Committee Comment No. 212-NFPA [ Section No [Excluding

Size: px
Start display at page:

Download "Committee Comment No. 212-NFPA [ Section No [Excluding"

Transcription

1 of 27 12/12/ :23 PM Committee Comment No. 212-NFPA [ Section No [Excluding any Sub-Sections] ] This was a Second Revision that has been modified or deleted as the result of Second Correlating Revision: SCR-1-NFPA NFPA 30 Committee Comments Page 1 of 30

2 of 27 12/12/ :23 PM Where automatic sprinkler systems or low-expansion foam-water sprinkler systems are used to protect storage of liquids, Figure (a), Figure (b), or Figure (c), whichever is applicable, and the appropriate table in Section 16.5 shall be used to determine protection criteria. Figure (a) Fire Protection Criteria Decision Tree for Miscible and Nonmiscible Flammable and Combustible Liquids in Metal Containers. Figure (b) Fire Protection Criteria Decision Tree for Miscible and Nonmiscible Flammable and Combustible Liquids in Nonmetallic Containers. Figure (c) Fire Protection Criteria Decision Tree for Miscible Flammable and Combustible Liquids in Nonmetallic Containers. NFPA 30 Committee Comments Page 2 of 30

3 of 27 12/12/ :23 PM Supplemental Information File Name Public_Comment_No._67_Figure_16.4.1_a_.pdf Description Shows revision to figure (a) Submitter Information Verification Submitter Full Name: FLC-SWC Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Jun 28 09:31:51 EDT 2016 Committee Statement Committee Statement: Note: Response Message: The technical committee has amended Figure (a) to reflect the adoption of new Table via SR#210. The Public Comment was initially accepted by the TC and resulted in Second Revision (SR) # 212. However, the Correlating Committee subsequently overturned the SR # 212 relegating the SR to CC # 212. Additionally, the Correlating Committee may or may not have created a Second Correlating Revision (SCR) # SCR-1-NFPA Accordingly, a NITMAM could be submitted to accept the resulting CC since this accomplishes that same action as 'accepting" the PC or to reject the SCR. Public Comment No. 67-NFPA [Section No [Excluding any Sub-Sections]] Ballot Results NFPA 30 Committee Comments Page 3 of 30

4 Revise Figure (a) as follows: Protected using Table , , or , or NFPA 30 Committee Comments Page 4 of 30

5 of 27 12/12/ :23 PM This item has passed ballot 31 Eligible Voters 3 Not Returned 26 Affirmative All 1 Affirmative with Comments 1 Negative with Comments 0 Abstention Not Returned Bellamy, Tracey D. Cosey, William V. F. Fitzgerald, Keric M. Affirmative All Apostoluk, Peter R. Carter, Glen A. De Taeye, Claire V. Foley, John J. Havens, Dwight H. Hicks, Donald B. Hild, Richard J. Kidd, Todd M. Kirby, David C. Kraus, Richard S. Kulpit, Jonathan LeBlanc, John A. Lentz, Thomas S. Nauman, Susan Nugent, David P. Ordile, Anthony M. Ozog, Nicholas Riegel, Roland A. Rindfuss, Lee T. Seuss, Jr., George A. Stephens, Ronald J. Swenson, David C. Willse, Peter J. NFPA 30 Committee Comments Page 5 of 30

6 of 27 12/12/ :23 PM Wright, Scott Wypychoski, Kevin M. de Nooij, Tom Affirmative with Comment Workman, Martin H. agree with committee Negative with Comment Wechsler, David B. After having reviewed the committee actions, the original submittal and the response from John Leblanc on SR210- I find the complete actions on all these related changes ill advised and We should not advocate an unlimited conditions. Again as my common voting comment: The proposed Scheme E is linked to the justification provided in Public Comment No. 52, which was associated with the test results of a single fire test conducted at UL. The protection recommendations are based on a single spill scenario and a single ignition source location. The two sprinklers that operated during the test both activated at 6 seconds after ignition, which leads to questions of whether a more delayed or relocated ignition or spill location, perhaps to a higher location in the rack structure, might have produced unsatisfactory results. It is unprecedented to base the entire protection scheme for an unlimited area, unlimited storage quantity of drums of Class II liquids on a worst case scenario of operating 3 in-rack sprinklers, particularly when that basis represents a single fire test and contemplates only a single additional operating sprinkler beyond the two that operated in the cited test as the factor of safety. NFPA 30 Committee Comments Page 6 of 30

7 of 27 12/12/ :23 PM Committee Comment No. 202-NFPA [ Section No [Excluding any Sub-Sections] ] This was a Second Revision that has been modified or deleted as the result of Second Correlating Revision: SCR-2-NFPA Paragraphs through and their related tables, Table through Table , shall be used to determine the protection criteria and storage arrangement for the applicable liquid class, container type, and storage configuration, as described in through and subject to the provisions of Submitter Information Verification Submitter Full Name: FLC-SWC Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Jun 21 14:14:21 EDT 2016 Committee Statement Committee Statement: Note: Response Message: This section has been revised to reflect the adoption of new Table via SR#210. The Public Comment was initially accepted by the TC and resulted in Second Revision (SR) # 202. However, the Correlating Committee subsequently overturned the SR # 202 relegating the SR to CC # 202. Additionally, the Correlating Committee may or may not have created a Second Correlating Revision (SCR) # SCR-2-NFPA Accordingly, a NITMAM could be submitted to accept the resulting CC since this accomplishes that same action as 'accepting" the PC or to reject the SCR. Public Comment No. 52-NFPA [Section No [Excluding any Sub-Sections]] Ballot Results This item has passed ballot 31 Eligible Voters 3 Not Returned 26 Affirmative All 1 Affirmative with Comments 1 Negative with Comments NFPA 30 Committee Comments Page 7 of 30

8 of 27 12/12/ :23 PM 0 Abstention Not Returned Bellamy, Tracey D. Cosey, William V. F. Fitzgerald, Keric M. Affirmative All Apostoluk, Peter R. Carter, Glen A. De Taeye, Claire V. Foley, John J. Havens, Dwight H. Hicks, Donald B. Hild, Richard J. Kidd, Todd M. Kirby, David C. Kraus, Richard S. Kulpit, Jonathan LeBlanc, John A. Lentz, Thomas S. Nauman, Susan Nugent, David P. Ordile, Anthony M. Ozog, Nicholas Riegel, Roland A. Rindfuss, Lee T. Seuss, Jr., George A. Stephens, Ronald J. Swenson, David C. Willse, Peter J. Wright, Scott Wypychoski, Kevin M. de Nooij, Tom Affirmative with Comment Workman, Martin H. agree with committee NFPA 30 Committee Comments Page 8 of 30

9 of 27 12/12/ :23 PM Negative with Comment Wechsler, David B. After having reviewed the committee actions, the original submittal and the response from John Leblanc on SR210- I find the complete actions on all these related changes ill advised and We should not advocate an unlimited conditions. Again as my common voting comment: The proposed Scheme E is linked to the justification provided in Public Comment No. 52, which was associated with the test results of a single fire test conducted at UL. The protection recommendations are based on a single spill scenario and a single ignition source location. The two sprinklers that operated during the test both activated at 6 seconds after ignition, which leads to questions of whether a more delayed or relocated ignition or spill location, perhaps to a higher location in the rack structure, might have produced unsatisfactory results. It is unprecedented to base the entire protection scheme for an unlimited area, unlimited storage quantity of drums of Class II liquids on a worst case scenario of operating 3 in-rack sprinklers, particularly when that basis represents a single fire test and contemplates only a single additional operating sprinkler beyond the two that operated in the cited test as the factor of safety. NFPA 30 Committee Comments Page 9 of 30

10 of 27 12/12/ :23 PM Committee Comment No. 203-NFPA [ Section No [Excluding any Sub-Sections] ] This was a Second Revision that has been modified or deleted as the result of Second Correlating Revision: SCR-3-NFPA Table through Table shall apply only to stable liquids. Submitter Information Verification Submitter Full Name: FLC-SWC Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Jun 21 14:16:06 EDT 2016 Committee Statement Committee Statement: Note: Response Message: This section has been revised to reflect the adoption of new Table via SR#210. The Public Comment was initially accepted by the TC and resulted in Second Revision (SR) # 203. However, the Correlating Committee subsequently overturned the SR # 203 relegating the SR to CC # 203. Additionally, the Correlating Committee may or may not have created a Second Correlating Revision (SCR) # SCR-3-NFPA Accordingly, a NITMAM could be submitted to accept the resulting CC since this accomplishes that same action as 'accepting" the PC or to reject the SCR. Public Comment No. 53-NFPA [Section No [Excluding any Sub-Sections]] Ballot Results This item has passed ballot 31 Eligible Voters 3 Not Returned 26 Affirmative All 1 Affirmative with Comments 1 Negative with Comments 0 Abstention NFPA 30 Committee Comments Page 10 of 30

11 0 of 27 12/12/ :23 PM Not Returned Bellamy, Tracey D. Cosey, William V. F. Fitzgerald, Keric M. Affirmative All Apostoluk, Peter R. Carter, Glen A. De Taeye, Claire V. Foley, John J. Havens, Dwight H. Hicks, Donald B. Hild, Richard J. Kidd, Todd M. Kirby, David C. Kraus, Richard S. Kulpit, Jonathan LeBlanc, John A. Lentz, Thomas S. Nauman, Susan Nugent, David P. Ordile, Anthony M. Ozog, Nicholas Riegel, Roland A. Rindfuss, Lee T. Seuss, Jr., George A. Stephens, Ronald J. Swenson, David C. Willse, Peter J. Wright, Scott Wypychoski, Kevin M. de Nooij, Tom Affirmative with Comment Workman, Martin H. agree with committee Negative with Comment NFPA 30 Committee Comments Page 11 of 30

12 1 of 27 12/12/ :23 PM Wechsler, David B. After having reviewed the committee actions, the original submittal and the response from John Leblanc on SR210- I find the complete actions on all these related changes ill advised and We should not advocate an unlimited conditions. Again as my common voting comment: The proposed Scheme E is linked to the justification provided in Public Comment No. 52, which was associated with the test results of a single fire test conducted at UL. The protection recommendations are based on a single spill scenario and a single ignition source location. The two sprinklers that operated during the test both activated at 6 seconds after ignition, which leads to questions of whether a more delayed or relocated ignition or spill location, perhaps to a higher location in the rack structure, might have produced unsatisfactory results. It is unprecedented to base the entire protection scheme for an unlimited area, unlimited storage quantity of drums of Class II liquids on a worst case scenario of operating 3 in-rack sprinklers, particularly when that basis represents a single fire test and contemplates only a single additional operating sprinkler beyond the two that operated in the cited test as the factor of safety. NFPA 30 Committee Comments Page 12 of 30

13 2 of 27 12/12/ :23 PM Committee Comment No. 204-NFPA [ Section No ] This was a Second Revision that has been modified or deleted as the result of Second Correlating Revision: SCR-4-NFPA The Fire Test Ref. number given for each entry in Table through Table shall be used to identify in Section D.2 or D.3 the information on the fire tests on which the protection criteria for that entry are based. Submitter Information Verification Submitter Full Name: FLC-SWC Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Jun 21 14:18:47 EDT 2016 Committee Statement Committee Statement: Response Message: This section has been revised to reflect the adoption of new Table via SR#210 and explanatory reference information in Annex D via SR#206. Public Comment No. 54-NFPA [Section No ] Ballot Results This item has passed ballot 31 Eligible Voters 3 Not Returned 26 Affirmative All 1 Affirmative with Comments 1 Negative with Comments 0 Abstention Not Returned Bellamy, Tracey D. Cosey, William V. F. NFPA 30 Committee Comments Page 13 of 30

14 3 of 27 12/12/ :23 PM Fitzgerald, Keric M. Affirmative All Apostoluk, Peter R. Carter, Glen A. De Taeye, Claire V. Foley, John J. Havens, Dwight H. Hicks, Donald B. Hild, Richard J. Kidd, Todd M. Kirby, David C. Kraus, Richard S. Kulpit, Jonathan LeBlanc, John A. Lentz, Thomas S. Nauman, Susan Nugent, David P. Ordile, Anthony M. Ozog, Nicholas Riegel, Roland A. Rindfuss, Lee T. Seuss, Jr., George A. Stephens, Ronald J. Swenson, David C. Willse, Peter J. Wright, Scott Wypychoski, Kevin M. de Nooij, Tom Affirmative with Comment Workman, Martin H. agree with committee Negative with Comment Wechsler, David B. After having reviewed the committee actions, the original submittal and the response from John Leblanc on SR210- I find the complete actions on all these related changes ill advised and We should NFPA 30 Committee Comments Page 14 of 30

15 4 of 27 12/12/ :23 PM not advocate an unlimited conditions. Again as my common voting comment: The proposed Scheme E is linked to the justification provided in Public Comment No. 52, which was associated with the test results of a single fire test conducted at UL. The protection recommendations are based on a single spill scenario and a single ignition source location. The two sprinklers that operated during the test both activated at 6 seconds after ignition, which leads to questions of whether a more delayed or relocated ignition or spill location, perhaps to a higher location in the rack structure, might have produced unsatisfactory results. It is unprecedented to base the entire protection scheme for an unlimited area, unlimited storage quantity of drums of Class II liquids on a worst case scenario of operating 3 in-rack sprinklers, particularly when that basis represents a single fire test and contemplates only a single additional operating sprinkler beyond the two that operated in the cited test as the factor of safety. NFPA 30 Committee Comments Page 15 of 30

16 5 of 27 12/12/ :23 PM Committee Comment No. 210-NFPA [ New Section after ] This was a Second Revision that failed ballot Table shall apply to the following: (1) Automatic sprinkler protection or foam-water sprinkler protection (2) Single- and double-row rack storage (3) Class II and Class III nonmiscible and Class II and Class III miscible liquids (4) Relieving-style metal containers Table Design Criteria for Sprinkler Protection or Foam-Water Sprinkler Protection of Single- and Double-Row Rack Storage of Class II and Class III Liquids in Relieving-Style Metal Containers Capacity (gal) Maximum Storage Height (ft) Maximum Ceiling Height (ft) Sprinkler Protection Ceiling Sprinkler Protection In-Rack Sprinklers Notes Fire Test Ref. >5 and 60 Unlimited Unlimited See , Fire Protection System Design Scheme E See , Fire Protection System Design Scheme E 1, 2 See Section D.3 (new) For SI units, 1 gal = 3.8 L, 1 ft = 0.3 m. Notes: (1) Minimum aisle width in all cases is 6 ft (1.8 m). (2) Maximum rack depth in all cases is 9 ft (2.7 m). Submitter Information Verification Submitter Full Name: FLC-SWC Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Jun 27 13:47:49 EDT 2016 Committee Statement NFPA 30 Committee Comments Page 16 of 30

17 16 of 27 12/12/ :23 PM Committee Statement: Response Message: The technical committee has reviewed all of the supporting documentation that substantiates the inclusion of new Table , including the answers to all questions that were raised by the technical committee when the public input was first submitted. Based on its review, the technical committee agrees that this new table provides acceptable fire protection system design criteria for the commodities to which the table applies. Public Comment No. 55-NFPA [New Section after ] Ballot Results This item has failed ballot 31 Eligible Voters 3 Not Returned 13 Negative with Comments 14 Affirmative All 0 Affirmative with Comments 1 Abstention Not Returned Bellamy, Tracey D. Cosey, William V. F. Fitzgerald, Keric M. Negative with Comment Apostoluk, Peter R. I agree with John LeBlanc. De Taeye, Claire V. I agree with John LeBlanc's comments. Havens, Dwight H. I have reviewed and agree with the concerns raised by Mr. LeBlanc. Hicks, Donald B. I agree with John Leblanc s comments. Kirby, David C. After reviewing John Leblanc's comments, they confirm my thoughts from the Meeting - that the tests were not conservative enough to meet worst credible case. I believe that there should at least be a safety factor. Unfortunately, I am not qualified to recommend a safety factor. Kraus, Richard S. agree with Mr LeBlanc comment Kulpit, Jonathan NFPA 30 Committee Comments Page 17 of 30

18 7 of 27 12/12/ :23 PM This protection scheme for unlimited storage height was extrapolated from one fire test which does not represent a reasonable worst case scenario of what the protection scheme aims to protect. That fire test did not address the possibility that a spill fire originating at the top and spilling down the face of a storage arrangement greater than four barrier levels tall may open more than the seven sprinklers (three at the top level and two on each of the next two lower levels) required to be calculated and / or involve ceiling sprinklers which are not required to be calculated. The protection scheme should not permit unlimited height without requiring hydraulic consideration of all sprinkler levels or proving with multiple fire tests that the number of sprinkler levels involved is independent of the height of the arrangement / number of barrier levels below the spill fire level of origin. LeBlanc, John A. The testing that was done used a ~34 ft high rack (4 tiers of filled drums, 3 tiers of empty drums) in a 48 ft high building. Actual filled drums were only used in the lower 4 tiers of the rack. The spill location was located at the bottom of the third tier instead of at the bottom of the highest stored drum. Two barrier/in-rack levels were provided. No ceiling sprinklers were provided. I believe the testing has clearly shown that this in-rack arrangement will meet the goal of keeping steel drums cool when they are exposed to a spill fire, however, the next critical element, the sprinkler system design, was not validated to support unlimited storage heights and roof heights. When using large orifice, quick response sprinklers at the ceiling or as in-racks it is critical to design the sprinkler system for an adequate number of sprinklers to conserve the water supply. Past full scale fire tests by FM Global with barriers installed in racks has shown that a spill down the face of an array will operate a large number of quick response in-rack sprinklers at every barrier level. Extrapolating the test results beyond the building height and storage height tested ignores this potential. Also, if the spill was initiated at the bottom of the top level of storage, there would have been a possibility of ceiling sprinkler involvement if ceiling sprinklers were installed. Since this protection option involves the use of K 25.2 sprinklers flowing 138 gpm each, operating more sprinklers than were included in the design can quickly overtax a water supply. The bottom line is this testing does not support extrapolating the results to unlimited storage heights when large containers are being stored. Ordile, Anthony M. I am concerned about this proposed Table and Scheme being developed on a single fire test. The TC has previously developed the protection criteria Tables based on redundant large-scale fire tests. My concern about basing this on a single test is emphasized by the fact that the in-rack sprinklers operated at 6 seconds after ignition. Perhaps a second test altering the location of the spill and ignition would yield different results that could have resulted in a delay of sprinkler operation that may have also caused some drums of product to be more involved and more than 2 rack sprinklers to operate. I also have concern over the unlimited storage height involving drums, especially when standard lift trucks are involved. The unlimited ceiling height is a concern with larger containers should the spill incident occur in an aisle or staging area. Riegel, Roland A. A single test is not sufficient. There is a need for additional testing that would substantiate unlimited storage heights for drums. Additional test scenarios should evaluate if an alternate ignition source / location and subsequent fire propagation would bypass the rack sprinkler systems and operate ceiling sprinklers. Wechsler, David B. After having reviewed the committee actions, the original submittal and the response from John Leblanc on SR210- I find the complete actions on all these related changes ill advised and We should not advocate an unlimited conditions. Again as my common voting comment: The proposed Scheme E is linked to the justification provided in Public Comment No. 52, which was associated with the test results of a single fire test conducted at UL. The protection recommendations are based on a single spill scenario and a single ignition source location. The two sprinklers that operated during the test both activated at 6 seconds after ignition, which leads to questions of whether a more delayed or relocated ignition or spill location, perhaps to a higher location in the rack structure, might have produced unsatisfactory results. It is unprecedented to base the entire protection scheme for an NFPA 30 Committee Comments Page 18 of 30

19 8 of 27 12/12/ :23 PM unlimited area, unlimited storage quantity of drums of Class II liquids on a worst case scenario of operating 3 in-rack sprinklers, particularly when that basis represents a single fire test and contemplates only a single additional operating sprinkler beyond the two that operated in the cited test as the factor of safety. Willse, Peter J. After reviewing John Leblanc's comments, I vote negative. Workman, Martin H. The fire test provided showed an exceptional fast operation of the sprinkler within the rack. This occurred because the fuel was ignited upon fuel release. In the past, fuel was allowed to discharge from the container prior to igniting the fuel, which would have created a spill fire and would have had slower sprinkler operation and in the long term would have activated more sprinklers within the rack area. I don't think the sprinkler operation would be realistic in a true scenario. I think the committee should reconsider this testing and ask the submitter to modify the testing scenario. Affirmative All Carter, Glen A. Foley, John J. Hild, Richard J. Kidd, Todd M. Lentz, Thomas S. Nauman, Susan Nugent, David P. Rindfuss, Lee T. Seuss, Jr., George A. Stephens, Ronald J. Swenson, David C. Wright, Scott Wypychoski, Kevin M. de Nooij, Tom Abstention Ozog, Nicholas Changes to this section should be based in research and testing. However, there is concern that existing industrial storage arrangements will be invalidated due to a vacuum in the current testing. How can the code provide additional options for those facilities? NFPA 30 Committee Comments Page 19 of 30

20 9 of 27 12/12/ :23 PM Committee Comment No. 211-NFPA [ New Section after ] This was a Second Revision that has been modified or deleted as the result of Second Correlating Revision: SCR-5-NFPA Fire Protection System Design Scheme E Sprinklers and horizontal barriers shall be installed in accordance with Figure (a) or Figure (b), whichever is applicable. Horizontal barriers shall be of plywood having a minimum thickness of 3/8 in. (10 mm) or of sheet metal of minimum 22 gauge thickness. All liquid storage shall be located beneath a barrier Vertical baffles shall not be installed between in-rack sprinklers In-rack sprinklers shall meet the following requirements: (1) In-rack sprinklers shall be intermediate temperature rated, pendent sprinklers with a nominal K-factor of 25.2 and shall be listed as extended coverage control mode density/area storage sprinklers. (2) In-rack sprinklers shall be positioned in a transverse flue below each barrier level. (3) In-rack sprinklers shall not be positioned within 3.5 ft of a rack upright. (4) The minimum in-rack sprinkler discharge pressure shall not be less than a gauge pressure of 30 psi. (5) Where one level of in-rack sprinklers is installed, the design shall include the 3 most hydraulically remote sprinklers on a single line. (6) Where two levels of in-rack sprinklers are installed, the design shall include the 3 most hydraulically remote sprinklers on a single line, and the 2 most hydraulically remote sprinklers on the next adjacent level. (7) Where three or more levels of in-rack sprinklers are installed, the design shall include the 3 most hydraulically remote sprinklers on a single line, and the 2 most hydraulically remote sprinklers on the next two adjacent levels. (8) Foam-water sprinkler protection shall be permitted to be substituted for water sprinkler protection, provided the same design criteria is used, and that the sprinkler is listed for use with foam If there are adjacent bays of in-rack arrays that are not dedicated to storage of liquids, the barrier and in-rack sprinkler protection shall be extended at least 6 ft (1.8 m) beyond the area devoted to liquid storage Ceiling sprinkler demand shall not be included in the hydraulic calculations for in-rack sprinklers Water demand at point of supply shall be calculated separately for in-rack and ceiling sprinklers and shall be based on the greater demand Ceiling sprinklers shall meet the following requirements: (1) Ceiling sprinkler protection shall be designed to protect the surrounding occupancy. (2) Any sprinkler type shall be acceptable. (3) If standard spray sprinklers are used, they shall be capable of providing not less than 0.30 gpm/ft 2 over 3000 ft 2 (8 mm/min over 270 m 2) when supplied with water. Design area NFPA 30 Committee Comments Page 20 of 30

21 0 of 27 12/12/ :23 PM can be reduced to 2000 ft 2 when using a pre-primed foam-water system installed in accordance with NFPA 16 and maintained in accordance with NFPA 25. (4) If the liquid storage does not extend to the full height of the rack, protection for commodities stored above the top horizontal barrier shall meet the requirements of NFPA13, Standard for the Installation of Sprinkler Systems, for the commodities stored, based on the full height of the rack A 500 gpm (1900 L/min) hose stream allowance shall be provided. Supplemental Information File Name Figure_16_6_4_1_a_ pdf Figure_16_6_4_1_b_ pdf Description Figure (a) Figure (b) Submitter Information Verification Submitter Full Name: FLC-SWC Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Jun 27 14:16:26 EDT 2016 Committee Statement Committee Statement: The technical committee has reviewed all of the supporting documentation that substantiates the inclusion of new Section , which accompanies new Table Response Message: Public Comment No. 57-NFPA [New Section after ] Ballot Results This item has passed ballot 31 Eligible Voters 3 Not Returned 21 Affirmative All 1 Affirmative with Comments 6 Negative with Comments 0 Abstention Not Returned NFPA 30 Committee Comments Page 21 of 30

22 NFPA 30 Committee Comments Page 22 of 30

23 NFPA 30 Committee Comments Page 23 of 30

24 1 of 27 12/12/ :23 PM Bellamy, Tracey D. Cosey, William V. F. Fitzgerald, Keric M. Affirmative All Apostoluk, Peter R. Carter, Glen A. De Taeye, Claire V. Foley, John J. Hild, Richard J. Kidd, Todd M. Kirby, David C. Kraus, Richard S. Kulpit, Jonathan LeBlanc, John A. Nauman, Susan Nugent, David P. Ozog, Nicholas Riegel, Roland A. Rindfuss, Lee T. Stephens, Ronald J. Swenson, David C. Willse, Peter J. Wright, Scott Wypychoski, Kevin M. de Nooij, Tom Affirmative with Comment Workman, Martin H. agree with committee Negative with Comment Havens, Dwight H. Based on my revised vote on SR-210, this revision is no longer needed. Hicks, Donald B. I agree with Wechsler's comments. Lentz, Thomas S. The time heads operated from the ignition of the fire test. Did not simulate a worse case scenario of NFPA 30 Committee Comments Page 24 of 30

25 2 of 27 12/12/ :23 PM possible obstructions or other delays Ordile, Anthony M. SAME RESPONSE AS SR I am concerned about this proposed Table and Scheme being developed on a single fire test. The TC has previously developed the protection criteria Tables based on redundant large-scale fire tests. My concern about basing this on a single fire test is emphasized by the fact that the in-rack sprinklers operated at 6 seconds after ignition. Perhaps a second test altering the location of the spill and ignition would yield different results that could have resulted in a delay of sprinkler operation that may have also caused some drums of product to be involved and more than 2 rack sprinklers to operate. I also have concern over the unlimited storage height with larger containers especially when standard lift trucks are involved. The unlimited ceiling height is a concern with larger containers should the spill incident occur in an aisle or staging area. Seuss, Jr., George A. I agree with John Leblanc's reasoning for why this resolution should not pass. Further, I am not comfortable with using only 3 in-rack sprinkler heads as the design basis. Wechsler, David B. After having reviewed the committee actions, the original submittal and the response from John Leblanc on SR210- I find the complete actions on all these related changes ill advised and We should not advocate an unlimited conditions. Again as my common voting comment: The proposed Scheme E is linked to the justification provided in Public Comment No. 52, which was associated with the test results of a single fire test conducted at UL. The protection recommendations are based on a single spill scenario and a single ignition source location. The two sprinklers that operated during the test both activated at 6 seconds after ignition, which leads to questions of whether a more delayed or relocated ignition or spill location, perhaps to a higher location in the rack structure, might have produced unsatisfactory results. It is unprecedented to base the entire protection scheme for an unlimited area, unlimited storage quantity of drums of Class II liquids on a worst case scenario of operating 3 in-rack sprinklers, particularly when that basis represents a single fire test and contemplates only a single additional operating sprinkler beyond the two that operated in the cited test as the factor of safety. NFPA 30 Committee Comments Page 25 of 30

26 3 of 27 12/12/ :23 PM Committee Comment No. 206-NFPA [ New Section after D.2 ] This was a Second Revision that has been modified or deleted as the result of Second Correlating Revision: SCR-6-NFPA D.3 Design Criteria for Sprinkler Protection of Single- and Double-Row Rack Storage of Class II and Class III Liquids Fire protection criteria in Section , Table , and is based on a full scale fire test documented in the report, Class II Combustible Liquids in 55-gallons Steel Drums Stored in Racks with Continues Combustible Horizontal Barriers Protect by K=25.2 EC In-Rack Sprinklers, prepared by Underwriters Laboratories, Inc. dated June 13, Submitter Information Verification Submitter Full Name: FLC-SWC Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Jun 21 14:24:35 EDT 2016 Committee Statement Committee Statement: Response Message: This revision provides a cross reference to the test report that supports new Table and new Scheme E diagrams. Public Comment No. 65-NFPA [New Section after D.2] Ballot Results This item has passed ballot 31 Eligible Voters 3 Not Returned 27 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned NFPA 30 Committee Comments Page 26 of 30

27 4 of 27 12/12/ :23 PM Bellamy, Tracey D. Cosey, William V. F. Fitzgerald, Keric M. Affirmative All Apostoluk, Peter R. Carter, Glen A. De Taeye, Claire V. Foley, John J. Havens, Dwight H. Hicks, Donald B. Hild, Richard J. Kidd, Todd M. Kirby, David C. Kraus, Richard S. Kulpit, Jonathan LeBlanc, John A. Lentz, Thomas S. Nauman, Susan Nugent, David P. Ordile, Anthony M. Ozog, Nicholas Riegel, Roland A. Rindfuss, Lee T. Seuss, Jr., George A. Stephens, Ronald J. Swenson, David C. Wechsler, David B. Willse, Peter J. Wright, Scott Wypychoski, Kevin M. de Nooij, Tom Affirmative with Comment Workman, Martin H. agree with committee NFPA 30 Committee Comments Page 27 of 30

28 5 of 27 12/12/ :23 PM Committee Comment No. 3-NFPA [ Section No. I ] This was a Second Revision that has been modified or deleted as the result of Second Correlating Revision: SCR-7-NFPA I ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved 2014). ASTM D4206, Standard Test Method for Sustained Burning of Liquid Mixtures Using the Small Scale Open-Cup Apparatus, 1996 (reapproved 2013). ASTM D4207, Standard Test Method for Sustained Burning of Low Viscosity Liquid Mixtures by the Wick Test, 1991 (withdrawn 1998). ASTM D4956, Standard Specification for Retroreflective Sheeting for Traffic Control, ASTM D6469, Standard Guide for Microbial Contamination in Fuels and Fuel Systems, ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials, ASTM E502, Standard Test Method for Selection and Use of ASTM Standards for the Determination of Flash Point of Chemicals by Closed Cup Methods, 2007e1 (reapproved 2013). ASTM E1529, Standard Test Methods for Determining Effects of Large Hydrocarbon Pool Fires on Structural Members and Assemblies, 2014a Manual on Flash Point Standards and Their Use, Submitter Information Verification Submitter Full Name: FLC-FUN Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Jun 22 14:27:50 EDT 2016 Committee Statement Committee Statement: Updates references Response Message: Public Comment No. 6-NFPA [Section No. I.1.2.6] Ballot Results NFPA 30 Committee Comments Page 28 of 30

29 6 of 27 12/12/ :23 PM This item has passed ballot 27 Eligible Voters 3 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Cosey, William V. F. Crumholt, Curtis W. Drechsel, Carl M. Affirmative All Apostoluk, Peter R. Barber, Jonathan R. Brennecke, Gregory C. Cole, Anthony R. De Taeye, Claire V. Foley, John J. Garfunkel, Felix J. Havens, Dwight H. Jablonski, Jay J. King, John W. Kraus, Richard S. Morgan, Bob D. Nugent, David P. Ramirez, Alfredo M. Richmond, Sr., John W. Shank, Peter M. Stocker, Warren G. Tyler, Scott M. Upson, Robert Wagner, Paul Wang, Qingsheng Wechsler, David B. Wethington, Robert P. NFPA 30 Committee Comments Page 29 of 30

30 7 of 27 12/12/ :23 PM Wieczorek, Christopher J. NFPA 30 Committee Comments Page 30 of 30

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE MEMORANDUM TO: FROM: Correlating Committee on Flammable and Combustible Liquids R. P. Benedetti DATE: October 24, 2016 SUBJECT: Agenda for NFPA 30 Second

More information

NFPA 30 FLC-SWC Public Comment Report

NFPA 30 FLC-SWC Public Comment Report of 224 9/6/2016 1:13 PM Public Comment No. 56-NFPA 30-2016 [ Global Input ] These definitions of Protected and Unprotected are intended for inclusion in Sections 9.2, 10.2, 11.2, 13.2 and 16.2. The current

More information

If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following:

If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Dear FLC-SWC Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For audio you MUST dial in on your phone. I will not be enabling the use of

More information

NFPA 30 FLC-SWC First Revisions Page 1 of 10 11/6/2015 9:21 AM. First Revision No. 208-NFPA [ Section No ]

NFPA 30 FLC-SWC First Revisions Page 1 of 10 11/6/2015 9:21 AM. First Revision No. 208-NFPA [ Section No ] of 46 11/6/2015 9:21 AM First Revision No. 208-NFPA 30-2015 [ Section No. 9.3.3.1 ] 9.3.3.1 Storage of liquids shall not physically obstruct a means of egress. Submittal Date: Wed Sep 09 18:24:20 EDT 2015

More information

Correlating Committee on Automatic Sprinkler Systems

Correlating Committee on Automatic Sprinkler Systems Correlating Committee on Automatic Sprinkler Systems M E M O R A N D U M DATE: May 14, 2014 TO: FROM: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems Matt Klaus,

More information

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Industrial and Medical Gases

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE MEMORANDUM TO: FROM: NFPA 30 Technical Committee on Storage and Warehousing of Containers and Portable Tanks R. P. Benedetti DATE: September 16, 2010 SUBJECT:

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE MEMORANDUM TO: FROM: NFPA 30 Technical Committee on Storage and Warehousing of Containers and Portable Tanks Janna Shapiro DATE: August 13, 2015 SUBJECT:

More information

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018) M EM O RA N D UM TO: FROM: DATE: SUBJECT: Correlating Committee on Combustible Dusts Yiu Lee, Project Administrator January 27, 2017 NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

More information

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Water Additives

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

M E M O R A N D U M. NFPA 1911 Second Draft Technical Committee FINAL Ballot Results (F2016 Cycle)

M E M O R A N D U M. NFPA 1911 Second Draft Technical Committee FINAL Ballot Results (F2016 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Department Apparatus

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM 1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017)

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Code Kelly Carey,

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Sprinkler System

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE MEMORANDUM TO: FROM: NFPA 30 Technical Committee on Storage and Warehousing of Containers and Portable Tanks R. P. Benedetti DATE: June 6, 2013 SUBJECT:

More information

NFPA 30. Flammable and Combustible Liquids Code Edition {EF6DAC55-A2FB-4989-A71E-5F7317D5967C}

NFPA 30. Flammable and Combustible Liquids Code Edition {EF6DAC55-A2FB-4989-A71E-5F7317D5967C} NFPA 30 Flammable and Combustible Liquids Code NFPA, 1 Batterymarch Park, Quincy, MA 02169-7471 An International Codes and Standards Organization IMPORTANT NOTICES AND DISCLAIMERS CONCERNING NFPA STANDARDS

More information

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

Public Comment No. 13-NFPA [ Section No ]

Public Comment No. 13-NFPA [ Section No ] Public Comment No. 13-NFPA 30-2013 [ Section No. 2.3.3 ] 2.3.3 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM A 395/A395M, Standard

More information

M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle)

M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications

More information

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies

More information

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12.

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12. 2/18/2016 National Fire Protection Association Report Committee Input No. 70 NFPA 54 2015 [ Section No. 12.5 ] This was a First Revision that failed ballot. 12.5 Type of Venting System to Be Used. 12.5.1

More information

Significant Advancements in Water Based Fire Suppression for Storage Occupancies

Significant Advancements in Water Based Fire Suppression for Storage Occupancies Significant Advancements in Water Based Fire Suppression for Storage Occupancies Presented by: James Golinveaux Sr. Fellow Tyco Fire Protection Products Higher Faster - Further How high can we go? Ceiling

More information

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Michael Billstroem Director of International Technical Services The Reliable Automatic Sprinkler Co.,

More information

Public Comment No. 1-NFPA [ Section No ]

Public Comment No. 1-NFPA [ Section No ] Page 1 of 7 Public Comment No. 1-NFPA 556-2014 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA, 19428-2959. ASTM D2859, Standard

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Suppression, Detection and Signaling Research and Applications Conference SupDet 2015 March 5, 2015

More information

Developing Sprinkler System Design Criteria for Flammable and Combustible Liquid Storage

Developing Sprinkler System Design Criteria for Flammable and Combustible Liquid Storage Developing Sprinkler System Design Criteria for Flammable and Combustible Liquid Storage David P. Nugent Aon Risk Consultants Introduction Safe handling and storage of flammable and combustible liquids

More information

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

WORKING DRAFT OF COMMITTEE MEETING OUTPUT WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF SECOND DRAFT REPORT Document: NFPA 221 Revision Cycle: A2014 Meeting Date: 5/20/2013

More information

M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014

M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications

More information

Public Comment No. 16-NFPA 13D-2014 [ Section No ]

Public Comment No. 16-NFPA 13D-2014 [ Section No ] of 52 9/22/2014 9:20 AM Public Comment No. 16-NFPA 13D-2014 [ Section No. 2.3.3 ] 2.3.3 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM

More information

Committee Input No. 28-NFPA 13R-2013 [ Global Input ]

Committee Input No. 28-NFPA 13R-2013 [ Global Input ] Page 1 of 6 Committee Input No. 28-NFPA 13R-2013 [ Global Input ] 6.2.2 Outside Dwelling Units. 6.2.2.1 All sprinklers used outside of the dwelling units shall be in accordance with 6.2.2 7.2 and 7.3.

More information

Public Comment No. 3-NFPA [ Chapter 7 ]

Public Comment No. 3-NFPA [ Chapter 7 ] Page 1 of 8 Public Comment No. 3-NFPA 405-2013 [ Chapter 7 ] Chapter 7 ARFF Personnel Safety and Safety Management 7.1 Scope. This chapter identifies the knowledge and skills necessary to ensure ARFF personnel

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information

12/21/2015 National Fire Protection Association Report

12/21/2015 National Fire Protection Association Report http://submittals.nfpa.org/terraviewweb/viewerpage.jsp?id=232 2012.ditamap&toc=false&draft=true 1/9 Public Comment No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents

More information

Revise the metric values throughout the standard to follow the soft conversions provided by the metric task group

Revise the metric values throughout the standard to follow the soft conversions provided by the metric task group of 36 9/22/2014 9:37 AM Second Revision No. 14-NFPA 13D-2014 [ Global Comment ] Revise the metric values throughout the standard to follow the soft conversions provided by the metric task group Supplemental

More information

M E M O R A N D U M. Technical Committee on Fire Fighter Professional Qualifications

M E M O R A N D U M. Technical Committee on Fire Fighter Professional Qualifications National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Fighter Professional

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Public Comment No. 2-NFPA 16-2013 [ Section No. 3.3.6 ] 3.3.6* Foam-Water Sprinkler System. A piping network connected to a source of foam concentrate and to a water supply. The piping network is equipped

More information

MEMORANDUM. NFPA Technical Committee on Liquefied Natural Gas. NFPA 59A Second Draft TC FINAL Ballot Results (F2015)

MEMORANDUM. NFPA Technical Committee on Liquefied Natural Gas. NFPA 59A Second Draft TC FINAL Ballot Results (F2015) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Liquefied Natural Gas

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels

More information

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Second Revision No. 3-NFPA [ Section No. 2.3 ] Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Protected Premises Fire Alarm

More information

MEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Emergency Power Supplies Kelly

More information

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard

More information

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Fire Alarm

More information

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ] 8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Residential Sprinkler

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard

More information

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Supervising Station

More information

MEMORANDUM. Technical Committee on Fundamentals of Combustible Dusts. NFPA 652 First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Fundamentals of Combustible Dusts. NFPA 652 First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Combustible

More information

M E M O R A N D U M. NFPA Technical Committee on Fire Safety and Emergency Symbols. NFPA 170 Second Draft TC FINAL Ballot Results (F2014)

M E M O R A N D U M. NFPA Technical Committee on Fire Safety and Emergency Symbols. NFPA 170 Second Draft TC FINAL Ballot Results (F2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Fire Safety

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 14 From: Kimberly Shea, Project Administrator

More information

Committee Input No. 60-NFPA [ Sections , ]

Committee Input No. 60-NFPA [ Sections , ] Page 1 of 15 Committee Input No. 60-NFPA 34-2013 [ Sections 3.3.7.1, 3.3.7.2 ] Sections 3.3.7.1, 3.3.7.2 3.3.7.1 Combustible Liquid. A Any liquid that has a closed-cup flash point at or above 100 F (37.8

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 496-2014 [ Section No. 5.2.2 ] 5.2.2 Where When the enclosure has been opened or if the protective gas supply has failed to maintain the required positive pressure, the enclosure

More information

MEMORANDUM. NFPA Technical Committee on Handling and Conveying of Dusts, Vapors, and Gases. NFPA 654 Second Draft TC FINAL Ballot Results (A2016)

MEMORANDUM. NFPA Technical Committee on Handling and Conveying of Dusts, Vapors, and Gases. NFPA 654 Second Draft TC FINAL Ballot Results (A2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Handling and Conveying

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical self-closing device

More information

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document 1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two

More information

MEMORANDUM. NFPA Technical Committee on Hazard and Risk of Contents and Furnishings. NFPA 556 First Draft TC FINAL Ballot Results (A2015)

MEMORANDUM. NFPA Technical Committee on Hazard and Risk of Contents and Furnishings. NFPA 556 First Draft TC FINAL Ballot Results (A2015) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Hazard and Risk of Contents

More information

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Alternative Approaches to

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Correlating Committee on

More information

Public Input No. 2-NFPA [Chapter F]

Public Input No. 2-NFPA [Chapter F] 1 of 66 1/26/2016 2:02 PM Public Input No. 19-NFPA 403-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this

More information

M E M O R A N D U M. NFPA Technical Committee on Fire Department Apparatus. Yvonne Smith, Project Administrator. Date: June 4, 2014

M E M O R A N D U M. NFPA Technical Committee on Fire Department Apparatus. Yvonne Smith, Project Administrator. Date: June 4, 2014 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Fire Department

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

IMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES

IMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 0171-735 7611 Fax: 0171-587 3210 Telex: 23588 IMOLDN G Ref. T4/4.01 IMO E MSC/Circ.914 4 June 1999 GUIDELINES FOR THE APPROVAL

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Residential

More information

The Effect of Large Orifice Sprinklers on High-Challenge Fires

The Effect of Large Orifice Sprinklers on High-Challenge Fires SUPPLEMENT 2 The Effect of Large Orifice Sprinklers on High-Challenge Fires Bill Thomas, P.E. Bill Tomes Editor s Note: Supplement 2 provides background information related to the development and application

More information

M E M O R A N D U M. NFPA 270 First Draft Technical Committee FINAL Ballot Results (F2017)

M E M O R A N D U M. NFPA 270 First Draft Technical Committee FINAL Ballot Results (F2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Tests Kelly

More information

Reference to the Smoke Damage Index (SDI) is needed as it is part of the test method.

Reference to the Smoke Damage Index (SDI) is needed as it is part of the test method. Public Input No. 4-NFPA 287-2014 [ Section No. 1.2.3.2 ] 1.2.3.2 Indices resulting from the test methods include critical heat flux (CHF), thermal response parameter (TRP), fire propagation index (FPI),

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

Public Comment No. 7-NFPA 30A-2013 [ Section No ]

Public Comment No. 7-NFPA 30A-2013 [ Section No ] Page 1 of 13 Public Comment No. 7-NFPA 30A-2013 [ Section No. 6.4.2 ] 6.4.2 Additional Proposed Changes Each pump shall have installed on the discharge side a listed leak detection device that will provide

More information

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fire Code (FCC-AAA) Gregory

More information

Public Comment No. 22-NFPA [ New Section after 1.4 ] Statement of Problem and Substantiation for Public Comment

Public Comment No. 22-NFPA [ New Section after 1.4 ] Statement of Problem and Substantiation for Public Comment of 25 5/14/2015 2:32 PM Public Comment No. 22-NFPA 14-2014 [ New Section after 1.4 ] A.1.4 A.1.4 It is the intent of the Commi ee to recognize that future edi ons of this standard are a further refinement

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time, changes

More information

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Water Additives

More information

MEMORANDUM. NFPA 99 Second Draft Correlating Committee FINAL Ballot Results (A2017)

MEMORANDUM. NFPA 99 Second Draft Correlating Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Correlating Committee on Health Care Facilities Elena

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement 1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 2 FROM: Kimberly Shea, Administrator,

More information

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

SECTION (13900) - FIRE SUPPRESSION SYSTEMS PART 1 GENERAL 1.01 SUMMARY SECTION 21 10 00 (13900) - FIRE SUPPRESSION SYSTEMS A. Section Includes: 1. Pipe and Fittings. 2. Sprinklers. B. Related Documents: 1. Marriott s Fire Protection and Life Safety

More information

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT PREPARED BY: Garner A. Palenske, P.E., and William N. Fletcher, P.E. Aon Fire Protection Engineering San Diego, CA, USA September 2015 Fire Protection

More information

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,

More information

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A. International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.800(19) Magnus Arvidson SP Fire Research SP Technical Research Institute

More information

Storage Sprinkler U.S. Quick Reference Guide

Storage Sprinkler U.S. Quick Reference Guide Storage U.S. Reference Guide This guide is intended for general reference only. Prior to the design, layout, and/or installation of any sprinkler system, please refer to Viking s technical documentation

More information

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Item No. Subject 13-6-1 Call to Order (8:00 A.M) 13-6-2 Roll Call 13-6-3 Approval

More information

First Revision No. 1-NFPA [ Chapter 2 ]

First Revision No. 1-NFPA [ Chapter 2 ] First Revision No. 1-NFPA 499-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this recommended practice

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

TECHNICAL COMMITTEE ON FIRE CODE

TECHNICAL COMMITTEE ON FIRE CODE TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2

More information

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Correlating Committee on Signaling Systems for

More information