of the ceiling after a test duration of 60 minutes
15 Page 15 of 16 The unexposed face of the ceiling after a test duration of 90 minutes The exposed face of the ceiling after a test duration of 90 minutes
16 The exposed face of the ceiling immediately after the test WF Test Report Page 16 of 16
Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves.
Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves Report No: 172158 Prepared for: Lindab Ventilation AB SE 26982 Båstad Järnvägsgatan
More informationWARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier
Page 1 of 27 Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Test Sponsor Saveguard (UK) Limited Warrington Fire Research Centre Ltd.,
More informationBS EN : 2001 & IEC :2000
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 60695-2-11: 2001 & IEC 60695-2-11:2000
More informationTitle: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance
More informationBS 476: Part 6: 1989+A1:2009
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 6: 1989+A1:2009 Method Of Test
More informationThe Fire Resistance Performance Of Timber Or Mineral Composite Based Insulated Doorsets When Fitted With D & E Architectural Hardware Spring Hinges
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance
More informationIEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IEC 60331-11-21 Method of test defined in
More informationBS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2002 Fire Tests For
More information25 th November Title:
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance
More informationBS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 13823: 2010 Reaction to Fire Tests
More informationTitle: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Air Leakage Performance of
More informationAd-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation
More informationBS 476: Part 6: 1989+A1:2009
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 6: 1989+A1:2009 Method Of Test
More informationBS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 1716: 2010 Determination Of The
More informationBS EN ISO : 2010
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2010 Fire Tests For Determination
More informationBS EN ISO : 2010
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2010 Fire Tests For Determination
More informationAd-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation
More informationBS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor:
BS EN 61034-2: 2005 Measurements Of Smoke Density Of Electric Cables WF Report Number 177599 Date: 17 th November 2008 Test Sponsor: FTC Fabbrica Trentina Conduttori Srl 0249 Page 2 of 13 Bodycote warringtonfire
More informationBS EN ISO : 2010
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Fire Tests For Determination Of The Burning
More informationNF X : Parts 1, 2, 3, 4 & 5
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com NF X 10-702: Parts 1, 2, 3, 4 & 5 Fire test
More informationEN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com EN 45545-2: 2013 Summary Test Report Requirement
More informationReview Fire Test Report
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Review Fire Test Report Determination of
More informationBS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.
BS EN 60332-1-2:2004 Test On Electric And Optical Fibre Cables Under Fire Conditions WF Report Number 177604 Date: 14 th November 2008 Test Sponsor: FTC Fabbrica Trentina Conduttori Srl 0249 Page 2 of
More informationBS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited
BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 158117 Date: 13 th October 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 158117 BS 476:
More informationIMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:
IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2 Smoke & Toxicity Test WF Report Number: 166040 Date: 13 th August 2007 Test Sponsor: Fiba Tech Industries Ltd. 0249 Page 2 of 13 Bodycote warringtonfire
More informationBS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.
BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions WF Report Number: 147709 Test Sponsor: FTC - Fabbrica Trentina Conduttori
More informationBS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.
BS EN 60332-1-2:2004 Test On Electric And Optical Fibre Cables Under Fire Conditions WF Report Number 177603 Date: 14 th November 2008 Test Sponsor: FTC Fabbrica Trentina Conduttori Srl 0249 Page 2 of
More informationBS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 13823: 2010 Reaction to Fire Tests
More informationFIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS
FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS Report number FSP 1290A CSIRO job number LP46ASP3085 Date of issue 30 NOVEMBER 2007 Client EFFICIENCY MATRIX PTY LTD and YOUNGEN
More informationASSESSMENT REVIEW. Review of Assessment Report WFRA C91415
ASSESSMENT REVIEW Review of Assessment Report WFRA C91415 Fire resistance performance of steel electrical wall boxes mounted in plasterboard partitions with modified mounting arrangements, box design and
More informationBS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited
BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 153420 Date: 28 th April 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 153420 BS 476: Part
More informationMethod of test defined in IEC for determining the circuit integrity performance of a cable under fire conditions.
Method of test defined in IEC 60331-21 for determining the circuit integrity performance of a cable under fire conditions. WF Report Number: 148371 Test Sponsor: FTC - Fabbrica Trentina Conduttori Srl
More informationIMO Resolution MSC 61(67): Annex 1: Part 2
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IMO Resolution MSC 61(67): Annex 1: Part
More informationContents Page No. Page 1 of Introduction Specimen verification Description of supporting constructions...
Contents Page No Page 1 of 14... 1 1 Introduction... 3 2 Specimen verification... 3 3 Description of supporting constructions... 3 4 Description of specimen... 3 4.1 Air transfer grille blocks... 3 5 Test
More informationFire-resistance test on fire collars protecting a plasterboard wall penetrated by services
INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services Test Report Author: Peter Gordon Report number: FSP 1960 Date: 5 February 2019 Client:
More informationResearch-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly
Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly ASTM E119-98: Standard Test Methods for Fire Tests of Building Construction and Materials* *Research-scale horizontal
More informationTest Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13
Test Report No. AJHG1501000530FB Date: FEB.17, 2015 Page 1 of 13 ZHEJIANG TERASUN AIR DUCT CO., LTD MAREN VILLAGE, CHONGREN INDUSTRIAL ZONE, CHONGREN TOWN, SHENGZHOU CITY, ZHEJIANG PROVINCE, CHINA The
More informationFire-resistance test on fire collars protecting a plasterboard wall penetrated by services
INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services Test Report Author: Mario Lara-Ledermann Report number: FSP 1658 Date: 15 January
More informationCERTIFICATE OF APPROVAL No CF 5236 EMVER PAINTS INDUSTRIES LLC
CERTIFICATE OF APPROVAL No CF 5236 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Jebel Ali Industrial
More informationCertifikat och provningsprotokoll för art och 4511
Certifikat och provningsprotokoll för art. 4509 och 4511 Innehållsförteckning: Declaration of conformity... sid 2 SINTEF Produktdokumentation 050-0204... sid 3 Efectis Nederland BV Brandtestunderlag...
More informationFIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES
FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES Report number FSP 1360 CSIRO job number SP3241 Date of issue 31 JULY 2009 Client SNAP FIRE SYSTEMS PTY LTD. Commercial-in-confidence
More informationFire resistance test on fire collars protecting a concrete slab penetrated by services
INFRASTRUCTURE TECHNOLOGIES Fire resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Mario Lara Report number: FSP 1601a Date: 11 April 2014 (This report
More informationCERTIFICATE OF APPROVAL No ME 5085
CERTIFICATE OF APPROVAL No ME 5085 1 Suite No. 52, 5 th Floor, Martin Burn Building, 1 RN Mukherjee Road, Kolkata- 700001 (West Bengal), India Tel: +91 33 40276600 Have been assessed against the requirements
More informationFire-resistance test on fire collars protecting a concrete slab penetrated by services
INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Chris Wojcik Report number: FSP 1735 Date: 8 September 2016 Client:
More informationWARNING: DOWNLIGHTS MUST BE FITTED CORRECTLY IN FIRE RATED CEILINGS
WARNING: DOWNLIGHTS MUST BE FITTED CORRECTLY IN FIRE RATED CEILINGS Requirement I: The fire protection rating of the downlight must be the same as, or exceed that of the ceiling. Ceilings range from 30
More informationReport Number BTC 15450A
Report Number BTC 15450A AN ACOUSTIC TEST REPORT COVERING LABORATORY SOUND INSULATION TESTS TO BS EN ISO 140-3:1995 ON A BRITISH GYPSUM GYPWALL AUDIO PARTITION WITH VARYING NUMBERS OF ELECTRICAL SOCKET
More informationTEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota
Architectural Testing TEST REPORT Report No.: D7913.05-121-24 Rendered to: 3M COMPANY St. Paul, Minnesota PRODUCT TYPE: Window Film SERIES/MODEL: 3M Scotchshield Ultra 800 TEST METHOD: ASTM E 84-11a, Standard
More informationCAN/ULC-S102 Surface Burning Characteristics of "ezobord 9 mm (Green)"
UNCONTROLLED ELECTRONIC COPY CAN/ULC-S12 Surface Burning Characteristics of "ezobord 9 mm (Green)" A Report To: ivekter Inc. 1625 Drew Rd. Mississauga, Ontario L5S 1J5 Phone: 416-665-3571 Attention: E-mail:
More informationASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB"
UNCONTROLLED ELECTRONIC COPY ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB" A Report To: Ciucevich 7200 Vermilion Ct. Wake Forest, NC 27587 USA Phone: (919) 570-291 E-mail:
More informationFire Test Reports for Interpon D Powder Coatings
Akzo Nobel Powder Coatings Ltd. Specification Fire Test Reports for Interpon D Powder Coatings Explanations and collations of key reports and approvals for the UK market. July 2017 Russell Deane Powder
More informationBCTC CARPET TECHNICAL CENTRE
Wira House West Park Ring Road Leeds, LS16 6QL Tel: +44 (0)113 259 1999 Fax: +44 (0)113 278 0306 Web: http://www.bttg.co.uk/bctc Email: CSLeeds@bttg.co.uk 7 September 2010 Page 1 of 7 Client: Rectory Farm
More informationEN 1155:1997 TESTS OF : PERKO R106 FS CONCEALED FIXED ELECTRICALLY POWERED FREE SWING DEVICES FOR SWING DOORS. Leopold Street, Birmingham.
Exova Warringtonfire Key Industrial ark Fernside Road Willenhall West Midlands WV13 3YA T : +44 (0) 1902 722 122 F : +44 (0) 1902 727 242 E : willenhall@exova.com W: www.exova.com EN 1155:1997 TESTS OF
More informationThe Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318
Retardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 21 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 Fire Retardant HOT LINE 1-8-913-9385 e-mail: info@fireretardantsinc.com
More informationBUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS
BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS Report number FSZ 1572 CSIRO job number SV3559 Date of issue 22 FEBRUARY 2013 Client BREEZWAY AUSTRALIA PTY LTD Commercial-in-confidence Copyright CSIRO 2013 Copying
More informationThe Radiators With Brains
Electrical Storage Radiators of the NEXT Generation Based on established German Technology..fine tuned By Cornish Engineering The Radiators With Brains Report of independent efficiency and electricity
More informationReport on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC
Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E 108-07a Rendered to: Trinity ERD Columbia, SC WFCi Project # 10135 & 11159 Testing Completed on: April
More informationLife Safety and Fire Resistant Glazing Systems
Life Safety and Fire Resistant Glazing Systems Kevin Hulin CEO, Mann McGowan Group Agenda GGF Introduction GGF and The Fire Resistant Glazing Group (FRGG) Fire Testing, Reports, Assessments and 3rd Party
More informationASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER
, Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong
More informationCAN/ULC-S102 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum
UNCONTROLLED ELECTRONIC COPY CAN/ULC-S12 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum A Report To: DiZal inc. 12 rue Bouvier, Suite 4 Québec, QC G2K K9 Phone:
More informationFUNDERMAX GMBH FIRE TEST REPORT
FUNDERMAX GMBH FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON 19 MM MAX COMPACT REPORT NUMBER I0002.02-121-24 TEST DATE 01/29/18 ISSUE DATE 02/16/18 RECORD RETENTION END DATE 01/29/22 PAGES 10 DOCUMENT
More informationASTM E 662 Rate of Smoke Generation of OXIFREE TM198"
ELECTRONIC COPY ASTM E 662 Rate of Smoke Generation of OXIFREE TM198" A Report To: Oxifree Global LLC 22955 State Highway 249, Suite 6 Tomball, TX 77375 USA Phone: (281) 251-7171 E-mail: ed.hall@oxifree.com
More informationTest Report: ICL/CR15/11/087
Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692 5155 Email: firetesting@intersciencecomms.co.uk
More informationCERTIFICATE OF APPROVAL No CF 5635 P3 SRL
CERTIFICATE OF APPROVAL No CF 5635 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Via Salvo D Acquisto
More informationSIGMADEK, LTD. FIRE TEST REPORT
SIGMADEK, LTD. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON ALUMINUM EXTRUSION DECK BOARD C/W PORCELAIN TILE INSERT REPORT NUMBER H5331.01-121-24 TEST DATE 09/13/17 ISSUE DATE 10/03/17 RECORD RETENTION
More informationCAN/ULC-S109 Flame Resistance of "Argo" Fabric
CAN/ULC-S109 Flame Resistance of "Argo" Fabric A Report To: Design/Craft Fabric Corporation 2230 Ridge Drive Glenview, IL 60025 USA Phone: Email: (847) 904-7000 x128 mboynton@design-craft.com Submitted
More informationFACADES AND FIRE The Essential Elements
FACADES AND FIRE The Essential Elements Andy Dean BSc (Hons), MCIOB, FSFE Head of Façade Engineering WSP Middle East Manama, Bahrain, Jun 2014 Reaction to fire versus fire resistance LEARNING OBJECTIVES
More informationReport Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors
February 2, 16 Rieke Office Interiors Mr. Todd Rieke Fox Ln. Elgin, IL 6123 Our Reference: SV3565 / 4787326412 Subject: Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By
More informationFTSG RESOLUTIONS. This document of FTSG resolutions was issued by the Company Secretary 20 July 2012.
FTSG RESOLUTIONS This document of FTSG resolutions was issued by the Company Secretary 20 July 2012. TABLE OF CONTENTS No. 1 Moisture Content... 3 No. 2 Moisture Content Limits... 4 No. 3 Moisture Content...
More informationTest Report No. AJD Date: JUN.09, 2013 Page 1 of 6
Test Report No. AJD201302471 Date: JUN.09, 2013 Page 1 of 6 WALER PRECISION MFG. SDN. BHD. NO.2, JALAN CANGGIH 1, TAMAN PERINDUSTRIAN CEMERALNG, 81800 ULU TIRAM, JOHOR, MALAYSIA. The following sample(s)
More informationCAN/ULC-S102 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel"
ELECTRONIC DRAFT COPY CAN/ULC-S12 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel" A Report To: ABET Corporation 5 Paxman Road, Unit 1 Toronto, Ontario M9C 1B7
More informationExova Warringtonfire - Expert Witness Directory 2018
Exova Warringtonfire Holmesfield Road Warrington Cheshire WA1 2DS United Kingdom T : +44 (0) 1925 655116 E : warrington@exova.com W: www.exova.com Exova Warringtonfire - Expert Witness Directory 2018 Please
More informationSTEEL DUCT - FIRE RATED CLADDING INSTALLATION MANUAL
14SH200001022 STEEL DUCT - FIRE RATED CLADDING INSTALLATION MANUAL DUCTLINER GS - VENTILATION, SMOKE OUTLET AND KITCHEN EXTRACT DUCT SYSTEMS Tested under BS 476: Part 24: 1987 Fire tests building materials
More informationBenefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E.
Benefiting Government, Industry and the Public Through Innovative Science and Technology Barry L. Badders, Jr. P.E. 7 December 2011 Part 1 Non-Combustibility Test Part 3 Test for A, B,, and F Class Divisions
More informationCAN/ULC-S109 Flame Resistance of "Xanadu" Material
CAN/ULC-S109 Flame Resistance of "Xanadu" Material A Report To: Design/Craft Fabric Corporation 2230 Ridge Dr. Glenview, IL 60025 USA Phone: (847) 904-7000 E-mail: mboynton@design-craft.com Attention:
More informationTNO report. Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box AA Delft. T F
ederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / etherlands Organisation for Applied Scientific Research TO report Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box 49
More informationTest Report: ICL/H18/9039 Rev 1
Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692 5155 Email: firetesting@intersciencecomms.co.uk
More informationThe Train Now Arriving At... Harmonised Fire Safety For European Rolling Stock
The Train Now Arriving At... Harmonised Fire Safety For European Rolling Stock Beth Dean beth.dean@exova.com : The Role of Accredited Laboratories in Regulation and Market Surveillance 10 th October 2012
More informationClassification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.
Classification of reaction to fire performance in accordance with BS EN 13501-1: 2007 +A1: 2009 on Sandwich Panel, WP 50 Prepared for: Sandwich Panel Factory Jeddah Saudi Arabia 13 July 2011 0578 Page
More informationC-01 FIRE DECKS AND BULKHEADS
Guideline No.: C-01(201510) C-01 FIRE DECKS AND BULKHEADS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection
More informationLoss Prevention Standard
Loss Prevention Standard LPS 1196: Issue 1.2 This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information purposes only. Its use for testing, assessment,
More informationPERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome
PERFORMANCE TEST REPORT Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome Report No: D3964.01-106-31 Report Date: 06/19/14 Test Record Retention Date: 06/03/18 130 Derry Court York, PA
More informationReport Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL
May 18, 2015 Mr. Simone Furiato Ebrille SRL S S Canelli 53/A Nizza Monferrato, AT 14049 Our Reference: Subject: SV29774/4786853196 Report Of Surface Burning Characteristics Tests On Samples As Submitted
More informationReport of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd
October 05, 2011 Eco-Sol Ltd Mr. Paul Allcock Cardiff House Cardiff Rd Barry, Vale of Glamorgan, CF63 2AW Great Britain Our Reference: Subject: R27181/11CA40094 Report of Surface Burning Characteristics
More informationCERTIFICATE OF APPROVAL No. ME 5008 EMIRATES FIRE FIGHTING EQUIPMENT FACTORY LLC (FIREX)
EWCL 5 CERTIFICATE OF APPROVAL No. ME 5008 PO Box 22436, Industrial Area 13, Sharjah, UAE Tel: +971 6 5340300 Fax: +971 6 5340090 Website: www.firexuae.com Have been assessed against the requirements of
More informationContact person Date Reference Page Richard Johansson P (2) Fire Research
issued by an Accredited Testing Laboratory Contact person Richard Johansson 215-8-13 5P4413 1 (2) Fire Research +46 1 516 56 75 richard.johansson@sp.se 12 ISO/IEC 1725 Sklejka-Pisz Paged S.A Ul. kwiatowa
More informationIntertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008
Intertek I 0:: o D.. W 0:: I en w I REPORT NUMBER: 3161466SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Rd. Elmendorf,
More information2 Examination of Cladding Panels (Laboratory)
30th November 2016 Fire and Safety Department Report To: For the attention of: Our ref: Your ref: LFB/Fire Investigation Team - Dowgate Examination of Cladding Panels Flat 28 Shepherds Court, 21 Shepherd
More informationCERTIFICATE OF COMPLIANCE
Date : 13th September 2017 CERTIFICATE OF COMPLIANCE TEST REPORT NUMBER Assessment Reports are not acceptable DATE OF ISSUE DATE OF EXPIRY FACTORY/ MANUFACTURER This certificate of compliance validates
More informationTEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria
TEST REPORT Report No.: E6736.01-121-24 Test Date: May 6, 2015 Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria PRODUCT TYPE: Max Exterior F-Quality SERIES/MODEL: Décor. 0085 TEST METHOD:
More informationReport Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.
August 11, 2017 Contego International Inc. Mr. Danny French PO Box 49 Rochester, IN 46975-0049 Our Reference: R25382 / 4788022828 Subject: Report Of Surface Burning Characteristics Tests On Coated Louvered
More informationCERTIFICATE OF FIRE APPROVAL
LR2009.030. CERTIFICATE OF FIRE APPROVAL This is to certify that The product(s) detailed below will be accepted for compliance with the applicable Lloyd s Register Rules and Regulations for use on offshore
More informationDepartment for Communities and Local Government Research Report:
Department for Communities and Local Government Research Report: BD 2890 Investigation of real fires - Electrical consumer unit fire experiments 293761 (E3V2) CPD/04/102/027 Prepared for: Brian Martin
More informationReport Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D
November 10, 2014 Mr. Carlos Khantzis Textures 3D 31280 Oak Crest Dr. #4 Westlake Village, CA 91361 Our Reference: Subject: SV19490/4786557998 Report Of Surface Burning Characteristics Tests On Samples
More informationFABRITRAK SYSTEMS, INC. FIRE TEST REPORT
FABRITRAK SYSTEMS, INC. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON POLYESTER INFILL REPORT NUMBER H5200.01-121-24 TEST DATE 08/31/17 ISSUE DATE 09/20/17 RECORD RETENTION END DATE 08/31/21 PAGES
More informationPRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona
Architectural Testing PRODUCT PERFORMANCE TEST REPORT Report No.: D7226.01-121-24 Test Date: May 29, 2014 Rendered to: Natural Light Energy Systems Phoenix, Arizona PRODUCT TYPE: Tubular Daylight Device
More informationClassification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:
Classification of reaction to fire performance in accordance with EN 13501-1: 2007 +A1: 2009 on Superfoil SFNC Prepared for: Boulder Developments Ltd Black Horse Farm Main Street Norwell Nottinghamshire
More informationGAS-FIRED ('INFRA-RED') HEATER FOR USE ON THE JOINTS
ROAD RESEARCH LABORATORY Ministry of Transport RRL Report LR123 GAS-FIRED ('INFRA-RED') HEATER FOR USE ON THE JOINTS IN WEARING-COURSE ROLLED ASPHALT by B.F. Buglass CROWTHORNE ROAD RESEARCH LABORATORY
More informationTHE HOME OF REACTIVE PROTECTION SYSTEMS
THE HOME OF REACTIVE PROTECTION SYSTEMS CONTENTS Page Introduction 1 Role of air transfer grilles 1 Definitions and functions 1 Fire performance requirements 2 Varieties of air transfer grilles 3 Recommended
More informationIndicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number
Indicative hoarding fire experiment Prepared for: London Fire Brigade 21 May 2014 Client report number 292366 1 Hoarding fire demonstration Prepared on behalf of BRE Fire and Security by Name Dr Sung-Han
More informationClassification of Fire Performance of Wall and Ceiling Lining Materials
Classification of Fire Performance of Wall and Ceiling Lining Materials Using the Method of Kokkala, Thomas and Karlsson Reference: Kokkala, M.A. Thomas, P.H. and Karlsson, B. Rate of Heat Release and
More information