DOOR MONITORING/DURESS SYSTEM

Size: px
Start display at page:

Download "DOOR MONITORING/DURESS SYSTEM"

Transcription

1 SECTION PART 1 - GENERAL 1.1 RELATED SECTIONS A. Comply with the requirements of Section Common Work Results for Communications. 1.2 DEFINITIONS A. Not used. 1.3 DESCRIPTION OF SYSTEM: A. Provide and install a complete and fully functional Intrusion Detection System as shown on the drawings and specified herein. B. Section includes: 1. Door Monitoring/Duress Control Panel 2. Door Contacts 3. Duress Buttons 4. Cable 5. Surge Suppression 1.4 SPECIAL REQUIREMENTS A. Not used. 1.5 FUNCTIONS AND OBJECTIVES A. Provide and install a complete and satisfactorily functioning system providing the following: 1. Interconnection, control, and indication of the various protected spaces and devices included in the system in both the main monitoring location and at remote locations as shown on the drawings and outlined herein. 2. The ability to arm or disarm the system or portions of the system through the use of keypads and other system devices, as shown on the drawings and outlined herein, as necessary to allow protection of the premises and personnel. 3. Monitoring and indication of the status of protected doors throughout the facility. Alarm indication of doors that have been opened during unauthorized times, or doors that have been held open beyond the time programmed into the system for passage. 4. Reporting of system status and alarm signals to a remote location. PART 2 - PRODUCTS 2.1 DOOR MONITORING/DURESS CONTROL PANEL A. The Door Monitoring/Duress Control Panel shall be a multi-tasking hybrid control panel feature rich for security applications. B. Features 1. Control Panel HB #I KOLTER HOSPITALITY

2 a. Eight (8) end-of-line resistor burglary zones programmable for area, exit/entry delay, interior, follower, day zone, chime, fire option, sensor watch, swinger shutdown, zone adding and a variety of other features b. Up to ninety-six (96) zones with optional zone-expansion modules and 4-zone keypads. c. Up to ninety-six (96) individually coded users, each with a programmable authority level. d. Exclusive RS232 panel-port for network integration for 9600 baud comprehensive communications. e. Three (3) on-board relay outputs, expandable to ninety-six (96). f. Three keypad panics: fire, police, and auxiliary. g. Up to eight (8) independent area partitions. h. Up to eight (8) separate access stations by up to 96 users. i. Up to sixty-four (64) separately addressable X-10 devices with GEM-X10 kit. j. English language prompts & system status messages from choice of keypad models. k. User-customized zone descriptions, reprogrammable as required. l. Reports alarms, restores, and troubles by zone. m. 255 event schedule n. 800 event log. o. Overview mode permitting monitoring and control of total system from one keypad. p. Support for up to four (4) RF receivers. q. Guard-tour programmable for start time, tour length, and check points. r. Two (2) programmable entry delay times. s. Two Interior bypass groups. t. Dynamic battery test interrupts charging and places batter under load every four hours. u. Chime by zone; programmable duration. v. Non-volatile RAM to retain memory during power losses. w. Auto-download log. 2. Communicator a. Compatible with all major receiver formats including BFSK, 4/2, modem 2, SIA, 4/3/1, $ + 2 express and point ID b. Rotary dial and touchtone with rotary backup c. Three (3) 20-digit telephone numbers d. Backup reporting; double reporting; split reporting e. Ninety-six (96) user codes with opening/closing reporting by user. f. AC failure reporting with programmable report delay g. Supervised telephone line cut with programmable delay HB #I KOLTER HOSPITALITY

3 h. Pager capability i. SIA CP01 compliant 3. Specifications a. Loop current: 2.5 ma with 2.2 ohm end-of-line resistor b. Loop resistance: 300W max c. Relay outputs (burglary; reset; aux: wet, 12 VDC, 1.2A max; Dry, SPDT contacts 24 VDC regulated. d. Remote power output: 12 VDC regulated. e. 750 ma of combined standby current f. Standby Time: 4 hours minimum. 4. System shall be provided with keypads in quantities as shown on the drawings. 5. Interface the Intrusion Detection Panel with the Access Control System in accordance with the manufacturer s recommendations for a complete and seamless integration. All Intrusion Detection signals and alarms shall appear on the Access Control system Alarm Workstation. C. Manufacturers 1. Basis of Design a. NAPCO Gemini P9600 Intrusion Detection Panel with Keypads or acceptable 2.2 DOOR CONTACTS A. Door contacts shall be balanced magnetic type contacts specifically designed for the location where installed. B. Standard pedestrian style doors shall be provided with contacts that are flush mounted, design for ¾ or 1 diameter holes, and manufactured of a molded, flame-retardant ABS plastic. The Color of the door contact shall match the door frame where installed. Metallic doors shall be provided with Rare Earth magnets. The magnet portion of the door contact shall be held in place with permanent adhesive that will not crack, dry out, or release the magnet over time. C. Door contacts for overhead doors shall be surface mounted and shall be traffic rated to withstand long-term abuse from trucks, forklifts, and other vehicles. D. Door contacts for curtain style doors shall be designed to protect the door contact from damage. E. Manufacturers 1. Basis of Design a. GE Security 2. Acceptable Substitutions a. Honeywell b. Bosch HB #I KOLTER HOSPITALITY

4 2.3 DURESS BUTTONS A. General 1. Shall be a commercial grade panic or hold-up device designed for silent operation. B. Functions and Features 1. Double-pole Double-throw contacts 2. Twin 45 degree screw terminals with EOL resistor slicing terminal 3. Adhesive pads for temporary positioning while installing 4. Stainless Steel cover 5. Fully supervised 6. Reset key for testing and/or reset of alarm. C. Manufacturers 1. Basis of Design a. Honeywell 270R Hold-Up Device or acceptable 2.4 CABLE: A. General 1. Provide multi-conductor insulated copper conductors with overall jacket as required by the intrusion detection system manufacturer to provide a complete, fully operational, UL Listed Intrusion Detection System. 2. Cables shall be plenum rated where installed in plenum spaces. 3. Cables shall not be installed below slab or in wet locations. 4. The Contractor shall field verify routing of cables prior to submitting Product Data or Shop Drawings under the submittal process. B. Device Requirements 1. Key Pads a. Homerun from each key pad to closest MDF or IDF room as shown on the drawings. b. One (1) Category 6 cable for data and one (1) 16 AWG, 2 conductor, unshielded, twisted, jacketed cable for power. Provide ten (10) feet of slack at both ends of both cables. c. Manufacturers 1) Basis of Design a) Category 6 Cable: Refer to Section [ ][16710] b) 16/2 Power Cable: Belden 5200UE (nonplenum) or acceptable c) 16/2 Power Cable: Belden 6200UE (plenum) or acceptable 2. Door Contacts HB #I KOLTER HOSPITALITY

5 a. Homerun from each contact (on single doors) or pair of switches (on double doors) to closest MDF or IDF room as shown on the drawings. b. Shall be a 22 AWG, 2 conductor, unshielded, jacketed cable with ten (10) feet of slack at both ends c. Manufacturers 1) Basis of Design a) Belden 5500UE (non-plenum) or acceptable b) Belden 6500UE (plenum) or acceptable 3. Duress Buttons and Motion Detectors a. Homerun from each Motion Detector to closest MDF or IDF room as shown on the drawings. b. Shall be a 22 AWG, 4 conductor, unshielded, twisted, jacketed cable with ten (10) feet of slack at both ends. c. Manufacturers 1) Basis of Design a) Belden 5502UE (non-plenum) or acceptable b) Belden 6502UE (plenum) or acceptable 2.5 SURGE SUPPRESSION: A. For Power Circuits (120 volt): 1. UL 1449 listed amp, 120V rated. 3. Suppressors shall be tested per IEEE, C for Categories A and B. 4. Normal mode (L-N), and common mode (L+N-G) protection. 5. Internal fusing. 6. Hybrid design. 7. Indicators for normal operation and failure indication. 8. Enclosure: a. Fire retardant high impact, phenolic or plastic housing or metal enclosure. 9. Clamping voltage UL 1449, Line to Neutral, Category B Impulse At (3KA, 8 x 20 s): 120V. 10. Maximum Surge Capacity: 20,000 amps. 11. Maximum Continuous Operating Voltage: 115% of line voltage. 12. Provide hardwire connection or add 15 amp receptacle device to hardwired devices to match equipment being protected and maintain UL listing. 13. Provide additional 15 amp in-line fusing as required to comply with UL and the NEC when connected to a 20 amp, 120V circuit. HB #I KOLTER HOSPITALITY

6 14. Manufacturers a. Basis of Design 1) Leviton #51020-WM (hardwired) b. Acceptable Substitution 1) EDCO #HSP-121BL2 PART 3 - EXECUTION 3.1 GENERAL A. Comply with the requirements of Section B. Comply with the requirements of Section C. Circuit routing for the system is not necessarily shown on the project drawings. The Contractor shall be responsible for the installation of the raceways, wiring and cabling necessary for a complete and fully functional system. D. The contractor shall provide and install the intrusion detection system (including raceways, pull and back boxes, and cable/wire) in accordance with the intrusion detection system manufacturer s requirements. E. Installation of device back boxes shall be in accordance with the system manufacturer s requirements. F. Termination of devices shall be in accordance with manufacturer s requirements. 3.2 TESTING A. Comply with the requirements of Section END OF SECTION HB #I KOLTER HOSPITALITY

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

EVO192 v3.0 Fire and Burglary What s New

EVO192 v3.0 Fire and Burglary What s New EVO192 v3.0 Fire and Burglary What s New Compatibility: EVO192 v3.0 TM50 v1.31 K641 v2.41 Overview: CP-01 Compliancy Wiring Diagram The following sections/options have been added to the EVO192 panel. They

More information

DS7400Xi Addressable Control/ Communicator

DS7400Xi Addressable Control/ Communicator DS7400Xi Addressable Control/ Communicator DS7400Xi DS7400Xi-EXP 110VAC operation 220VAC operation Remotely Programmable WDSRP (Windows Detection Systems Remote Programming Software), allows the systems

More information

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 XL-2G Gold Product Overview 7 Zones (6 programmable + panic or keyswitch zone) Fast Loop Response

More information

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing

More information

Control/Communicator

Control/Communicator Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. TABLE OF CONTENTS... P.1 2. GENERAL DESCRIPTION... P.2... 3. STANDARD AND OPTIONAL PARTS LIST... P.2... 4. FEATURE

More information

RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION...2 STANDARD AND OPTIONAL PARTS LIST...2 FEATURE DEFINITIONS...3 TERMINAL DRAWING AND SPECIAL NOTES...4

More information

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.

More information

KT-100 Door Controller

KT-100 Door Controller WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 16725 INTRUSION DETECTION SYSTEM SECURITY SYSTEM FOR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The General Provisions of the Contract, including the General Conditions, Supplementary Conditions

More information

TABLE OF CONTENTS. General Description Standard and Optional Parts List Feature Definitions Comments about the 8600E...

TABLE OF CONTENTS. General Description Standard and Optional Parts List Feature Definitions Comments about the 8600E... 5$1*(5( DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS General Description... 2 Standard and Optional Parts List... 2 Feature Definitions... 3 Comments about the 8600E... 4 Terminal

More information

Series. NX-4-EUR Control Panel. Installation manual

Series. NX-4-EUR Control Panel. Installation manual g GE Security NetworX TM Series NX-4-EUR Control Panel Installation manual CONTENTS CONTENTS...2 GENERAL INFORMATION...4 ORDERING INFORMATION...4 FEATURE DEFINITIONS...5 PROGRAMMING THE NX-4 KEYPADS...12

More information

CC408. Quick Reference Guide Solution 880

CC408. Quick Reference Guide Solution 880 CC408 EN Quick Reference Guide Solution 880 CC408 Quick Reference Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems Pty Ltd ( Bosch

More information

OJD ITB No Attachment E Duress Alarm Equipment Specifications

OJD ITB No Attachment E Duress Alarm Equipment Specifications Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-12 Control/Communicator Installation Manual General Description...2 Ordering Information...2 Option Definitions...3 Programming the LED Code Pads...5 Programming the NX-12...9 Types of Programming

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

Property of Monitronics Inc

Property of Monitronics Inc Enter Program Program Location 1. Hold 8 key for 3 seconds, keypad will beep 2. Enter 4 5 6 7 8 9, display should show dash on display 1. Press [B/A] key display will show 3 dashs 2. Enter 3-digit location

More information

DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION...P.2 2. STANDARD AND OPTIONAL PARTS LIST...P.2 3. FEATURE DEFINITIONS...P.3 4. TERMINAL DRAWING AND

More information

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing Control Panels Control Panels for Commercial Applications Control panels provide the central processing and logic for an integrated system. In a typical system, there are four major functions: inputs,

More information

CC488. Quick Reference Guide Solution Ultima 880

CC488. Quick Reference Guide Solution Ultima 880 CC488 EN Quick Reference Guide Solution Ultima 880 CC488 Quick Reference Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems Pty

More information

P Zone Expandable Hybrid Security System

P Zone Expandable Hybrid Security System Page 1 of 11 up to 8 hardwired keypads and 4 wireless keypads 4 hardwired keypads available with zone input PWLS910 wireless handheld keypad added wireless control is provided by - PWLS908 wireless panic

More information

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 2 2. STANDARD AND OPTIONAL PARTS LIST... 2 3. FEATURE DEFINITIONS... 3 4. TERMINAL DRAWING AND SPECIAL

More information

DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION...P.2 2. STANDARD AND OPTIONAL PARTS LIST...P.2 3. FEATURE DEFINITIONS...P.3 4. TERMINAL DRAWING AND

More information

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup NetworX Series NX-8 Commercial Fire Panel Installation and Startup 2004 GE Security All rights reserved. Printed in the United States of America. These instructions do not purport to cover all details

More information

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide Digiplex System V2.14 / V2.2ACC Control Panel Programming Guide Table of Contents Getting Started...2 What Do I Do First?...2 How Do I Program the Control Panel?...2 Single Digit Entry Method...2 Multiple

More information

RE6100 Series Helix Security and Automation Platform

RE6100 Series Helix Security and Automation Platform CONFIGURATION Resolution Compatibles RE6100 Series Helix Security and Automation Platform C G UI D E Configuration Settings Table 1 - Panel Settings Table 2 - Zone Settings Table 3 - Device Settings Table

More information

NetworX Series NX-6 CONTROL PANEL. Installation and Startup

NetworX Series NX-6 CONTROL PANEL. Installation and Startup NetworX Series NX-6 CONTROL PANEL Installation and Startup 25 GE Security All rights reserved. These instructions do not purport to cover all details or variations in equipment nor to provide every possible

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. ( 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2) Connect

More information

2000 Series. Program Entry Guide. Control Panels

2000 Series. Program Entry Guide. Control Panels 2000 Series EN Program Entry Guide Control Panels 2000 Series Program Entry Guide About This Manual EN 2 About This Manual This guide describes the programming parameters available to the 2000 Series Control

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

Installation Instructions

Installation Instructions g 466-2339A October 2009 2009 GE Security, Inc. Introduction This is the GE. Installations should only be done by trained professionals. Use this document to install the system with default settings that

More information

INSTALLATION MANUAL & PROGRAM RECORD SHEET

INSTALLATION MANUAL & PROGRAM RECORD SHEET INSTALLATION MANUAL & PROGRAM RECORD SHEET TABLE OF DESCRIPTION CONTENTS PAGE WIRING MANUAL 2-6 MENU CHART 7 INSTALLER FUNCTIONS 8 MENU 1 SYSTEM TIMES 9 MENU 2 ZONE CONFIGURATION 10-14 MENU 3 SYSTEM OPTIONS

More information

GEM-P800 Programming Instructions

GEM-P800 Programming Instructions NOTE After 15 minutes of keypad inactivity the keypad will emit a steady tone indicating the panel has been left in Dealer Program Mode Enter Dealer Code to exit or press the key to return to Dealer Program

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING 48ESEP-01 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160 All-In-One Wireless Security System V3.2 Programming Guide Model # MG6130 / MG6160 We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com

More information

GEM-P800. Control Panel/Communicator. Installation Instructions

GEM-P800. Control Panel/Communicator. Installation Instructions GEM-P800 Control Panel/Communicator Installation Instructions NAPCO 2002 WI850C 9/02 WI850C GEM-P800 Installation Instructions Table of Contents General Information GEM-P800 Features General Information...

More information

Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts

Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS Feature Charts Control Panels FEATURE CHART LYNX Plus (L3000) (Supported Feature) (Not Supported) N/A (Not Applicable) LYNX Touch (L5210)

More information

Contact ID as of 2/2/2015

Contact ID as of 2/2/2015 Contact ID as of 2/2/2015 100 Medical Zone A non-specific medical exists 101 Personal Emergency Zone Emergency Assistance request 102 Fail to report in Zone A user has failed to activate a monitoring device

More information

The revolutionary code-free system as easy as

The revolutionary code-free system as easy as NAPCO introduces a new revolution in home security By NAPCO Complete, standard Freedom F-8KIT1, shown Code-free F-8 security system with 8-zone hybrid control The revolutionary code-free system as easy

More information

VISTA-100 Commercial Fire & Burglary Partitioned System

VISTA-100 Commercial Fire & Burglary Partitioned System VISTA-100 Commercial Fire & Burglary Partitioned System 4XLFN6WDUW Step-by Step Programming Procedure Single and Multiple Programming Forms System Worksheets FIRE FIRE * PULL VISTA-100PR Rev B 4/99 TABLE

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM SECURITY ACCESS AND SURVEILLANCE SECTION 13850 VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM ADEMCO Group 165 Eileen Way Syosset, New York 11791 1-800-645-7568 SECTION 13850 DETECTION

More information

GEM-P801 Control Panel/Communicator For use with the GEM-RP8 or the GEM-K800 Keypads. Installation Instructions

GEM-P801 Control Panel/Communicator For use with the GEM-RP8 or the GEM-K800 Keypads. Installation Instructions 333 Bayview Avenue Amityville, New York 11701 For Sales and Repairs, (800) 645-9445 For Technical Service, (800) 645-9440 Publicly traded on NASDAQ Symbol: NSSC GEM-P801 Control Panel/Communicator For

More information

System Introduction. 1.1 Specifications S E C T I O N 1

System Introduction. 1.1 Specifications S E C T I O N 1 System Introduction S E C T I O N 1 1.1 Specifications Control Panel Specifications Flexible Zone Configuration: 8 Fully Programmable Zones 37 Access Codes: 32 User, 1 System Master, 2 Partition Master

More information

Contact ID as of 11/28/2018

Contact ID as of 11/28/2018 Contact ID as of 11/28/2018 100 Medical Zone A non-specific medical exists 101 Personal Emergency Zone Emergency Assistance request 102 Fail to report in Zone A user has failed to activate a monitoring

More information

D6500 reports are shown in typewriter style letters. For example, AC FAILED indicates the report sent when the panel reports an AC power failure.

D6500 reports are shown in typewriter style letters. For example, AC FAILED indicates the report sent when the panel reports an AC power failure. Notice The material and instructions covered in this manual have been carefully checked for accuracy and are presumed to be reliable. However, Radionics, Inc. assumes no responsibility for inaccuracies

More information

System Programming Guide

System Programming Guide & System Programming Guide Software Versions 4.4 (728ULT) and 4.1 (738ULT) Installer Code (Default - 728 Ultra: 282828; 738 Ultra: 383838) Full access to programming, except user access codes (PINs). No

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSI 3.10 CTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT SPEC SHEET Simple Expansion Solutions Expand your DMP panel options with a wide array of expansion modules. Add supervised Class B burglary zones. Connect non-powered burglary or fire type devices for

More information

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0 User s Guide SUB-MA7240O-0001.OG.Solution40-111.doc Created: 6/05/03 Last Updated: 23/09/03 MA7240AO-0001 Version 1.0 2 Table Of Contents User List...6 Quick Reference..7 Features...7 Keypad User's Guide...8

More information

NX-4V2 Control Panel Installation Instructions

NX-4V2 Control Panel Installation Instructions 4V2 Control Panel Installation Instructions Introduction This is the 4V2-Control Panel Installation Instructions. Installations should only be done by trained professionals. Use this document to install

More information

ITI Caretaker Basic Commands

ITI Caretaker Basic Commands ITI Caretaker Basic Commands System can be accessed by telephone or wireless keypad Zones - Up to 30 Wireless or 24 Hardwired Battery - 12 volt 1.9 amp rechargeable Lead-Acid inside main panel, only found

More information

First Alert 1200C Installer Notes M. Leuck

First Alert 1200C Installer Notes M. Leuck First Alert 2C Installer Notes M. Leuck. Programming can done by standard keypads 2. Enter programming with Installer Code + 8 + + 3. Another method of entering programming: Power system down, then back

More information

System Introduction. Digital Communicator Specifications: Supports all Major Formats including SIA and Contact ID Event Initiated Personal Paging

System Introduction. Digital Communicator Specifications: Supports all Major Formats including SIA and Contact ID Event Initiated Personal Paging 1.1 Specifications System Introduction S E C T I O N 1 Control Panel Specifications Flexible Zone Configuration: 8 Fully Programmable Zones 38 Access Codes: 32 User, 1 System Master, 2 Partition Master,

More information

All-In-One Wireless Security System V1.0. Model #: MG Reference and Installation Manual

All-In-One Wireless Security System V1.0. Model #: MG Reference and Installation Manual All-In-One Wireless Security System V1.0 Model #: MG-6060 Reference and Installation Manual Table of Contents Introduction... 3 About Magellan and this Manual... 3 Conventions... 3 Specifications... 3

More information

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA-128FB ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA-128FB ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM SECURITY ACCESS AND SURVEILLANCE SECTION 13850 VISTA-128FB ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM ADEMCO Group 165 Eileen Way Syosset, New York 11791 1-800-645-7568 SECTION 13850 DETECTION

More information

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250FBP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250FBP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM SECURITY ACCESS AND SURVEILLANCE SECTION 13850 VISTA 250FBP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM ADEMCO Group 165 Eileen Way Syosset, New York 11791 1-800-645-7568 SECTION 13850 DETECTION

More information

System Introduction. 1.1 PC5015 Specifications S E C T I O N 1

System Introduction. 1.1 PC5015 Specifications S E C T I O N 1 1.1 PC5015 Specifications System Introduction S E C T I O N 1 Flexible Zone Configuration: 8 Fully Programmable Zones 38 Access Codes: 32 User, 1 System Master, 2 Partition Master, 2 Duress and 1 maintenance

More information

SP-1000X. Panic Device Power Controller Installation Guide. Rev

SP-1000X. Panic Device Power Controller Installation Guide. Rev TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current

More information

Installation Manual Premier 412/816/832. Issue 10

Installation Manual Premier 412/816/832. Issue 10 Installation Manual Premier // Issue 0 Premier // Installation Manual 5. Operating the System Introduction Before attempting to operate the alarm system ensure you have familiarised yourself with all the

More information

L900 series USER MANUAL

L900 series USER MANUAL INTRODUCTION The BLUGUARD Control Panel is designed for simple operation yet provides the maximum protection for you. Please read this manual carefully and follow the instructions contained in this book.

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

System Manual W A R N I N G. PC6O1O Software Version 2.1

System Manual W A R N I N G. PC6O1O Software Version 2.1 System Manual W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual

More information

First page of this international document resides under separate cover: 20SEaCOV.ps

First page of this international document resides under separate cover: 20SEaCOV.ps First page of this international document resides under separate cover: 20SEaCOV.ps TABLE OF CONTENTS Section 1. GENERAL DESCRIPTION... 6 Section 2. INSTALLING THE CONTROL... 9 Mounting the Cabinet...

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

INSTALLATION MANUAL PC15OO

INSTALLATION MANUAL PC15OO INSTALLATION MANUAL PC15OO This device complies with Parts 15 and 68 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2)

More information

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad

More information

TABLE OF CONTENTS TABLE OF CONTENTS 1

TABLE OF CONTENTS TABLE OF CONTENTS 1 TABLE OF CONTENTS TABLE OF CONTENTS 1 FEATURES 2 Keypad Programmable... 2 EEPROM Memory... 2 Static/Lightning Protection... 2 Supervision... 2 Operation... 2 SPECIFICATIONS 2 PC1550 Control Panel... 2

More information

Solution-8248 Installation Manual ISSUE 1.16

Solution-8248 Installation Manual ISSUE 1.16 Solution-8248 Installation Manual ISSUE 1.16 MA880I Solution- 8248 This page has been included for you to cut out and insert into the spine of the folder Installation Manual ISSUE 1.16 www.dsworld.com

More information

VISTA-128BP/VISTA-250BP/ VISTA-128SIA Enhanced Commercial Burglary Partitioned Security System With Scheduling User Guide K5895V5 4/09 Rev C

VISTA-128BP/VISTA-250BP/ VISTA-128SIA Enhanced Commercial Burglary Partitioned Security System With Scheduling User Guide K5895V5 4/09 Rev C VISTA-128BP/VISTA-250BP/ VISTA-128SIA Enhanced Commercial Burglary Partitioned Security System With Scheduling User Guide K5895V5 4/09 Rev C Your Honeywell security system is designed for use with devices

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

SENTROL ZX200/ZX210. Security System Control. Installation/ Programming

SENTROL ZX200/ZX210. Security System Control. Installation/ Programming SENTROL ZX200/ZX210 Security System Control Installation/ Programming 1 2 TABLE OF CONTENTS Table of Contents Feature Overview... 5 A New Standard For Value...5 ZX System Advantages...5 More Than A Security

More information

/10 Rev A

/10 Rev A VISTA-128BPT/ VISTA-250BPT/ VISTA-128BPTSIA Commercial Burglary Partitioned Security System With Scheduling User Guide 800-06905 6/10 Rev A Your Honeywell security system is designed for use with devices

More information

VISTA-128FBP/ V128FBP-24 Commercial Fire and Partitioned Burglary Alarm Control Panel

VISTA-128FBP/ V128FBP-24 Commercial Fire and Partitioned Burglary Alarm Control Panel VISTA-128FBP/ V128FBP-24 Commercial Fire and Partitioned Burglary Alarm Control Panel Designed to integrate seamlessly with, access control, and ADEMCO s full range of fire and burglary components, the

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

Concord 4 Series Security Systems

Concord 4 Series Security Systems g GE Security 466-2182 Rev. A March 2005 www.gesecurity.com Part Numbers: 600-1021-95R 600-1022-95R 600-1040 Concord 4 Series Security Systems Installation Instructions Notices FCC Part 15 Information

More information

VISTA-128BPT/ VISTA-250BPT/ VISTA-128BPTSIA

VISTA-128BPT/ VISTA-250BPT/ VISTA-128BPTSIA VISTA-128BPT/ VISTA-250BPT/ VISTA-128BPTSIA Commercial Burglary Partitioned Security System With Scheduling User Guide 800-06905 6/10 Rev. E IMPORTANT! RECOMMENDATIONS FOR PROPER INTRUSION PROTECTION For

More information

Intelligent technology made simple

Intelligent technology made simple Intelligent technology made simple Freedom F-64: 8 to 64-zone hybrid security system featuring multifunction talking custom alpha touchpad with intelligent exit/entry technology for up to 8 doors of code-free,

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.

More information

Installation Instructions

Installation Instructions Model S5832SG Control Panel 8 to 32 Zones Installation Instructions Table of Contents Table of Contents Compliance and Regulatory Information...i Installing and Connecting the Control Panel... 1-5 Sierra

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

Installation Instructions

Installation Instructions NX-148E-RF LCD Touchpad with Receiver 466-2198C February 2006 Copyright 2006, GE Security Inc. Contents Product summary 1 Installation 1 Transmitter programming 2 Touchpad programming 5 Reference tables

More information

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68) F A 1 7 0 0 c Testing the System Battery Test When AC power is present, the FA1700C runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery

More information

Alarm Control Panel WIC-16Z4P WIC-5Z2P. Installation & Operation User Manual

Alarm Control Panel WIC-16Z4P WIC-5Z2P. Installation & Operation User Manual WIC-16Z4P WIC-5Z2P Installation & Operation User Manual Page : 1/34 INDEX # Function Page 1 Abort Current Communication and Clear Reporting Queue (*59) 13 2 Abort Current Communications (*59) 10 3 Account

More information

RMS/RPX Reader. User Manual

RMS/RPX Reader. User Manual RMS/RPX Reader User Manual Copyright Disclaimer Trademarks and patents Intended use FCC compliance Copyright 2005, GE Security Inc. All rights reserved. This document may not be copied or otherwise reproduced,

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp

More information

The system should also be capable of recording events automatically on any compatible DVR and should be able to retrieve recordings based on events.

The system should also be capable of recording events automatically on any compatible DVR and should be able to retrieve recordings based on events. 0BThe System The Security Management System should be capable of Controlling and Monitoring Access through the doors, Monitor and control Inputs and Outputs, include an Integrated Video Badging, Integrate

More information

MAXSYS Zone Control Panel PC4020. Maxsys Commercial Fire Panel PC4020CF. MAXSYS 16 Output Module PC4216

MAXSYS Zone Control Panel PC4020. Maxsys Commercial Fire Panel PC4020CF. MAXSYS 16 Output Module PC4216 16-128 Zone Control Panel PC4020 16 zones on main control panel supports up to 16 hardwired keypads Expandable up to 128 zones using hardwire, wireless modules and addressable zones COMBUS hardwired expansion

More information

ALARM... CONTROL... PANELS... AND... KEYPADS...- WIRED...

ALARM... CONTROL... PANELS... AND... KEYPADS...- WIRED... ALARM... CONTROL..... PANELS... AND... KEYPADS....- WIRED........ Securi-Prod 4 Zone Perimeter Alarm 4 x EOL zone alarm panel 2K2 Zone EOL resistance value Multiple Arm/Disarm functions Built in receiver

More information

NetworX Series NX-4V2 Control Panel Installation and Startup

NetworX Series NX-4V2 Control Panel Installation and Startup NetworX Series NX-4V2 Control Panel Installation and Startup 2005 GE Security All rights reserved. These instructions do not purport to cover all details or variations in equipment nor to provide every

More information

OPERATING GUIDE for your GEM-RP1CAe2 KEYPAD

OPERATING GUIDE for your GEM-RP1CAe2 KEYPAD OPERATING GUIDE for your GEM-RP1CAe2 KEYPAD GEMINI SYSTEM READY 09/01/05 12:09 AM ARMED STATUS A 1 2 3 B 4 5 6 J C 7 8 9 0 NEXT / YES E PRIOR / NO F AREA G COMPUTERIZED SECURITY SYSTEM Simplified instructions

More information

PROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX

PROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX PROGRAMMING GUIDE SPECTRA CONTROL PANELS V1.2 1725, 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX TABLE OF CONTENTS HOW DO I PROGRAM THE SYSTEM?... 4 Single Digit Data Entry Method (Hexadecimal

More information

USER'S GUIDE FA1220CV. 2-Partition Security System N7003-1V2 7/98

USER'S GUIDE FA1220CV. 2-Partition Security System N7003-1V2 7/98 USER'S GUIDE FA1220CV 2-Partition Security System N7003-1V2 7/98 SYSTEM OVERVIEW... 3 General... 3 A Partitioned System... 3 Zones... 3 Burglary Protection... 4 Fire Protection... 4 Alarms... 5 Emergency

More information

0 4 / 0 4 / 1 4. GE Concord 4 Quick User Guide. GE Concord 4 Quick User Guide Page 1

0 4 / 0 4 / 1 4. GE Concord 4 Quick User Guide. GE Concord 4 Quick User Guide Page 1 0 4 / 0 4 / 1 4 GE Concord 4 Quick User Guide GE Concord 4 Quick User Guide Page 1 Before Calling Is the keypad beeping? Press *. This will silence the beeping and let you know where the trouble is. Is

More information

Flair 500 Series Annunciators

Flair 500 Series Annunciators Flair 500 Series s Basics Flair Multi-Zone s (MZAs) are fully functional, flexible, programmable micro controller based alarm control panels. They can be used independently d or in conjunction with other

More information