1 San Francisco Housing Authority (SFHA) Work Order, Inspection and Fire Safety Analysis August 215 Presented to Resident Services, Operations and Personnel (RSOP) Committee September , 215
2 Table of Contents Major Work Order Activities 3 Work Order Summary 4 Addressing the Backlog 5 August 215: Open Work Order Analysis by AMP 6-7 Fire Safety and Inspections Reporting 8-11 Appendix Open Work Order Analysis by Trade
3 Major Work Order Activities Declaration of Emergency SFHA declared a state of emergency on July 1 st, 213, allowing the Authority to hire two contractors to provide supplemental maintenance services to 23 Asset Management Projects (AMPs) with 3,8 work orders outstanding Site-Based Maintenance Implementation As part of its conversion to Asset Management and compliance with the HUD Stop Loss Action Plan, in November 213, SFHA implemented site-based maintenance and through staff training and hiring now has 68 maintenance mechanics assigned to the Authority s AMPs 3
4 Work Order Summary Work Orders As of 8/31/215 Percent of the original 3,8 open work orders have been closed 1% Open work orders as of 8/31/215 1,874 Work orders that have been open for less than 3 days 1,376 Work orders that have been open for 3 days or greater 498 4
5 Addressing the Backlog* Next Steps and Progress to Date SFHA has implemented a FIFO methodology, keeping work orders open for no later than 6 days between July and August 215 (with Elite, some work orders were completed but not closed within the timeframe) While addressing the backlog, SFHA is still able to respond to created work orders, demonstrated capacity to consistently close work orders in excess of those created For month end August 215, SFHA had 498 work orders open over 3 days Open Work Orders Open Work Orders June 215 vs August 215 1,6 1,4 1,2 1,513 1,376 Under 3 Days 1, Days or Greater Jun-15 Jul-15 Aug-15 * Backlog refers to work orders that have been open for 3 or more days. 5
6 August 215: Open Work Order Analysis by AMP The highest concentration of open work orders is at AMP Sunnydale and AMP 973 Hunters Point A East & West Open Work Orders AMPs with Most Open Work Orders June vs. August Jun-15 Aug AMP 6
7 August 215: Open Work Order Analysis by AMP On average, open work orders at AMP 977 has been open for 37.4 days, which is above the overall average of 24.2 days Days Average Age of Open Work Orders as of August Overall Average Age: 24.2 Days AMP 7
8 Fire Prevention and Safety Reporting Next Steps and Progress to Date Fire Safety and Prevention SFHA has completed fire safety inspections at 3,421 apartments, with 12,66 smoke detectors and combination smoke/carbon monoxide detectors installed or replaced. SFHA intends to complete inspections at all family and Rosa Parks units, a total of 3,448. SFHA s goal is to complete all inspections next month. Smoke Detector Notices As work is completed, Smoke Detector Notices are provided to each household reminding them of their lease obligations regarding smoke detectors. Smoke Detector Notices are sent out in English, Chinese, Spanish, Vietnamese and Russian to all residents annually to remind them of their lease obligations regarding smoke detectors. Lease states that residents must not damage, remove, or tamper with the operation of smoke detectors installed; this lease violation puts residents at risk in the event of a fire. Residents are asked to acknowledge that they understand these requirements at the time of annual recertification. 8
9 Inspections Performed as of August , 12,66 Fire Prevention and Inspections Data 8/31/215 12, 1,771 1, 1,98 8, 6, Actual 8/31/215 Goal Month End 8/31/215 Goal Month End 9/3/215 4, 3,421 3,492 3,421 3,492 3,492 3,492 2, Smoke and CO2 Detectors Installed/Replaced Apartments Inspected and Detectors Installed Distribute Smoke Detector Notices 9
10 August 215: Uniform Physical Condition Standards Inspections for Occupied Units Uniform Physical Condition Standards (UPCS) Inspections SFHA property managers perform UPCS inspections of all apartments in conjunction with the annual recertification process for residents, including verification of hard-wired, battery back-up smoke detectors are working properly. 6, UPCS Inspections For ALL Occupied Units 5, 4, 3,621 4,845 4,448 3, 2, Actual 8/31/215 Goal Month End 8/31/215 Goal Month End 9/3/215 1, Property Manager UPCS Inspections 1
11 August vs. June 215: Uniform Physical Condition Standards Inspections per AMP 38 UPCS inspections were completed across 23 AMPs at SFHA during August 215 Inspections 7 July vs. August 215 inspections by AMP July August AMP 11
12 Appendix 12
13 August 215: Trade Work Order Analysis Plumbing open work orders account for 38.2% of all open work orders for the month of August 8 Open Work Orders by Trade June vs. August Plumber Maintenance Mechanic Carpenter Electrician Glazier Painter Vendor - Pest Control Tile Layer Jun Vendor - Mold and Mildew Aug-15 Steamfitter Trade 13
14 Trade Work Order Analysis - Backlog There were 498 backlogged work orders for the month of August Backlog Work Orders by Crew
CROWN YEARLY PROPERTY SCHEDULE
This Yearly Property Schedule is simply a guide to managing your Facility. Please reallocate duties as they suit the management of your Facility, however, note that all tasks should be listed on the schedule
More informationLEASEHOLD YEARLY PROPERTY SCHEDULE
This Yearly Property Schedule is simply a guide to managing your Facility. Please reallocate duties as they suit the management of your Facility, however, note that all tasks should be listed on the schedule
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 3 Page 1 of 6 I. PURPOSE This policy establishes the steps required for performing the monthly fixed systems inspections and the semi-annual systems testing. Fixed systems include; wet chemical
More informationUK HOUSEHOLDERS SPEND 16.6 BILLION ON HOME MAINTENANCE IN 2008
41/09 Saturday 4 th April 2009 This report is part of a series of research pieces published by the Lloyds Banking Group. Data on home maintenance has been drawn from the ONS publications Consumer Trends
More informationTechnician Tools CAN/ULC-S CAN/ULC-S537-13
September 21 2016 Edmonton, AB Technician Tools CAN/ULC-S536-13 CAN/ULC-S537-13 Presented By: Mark Wilson Disclaimer The following presentation is in no way affiliated with, or presented on behalf of any
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report
More informationSMOKE/CARBON MONOXIDE DETECTOR REQUIREMENTS
HOMES BUILT PRIOR TO JANUARY 1, 1975 WITH NO RENOVATIONS As of December 1, 2016, upon sale or transfer Must be located on every level of the residence Must be located on the ceiling at the base of each
More informationUnderstanding the Varying Viewpoints of the Water Utility Provider and Landscape Contractor
Understanding the Varying Viewpoints of the Water Utility Provider and Landscape Contractor Debra Lane, CLIA, Water Conservation Representative City of Santa Rosa, CA Introduction Water agencies in the
More informationUNIVERSITY. Facilities Management
EAST TENNESSEE STATE UNIVERSITY Facilities Management Policy Number: 700.10 Title: Fire Protection Impairment Program Implementation Date: April, 2008 Last Revised: August 4th, 2014 Introduction The probability
More informationBULLETIN: Subchapter 4 Retrofit Requirements for Nightclubs
Department of Community Affairs Division of Fire Safety Fire Code Enforcement BULLETIN: 2009-1 SUBJECT: REFERENCE: Subchapter 4 Retrofit Requirements for Nightclubs N.J.A.C. 5:70-4.1(b) 2, N.J.A.C. 5:70-4.7(a),
More informationPart 745 Lead-Based Paint Poisoning Prevention in Certain Residential Structures
Part 745 Lead-Based Paint Poisoning Prevention in Certain Residential Structures Overview Safe Work Practice Requirements - RRP Common Misconceptions Enforcement & Outreach Public & Commercial Buildings
More informationHome Inspection Report
Pfeifer Home Inpsection, LLC 8332 Crystal Pointe Lane Indianapolis, Indiana 46236 317-340-1734 Lic #HI01700103 Home Inspection Report Columbus, IN 47201 Page 1 of 20 Table of Contents Definitions 2 General
More informationCARBON MONOXIDE ALARM STANDARDS ACT - ENACTMENT Act of Dec. 18, 2013, P.L. 1229, No. 121 Cl. 35 An Act
CARBON MONOXIDE ALARM STANDARDS ACT - ENACTMENT Act of Dec. 18, 2013, P.L. 1229, No. 121 Cl. 35 An Act Providing standards for carbon monoxide alarms; and imposing penalties. The General Assembly of the
More informationAustralian Standard. Automatic fire detection and alarm systems System design, installation, and commissioning AS
AS 1670 1986 Australian Standard Automatic fire detection and alarm systems System design, installation, and commissioning This Australian standard was prepared by Committee FP/2, Automatic Fire Detection
More informationWater Heater Innovations Marathon Water Heater Limited Warranty Policies & Procedures
INTRODUCTION Water Heater Innovations (WHI) offers a Limited Warranty against defects in materials and workmanship on all its products. Our warranty program was developed to assure those who buy and sell
More informationBecome a WM Recycling All Stars Champion!
RECYCLE MORE. EARN REWARDS. Become a WM Recycling All Stars Champion! Waste Management wants to reward you and your residents for recycling more and recycling right! THE STEPS Snohomish County property
More informationFood Scraps Diversion Cart Tag Study
Food Scraps Diversion Cart Tag Study On behalf of King County Solid Waste Division June 23, 2017 Cascadia Consulting Group EXECUTIVE SUMMARY Table of Contents Table of Contents... 2 Executive Summary...
More informationShelter submission to the DCLG review of the Smoke and Carbon Monoxide Alarm (England) Regulations 2015
Submission Shelter submission to the DCLG review of the Smoke and Carbon Monoxide Alarm (England) Regulations 2015 /policylibrary 2010 Shelter. All rights reserved. This document is only for your personal,
More informationKITCHEN TRENDS - January 2016 INTERNATIONAL COMPARISON. Overview of Kitchen Trends in Houzz Inc.
2017 KITCHEN TRENDS - INTERNATIONAL COMPARISON January 2016 Overview of Kitchen Trends in 2016-2017 Big Ideas HEALTHY RENOVATORS In most surveyed countries,* one in four or more homeowners who are renovating
More informationa) Establishment of emergency procedures to be followed at the time of an emergency;
5.10 Fire Safety 5.10.1 Introduction The Corporation is responsible for carrying out the provisions of the Ontario Fire Code. This section outlines our responsibilities as well as inspections and testing
More informationRiverside Fire Department
PERFORMANCE AUDIT Riverside Fire Department Fire Prevention Division ~ Managing False/Avoidable Fire Alarms AU15-01 Office of the City Manager Internal Audit Division Cheryl Johannes, Internal Audit Manager
More informationMONTH-BY-MONTH GUIDE TO HVAC MAINTENANCE
Just like any critical piece of equipment, your heating and cooling systems require regular HVAC maintenance to keep them running properly. Home and business owners should stay on top of maintenance tasks
More informationCommittee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM
1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:
More informationGATEWAY BUILDING ELEVATOR AND ESCALATOR SERVICES
29 One Gateway Plaza Los Angeles, CA 90012-2952 213.922.2000 Tel metro.net SYSTEM SAFETY AND OPERATIONS COMMITTEE JANUARY 16, 2014 SUBJECT: ACTION: GATEWAY BUILDING ELEVATOR AND ESCALATOR SERVICES APPROVE
More informationThe InSinkErator City of Philadelphia. How Food Waste Disposers Can Benefit Municipalities
The InSinkErator City of Philadelphia P R O J E C T How Food Waste Disposers Can Benefit Municipalities BACKGROUND The InSinkErator City of Philadelphia P R O J E C T How Food Waste Disposers Can Benefit
More informationSouth Lyon Fire Department 2012 Annual Report
South Lyon Fire Department 2012 Annual Report Message from the Chief During 2012, continual improvements were made to the organization, operation, and administration of the South Lyon Fire Department.
More informationIndex. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9
Index Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8 Fire Risk Assessments 9 Fire Alarm Systems 10-20 Locations 10 Servicing 11 12 Activations 13 14 Weekly Checks
More informationCity of Regina Alarm Bylaw
City of Regina Alarm Bylaw For more information visit the City of Regina website. BYLAW NO. 2004-24 THE FALSE ALARM BYLAW THE COUNCIL OF THE CITY OF REGINA ENACTS AS FOLLOWS: Purpose 1 The purpose of this
More informationCommercial Application/Plan Review Submittal Checklist
Commercial Application/Plan Review Submittal Checklist The following checklist has been compiled to assist in expediting the commercial plan review and permit issuance process. Please take a moment to
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot # 59-87, Adamjee Export Processing ZONE, Adamjee Nagar, Siddergonj, Narayangonj, Siddirgonj, Narayangonj Dhaka Bangladesh 09 Jun 2014 The
More information7 windows with wood shutters... in & out in an hour! All the shutters fit like like a glove thanks to their precise measurements.
Customer Feedback Summary Of 2,249 customers surveyed, 1,156 responded Clean & Safe 97% Installation Crew 91% Professional & Organized 86% Quality Of Materials 94% Quality Of Workmanship 92% Schedule 85%
More informationUCSF 2014 Long Range Development Plan
Final UCSF 2014 Long Range Development Plan Building on 150 Years: UCSF Plans for 2035 November 2014 Updated to reflect LRDP Amendments #1 #4 (through May 2017) Tejal Desai, PhD, Professor, Department
More informationSUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING.
SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING Table of Contents Section Title Page 1 Introduction 2 2 Proposed Schedule 2 3 Instructions
More informationContents. Glossary
Contents Glossary ------------------------------------------------------------------------------------------------------ 6 1. Introduction to the IDS 1632 -------------------------------------------------------------
More informationFlorida Building Code Chapter 9 Fire Protection Systems Advanced Course
Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors
More informationSite Security Plan - Operations Baron Winds Project
Site Security Plan - Operations Baron Winds Project August 2017 Table of Contents 1. Introduction... 3 2. Access Roads... 3 3. Wind Turbines... 3 4. Substation... 4 5. Operations and Maintenance Building...
More informationIDS816 User Manual H Issued January 2009
1 Contents Glossary-------------------------------------------------------------------------------------------------------------------6 1. Introduction to the IDS 816---------------------------------------------------------------------------7
More informationWLAC Facilities Committee Meeting. September 18, 2017
Campus Program Report WLAC Facilities Committee Meeting September 18, 2017 Page 1 DSA approved the plans on May 15, 2017. Notice to Proceed was issued June 8, 2017 and the project remains on schedule for
More informationWeatherization Assistance Program (WAP) Space Heater Policy
Department of Energy MEMORANDUM Date: March 18, 1992 Subject: To: Weatherization Assistance Program (WAP) Space Heater Policy Support Office Directors, WAP Program Managers BACKGROUND An estimated three
More informationLAKE JOHANNA FIRE DEPARTMENT
LAKE JOHANNA FIRE DEPARTMENT 2017 ANNUAL FIRE REPORT REPORT PREPARED BY: DEBI KRAUSE OFFICE MANAGER & TIM BOEHLKE FIRE CHIEF Lake Johanna Fire Department 2017 Annual Fire Report In 2017 the Lake Johanna
More informationUser s Information Guide R2A
Pi HSC505 Home Security Controller User s Information Guide R2A Page 1 of 15 of its development program. 1This document and product are copyrighted and all rights are reserved. Introduction Convention
More informationFirst Revision No. 88-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement. 3 of /21/2013 1:03 PM
3 of 326 11/21/2013 1:03 PM First Revision No. 88-NFPA 72-2013 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 70, National Electrical Code, 2011 2014 edition. NFPA 96, Standard
More informationAcquisition and Collection Development Section
Acquisition and Collection Development Section ACTION PLAN 2011-2013 REVISED SEPTEMBER 2010 REVISED AND ANNOTATED AUGUST 2012 Background information The Acquisition and Collection Development Section focuses
More informationTable of Contents Board of Education of Queen Anne's County Comprehensive Maintenance Plan Page
Table of Contents Board of Education of Queen Anne's County Comprehensive Maintenance Plan 2015 2020 Page Purpose of Plan... 1 Objectives of Maintenance... 1 Personnel Organization... 1 Supporting Services...
More informationORDINANCE NO. Establishing Fire and Life Safety Requirements for Existing Multi-Family Residential Buildings Classified as Group R, Division Occupancy
ORDINANCE NO. Establishing Fire and Life Safety Requirements for Existing Multi-Family Residential Buildings Classified as Group R, Division Occupancy WHEREAS, the City of Bremerton has previously exercised
More informationMaryland Updates Smoke Alarm Law What You Need to Know
Maryland Updates Smoke Alarm Law What You Need to Know Fire and Rescue personnel are frequently the only smoke alarm experts the general public will meet. The department s Safety in our Neighborhood and
More informationNERC s Compliance Enforcement Initiative Find, Fix, Track and Report Implementation
NERC s Compliance Enforcement Initiative Find, Fix, Track and Report Implementation Compliance Committee Meeting Open Ken Lotterhos, Associate General Counsel and Director of Enforcement February 8, 2012
More informationFIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe
FIRE SAFETY PLAN Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA May / 2017 Prepared by: Chris Pancoe TABLE OF CONTENTS Contents A. BUILDING AUDIT:... 3 BUILDING DESCRIPTION... 3 1. Level
More informationAIRPORT OFFICE BUILDING. Smoke Control System. Testing Procedures Manual. September 10, 2016
IMPACT ENGINEERING, INC. AIRPORT OFFICE BUILDING Smoke Control System Testing Procedures Manual September 10, 2016 All Rights Reserved This manual is protected by the U.S. Copyright Law (Title 17 United
More informationFire Safety Requirements for Peer Review
Fire Safety Requirements for Peer Review SITE: DATE: REVIEWER: Focus Area 1. Fire Safety Binder Section A. Is there a Fire Safety Binder on site? B. Is the Table of Contents the most recent edition? C.
More informationWatchguard WGAP864 User Manual
Watchguard WGAP864 User Manual v1.0 Issued September 2016 1 2 Table of Contents Glossary... 5 1. Introduction to your Watchguard WGAP864... 6 2. Before Operating your Alarm System... 6 3. Understanding
More informationNFPA 101 SAF-RES PUBLIC COMMENTS
Page 134 of 195 Public Comment No. 3-NFPA 101-2013 [ Section No. 28.7.6.1 ] 28.7.6.1 New draperies, curtains, and other similar loosely hanging furnishings and decorations shall be flame resistant as demonstrated
More informationLA GRANGE FIRE DEPARTMENT JANUARY 2018
LA GRANGE FIRE DEPARTMENT JANUARY 2018 A SERVICE PUBLICATION OF THE LA GRANGE FIRE DEPARTMENT 8-579-2338 LOCAL EVENTS 2018 71 st Annual Pet Parade Saturday June 2, 2018 9:30 AM 11:00 AM Farmers Market
More informationSAFETY POLICY AND PROCEDURE MANUAL All Euramax Subsidiaries. Number F-2.0 Emergency Eyewash / Emergency Showers
Number F-2.0 Issued: 1/2009 Revised: 9/2013 Page 1 of 3 1.0 PURPOSE: To minimize the risk of injury by providing emergency eyewash and/or emergency shower stations at all manufacturing facilities and to
More informationCarbon Monoxide Alarm Update
MAYOR GARY O. PHILLIPS VICE MAYOR BARBARA HELLER COUNCILMEMBER KATE COLIN COUNCILMEMBER DAMON CONNOLLY COUNCILMEMBER ANDREW CUYUGAN MCCULLOUGH FOR IMMEDIATE RELEASE FEBRUARY 6, 2013 FIRE DEPARTMENT FIRE
More informationTHE GENERAL ASSEMBLY OF PENNSYLVANIA SENATE BILL
HOUSE AMENDED PRIOR PRINTER'S NOS., 1 PRINTER'S NO. 10 THE GENERAL ASSEMBLY OF PENNSYLVANIA SENATE BILL No. 0 Session of 0 INTRODUCED BY BROWNE, ARGALL, YUDICHAK, FARNESE, WASHINGTON, STACK, BREWSTER,
More informationUnderstanding the Code Pad lights...4. Code Pad tones...5. Fully arming the system On MODE...6. Fully arming the system - Quick Arm MODE...
TABLE OF CONTENTS...Glossary of terms...2...code Pad Diagram...3 Understanding the Code Pad lights...4 Code Pad tones...5 Fully arming the system On MODE...6 Fully arming the system - Quick Arm MODE...6
More informationSECTION 915 CARBON MONOXIDE DETECTION
SECTION 915 CARBON MONOXIDE DETECTION 915.1. General. Carbon monoxide alarms and carbon monoxide detectors shall be installed in buildings as required in accordance with Section 915.2 for residential buildings
More informationSECTION : FIRE ALARM & DETECTION SYSTEMS
SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction
More informationSubject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees
Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees Purpose: To establish procedures to be followed when a fire
More informationCity of Milpitas. We invite applications for the position of: Fire Prevention Inspector
Annual Salary Range: $ 118,831 - $143,804 Post Date: August 29, 2017 Close Date: September 12, 2017, 5:00 p.m. Why Milpitas? Located at the southern tip of the San Francisco Bay, the City of Milpitas is
More informationBUILDING DIVISION. Multi-family Rental Inspection Program SELF-CERTIFICATION APPLICATION
SC_Application.doc (rev. 04/24/2017) BUILDING DIVISION Multi-family Rental Inspection Program SELF-CERTIFICATION APPLICATION Please refer to the Self-Certification Application, Affidavit and Checklist
More informationUPCS. Inspection Standard
UPCS Inspection Standard Summary The purpose of the physical inspection process is to provide HUD with the ability to assess whether its properties are in a safe, decent, sanitary condition and in good
More informationEarly Warning Fire Detection Engineering
Early Warning Fire Detection Engineering Conference Presentation Author: Adrian Haenni Senior Project Manager EARL WARNING Objective Nature of an Early Warning System Structured method for a successful
More informationInspection Report. Prepared for: Tonia Mann. Property Address: 402 Leslie Court McDonough, GA Date: March 07, 2013
Inspection Report Prepared for: Tonia Mann Property Address: 402 Leslie Court McDonough, GA 30253 Date: March 07, 2013 Inspector: Charles Mann Edifice Inspections, Inc. (770) 594-2222 www.edificeinspections.com
More informationOPERATIONAL GUIDELINE. Office of the Fire Commissioner O.G.# Revision #1 TITLE: ISSUING ORDERS Page 1 of 8
TITLE: ISSUING ORDERS Page 1 of 8 PURPOSE: SCOPE: POLICY: To ensure a consistent approach to the issuance of Province fire orders. All Local Assistants to the Fire Commissioner. All orders shall be dealt
More informationThe Future of Smart Technology
The Future of Smart Technology What Consumer s Want Presented by: Two Paths to Market Products Systems 2 2 Smart Home Market Overcoming Barriers to Smart Home Adoption Presented by: % of Respondents Barriers
More informationFunctional Performance Test
Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control
More informationReport Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D
November 10, 2014 Mr. Carlos Khantzis Textures 3D 31280 Oak Crest Dr. #4 Westlake Village, CA 91361 Our Reference: Subject: SV19490/4786557998 Report Of Surface Burning Characteristics Tests On Samples
More informationEC 5.10 FIRE PREVENTION MANAGEMENT
EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively
More informationBATHROOM TRENDS - October 2017 INTERNATIONAL COMPARISON. Overview of bathroom trends in Houzz Inc.
2017 BATHROOM TRENDS - INTERNATIONAL COMPARISON October 2017 Overview of bathroom trends in 2016-17 Big Ideas LAST UPDATED MORE THAN 15 YEARS AGO In most surveyed countries,* at least half of bathrooms
More informationDispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth
Determination 2016/058 Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth Summary This determination considers whether signage is required between
More informationEDA Scottish Section Regional Business Forum
EDA Scottish Section Regional Business Forum 1 The trade association for Electrical Contractors in Scotland Founded in 1900 as the Electrical Contractors Association of Scotland Over 1200 members SELECT
More informationSECURITY SYSTEM NOTES
SECURITY SYSTEM NOTES Installing/Service Company For Service Call Central Station Duress Code FUNCTION CODES Function Code Controls Function EMERGENCY ACTIVATION KEYS (check if enabled) Fire Auxiliary
More informationA Notification under Article 12 of Regulation (EU) No 1025/2012 1
EUROPEAN COMMISSION ENTERPRISE AND INDUSTRY DIRECTORATE-GENERAL Sustainable Growth and EU 2020 Standards for Boosting Competitiveness Brussels, 02/07/2014 A Notification under Article 12 of Regulation
More informationFIRE SAFETY IN SHARED OR RENTED ACCOMMODATION
FIRE SAFETY IN SHARED OR RENTED ACCOMMODATION Did you know? Landlords obligations to keep your home safe from fire People living in rented or shared accommodation are seven times more likely to have a
More informationMonitoring Natural Air Corn Drying A Demonstration Project
Biological Systems Engineering Biological Systems Engineering: Papers and Publications University of Nebraska - Lincoln Year 1988 Monitoring Natural Air Corn Drying A Demonstration Project Richard O. Pierce
More informationPublic Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance
Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance It is ordained by the Town Council of the Town of New Shoreham
More informationArticle 3: Police Regulated Occupations and Businesses. Division 37: Burglary, Robbery and Emergency Alarm Systems
Article 3: Police Regulated Occupations and Businesses Division 37: Burglary, Robbery and Emergency Alarm Systems 33.3701 Definitions Defined words appear in italics. Except as otherwise provided, for
More informationCombination Type AFCI
Combination Type AFCI Evolution of the Arc Fault Circuit Interrupter www.usa.siemens.com/afci 2 Alarming Statistics According to the U.S. Fire Administration (USFA), an estimated 67,800 fires, 485 deaths,
More informationCountywide Recycling and Disposal Facility Weekly Progress Report 08/22/08
Countywide Recycling and Disposal Facility Weekly Progress Report 08/22/08 This Weekly Progress Report is prepared by Countywide and submitted to the OEPA weekly by the close of business on each Friday.
More informationAMENDED IN BOARD 07/26/16 ORDINANCE NO [Fire, Housing, Building Codes - Fire Safety Requirements for Existing Buildings]
FILE NO. 160422 AMENDED IN BOARD 07/26/16 ORDINANCE NO. 165-16 1 [Fire, Housing, Building Codes - Fire Safety Requirements for Existing Buildings] 2 3 Ordinance amending the Fire Code and the Housing Code
More informationSmoke & Carbon Monoxide
A Guide to the Massachusetts Smoke & Carbon Monoxide Requirements when Selling a Oneor Two-Family Residence FIRE SERVICES Department of Fire Services PO Box 1025 Stow, MA 01775 978-567-3300 www.mass.gov/dfs
More informationX-Ray Protection Program
OFFICE OF ENVIRONMENTAL HEALTH AND SAFETY Approved by: Date: November 2016 2016 University of New Hampshire Office of Environmental Health and Safety. All rights reserved. University of New Hampshire Page
More informationSTATE OF MAINE Department of Public Safety Office of State Fire Marshal 52 State House Station Augusta, ME
Paul R. LePage GOVERNOR STATE OF MAINE Department of Public Safety Office of State Fire Marshal 52 State House Station Augusta, ME 04333-0052 John E. Morris COMMISSIONER Joseph E. Thomas STATE FIRE MARSHAL
More informationTHE ANNUAL FIRE SAFETY REPORT
THE ANNUAL FIRE SAFETY REPORT 2016 Portland State University Campus Public Safety ANNUAL FIRE SAFETY REPORT The report contains information about the number and location of such fires, evacuation plans
More informationAudio Monitoring: A system which allows a person supported to be heard by support staff to ensure their well-being and security.
Health & Safety Manual Equipment ENVIRONMENTAL CONTROLS POLICY AND PROCEDURES POLICY STATEMENT Community Living Windsor recognizes that some individuals may require specialized support arrangements as
More information2017 Concordia College Moorhead MN Campus Public Safety Fire Safety Report
2017 Concordia College Moorhead MN Campus Public Safety Fire Safety Report FIRE SAFETY Students residing in Concordia College residence halls are provided with training and information that will enable
More informationStandard Development Timeline
Standard Development Timeline The drafting team maintained this section while developing the standard. It will be removed when the standard becomes effective. Description of Current Draft This draft is
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 21 0800 - COMMISSIONING OF FIRE SUPPRESSION SYSTEMS GENERAL 1.1 SUMMARY General 1. Work under this contract shall meet the requirements of Division 01, General Requirements, Conditions of Contract,
More informationRESIDENCE HALL FIRE REPORT
your vehicle. If you must do so, lock it in your trunk or conceal any valuables so they are not visible. SUMMARY OF PERSONAL AND PROPERTY SAFETY TIPS: Make a commitment not to be a victim. Follow up on
More informationAS Australian Standard. Guards and patrols. This is a free 6 page sample. Access the full version online.
AS 4421 1996 Australian Standard Guards and patrols This Australian Standard was prepared by Committee EL/31, Intruder Alarm Equipment and Installations. It was approved on behalf of the Council of Standards
More informationA Study into the Standardization of Using Fire Detectors in Rail Vehicles for China
Available online at www.sciencedirect.com Procedia Engineering 52 ( 2013 ) 240 244 A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China LIU Xiao-lu *, WANG Wen-qing Shenyang
More informationPLUMBING & CARBON MONOXIDE
2 PLUMBING & CARBON MONOXIDE - by John Williams, Jr. Plumbing Control Supervisor Onondaga County Water Environment Protection WHY PLUMBING & CARBON MONOXIDE POISONING? 3 CARBON MONOXIDE IS AN ODORLESS,
More informationREGULAR MEETING OF THE THIRD LAGUNA HILLS MUTUAL LANDSCAPE COMMITTEE
OPEN MEETING REGULAR MEETING OF THE THIRD LAGUNA HILLS MUTUAL LANDSCAPE COMMITTEE Thursday, January 4, 218 9: a.m. Laguna Woods Village Community Center Board Room 24351 El Toro Road AGENDA 1. 2. 3. 4.
More informationFIRE SAFETY AND PREVENTION POLICY
Effective Date: July 26, 2011 Supersedes /Amends: VRS-49/April 2006 Originating Office: Office of the Vice-President, Services Policy Number: VPS-49 PREAMBLE Concordia University (the University ) has
More informationCanadian Fire Alarm Association. Fire Alarm System Activation. Fire Alarm with malfunction history
Canadian Fire Alarm Association Discussion topics False alarms Shut off notices Owner s responsibilities Documents required by AHJ Fire Alarm System Activation Fire detection (early warning at insipient
More informationSecurity System. User Guide for the LED Command Center
Security System User Guide for the LED Command Center National Security Systems Inc (800)457-1999 MY SECURITY COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY
More informationMAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS
FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are
More informationLandscaping Securities August 28, 2014
Landscaping Securities August 28, 2014 The Office of the City Auditor conducted this project in accordance with the International Standards for the Professional Practice of Internal Auditing Office of
More information