Project Number QMSN Install Basewide EMCS System Moffett Federal Airfield, California

Size: px
Start display at page:

Download "Project Number QMSN Install Basewide EMCS System Moffett Federal Airfield, California"

Transcription

1 1. Energy Management and Control System 1.1. Project Objective Project Number QMSN Install Basewide EMCS System Moffett Federal Airfield, California The objective of this project is to provide a complete and fully capable, OPC-compliant Automated Logic Corporation (ALC) brand Energy Management Control System (EMCS) across nine of the California Air National Guard s (ANG) facilities (listed below) located in and around the ANG Cantonment Area at Moffett Federal Airfield (Moffett Field), Santa Clara County, California. The facilities to be included under this Statement of Work (SOW) are Buildings 683, 680, 681, 650, 653, 654, 656, 662 and 663. The project will conclude with the most current version of ALC hardware and software being installed in each of the buildings in this statement of work and all communicating via the base s existing fiber optic backbone; the server shall be located in the ANG s Base Network Control Center (BNCC) located in building 680 and the master controller to be located in building 683 (Controller). The completed project shall see the EMCS monitoring and controlling all existing HVAC equipment through the use of existing sensors connected to existing building-by-building DDC systems plus new supply air and smoke detectors that shall be installed by the Contractor in all building zones. Programming shall provide for a sequence of operations that allows the ANG to operate the mechanical and electrical systems of each building and to maintain building temperatures in the most energy efficient manner possible with the existing equipment in the facility. The Contractor shall provide 3-D graphics that show the operating status of the mechanical and electrical components in the building to assist ANG personnel with the troubleshooting of equipment issues. All work performed under this SOW should be accomplished in a manner that compliments the Direct Digital Control (DDC) installation (sequence of operations, programming, etc.) that is or will be installed in the new operations and training facility(building 663) to the greatest extent permissible with the existing equipment installed in these facilities. The environmental management systems in building 663 and building 653 (not included under this SOW) shall be connected to the EMCS and shall report to the Controller. Additionally, these systems shall be configured to allow them to be controlled and adjusted by the Controller. The Controller shall include graphics for these two facilities which should be similar to those provided for the other facilities. Each of the remaining buildings included under this SOW shall have an ALC building controller (Subordinates) installedat a location to be identified by the 129th Civil EngineeringFlight. The Subordinates shall be able to control that building s systems and have

2 the capacity for two way communications with the Controller. Computer and software requirements for the Subordinates will be the same as that of the Controller. The Contractor shall also connect all electric, gas, and water meters to be tied into the EMCS with the EMCS saving at least ninety (90) days worth of consumption data for each of the utilities before being over-written. The EMCS shall provide the capability for graphically representing this data via charts and graphs. The Contractor shall be required to provide the system network certifications, all background paperwork, the system architecture and any other documentation to the 129th Communications Flight (CF) in sufficient time and in order to get the system operating on the communications cabling on the base. Individual addresses and connectivity at each facility will require coordination with the CF. The contractor shall investigate any rebates potential, fill out any required paperwork and provide any calculations then submit to the Government representative for signature and submission. The contractor is encouraged to propose their most cost effective solution to meet the requirements of this Statement of Work Scope A. Design, furnish, install, and test a complete and operational EMCS. Provide complete engineering, programming, design, installation, setup and commissioning services for development and installation of a basewide EMCS DDC on and around the ANG Cantonment Area of Moffett Field. Work includes investigative services requiring a survey and analysis of existing HVAC equipment systems and facilities. Work also includes removal and proper disposal of existing DDC equipment that cannot be reused in this contract which includes all the hardware and software from the building controllers of non-alc systems. B. Services shall include the development of specific sequences of operational control for each Subordinate system. Contractor shall develop plans that include sequences of operations, elementary ladder control diagrams, and details, schematics, and controls plans for each Subordinate system. Services shall include development of detailed lists of analog and digital input/output (AI/AO and/or DI/DO) points for each connected system or facility. C. Submittals for controls shall conform to the requirements of part 2, EMCS System Commissioning, of this SOW. This includes a required preliminary plan (Preliminary Submittal) to be submitted to the ANG for approval prior to beginning construction. The Preliminary Submittal shall be an executive summary that includes, but is not limited to, an outline plan and description of the EMCS and the local facility control systems, descriptions of the proposed network setup, strategies for connectivity (to include required base infrastructure if necessary), ordered priority of facilities, and definitions of the ALC (protocol, hardware and software to include version). The Preliminary Submittal shall include the Commissioning Agents Coordinator's resume listing applicable experience for review and approval by the ANG s designated representative. The Preliminary Submittal shall also include a complete list of the project managers and subcontractors, to include the test and balancing contractor. At a

3 minimum, one copy of all submittals shall be provided via an electronic, commercially-available format that is suitable for long-term electronic archive. Submittals may be secured to protect the contents from further editing or modification so long as such protections don t preclude the transmission of the document to a Government storage facility or server. As an instrumentality of the United States Government, such protections shall not be construed to abridge the Government and/or ANG s rights of ownership or propriety. D. Commissioning services shall be performed by a certified Commissioning Agent and Authority (CAA) IAW the requirements of the SOW. The CAA shall act as the project Commissioning Coordinator. The CAA s qualifications shall be presented to the ANG or the ANG s designated representative prior to commencement of any commissioning work. Services shall provide for the development of scenarios for HVAC system optimization; the improvement of energy conservation, scheduling, or alarm notification; maintenance messaging; demand limiting; equipment duty cycling; load shedding; electrical demand side management; use with backup generators and backup fuel supply. Services may require coordination with local utility companies. E. The system shall establish a central EMCS Controller to be located on a personal desktop computer that will be located in building 683. The ANG shall determine the location. Licensed, electronic copies of all vendor software, to include programming tools, operating software, and extension software, shall be provided to the ANG on portable computer disks. Software shall be loaded and configured on the Controller; the Controller shall be configured for immediate use upon delivery to the ANG. To the greatest extent possible, the Controller and vendor software shall be configured to provide a customized, easily-understood, graphical user interface (GUI) with point and click features. Customized graphical representation of each facility and each controlled system within the facility shall be accurately created and completely depicted. GUI shall display current readings of attached utility meter readings (including both master and sub meters) for electric, gas, water. F. Services shall include any and all necessary verification and investigation of existing and planned HVAC systems in the identified facilities. The required work (EMCS and DDC) at each of the facilities shall be ordered in priority and approved by the 129th Civil Engineering Flight, or the ANG s designated representative Basic Description of the System A. The EMCS and DDC system shall remotely control and monitor base HVAC systems. The systems to be controlled include but are not limited to HVAC Systems, Plumbing Systems, and Utilities Master Meters, Facility level Meters, and Sub Meters B. Design shall incorporate state of the art direct digital control system and shall be manufactured by ALC and must be compatible and integratable with the protocol of the DDC system installed or being installed in building 663. The system must be expandable and upgradable to incorporate additional facilities that may be constructed in the future. Design must employ the base standard system of protocol for interfacing DDC systems to the EMCS using BACNET.

4 C. EMCS system shall interface with and remotely monitor and gather base utility consumption data at master meters and facility sub meters. Utilities to be monitored include gas, water, and electricity. D. Design shall include interface with duct-mounted smoke detectors and separate fire alarm panels for the monitoring and relaying of HVAC shut-down sequence in emergency conditions. E. Design shall include interfacing with existing chillers, boilers, and modular boilers in a staged sequence for efficient partial load matching. F. Design shall include status and start/stop control of electric motor on pumps, fans, air conditioning units, chillers, computer room air conditioners, cooling towers, air handling units, fan coil units, variable speed drives, variable air volume boxes, and other HVAC equipment. G. Design shall include interfacing with separate, existing, proprietary control panels and management systems for infrared heating in the maintenance hangar, backup power panels, generators, and other panels. H. System shall be programmed for night and weekend setbacks as prescribed by the 129th Civil Engineering Flight and shall provide for manual overrides as well as simple reprogramming to allow for schedule changes. I. Design shall provide a single point shut off for all mechanical systems in all buildings from the Controller and one auxiliary to be located in the 129th Security Forces Squadron s Base Defense Operations Center (BDOC) in building 653. J. Software shall include but not be limited to backup program disk, all necessary information to install or update software, all access devices (i.e. keys) necessary to install and/or operate system. K. Provide all necessary programming of each individual facility to properly identify the device and transmit the data indicated in part 1.1., Project Objective. L. Provide master updated copy of control drawings for entire base in binder with dividers and table of contents. Provide equipment datasheets in separate binder with table of contents and binders. M. Controller and Subordinates shall be provided by the Contractor and shall be laptop or desktop computers. N. The Contractor shall provide a rough-in riser system architecture diagram which details point operation of the systems as depicted in the example for each facility: (See Attachment 1). O. The Contractor shall also provide an input/output schedule that delineates various pieces of equipment operations concerning input, output, alarms, and functions etc. for each facility.

5 Attachment 2 is provided as an example of what points should be incorporated; this is merely an example and is not all-inclusive. P. The Contractor shall draw and load color graphics for all new controllers and their controlled HVAC system, to include meters, and load the drawings on to the controllers. Drawings should include the facility floor plan with room numbers, FCUs (numbered), and the temperature at each sensor. The system shall incorporate thermo-coded graphics whereby an area is depicted as too hot (red), at set point (green) or too cold (blue). Q. The Contractor shall replace three pneumatic controls in building 650 with digital controls and connect them to the EMCS system. R. Design shall include a single fiber solution for connectivity between facilities System Performance The communication speed between the controllers, gateways, network interface devices, and operator interface devices shall be sufficient to ensure a fast system response time under any loading condition. This includes when system is collecting trend data for commissioning and for long term monitoring. The contractor shall configure the DDC and/or EMCS and network as necessary to accomplish the performance requirements System Hierarchy Air handling systems serve a collection of Isolation Areas which in turn are a collection of zones. Each Isolation Area can have a different occupancy schedule, allowing the system to serve only a small number of spaces for off-hour energy savings. For small systems and for single zone systems, there may be only one Isolation Area but the basic logic shall be applied GUI Software The GUI software shall provide easy-to-read graphical shortcuts and links between connecting equipment, systems, facilities, and auxiliary or operational features. The GUI shall encompass graphical methods for setup of occupancy, scheduling, trending, alarms, and messaging. The GUI shall depict real time operating conditions and settings. The GUI shall employ color coded building graphics, and color shading to depict operating conditions. Changes in color shall depict deviation from acceptable operating levels; such deviation away of acceptable zone temperatures, or higher demand levels, or active alarms. GUI shall be a laptop in a docking station and include all tools and connectors necessary to completely service the system at the main location or remotely in the buildings. Monitor shall be 30 minimum with resolution of 2560 x 1600, rotatable display, adjustable height and tilt, similar to Dell Ultrasharp U3014. Laptop shall have minimum specifications of 1 TB hard drive, 8 GB memory and windows 7-64 bit operating system. A. Trends. Trending setup for both commissioning and normal operation is required.

6 1. Trending and trend analysis capabilities are considered critical to system performance. The system shall be designed to upload and record large amounts of point data without causing network bottlenecks or affecting proper system operation. 2. Every point, both real and virtual, shall be available for data reading. 3. Trending software shall be capable of recording point values and time on a user specified regular time step and on a change-of-value (COV) basis at the user s option. Sampling intervals shall be as small as one second. Each trended point shall have the ability to be trended at a different sampling interval. 4. Trend data shall be sampled and stored in control panel memory. There shall be no limit to the amount of trend data stored at the Operator Workstation other than hard disk limitations. 5. Trends shall conform to the BACnet Trend Log Object specification. Trends shall both be displayed and user configurable through the GUI. 6. Provide software to archive trend data to CD or other storage media. 7. Viewing trends. a. Trend data shall be displayed graphically by the GUI. This shall be a capability internal to the workstation software and not a capability resulting from download of trend data on a third-party spreadsheet program unless such transfer is automatic and transparent to the operation and the third-party software is included with the workstation software package. Additionally, such third-party software must be commercially available and the data easily transcribed between formats (i.e., comma separated values, plain text, rich format text, etc.). b. The software shall be capable of dynamically graphing the trend logged object data by creating two-axis (x,y) graphs that simultaneously display values relative to time for at least eight objects in different colors, even if objects have been trended at different time intervals. c. Trends shall be able to dynamically update at operator-defined intervals, including on a 1 second interval for loop tuning. B. Data storage and analysis by other software. Data shall be stored in or be exportable to one or more of the following formats for: Text (Comma or tab delimited with text delimiters), MS Excel, MS Access, dbase, and SQL. Stored data shall not have duplicate records, and have an individual or unique time/date stamp for a specific point, and the data shall be fully contained in a single file or table for each point. Data shall not span multiple files or database tables. C. Security Access. At a minimum, the EMCS security protocols shall comply with DIACAP requirements for password length, complexity, and change frequency. Integration of Common Access Cards (CACs) is desirable. See ATO testing procedures for more information.

7 D. Reporting Software/Alarms/Maintenance Messaging. The EMCS shall have the capability to generate energy reports in the form of bar charts, pie charts, and trend lines. ALC Energy Reporting package shall be included and configured into the EMCS under this SOW Sequence of Operation A. General 1. All setpoints, timers, deadbands, PID gains, etc. listed in sequences shall be capable of being adjusted by the operator without having to access programming whether indicated as adjustable in sequences or not. Software (virtual) points shall be used for these setpoints. Fixed scalar numbers shall not be imbedded in programs unless the value will never need to be adjusted. 2. Reset control shall be applied as appropriate and shall include but not be limited to Hot Water temperature/boiler Reset, Chilled Water temperature/chiller Reset, Supply Air temperature Reset, Duct Static Pressure Reset, and Hydronic system pressure Reset. a. Where zone data (i.e., damper or valve position, control loop signal) is used for reset of the AHU/pump system serving the zone, the zone tag (name) and damper/valve position shall be recorded when it is the zone driving the reset. This data shall be available for Reports so that zones that are undersized or otherwise driving the system can be identified for remediation if required. The position of the most open damper/valve is also critical for commissioning the reset sequences. c. Unless otherwise indicated, control loops shall be enabled and disabled based on the status of the system being controlled to prevent wind-up. B. Zones: This section applies to all single zone systems and sub-zones of air handling systems, such as VAV boxes, fan powered boxes, etc. 1. Setpoints a. Each zone shall have separate unoccupied and occupied setpoints, and separate heating and cooling setpoints. b. Where the zone has a local occupant adjustable setpoint adjustment knob/button, the adjustment shall be capable of being limited in software. If a demand limit setpoint adjustment is in place or the door or window switch indicates a door is open, the local setpoint adjustment shall be disabled. c. Demand limits setpoint adjustment. Cooling setpoints shall be increased upon demand limit requests from the associated Isolation Area. i. At Demand Limit Level 1, increase current setpoint by 1 F. ii. At Demand Limit Level 2, increase current setpoint by 2 F.

8 iii. At Demand Limit Level 3, increase current setpoint by 4 F. d. Hangar door switches and facilities with large overhead doors. Large maintenance zones and aircraft hangars shall have indicator switches that when large doors indicate that they are open, the heating setpoint shall be temporarily set to 40 F. e. Occupancy sensors. For zones that have an occupancy switch associated with the zone, when the switch indicates the space is unoccupied during the Occupied mode, the heating setpoint shall be reset to 4 F lower than the active setpoint, and the cooling setpoint shall be reset to 4 F higher than the active setpoint and the ventilation shall be shut off. VAV flow shall go to 0, and fan coil unit shall turn to auto. f. Hierarchy of setpoint adjustments. The following adjustment restrictions shall prevail in order from highest to lowest priority: i. Setpoint overlap restriction ii. Door switches iii. Demand limit iv. Occupancy sensors v. Local setpoint adjustment vi. Scheduled setpoints based on zone mode 2. Local override. Thermostat override buttons shall be sent up for the Isolation Area override control for 60 minutes. 3. Control Loops. Two separate control loops shall operate to maintain space temperature at setpoint, the Cooling Loop and the Heating Loop. Both loops shall be continuously active. The Cooling Loop shall maintain the space temperature at the active cooling setpoint. Mode. 4. Zone Modes shall consist of a Heating Mode, Cooling Mode, and Deadband 5. Alarms a. Inhibit alarms after zone setpoint is changed for a period of 10 minutes per degree of change and while Isolation Area is in Warm-up or Cool-down Modes. b. If the zone is 2 F above cooling or below heating setpoint. c. If the zone is 4 F above cooling or below heating setpoint. d. For zones with CO 2 sensors, if the CO 2 concentration is less than 300 ppm, or the zone is in unoccupied mode for more than 2 hours and zone CO 2 concentration exceeds 600 ppm, generate a level 3 alarm, indicating sensor may be out of calibration.

9 e. For zones with door switches, generate an alarm if the door switch is open and the zone is in unoccupied mode. C. VAV with reheat boxes. 1. Design airflow rates: Zone design maximum cooling and maximum heating airflow setpoints may be initially as scheduled on as built plans; but final airflow CFMs shall be determined by the commissioning Agent or coordinator. Typical minimum levels are as follows: a. Zones with CO 2 controls and occupancy sensors; zone minimum; 0.15 cfm/ft 2 times the room area. b. Zones without CO 2 controls or occupancy sensors; zone minimum; 0.15cfm/ft 2 times the room area or 15 cfm per person, whichever is larger. c. If the zone has a CO 2 sensor, during Occupied Mode, a P-only loop shall maintain CO 2 concentration below 1000 ppm. 2. Alarms required: a. Low airflow b. Low supply air temperature c. Floating damper alarm, generate an alarm indicating a control stability problem and excess damper motor wear. D. Isolation Areas 1. Each system shall be broken into separate Isolation Areas composed of a collection of one or more zones served by the air handling system. 2. Individual Isolation Areas shall be as follows: a. Each floor b. All 24/7 areas, such as computer rooms c. Other areas as required. Make sure they are not so small that fan or cooling stability problems arise. 3. Each Isolation Area shall have separate occupancy schedules and operating modes from other Isolation Areas served by the air handling system. All zones in the Isolation Area shall be in the same operating mode. 4. Each Isolation Area shall be a separate zone with respect to the occupant override system. Occupant interface software shall be programmed to allow occupants to override normal schedule programming to operate the system during off hours for a period set by the occupant, within software time limits adjustable by the operator.

10 modes: 5. Isolation Area Operating Modes: Each Isolation Area shall have the following a. Normal b. Warm-up mode c. Cool-down mode d. Setback mode e. Setup mode f. Unoccupied mode 6. Air Handling Unit System Modes: AHU system modes are the same as the mode of the Isolation Areas served by the system. When Isolation Areas served by an air handling system are in different modes, the following hierarchy applies (highest one sets AHU mode): a. Occupied mode b. Cool-down mode c. Setup mode d. Warm-up mode e. Setback mode f. Unoccupied mode E. VAV Air Handling System 1. Supply fan control a. AH fan start/stop b. Static pressure setpoint reset c. Supply fan speed 2. Minimum outdoor air control a. CO 2 controls under VAV zone controls b. Open minimum outdoor air damper when the supply air fan is proven on and the system is not in warm-up, cool-down, setup, or setback mode. Damper shall be closed otherwise. 3. Supply air temperature control a. Cooling supply air temperature b. Supply air temperature setpoint 4. Economizer lockout. The normal sequencing of the economizer dampers (above) shall be overridden and economizer outdoor air dampers shall be shut whenever the outdoor air temperature is greater than return air temperature. 5. Return fans

11 a. Return fan operates whenever associated supply fan is proven on. b. Return fan speed shall be controlled to maintain return fan suction pressure at setpoint. c. Relief/exhaust dampers: Control of building static pressure to avoid over-pressurizing the building. Control building static pressure in a slightly positive overpressure status by controlling the fresh air intake. d. If there are several air handlers serving a common atmosphere, control all relief fans together to avoid hunting. 6. Alarms a. Maintenance interval alarm for number or run hours, and failed starts. b. Fan alarm. c. Filter pressure drop exceeds alarm limit. d. High supply air temperature off cooling coils. e. If the temperature drops across the cooling coil while cooling valve is closed, an indication of a leaking valve should be noted. f. If mixed air temperature abnormal range indicating economizer damper control problems. g. Low static pressure. F. Boilers and Pumps 1. All boilers and pumps shall be sequenced and staged for efficient partial load matching. Boiler operating hours shall be evened out by switching lead and lag boilers, as determined by cumulated run hours or by cumulated number of starts. 2. Local boiler control panels and local boiler controls and burner management shall be mapped to the EMCS for remote monitoring. The EMCS shall not be allowed to interfere with boiler safety controls. G. Air conditioning systems, Chillers, Condenser water System, and Pumps 1. Generally, chilled water [and large condenser water, cooling tower water] hydronic systems shall vary water flow by employing circulating pumps with variable frequency drives in lieu of three way control valves. 2. On board chiller control panels and panels for other Air Conditioning systems such as water loop heat pump systems, packaged unitary air conditioning systems, and computer room air conditioning systems shall map all critical maintenance and critical operating points and parameters to EMCS for remote monitoring. 3. Special care to map points for interface and control of chillers such that full remote operation and monitoring can be accomplished through the EMCS. The EMCS shall not be allowed to interfere with chiller safety controls.

12 Part 2. EMCS System Commissioning 2.1. Work Included This section applies to all EMCS components/equipment in all facilities/associated systems on this contract. The intent of this section is to deliver a detailed and documented performance functional test and commissioning of all contracted components and systems that clearly verify the entire EMCS system is fully operational in accordance with this contract: 2.1. Including but not limited to the following: A. EMCS and equipment testing and start-up B. Development and validation of control operating sequences C. Validation of proper occupant ventilation airflow rates D. Validation of proper and thorough installation of EMCS and equipment E. Functional testing of control systems F. Demonstration testing of control systems G. Documentation of tests, procedures, and installations H. Coordination of EMCS training I. Documentation of EMCS Operation and Maintenance materials J. Training K. Reference Management Manual for Retro-commissioning 2.2. Sequencing A. The following list outlines the general sequence of events for submittals and commissioning: 1. Submit Preliminary Submittal Package, including Commissioning plans and Qualifications; and receive approval. See part 1, Energy Management and Control System for the Preliminary Submittal Package requirements. 2. Submit Commissioning Submittal Package, 1, for Hardware and Shop Drawings and receive approval. 3. Initiate installation of EMCS hardware, devices and wiring. 4. Develop point database and application software. 5. Simulate sequencing and debug programming off-line to the extent practical. approval. 6. Submit Submittal Package 2 (Programming and Graphics) and receive 7. Complete installation of EMCS hardware, devices and wiring. 8. Install point database and application software in field panels.

13 9. Submit Submittal Package 3 (Functional Testing) and receive approval. 10. Perform EMCS Pre-functional Tests (start up, calibration and tuning) and submit Pre-functional Tests for approval. 11. Field test application programs prior to functional testing. 12. Receive EMCS Pre-functional Test Report approval and approval to schedule Functional Tests. approval. 13. Perform and record functional tests and submit Functional Test Report for 14. Assist TAB contractor in TAB tests and determine setpoints as specified in Section Submit Package 4 (Training Materials) and receive approval. 16. Receive EMCS Functional Test Report approval and approval to schedule Demonstration Tests. 17. Perform Demonstration Tests to Commissioning Coordinator and Owner Representatives and submit Demonstration Test Report. 18. Receive acceptance of Demonstration Tests. 19. Train Owner personnel on EMCS operation and maintenance. 20. Substantial Completion 21. Prepare and initiate commissioning Trend Logs. 22. Submit Trend Logs in format specified for review and approval. 23. Receive approval of successful Trend Log tests, or retest as required. 24. Provide administration level password access to the Owner. 25. Prepare and provide the Reference Retro-Commissioning Management Manual, Submittal Package 5, and receive approval. Contractor shall provide a backup copy of the final EMCS sequence of operations to the government on a medium that can be stored for later use. 26. Final Acceptance 27. Begin Warranty Period. 28. Prepare and initiate post-occupancy Trend Logs.

14 and approval. 29. After 6 months of operation, submit Trend Logs in format specified for review 30. Receive approval of successful Trend Log tests, or retest as required. 31. Two months prior to end of Warranty Period, submit Trend Logs in format specified for review and approval. 32. Receive approval of successful Trend Log tests, or retest as required. 33. Revise and submit record documents and O&M Manuals. 34. Update all software as specified. 35. End of Warranty Period 2.3 Functional Test Documentation A. Pre-functional Tests 1. Prepare forms to document the proper startup of the EMCS. 2. All equipment shall be included on test forms including but not limited to: verification a. Digital outputs: proper installation, normal position, response b. Digital inputs: proper installation, device test, response verification min stroke c. Analog outputs: proper installation of devices, verification of max and d. Analog inputs: proper installation of sensors, calibration e. Wiring connections and other electrical issues f. Panels g. Alarms and safeties h. Loop tuning i. Network traffic

15 3. Each form shall have a header or footer where the technician performing the test can indicate his/her name and the date of the test. 4. Submit forms for approval in Submittal Package Complete work, document results on forms, and submit for approval as Prefunctional Test Report. B. Functional Tests 1. Prepare functional testing forms after Submittal Package 2 has been reviewed and approved. Tests will be designed to test all sequences in a formal manner with simulations and expected outcomes. 2. Contractor shall prepare functional testing forms and test all sequences in a formal manner. Test forms shall include at a minimum: a column indicating the tests and simulations to be performed, the expected outcomes, the actual outcome, and check box indicating whether the system passed or failed. All forms shall be given to the government representative and all functional tests that do not pass, the contractor shall make appropriate adjustments until the system passes retests. 3. All control sequences shall be functionally tested. For systems that use identical control logic (e.g. VAV boxes, identical air handler), only one subsystem needs to be tested. Any changes to programming resulting from tests shall be made to all identical applications. 4. Each form shall have a header or footer where the technician performing the test can indicate his/her name and the date of the test. 5. Submit forms for approval in Submittal Package 3 6. Complete work, document results on forms, and submit for approval as Functional Test Report Instrumentation A. All instrumentation required to verify readings, to calibrate sensors, and to test the system and equipment performance shall be provided by Contractor. B. All equipment used for testing and calibration shall be NIST/NBS traceable and calibrated within the preceding 6-month period. Certificates of calibration shall be submitted. C. Test equipment used for testing and calibration of field devices shall be at least twice as accurate as respective field device (e.g. if field device is ±0.25% accurate over same range) Testing

16 2.5.1 Pre-functional Tests A. General 1. Inspect the installation of all devices. Review the manufacturer s installation instructions and validate that the device is installed in accordance with them. 2. Verify proper electrical voltages and amperages, and verify that all circuits are free from faults. 3. Verify integrity/safety of all electrical connections. 4. Verify that shielded cables are grounded only at one end. 5. Verify that all sensor locations are as indicated on drawings and are away from causes of erratic operation. 6. Ensure that minimum speed settings programmed into variable speed drive are at or below the minimum speed settings in control sequences. B. Digital Outputs 1. Verify that all digital output devices (relays, solenoid valves, two-position actuators and control valves, magnetic starters, etc.) operate properly and that the normal positions are correct. C. Digital Inputs 1. Adjust setpoints where applicable a. For current switches used as status on fans, adjust current set point so that fan status is off when fan discharge damper (if present) is fully closed and when belt is broken (temporarily remove belt). b. For current switches used as status on pumps, adjust current setpoint so that pump status is off when pump is dead-headed (temporarily close discharge valve). c. For differential pressure sensors on pumps and fans, set so that status is on when pump is operating with all valves open (out on its curve). D. Analog Outputs 1. Verify start and span are correct and control action is correct. 2. Check all control valves and automatic dampers to ensure proper action and closure. Make any necessary adjustments to valve stem and damper blade travel.

17 3. Check all normal positions of actuators with spring return. 4. For outputs to reset other manufacturer s devices (e.g. chiller setpoint) and for feedback from them, calibrate ranges to establish proper parameters. 5. Test and document actual spring range of pneumatic actuators from full open to full close and reflect this in pneumatic output ranges. E. Analog Input Calibration 1. Sensors shall be calibrated. Calibration methods shall be one of the following: a. Factory: Calibration by factory, to standard factory specifications. Field calibration is not required. b. Handheld: Field calibrate using a handheld device with accuracy meeting the requirements of Paragraph 2.1. c. Drywell Bath: Field calibrate using a 2-point procedure, using a drywell calibrator block constructed for that purpose, or an ice bath with a reference standard. 2. The calibrating parameters in software (e.g. slope and intercept) shall be adjusted as required. A calibration log shall be kept and initialed by the technician showing date and time, sensor and hand-held readings, and calibration constant adjustments and included in the Pre-functional Test Report. 3. Inaccurate sensors must be replaced if calibration is not possible. F. Alarms and Interlocks 1. A log shall be kept and initialed by the technician showing date and time, alarm/interlock description, action taken to initiate the alarm/interlock, and resulting action, and included in the Pre-functional Test Report. 2. Check each alarm separately by including an appropriate signal at a value that will trip the alarm. 3. Coordinate and interface with life safety systems and fire alarm contacts. 4. Interlocks shall be tripped using field contacts to check the logic, as well as to ensure that the fail-safe condition for all actuators is in the proper direction. 5. Interlock actions shall be tested by simulating alarm conditions to check the initiating value of the variable and interlock action. G. Tuning

18 1. Tune all control loops to obtain the fastest stable response without hunting, offset or overshoot. Record tuning parameters and response test results for each control loop in the Pre-functional Test Report. Except from a startup, maximum allowable variance from set point for controlled variables under normal load fluctuations shall be as follows. Within 3 minutes of any upset (for which the system has the capability to respond) in the control loop, tolerances shall be maintained (exceptions noted): Controlled Variable Control Accuracy Duct Pressure ±0.1 w.g. Building and relief plenum ±0.01 w.g. Airflow ±10% Laboratory fume hood and make-up See airflow Space Temperature ±1.5 F Chilled Water Temperature ±1 F Hot Water Temperature ±3 F Duct Temperature ±2 F Water Differential Pressure ±1.5 psi Others ±2 times reported accuracy H. Interface and Control Panels 1. Ensure devices are properly installed with adequate clearance for maintenance and with clear labels in accordance with the record drawings. 2. Ensure that terminations are safe, secure, and labeled in accordance with the record drawings. 3. Check power supplies for proper voltage ranges and loading. 4. Ensure that wiring and tubing are run in a neat and workman-like manner, either bound or enclosed in trough. 5. Check for adequate signal strength on communication networks. 6. Check for standalone performance of controllers by disconnecting the controller from the LAN. Verify the event is annunciated at Operator interfaces. Verify that the controlling LAN reconfigures as specified in the event of a LAN disconnection. 7. Ensure that buffered and/or volatile information is held through power outage. 8. With all system and communications operating normally, sample and record update/annunciation times for critical alarms fed from the panel to the Operator Interface. I. Operator Interfaces

19 1. Verify that all elements on the graphics are functional and are properly bound to physical devices and/or virtual points, and that hot links or page jumps are functional and logical. 2. Verify that the alarm printing, logging, paging, ing etc. is functional and per requirements. J. Trending/Network Traffic Test. Perform tests to verify that system has been designed adequately to simultaneously capture trends and allow proper operation of the control system. operational. 1. Tests shall be performed after the verification trends have been set up and are 2. Randomly select a device whose failure will generate an alarm and manually shut it off. The status points for the device must indicate the change of state of the device at the Operator Workstation within 5 seconds. The test shall be repeated for four devices in each building. 3. Test the clock signal from a field controller randomly selected. Test is considered acceptable if the local clock signal is no more than 2 seconds off of the system clock. 4. If the system fails any test, the system architecture shall be revised as required (e.g. more trend memory, more controllers with trend storage capability, network repeaters to allow an increase in network speed, etc.) followed by additional tests TAB Tests A. Setpoint Determination 1. Assist the TAB contractor in determining fan and pump differential pressure setpoints, outdoor air damper minimum positions and DP setpoints, and Testing, Adjusting and Balancing (TAB). operational. leaking valve. B. Coil Valve Leak Check 1. Coordinate test procedures concurrent with Testing, Adjusting and Balancing. 2. Test conditions for each hydronic system a. Tests shall be done when central plant cooling and heating systems are b. Close all control valves c. Start all fans associated with control valves d. Open bridge connection control valve e. Start both pumps f. Observe flow meter. If reading changes after pumps start, there is a

20 g. Observe supply air temperature at each coil after test starts h. Should any supply air temperature rise, close the isolation valves to the coil to see if temperature changes. If so, this validates that the valve is not fully closing. Remedy the condition by adjusting the stroke and range, increasing the actuator size/torque, replacing the seat, or replacing the valve as applicable Functional Tests A. Test schedule shall be coordinated with the Commissioning Coordinator. B. Tests may be witnessed by an Owner Representative at the Owner s option. C. All approved Functional Tests shall be conducted by the EMCS Contractor with results confirmed and signed by the Contractor s start-up technician. D. Test documentation shall be submitted to the Owner for review and approval Demonstration Test A. Demonstration tests consist of a small representative sample of functional tests and systems randomly selected by the Owner. Tests will be designed to occur over no longer than [Select: 2 days commonly, 4 days for complex systems] days. B. Schedule the demonstration with the Owner s representative 1 week in advance. Demonstration shall not be scheduled until the Functional Test Report has been approved. C. The contractor shall supply all personnel and equipment for the demonstration, including, but not limited to, instruments, ladders, etc. Contractor-supplied personnel shall be those who conducted the Functional tests or who are otherwise competent with and knowledgeable of all project-specific hardware, software, and the HVAC systems. D. The system will be demonstrated following procedures that are the same or similar to those used in the Pre-functional and Functional Tests. The Owner s representative will supply the test forms at the site at the start of the tests. E. Contractor shall conduct tests as directed by and in the presence of the Owner s representative and complete test forms. Completed forms shall be submitted as the Demonstration Test Report to the Owner and Commissioning Coordinator after tests are complete. F. Demonstration Tests shall be successfully completed and approved prior to Substantial Completion Trend Log Tests A. Commissioning (Post Construction) Trend Test

21 completed. 1. Trend logging shall not commence until Demonstration Tests are successfully 2. Contractor shall configure points to trend as required for Commissioning Trends including: a. For equipment of identical function, such as VAV zones and AHUs with identical components and control sequences, only a sample of such equipment need to be trended. The sampling shall be 10% of the identical components, but no more than 10 and no less than 3. Review with Owner representative before setting up trends. b. Where zone data (e.g. damper or valve position, control loop signal) is used for reset of the AHU/pump system serving the zone, the zone tag (name) and zone data (e.g. damper or valve position) shall be trended. c. All points trended for a single HVAC subsystem (e.g. air handling unit, chilled water system, etc.) shall be trended during the same trend period and the same time intervals so that data may be easily plotted using a spreadsheet. 3. Trends shall be uploaded to the Trend Historian Server in data format specified. 4. Trend logs of all points indicated above shall be collected for a (normally 2 or 4 week) week Trend Period. 5. At the completion of the Trend Period, data shall be reviewed by the Contractor to ensure that the system is operating properly. If so, data shall be submitted to the Owner in an electronic format agreed to by the Owner and Contractor (e.g. CD-ROM or via direct access to the Operator Workstation via the internet). 6. Data will be analyzed over approximately a two- to three-week period by an Owner representative. 7. The system shall be accepted only if the trend review indicates proper system operation without malfunction, without alarm caused by control action or device failure, and with smooth and stable control of systems and equipment in conformance with these specifications. If any but very minor glitches are indicated in the trends, steps 4 to 6 above shall be repeated for the same Trend Period until there is a complete Trend Period of error free operation. B. Post Occupancy Trend Tests 1. After successfully completing the Commissioning Trend Tests, the Contractor shall configure all points as required to trend for final Continuous Trending. 2. Archive trends up to the Operator Workstation without overwriting stored data for the entire Warranty Period. 3. Data will be reviewed by an Owner representative at the following intervals:

22 a. Approximately 6 months after system acceptance b. Approximately 2 months prior to the end of the Warranty Period Remedial Work A. Remedial work identified by site reviews, review of submittals, demonstration test, trend reviews, etc. shall be performed to the satisfaction of the Owner s representative, at no additional cost to the Owner Training Provide two (2) 16 hour training sessions for four people in the Civil Engineering facility. Contractor will provide the trainer and materials as part of the contract. The first training session will be immediately following successful commissioning of the DDC system and the second training session occurring approximately 6-12 months after the initial training session as requested and coordinated by the base personnel. 2.8 Retro-Commissioning Management Manual Prepare and submit a Reference Retro-Commissioning Management Manual containing the following information organized into a 3-ring binder with tabbed sections as listed. A. Design Intent: Final version of the owner s requirements and design basis narratives, including brief descriptions of each system. Shall also include a complete list of points of contacts for key personnel with all vendors and contractors, subcontractors including the Test & Balance contractors that were employed, consulted or referenced for completion of the project. B. Controls: 1. As-built sequences of operation for all equipment. 2. Controls drawings 3. A list of time of day schedules and a schedule to review them for relevance and efficiency. 4. A list of all user adjustable setpoints and reset schedules with rationale for their selection and range. C. Energy and Water Efficiency Measures: 1. A description and rationale for all energy and water saving features and strategies with operating and instructions. 2. Guidelines for establishing and tracking benchmarks for whole building energy use and equipment efficiencies of cooling, heating, and service hot water equipment.

23 3. Seasonal Issues. 4. Calibration: Recommendations for recalibration frequency of sensors and devices by type and use. 2.9 Warranty Contractor to provide a one (1) year warranty on all parts and labor and a five (5) year warranty on all sensors, valves, and actuators installed in this contract.

24 Bldg 650 Bldg 654 Bldg 656 Bldg 662 Bldg 680 Bldg 653 Bldg 663 Bldg 681 Bldg 683 Project Number QMSN Install Basewide EMCS System Facilities included in this Statement of Work: Bldg 653 has an ALC system installed. Contractor shall connect this building to the basewide EMCS and report to the controller. Operations and Training Facility under construction and will have an ALC system installed. Contractor shall connect this building to the basewide EMCS and report to the controller. Shall be an optional bid item Shall be an optional bid item.

25

SECTION INTEGRATED AUTOMATION COMMISSIONING

SECTION INTEGRATED AUTOMATION COMMISSIONING SECTION 25 08 00 INTEGRATED AUTOMATION COMMISSIONING PART 1. GENERAL 1.01 SECTION INCLUDES: A. BAS and equipment testing and start-up B. Validation of proper and thorough installation of BAS and equipment

More information

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

SECTION FUNCTIONAL PERFORMANCE TESTING (FPT) PROCEDURES - CONSTRUCTION MANAGER EDITION

SECTION FUNCTIONAL PERFORMANCE TESTING (FPT) PROCEDURES - CONSTRUCTION MANAGER EDITION Montgomery County Public Schools Facilities DIVISION 1 - GENERAL REQUIREMENTS SECTION 01915 - FUNCTIONAL PERFORMANCE TESTING (FPT) PROCEDURES - CONSTRUCTION MANAGER EDITION PART 1 GENERAL 1.1 Section includes:

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0993 SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS A. This section defines the manner and method by which controls function. Requirements for each type of

More information

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Related Sections..1 The contractor is to ensure that all related work is co ordinated among all specification sections, as well as between Division 11,

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 0800 - COMMISSIONING OF FIRE SUPPRESSION SYSTEMS GENERAL 1.1 SUMMARY General 1. Work under this contract shall meet the requirements of Division 01, General Requirements, Conditions of Contract,

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

Fire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC

Fire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC PART 1 GENERAL 1.01 SUMMARY SECTION 23 08 00 COMMISSIONING OF HVAC A. This section covers the Contractor's and Commissioning Authority (CA) responsibilities for commissioning; each subcontractor or installer

More information

American University Design Standards

American University Design Standards 25 95 00 CONTROL SEQUENCES FOR HVAC PART 1. GENERAL 1.01 SECTION INCLUDES A. Description of Work B. Control Sequences General Requirements C. System Specific Control Sequences 1.02 RELATED DOCUMENTS A.

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Virginia Tech Standards for Building Automation System

Virginia Tech Standards for Building Automation System March 1, 2016 Virginia Tech Standards for Building Automation System A. Existing Conditions: The Campus Building Automation System is Siemens Apogee and controls all significant campus facilties. Virginia

More information

SECTION BUILDING AUTOMATION SYSTEM

SECTION BUILDING AUTOMATION SYSTEM SECTION 25 10 00 BUILDING AUTOMATION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Work hereunder includes a complete and operational, fully-tested, distributed logic, direct digital control system for control

More information

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE PAGE 280800-1 SECTION 280800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

CxA to Answer this Section

CxA to Answer this Section EXHIBIT 01 91 13-3, SAMPLE Construction checklist items are to be completed as part of initial checkout and subsequent startup, preparatory to Functional testing. This checklist does not take the place

More information

opti-visor ultra-efficient chiller plant automation Typical specification

opti-visor ultra-efficient chiller plant automation Typical specification opti-visor ultra-efficient chiller plant automation Typical File No: 90.893 Date: february 9, 2015 Supersedes: 90.893 Date: april 20, 2012 contents 1.0 Chilled water plant 4 1.1 General system requirements

More information

Feature Summary. I. System

Feature Summary. I. System I. System A. Supports up to 60 VAV HVAC Units 1. Each HVAC Unit Can Support up to 59 VAV Boxes 2. Constant Volume Units Can Be Integrated With VAV Units 3. System Can Support Over 3000 Controllers B. Fill-in

More information

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

November 11, City of Sparks 215 S. 21 st St. Sparks, NV November 11, 2014 City of Sparks 215 S. 21 st St. Sparks, NV 89432-0857 Attn: Brian Cason Re: Sparks City Hall HVAC Upgrade Project-Alerton Direct Digital HVAC Control System to Match Existing City of

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Mechanical. Environmental Control Systems. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Mechanical. Environmental Control Systems. Basis of Design Basis of Design University of Washington Specific Controls Features The following items are specific to the University of Washington: The goal is to move from pneumatic to DDC controls. This goal shall

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION SECURITY TESTING AND COMMISSIONING

SECTION SECURITY TESTING AND COMMISSIONING SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,

More information

SECTION PLUMBING/HVAC FINAL TESTING, ADJUSTING AND BALANCING

SECTION PLUMBING/HVAC FINAL TESTING, ADJUSTING AND BALANCING SECTION 15990 PLUMBING/HVAC FINAL TESTING, ADJUSTING AND BALANCING PROJECT NO. ####### PART I - GENERAL 1.01 WORK INCLUDED A. Final test and balance of air distribution systems. B. Final test and balance

More information

TESTING, ADJUSTING AND BALANCING

TESTING, ADJUSTING AND BALANCING PART 1 GENERAL 1.01 DESCRIPTION A. Work Included: After completion of the work of installation, owner is responsible for procuring an air balancing and testing agency to test and regulate all components

More information

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0593 TESTING, ADJUSTING, AND A. Testing, adjustment, and balancing of air systems. B. Testing, adjustment, and balancing of hydronic, steam, and refrigerating

More information

Building Automation System

Building Automation System University of New Hampshire University of New Hampshire Scholars' Repository Division 25 Integrated Automation Chapter 5 Technical Construction and Renovation Standards 8-1-2014 250000 - Building Automation

More information

SECTION ELECTRICAL SYSTEMS COMMISSIONING

SECTION ELECTRICAL SYSTEMS COMMISSIONING SECTION 16990 PART 1 - GENERAL 1.01 SECTION INCLUDES A. Section Includes: 1. General requirements for Commissioning (Cx) of lighting systems components, lighting controls and HVAC systems line voltage

More information

Automation and Energy Efficiency of Industrial Refrigeration Systems

Automation and Energy Efficiency of Industrial Refrigeration Systems Automation and Energy Efficiency of Industrial Refrigeration Systems E360 Forum Chicago, IL October 5, 2017 Mike Micak Director of Sales Logix Controls Introduction Management thinker Peter Drucker was

More information

Building Automation System (BAS) Design Criteria

Building Automation System (BAS) Design Criteria 25 0520 Building Automation System (BAS) Design Criteria 1. Design Statement a. During the various design phases of this project, the Engineer will develop options and strategies for selection of the appropriate

More information

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE

More information

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application 2025 Application Note 140-1054 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

SECTION GAS-FIRED RADIANT HEATERS

SECTION GAS-FIRED RADIANT HEATERS SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

AirTrak. Digital Control System. User Manual. Touchscreen Systems

AirTrak. Digital Control System. User Manual. Touchscreen Systems AirTrak Digital Control System User Manual Touchscreen Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 9 AIRTRAK DEFAULT SETTINGS... 9 Unit Operating Modes... 10 MRT Controls...

More information

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate COMcheck Software Version 4.0.4. Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 205 IECC Dallas, Texas 3a New Construction Construction Site: 56

More information

Updated: September 12, 2018 DIVISION INTEGRATED AUTOMATION. INTEGRATED AUTOMATION Page 1 of INTEGRATED AUTOMATION

Updated: September 12, 2018 DIVISION INTEGRATED AUTOMATION. INTEGRATED AUTOMATION Page 1 of INTEGRATED AUTOMATION Page 1 of 7 25 00 00 25 10 00 NETWORK EQUIPMENT Standby Power 1. Consider whether the controls system should be on standby/emergency power, or UPS when central applications are controlled or the equipment

More information

Integrated Automation Instrumentation & Terminal Devices

Integrated Automation Instrumentation & Terminal Devices Sections Included In This Standard: 1.1 Building Systems Control 1.2 Building Aumotation Systems (BAS) 1.1 BUILDING SYSTEMS CONTROL A. HVAC CONTROLS: 1. General: Temperature control zones shall not combine

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 25- INTEGRATED AUTOMATION DESIGN STANDARDS SECTION INTEGRATED CONTROL OF FACILITY LAB FUME HOODS

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 25- INTEGRATED AUTOMATION DESIGN STANDARDS SECTION INTEGRATED CONTROL OF FACILITY LAB FUME HOODS PART 1 - GENERAL 1.01 General: A. Laboratory ventilation system will ensure the health and safety of laboratory occupants. B. Room pressurization control will utilize airflow tracking to vary the volume

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS 1 AIR HANDLING UNIT TRENDS 2 1. The trending charts provided on the following pages prepared as part of a retro-commissioning investigation. The

More information

Architectural and Engineering Specification for a Real-Time Locating System Flare

Architectural and Engineering Specification for a Real-Time Locating System Flare Architectural and Engineering Specification for a Flare AE-T1-IN-R3-E-0617 Page 1 of 14 This document is intended to provide performance specifications and operational requirements for the Flare. It is

More information

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC PART 1 GENERAL SECTION 23 0923 DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC 1.01 RELATED WORK UNDER OTHER SECTIONS: A. In addition to the general building construction, work directly related to the automatic

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

Demonstration and Training of MEP Systems Page 1 of 15

Demonstration and Training of MEP Systems Page 1 of 15 Page 1 of 15 Last Update: May 17, 2018 A. General: 1. Demonstrations and Training of various MEP and other systems is very important to BSU Facilities, especially on new building or major renovation projects.

More information

FUNCTIONAL DESIGN SPECIFICATION

FUNCTIONAL DESIGN SPECIFICATION Issue Date: Issued To: Revision: FUNCTIONAL DESIGN SPECIFICATION Specification Number: SP-XXXX Company Name Signature Date Issued By: Manutec Ltd. Approved By: Approved By: Approved By: Approved By: Authorised

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

Instrumentation and Control for HVAC

Instrumentation and Control for HVAC 23 09 00 Instrumentation and Control for HVAC 1. All controls to be corporate Trane or Honeywell, no substitutes. 2. Factory Mounted controls to be Trane only, otherwise provide terminal strips for TC

More information

"This is only the scope of work for the project. For more information, interested parties should contact Procurement at

This is only the scope of work for the project. For more information, interested parties should contact Procurement at "This is only the scope of work for the project. For more information, interested parties should contact Procurement at purchasing@stpgov.org to ensure receipt of a full bid package, to be listed as a

More information

SECTION GENERATOR PARALLELING CONTROLS

SECTION GENERATOR PARALLELING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

"This is only the scope of work for the project. For more information, interested parties should contact Procurement at

This is only the scope of work for the project. For more information, interested parties should contact Procurement at "This is only the scope of work for the project. For more information, interested parties should contact Procurement at purchasing@stpgov.org to ensure receipt of a full bid package, to be listed as a

More information

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story

More information

IE Code IE Competency Title Credit OAC Ref.

IE Code IE Competency Title Credit OAC Ref. Compulsory Workplace Competency Standards Level Four IE Code IE Competency Title Credit OAC Ref. IE119-4WC Design and draw electrical and electronic drawings including schematics, 4 F5 maintain documentation

More information

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 15990 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the Specifier in correctly specifying Mechanical System Testing Adjusting

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

i-vu CCN 4.0 Owner s Guide

i-vu CCN 4.0 Owner s Guide i-vu CCN 4.0 Owner s Guide CARRIER CORPORAION 2007 A member of the United echnologies Corporation family. Stock symbol UX. 11-808-377-01 07/07 able of Contents ACCESSING YOUR SYSEM... 3 YOUR SYSEM DEAILS...

More information

San Marcos Building Standards PART 1 - GENERAL 1.1 SUMMARY

San Marcos Building Standards PART 1 - GENERAL 1.1 SUMMARY PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control equipment for HVAC systems and components, including control components for terminal heating and cooling units not supplied with factory-wired

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-05 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Galveston (TAMU-G) Galveston, Texas Submitted to Texas A&M University

More information

L CONNECTION NETWORK Commercial Controls

L CONNECTION NETWORK Commercial Controls L CONNECTION NETWORK Commercial Controls SIMPLIFIED, CENTRAL CONTROL Simplified Control for Your Facility The L Connection Network not only enhances comfort and energy-efficiency throughout your facilities,

More information

Installation and Maintenance Manual IM Single Duct VAV Terminals. Group: Controls Part Number: IM 1093 Date: February 2015

Installation and Maintenance Manual IM Single Duct VAV Terminals. Group: Controls Part Number: IM 1093 Date: February 2015 Installation and Maintenance Manual IM 1093-1 Single Duct VAV Terminals Group: Controls Part Number: IM 1093 Date: February 2015 Table of Contents Introduction.... 3 Revision History...3 Reference Documents...3

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 23 0594 - TESTING, ADJUSTING, AND BALANCING (TAB) PART 1 - GENERAL 1.1 SUMMARY A. This Section includes testing, adjusting and balancing HVAC systems to provide design conditions as indicated by

More information

Computing Services Center

Computing Services Center Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Northwestern University Scope of BAS Contractor

Northwestern University Scope of BAS Contractor The purpose of this document is to describe the Enterprise Level Server at Northwestern University, and the separation of roles between the System Integrator and the Building Automation System Contractor.

More information

Architectural and Engineering Specification for a. Flash / Flare

Architectural and Engineering Specification for a. Flash / Flare Architectural and Engineering Specification for a Flash / Flare June 27, 2014 Page 1 of 12 T1DA0115-001 Rev D This document is intended to provide performance specifications and operational requirements

More information

SECTION LIGHTING CONTROLS

SECTION LIGHTING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available. PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application 2023 Application Note 140-1052 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 6 Hardware Outputs...

More information

Section PERIMETER SECURITY SYSTEMS

Section PERIMETER SECURITY SYSTEMS Section 28 16 43 PERIMETER SECURITY SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide and install a perimeter security system as herein specified for the purpose of detecting entry into a designated security

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and

More information

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas

More information

WESTIN HOTEL. Smoke Control System. Testing Procedures Manual. October 10, Copyright Impact Engineering, Inc All Rights Reserved

WESTIN HOTEL. Smoke Control System. Testing Procedures Manual. October 10, Copyright Impact Engineering, Inc All Rights Reserved IMPACT ENGINEERING, INC. WESTIN HOTEL Smoke Control System Testing Procedures Manual October 10, 2016 Copyright Impact Engineering, Inc. 2016 All Rights Reserved This manual is protected by the U.S. Copyright

More information

LineGuard 2300 Program User Manual (FloBoss 107)

LineGuard 2300 Program User Manual (FloBoss 107) Form A6251 Part Number D301346X012 November 2012 LineGuard 2300 Program User Manual (FloBoss 107) Remote Automation Solutions Revision Tracking Sheet November 2012 This manual may be revised periodically

More information

Improving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks

Improving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks Improving Performance with a Building Tune-Up Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks How much is too much? Most buildings can cut total energy use by 5-30% while

More information

SECTION ENERGY MANAGEMENT SYSTEM (EMS)

SECTION ENERGY MANAGEMENT SYSTEM (EMS) SECTION 13810 ENERGY MANAGEMENT SYSTEM (EMS) PART 1 GENERAL 1.01 SUMMARY A. Section Includes: The energy management system (EMS) including the following major subsystems: HVAC temperature controls, HVAC

More information

FACILITY CONTROLS BUILDING AUTOMATION SYSTEM (BAS) DESIGN AND CONSTRUCTION STANDARD

FACILITY CONTROLS BUILDING AUTOMATION SYSTEM (BAS) DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. The design guidelines contained herein include the requirements for integrated automation facility controls at The University of Texas at Austin. It is the intention of

More information

Electronic Safety and Security

Electronic Safety and Security 28 Electronic Safety and Security NOTE: This is a new section, which includes content from previous sections of the KU Design Standards, along with appropriate revisions and updates. Significant revisions

More information

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Technical Report #3 Mechanical Systems Existing Conditions Evaluation Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents

More information

Tri-Stack Smart System

Tri-Stack Smart System Tri-Stack Smart System TM Notes & Warnings - The protection provided by this equipment may be impaired if it is not used in the manner specified herein. - Ensure all wiring meets applicable national and

More information

Florida Department of Transportation

Florida Department of Transportation Page 1 of 7 RICK SCOTT GOVERNOR Florida Department of Transportation 1109 S. Marion Avenue Lake City, Florida 32025 ANANTH PRASAD SECRETARY September 27, 2011 To: Proposal Holders Addendum No: 1, E2Q23,

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 23 05 93 - TESTING, ADJUSTMENT AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.

More information

ADDENDUM NO.1. March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL

ADDENDUM NO.1. March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL ADDENDUM NO.1 March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL The data included hereinafter is issued by the Engineer (Engineered Systems Associates, 1355 East Center, Pocatello, ID

More information

Samsung SDS BMS Ver.2.0. Technical Specification

Samsung SDS BMS Ver.2.0. Technical Specification Samsung SDS BMS Ver.2.0 Technical Specification Technical Specifications All rights and title, including all intellectual property rights to Samsung SDS BMS" is retained by Samsung SDS Co, Ltd. ("SDS"),

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if