1 Overview of the Water Detection System 2 Components of a System 4 Design & Planning 5 System Installation Notes 7 Control Panel Installation - HSCPI-K Control Panel Commissioning HSCPC-K Front Panel Indicators 12 Internal Indicators 13 Internal Controls and Terminal Connections 14 Hydrowire Installation and Commissioning 16 Floor Probe or Drip Tray Probe Installation HSFPI Floor or Drip Tray Probe Testing 19 Hydrowire Connection Box 20 Remote Lamp Connection 20 Commissioning Record 21 Hydrowire Layout 23 Probe Layout 24 Consultants Specification 25 Vimpex Limited Star Lane Great Wakering Essex SS3 0PJ Tel: +44 (0) Fax +44 (0) sales@vimpex.co.uk web: DS/HYDINF/ISS.5 1

2 Overview of the Water Detection System The water detection system is designed to detect the intrusion of water in concealed areas or any place where water penetration must be identified so that corrective action can be taken immediately. It will continuously monitor the potential hazards 24 hours a day and has the facility for 24 hours battery standby in the event of power failures. Any water penetration detected will be signalled to a control panel that can give audible and visual alarms. The detection system comprises of three basic components, water detection cable, localised probes and a control panel. Water leak detection systems can be divided into two basic categories: (a) Linear Detection (b) Point Detection The System incorporates both. DS/HYDINF/ISS.5 2

3 Linear Detection Where floor areas, ducts and suspended ceilings need to be protected this is usually best achieved by installing lengths of Hydrowire. Hydrowire is a highly conductive cable extremely sensitive to moisture. It is available in 5 metre lengths (K2104) or 10 metre lengths (K2105). Each length of Hydrowire is terminated with a male and female din plug to enable them to be plugged together up to maximum zone length of 50 metres. As soon as the cable detects moisture this will trigger an alarm. Each zone of Hydrowire is plugged into a Connection Box (K2106) and terminated by an End of Line Plug (K2110) which enables it to be continuously monitored for defects. The connection box is then connected to the control panel using 0.75mm 2 2 core cable (K2111). Up to 24 zones can be incorporated on one panel. Point Detection Where there is a need for more localised detection such as HVAC plant, drip trays, elevator shafts and storage areas a probe can be installed and adjusted to the required level of protection. As with the cable the detection of moisture triggers an alarm and is also monitored by the line fault circuit of the control panel. Additionally the probe has an LED indicator on top to identify exactly which probe has been activated. Up to 20 detectors can be used in each zone. DS/HYDINF/ISS.5 3

4 Components of a System This guide will help to select products from the range for water detection in a variety of applications. Basic Components Control Panel (1 to 24 Zones) There are two types of control panel available: a) K1000 Series This panel features an ABS enclosure and is available in 1, 2, 4 & 6 Zones. This has a common Fault Volt- Free Contact and an Alarm Volt-Free Contact for remote signalling or plant shutdown on the occurrence of any fault or alarm condition. It does not have zonal repeat contacts. b) K3000 Series This panel is housed in a metal enclosure. The K3000 panel features a normally open repeat contact for fault and alarm for each zone in addition to the K1000 features. This is available in 2, 4, 8, 12 and 24 zones. Larger zone requirements can be manufactured. The following components are common to both panels: Hydrowire (5 metre Length) K2104 Hydrowire (10 metre Length) K2105 End of Line Plug K2110 Hydrowire Connection Box K2106 Leader Cable K2111 Hydrowire / Leader Cable Fixing Clips K2112 Batteries K1220 Options Floor Mounted Probe K2101 Drip Tray Probe K2102 Remote Lamp Unit K2103 Strobe Light SL Voice Sounder F/A/1W Sounder (Multi Tone) 892A6A0 FlashTone - Combined sounder and strobe DS/HYDINF/ISS.5 4

5 Design & Planning Design Notes Water finds its own level so careful consideration must be given to slopes and dips in the area to be protected. Can the cable be installed to avoid doorways and traffic. Floor probes can be used to protect wells, cavities or hollows. Is the site occupied? If so, will the site require just visible alarms or will there be a need for conventional or voice enhanced sounders? Is a remote signalling device required? How is the cable to be fixed to the floor? Are other services going to interfere with it? Check with the building owner or manager for future plans or designs that may alter the requirements or siting of the equipment. Will the system require expansion? Give consideration to the possible addition of extra zones. Maximum length of cable should be kept to 50 metres Maximum number of detectors per zone should not exceed 20. Only one remote indicator to each Hydrowire Connection Box. DS/HYDINF/ISS.5 5

6 Design Guidelines Probe: Maximum recommended coverage: - 20 sq.m per detector Maximum recommended detectors per zone - 20 Maximum distance between probes for perimeter detection - 3 metres Sensor height above finished floor - 1mm to 15mm Leader cable mm round 3A Hydrowire Cable: Maximum recommended length per zone - 50 metres Recommended pitch between cable for area protection - 2 metres Minimum bend radius - 150mm Note: Do not mix probes and Hydrowire on the same zone DS/HYDINF/ISS.5 6

7 System Installation Notes 1. Check design with the kit and components in hand to check that all materials are on site. Check the BOM. 2. Store Hydrowire lengths carefully in a dry area. 3. Prepare the installation area. Remove any furniture or equipment that may obstruct installation. Make sure the area is clean and free from debris. 4. Install the Control Panel in accordance with the appropriate installation procedure HSCPI-K1000 (ABS Panel) or HSCPI-K3000 (Steel Panel) 5. Commission the Control Panel in accordance with the appropriate test procedure HSCPC-K1000 or HSCPC-K Install the Hydrowire in accordance with the installation procedure HSHWI Commission the Hydrowire in accordance with the test procedure HSHWC Install and test any floor probes in accordance with the appropriate test procedure HSFPI Test the complete system 10. Commission 11. Train the owner / operator DS/HYDINF/ISS.5 7

8 Control Panel Installation - HSCPI-K3000 Safety This product should be installed, commissioned and maintained by or under the supervision of competent persons according to good engineering practice and : IEE Regulations for the electrical equipment of buildings Codes of Practice Statutory Requirements Any instructions specifically advised by the manufacturer This equipment is designed to be operated at V AC mains supplies and is of Class 1 construction. As such it must be connected to a protective earthing conductor in the fixed wiring of the installation. Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe. Power Supply Input There are four terminals provided for connection to the power supply. (i) (ii) (iii) (iv) + to +24 Volt load output to VE Load output at PSU PF to power fault output at PSU (Not normally used) PO to power on output at PSU DS/HYDINF/ISS.5 8

9 1. Unpack the unit and verify that all parts are enclosed. (2 Enable Control Keys, 2 Control Locking Keys, Control Panel with correct zone quantity) 2. Unlock the front panel using the key provided. This will expose the internal equipment and four fixing holes. 3. Unclip the printed circuit boards and place them in a safe area for later installation. 4. Locate the unit on the wall in the agreed position and mark the fixing points through the dished mounting holes (see Fig. 1). Remove the unit. Drill and fit suitable wall plugs and screw the panel to the wall. Carefully refit the printed circuit boards. 5. Use the knockouts provided to make off the cables. Earth or drain wires should be kept as short as is practicable and be connected to a metal cable gland making sound electrical contact with the enclosure. 6. If additional or larger cable entries are required any swarf or debris must be cleared from the inside of the equipment. Failure to do this will result in equipment malfunction and could represent a danger to building occupants. 7. The mains fuse must only be replaced with a 3 amp fuse conforming to BS: This equipment is designed to be powered from the 220V 240V mains supply. The mains connection must include a protective earth conductor to the requirements of BS:7671 (see Fig 1) 9. The mains supply must be from a separate dedicated fused spur labelled WATER ALARMS - DO NOT SWITCH OFF 10. Connection of the 24V battery supply should be carried out with great care and respect. Misconnection or short circuiting of the battery terminals will result in FIRE. 11. The system fuse F1 is a 5 amp 20mm quick blow fuse and should only be replaced with mains and battery disconnected. DS/HYDINF/ISS.5 9

10 Figure 1 DS/HYDINF/ISS.5 10

11 Control Panel Commissioning HSCPC-K Connect the control panel to the mains supply with the batteries in place. Only the green [SUPPLY HEALTHY] indicator should be illuminated. The system healthy indicator will extinguish in the event of : a) Mains Failure b) Battery Disconnection c) System Fuse Failure d) Total Power Failure 2. [Enable Controls] No controls are enabled unless the [Enable Control Key Switch] is activated. Whilst the switch is activated the buzzer should beep every few seconds and the Alarm Silence and Lamp Test & Reset switches are enabled. 3. [Lamp Test & Reset] Insert the key and test the [Lamp Test & Reset] test switch. All indicators should be illuminated. (If any zones are in alarm condition these will reset provided that the silence alarms switch has first been operated and the input signal e.g. Hydrowire or probe has been restored to normal.) 4. [Silence Alarm] To silence an alarm activated by operation of a detection zone, i.e. Hydrowire or Probe, press the [Silence Alarm] Button. The alarm silenced indicator will illuminate and the sounders will stop. Note: To mute the fault buzzer, press the alarm switch. DS/HYDINF/ISS.5 11

12 Front Panel Indicators [System Fault] The system fault indicator will illuminate under any abnormal condition. Certain conditions may be diagnosed without looking inside the enclosure as follows: 1) System Fault [ON], Supply Healthy [OFF] = Mains or battery failure 2) System Fault [ON], Zone Fault [ON] = Zone fault in indicated zone [Alarm Silenced] The alarm silenced indicator should only be accompanied by one or more steady alarm indicators and indicates that the sounders have been silenced. Operation of subsequent alarm zones or the alarm test switch will extinguish the alarm silenced indicator. [Zone Fault Indicators] Illumination of a zone fault indicator may mean that one or more trigger devices are inoperative and requires immediate attention. Zone fault indicators will illuminate in the event of: 1. Disconnection or severance of zone wiring 2. Short circuit on zone wiring 3. Removal of Hydrowire or probes from the zone 4. Disconnection of the end of line monitor resistor 5. Test Mode Activated [Alarm Indicators] Upon detection of an alarm the amber zone alarm indicator will flash to give warning of the zone or area in alarm and the common alarm indicator will be illuminated. This will be accompanied by a pulsing buzzer within the control panel and the operation of the sounders if fitted. DS/HYDINF/ISS.5 12

13 Internal Indicators The internal indicators are numbered 1 to 6 and represent the following: S1 S2 FUSE REM CON (C) TEST (T) Illuminates in the event of a short circuit to sounder circuit 1 or failure of Fuse F3 Illuminates in the event of a short circuit to sounder circuit 2 or failure of Fuse F4 Illuminates in the event of either failure of F1 or F2. Failure of F2 will be indicated by the front panel System Fault indicator. Failure of F1 will not illuminate the front panel System Fault indicator. This indicator will illuminate upon activation of the isolate remote (dil switch A) switch on the CON.05 pcb. The front panel system fault indicator will also illuminate. Disconnection of ribbon cables to extender boards. The front panel system fault indicator will also illuminate. Operation of one or more zone test switches. DS/HYDINF/ISS.5 13

14 Internal Controls and Terminal Connections The panel has internal DIL switches which are usually used for engineering functions. These switches should in normal circumstances be in the off position. Further details are available if required. Water Detection Circuits Two to twenty-four water detection circuits are provided and supply 28 volts (+ or 5%) for the operation of trigger devices (Hydrowire or Probes). Terminals for the water detection circuits are labelled Z1+ and Z1- to Z24+ and Z24- for positive and negative connections respectively. It is important to observe the polarity of these connections for correct operation of the system. Sounder Circuits Two sounder circuit outputs are provided and labelled (S1+ and S1-) and (S2+ and S2-). These outputs will operate together upon activation of a water detection zone or the Remote Alarm input. Each sounder is protected by a 500mA fuse. A standard electronic sounder such as the Banshee MT or more usually a voice enhanced sounder, the Fire-Cryer, which will announce Water Alarm Activated. Immediate attention required can be fitted to these circuits. Both outputs are monitored against open and short circuit faults in the field wiring. Any such faults are annunciated by the front panel system fault indicator immediately. The sounder circuit is normally fitted with a 22K or 27K end of line monitoring resistor. Fault VFCO Contact A volt-free contact is provided for remote signalling or plant shut down on the occurrence of any fault condition. The contact will also be operated upon total power failure. Alarm VFCO Contacts A volt-free contact is provided for remote signalling or plant shut down on the occurrence of any alarm condition or alarm test condition. All contacts are rated at 30Vd.c. 1 amp maximum and should under no circumstances be used to switch greater voltages or currents. DS/HYDINF/ISS.5 14

15 Repeat Contact A normally open contact is provided for each zone. Remote Control Input Four terminals are provided for duplicating the controls on the front panel. These are marked OV, AL, S and R. Remote Signal Contact A volt-free changeover circuit is provided for signalling to an auto dialler, house system or plant shutdown relay. This contact operates on any alarm condition and remains operated until the system is reset. DS/HYDINF/ISS.5 15

16 Hydrowire Installation and Commissioning HYDROWIRE INSTALLATION HSHWI-100 (1) Check the length of cable for fraying or damage. (2) Connect the lengths of Hydrowire to be used in the zone and terminate with an End of Line Plug (K2110). Temporarily connect the cable to the control panel via a Hydrowire Connection Box (K2106). Check that no fault or alarm is reported. (3) Remove the end of line plug and check that an alarm is reported. (4) Disconnect the Hydrowire and store ready for installation. (5) Ensure that the installation area is clean and free from water, dust and debris. EOL Plug K2110 Note Red Warning Tag (6) Lay the length of Hydrowire on the floor of the area to be protected so that the distance between any two Hydrowires is no more than 2 metres. (For localised protection of sources of potential water leakage, such as air conditioning and water filled radiators, the distance between Hydrowires may be greater). (7) The cable should be installed so that it remains in contact with the floor for as much of its length as is possible. This would usually require the use of Hydrowire fixing clips (K2112). Great care must be taken when using other fixing clips. Although the cable is quite sturdy is can be damaged by crushing or excessive bending. A bend radius of 150mm is recommended as a minimum. DS/HYDINF/ISS.5 16

17 (8) The terminating Hydrowire Connection Box (K2106) should be secured to the wall or floor such that the Hydrowire does not have to be stretched or pulled to reach it. (9) Plug the cable into the Hydrowire Connection Box (K2106). (10) The red warning label should be left such that it is clearly visible. (11) Terminate the cable with an end of line plug (K2110). Notes : Hydrowire should not come into contact with surface temperatures greater than 70 o C. Lengths greater than 50 metres are not permissible. HYDROWIRE COMMISSIONING HSHWC-100 Once all terminations have been made and the system is powered, the Hydrowire is ready for testing. This is best achieved by dipping the forefinger and thumb into a cup of tap water, shaking off the excess drips and then gripping the Hydrowire firmly whilst rolling it slowly. This should produce a reaction at the control panel and if fitted, the remote lamp unit and or sounder. Over-wetting of the Hydrowire should be avoided as a great deal of time can be wasted waiting for the Hydrowire to dry out. DO NOT MIX PROBES AND HYDROWIRE IN THE SAME ZONE. It is advisable to test all lengths of Hydrowire before fixing into place so that should a fault be found it can easily be replaced. DS/HYDINF/ISS.5 17

18 Floor Probe or Drip Tray Probe Installation HSFPI -100 The floor probe is connected to the control panel via a 6 way connector / junction box (See Fig. 11). Note: The 6K8 resistor taken from the zone being used in the control panel must be installed as shown in Fig. 11with the last Probe in the zone (maximum of 20 probes per zone.) Figure 9 Floor Probe Floor Probe K2101 Figure 10 Drip Tray Probe Drip Tray Probe K2102 DS/HYDINF/ISS.5 18

19 Floor or Drip Tray Probe Testing (1) This is best achieved by dipping the tips of the probe pins into a cup of tap water. (2) This should produce an immediate reaction at the control panel, the LED mounted on top of the probe and, if fitted, the remote lamp unit and or sounder. Figure 11 Probe Wiring Diagram - TO PANEL + - REMOTE LAMP + 6K8 EOL RESISTOR BROWN GREEN / YELLOW BLACK BLUE BROWN GREEN / YELLOW BLACK BLUE TO WATER DETECTOR PROBE TO WATER DETECTOR PROBE Note that the last junction box must have the end of line resistor fitted. DS/HYDINF/ISS.5 19

20 Hydrowire Connection Box The K2106 Connection Box, when triggered presents an impedance of 470 ohms to the 24 Volt circuit from the control panel. Figure 8 Hydrowire Connection Box The + and terminals inside the Connection Box must be connected via a 2 wire 0.75mm round 3A cable to the Z+ and Z- terminals at the control panel. The end of line resistor at the control panel can be discarded. It is advisable to leave the lid off the control panel until all testing is complete. Remote Lamp Connection In some installations, particularly in floor voids, it is desirable to identify the area in which water has been detected with a remote indicator unit (K2103) mounted above the void. This can be achieved by wiring a K2103 remote lamp unit to the ve and REM terminals in the K2106 Connection Box. Note : Only one remote lamp unit should be connected to each Connection box. DS/HYDINF/ISS.5 20

21 Commissioning Record Customer / Site Address Town / City Post Code Site Tel No. Site Contact Name Control Panel Type No. of Hydrowire Zones No. of Probe Zones Authorised Engineer Company Tel No. Date 1. Control Panel Control panel is connected via a dedicated power supply Green Supply Healthy lamp illuminated. No other lamps illuminated Internal buzzer operates when enable key is inserted Reset test switch illuminates all lamps Alarm Test Switch operates the internal buzzer 2. Hydrowire Installed Not Installed Hydrowire checked for damage Hydrowire wetted and checked for correct zone alarm End of Line Plug removed and checked for correct zone fault Check correct clips installed and not crushing or over bending Hydrowire Red warning labels are in place DS/HYDINF/ISS.5 21

22 Commissioning Record 3. Connection Boxes Installed Not Installed Fixed securely Wiring terminated correctly 4. Floor and Drip Tray Probes Installed Not Installed Din plug disconnected from probe and checked for correct zone fault Probe conductor pins set at correct height Probe pins immersed in water and checked for correct zone alarm Probe terminated correctly into junction box The above commissioning record has been completed by : Authorised Engineer Print Name Company Tel No. Date The above commissioning record has been accepted by : Authorised Representative Print Name Company Tel No. Date DS/HYDINF/ISS.5 22

23 Hydrowire Layout Part Ref Description Qty K Zone Steel Control Panel 1 K2105 Hydrowire 10M Length 8 K2110 End of Line Plug 2 K2106 Connection Box 2 K2112 Pack of Fixing Clips 3 K2102 Floor Mounted Probe 2 K/Z/Box1 ABS Junction Box for Probes 2 *PS V 2.0ah Battery 2 *K2111 Leader Cable (50M 2 core 0.75mm 3A) 1 **F/A/1/BH Voice Enhanced Sounder 1 Component marked (*) can be sourced locally Components marked (**) are optional DS/HYDINF/ISS.5 23

24 Probe Layout DS/HYDINF/ISS.5 24

25 CONSULTANTS SPECIFICATION FOR WATER LEAK DETECTION The water detection system should be able to detect the intrusion of water in concealed areas or any place where water penetration must be identified so that corrective action can be taken immediately. It will continuously monitor the potential hazards 24 hours a day and has the facility for 24 hours battery standby in the event of power failures. Any water penetration detected will be signalled to a control panel that can give audible and visual alarms. The detection system will be able to provide linear detection using water detection cable and point detection using localised probes and a control panel. The water detection cable must be reusable after detecting moisture and be monitored for fault at all times. Additionally the probe will incorporate an LED indicator to identify exactly which probe has been activated. Up to 20 detectors should be able to be connected to a single zone. Sensor height should be adjustable from 1mm to 30mm from above finished floor. The probe shall be monitored for faults at all times and shall be of the latching type. The Control Panels will be available as a single zone panel as well as multi zones up to a minimum of 24 zones. The control panel will provide Fault Volt-Free Contacts and Alarm Volt- Free Contacts for remote signaling or plant shutdown on the occurrence of any fault or alarm condition. DS/HYDINF/ISS.5 25

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd OPERATIONAL NOTES FOR CONCEPT FIRE PANEL. NOTE ON NEW FIRE PANELS, POSITION 1 ON THE SIX WAY INTERNAL OPTION SWITCH IS TURNED ON, DISABLING THE ZONAL SOUNDERS. TO ENABLE ZONAL SOUNDERS TURN OFF. Operation

More information

Operation and Maintenance Manual

Operation and Maintenance Manual (FKER Series) Repeater Panel (FKER, FKER, FKER8) Operation and Maintenance Manual Man-9EL Issue June Index Section Page. Introduction.... Safety and mounting.... Technical specification.... Control panel

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology

Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology Fire-Cryer Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX Shaping Alarm Technology Fire-Cryer Plus The Fire-Cryer range of voice sounders was first introduced to the market by Vimpex in 1999.

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL INSTALLATION AND COMMISSIONING MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax:

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

OPERATION AND INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in

More information

DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual

DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: 01825 733600 DMWD 1 to 4 Zone Water Detection with Distance to Leak Measurement Installation and Operation Manual

More information

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk

More information

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014 Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual Man-1078EL Issue 01 February 2014 B Index Page 1. Introduction... 3 1B2. Safety and mounting... 3 2B3. Technical specification...

More information

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System SYSTEM MANUAL FT1-SB Single Zone Fire Alarm System DOCUMENT HISTORY Issue Date Description Written By Checked By Draft 0 2/9/2008 Original Document. A. Shenouda C. Orr Issue 1 4/11/2011 Update drawing

More information

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual VoCALL - CFVCC5 Compact 5 Line Exchange Unit Installation & Commissioning Manual Introduction A VoCALL Emergency Voice Communications System (EVCS) is a fixed, secure, bi-directional, full duplex voice

More information

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL The LeakStopper Multizone detects the presence of water in environments where it is not supposed to be. Should water

More information

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL 3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where

More information

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation. Saffire+ 8-12 User & Installation Manual IMPORTANT This manual should be left with the panel after installation. We reserve the right to change product specifications without prior notice. Copyright VRC

More information

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual BiWire Flexi BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual Contents Contents 1. INTRODUCTION... 4 1.1 Purpose...4 2. THE BIWIRE FLEXI FIRE DETECTION & ALARM

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

Installation and user manual for the BiWire / Conventional Repeater Panel

Installation and user manual for the BiWire / Conventional Repeater Panel Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....

More information

Conventional Fire Control Panel

Conventional Fire Control Panel (FKEW Series) Conventional Fire Control Panel (FKEW2, FKEW4, FKEW8) Man-1138EL Issue 01 February 2014 Contents 1. Introduction... 4 2. Safety... 4 4. Technical specification... 5 5. Control panel fascia...

More information

EXTINGUISHING AGENT RELEASE MODULE

EXTINGUISHING AGENT RELEASE MODULE EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153

More information

5000 INSTALLATION GUIDE

5000 INSTALLATION GUIDE 5000 INSTALLATION GUIDE Table of Contents Section Page No 1. INTRODUCTION... 3 2. WARNINGS AND CAUTIONS... 3 3. UNPACKING... 3 4. INSTALLATION... 4 5. CONTROL PANEL - REMOVING ITEMS BEFORE MOUNTING...

More information

LEAKSTOPPER 1 Single zone water leak detection system

LEAKSTOPPER 1 Single zone water leak detection system LEAKSTOPPER 1 Single zone water leak detection system WHAT DOES THE PRODUCT DO? The LeakStopper 1 detects the presence of water in environments where it is not supposed to be. Should water be detected

More information

SECURIT 700L PLUS ENGINEERING MANUAL

SECURIT 700L PLUS ENGINEERING MANUAL SECURIT 700L PLUS ENGINEERING MANUAL C & K Systems Ltd 13/03/97 C031-096-02 NEW ENHANCED FEATURE SET Securit 700L PLUS Engineering instructions INTRODUCTION The Securit 700L is a microprocessor intruder

More information

Surveyor Envoy-MINI 4

Surveyor Envoy-MINI 4 Surveyor Envoy-MINI 4 CONTENTS SECTION 1 INTRODUCTION Page 4 About this manual Page 4 System design and planning Page 4 Panel types Page 4 General Page 4 SECTION 2 INSTALLATION Page 5 General Page 5 ESD

More information

SOLO Single Loop Addressable Fire Control Panel

SOLO Single Loop Addressable Fire Control Panel Solo Single Loop Analogue Addressable Fire Control Panel Apollo Protocol Installation, Commissioning & Operating Manual Issue 03 June 1999 CONTENTS Section... Page 1. Introduction...1 2. Safety...2 3.

More information

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above Surveyor Excel Fire Alarm Control Equipment Network version Programming Manual VERSION 14.0 and Above MASTER MANUAL Drawing S1606. PCB Layout guide for XLK range of control panels FCPXLK-2/4/6/8 & FCPXLK2/4/6/8TW

More information

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL FIRE CONTROL PANEL MAG2/4 USER MANUAL AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 READ THIS MANUAL BEFORE CONNECTING THE EQUIPMENT AND KEEP IT SAFE FOR FUTURE REFERENCE. To call our technical support

More information

FSTP2-2-wire 2 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS2 Issue 01 April 2012

FSTP2-2-wire 2 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS2 Issue 01 April 2012 FSTP2-2-wire 2 Zone Conventional Fire Control Panel Operation and Maintenance Manual Man-1078FS2 Issue 01 April 2012 Index Page 0B1. Introduction... 3 1B2. Safety and mounting... 3 2B3. Technical specification...

More information

Installation, Commissioning & Operating Manual

Installation, Commissioning & Operating Manual EN54 APPROVED 2-4 ZONE ALARMSENSE CONTROL PANEL Installation, Commissioning & Operating Manual 810a/05 Approved Document UI-ALS-01 Issue 2.0 0832 Haes Systems Ltd, Columbia House, Packet Boat Lane, Cowley

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

FSTP4-2-wire 4 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS4 Issue 01 April 2012

FSTP4-2-wire 4 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS4 Issue 01 April 2012 FSTP4-2-wire 4 Zone Conventional Fire Control Panel Operation and Maintenance Manual Man-1078FS4 Issue 01 April 2012 Index Page 1. Introduction... 3 2. Safety and mounting... 3 3. Technical specification...

More information

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES Prem1er EVACS16 VOICE ALARM CONTROL PANEL 4 16 ZONES Installation Manual Approved Document No: GLT.MAN-141 PAGE 1 INDEX INDEX... 2 Summary... 3 Safety information & use of this manual... 5 Installation

More information

LEAKSTOPPER RANGE Multizone water leak detection systems

LEAKSTOPPER RANGE Multizone water leak detection systems LEAKSTOPPER RANGE Multizone water leak detection systems WHAT DOES THE PRODUCT DO? The LeakStopper detects water leaks and instantly triggers an alarm to warn you. It is capable of monitoring between 2

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels The panels are designed in accordance with the requirements of EN54 Part 2:1997 (and include optional clauses

More information

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS Fire Control Panel Installation & Programming Manual TBLE OF CONTENTS Page Getting Started 2 Power Supply Unit 3 Inputs 4 Outputs 4 LED Indications 4 User Keypad Functions 5 Engineer Keypad Functions 6

More information

Installation and Operating Instructions

Installation and Operating Instructions Twinflex and Multipoint Installation and Operating Instructions Rafiki Protection Limited 55 Springvale Industrial Estate Cwmbran South Wales NP44 5BD United Kingdom Tel. (+44) 01633 865558 Fax (+44) 01633

More information

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL 6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)

More information

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No...G108WO1.DOC Serial No... Issue Date...17 th SEPTEMBER 1999 Software Version...1.4 APPROVED TO: NZS 4512:1997 AS/NZS 3548:1992 Fire Alarm

More information

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL 26 Aug 2015 V1.8 Page 1 SECTION CONTENTS PAGE NO. 1.0 SYSTEMS DESCRIPTION 1.1 General descriptions 2 1.2 Master Alarm PCB 2 1.3 Zone Display Board 2 1.4

More information

User Operation Manual

User Operation Manual APPROVED BY: JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL User Operation Manual PAGE 1 of 6 1 CONTENTS 1. FIRE - GENERAL... 3 2. FIRE - ZONES 1 OR 2 - AUTOMATIC MODE... 3 3. FIRE - ZONES

More information

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP FLx-LT-XP CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP Installation, Configuration and Operating Manual MAY 2008 MIE-MI-580I_FL rev.003 Information in this document is subject to change without notice.

More information

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel Installation and Operating Manual HLSI-MN-025-I v.05 April 2015 Note: This manual is valid for the following control panel models: NFS-Supra

More information

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 highline WINDOW CONTROLS INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM SVCS-1 * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 CERTIFICATE OF COMPLIANCE SVCS-1 We the undersigned

More information

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview Water Leak Detector - Four Zone with open/short-circuit detection Product overview The AX-WLDF is a four zone water leak detection module with open or short circuit sensor cable detection. The module must

More information

Control Panel Engineering and Commissioning Instructions

Control Panel Engineering and Commissioning Instructions Twinflex - V3 Fire Detection & Alarm System Control Panel Engineering and Commissioning Instructions (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0338 Issue 9 Fike s policy is one of continual improvement

More information

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses BCU Power Supplies Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses Installation, Commissioning and Operating Manual BCU RANGE OF

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

USER MANUAL & MAINTENANCE GUIDE OG OO

USER MANUAL & MAINTENANCE GUIDE OG OO M+48. USER MANUAL & MAINTENANCE GUIDE OG OO What to do if the Fire Alarm Panel shows an Alarm (Red LED) Write down which LEDs are lit (either in the log book, or on a piece of paper for transferring to

More information

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels The panels are designed in accordance with the requirements of EN54 Part 2:1997 (and include optional clauses

More information

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater APPROVED BY: JBJ Precept EN Fire Detection/Alarm Panel & Precept EN Repeater Logbook PAGE 1 of 19 List of Contents 1. FIRE ALARM SYSTEM MAINTENANCE... 3 2. USER RESPONSIBILITIES... 3 2.1. RESPONSIBLE PERSON...

More information

FIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF

FIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF DETECTOR TYPE ED816 ZE 1 ZE 2 ZE 3 ZE 4 ZE 5 ZE 6 ZE 7 S ZE 8 CIRCUIT 1 ZE 9 ZE 10 ZE 11 ZE 12 ZE 13 ZE 14 ZE 15 ZE 16 CIRCUIT 1 POWER POWER SUPPLY GENERAL MENT DC GENERAL SYSTEM ALARM DELAYED ALARM RESOUND

More information

Premier Hazard STC Instructions

Premier Hazard STC Instructions PREMIER HAZARD Ltd Bessingby Industrial Estate Bridlington YO16 4SJ Tel: +44 (0) 113 239 1111 Fax: +44 (0) 113 239 1131 www.premierhazard.co.uk info@premierhazard.co.uk Premier Hazard STC Instructions

More information

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation The most user friendly Contents Section 1 Overview of System 1.1 Kit Contents 1.2 Tools Required 1.3 System Features Security Alarm System L S 4 0 0 Section 2 Planning your Installation 2.1 Location of

More information

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Australia Issue 01 April 2012 Contents 1 Introduction 3 2 Safety 3 3 Installation 4 3.1 Mounting the Cabinet 4 4 Specifications

More information

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

FIREBETA EXTINGUISHING CONTROL PANEL (ECP) F I R E D E T E C T I O N A N D C O N T R O L FIREBETA EXTINGUISHING CONTROL PANEL (ECP) Three versions: 2 areas of detection and 1 area extinguishing 4 areas of detection and 1 area extinguishing 4 areas

More information

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL The LeakMonitor alarm panel is a microprocessor controlled fully adjustable alarm system suitable for multizone

More information

Accessible Toilet Alarm

Accessible Toilet Alarm N C 9 5 1 D E S I G N & I N S T A L L A T I O N G U I D E Accessible Toilet Alarm This equipment must be installed and maintained by a suitably skilled and technically competent person. This document provides

More information

SYSTEM 5000 USER MANUAL

SYSTEM 5000 USER MANUAL SYSTEM 5000 USER MANUAL Table of Contents Section Page No 1 Introduction: -... 3 1.1 Procedure:... 3 1.2 Warnings and Cautions:... 3 2 User Control Levels:... 4 3 User Passwords:... 4 4 Controls and Displays:

More information

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-5

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-5 EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-5 MAN2995-2 05/09/12 TABLE OF CONTENTS Section Page No. 1 About This Manual... 3 1.1 Introduction...

More information

Menvier Fire System MF9300

Menvier Fire System MF9300 Menvier Fire System MF9300 Eight and sixteen zone control panels Installation and User Instructions and Systems Log IMPORTANT THIS MENVIER FIRE PANEL IS DESIGNED TO BE USED WITH POLARISED AND SUPPRESSED

More information

Control Panel User Guide (TO BE RETAINED BY THE USER)

Control Panel User Guide (TO BE RETAINED BY THE USER) Fire Detection & Alarm System Control Panel V3 (Suitable for Quadnet control panels from V2.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-0585 Issue 7 Fike s policy is one of continual improvement

More information

Precept Marine Control Panel Application Guide

Precept Marine Control Panel Application Guide Precept Marine Control Panel Application Guide Contents Page 1.0 Cabinet Specifications 2 2.0 Panel Hardware Specifications 5 3.0 Panel Configuration 8 4.0 Technical Specifications 8 5.0 Battery Sizes

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES POWER SUPPLY AND BATTERY CHARGER AC AND DC STATUS INDICATORS ENOUGH POWER TO SUPPORT UP TO 3 MAGLOCKS OR ELECTRIC STRIKES PLUS REQUIRED

More information

installation & maintenance manual LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL approved document no. DFU rev 5

installation & maintenance manual LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL approved document no. DFU rev 5 LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL installation & maintenance manual approved document no. DFU7004000 rev 5 CFP 2/4/8 ZONE LPCB APPROVED FIRE PANEL INSTALLATION & MAINTENANCE MANUAL

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels The panels are designed in accordance with the requirements of EN54 Part 2:1997 (and include optional clauses

More information

Features. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign

Features. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign Features DATASHEET Connects to multiple sensing instruments One/Two Channel Device Bright solid state LED Alarm Display Audible Alert (internal and external) High reliability, fully dual redundant alarm

More information

Smoke Vent Control Panel PCB4 V4 Installation Manual

Smoke Vent Control Panel PCB4 V4 Installation Manual Smoke Vent Control Panel PCB4 V4 Installation Manual 10A PCB4 Control Panel Do Not Remove From PCB4 Control Panel www.besafedirect.com Page 1 Contents Page 3) Important Regulations, Safety, Maintenance,

More information

Door Release Power Supply

Door Release Power Supply www.protectingpeople.co.uk Door Release Power Supply Engineer / Installation Manual Document: VI55.1 Protecting People Printed : 04/03/2004-1 - Ventcroft Ltd Door Release Power Supply Engineer / Installation

More information

Interface and EOL Modules 8

Interface and EOL Modules 8 Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface

More information

GAS SUPRESSION CONTROL PANEL:

GAS SUPRESSION CONTROL PANEL: GAS SUPRESSION CONTROL PANEL: MODEL NAME: COMPANY: DELTA 437/2, Main Road, Mandwali Fazalpur, Delhi-110092 Page 1 ABOUT THE PRODUCT ASES is very proud of to introduce DELTA the completely digital microprocessor

More information

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-9

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-9 EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-9 TABLE OF CONTENTS Section Page No. 1 About This Manual... 3 1.1 Introduction... 3 1.2 References...

More information

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 PAT E N T System 88 COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 Pg 1 of 12 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description

More information

Conventional & Twin-wire Fire System

Conventional & Twin-wire Fire System Conventional & Twin-wire Fire System Advanced Customer Service At Advanced we re not just famous for our fire systems. Our Advanced360 customer support, service and technical training are widely acknowledged

More information

Maintenance Guide EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM

Maintenance Guide EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM Maintenance Guide 2015 EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM Contents Overview 3 Pre-testing Guidelines 4 Daily Maintenance 4 Weekly Maintenance 5 Six Monthly Maintenance

More information

Doc. No.: OMPII.DOC Rev. 2 Written By: Raj Patel Checked By: AJC Approved By: JBJ Date: 03/05/05

Doc. No.: OMPII.DOC Rev. 2 Written By: Raj Patel Checked By: AJC Approved By: JBJ Date: 03/05/05 Doc. No.: OMPII.DOC Rev. 2 Written By: Raj Patel Checked By: AJC Approved By: JBJ Date: 03/05/05 PRESCIENT II GAS EXTINGUISHANT CONTROL PANEL INSTALLATION, OPERATION & MAINTENANCE MANUAL Page 1 of 27 CONTENTS

More information

FIRE ALARM CONTROL PANEL FVC01-08

FIRE ALARM CONTROL PANEL FVC01-08 FIRE ALARM CONTROL PANEL FVC01-08 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Radal Technology Limited Unit 1, Webber Court Billington Road, Burnley Lancashire, BB11 5UB Tel: +44 (0) 1282 463 770 Fax: +44

More information

LeakSafe. solutions. WaterSwitch2. Installation Instructions

LeakSafe. solutions. WaterSwitch2. Installation Instructions LeakSafe solutions TM WaterSwitch2 Installation Instructions WATERSWITCH2 COMPONENTS WaterSwitch2 Valve Control Extended Range Valve Driver Valve Water Flow Sensor Leak Detection tape available in 0.3M

More information

The Remote alarm Panel, TYPE RAPv2

The Remote alarm Panel, TYPE RAPv2 1. Introduction The Remote alarm Panel, TYPE RAPv2 The microprocessor based remote monitor from Metron Eledyne is the latest version of a whole line of successful products, marketed previously under the

More information

INSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder

INSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder INSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder 1) Introduction The Appello tone and speech annunciation sounder has three different styles in AC and DC. A105NAPPX

More information

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1 Gas Safety Products Merlin CT1650+ Gas Interlock System Installation, operating and maintenance 09/05/2016 S&S Northern Ltd 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel (Suitable for TWINFLEX pro control panels from V1.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-1028 Issue 2 Fike s policy is one of continual

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

Ax60+ Multi-Gas, Quick Connect Option

Ax60+ Multi-Gas, Quick Connect Option Ax60+ Multi-Gas, Quick Connect Option Analox Limited 15 Ellerbeck Court, Stokesley Business Park, North Yorkshire, TS9 5PT, UK UK/RoW T: +44 (0)1642 711400 F: +44 (0)1642 713900 US T: (714) 891-4478 W:

More information

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1 Matrix2000 User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 s Version: 2.0 Revision: 1 IMPORTANT INFORMATION Limitation of liability It is mandatory, Matrix2000 panel to be installed in accordance

More information

Intruder - Fire - Water Combined Alarm

Intruder - Fire - Water Combined Alarm 65 Intruder - Fire - Water Combined Alarm Installation Manual and User Operating Instructions TALE OF CONTENTS Page First Power-Up 2 Power Supply Unit 3 Input & Detection Circuits 3 Output & Alarm Circuits

More information