Box-in-Box Cold Storage Fire Protection Options

Size: px
Start display at page:

Download "Box-in-Box Cold Storage Fire Protection Options"

Transcription

1 Box-in-Box Cold Storage Fire Protection Options FireAustralia TYCO Model ESFR-17 Dry Type Pendent Sprinkler Jeffrey Barkley Tyco Fire Protection Products

2 Objective Common Box-inBox Cold Storage Challenges Dry Type Pendent ESFR Sprinklers Advantages Applications Summary 2

3 Box-in-Box Cold Storage Refrigerated storage area built inside a new or existing building Achieving higher storage heights and cube availability Providing flexible stocking configurations Protection of more commodity classifications Often non-structural insulating panels Sprinkler pipe can be hung from building structure Wet System may already be installed above box Recalculate the system hydraulics Any place a refrigerated box is built inside a structure with non-freezing temperatures 3

4 Traditional Protection Options Storage Arrangement Palletized and Solid Piled Open Frame Rack Without Solid Shelves Class I & II VANQUISH ESFR Anti- Freeze Double Interlock Pre-action Class III * Commodity Class Class IV and Cartoned Unexpanded Plastics Exposed/Uncartoned Unexpanded Plastics Idle Pallets & Rubber Tires Roll Paper Storage Height 35 ft (10,7 m) Maximum 40 ft (12,2 m) Maximum 40 ft (12,2 m) Maximum 4 Ceiling Height 45 ft (13,7 m) Maximum 48 ft (14,6 m) Maximum * Maximum storage height 25 ft (7,6 m)

5 ESFR Dry-Type Pendent Sprinkler Supported by building structure outside of box-in-box area Installed on simple wet system Provides suppression performance to cold storage Ceiling heights to 40 ft (12,2m) Wide range of commodities Wide range of storage arrangements 60 minute water duration Protection of Wide Range of Commodities and Storage Arrangements Without In-rack Sprinklers 5

6 Model ESFR-17 Dry-Type New Tyco Storage Sprinkler The Model ESFR-17 Dry-Type Sprinkler provides fire protection for box-in-box cold storage facilities with: Greater flexibility and marketability of the facilities Lower installed cost and better fire protection when compared to other ceiling-only protection options Lower installed cost when compared to in-rack protection Lower cost of operation than other options Only the TYCO Model ESFR-17 Dry-Type offers: Low installed cost because of the opportunity to reduce pipe size and use smaller fire pumps because of the lower minimum pressures compared to other ESFR dry pendents 40 ft (12,2 m) ceiling only protection under NFPA Edition 6 Complete ESFR Protection for Box-in-Box Cold Storage

7 ESFR-Class Fire Protection for Cold Storage The Model ESFR-17 Dry-Type Sprinkler Pendent provides ESFR class protection for box-in-box cold storage facilities Installed to NFPA Guidelines for ESFR 16.8 (242) sprinklers Solid pile or palletize storage of Class I IV to 35 ft (10.7 m) of storage and Group A or B Plastics Open frame single, double and multiple-row rack (no solid shelves) of Class I IV to 35 ft (10.7 m) of storage and Group A or B Plastics Idle pallet storage Rubber Tire Storage Rolled paper storage Flammable liquid storage 7 Aerosol storage Greater flexibility and Marketability of the facilities

8 Box-in-Box Ceiling Only Protection Options Comparison per NFPA 13 Dry Pendent ESFR K 16.8 (242) VANQUISH ESFR With Anti-freeze (Wet) NFPA 13 Double Interlock Pre-action Application Box-in-Box Structural Structural Structural System Type Wet Double Interlock Pre-action Single Interlock Pre-action (Wet) Double Interlock Pre-action Piping System Tree or Grid Tree Tree Tree Rack Commodity Max Rack Ceiling Height Max Cartoned Expanded 40 ft (12,2) Class IV Cartoned Unexpanded 48 ft (14,6) Class III Class II 45 ft (13,7) Class II Class III Max Storage 25 ft (7,6 m) 40 ft (12,1) Class II Rack Storage Height Max Pressure at Max Height System Volume Limitation Minimum Temperature 35 ft (10,5 m) Class IV 52 psi (3.6 bar) N/A Note: Maximum System Protection Area 40,000 ft 2 (3,716 m 2 ) 40 ft (12,2 m) Class III 30 psi (2.1 bar) 4200 gal (15899 l) 40 ft (12,2 m) Class II 60 psi (4.1 bar) 1100 gal (4164 l) Lower installed Cost and Better Fire Protection Than Alternatives 35 ft (7,5 m) Class II 22 psi (1,5 bar) Meeting 40 Second Water Delivery Time -60 F (-51 C) No Restriction -21 F (-29.4 C) No Restriction

9 Maintenance Schedule For Various Systems Per NFPA 25, 2010 Edition Weekly Monthly Inspect Gauges Inspect Gauges Inspect Control Valves Test Mechanical water flow alarm devices Inspect Control Valves Dry ESFR Pendent VANQUISH Anti- Freeze Double Interlock Pre-action Quarterly Semi - annually Inspect water flow alarm devices, Valve supervisory alarm devices, Supervisory signal devices, Hydraulic Nameplate Test priming water level, low air pressure alarms, Test Quick Opening Devices, Test low air pressure alarms Test valves supervisory, vane/pressure switch water flow alarm devices, Test Antifreeze solution 9 Fewer inspection and maintenance activities on weekly, monthly, quarterly and semi-annual result in lower cost of operation

10 Maintenance Schedule For Various Systems Continued Per NFPA 25, 2010 Edition Dry ESFR Pendent VANQUISH ESFR Anti- Freeze (Wet) Double Interlock Pre-action Inspect Pipe and fittings, sprinklers, inspect spare sprinklers, inspect information sign, Test valves operation, Test Supervisory signal devices, Test main drain Annually Inspect interior of non-re-settable Control Valves, inspect condition of detection devices, Conduct Partial Flow Trip Test Pre-action System Maintenance Low-point drains, Test automatic air pressure maintenance devices 3 Years Full Flow Trip Test Pre-action System* Test for air leakage, Inspect Sprinkler Piping for Ice Plugs 5 Years Test Gauges Inspect interior of resettable Control Valves, 10 Years Test Sprinklers Dry 10 * NFPA Pre-action or deluge valves protecting freezers shall be trip tested in a manner that does not introduce moisture into the piping in the freezer. Fewer inspection and maintenance activities on annual and longer basis result in lower cost of operation

11 Example Comparing K-Factor 16.8 (242) with 14.0 (200) For a box-in-box freezer that is: K-16.8 (242) uses less material 200 x 100 ft (61 x 30 m) 2000 ft2 (186 m2) 40 ft (12.1 m) ceiling 35 ft (10.5 m) storage Class III Commodities Open frame rack 2.0 in (DN50) versus 2.5 in (DN65) branch lines 10% less labor K-16.8 (242) has 10% lower system pressure when using same main size and the smaller branch lines Opportunity to reduce pipe size saving material and labor and to possibly downsize or eliminate fire pump saving installation cost 11

12 NFPA 13 ESFR Protection Height Change Table Class I through Class IV Palletized and Sold-Piled Storage NFPA Edition and Earlier NFPA Edition ESFR K 14.0 (200) 75 PSI (5,2 bar) ESFR K 16.8 (242) 52 PSI 3,6 bar) ESFR K 14.0 (200) 35 ft (10,7 m) Ceiling 25 ft (9,1 m) Storage 75 PSI (5,2 bar) ESFR K 16.8 (242) 52 PSI 3,6 bar) 12

13 NFPA 13 ESFR Protection Height Change Table Cartoned and Exposed Unexpanded Plastic Palletized and Sold-Piled Storage NFPA Edition and Earlier ESFR K 14.0 (200) 75 PSI (5,2 bar) ESFR K 16.8 (242) 52 PSI 3,6 bar) ESFR K 14.0 (200) 35 ft (10,7 m) Ceiling 30 ft (9,1 m) Storage 75 PSI (5,2 bar) NFPA Edition ESFR K 16.8 (242) 52 PSI 3,6 bar) 13

14 NFPA 13 ESFR Protection Height Change Table Class I through Class IV Rack Storage Up to and Including 25 ft (7,6 m) NFPA Edition and Earlier NFPA Edition ESFR K 14.0 (200) 75 PSI (5,2 bar) ESFR K 16.8 (242) 52 PSI 3,6 bar) ESFR K 14.0 (200) 35 ft (10,7 m) Ceiling 25 ft (9,1 m) Storage 75 PSI (5,2 bar) ESFR K 16.8 (242) 52 PSI 3,6 bar) 14

15 NFPA 13 ESFR Protection Height Change Table Class I through Class IV Rack Storage Over 25 ft (7,6 m) NFPA Edition and Earlier NFPA Edition ESFR K 14.0 (200) 75 PSI (5,2 bar) ESFR K 16.8 (242) 52 PSI 3,6 bar) ESFR K 14.0 (200) 40 ft (12.2 m) Ceiling 75 PSI (5,2 bar) ESFR K 16.8 (242) 52 PSI 3,6 bar) 15

16 NFPA 13 ESFR Protection Height Change Table Cartoned and Exposed Unexpanded Plastic Rack Storage Up to and Including 25 ft (7,6 m) NFPA Edition and Earlier ESFR K 14.0 (200) 75 PSI (5,2 bar) ESFR K 16.8 (242) 52 PSI 3,6 bar) ESFR K 14.0 (200) 35 ft (10,7 m) Ceiling 25 ft (9,1 m) Storage 75 PSI (5,2 bar) NFPA Edition ESFR K 16.8 (242) 52 PSI 3,6 bar) 16

17 NFPA 13 ESFR Protection Height Change Table Cartoned and Exposed Unexpanded Plastic Rack Storage Over 25 ft (7,6 m) NFPA Edition and Earlier ESFR K 14.0 (200) 75 PSI (5,2 bar) ESFR K 16.8 (242) 52 PSI 3,6 bar) ESFR K 14.0 (200) 35 ft (10,7 m) Ceiling 25 ft (9,1 m) Storage 75 PSI (5,2 bar) NFPA Edition ESFR K 16.8 (242) 52 PSI 3,6 bar) 17

18 Tyco Storage Sprinklers Categories Under NFPA 13 Control Mode, Density-Area Method (ELO, K17-231) Control Mode, Specific application (Ultra K17 and Large Drop) Intermediate Level Sprinkler (TY and Flat Spray) Extended Coverage (Model EC-25) Suppression Mode, Early Suppression Fast Response Model ESFR-1,Model ESFR-17, Model ESFR-25 Now Model ESFR-17 Dry-Type Pendent 18

19 Model ESFR-17 Dry Type Pendent Sprinkler Flexibility to match the application Threaded 1 ¼ Inch NPT or ISO 7-R 1-¼ 2 Inch (DN50) Groove Nominal Temperature 165 F (74 C) or 214 F (101 C) 19

20 Installation Using Threaded Fitting Exposure Length of Ambient Temperature of Sprinkler inches (mm) Discharge End of Sprinkler in Heated Area 40 F (4 C) 0 30 F (-1 C) 0 20 F (-7 C) 4 (100) 10 F (-12 C) 8 (200) 0 F (-18 C) 12 (305) -10 F (-23 C) 14 (355) -20 F (-29 C) 14 (255) -30 F (-34 C) 16 (405) -40 F (-40 C) 18 (455) -50 F (-46 C) 20 (510) -60 F (-51 C) 20 (510) 20

21 Installation Using Grooved Fitting Ambient Temperature of Discharge End of Sprinkler Exposure Length of Sprinkler inches (mm) in Heated Area 40 F (4 C) 0 30 F (-1 C) 0 20 F (-7 C) 4 (100) 10 F (-12 C) 8 (200) 0 F (-18 C) 12 (305) -10 F (-23 C) 14 (355) -20 F (-29 C) 14 (255) -30 F (-34 C) 16 (405) -40 F (-40 C) 18 (455) -50 F (-46 C) 20 (510) -60 F (-51 C) 20 (510) 21

22 Model ESFR-17 Dry Type Pendent Sprinkler Complete ESFR Protection Lower installation cost than alternatives Opportunity to downsize pipe and fire pump as compared to other dry ESFR sprinklers Flexibility in sprinkler location because of the availability of two temperature ratings Uses lower cost threaded outlets Simpler system than other ceiling only alternatives Eliminate in-rack sprinklers for cold storage application Lower operating cost than alternative technologies Less complex system Few maintenance requirements One of the Tyco Solutions for Storage Protection 22

23 Tyco Fire Protection Overview Provides fire protection contracting, services and products, and life safety products Strong market position with leading technologies Attractive markets with good growth and profit opportunities Over US$ 4B in annual revenue 23,000 employees worldwide 27 manufacturing facilities 16 engineering Centers of Excellence 23

24 24 Your Questions

25 Thank You

Sprinkler Solutions for Storage Applications

Sprinkler Solutions for Storage Applications Sprinkler Solutions for Storage Applications Logistics and Distribution As storage facilities and their distribution methods have evolved, so have the challenges of protecting them. When installing a fire

More information

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Product Description The Reliable Model JL-14 Early Suppression Fast Response

More information

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed. Page of 5. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK506 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor allows

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) Page 1 of 7 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) February 27, 2009 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition

More information

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN) Worldwide Contacts www.tyco-fire.com Model ESFR-25 25.2 K-factor Pendent Sprinkler Early Suppression, Fast Response General Description TYCO Model ESFR-25 Pendent Sprinklers are Early Suppression, Fast

More information

Significant Advancements in Water Based Fire Suppression for Storage Occupancies

Significant Advancements in Water Based Fire Suppression for Storage Occupancies Significant Advancements in Water Based Fire Suppression for Storage Occupancies Presented by: James Golinveaux Sr. Fellow Tyco Fire Protection Products Higher Faster - Further How high can we go? Ceiling

More information

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA Page 1 of 7 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor

More information

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA Page 1 of 6 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK500 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

TECHNICAL DATA NOTICE

TECHNICAL DATA NOTICE Page 1 of 5 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Upright Sprinkler VK520 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fire.com Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description The TYCO Model ESFR-17 Dry

More information

STORAGE FIRE PROTECTION SPRINKLERS

STORAGE FIRE PROTECTION SPRINKLERS STORAGE FIRE PROTECTION SPRINKLERS HOW CAN YOU REDUCE YOUR FIRE SPRINKLER INSTALLATION COSTS? Tyco Storage Sprinklers are intended for use in storage applications such as big box retail, extra hazard,

More information

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed. March 7, 2008 Sprinkler 120a Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent

More information

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Email: techserv@tycofp.com Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description The Tyco Model

More information

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Email: techserv@tycofp.com Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description The Tyco Model

More information

Sprinkler Identification Numbers

Sprinkler Identification Numbers Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-50 Model Early Suppression Fast Response Pendent Sprinklers 16.8 K-factor General Description The Model Pendent Sprinklers (Ref. Figure 1) are Early

More information

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed.

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed. Sprinkler 121a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Upright Sprinkler VK520 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

Storage Sprinkler U.S. Quick Reference Guide

Storage Sprinkler U.S. Quick Reference Guide Storage U.S. Reference Guide This guide is intended for general reference only. Prior to the design, layout, and/or installation of any sprinkler system, please refer to Viking s technical documentation

More information

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description The TYCO Model ESFR-17 Dry Type Pendent Sprinklers (TY7229)

More information

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 16.8 K-factor Dry Type Pendent s Early Suppression, Fast Response General Description TYCO Model ESFR-17 Dry Type Pendent s are Early Suppression, Fast

More information

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 16.8 K-factor Dry Type Pendent s Early Suppression, Fast Response General Description TYCO Model ESFR-17 Dry Type Pendent s are Early Suppression, Fast

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE November 2, 2007 Sprinkler 113a 1. DESCRIPTION The Viking Standard Response High Challenge Upright Large-Drop Sprinkler VK540 is a thermosensitive, glass-bulb sprinkler intended for use in protecting high

More information

esfr dry pendent sprinkler Vk502 (k14.0)

esfr dry pendent sprinkler Vk502 (k14.0) Page 1 of 11 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series ELO-231 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description Response, Standard Coverage Upright and Pendent

More information

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed.

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed. Page 1 of 10 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK504 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

esfr dry pendent sprinkler Vk501 (k14.0)

esfr dry pendent sprinkler Vk501 (k14.0) September 13, 2012 Sprinkler 122a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK501 is a fast response fusible element type sprinkler designed for use in storage

More information

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014 NFPA 13 2016 Edition NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s Committees created the First Draft at meetings between July 2013 and December 2013 Balloting ended in early 2014 First Draft decisions

More information

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J. American Society of Safety Engineers Professional Development Conference June 9-12, 2008 Session No. 101F Fire Protection Stephen J. Musur CSP, CFPS Chubb Group of Insurance Companies June 12, 2008 1 Fundamentals

More information

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Michael Billstroem Director of International Technical Services The Reliable Automatic Sprinkler Co.,

More information

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses PART 1 - GENERAL 1.1 SCOPE A. Through Class III Commodity Classification, up to 12.2m of single, double or multiple row rack storage, up to 14.6m building height (VanQuish Fire Sprinkler System). Cartoned

More information

E x t E N d e d Co v e r ag e S p r i n k l e r s. Office Buildings Hotels Hospitals Libraries. High-Piled Storage Big-Box Retailing

E x t E N d e d Co v e r ag e S p r i n k l e r s. Office Buildings Hotels Hospitals Libraries. High-Piled Storage Big-Box Retailing Extended Coverage Sprinklers Extended Coverage Sprinklers are intended for the protection of areas larger than those specified in standard installation rules and for specific light, ordinary, or extra

More information

The Effect of Large Orifice Sprinklers on High-Challenge Fires

The Effect of Large Orifice Sprinklers on High-Challenge Fires SUPPLEMENT 2 The Effect of Large Orifice Sprinklers on High-Challenge Fires Bill Thomas, P.E. Bill Tomes Editor s Note: Supplement 2 provides background information related to the development and application

More information

PLAN REVIEW CHECKLIST

PLAN REVIEW CHECKLIST PLAN REVIEW CHECKLIST Date Documents Submitted: Log No.: File No.: Property Information Building Name: Building Address: Owner s Name: Owner s Address: Owner s Phone: Fax: E-mail: System Designer/Contractor

More information

ADDENDUM #1 ITB# Fire Protection Maintenance Services Responses to Clarification Questions 10/06/2015

ADDENDUM #1 ITB# Fire Protection Maintenance Services Responses to Clarification Questions 10/06/2015 ADDENDUM #1 ITB# 2015-09-002 Fire Protection Maintenance Services Responses to Clarification Questions 10/06/2015 1. Building #222, The UPS Building, has one (1) dry Sprinkler riser, valve. (This is a

More information

standard response elo upright and pendent sprinklers (storage-density/area)

standard response elo upright and pendent sprinklers (storage-density/area) December 5, 2008 Sprinkler 13e 1. DESCRIPTION The Viking Standard Response ELO Upright and Pendent Sprinklers are thermosensitive glass bulb spray sprinklers available in several different finishes and

More information

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.0 GENERAL: Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.1 PURPOSE -The intent of this guideline is to provide the requirements for the protection

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

Storage Sprinkler. Model LP-46 (SIN) V4603, K25, Standard Response Storage Upright Sprinkler, Patent Pending

Storage Sprinkler. Model LP-46 (SIN) V4603, K25, Standard Response Storage Upright Sprinkler, Patent Pending FireLock LP-46 Low Pressure Storage Sprinkler This storage sprinkler was designed for controlling fires in single, double and multiple row rack storage of up to Cartoned, Unexpanded, Group A plastic commodities

More information

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Suppression, Detection and Signaling Research and Applications Conference SupDet 2015 March 5, 2015

More information

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Building/Business Name: Address of Property: Inspector Name: Joe Price THE CORNERSTONE 1425 NE 7TH AVENUE PORTLAND OR Date

More information

Tire Storage. Michigan Fire Inspectors Society Fall Conference

Tire Storage. Michigan Fire Inspectors Society Fall Conference Tire Storage Michigan Fire Inspectors Society Fall Conference September 15, 2016 This material, including the illustrations, represent the opinion of the author and instructor. This material is not designed,

More information

Model G5 Series Sprinkler Summary. Listings and Approvals. G4/G5 QR Gasket culus QR G4/G5 SR Gasket culus, FM SR G4/G5

Model G5 Series Sprinkler Summary. Listings and Approvals. G4/G5 QR Gasket culus QR G4/G5 SR Gasket culus, FM SR G4/G5 Bulletin 034 Rev. F Model G5 Series Sprinklers Available with Solid, Perforated, or Gasket Standard Coverage, Concealed Pendent K2.8, 4.2, 5.6, & 8.0 (40, 60, 80, & 115 metric) Product Features Model G5

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 847/866-7479 SPRINKLER PROTECTION BASICS: TYPES OF : SPRAY - standard response - quick response -

More information

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE Page 1 of 12 1. DESCRIPTION (Refer to Figures 1-6.) Viking Electric/Pneu-Lectric Double Interlocked Preaction Systems utilize a Viking deluge valve, pneumatic supervision of the automatic sprinkler system,

More information

STORAGE PRODUCT BROCHURE

STORAGE PRODUCT BROCHURE STORAGE PRODUCT BROCHURE J168 HL-22 Spec App ESFR N252 EC JL-17 ESFR Control-mode, density area standard coverage Coverage for 48 ft high buildings 14 x 14 coverage Protection of encapsulated or non-encapsulated

More information

High Ceiling Protection

High Ceiling Protection High Ceiling Protection High Ceiling Protection An Investigation of Automatic Sprinkler Protection of Buildings with Non-Storage Occupancies and High Clearances Company Confidential 2 Background New architectural

More information

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. Page 1 of 9 1. (Refer to Figures 1-3.) Viking Electric/Pneumatic Double Interlocked Preaction Systems utilize a Viking deluge valve controlled by a pneumatic actuator (E.1), normally held closed by supervisory

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE January 27, 2012 311a 1. DEsCrIpTIoN (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system.

More information

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE Page 1 of 12 1. (Refer to Figures 1-7.) Viking supervised Single-Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system piping

More information

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT 58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the

More information

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA. 319a. January 27, 2012 January 27, 2012 319a 1. DEsCrIpTIoN (Refer to Figures 1-3.) Viking Electric/Pneumatic Double Interlocked Preaction Systems utilize a Viking deluge valve controlled by a pneumatic actuator (E.1), normally

More information

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT PREPARED BY: Garner A. Palenske, P.E., and William N. Fletcher, P.E. Aon Fire Protection Engineering San Diego, CA, USA September 2015 Fire Protection

More information

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Customer Service/Sales: Tel: (215) 362-0700 / (800) 523-6512 Fax: (215) 362-5385 Series ELO-231 Upright and Pendent Sprinklers Standard Response,

More information

TECHNICAL DATA EASYPAC COMMERCIAL RISER MANIFOLD ASSEMBLIES 1-1/4-8 (DN32 - DN200)

TECHNICAL DATA EASYPAC COMMERCIAL RISER MANIFOLD ASSEMBLIES 1-1/4-8 (DN32 - DN200) Page 1 of 6 1. DESCRIPTION Viking EasyPac Commercial Riser Manifold Assemblies are available in sizes 1-1/4, 1-1/2, 2, 2-1/2, 3, 4, 6 and 8 for commercial systems. They are available with an AGF TESTanDRAIN

More information

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Customer Service/Sales: Tel: (215) 362-0700 / (800) 523-6512 Fax: (215) 362-5385 Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers

More information

TECHNICAL DATA. 32a. September 18, /4-8 (DN32 - DN200)

TECHNICAL DATA. 32a. September 18, /4-8 (DN32 - DN200) September 18, 2009 32a 1. DESCRIPTION Viking EasyPac Floor Control Riser Manifold Assemblies are available in sizes 1-1/4, 1-1/2, 2, 2-1/2, 3, 4, 6 and 8 for commercial use, in high rise buildings requiring

More information

Standard response. elo sprinklers

Standard response. elo sprinklers Page 1 of 9 1. DESCRIPTION Viking Standard Response Dry Pendent Extra-Large Orifice (ELO) Sprinklers are thermosensitive spray sprinklers suitable for use in areas subject to freezing. These dry pendent

More information

Sprinkler System Installer Level 2

Sprinkler System Installer Level 2 Sprinkler System Installer Level 2 Sprinkler System Installer Unit: A8 Electrical Principles* Level: Two Duration: 17 hours Theory: Practical: 14 hours 3 hours Overview: Upon completion of this unit the

More information

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91% 210 N CHURCH ST CHARLOTTE NC 28202-2256 MECKLENBURG COUNTY RISK ID: 32 NC99 040235 ON-SITE SURVEY: 4/1/2009 LAST UPDATE: 4/1/2009 SUMMARY Building receiving sprinkler credit: SPRINKLERED Grade: 68 Percent

More information

False Sense of Security???

False Sense of Security??? IS YOUR SPRINKLER SYSTEM GIVING YOU A FALSE SENSE OF SECURITY? Best Practices in Fire Safety An ASSE Virtual Symposium March 1 & 2, 2011 Walter S. Beattie CSP, CFPS, CSHM False Sense of Security??? Fire

More information

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems STEVEN WOLIN, VICE PRESIDENT, PRODUCT TECHNOLOGY & COMPLIANCE ANTONIO LUIS, TECHNICAL SERVICES MANAGER RELIABLE AUTOMATIC SPRINKLER

More information

Plan Submittal Checklist

Plan Submittal Checklist City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project

More information

Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description

Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description Worldwide Contacts www.tyco-fire.com Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description The Series TY-B, 5.6 and 8.0 K-factor Upright

More information

Model G5-56 Dry (SIN RA5114) K5.6 (80 metric) Concealed Dry Pendent Sprinkler

Model G5-56 Dry (SIN RA5114) K5.6 (80 metric) Concealed Dry Pendent Sprinkler UL Quick Response FM Standard Response ½ (13mm) Cover plate Adjustment Features 1. Flat cover plate with threaded attachment. 2. Solid or perforated cover plate available in chrome and white as Standard

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Pendent Sprinklers (TY2235)

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Pendent Sprinklers (TY2235)

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Fire Prevention Coffee Break Training. May 2017

Fire Prevention Coffee Break Training. May 2017 Fire Prevention Coffee Break Training May 2017 Agenda Introduction Submittals - Phelan Changes to NFPA 13 - Phelan Questions and Answers Open Forum Please welcome our S ummer Intern Charlie Poppe Small

More information

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA Page of 5. DESCRIPTION Viking EC/QREC Ordinary Hazard ELO Fusible Element Sprinkler VK535 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings to meet varying

More information

Sprinkler Standards Proposed Technical Changes

Sprinkler Standards Proposed Technical Changes Sprinkler Standards 2002-2007 Proposed Technical Changes Featuring Speaker Bob Caputo Consolidated FireProtection, Inc August 9, 2006 1 1 SPEAKER Bob Caputo Consolidated FireProtection, Inc Bob Caputo

More information

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology Warehouse Protection of Exposed Expanded Group-A Plastics with Sprinkler Technology Zachary L. Magnone, Jeremiah Crocker, Pedriant Peña Tyco Fire Protection Products, Cranston, RI, USA Abstract The focus

More information

SPRINKLER TECHNOLOGY:

SPRINKLER TECHNOLOGY: SPRINKLER TECHNOLOGY: CURRENT STATE OF THE ART AND GLIMPSE INTO THE CRYSTAL BALL James Golinveaux Senior Fellow Tyco Fire Protection Products First known patent for automatic suppression system - 1723

More information

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932) Model MBEC-14 (SIN R6932) Features 1. Designed to be installed on piping that is supported by the primary structure, not the purlins. 2. Provides Extended Coverage Ordinary & Extra Hazard protection to

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Correlating Committee on

More information

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3 Page 1 of 6 TECHNICAL DATA 1. DESCRIPTION The Viking Standard Response ELO Pendent Sprinkler is a thermosensitive glass bulb spray sprinkler available in several different finishes and temperature ratings

More information

TotalPac X Single interlock SUREFIRE system

TotalPac X Single interlock SUREFIRE system DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a trim totally preassembled, pre-wired and factory tested. All electrical and mechanical components of

More information

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 May 14, 2010 Sprinkler 85h 1. DESCRIPTION Viking Standard/QREC Light Hazard ELO Fusible Element Pendent Sprinkler VK617 is a thermosensitive spray sprinkler available in several different finishes and

More information

Model RFC Series Residential Sprinklers Flat Cover Plate, Concealed Pendent Sprinkler. Product Features. Product Description

Model RFC Series Residential Sprinklers Flat Cover Plate, Concealed Pendent Sprinkler. Product Features. Product Description Bulletin 006 Rev. K February 2017 Model RFC Series Residential Sprinklers Flat, Concealed Pendent Sprinkler Product Features as Residential Sprinklers Push-On cover plate installation Low water flow requirements

More information

Gas Station & C Store SECTION CWM Job No

Gas Station & C Store SECTION CWM Job No SECTION 21 1300 - PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract

More information

TotalPac X Firecycle III Preaction Double interlock system

TotalPac X Firecycle III Preaction Double interlock system DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a multicycling Firecycle III system trim totally pre-assembled, pre-wired and factory tested. All electrical

More information

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Inspection of Fire Sprinkler Systems NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Objective To familiarize Facility Managers with the process of routine inspection

More information

EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5

EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5 UNIT PRICING IS A "NOT TO EXCEED" PRICE EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5 Unit Pricing to perform all required Test

More information

STANDARD RESPONSE DRY PENDENT ELO SPRINKLERS TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS

STANDARD RESPONSE DRY PENDENT ELO SPRINKLERS TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS Page 1 of 9 1. DESCRIPTION Viking Standard Response Dry Pendent Extra-Large Orifice (ELO) Sprinklers are thermosensitive spray sprinklers suitable for use in areas subject to freezing. These dry pendent

More information

O-RING UPRIGHT SHIELD WRENCH FLATS WRENCH FLATS FIGURE 1 SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS

O-RING UPRIGHT SHIELD WRENCH FLATS WRENCH FLATS FIGURE 1 SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS Worldwide Contacts www.tyco-fire.com Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description The Series TY-B, 5.6 and 8.0 K-factor Upright

More information

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description Worldwide Contacts www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K and Pendent Extended Coverage Light and Ordinary Hazard General Description TYCO Series EC-11 and EC-14 Extended

More information

High-Piled Combustible Storage

High-Piled Combustible Storage High-Piled Combustible Storage Presenters: Rob Neale & Scott Adams Tuesday, September 12, 2017 1:30 PM - 4:30 PM High-piled Combustible Storage Based on the 2015 International Fire Code ICC Annual Conference

More information

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5 Page 1 of 5 1. SYSTEM DESCRIPTION Viking supervised, single interlocked preaction pre-primed systems utilize a Viking Deluge Valve (A.1) and a hydraulically pressurized automatic sprinkler system. The

More information

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA Page of 5. DESCRIPTION Viking Horizon Standard Response Flush Pendent Sprinkler VK400 is a small, flush, solder link and lever spray sprinkler. Designed for use with concealed piping, the unit is mounted

More information

Early Suppression Fast Response Sprinklers and Obstructions

Early Suppression Fast Response Sprinklers and Obstructions Early Suppression Fast Response Sprinklers and Obstructions Presented at SUPDET 2016 March 1, 2016 San Antonio, Texas Presented by: Garner Palenske, P.E. Senior Vice President Aon Fire Protection Engineering

More information

Model F1 Residential Sprinklers for Design Density of.10 gpm/ft 2

Model F1 Residential Sprinklers for Design Density of.10 gpm/ft 2 Model F1 Res s engineered for the lowest flows to meet the minimum design density of.05 gpm/ft 2 Types: 1. F1 Res 49 Pendent 2. F1 Res 49 Recessed Pendent/F1 3. F1 Res 49 Recessed Pendent/FP 4. F1 Res

More information

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description Worldwide Contacts www.tyco-fire.com Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description The TYCO Model WS Specific Application Window

More information

standard/quick response extended coverage light and ordinary hazard elo sprinklers

standard/quick response extended coverage light and ordinary hazard elo sprinklers January 27, 2012 Sprinkler 83a 1. DESCRIPTION Viking EC/QREC Light and Ordinary Hazard Extra-Large Orifice Sprinklers VK532 and VK534 are thermosensitive spray sprinklers available in several different

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

standard response elo upright sprinkler

standard response elo upright sprinkler Page of 5. DESCRIPTION The Viking Standard Response ELO Upright Sprinkler is a thermosensitive glass bulb spray sprinkler available in several different finishes and temperature ratings to meet design

More information

sprinkler vk538 (K11.2)

sprinkler vk538 (K11.2) December 6, 2012 Sprinkler 89h 1. DESCRIPTION Viking Mirage EC/QREC ELO Concealed Pendent Sprinkler VK538 is a thermosensitive solder link spray sprinkler designed for installation on concealed pipe systems

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

Today's Topics & Sustainability Themes

Today's Topics & Sustainability Themes 2012 Chicago Symposium Fire Safety Design and Sustainable Buildings: Challenges and Opportunities Research Efforts in Fire Protection Engineering are Contributing to Sustainability Goals Dan O Connor,

More information

CONSTRUCTION REQUIREMENTS

CONSTRUCTION REQUIREMENTS CONSTRUCTION REQUIREMENTS Note: The buildings on the UCCS campus are divided into two categories: General Fund and Auxiliaries. General Fund Buildings include academic and administrative functions. Auxiliary

More information