2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)

Size: px
Start display at page:

Download "2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)"

Transcription

1 2007 & CFC Residential Care Facility Requirements (24 hour care only) Occupancy Construction Smoke Barrier I-1 Bedridden 7+non- Ambs Or bed- Ridden R-4 7+ambs (May have 6 nonambs or 6 bedridden) R or less Regardless of ambulatory status Rated & Table 503 n-rated up to 7,000 sq. feet Table 503 except in and n-rated Table 503 special considerations in CB If > than 6,000 sq. feet If > than 6,000 sq. feet Sprinkler System Except. if only 1 bedridden provisions of Smoke Alarm & Fire Alarm System Manual & Auto. System Exc. Manual & Auto. System except. Strobes required in protective social care facilities housing any deaf person # of Exits Two Two Two exiting provisions of & for exiting from client sleeping rooms Rated Corridors Table wide for nonambs and 44 wide for ambs If serving 11+ Table 1017 Exit Enclosur e If more than 6 nambs Above 1 st floor If more than 6 n-ambs Above 1 st floor floor separation provisions in & Delayed Egress Must meet all req. of Must meet all req. of Must meet all req. of Up to 6 allowed Hospice can have up to six. Others can have 1 if nonsprinklered and 6 if sprinklered. provisions of Exit Signs Floor level Exit path Marking Floor level Exit path Marking Tactile Exit Signs Emergenc y Lights exc exc Except. #3 Fire Exiting. CFC & CFC & CFC #1 Ramps Unless housing non-ambs or bedridden

2 Residential Care Facilities (Group I-1) REQUIREMENTS Definition = More than six non-ambulatory or bedridden. Section Type V-1 Hour construction. Max of 10,500 sq. ft. 2 stories if more than six non-ambulatory elderly. 3 stories for others. Section & Table 503. Smoke Barriers: a. Required where individual floor area exceeds 6,000 sq. ft. Area of a single smoke compartment shall not exceed 22,500 sq. ft. and travel distance to an exit or smoke barrier wall shall not exceed 200 feet., Sec Exception: One story facilities housing more than six non-ambulatory elderly where the buildings have direct exits from each dwelling unit. H & S code, Section b. Smoke barrier framing to be covered with noncombustible material with thermal barrier index of not less than Automatic Fire Sprinkler Protection: Fire Sprinkler System in accordance with NFPA 13. Sec Exception: Facilities located in Type 1A construction in existence on March 4, Required in each sleeping area and in the corridor or area giving access to each separate sleeping area. Sec and t required in facility has automatic fire alarm system with smoke detectors Fire Alarm: A complete automatic and manual fire alarm system shall be provided in accordance with Section a. Exception: Buildings housings non-ambulatory clients only on the first floor and protected throughout by all of the following: 1. An approved supervised automatic fire sprinkler system installed in accordance with NFPA #13. Activation of sprinkler system shall sound the building fire alarm system 2. A manual fire alarm system 3. Smoke alarms as required by Sec b. Strobes shall be provided in public areas, common use areas, sleeping rooms and protective care facilities housing hearing impaired clients. Section , & Two Exits required. Sec Hallways/corridors serving 7 or more shall be 1-hour fire resistive with door openings protected by 20-minute fire rated assemblies. Doors to be maintained self-closing or automatic-closing by activation of a smoke detector. Glazed openings to be labeled ¾ hour fire-rated assemblies. Sec & Table Exception: In sprinklered buildings, rated corridor doors to client rooms do not require self-closers. ( Sec ) 60 inches on floors housing non-ambulatory clients and 44 inches on floors housing only ambulatory clients. Sec Corridors shall not be interrupted by intervening rooms. Sec Exception 1: Foyers, lobbies and reception rooms shall not be considered intervening rooms. Exit Enclosure: Two enclosed exit stairways remotely located shall be required if 7 or more non-ambulatory clients are located above the first floor. Sec Delayed Egress: Allowed if conforming to requirements of Sec Bedridden Clients: Allowed for facilities licensed after Jan. 1, definition in Section Required as per Section Floor Level Required as per Section Exception: Where exit path marking is provided Exit Path Marking: Required as per Section

3 Excepting: Where floor level exit signs are provided Required as per Section Required as per Section Exception: Client sleeping rooms. Required as per CFC Section & Required as per Section

4 Residential Care Facilities (Group R-4) REQUIREMENTS Definition = More than 6 Ambulatory, Regardless of licensing agency. (May have up to 6 non-amb or bedridden) Type V-B Maximum of 7000 sq. ft. 2 stories. Higher if different construction. Table 503. Exception 1: Where non-ambulatory clients are housed above the first floor, or there is more than 3000 Sq. Ft. of area above the first floor or housing more than 16 clients at this level, the construction shall be 1-hour fire resistive throughout. Sec Exception 2: Facilities housing non-ambulatory elderly clients shall be at least Type V, 1-hour throughout., Section Smoke Barriers: a. Required where individual floor area exceeds 6000 sq. ft. Area of a single smoke compartment shall not exceed 22,500 sq. ft. and travel distance to an exit or smoke barrier wall shall not exceed 200 feet., Sec b. Smoke barrier framing to be covered with noncombustible material with thermal barrier index of not less than Automatic Fire Sprinkler Protection: Fire Sprinkler System in accordance with NFPA 13. Sec Exception 1: Protective Social Care facilities housing ambulatory persons ages years. Exception 2: Occupancies housing ambulatory children only none of whom are mentally ill or mentally retarded, and the building does not exceed 2 stories in height and is equipped with a complete smoke detection system. Required in each sleeping area and in the corridor or area giving access to each separate sleeping area. Sec & t required if facility has automatic fire alarm system with smoke detectors Shall be hardwired and shall be interconnected so that activation of one sets off the others Fire Alarms: a. An approved manual and automatic fire alarm system. Sec Exception 1: Protective social care facilities housing persons none of whom are physically or mentally handicapped or non-ambulatory and provided with manual fire alarm system. Exception 2: Protective social care facilities provided with a sprinkler system and a manual fire alarm box that will actuate a fire alarm signal audible throughout the facility. b. Strobes shall be provided in public areas, common use areas and protective social care facilities housing hearing impaired clients. Section , Two Exits required. Sec Hallways/corridors serving 11 or more shall be 1-hour fire resistive with door openings protected by 20-minute fire rated assemblies. Doors to be maintained self-closing or automatic-closing by activation of a smoke detector. Glazed openings to be labeled ¾ hour fire-rated assemblies. Sec & Table inches on floors housing only ambulatory clients. Sec Exception 1: Corridors serving 10 or less may be 36 inches in width. Exception 2: Corridors serving ambulatory persons only and having an occupant load of 49 or less may be 36 inches in width. Corridors shall not be interrupted by intervening rooms. Sec Exception 1: Foyers, lobbies and reception rooms shall not be considered intervening rooms. Exit Enclosure: Two enclosed exit stairways remotely located shall be required if 7 or more non-ambulatory clients are located above the first floor. Sec Delayed Egress: Allowed if conforming to the requirements of Sec Required as per Section Floor Level Required as per Section Exception: Where exit path marking is provided.

5 Exit Path Marking: Required as per Section Exception: Where floor level exit signs are provided Required as per Section Required as per Section & Exception: Client sleeping rooms. Required as per CFC Sections & Required as per Section

6 Residential Care Facilities (Group R-3.1) Definition = Six or less clients ambulatory, non-ambulatory or bedridden. Section n-rated up to 3 stories. Table 503. (Must be Type V 1-hour in facilities housing clients above the first floor, more than 2 stories in height or having more than 3,000 sq. ft. floor area above the first floor). Section In facilities housing a bedridden client, the client sleeping room shall not be located above or below the first floor Exception: Clients who are temporarily bedridden for up to 14 days as per H&S Code Smoke Barriers: t required. Automatic Sprinklers: a. t required unless housing bedridden clients or housing non-ambulatory clients above the first floor or housing clients above the second floor. b. t required if housing only one bedridden client and complying with Section If required, can have either an NFPA 13-R or 13-D system. Section 4-6 of NFPA 13-D shall not apply unless approved by AHJ. Section #3 & 4. a. Required in all habitable areas of the facility including stairwells. Section b. Smoke alarms shall receive their primary power from the building wiring and shall be equipped with battery backup. Alarms shall be interconnected so that they all sound upon actuation of a single smoke alarm. They are not required to be interconnected to a control panel. Sections & Fire Alarm: t required. Strobes: Required in protective care facilities that house any deaf patient. Strobes shall activate upon initiation of any smoke alarm. Section Minimum of two exits are required. Section n-rated Shall be 36 inches on floors housing clients. Section #3 Means of egress shall not pass through more than one intervening room. A means of egress shall not pass through kitchens, storerooms, closets, garages or spaces used for similar purposes. Section Exception: Kitchens that do not form separate rooms by construction. Exit Access: a. Sleeping rooms used for non-ambulatory clients shall have access to one of the following exit arrangements: 1. Direct exit from the sleeping rooms to the exterior. 2. From sleeping room through an adjoining sleeping room with direct exit. 3. From sleeping room through the hallway serving the sleeping and which has an exit directly to the outside. The hallway shall be separated from the rest of the house by a wall and a 1-3/8 self-closing, solid wood door. The door can be automatic closing by actuation of a smoke alarm. 4. From sleeping room though the hallway into another sleeping room that has an exit directly to the outside. The hallway shall be separated from the rest of the house by a wall and a 1-3/8 self-closing, solid wood door. The door can be automatic closing by actuation of a smoke detector. Section b. Sleeping rooms used for a bedridden client in an non-sprinklered facility shall meet all of the following requirements: 1. Sleeping rooms shall exit directly to the exterior of the building. 2. Interior doors to sleeping room shall be self-closing, positive latching 1-3/8 solid wood door provided with a gasket to be smoke-tight. The door can be automatic closing by actuation of a smoke alarm. 3. Doors from sleeping rooms leading to an interior corridor or interior areas shall not have a night-latch, dead-bolt, security chain, or any similar locking devices. 4. The exterior sleeping room door shall be operable from both the interior and exterior of the residence. 5. Exterior sleeping room doors shall be at least 3 foot wide and 6 feet 8 inches high with a clear width of 32 and capable of opening at least 90 degrees. Section

7 Floor Separation: a. Floor separations shall be provided with non-rated smoke partition to prevent smoke travel between floors. Such partitions shall have construction equal to ½ gypsum board on one side of wall framing. Section Exceptions: 1. Occupancies with at least one exterior exit from floor occupied by patients. 2. Occupancies provided with automatic fire sprinkler systems. b. Door openings in floor separations shall be protected by 1-3/8 inch solid wood core doors which shall be positive latching, smoke gasketed and self-closing or automatic closing by activation of a smoke detector. Section Delayed Egress: Allowed if facility meets all requirements of Section t required. Section , Exception #3 t required. t required. Section , Exception #3 t required. Section 906.1, Item #1 Required in facilities housing non-ambulatory clients when changes in level exceed ½ inches. Section

8 Day Care Facilities (Group E) REQUIREMENTS Definition = a. Seven or more children 2-1/2 years of age or older Exception Day care facilities where occupants are not capable of responding to an emergency situation without physical assistance from staff shall be an I-4. b. Facilities for children 2-1/2 years or less for children when the rooms where children are located on the level of exit discharge and each of these child care rooms have an exit door directly to the exterior shall be classified as a Group E Occupancy. Section Type V-B Maximum of 9,500 sq. ft. 1 story. Higher if different construction. Table 503. Location: Daycares shall not be located above or below the first story. ( exceptions) Section Automatic Fire Sprinkler Protection: Fire Sprinkler System required in daycares that exceed 20,000 square feet. Section t required. Fire Alarms: An approved manual and automatic fire alarm system required when more than 50 persons. Section te exceptions. Two Exits required. Sec Hallways/corridors serving 11 or more shall be 1-hour fire resistive. Table Corridors shall not be used as plenums. Section t less than 44 inches. Section Exception #4 72 if corridor serves 100 or more. Corridors shall not be interrupted by intervening rooms. Sec Exception 1: Foyers, lobbies and reception rooms shall not be considered intervening rooms. Delayed Egress: t permitted in this occupancy. Section Required as per Section Floor Level Required as per Section Exception: Where exit path marking is provided. Exit Path Marking: Required as per Section Exception: Where floor level exit signs are provided Required as per Section Required as per Section & Required as per CFC Sections & Required when changes in elevation of less than 12 as per Section

9 Day Care Facilities (Group I-4) REQUIREMENTS Definition = a. More than 6 persons of any age in a commercial building. Sections & Exception: Facilities for children 2-1/2 years or less for children when the rooms where children are located on the level of exit discharge and each of these child care rooms have an exit door directly to the exterior shall be classified as a Group E Occupancy. Section b. Day care facilities where occupants are not capable of responding to an emergency situation without physical assistance from staff shall be an I Exception Type V-B Maximum of 9,000 sq. ft. 1 story. Higher if different construction. Table 503. Day care areas shall not be located above or below the first story. important exceptions on Smoke Barriers: t required. Automatic Fire Sprinkler Protection: Fire Sprinkler System in accordance with NFPA 13. Sec Required in locations approved by AHJ To be hardwired with battery back-up. Fire Alarms: t required. Two Exits required. Sec & Table Hallways/corridors serving 7 or more shall be 1-hour fire resistive. Table Corridors shall not be used as plenums. Section inches wide with 36 on facilities housing 49 or less. Section and Exception #2. Corridors shall not be interrupted by intervening rooms. Sec Exception 1: Foyers, lobbies and reception rooms shall not be considered intervening rooms. Delayed Egress: Allowed if conforming to the requirements of Sec Required as per Section Floor Level Required as per Section Exception: Where exit path marking is provided. Exit Path Marking: Required as per Section Exception: Where floor level exit signs are provided Required as per Section Required as per Sections & Required as per CFC Sections & Required as per Section

10 Residential Day Care Facilities (Group R-3) REQUIREMENTS Definition = Six or less adults (regardless of residential or Commercial location) Section & Small Family Day Care = 1-8 persons t regulated. Also speak to discrepancies. Large Family Day Care = 9-14 persons Health & Safety Code, Section (Large family day cares to be Group R-3 s as per ) Basic requirements found on Section 445 R-3 Occupancies also include facilities not in a residence (commercial building) housing six or less occupants n-rated up to 3 stories. Table 503. Day cares shall not be located above first floor unless sprinklered and one of the exits from second floor goes directly to exterior. Can use NFPA 13-R sprinklers, but sprinkler omissions of 13-R are not applicable. Section Automatic Sprinklers: t required. Section , Exception #1 Required. Number and placement to be determined by AHJ. Section Fire Alarm: One manual device approved by AHJ, audible throughout facility and of distinct tone. Section & At least two exits. Exit doors to have no less than 32 of clear width and not less than 6 8 in height. Horizontal slider can be used as one of the exits. Basement to have one of the exits go directly to outside if basement used for day care. Tables and relative to number of exits are not applicable to this occupancy n-rated Shall be 36 inches. Section Exception #3. As per R-3 s. Section Exit Access: As per R-3 s. Locks and latches shall be no-special knowledge types. Section Special Hazards: Unenclosed gas water heaters and furnaces in areas used for day care shall be protected so that children cannot make contact with appliances. Exception Kitchen stoves and ovens. Section t required. Section , Exception #3 t required t required. Section , Exception #3 At least one 2A10BC extinguisher required. Section Required in facilities housing non-ambulatory clients and where there are elevation changes of less than 12 as per Section

Residential Based Care Facility Guidelines

Residential Based Care Facility Guidelines Moreno Valley Fire Department Fire Prevention Bureau Residential Based Care Facility Guidelines Approved and Authorized By: Randall Metz, Fire Marshal Issued: January 1, 2011 Residential Based Care Facilities

More information

For additional information regarding R-3.1 residential care facilities please contact (951)

For additional information regarding R-3.1 residential care facilities please contact (951) Riverside County Fire Department Fire/Life Safety Inspection Division Riverside Office: 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4823 Fax (951) 955-4886 Palm Desert Office: 77-933 Las

More information

Residential Care Facilities Requirements

Residential Care Facilities Requirements Development Services Department Building Division 311 Vernon Street Roseville, California 95678-2649 Residential Care Facilities Requirements SUBMITTAL REQUIREMENTS: Note: These requirements are in addition

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES 2007 CBC/CFC (R-3.1)

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES 2007 CBC/CFC (R-3.1) July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: This Checklist outlines

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Guideline Title: Residentially Based Care Facilities Group

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD LICENSED CARE FACILITIES SCOPE: This standard provides requirements for licensed care facilities known as for the Elderly with seven

More information

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1. EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-003 EFFECTIVE 06-03-2009 PURPOSE To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified

More information

Residential-based Care Facility R-4 Guideline

Residential-based Care Facility R-4 Guideline Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care

More information

Large Family Daycare Guideline

Large Family Daycare Guideline Moreno Valley Fire Department Fire Prevention Bureau Large Family Daycare Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 10, 2017 Large Family Daycare Guideline Purpose

More information

Residential Care Facilities

Residential Care Facilities Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA. 92602 www.ocfa.org 714-573-6180 Residential Care Facilities with six or fewer non-ambulatory or bedridden

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

Residential Care Facilities Having 6 or Fewer Clients Classified in the California Building Code as R-3.1 Occupancies

Residential Care Facilities Having 6 or Fewer Clients Classified in the California Building Code as R-3.1 Occupancies Building Permits & Inspection Division General Information: (916) 875-5296 www.building.saccounty.net Full Service Center 827 7th Street, Room 102 Sacramento, CA 95814 M-F 8:30am - 4:30pm Bradshaw Center

More information

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES [B] APPENDIX SR GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon SECTION SR101

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES [B] APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL

More information

FIRE PREVENTION STANDARDS

FIRE PREVENTION STANDARDS DATE: 04/11/02 APPROVED: NUMBER: FP0-010 REVISED: FIRE PREVENTION STANDARDS TITLE: Large Family Day Cares (9-14 kids) PURPOSE: The purpose of this standard is to acquaint the applicant with the applicable

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

CHILD CARE CENTER INSPECTION CHECKLIST 06C

CHILD CARE CENTER INSPECTION CHECKLIST 06C CHILD CARE CENTER INSPECTION CHECKLIST 06C OCCUPANCY-SPECIFIC FIRE S November 2006: Kansas State Fire Marshal Page: 29 November 2006: Kansas State Fire Marshal Page: 30 CHILD CARE CENTERS & PRESCHOOLS

More information

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE

More information

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control 11-27-12 This document is designed as a summary guide using IFC requirements for the provisions associated with exiting,

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 HCFMO Harris County Fire Marshal M.S. Montgomery Fire Marshal FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 EFFECTIVE JANUARY 1, 2007 These guidelines

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES 1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)

More information

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL

More information

Burien/Normandy Park Fire Department 900 SW 146 th ST PO Box Burien, WA BP (206) Fax (206)

Burien/Normandy Park Fire Department 900 SW 146 th ST PO Box Burien, WA BP (206) Fax (206) Burien/Normandy Park Fire Department 900 SW 146 th ST PO Box 66029 Burien, WA 98166 BP (206) 242-2040 Fax (206) 433-6042 HOME DAYCARE SELF-INSPECTION CHECKLIST ` Complete the following daycare checklist,

More information

COUNTY OF SACRAMENTO DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PERMITS & INSPECTION DIVISION

COUNTY OF SACRAMENTO DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PERMITS & INSPECTION DIVISION COUNTY OF SACRAMENTO DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PERMITS & INSPECTION DIVISION Document # GI-16 Page 1 of 7 Large Family Day Care Homes Large family day care homes are licensed for day

More information

Residential-based Care Facility R2.1 Guideline

Residential-based Care Facility R2.1 Guideline Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R2.1 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 5, 2017 Residential-based Care

More information

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Section No. Subject Page No. 1 Authority and Purpose 10-1 2 Definitions

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements

More information

FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group

FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway AIA Healthcare Group Introductions Presenters Coffman Engineers Scott M. Twele, P.E. Operations Manager,

More information

Chapter Nursing Homes

Chapter Nursing Homes Chapter 16.01 Nursing Homes Section 1. Licensing. No nursing, convalescent or old age home, as defined in Section 2 of this ordinance, shall be operated except under a license from the City Council of

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-002 EFFECTIVE 05-27-2009 PURPOSE: To define the requirements for a License. To facilitate the quick application and review of new or changed

More information

APPLICATION FOR Large Family Day Care Permit

APPLICATION FOR Large Family Day Care Permit PLANNING SERVICES DEPARTMENT 411 Main Street (530) 879-6800 P.O. Box 3420 Chico, CA 95927 Application No. APPLICATION FOR Large Family Day Care Permit Applicant Information Applicant Daytime Phone Street

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

For additional information regarding Group I occupancies please call (951)

For additional information regarding Group I occupancies please call (951) Riverside County Fire Department Fire/Life Safety Inspection Division Riverside Office: 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4823 Fax (951) 955-4886 Palm Desert Office: 77-933 Las

More information

Public. Mike Free Health. State of Alabama Department of

Public. Mike Free Health. State of Alabama Department of State of Alabama Department of Mike Free Building Construction Specialist Technical Services Unit Office of Facilities Management Public 334-206-5221 334-206-5177 Health Fax: 334-206-5890 Web Site: www.adph.org.facmgmt

More information

Public Health Fax: Web Site:

Public Health Fax: Web Site: State of Alabama Department of Public Health Fax: 334-206-5890 Web Site: www.adph.org.facmgmt Mike Free Building Construction Specialist Technical Services Unit Office of Facilities Management 334-206-5221

More information

1. The provisions of paragraph (D)(1104) of this rule shall apply to all existing buildings.

1. The provisions of paragraph (D)(1104) of this rule shall apply to all existing buildings. ACTION: Final DATE: 12/04/2017 11:44 AM 1301:7-7-11 Construction requirements for existing buildings. (A) Section 1101 General (1) 1101.1 Scope. The provisions of this rule shall apply to existing buildings

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 94 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General

More information

Family Foster Home Fire Safety Evaluation Checklist Instructions

Family Foster Home Fire Safety Evaluation Checklist Instructions Family Foster Home Fire Safety Evaluation Checklist Instructions Please read these instructions prior to commencing your inspection. This checklist is provided to specific Foster Family Homes for the purpose

More information

Fire Protection Coffee Break Training May 2016

Fire Protection Coffee Break Training May 2016 Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers

More information

Residential Alcohol & Drug Rehabilitation Facilities

Residential Alcohol & Drug Rehabilitation Facilities Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA. 92602 www.ocfa.org 714-573-6180 Residential Alcohol & Drug Rehabilitation Facilities Providing On-site

More information

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document

More information

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - 2000 LIFE SAFETY CODE Intermediate Care Facilities for the Mentally Retarded LARGE PART I Figure

More information

WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES 1 WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 3.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies each fire zone) Building

More information

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal M.S. Montgomery Fire Marshal September 1, 2010 This document describes rules changes affecting the operation and fire safety in foster homes licensed and regulated by the Texas Department of Family and

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.dps.state.mn.us

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

Requirements for Smoke / Carbon Monoxide / Fire Extinguisher Certification

Requirements for Smoke / Carbon Monoxide / Fire Extinguisher Certification Requirements for Smoke / Carbon Monoxide / Fire Extinguisher Certification In order to successfully pass the inspection, your property will need to meet all regulations mandated by the state and municipality.

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

Smoke Alarms and Carbon Monoxide Alarms

Smoke Alarms and Carbon Monoxide Alarms 70 N 1st Street Campbell, California 95008 Phone (408) 866-2130 Fax (408) 871-5101 Smoke Alarms and Carbon Monoxide Alarms March, 2018 When building permits are issued for additions, alterations or repairs

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

E25 (D) Automatic controls for general means of egress lighting

E25 (D) Automatic controls for general means of egress lighting Adhoc Health Care MOE Study Group Study Group Report of Adhoc Meeting July 12&13, 2012 Possible Public Comments E25, E69, E74, G71, G77/G80 Study Group E25 (D) Automatic controls for general means of egress

More information

Requirements for Smoke Detector / Carbon Monoxide/ Fire Extinguisher Certification

Requirements for Smoke Detector / Carbon Monoxide/ Fire Extinguisher Certification Requirements for Smoke Detector / Carbon Monoxide/ Fire Extinguisher Certification In order to successfully pass the inspection, your property will need to meet all regulations mandated by the state and

More information

First Published in the Wichita Eagle on DELINEATED 10/02/2010 ORDINANCE NO.

First Published in the Wichita Eagle on DELINEATED 10/02/2010 ORDINANCE NO. First Published in the Wichita Eagle on DELINEATED 10/02/2010 ORDINANCE NO. AN ORDINANCE AMENDING SECTIONS 15.02.010, 15.02.020, 15.02.030, 15.02,040, 15.02.050, 15.02.060, 15.02.060, 15., 02.070 AND 15.02.080

More information

2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata) [F]TABLE 903.2.11.6 ADDITIONAL REQUIRED SUPPRESSION SYSTEMS SECTION SUBJECT 402.10 402.5 Covered and open mall buildings (Portions of table not show remain unchanged) 2012 International Building Code SEVENTH

More information

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved Life Safety Code Common Discepancies Course# LSC102 EZpdh.com All Rights Reserved 1. K147 Electrical - Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code. 9.1.2

More information

Johnson County, Kansas. Home Daycare Handbook 2013 Edition

Johnson County, Kansas. Home Daycare Handbook 2013 Edition Johnson County, Kansas Home Daycare Handbook 2013 Edition INTRODUCTION The Fire Departments of Johnson County have had the responsibility to ensure the places where we live, work and congregate are safe

More information

Short Term Accommodations Fire Code Requirements

Short Term Accommodations Fire Code Requirements Short Term Accommodations Fire Code Requirements 1 Foreward The following is a comprehensive reference to Retrofit 9.3 of Division B of the Ontario Fire Code (OFC). Retrofit provisions were developed to

More information

Residential Large Family Daycare Facilities

Residential Large Family Daycare Facilities Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA. 92602 www.ocfa.org 714-573-6180 Residential Large Family Daycare Facilities Guideline F-07 Serving the

More information

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC Changes Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC New Sentence 3.2.4.2(6) Buildings interconnected by walkways permitted in Articles

More information

Rental Housing Initial Inspection Checklist Community Development Department 208 NW 1 st Ave., Faribault, MN

Rental Housing Initial Inspection Checklist Community Development Department 208 NW 1 st Ave., Faribault, MN Rental Housing Initial Inspection Checklist Community Development Department 208 NW 1 st Ave., Faribault, MN 55021 www.faribault.org (507) 333-0359 Property Address: Number of Units Building Type Name

More information

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments

More information

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com 2 Wis Professional Engineer Experienced Facility Director Experienced AHJ WHEA Code

More information

BALTIMORE CITY RENTAL LICENSE INSPECTION FORM RENTAL LICENSING INSPECTOR GUIDANCE

BALTIMORE CITY RENTAL LICENSE INSPECTION FORM RENTAL LICENSING INSPECTOR GUIDANCE BALTIMORE CITY RENTAL LICENSE INSPECTION FORM RENTAL LICENSING INSPECTOR GUIDANCE Checklist items A - L may receive a result of Pass or Fail A. Railing is present for interior and exterior steps with more

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for

More information

January 1, 2014 Mandatory Effective Date

January 1, 2014 Mandatory Effective Date 2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective

More information

Defend In Place 2012 IFC Overview of Institutional Occupancies

Defend In Place 2012 IFC Overview of Institutional Occupancies Defend In Place 2012 IFC Overview of Institutional Occupancies ICC Course No. ICC CEU s = 0.50 SCFA Course 8506-15-0 Nathan Ellis Cell: 864-812-5183 Nathan.Ellis@llr.sc.gov Institutional Occupancies Course

More information

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare

More information

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare

More information

AHC Meeting #7 July 12-13, Occupancy WG Report

AHC Meeting #7 July 12-13, Occupancy WG Report AHC Meeting #7 July 12-13, 2012 Part 1: CTC public comments on I-1/I-2 Condition designations..page 1 Part 2; AHC public comments on I-2 Condition designations Page 6 Part 3: Approved code change G244

More information

5123: information. The graphic plan shall include, but may not be limited to: (a) A primary and secondary means of exit from each floor;

5123: information. The graphic plan shall include, but may not be limited to: (a) A primary and secondary means of exit from each floor; ACTION: Original DATE: 09/30/2005 1:17 PM 5123:2-3-11 Fire safety and emergency response plans. (A) Purpose The purpose of this rule is to ensure the safety of individuals residing in residential facilities

More information

Interim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017

Interim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017 Interim Amendments to Ontario s 2012 Building Code Retirement Homes August 17, 2017 Notice This presentation is intended for general information purposes only. It is not intended as legal or technical

More information

Fire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities

Fire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities Fire & Life Safety Code Compliance Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities LTC, Skilled Nursing Facilities COMMON LIFE SAFETY DEFICIENCIES

More information

Residential Based Care Facilities (6 or less)

Residential Based Care Facilities (6 or less) Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA. 92602 www.ocfa.org 714-573-6180 Residential Based Care Facilities (6 or less) Guideline F-03 Serving

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 75 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K0100 - General Requirements - Other Title General Requirements - Other General Requirements - Other List in the REMARKS

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

FIRE SAFETY PLAN PART 1 BUILDING INFORMATION SECTION. Type of Construction: Combustible Non-Combustible

FIRE SAFETY PLAN PART 1 BUILDING INFORMATION SECTION. Type of Construction: Combustible Non-Combustible FIRE SAFETY PLAN PART 1 BUILDING INFORMATION SECTION BUILDING ADDRESS: Sigma Phi Epsilon (SPE) - 550 West 113 th Street BUILDING OWNER / REPRESENTATIVE: Name: Trustees of Columbia University Address: 535

More information

WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS

WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS 1 WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS TABLE 4.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF ASSEMBLIES Construction

More information

780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS 780 CMR: MASSACHUSETTS AMENDMENTS TO AND THE INTERNATIONAL BUILDING CODE 2009

780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS 780 CMR: MASSACHUSETTS AMENDMENTS TO AND THE INTERNATIONAL BUILDING CODE 2009 780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS 780 CMR: MASSACHUSETTS AMENDMENTS TO AND THE INTERNATIONAL BUILDING CODE 2009 CHAPTER 9: FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope.

More information

THE BASICS OF FIRE ALARM PLAN REVIEW

THE BASICS OF FIRE ALARM PLAN REVIEW THE BASICS OF FIRE ALARM PLAN REVIEW Art Shaw A Shaw & Associates, LLC. ashaw@arthurshaw.com 231.838.3269 Fire Protection System Plan Reviewer FP000006 NFPA Certified Plans Examiner 02-0005 NFPA Certified

More information

Smoke & Carbon Monoxide

Smoke & Carbon Monoxide A Guide to the Massachusetts Smoke & Carbon Monoxide Requirements when Selling a Oneor Two-Family Residence FIRE SERVICES Department of Fire Services PO Box 1025 Stow, MA 01775 978-567-3300 www.mass.gov/dfs

More information

Top (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012)

Top (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012) 1. K62 Automatic Sprinkler Systems - Automatic sprinkler systems are continuously maintained in reliable operating condition and are inspected and tested periodically. 18.7.6, 19.7.6, 4.6.12, NFPA 13,

More information

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition Accreditation Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Primarily based on Section 907 Portions of Section 903 and 909 are included. Portions of Chapter 10 are included.

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Means of Egress

More information