Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Size: px
Start display at page:

Download "Nitrogen Dioxide (NO2) Single-Point Gas Detection System"

Transcription

1 Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary gas sensor, temperature or humidity sensor. PolyGard SPC-0 APPLICATION To detect and control levels of nitrogen dioxide (NO) and other gases in a wide variety of commercial and industrial applications such as vehicle diesel exhaust in parking structures, engine repair shops, equipment rooms and ventilation systems, etc. The controller can communicate with any compatible electronic analog control, DDC/PLC control or automation system via binary and/or analog output signal. FEATURES Continuous monitoring One () built-in NO electrochemical sensor Easy plug-in sensor One () remote analog input, -0 ma One () digital input Two () relay outputs: - Four stage control - Fail-safe assignable One () analog output, (0)-0 ma / (0)-0 VDC - Selectable for low, high, or averaging One () VDC switched output Liquid Crystal Display (LCD) LED status indicators Accepts toxic or combustible gas, refrigerant, temperature or humidity secondary remote sensor input Built-in horn Keypad user interface Simple menu-driven programming Modular technology Overload & short-circuit protected NEMA X enclosure Easy maintenance NRTL Certification to STD UL 00- Specifications Electric Power supply VAC/VDC, -0%/+% 0/0 Hz, reverse polarity protected Power consumption VA (0. A) w/() remote sensor connected Sensor Performance Gas detected Nitrogen Dioxide (NO) Sensor element Electrochemical, diffusion Range Span 0-0 or 0-0 ppm factory calibrated, 0-0 standard Stability & Resolution ± 0. ppm of reading Repeatability ±.0 % of reading Long term output drift % signal loss/month Response time t90 0 sec. Sensor life expectancy years, normal operating environment Sensor coverage,000 sq.ft., max.,00 sq.ft. ( m², max. 9 m²), under ideal conditions Installation Location Mounting height to ft. (0. to.0 m) above Type of Control General Analog input Analog reading Stage level / setpoint - hysteresis/ switching differential floor for standard garage applications, consult with factory for other applications Four-stage (S to S) control, assignable up to two () binary/ relay, horn/audible alarm, and VDC / 0 ma switched outputs, i.e. low-high stage for relay output, horn / audible alarm and switched VDC at any stage for remote alarming One () -0 ma, for additional remote sensor, load ma / 00 Ω, reverse polarity protected Current and mean (average) value Field adjustable over full range, four () stages (S to S) per analog input, assignable to current or mean (average) value Selectable for each sensor point Page of Printed in USA 09

2 SPC-0 SPECIFICATION Type of Control (cont...) Digital input One (); can be assigned to any relay (R, R). - application Remote audio/visual alarm reset or override function Relay outputs (R, R) () SPDT (R), and () SPST-NC w/status LEDs or SPST-NO (R), jumper selectable Contact rating 0 VAC/VDC, 0. A, max. - each stage level (S-S) Assignable to any relay - sensor fail-safe Assignable to any stage level Time delay switching Selectable for make and brake of each sensor point (SP to SP) 0 9,999 seconds Analog output One (), (0) 0 ma, load 00 Ω; (0)-0 VDC, load 0K Ω; jumper selectable; polarity protected, assignable to low, high or averaging of sensor inputs VDC switched output One () VDC, 0 ma max Audible alarm 8 unit, enabled or disabled, selectable; assignable to stage level S, S, S or S Alarm acknowledgment Menu-driven and system reset function for latched relays User Interface Keypad type Refer to illustration Keypad User Interface Touch buttons Four () Status LED s Four (), for system on, stage status, and failure Digital display Liquid Crystal Display (LCD), two lines, characters per line, digit resolution - unit display Menu selectable, per sensor; ppm, %v/v, %LEL, F or %RH Environmental Permissible ambient - working temperature F to F (-0 C to 0 C) - storage temperature F to 8 F (- C to 0 C) - humidity to 9% RH, non-condensing - working pressure Atmospheric ± 0% Physical Enclosure (panel) - material Polycarbonate, UL 9-HB, fire-retardant - conformity UL 0 standards - color Light gray - protection NEMA X (IP) - installation Wall (surface) mounted, or single gang electrical box Dimensions (H x W x D). x. x.9 in. (0 x 0 x mm) Cable entry holes for / in. conduit for wall (surface) mounting and hole on back side of base plate for single gang electrical box mounting Wire connection Terminal blocks, screw type for lead wire Wire size Min. AWG (0. mm ) Max AWG (. mm ) Wire distance Max. loop resistance 0 Ω (= wire distance plus controller input resistance) Weight 0. lbs (0. kg) Approvals / Listings - unit rating NRTL Certification to STD ANSI/UL 00- CE EMV-Compliance 00/08/EWG Low voltage directive //EWG - relays (R-R) UL Recognized, E CSA, C. No. 0, No. (File No. LR98) - enclosure UL Listed, E080 CSA Certified, E080 Warranty Two years material and workmanship, months normal exposure for sensor element Options Enclosure Metal, wall-mount - material Galvanized steel w/zinc coating, corrosion resistant - color Light gray - protection NEMA, general purpose - installation Wall (surface) mounted, or single gang electrical box Dimensions (H x W x D).9 x.9 x.8 in. ( x x mm) Cable entry holes for / in. conduit for wall (surface) mounting and hole on back side of base plate for single gang electrical box mounting Page of Printed in USA 09

3 SPC-0 ORDERING INFORMATION SPC-0-00 US 0 Enclosures Wall NEMA, metal Wall NEMA X = Standard enclosure 00 0 Trip/Setpoints Factory set (for built-in sensor): Stage (S to S) S = Low ppm NO (Relay R) S = High ppm NO (Relay R) S = Audible ppm NO (built-in horn) S = Remote ppm NO ( VDC switched output disabled ) Special request Standard control system, ordering part number: SPC US, configuration includes: Digital, programmable controller with menu-driven keypad user interface, LCD & LEDs, VAC/VDC, 0/0 Hz NEMA X enclosure Built-in: () NO sensor/transmitter () Horn, audible alarm Input: () -0 ma, for remote sensor Outputs: () Relays, 0 VAC/VDC 0. A; - SPDT (R) and - SPST-NO/NC (R), jumper selectable () Switched VDC, 0 ma () (0)-0 ma or (0)-0 VDC, selectable Page of Printed in USA 09

4 SPC-0 USER INTERFACE & CONTROLLER Keypad User Interface Alarm Orange LED Alarm Red LED Failure Yellow LED Power Green LED Alarm Alarm INTEC Controls SPC Flashes when any stage level setpoint is exceeded; steady when any relay output is in manual override operation Flashes when high alarm stage or multiple alarm stage level setpoints are exceeded; steady when any relay output is in manual override operation Flashes when system or sensor fails Steady when power is ON Exit programming mode and saves settings; return to previous level or menu Enter Main Menus; scrolls through Main Menus and Sub Menus; increase or decrease a value Navigates through menus on the same level; moves cursor when inputing data Enter Sub Menus; accepts and stores data; silence horn (if assigned) Main Page & Main Menu INTEC Controls SPC System Errors Stage Status Relay Status Sensor Readings Relay Setup SP Setup System Operation All programming is made via the keypad user interface in combination with the display screen. Security is provided via two password levels. The lower level password () allows to override or to reset system status functions. The upper level password (900) allows all programming and override functions. Main Page Display After powered on, displays INTEC and part number and changes to sensor reading display unless a system error occurs; then the error is displayed. Main Menu Displays headings of System Errors, Stage Status Relay Status, Sensor Readings, Relay Setup, SP (Sensor Point) Setup, and System Setup. Sub Menu System Errors Displays errors, reset corrected errors, and historical error summary. Sub Menu Stage Status Displays status of each SP sensor point, stage level/setpoint exceeded. Sub Menu Relay Status Displays status and manual control of each output relay. Sub Menu Sensor Readings The current and mean/average values are displayed for each SP sensor point with sensing type and engineering unit (ppm, %v/v, %LEL, F, %RH). Sub Menu Relay Setup Enter and/or change parameters of each relay. - Assign de-energized or energized normal operation - Select steady or flashing function - Select horn function - Select latching or non-latching mode - Select digital input usage, and assign to any output relay - Set delay ON/OFF time Sub Menu SP Setup Enter and/or change parameters of each sensor point. - Activate sensor point - Select sensor point type (gas, temperature, humidity) - Select measuring range - Select sensor signal - Select stage/setpoint to - Select hysteresis - Set delay ON/OFF time - Select current or mean/average value - Assign sensor point fault to stage level setpoint - Assign setpoint to to any output relay - Assign to analog output Sub Menu System Setup Enter and/or change system parameters. - Select service mode - Display software version - Set next maintenance date - Select service phone number - Select averaging function, time and overlay, of any SP - Set date, time and time format - Change customer password - Set failure relay - Select power ON time - Select analog output function System Setup Page of Printed in USA 09

5 SPC-0 WIRING CONFIGURATION VAC/VDC Input Power Supply, and Analog Output AO0 X (0) -0 ma, or (0) -0 VDC*** VAC/VDC** -0%/%, 0/0 Hz ***Jumper output signal AO0 range selectors: 0-0% V-A X Over both pins Pins not covered Over both pins Pins not covered = VDC = ma = -0 ma / -0 VDC = 0-0 ma / 0-0 VDC Optional -0 Remote AT-...V Series Sensor/Transmitter Input SP0-0 ma, -wire sensor/transmitter -0 ma Common VAC or VDC** -0 ma, -wire loop-powered sensor/transmitter X Binary-Relay Outputs R0 and R0, VDC switched Output S, and Digital Input Digital input VDC, 0 ma Relays are normally de energized, 0 VAC/VDC 0. A S = Built-in horn S = Switched output **Jumper SPST relay (R) NC/NO selector: NC NO NO NC Common NC/NO** Common X Covers top two pins = SPST-NC Covers bottom two pins = SPST-NO S S R R -0 ma VDC** Twisted, shielded wire is recommended for - or - wire configurations. **/*** Attention: Only the same type of power, VAC or VDC, as supplied to the unit, is available for the remote transmitter. i.e. When VDC transmitter power is required, the unit must be powered with VDC. -wire loop powered transmitter can use the internal power. -wire transmitters that allow power common to DC common can use the same power supply to power the SPC and the transmitter. -wire transmitters that require separate power common from DC common must use a separate power source. Page of Printed in USA 09

Oxygen (O2) Single-Point Gas Detection System

Oxygen (O2) Single-Point Gas Detection System Oxygen (O) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in oxygen (O) sensor, accepts one analog remote device such as a secondary gas sensor, temperature or humidity

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

Combustible Gas Detection and Control System

Combustible Gas Detection and Control System Combustible Gas Detection and Control System DESCRIPTION Gas monitor with built-in combustible gas sensor, wall-mounted, accepts inputs from remote devices such as other gas sensors, temperature or humidity

More information

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6 Digital Gas Transmitters with Auxiliary s & Control Specifications subject to change without notice. USA 181011 Page 1 of 5 DESCRIPTION Digital RS-485 communicating, addressable toxic and combustible gas

More information

PolyGard 2-channel Gas Controller MGC-03

PolyGard 2-channel Gas Controller MGC-03 PolyGard 2-channel Gas Controller MGC-03 DESCRIPTION Gas measuring and monitoring controller based on state-ofthe-art micro-technology with integrated buzzer for continuous monitoring of the ambient air

More information

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours DESCRIPTION Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology with integrated sensor

More information

PolyGard Controller LGC/LG2-04. Multi-Point Controller Serial Number S00 User Manual Preliminary Version. August 11, 2006

PolyGard Controller LGC/LG2-04. Multi-Point Controller Serial Number S00 User Manual Preliminary Version. August 11, 2006 PolyGard Controller LGC/LG2-04 Multi-Point Controller Serial Number S00 User Manual Preliminary Version August 11, 2006 January 04, 2016 Revision Specifications subject to change without notice. USA 160104

More information

PolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen

PolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen PolyGard Single Point Controller SPC-X3-XX for Toxic Gases and Oxygen DESCRIPTION Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology with integrated sensor and

More information

Multi-Gas-Controller MGC2

Multi-Gas-Controller MGC2 Page 1 Aug. 2018 Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology for continuous monitoring of the ambient air to detect toxic and combustible gases, refrigerants

More information

Gas Central with built-in Gas Detector for Nitrogen Dioxide (NO 2

Gas Central with built-in Gas Detector for Nitrogen Dioxide (NO 2 Features Integrated (built-in NO2 sensor / detector (Electro chemical sensor type Measuring ranges 0-10 ppm, 0-20 ppm or 0-30 ppm LCD display to show actual in ppm Status LED indication Normal operation

More information

User Manual. PolyGard Gas Controller MGC3. Two-Channel Analog Gas Controller Serial Number _E _0907. September 2007

User Manual. PolyGard Gas Controller MGC3. Two-Channel Analog Gas Controller Serial Number _E _0907. September 2007 PolyGard Gas Controller MGC3 Two-Channel Analog Gas Controller Serial Number _E _0907 User Manual September 2007 January 04, 2016 Revision Specifications subject to change without notice. USA 160104 Page

More information

User Manual. PolyGard Single Point Controller SPC3-11XX. Single Point Gas Controller Serial Number _E_1007. May 2009

User Manual. PolyGard Single Point Controller SPC3-11XX. Single Point Gas Controller Serial Number _E_1007. May 2009 PolyGard Single Point Controller SPC3-11XX Single Point Gas Controller Serial Number _E_1007 User Manual May 2009 January 04, 2016 Revision Specifications subject to change without notice. USA 160104 Page

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases

PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases DESCRIPTION Gas measuring and monitoring controller based on stateof-the-art microtechnology with integrated sensor for continuous monitoring

More information

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006 PolyGard CO LC-1112 V3 Electrochemical analog carbon monoxide transmitters serial no. EC-S 002 User Manual August 29, 2006 January 04, 2016 Revision Specifications subject to change without notice. USA

More information

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM User Instructions For The Model 5200 Gas Monitor System To completely customize the specifications to your exact application, modifications to the following

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

PolyGard Digital Gas Controller DGC-05 RS-485 Bus

PolyGard Digital Gas Controller DGC-05 RS-485 Bus PolyGard Digital Gas Controller DGC05 RS485 DESCRIPTION Gas measuring controller series for continuous monitoring and warning of toxic, combustible and refrigerant gases and vapours. The gas controller

More information

CN7232 Advanced Garage Ventilation Controller

CN7232 Advanced Garage Ventilation Controller CN7232 Advanced Garage Ventilation Controller For Demand Controlled Ventilation Using: Carbon Monoxide (Gas Vehicles) Nitrogen Dioxide (Diesel) Combustible Gases (Alternative Fuels) Carbon Dioxide (Any

More information

Model D12-IR. Digital Gas Transmitter...

Model D12-IR. Digital Gas Transmitter... Model D12-IR Digital Gas Transmitter... ATI s Series D12 gas transmitter line now includes a versatile Infrared system that can be configured for LEL or select toxic gases. The D12-IR utilizes a compact

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

User Manual. PolyGard Single Point Controller SPC-43-20XX. Single Point Gas Controller for Refrigerant Gases Serial Number _E_.

User Manual. PolyGard Single Point Controller SPC-43-20XX. Single Point Gas Controller for Refrigerant Gases Serial Number _E_. PolyGard Single Point Controller SPC-43-20XX Single Point Gas Controller for Refrigerant Gases Serial Number _E_ User Manual January 2015 Phone: 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification

More information

Process Alarm Module RTA 421

Process Alarm Module RTA 421 Technical Information TI 074R/24/ae Process Alarm Module RTA 421 Alarm module and power supply for monitoring current or voltage signals Application Areas Plant and machine construction Panel builders

More information

Nitrogen Dioxide Stand-Alone Detector - Analog, ModBus

Nitrogen Dioxide Stand-Alone Detector - Analog, ModBus Features Internal function monitoring with integrated hardware watchdog Hardware and software according to SIL2 compliant development process Easy maintenance / calibration by replacing the sensor cartridge

More information

Product Manual SZ1145

Product Manual SZ1145 Product Manual SZ114 General Purpose Monitor Communicating Controls Description The SZ114 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum temperature

More information

Product Manual SZ1144

Product Manual SZ1144 Product Manual SZ1144 Refrigeration Temperature Monitor Communicating Controls Description The SZ1144 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum

More information

Universal Gas Detector

Universal Gas Detector Universal Gas Detector Instruction Manual PureAire Monitoring Systems, Inc. 557 Capital Drive Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free: 888-788-8050 pureairemonitoring.com

More information

Macurco DVP-120 Detection and Ventilation Control Panel

Macurco DVP-120 Detection and Ventilation Control Panel Macurco DVP-120 Detection and Ventilation Control Panel User Instructions IMPORTANT: Keep these User Instructions for reference. TABLE OF CONTENTS 1 Introduction 4 1.1 General Information 4 1.2 Features

More information

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL Installation and Operation Manual 2 GG-2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL GASGUARDIAN 2 3 2-Channel Controller OPERATING & INSTALLATION MANUAL GasGuardian 2 3 Operating and Installation Manual Table of Contents General description.... 3 Installation. 3 Locating the GasGuardian-2..

More information

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro A d e v i h c r D c o n e m u WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship

More information

User Manual. PolyGard SPC Carbon monoxide (CO) gas detection and control system serial no. SPC April 01, 2004

User Manual. PolyGard SPC Carbon monoxide (CO) gas detection and control system serial no. SPC April 01, 2004 PolyGard SPC-0 Carbon monoxide (CO) gas detection and control system serial no. SPC-0-0 00 0 User Manual April 0, 2004 User Manual - PolyGard CO SPC-0 Page 2 Carbon monoxide (CO) gas detection and control

More information

Carbon Monoxide CO Transmitter ADT-X3-1110

Carbon Monoxide CO Transmitter ADT-X3-1110 Page 1 Sep. 2017 CO transmitter including digital measurement value processing and temperature compensation for the continuous monitoring of the ambient air to detect carbon monoxide concentrations (CO).

More information

Warranty Registration

Warranty Registration WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship and materials for a period

More information

User Manual. PolyGard Single Point Controller SPC Single Point Gas Controller for Combustible Gases Serial Number _E_1008.

User Manual. PolyGard Single Point Controller SPC Single Point Gas Controller for Combustible Gases Serial Number _E_1008. PolyGard Single Point Controller SPC3-3300 Single Point Gas Controller for Combustible Gases Serial Number _E_1008 User Manual October, 2008 January 04, 2016 Revision PolyGard is a registered trademark

More information

Danfoss gas detection unit Type GD Heavy Duty

Danfoss gas detection unit Type GD Heavy Duty Data sheet Danfoss gas detection unit Type GD Heavy Duty The Heavy Duty gas detection units are used for monitoring and warning of hazardous Ammonia gas concentrations. They are intended for ATEX/ IECEx

More information

Carbon Monoxide (CO) Gas Detectors with (0)2-10 Vdc or (0)4-20 ma Output

Carbon Monoxide (CO) Gas Detectors with (0)2-10 Vdc or (0)4-20 ma Output Features Electrochemical sensor element (0)2-10 Vdc or (0)4-20 ma output, jumper selectable Standard IP65 plastic enclosure Measuring ranges 0-50 ppm 0-100 ppm 0-150 ppm 0-200 ppm 0-250 ppm 0-300 ppm 0-500

More information

GasSens. Self Checking Gas Sensors. Modular Gas Detector... Gas & Range Availability

GasSens. Self Checking Gas Sensors. Modular Gas Detector... Gas & Range Availability GasSens Modular Gas Detector... Self Checking Gas Sensors GasSens is a flexible component system providing a variety of options to meet individual gas detection and alarm requirements. From chemical and

More information

Danfoss gas detection Controller unit

Danfoss gas detection Controller unit Data sheet Danfoss gas detection Controller unit The gas detection Controller Unit is used for a centralized monitoring and warning of hazardous gas concentrations. The input signals for the controller

More information

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals Technical Information RTA421 Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals Application Plant and machine construction Panel builders Process monitoring Process

More information

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING Manual Contents Introduction...3 Valve compatibility...3 Features...3 Application examples...3 Ordering...3 Operating the EKC 347...4-5

More information

GLD-30 Gas Leak Detector

GLD-30 Gas Leak Detector GLD-30 Gas Leak Detector Installation, Operation & Maintenance General: The Archer Instruments GLD-30 is an ambient air monitor, used to detect the presence of a target gas (or gases) and to alert operators

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

Macurco DVP-120 / DVP-120M Detection and Ventilation Control Panel User Instructions

Macurco DVP-120 / DVP-120M Detection and Ventilation Control Panel User Instructions Macurco DVP-120 / DVP-120M Detection and Ventilation Control Panel User Instructions IMPORTANT: Keep these User Instructions for reference. TABLE OF CONTENTS 1 Introduction 4 1.1 DVP-120 General Information

More information

Gas Controller Module GC-06

Gas Controller Module GC-06 Page 1 Oct. 2015/2 Measuring, warning and controlling module for toxic, combustible and refrigerant gases and vapours. The gas controller series GC-06 is designed in accordance with the standard EN 50545-1.

More information

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES USER INSTRUCTIONS FOR THE CHEMGARD INFRARED GAS MONITOR SERIES To completely customize the specification to your exact application, modification to the

More information

Controllers. Instruction Manual WARNING

Controllers. Instruction Manual WARNING Controllers Instruction Manual WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like any piece of

More information

Pioneer-R16 Gas Monitor Operator s Manual

Pioneer-R16 Gas Monitor Operator s Manual Pioneer-R16 Gas Monitor Operator s Manual Edition 7/2/97 RKI INSTRUMENTS, INC RKI Instruments, Inc. 33248 Central Ave, Union City, CA 94587 (510) 441-5656 Chapter 1: Description About the Pioneer-R16 Gas

More information

Improve Performance and Reduce Maintenance Costs. Model Q45D. Dissolved Oxygen Monitor...

Improve Performance and Reduce Maintenance Costs. Model Q45D. Dissolved Oxygen Monitor... Improve Performance and Reduce Maintenance Costs Model Q45D Dissolved Oxygen Monitor... Why Throw Away Money? Why Throw Away Money? ATI s Model Q45D Dissolved Oxygen monitor is designed to provide reliable

More information

Instruction Manual WARNING

Instruction Manual WARNING Controllers Instruction Manual WARNING THIS MANAUL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like any piece of

More information

Temperature Controllers

Temperature Controllers Model TEC-4100 1/4 DIN Model TEC-4100 1/4 DIN Temperature Controller Ordering Code: Power Input BOX 1 4 = 90-250 VAC 5 = 11-26 VAC / VDC TEC-4100- Configurable for 4 Programmable Outputs and NEMA 4X/IP65

More information

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification 1.0 This specification details the attributes and operating characteristics of the MSA Ultima X Series sensors/transmitters.

More information

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual Toxic and Explosive Smart Gas Monitor PN 151022/151023 Installation and User Manual Quest Controls, Inc. 208 9 th Street Dr. West Palmetto, FL 34221 www.questcontrols.com Phone: (941) 729-4799 Fax: (941)

More information

Beacon 800 Gas Monitor Operator s Manual

Beacon 800 Gas Monitor Operator s Manual Beacon 800 Gas Monitor Operator s Manual Part Number: 71-0037RK Revision: F Released: 4/18/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be

More information

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector.

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector. Introduction United Safety applies the detection system as a multi-point monitoring for toxic gases, combustibles and oxygen hazards. Self-powered and solar-capable, the features unequaled versatility,

More information

Duct and Rough Service Carbon Monoxide Sensor

Duct and Rough Service Carbon Monoxide Sensor Product Identification and Overview Duct and Rough Service Carbon Monoxide Sensor BAPI s Carbon Monoxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations.

More information

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features. CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse

More information

Series RSM Room Status Monitor. Specifications - Installation and Operating Instructions 5-13/32 [137.16] 8 [203.20] 4-5/8 [117.

Series RSM Room Status Monitor. Specifications - Installation and Operating Instructions 5-13/32 [137.16] 8 [203.20] 4-5/8 [117. Series RSM Room Status Monitor Specifications - Installation and Operating Instructions Bulletin p-3-rsm 5-13/32 [137.16] 1-5/8 [41.66] 2-5/32 [55.12] 8 [203.20] 4-5/8 [117.09] TUBING HEADER PORT ROOM

More information

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors Dräger Polytron 5700 Fixed Gas Detector Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors Dräger Polytron 5700 Including e-box for increased safety wiring The Dräger

More information

DIGITAL METERS Large Display Temperature Meters Instruction Manual

DIGITAL METERS Large Display Temperature Meters Instruction Manual DIGITAL METERS Large Display Temperature Meters PD755 PD756 PD757 Handles Thermocouple & RTD Inputs with Simplicity J, K, T, E, R, & S Thermocouples 100 Ω Platinum RTD (0.00385 or 0.00392 curve) Large

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS INSTALLATI AND OPERATING INSTRUCTIS PRODUCTS CMD Series CO Detectors FGD Series Refrigerant Detectors AGD Series Toxic Gas Detectors CGD Series Combustible Gas Detectors (All transmitters are factory set

More information

Sensor unit MC2 with analog output for Freon gases and refrigerants

Sensor unit MC2 with analog output for Freon gases and refrigerants Page 1 Dec. 2018 Sensor unit MC2 with analog output for Freon gases and refrigerants Exchangeable sensor unit including digital value processing and self control for the continuous monitoring of the ambient

More information

Remote Display Alarm Indicator for Oxygen monitor

Remote Display Alarm Indicator for Oxygen monitor Remote Display Alarm Indicator for Oxygen monitor (Part number 99091) The Remote Display Alarm Indicator is designed to display remote oxygen concentration information from PureAire oxygen monitors. All

More information

JDDT1 - Single Stage Digital Thermostat

JDDT1 - Single Stage Digital Thermostat JDDT1 - Single Stage Digital Thermostat CAUTION NOTICE: The thermostat must be installed by authorized professionals. It should be located in a place free of vibrations, impacts, and corrosive gases. SET

More information

Operation Manual. Rev. E GEM-II Self Contained Gas Detector.

Operation Manual. Rev. E GEM-II Self Contained Gas Detector. Operation Manual Rev. E 2014.10 GEM-II Self Contained Gas Detector www.critical-environment.com GEM-II - Operation Manual Rev. E 2014.10 Table of Contents 1 POLICIES... 5 1.1 Important Note...5 1.2 Warranty

More information

Carbon Monoxide (CO) Gas Detector March 15 GCO 300

Carbon Monoxide (CO) Gas Detector March 15 GCO 300 GCO Carbon Monoxide (CO) Gas Detector March 15 Features Output 4-20 ma or 2-10 Vdc Power supply 24 Vdc Ranges 0-100 ppm or 0-300 ppm IP65 enclosure with quick locking screws Digital measurement value processing

More information

Guidelines for the Design Engineer

Guidelines for the Design Engineer Carbon Monoxide (CO) Detection and Control Systems for Parking Structures Guidelines for the Rev 1.13 1 General Overview... 3 1.1 Carbon Monoxide and Its Effects... 3 2 Installation and Application Codes

More information

CLEANROOM MONITOR CR3A Network - Installation Instructions

CLEANROOM MONITOR CR3A Network - Installation Instructions CLEANROOM MONITOR CR3A Network - Installation Instructions INTRODUCTION The CR3 Series Cleanroom Monitor, was developed specifically to allow for monitoring of confined spaces with accuracy and reliability.

More information

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08 GasScanner 8C Eight Channel Monitor Operator s Manual MINT-0281-XX Rev. A 01/29/08 Product Warranty Matheson Tri-Gas, Inc., warrants gas alarm equipment sold by us to be free from defects in materials,

More information

Beacon 110 Gas Monitor Operator s Manual

Beacon 110 Gas Monitor Operator s Manual Beacon 110 Gas Monitor Operator s Manual Part Number: 71-0110RK Revision: H Released: 12/5/17 RKI Instruments, Inc. www.rkiinstruments.com Product Warranty RKI Instruments, Inc., warrants gas alarm equipment

More information

Instruction Manual December 2001 ENACOCU02

Instruction Manual December 2001 ENACOCU02 SENACOCU02 Instruction Manual December 2001 ENACOCU02 Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected

More information

Instruction Manual August sitrans CU 02

Instruction Manual August sitrans CU 02 Instruction Manual August 2005 sitrans CU 02 Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment.

More information

PureAire Combo O 2 / CO 2 Monitor

PureAire Combo O 2 / CO 2 Monitor PureAire Combo O 2 / CO 2 Monitor Instruction Manual PureAire Monitoring Systems, Inc. 557 Capital Drive Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free: 888-788-8050 pureairemonitoring.com

More information

I/A Series 716C 1/16 DIN Temperature Controller

I/A Series 716C 1/16 DIN Temperature Controller Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of

More information

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE / 3 GM20 Digital Ground Continuity Relay For AC Systems Technical Bulletin NAE03230 / 0.20 GM20 Ground continuity monitor For AC systems Description The GM20 monitors the loop resistance of ground conductors

More information

Air Check O 2 Deficiency Monitor 0-25%

Air Check O 2 Deficiency Monitor 0-25% Air Check O 2 Deficiency Monitor 0-25% Instruction Manual RS-485 Revision 4.05 Part number 99066 PureAire Monitoring Systems, Inc. 557 Capital Drive Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax:

More information

GAS PLUS ALARM SYSTEM

GAS PLUS ALARM SYSTEM GAS PLUS -IR SERIES 4688-IR COMBUSTIBLE GAS OR CARBON DIOXIDE TRANSMITTER GAS PLUS -IR TRANSMITTER SERIES 4688-IR COMBUSTIBLE GAS OR CARBON DIOXIDE TRANSMITTER The Scott Gas Plus -IR Model 4688 IR Gas

More information

Stand Alone DYNAGARD SP Operation Manual

Stand Alone DYNAGARD SP Operation Manual Stand Alone DYNAGARD SP Operation Manual Contents Page General Description 1 Detection Principle 1 For Your Safety 1 Design 2 Mounting 2 Mounting Position of DYNAGARD SP 2 Installation of Electrical Connections

More information

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications Instruction Manual Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications Manual PCT30006, Revision 9/20/2016 The PCT30006 control enclosure incorporates

More information

Air Check O 2 Deficiency Monitor 0-25%

Air Check O 2 Deficiency Monitor 0-25% Air Check O 2 Deficiency Monitor 0-25% Instruction Manual For model KF-25 Part number 99035 PureAire Monitoring Systems, Inc. 557 Capital Drive Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax: 847-726-6051

More information

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11 Table of Contents 1. OVERVIEW... 3 2. SYSTEM LAYOUT... 4 3. SPECIFICATIONS... 8 3.1 SYSTEM COMPONENTS...9 3.2 PLC INPUTS AND OUTPUTS...9 3.3 FUNCTION KEYS...10 3.4 DEFAULT SET POINTS AND TIMERS...10 4.

More information

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A GasScanner 1C Single Channel Monitor Operator s Manual MINT-0278-XX Rev A Product Warranty Matheson Tri-Gas, Inc., warrants gas alarm equipment sold by us to be free from defects in materials, workmanship,

More information

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Process & TeMPerATUre UniversAl input DigiTAl MeTers Process & TeMPerATUre UniversAl input DigiTAl MeTers nova PD56 series Thermocouple, rtd, & Process inputs Universal Power supply 1-24 va c Up to 3 Alarm relays retransmitting 4-2 ma output input Max/Min

More information

ULTIMA X5000. MSAX5000.com

ULTIMA X5000. MSAX5000.com ULTIMA X5000 MSAX5000.com WE KNOW YOU RE TIRED OF... NEEDING TO DISCONNECT POWER BEFORE CHANGING A SENSOR REMEMBERING HOW TO CALIBRATE THIS THING HAVING TO PULL SO MUCH WIRE AT EVERY GAS DETECTOR INSTALLATION...

More information

Air Check O 2 Remote Monitor 25%

Air Check O 2 Remote Monitor 25% Air Check O 2 Remote Monitor 25% Instruction Manual Part number 99087 PureAire Monitoring Systems, Inc. 557 Capital Drive Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free: 888-788-8050

More information

ALTAIR 5X Multigas Detector Product Specification

ALTAIR 5X Multigas Detector Product Specification ALTAIR 5X Multigas Detector Product Specification PHYSICAL CHARACTERISTICS Gas delivery Size, pumped unit without IR Size, pumped unit with IR Weight Handling Case material Environmental protection Display

More information

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS NOVA PD56 Series Thermocouple, RTD, & Process Inputs Universal Power Supply 1-24 VAC Up to 3 Alarm Relays Retransmitting 4-2 ma Output Input Max/Min

More information

Model D12. Digital Gas Transmitter

Model D12. Digital Gas Transmitter Model D12 Digital Gas Transmitter Gas detection systems come in all shapes and sizes. Some require simple 4-20 ma transmission. Some are better suited to local alarm relay functions. Some really require

More information

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08 GasScanner 4C Four Channel Monitor Operator s Manual MINT-0280-XX Rev. A 02/25/08 Product Warranty Matheson Tri-Gas., warrants gas alarm equipment sold by us to be free from defects in materials, workmanship,

More information

S5000 Gas Monitor. GMS5000.com

S5000 Gas Monitor. GMS5000.com S5000 Gas Monitor GMS5000.com A DETECTOR AS TOUGH AS YOU ARE... LOWER TEMPERATURE SPEC?... ARCTIC WINTERS IT HAS TO BE THE MOST RELIABLE PIECE OF EQUIPMENT OUT HERE IF THE DETECTOR DOESN T WORK, WE DON

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features September 007 DIESEL Engine Fire Pump Controllers Features FD0 Diesel Engine Controllers 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller.

More information

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements Specifications COMMANDER 150 Universal Process Indicator High visibility 6-digit LED display the clearest view of your process status 0.1% measurement accuracy precise indication of process measurement

More information

Air Check O 2 Sample Draw Monitor

Air Check O 2 Sample Draw Monitor Air Check O 2 Sample Draw Monitor Instruction Manual Part number 99019 without horn, Part number 99029 with horn PureAire Monitoring Systems, Inc. 557 Capital Drive Lake Zurich, Illinois 60047 Phone: 847-726-6000

More information

Nov 08 PRODUCT SPECIFICATION SHEET

Nov 08 PRODUCT SPECIFICATION SHEET Honeywell UDC1200 and UDC1700 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS 51-52-03-35 Nov 08 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC1200 & UDC1700 are microprocessor-based 1/16 DIN and 1/8 DIN

More information

PointGard II. Operating Manual

PointGard II. Operating Manual PointGard II Operating Manual For Your Safety For Your Safety Strictly follow the assembly and installation instructions The instrument must be calibrated at intervals recommended in the operating manual

More information

SIL 2. Ultima X Series Gas Monitors CERTIFIED

SIL 2. Ultima X Series Gas Monitors CERTIFIED Ultima X Series Gas Monitors 5 Now with SIL 2 CERTIFIED Products Versatile fixed instruments provide continuous monitoring of many hazardous gases using catalytic, electrochemical, and infrared gas detection

More information

Operation Manual. Rev. I SCC Self Contained Controller.

Operation Manual. Rev. I SCC Self Contained Controller. Operation Manual Rev. I 2016.06 SCC Self Contained Controller www.critical-environment.com SCC - Operation Manual Rev. I 2016.06 Table of Contents 1 POLICIES... 5 1.1 Important Note...5 1.2 Warranty Policy...5

More information

UDC100 Universal Digital Controller Specifications

UDC100 Universal Digital Controller Specifications UDC100 Universal Digital Controller Specifications 51-52-03-29 November 1999 Overview The UDC100 Universal Digital Controller is a microprocessor-based 1/4 DIN low cost temperature controller. It combines

More information

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd. F-2000 PC and AO OUTPUT BOARDS INSTRUCTION MANUAL Blue-White R Industries, Ltd. 500 Business Drive Huntington Beach, CA 92649 USA Phone: 714-89-8529 FAX: 714-894-9492 E mail: sales@blue-white.com or techsupport@blue-white.com

More information