M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle)

Size: px
Start display at page:

Download "M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle)"

Transcription

1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications Elena Carroll, Project Administrator Date: May 20, 2015 Subject: NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle) According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. 25 Members Eligible to Vote 6 Not Returned (Betz, Backstrom, Custer, Durgin, Quillin, Rice) ffirmative on All Revisions (Kasiski, Nelson, Oimette with comment) Negative on one or more Revision (Ingram, Kasiski, Nelson, Oimette) 0 Abstentions The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each second revision. There are two criteria necessary for each second revision to pass ballot: (1) simple majority and (2) affirmative 2 /3 vote. The mock examples below show how the calculations are determined. (1) Example for Simple Majority: Assuming there are 20 vote eligible committee members, 11 affirmative votes are required to pass ballot. (Sample calculation: 20 members eligible to vote 2 = = 11) (2) Example for Affirmative 2 /3: Assuming there are 20 vote eligible committee members and 1 member did not return their ballot and 2 members abstained, the number of affirmative votes required would be 12. (Sample calculation: 20 members eligible to vote 1 not returned 2 abstentions = 17 x 0.66 = = 12 ) As always please feel free to contact me if you have any questions.

2 of 36 5/20/2015 9:27 AM Second Revision No. 7-NFPA [ Detail ] Change title of 8.8 to the following: Telecommunications Equipment Ignition and Fire Performance Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 12:59:51 CDT 2015 Committee Statement Committee Statement: Fire resistance is defined as a property assessing the ability of a material, product, or assembly to withstand fire or give protection from it for a period of time. This chapter addresses fire performance requirements. Response Message: Public Comment No. 21-NFPA [Section No. 8.8] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 17 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard Bosma, Michael J.

3 Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment of 36 5/20/2015 9:27 AM

4 of 36 5/20/2015 9:27 AM Second Revision No. 2-NFPA [ Section No ] ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2013 Rev A ASTM E814, Standard Test Method for Fire Tests of Penetration Firestop Systems, 2013 Rev A 2013a. ASTM E1537, Standard Test Method for Fire Testing of Upholstered Furniture, ASTM E1966, Standard Test Method for Fire Resistive Joint Systems, (2011). Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 10:58:56 CDT 2015 Committee Statement Committee Statement: This revision updates the referenced standards to the most current editions. Response Message: Public Comment No. 2-NFPA [Section No ] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 17 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard Bosma, Michael J.

5 Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment of 36 5/20/2015 9:27 AM

6 of 36 5/20/2015 9:27 AM Second Revision No. 17-NFPA [ Section No ] UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/UL 44, Thermoset-Insulated Wires and Cables, ANSI/UL 83, Thermoplastic-Insulated Wire and Cables, ANSI/UL 444, Communications Cables, 2008, revised ANSI/UL 568, Nonmetallic Cable Tray Systems, 2002, reaffirmed UL 723, Standard for Test For Surface Burning Characteristics of Building Materials, ANSI/UL 900, Standard for Air Filter Units, 2004, revised ANSI/UL 1277, Electrical Power and Control Tray Cables with Optional Optical-Fiber Members, ANSI/UL 1651, Optical Fiber Cable, ANSI/UL 1666, Standard Test for Flame Propagation Height of Electrical and Optical-Fiber Cables Installed Vertically in Shafts, ANSI/UL 1685, Standard for Vertical Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables, 2007, including revisions through July 7, ANSI/UL 2024, Cable Routing Assemblies and Communications Raceways, 2014, including revisions through January 9, ANSI/UL , Information Technology Equipment Safety Part 1: General Requirements, Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 14:31:42 CDT 2015 Committee Statement Committee Statement: update Response Message: Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 17 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention

7 Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard Bosma, Michael J. Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment of 36 5/20/2015 9:27 AM

8 of 36 5/20/2015 9:27 AM Second Revision No. 3-NFPA [ Section No ] Cable Telecommunications. One- and two-way communications service provided over a network, generally through optical fiber-optic and coaxial cable. Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 11:02:26 CDT 2015 Committee Statement Committee Statement: Response Message: This editorial change correlates with National Electrical Code Article 770 which refers to optical fiber cables, not fiber-optic cables. Public Comment No. 4-NFPA [Section No ] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 17 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard Bosma, Michael J. Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C.

9 Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment of 36 5/20/2015 9:27 AM

10 of 36 5/20/2015 9:27 AM Second Revision No. 4-NFPA [ Section No ] Wires and cables intended for powering signal-processing equipment, telecommunications cables, optical fiber cables, and insulated ground wires installed in plenums shall be listed as having a maximum flame spread of m (5.0 ft) or less, a maximum peak optical density of 0.50 or less, and a maximum average optical density of or less when tested in accordance with NFPA 262 or Flame and Smoke Test in the Appendix to CSA C22.2 No. 0.3-M-1996 (FT6 Rating). Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 11:08:41 CDT 2015 Committee Statement Committee Statement: This revision does not extract language from NFPA 90A but simply makes the requirements identical. Note that CSA FT6 is not referenced in NFPA 90A because it has not kept up with the advances incorporated into NFPA 90A. Standards Council has stated that NFPA 90A has jurisdiction over the requirements for materials in plenums. This revision does not incorporate any material or products that are not already referenced in NFPA 76. Response Message: Public Comment No. 17-NFPA [Section No ] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 17 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All

11 Belliveau, Jr., Leonard Bosma, Michael J. Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment 0 of 36 5/20/2015 9:27 AM

12 1 of 36 5/20/2015 9:27 AM Second Revision No. 5-NFPA [ Section No ] Communications raceways installed in plenums shall be listed as having a maximum flame spread of m (5.0 ft) or less, a maximum peak optical density of 0.50 or less, and a maximum average optical density of or less when tested per in accordance with ANSI/UL 2024 or the flame and smoke test in CSA C22.2 No. 0.3, Appendix B (FT6 Rating), Cable Routing Assemblies and Communications Raceways. Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 11:17:28 CDT 2015 Committee Statement Committee Statement: This revision simply slightly revises the requirements by incorporating language that corresponds to the language from NFPA 90A, which has jurisdiction over materials in plenums, in accordance with Standards Council. The reference to the CSA standard is being removed because it has not kept up to date with the changes in NFPA standards. Response Message: Public Comment No. 18-NFPA [Section No ] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 17 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard

13 Bosma, Michael J. Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment 2 of 36 5/20/2015 9:27 AM

14 3 of 36 5/20/2015 9:27 AM Second Revision No. 6-NFPA [ Section No ] * Nonmetallic cable trays used in plenums shall be listed for use in plenums and shall be constructed of materials that are either noncombustible or that exhibit a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or with UL 723, Standard Test Method for Surface Burning Characteristics of Building Materials. Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 11:40:41 CDT 2015 Committee Statement Committee Statement: This introduces the requirements from NFPA 90A for materials in plenums. The requirements for noncombustible or low flame spread and smoke based on testing to ASTM E84 are those that apply to all materials and products not otherwise mentioned with specific requirements. Response Message: Public Comment No. 19-NFPA [Section No ] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 17 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard Bosma, Michael J.

15 Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment 4 of 36 5/20/2015 9:27 AM

16 5 of 36 5/20/2015 9:27 AM Second Revision No. 8-NFPA [ Section No ] 9.1.4* Heat-Producing Appliances. The use of portable Portable heat-producing appliances shall not be located used in any telecommunications equipment area, computer room, individual office areas, individual office cubicles, storage areas, or shipping areas The use of portable heat-producing tools necessary for installation and maintenance activities within the telecommunications facility shall be permitted. Supplemental Information File Name SR_8.docx Description Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 13:19:04 CDT 2015 Committee Statement Committee Statement: Response Message: This revision removes unintended restrictions in An example of an unintended restriction is a heat-producing tool such as a soldering iron or heat shrink device. Public Comment No. 7-NFPA [Section No ] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 17 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A.

17 Rice, Buddy Affirmative All Belliveau, Jr., Leonard Bosma, Michael J. Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment 6 of 36 5/20/2015 9:27 AM

18 Second Revision No. 9-NFPA [ Section No. 9.6 ] 9.6 Physical Security A key box(es), where required by the authority having jurisdiction, shall be listed and installed in an accessible location The operator of the premises shall immediately notify the authority having jurisdiction and provide the new key(s) when a lock shall be changed or re-keyed, and a key(s) to that lock shall be contained in the key box. Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 13:26:29 CDT 2015 Committee Statement Committee Statement: Key boxes are not unique to telecommunications facilities. The requirements in NFPA 1 specifically address the use of key boxes in more detail than do those in Section 9.6. NFPA 76 should only address fire hazards unique to the telecommunications equipment occupancy. More general hazards are already addressed in other NFPA standards. NFPA 1 is the fundamental document that provides general fire protection requirements. It is the definitive standard and should be the only one that contains general requirements. Repeating requirements already in NFPA 1 leads to confusion and conflicting enforcement when requirements of one document diverge from the other, which occurs because they are not on the same revision cycle. Response Message: Public Comment No. 9-NFPA [Section No. 9.6] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 16 Affirmative All 2 Affirmative with Comments 1 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. 7 of 36 5/20/2015 9:27 AM

19 Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard Bosma, Michael J. Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment Negative with Comment Kasiski, Robert NFPA 1 is a general occupancy document. Specific requirements should identified in NFPA 76 for the security of this occupancy. 8 of 36 5/20/2015 9:27 AM

20 Second Revision No. 10-NFPA [ Sections 9.8.1, 9.8.2, 9.8.3, 9.8.4, ] Displays, holiday trees, or other decorations shall not be allowed to obstruct corridors, exit ways, or other means of egress Natural cut holiday trees shall not be permitted Artificial holiday trees, displays, and decorations shall be labeled or otherwise identified or certified by the manufacturer as being flame retardant or flame resistive Only listed electric lights and wiring shall be used on holiday trees and similar decorations Electric lights shall be prohibited on metal artificial trees, displays, and other decorations not labeled for the use of listed lights. Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 13:41:54 CDT 2015 Committee Statement Committee Statement: Section 9.8 already prohibits displays, holiday trees or other decorations in telecommunication areas. Sections through contain requirements not unique to telecommunications facilities. NFPA 76 should only address fire hazards unique to the telecommunications equipment occupancy. More general hazards are already addressed in other NFPA standards. NFPA 1 is the fundamental document that provides general fire protection requirements. It is the definitive standard and should be the only one that contains general requirements. Response Message: Public Comment No. 11-NFPA [Sections 9.8.1, 9.8.2, 9.8.3, 9.8.4, 9.8.5] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 17 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned 9 of 36 5/20/2015 9:27 AM

21 Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard Bosma, Michael J. Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment 0 of 36 5/20/2015 9:27 AM

22 Second Revision No. 11-NFPA [ Section No. 9.9 ] 9.8 Open Flame Devices In nontelecommunications areas, the use of solid-fueled heat sources for warming of food trays shall be permitted and shall be constantly attended and operated with the approval of management Other open flames shall only be permitted as otherwise stated in this document Portable fire extinguishers shall be provided in accordance with NFPA 10. Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 13:42:24 CDT 2015 Committee Statement Committee Statement: Section 9.9 contains requirements not unique to telecommunications facilities. NFPA 76 should only address fire hazards unique to the telecommunications equipment occupancy. More general hazards are already addressed in other NFPA standards. NFPA 1 is the fundamental document that provides general fire protection requirements. It is the definitive standard and should be the only one that contains general requirements. Response Message: Public Comment No. 12-NFPA [Section No. 9.9] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 17 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy 1 of 36 5/20/2015 9:27 AM

23 Affirmative All Belliveau, Jr., Leonard Bosma, Michael J. Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment 2 of 36 5/20/2015 9:27 AM

24 3 of 36 5/20/2015 9:27 AM Second Revision No. 12-NFPA [ Section No ] 9.9 Vacant Areas. Vacant areas or spaces in a building shall be reviewed annually for the fire risk. Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 13:48:45 CDT 2015 Committee Statement Committee Statement: The term vacant areas or spaces is ambiguous. Vacant spaces are not unique to telecommunications facilities. All facilities are vulnerable to the hazards of combustible material stored in vacant spaces. However if those spaces contain stored material, they are not vacant and therefore not covered by Section If the space is truly vacant (i.e., clean and empty floor to ceiling and wall to wall) then there are no additional fire protection measures necessary. The risk is already minimized. In addition, the requirement is vague. It gives no guidance as to what an annual review for the fire risk consists of and what should be done with any findings. Response Message: Public Comment No. 13-NFPA [Section No. 9.11] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 16 Affirmative All 2 Affirmative with Comments 1 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard Bosma, Michael J.

25 Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment Negative with Comment Kasiski, Robert If the vacant area has changed its use and there is no record, inadequate protection may be provided for the additional risk. 4 of 36 5/20/2015 9:27 AM

26 5 of 36 5/20/2015 9:27 AM Second Revision No. 13-NFPA [ Section No ] The pre-fire plan shall be reviewed and updated annually and where as personnel changes, management structure realignment, or facility changes occur that potentially affect the existing pre-fire plan. Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 13:54:32 CDT 2015 Committee Statement Committee Statement: Neither OSHA regulations covering emergency action plans nor NFPA 101 emergency plans require annual review. There is nothing unique about a telecommunications facility that requires annual review. The requirement is vague. No guidance is provided as to what constitutes an annual review. Response Message: Public Comment No. 14-NFPA [Section No ] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 16 Affirmative All 3 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard Bosma, Michael J. Brasseau, Shaun A.

27 Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Kasiski, Robert I disagree with the Committee Substantiation as Telecommunication Facilities are unique as they have been deemed as mission critical so it is imperative that confirmation the pre-fire plan can be implemented. In some cases fire protection is reliant upon the Fire Service as part of the Pre-fire plan and would be addressed in the conditions identified unless there is a annual review. Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment 6 of 36 5/20/2015 9:27 AM

28 7 of 36 5/20/2015 9:27 AM Second Revision No. 1-NFPA [ Section No. A ]

29 8 of 36 5/20/2015 9:27 AM A

30 9 of 36 5/20/2015 9:27 AM The design and installation of fire detection and suppression systems for areas in which aisle containment systems are installed should meet the performance or prescriptive requirements of Chapters 5, 6, or 7 that have been applied to the areas. The following outline provides smoke detector: sensitivity and spacing guidance for protection of signalprocessing equipment in high airflow areas: General For smoke detection systems to detect products of combustion, the products must travel from the source to a sensor or port and arrive there in sufficient density to be detectable. Products of combustion follow forced air streams early in the development of a fire or overheat condition where the influence of mechanical systems is greater than the buoyant forces of the fire or overheat condition. Detection system sensors or ports installed in the paths of cooling air exhaust from the cooled equipment can be expected to respond to a small fire in the equipment sooner than sensors or ports located outside of the ventilation air envelope. To be effective, the detection equipment installed within the ventilation air envelope should be suitable for the temperatures, air velocities, and other conditions present. If suitable detection equipment cannot be installed within the exhaust ventilation air envelope, a fire in the cooled equipment should be expected to grow to a size at which its energy is sufficient to overcome the mechanical forces of the HVAC containment system. In the presence of aisle containment systems used to enhance the effectiveness of cooling signalprocessing equipment, sensors or ports located in hot aisles or in the above ceiling plenum might be effective. Regardless, sensors or ports located on the ceiling in signal-processing equipment areas are a basic requirement and contribute to effective detection over a broad range of signal-processing equipment area configurations. Listed signal-processing equipment has inherent fire-resistant characteristics. Failing or overheated components or connections can lead to smoldering events that produce smoke but tend to remain small due to the very low electrical voltages present at the board level in the signal-processing equipment. Exceptions can occur where a source of energy external to the signal-processing equipment drives increasing involvement of the materials present. In such exceptional cases, flaming fires can result. Automatic fire and smoke detection systems installed to detect smoldering events and/or flaming fires in signal-processing equipment areas are more effective in detecting flaming fires than smoldering events due to the respective release rates of combustion products and the effects of forced air flow on the products of combustion. The greater the air flow, which dilutes and channels detectable products of combustion, the less effective will be the performance of the detection system. Damage or losses that could result from smoldering events or flaming fires in signal-processing equipment prior to detection are likely to be greater in the presence of greater forced air flow due to the likely decrease in detection system performance. Smoke Detection Systems for Very Early Warning Where a smoke detection system is installed for the primary purpose of summoning responsible people to the presence of a small signal-processing equipment fire or electrical event that produces smoke, the system should be arranged with high sensitivity and close spacing to achieve response to low-density products of combustion suspended in air with reasonable stability and tolerance of the environment. Smoke Detection Systems to Initiate Operation of HVAC Dampers or to Close Openings in Fire Rated Walls Where a smoke detection system is installed for the primary purpose of initiating operation of dampers, shutters, doors, or other closures in the event of a fire in a signal-processing equipment area, the system should be arranged with medium sensitivity and spacing less than listed spacing to assure the integrity of fire-resistive barriers. Smoke Detection Systems to Initiate Release of a Fire Suppression Agent Where a smoke detection system is installed for the primary purpose of initiating the release of a fire suppression agent into a signal-processing equipment area, the system should be arranged with low sensitivity, spacing less than listed spacing, and should include a form of logical confirmation of the presence of products of combustion to assure that a single indication does not release the agent. Sensitivity and Spacing Ranges The following is guidance for sensitivity and spacing ranges for different locations in high airflow areas:

31 0 of 36 5/20/2015 9:27 AM (1) Smoke sensor and port spacing on ceilings in the presence of high air movement should follow the requirements of of NFPA 72. (2) Where air changes per hour (ACH) in the room served by the ventilation system exceeds 60, and where the supply air is delivered to the room through a raised floor, smoke sensors or ports under the floor might not be effective in detecting a fire originating under the floor. They might, however, be effective in detecting a fire originating in an air-handling unit supplying air to the underfloor space. (3) In applying the sensor or port spacing, it is recommended that sensors and ports be located at strategic points where smoke is likely to pass; for example, in hot air return streams and at return air registers. (4) For sensors and ports installed in the exhaust/return air stream in hot aisles or above ceiling plenums, the spacing and sensitivities listed in Table A should be used. The guidance in Table A comes partly from a study sponsored by the Fire Protection Research Foundation. That guidance is conservative because it is based on testing using airflow without recirculation into the volume being studied. Table A Recommended Sensitivity and Spacing of Smoke Sensors or Ports in Exhaust/Return Air Streams in Telecommunications Facilities with High Air Flow Where Aisle Containment Is Present Intended Function Low ACH Up to 30 High ACH Greater Than 30 Sensitivity Spacing Sensitivity Spacing Very early warning 0.2%/ft 200 ft 2 0.1%/ft 100 ft 2 Operating dampers, doors, and shutters 1.5%/ft 400 ft %/ft 200 ft 2 Suppression agent release > 2.5% 4%/ft 400 ft 2 > 1.5% 3%/ft 200 ft 2 Notes: (1) See Fire Protection Research Foundation reports Validation of Modeling Tools for Detection Design in High Air Flow Environments, and Validation of Modeling Tools for Detection Design in High Air Flow Environments Phase II, and FM Global report "Experimental Data for Model Validation of Smoke Transport in Data Centers. (2) It is essential that the user understand the material in A prior to the application of the recommended sensitivity and spacing in this table. Where aisle containment systems are installed in an area after the fire detection or suppression systems have been designed and installed in the area, the design and installation of the fire detection and suppression systems should be reviewed for the following: (1) If system changes are necessary to maintain the level of protection as required in (2) If changes to the fire detection or suppression systems are necessary to maintain the previously existing level of protection. Where sensors or ports are installed to monitor return air in accordance with , a review should be conducted to determine that a containment system does not degrade the performance level of the detection system. Supplemental Information File Name SR_1_A _Final_.docx SR_1_Table_A docx Description Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address:

32 1 of 36 5/20/2015 9:27 AM City: State: Zip: Submittal Date: Thu Mar 26 10:13:44 CDT 2015 Committee Statement Committee Statement: A joint task group of the NFPA 75 and 76 technical committees developed more thorough guidance on the subject of detection in high air flow electronic equipment areas. The additional text is based on results of a study sponsored by FPRF and previously known detection application guidance. Response Message: Public Comment No. 23-NFPA [Section No. A ] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 16 Affirmative All 0 Affirmative with Comments 3 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard Bosma, Michael J. Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Negative with Comment

33 2 of 36 5/20/2015 9:27 AM Ingram, Jonathan G. I am still having issue with the guidance given based upon the Hughes report for a number of reasons. 1) The testing Hughes did was with 100% air change with no recirculation of air. You would typically find a substantial amount of air recirculated in a telecomm facility than completely exhausted. Feel the chart using "up to 30" and "Over 30" does not help reference anything or tie back to NFPA 72. We have guidance in NFPA 72 that states up to 60 ACH deration of spacing is down to approximately 125 sq ft per detector, but not sure what the new table is actually telling the designer and installer, and quite frankly is a bit confusing on how we are defining ACH in this section versus NFPA 72 guidance. Nelson, Paul R. Significant concern regarding this table: Table A Recommended Sensitivity and Spacing of Smoke Sensors or Ports in Exhaust/Return Air Streams in Telecommunications Facilities with High Air Flow Where Aisle Containment 3 weeks following our meeting, an air sampling supplier shared with me some information that suggested our spacing of 100 sq. ft. for high air flow will not detect smoke. I think this graph should be reevaluated again before this is published. Ouimette, Ronald D. The reference to NFPA 72, table for spacing is not germane to NFPA 76 and could cause confusion in the standard and reduce the minimum detection level required to prevent a network outage. I believe this section may have been inadvertently carried over from the NFPA 75/76 joint committee discussions to the NFPA 76 annex material. All previous NFPA 76 prescriptive spacing references require 200 sq. ft. spacing for all signal processing (VEWFD) areas, regardless of airflow or air changes per hour. The reference to NFPA 72 table could diminish the minimum detection levels previously established by adding the possibility to increase the spacing requirement. If this was the intent of adding the reference to NFPA 72 table , I would ask what new test data has been provided to substantiate the change and allow the increased spacing? In order to prevent confusion for AHJ's and designers, I recommend that the reference to NFPA 72, table be deleted from the annex material or new test data be provided to substantiate the change.

34 3 of 36 5/20/2015 9:27 AM Second Revision No. 14-NFPA [ Section No. A ] A UL , Information Technology Equipment Safety Part 1: General Requirements, specifies the fire resistance performance of the materials used in making the equipment and therefore provides a level of protection. However, UL does not require fire safety performance testing of the final equipment configuration as Telcordia-GR-63-CORE, Network Equipment Building System (NEBS) Requirements: Physical Protection, does, and does not provide assurances that the fire will not continue to propagate past a single piece of equipment as required by GR-63. Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 13:58:47 CDT 2015 Committee Statement Committee Statement: Fire resistance is defined as a property assessing the ability of a material, product, or assembly to withstand fire or give protection from it for a period of time. Thissection addresses fire performance requirements. Response Message: Public Comment No. 22-NFPA [Section No. A.8.8.3] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 17 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard

35 Bosma, Michael J. Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C. Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment 4 of 36 5/20/2015 9:27 AM

36 5 of 36 5/20/2015 9:27 AM Second Revision No. 15-NFPA [ Section No. G ] G ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA ASTM E648, Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source, 2010e1 2014c. Submitter Information Verification Submitter Full Name: Jon Hart Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Mar 26 14:07:24 CDT 2015 Committee Statement Committee Statement: date update Response Message: Public Comment No. 3-NFPA [Section No. G.1.2.2] Ballot Results This item has passed ballot 25 Eligible Voters 6 Not Returned 17 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Betz, Jeffrey A. Custer, Richard L. P. Durgin, Ronald A. Quillin, Charles A. Rice, Buddy Affirmative All Belliveau, Jr., Leonard Bosma, Michael J. Brasseau, Shaun A. Driggers, Mickey L. Dryden, Steve C.

37 Gardner, Robert P. Ingram, Jonathan G. Johnson, William D. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McNamara, Jack Meyring, William Norton, Thomas F. O'Connor, Daniel J. Reiswig, Rodger Ziegler, Thomas F. Affirmative with Comment Nelson, Paul R. Affirm, no comments Ouimette, Ronald D. Affirmative vote - no comment 6 of 36 5/20/2015 9:27 AM

M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014

M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications

More information

Technical Committee on Telecommunications Facilities (TEL-AAA)

Technical Committee on Telecommunications Facilities (TEL-AAA) Technical Committee on Telecommunications Facilities () M E M O R A N D U M DATE: February 20, 2014 TO: Principal and Alternate Members of the Technical Committee on Telecommunications Facilities () FROM:

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard

More information

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25

More information

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Second Revision No. 3-NFPA [ Section No. 2.3 ] Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler

More information

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Protected Premises Fire Alarm

More information

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ]

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ] of 71 6/11/2014 8:20 AM First Revision No. 36-NFPA 76-2014 [ Section No. 1.1 [Excluding any Sub-Sections] ] This standard provides requirements for fire protection of telecommunications facilities where

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

MEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Initiating Devices for Fire

More information

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application. 1.3.1 This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Furnishings

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Residential

More information

MEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Emergency Power Supplies Kelly

More information

Correlating Committee on Automatic Sprinkler Systems

Correlating Committee on Automatic Sprinkler Systems Correlating Committee on Automatic Sprinkler Systems M E M O R A N D U M DATE: May 14, 2014 TO: FROM: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems Matt Klaus,

More information

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Fire Alarm

More information

Public Comment No. 1-NFPA [ Section No ]

Public Comment No. 1-NFPA [ Section No ] Page 1 of 7 Public Comment No. 1-NFPA 556-2014 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA, 19428-2959. ASTM D2859, Standard

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Building Service and

More information

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018) M EM O RA N D UM TO: FROM: DATE: SUBJECT: Correlating Committee on Combustible Dusts Yiu Lee, Project Administrator January 27, 2017 NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Portable Fire Extinguishers

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Industrial and Medical Gases

More information

MEMORANDUM. NFPA Technical Committee on Hazard and Risk of Contents and Furnishings. NFPA 556 First Draft TC FINAL Ballot Results (A2015)

MEMORANDUM. NFPA Technical Committee on Hazard and Risk of Contents and Furnishings. NFPA 556 First Draft TC FINAL Ballot Results (A2015) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Hazard and Risk of Contents

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Alternative Approaches to

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

MEMORANDUM. NFPA 99 Second Draft Correlating Committee FINAL Ballot Results (A2017)

MEMORANDUM. NFPA 99 Second Draft Correlating Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Correlating Committee on Health Care Facilities Elena

More information

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic

More information

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies

More information

National Fire Protection Association

National Fire Protection Association National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M (AMENDMENT) TO: FROM: Technical Committee on Mercantile

More information

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

WORKING DRAFT OF COMMITTEE MEETING OUTPUT WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF SECOND DRAFT REPORT Document: NFPA 221 Revision Cycle: A2014 Meeting Date: 5/20/2013

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Supervising Station

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

12/21/2015 National Fire Protection Association Report

12/21/2015 National Fire Protection Association Report http://submittals.nfpa.org/terraviewweb/viewerpage.jsp?id=232 2012.ditamap&toc=false&draft=true 1/9 Public Comment No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents

More information

TECHNICAL COMMITTEE ON FIRE CODE

TECHNICAL COMMITTEE ON FIRE CODE TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2

More information

Circulation Report for SIG-TMS Comments Document # 72

Circulation Report for SIG-TMS Comments Document # 72 1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

NFPA Technical Committee on Fire Tests

NFPA Technical Committee on Fire Tests National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Tracy

More information

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fundamentals of Fire

More information

2009 NFPA Text 2009 International Building Code Text Recommendation. NFPA IBC 2009 IBC is most recent

2009 NFPA Text 2009 International Building Code Text Recommendation. NFPA IBC 2009 IBC is most recent 2009 Changes of the Referenced Standards of the National Fire Protection Association- 101 Compared to the International Building Code- 2009 Referenced Standards For the Florida Building Commission And

More information

First Revision No NFPA [ Section No ]

First Revision No NFPA [ Section No ] of 45 10/21/2015 8:54 AM First Revision No. 3501-NFPA 101-2015 [ Section No. 3.3.190.1 ] 3.3.196.1* Ambulatory Health Care Occupancy. An occupancy used to provide services or treatment simultaneously to

More information

Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101

Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101 Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101 For the Florida Building Commission And the Fire Code Advisory Council Introduction The scope

More information

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Water Additives

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017)

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Code Kelly Carey,

More information

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12.

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12. 2/18/2016 National Fire Protection Association Report Committee Input No. 70 NFPA 54 2015 [ Section No. 12.5 ] This was a First Revision that failed ballot. 12.5 Type of Venting System to Be Used. 12.5.1

More information

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM 1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling

More information

Second Revision No. 1 NFPA [ Chapter 2 ]

Second Revision No. 1 NFPA [ Chapter 2 ] Second Revision No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be

More information

Diane D. Matthews, Administrator, Technical Projects. The September 19, 2013 date for receipt of the NFPA 5000 Second Draft Ballot has passed.

Diane D. Matthews, Administrator, Technical Projects. The September 19, 2013 date for receipt of the NFPA 5000 Second Draft Ballot has passed. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Fire Protection Features Diane D. Matthews,

More information

Throughout standard remove references to the following and replace with the following:

Throughout standard remove references to the following and replace with the following: of 35 12/3/2015 7:13 AM Public Input No. 1-NFPA 90A-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/UL and replace with UL. (2) ANSI/ASHRAE

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Residential Occupancies Kelly

More information

M E M O R A N D U M. NFPA 270 First Draft Technical Committee FINAL Ballot Results (F2017)

M E M O R A N D U M. NFPA 270 First Draft Technical Committee FINAL Ballot Results (F2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Tests Kelly

More information

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input Public Input No. 2-NFPA 259-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D 5865, Standard Test Method

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Correlating Committee on Signaling Systems for

More information

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement First Revision No. 1-NFPA 259-2016 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D5865, Standard Test Method

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference Matthews, Diane Subject: Location: Start: End: Show Time As: Recurrence: Meeting Status: Organizer: Required Attendees: Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference http://nfpa.adobeconnect.com/rpbmeet/

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES 1.

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

Air Moving Systems. Fire Safety Inspection and Testing of. NBSIR jan «1933. Washington, DC General Services Administration

Air Moving Systems. Fire Safety Inspection and Testing of. NBSIR jan «1933. Washington, DC General Services Administration National Bureau of Standards Gaithersburg, Maryland 2.0899 NBSIR 87-3660 jan «1933 Fire Safety Inspection and Testing of Air Moving Systems John H. Klote U.S. DEPARTMENT OF COMMERCE National Bureau of

More information

Page 1 of 126 First Revision No. 113-NFPA 45-2013 [ Global Input ] Change all references to Material Safety Data Sheets (MSDS) to Safety Data Sheets (SDS) Submittal Date: Thu May 09 11:40:44 EDT 2013 Response

More information

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document 1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two

More information

PROPOSAL BALLOT DUE BY: Thursday, September 18, 2008

PROPOSAL BALLOT DUE BY: Thursday, September 18, 2008 PROPOSAL BALLOT DUE BY: Thursday, September 18, 2008 NFPA 204 SMO-AAA Standard for Smoke and Heat Venting Staff Liaison: Return Completed Ballot To: Jill McGovern E-Mail to jmcgovern@nfpa.org Fax to 617-984-7110

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Construction

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 2 FROM: Kimberly Shea, Administrator,

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR3002 SAF-HEA (18.1.3.2) Recommendation: 18.1.3.2 Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies

More information

MEMORANDUM. Technical Committee on Fundamentals of Combustible Dusts. NFPA 652 First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Fundamentals of Combustible Dusts. NFPA 652 First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Combustible

More information

2016 Annual Revision Cycle Consent Document NFPA 75

2016 Annual Revision Cycle Consent Document NFPA 75 2016 Annual Revision Cycle Consent Document NFPA 75 The Committee on Electronic Computer Systems produced a Technical Committee Report that received at least one Notice of Intent to Make a Motion (NITMAM)

More information

Report on Public Input June 2014 NFPA 101

Report on Public Input June 2014 NFPA 101 101 PI# 115 SAF-FUR (10.2.1.2) 10.2.1.2 Materials applied directly to the surface of walls and ceilings in a total thickness of less than 1 / 28 in. (0.9 mm) shall not be considered interior finish and

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input Public Input No. 4-NFPA 111-2016 [ Section No. 1.1.4.1 ] 1.1.4.1 * This standard shall not cover the following: (1) Application of the SEPSS (2) Distribution wiring (3) Systems having total outputs less

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Standpipes Elena

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Water Additives

More information

M E M O R A N D U M. NFPA Technical Committee on Fixed Guideway Transit and Passenger Rail Systems

M E M O R A N D U M. NFPA Technical Committee on Fixed Guideway Transit and Passenger Rail Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Fixed Guideway

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical on Laser Fire Protection Kimberly

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

M E M O R A N D U M. NFPA 1911 Second Draft Technical Committee FINAL Ballot Results (F2016 Cycle)

M E M O R A N D U M. NFPA 1911 Second Draft Technical Committee FINAL Ballot Results (F2016 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Department Apparatus

More information

First Revision No. 1-NFPA [ Chapter 2 ]

First Revision No. 1-NFPA [ Chapter 2 ] First Revision No. 1-NFPA 499-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this recommended practice

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

The Technical Committee on Commissioning and Integrated Testing

The Technical Committee on Commissioning and Integrated Testing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: The Technical Committee on Commissioning and Integrated Testing

More information

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Item No. Subject 13-6-1 Call to Order (8:00 A.M) 13-6-2 Roll Call 13-6-3 Approval

More information

Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

Change all instances of flame resistant (hypobaric) to Limited-Combustible (material) in all instances in the document. 1 of 9 10/21/2015 1:22 PM First Revision No. 3-NFPA 99B-2015 [ Global Input ] Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

More information