3.1 Introduction. 3.1 Introduction

Size: px
Start display at page:

Download "3.1 Introduction. 3.1 Introduction"

Transcription

1 DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional fire detection and alarm systems 3.3 Addressable fire detection and alarm systems 3.4 Categorisation of fire alarm and detection systems 3.5 Fire Alarm System Principles 3.6 Building codes for fire detection and alarm systems 3.7 Examples of fire detection and alarm systems 3.8 References Fire detection and alarm systems have several main functions: They provide a means to identify a developing fire through automatic methods. They alert building occupants to a fire condition and the need to evacuate. They commonly transmit an alarm notification signal to the fire department or other emergency response organization. They may also shut down electrical, air handling equipment or special process operations, and they may be used to initiate automatic suppression systems. The requirements depend on the anticipated fire scenario, building and use type, number and type of occupants and criticality of contents and mission. There are 3 common types of systems: conventional, addressable, and analogue addressable systems. Analogue addressable systems are not commonly used Common Abbreviations and definitions AFD EOLR FACP NAC SLC SUFMO Automatic Fire Detection End of Line Resistor Fire Alarm Control Panel Notification Appliance Circuit Signalling Line Circuit Stanford University Fire Marshal's Office Common Definitions 3.2 Conventional fire detection and alarm systems These systems are characterised by the following: They have lower initial equipment costs. Defined location of fire or alarm is not provided at the panel or central station. They can be easier to program. They have limited expansion capability. 1

2 Wiring must be installed in a supervised manner either Class A, or Class B with an EOLR. Alarm/Trouble conditions are annunciated by zone only. Inspection is required to determine the device in alarm or trouble. 3.3 Addressable fire detection and alarm systems These systems are characterised by the following: They are easier to install. More system status information is available at the panel and central station. Input and output programming is much more flexible. There is usually much more room available to expand. Each point on the SLC loop is given a unique address when installed. Alarm or trouble conditions are annunciated by a unique message for each device. 2

3 3.4 Categorisation of fire alarm and detection systems Property Protection Fire Systems These are Automatic Fire Detection (AFD) systems designed to primarily protect property categories. There are two types: P1 P2 AFD installed throughout all areas. AFD installed only in defined areas Life Protection Fire Systems These are Automatic Fire Detection (AFD) systems designed to primarily protect human life categories. There are various types. L1 Manually operated system (M) and AFD installed throughout all areas. L2 AFD installed in defined areas of higher risk of ignition, in addition to L3. L3 L4 L5 M Manually operated system (M) and AFD installed in escape routes and rooms opening into these routes. Manually operated system (M) and AFD installed in escape routes comprising circulation areas and space such as corridors and stairways. A non-prescriptive system in which protected area(s) and/or the location of detectors is designed to satisfy a specific fire risk objective (other than that of L1 to L4). System designed to be operated manually (no AFD). 3

4 3.5 Fire Alarm System Principles Manual Fire Detection Manual fire detection is the oldest method of detection. In the simplest form, a person yelling can provide fire warning. In buildings, however, a person's voice may not always transmit throughout the structure. For this reason, manual alarm stations are installed. The general design philosophy is to place stations within reach along paths of escape/egress. It is for this reason that they can usually be found near exit doors. The advantage of manual alarm stations is that, upon discovering the fire, they provide occupants with a readily identifiable means to activate the building fire alarm system. The alarm system can then serve in lieu of the shouting person's voice. They are simple devices, and can be highly reliable. 4

5 3.5.2 Automatic Fire Detectors Automatic Photoelectric Fire Detectors These are Light Scattering Smoke Detectors. The principle of using a light source and a photosensitive sensor arranged so that the rays from the light source do not normally fall onto the photosensitive sensor. When smoke particles enter the light path, some of the light is scattered by reflection and refraction onto the sensor. The light signal is processed and used to convey an alarm condition when it meets pre-set criteria. Automatic Ionization Fire Detectors This type is better at detecting the smaller amounts of smoke produced by flaming fires. An ionization chamber consists of two plates with a voltage across them, along with a radioactive source of ionizing radiation. Inside the ionization detector is a small amount (about 1/5000th of a gram) of Americium-241. This radioactive element has a half-life of 432 years, and is a good source of alpha particles. They operate on the principle of using a small amount of radioactive material to ionize the air between two differentially charged 5

6 electrodes to sense the presence of smoke particles. Smoke particles entering the ionization volume decrease the conductance of the air by reducing ion mobility. The reduced conductance signal is processed and used to convey an alarm condition when it meets pre-set criteria. Automatic Combination Fire Detectors Combination detectors contain more than one element which responds to fire. These detectors may be designed to respond from either element, or from the combined partial or complete response of both elements. An example of the former is a heat detector that operates on both the rate-of-raise and fixed-temperature principles. Its advantage is that the rate-of-rise element will respond quickly to rapidly developing fire, while the fixedtemperature element will respond to a slowly developing fire when the detecting element reaches its set point temperature. These devices either respond to more than one of the fire phenomena or employ more than one operating principle to sense one of these phenomena. Typical examples are a combination of a heat detector with a smoke detector or a combination of rate-of-rise and fixed temperature heat detector. These devices have listings for each sensing method employed Fire Notification Appliances These are fire alarm system components such as a bell, horn, speaker, light or text display that provide audible, tactile, or visible outputs, or any combination thereof. Audible Notification Appliance A notification appliance that alerts by the sense of hearing. Visible Notification Appliance A notification appliance that alerts by the sense of sight. Initiating device circuits, notification appliance circuits, and signalling line circuits are designated as either Class A or Class B, depending on their performance during nonsimultaneous single circuit fault conditions. Class A Fire Alarm Circuits These are initiating device circuits and signalling line circuits that transmit an alarm or supervisory signal, or notification appliance circuits that allow all connected devices to operate during a single open or a non-simultaneous single ground fault on any circuit conductor. When a single open circuit condition causes a trouble on the panel, all devices on the loop remain operative. 6

7 Class B Fire Alarm Circuits These are initiating device circuits and signalling line circuits that do not transmit an alarm or supervisory signal, or notification appliance circuits that do not allow all connected devices to operate beyond the location of a single open on any circuit conductor. A single open circuit condition causes a trouble on the panel and renders all devices beyond the fault inoperative. 7

8 3.5.4 Types of Fire Alarm Signals Trouble Alarm Alarm type: local sounding (beeping) on Fire Alarm Control Panel (FACP) and Annunciators. Other alarm signals: no horn/strobes sounding or flashing. Caused by: low battery, smoke detector removed, ground fault, open horn circuit, etc. Response: alarm technician responds. Supervisory Alarm Alarm type: local sounding (beeping) on FACP and Annunciators. Other alarm signals: no horn/strobes sounding or flashing. Caused by: sprinkler valve closed, duct detector activated, low-air on pre-action system. Response: fire department responds. 8

9 Fire Alarm Alarm type: all horns and strobes sounding and flashing. Required: building occupants to evacuate. Caused by: smoke detector, manual pull, water flow, duct detector, or heat detector activated. Response: fire department responds Limitation of false alarms Design guidance to minimise false alarms. Systems above 50 detectors to be soak tested False alarm categories include: 1. Unwanted alarm 2. Equipment false alarms 3. Malicious alarms 4. Good intent alarms False alarm rates should be monitored and should trigger an investigation if they exceed recommended limits. 9

10 3.5.6 What Happens When There is a Fire Alarm 4.1 Building codes for fire detection and alarm systems The minimum sound level of a sounder device should be 65 db(a) or 5 db(a) above a background noise (if lasting more than 30 seconds) and at a frequency between 500 Hz 10

11 and 1000 Hz. The maximum sound level should not exceed 120 db(a). BS 5839 Clause Sounder device cabling should be arranged so that in the event of a fault at least one sounder located within the vicinity of the control and indicating panel will remain in operation. BS 5839 Clause The maximum zone floor area should not exceed 2000 m². A person searching a zone for a fire should not have to travel more than 60 m from the zone entrance to identify the source of the fire. BS 5839 Section A person should not have to travel more than 45 m along an escape route to reach a manual call point, when the layout of the building is known. BS 5839 Clause 20.2 The centre of the element of the manual call point should be positioned 1.4 m (+/-200 mm) from floor level (unless a wheelchair user is likely to be the first person to raise the alarm, when this is applicable it should be noted on any certification). BS 5839 Clause 20.2h. Visual alarms such as beacons should always be mounted at a minimum height of 2.1 m from floor level, in a position that is likely to attract attention. BS 5839 Clause 17. Unless MICC or armoured cable to BS7846 standard is used, consideration should be given to the protection of cables against physical damage from floor level to the height of 2 m. BS 5839 Clause For areas where people are sleeping, sounder devices should produce a minimum 75 db(a) at the bed-head with all doors shut. In buildings likely to provide sleeping accommodation for the hearing impaired, consideration should be given to the incorporation of both audio and visual devices. BS 5839 Clause When mounted on a flat ceiling, smoke detection devices have an individual coverage of 7.5 m radius. However these radii must overlap to ensure there are no blind spots. Therefore individual coverage can be represented by a square measuring 10.6 x 10.6 m giving an actual coverage area of 112 m² per device. BS 5839 Clause When mounted on a flat ceiling, heat detection devices have an individual coverage of 5.3 m radius. However these radii must overlap to ensure there are no blind spots. Therefore individual coverage can be represented by a square measuring 7.5 x 7.5 m giving an actual coverage area of 56.3 m² per device. BS 5839 Clause In corridors less than 2 m wide the horizontal spacing of detectors can be increased, the area of coverage need not overlap as in the case of a room. Any corridor over 2 m wide is deemed as a room and must adhere as specified. Please note that heat detectors are not recommended for use in corridors that may be used as escape routes. Vertical shafts like lift shafts and stairways should have a device mounted within 1.5m of any opening. BS 5839 Clause Enclosed stairways should have a detector on the top of the stairway and on each main landing. BS 5839 Clause Cables used for all critical paths, i.e. detector, sounder and the mains supply should be wired in fire resistant cable with a minimum cross sectional area of 1 mm². BS 5839 Clause 26.2j. 11

12 All sounders in a building should have a similar sound, this precludes the mixing of bells and electronic sounders. BS 5839 Clause c. Disabled persons toilets require to be fitted with visual alarm devices. BS 5839 Clause The user of the system should be provided with adequate records and documentation. BS 5839 Clause On completion of each process suitable certification should be provided by the organisations responsible for each stage of the system i.e. design, installation and commissioning. BS 5839 Clause

13 4.2 Examples of fire detection and alarm systems Stanford University 13

14 14

15 15

16 16

17 17

18 18

19 4.3 References British Standards Institute (2002). BS 5839:1. Fire detection and fire alarm systems for buildings Part 1: Code of practice for system design, installation, commissioning and maintenance. British Standards Institute. Clymac Fire & Security Systems (2016). BS5839 Part 1:2002 Overview. Available at Cooper Lighting and Safety Ltd (2016). A Guide to BS5839 Part 1:2002. Menon, G. B. & Vakil, J. N. (nd). Handbook on Building Fire Codes. Available at Indian Institute of Technology Kanpur. Singapore Civil Defence Force (2016). Fire Code 2002 Handbooks. Handbook Volume 5, Purpose Group IV, V & VII (Office, Shop & Place of Public Resort) Chapter 6: Fire Fighting Systems. Available at r/download_31/file.res/hb_v5_ch6.pdf. Singapore Civil Defence Force (2016). Fire Code 2013 Handbook (Chapter 6). Available at cations%20and%20circulars/firecode2013handbook/chapter%206.pdf. Tyco Fire Protection Products (2016). Consultant s Guide for Designing Fire Detection & Alarm Systems. Available at ass%20consultants%20guide%20(lr).pdf 19

A Guide To BS Understanding the selection, spacing and siting of detectors

A Guide To BS Understanding the selection, spacing and siting of detectors World Class Leaders in Fire Detection Since 1918 A Guide To BS5839-12017 Understanding the selection, spacing and siting of detectors Welcome to A Guide to BS5839 Part 1 : 2017 from HOCHIKI EUROPE (UK)

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!

More information

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002 a guide to Fire Alarm Systems Design BS5839 Part1:2002 incorporating Amendment No.2 The Regulatory Reform (Fire Safety) Order (RRO) became law on 1 October 2006 Legally you must comply! What is the RRO?

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

A GUIDE TO FIRE DETECTION AND ALARM SYSTEMS

A GUIDE TO FIRE DETECTION AND ALARM SYSTEMS A GUIDE TO FIRE DETECTION AND ALARM SYSTEMS A Fire detection and alarm ( FD+a ) system is what most workplaces and public accessed buildings have in place. The FD+a system has two primary functions and

More information

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA Presentation Objective Compare fire alarm system design methods

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

Fire Systems Design Pocket Guide BS 5839 Part 1:2017 and CoP 0001 for Visual Alarm Devices. Fire Installers Mate. A guide to fire system design

Fire Systems Design Pocket Guide BS 5839 Part 1:2017 and CoP 0001 for Visual Alarm Devices. Fire Installers Mate. A guide to fire system design Fire Systems Design Pocket Guide BS 5839 Part 1:2017 and CoP 0001 for Visual Alarm Devices Fire Installers Mate A guide to fire system design * We make what matters work.* Every day, people depend on things

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

Hi, welcome to the topic on Fire Detection and Alarm Systems. This topic forms one of the critical knowledge areas for prospective fire safety

Hi, welcome to the topic on Fire Detection and Alarm Systems. This topic forms one of the critical knowledge areas for prospective fire safety Hi, welcome to the topic on Fire Detection and Alarm Systems. This topic forms one of the critical knowledge areas for prospective fire safety manager. As the appointed fire safety manager for a premise,

More information

EN54 Part 23 Made Easy CPD PRESENTED BY SIMON ADAMS GENT BY HONEYWELL

EN54 Part 23 Made Easy CPD PRESENTED BY SIMON ADAMS GENT BY HONEYWELL EN54 Part 23 Made Easy CPD PRESENTED BY SIMON ADAMS GENT BY HONEYWELL EN54 Part 23 Intent Standardise output levels from Visual Alarm Devices Improve designs & safety through ensuring enough light is generated

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD Fire alarm and emergency power SPRINKLER HEAD 1 Alert signal Alarm signal Fire detector Heat detector Smoke detector Smoke alarm 1. Detector locations 1. Fire detector locations (3.2.4.11) 2. Smoke detector

More information

2004 AUSTRALIAN STANDARDS UPDATE

2004 AUSTRALIAN STANDARDS UPDATE 2004 AUSTRALIAN STANDARDS UPDATE PREPARED by Peter Parsons Chairman of SAI FP-002 Chairman of ISO TC 21/SC 3 TSP Strategic Product Management Kjell Jawerth Chairman FPA Aust. TC/2 Member SAI FP-002 TSP

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Fire detection and alarm

Fire detection and alarm Fire detection and alarm Aesthetic Install all cabling and cable containment neatly and unobtrusively, meeting the highest electrical industry installation standards. Neatly lay and securely fix cables.

More information

BASIC FIRE ALARM SYSTEM

BASIC FIRE ALARM SYSTEM BASIC FIRE ALARM SYSTEM Abstract A fire alarm fundamentally to clear the premises in the occasion of event of a fire condition and afterward optionally to report the fire to the best possible powers. A

More information

Required vs. Non-required Fire Protection Systems. Dan Austin Chief Fire Code Consultant/State Fire Protection Engineer

Required vs. Non-required Fire Protection Systems. Dan Austin Chief Fire Code Consultant/State Fire Protection Engineer Required vs. Non-required Fire Protection Systems Dan Austin Chief Fire Code Consultant/State Fire Protection Engineer What are we going to cover? What makes a system required? What to do when a non-required

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

Design of Fire safety in Multi Occupancy Residential Accommodation

Design of Fire safety in Multi Occupancy Residential Accommodation Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability

More information

TrueAlarm ES Analog Sensing

TrueAlarm ES Analog Sensing TrueAlarm ES Analog Sensing UL, ULC, CSFM Listed; FM Approved* Features TrueAlarm addressable sensor base with 520 Hz sounder TrueAlarm sensor bases with 520 Hz tone require a TrueAlarm photoelectric,

More information

11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies

11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies 11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies Visible Signals Agenda 1. Physics 2. Installation Considerations

More information

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5 Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance

More information

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Smoke Detector Activation of any smoke detector shall start the alarm verification mode. Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,

More information

Date Issued: December 14, 2017 Revision: 2.1

Date Issued: December 14, 2017 Revision: 2.1 2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

SMOKE ALARM SUMMIT Technological Advances in Smoke Alarms Richard Roberts Honeywell Fire Safety Industry Affairs Manager

SMOKE ALARM SUMMIT Technological Advances in Smoke Alarms Richard Roberts Honeywell Fire Safety Industry Affairs Manager Technological Advances in Smoke Alarms Richard Roberts Honeywell Fire Safety Industry Affairs Manager Agenda Smoke Detection in Model Codes Importance of Smoke Alarms Single Technology Smoke Alarms Photoelectric

More information

LOG BOOK & CERTIFICATES

LOG BOOK & CERTIFICATES M+48 LOG BOOK & CERTIFICATES. FIRE ALARM SYSTEM SUMMARY: FIRE ZONE INFORMATION ZONE NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

LEARNING SPECIAL HAZARD DETECTION TYPES

LEARNING SPECIAL HAZARD DETECTION TYPES LEARNING SPECIAL HAZARD DETECTION TYPES JUNE 2013 COPYRIGHT CLIMATEC SPECIAL HAZARDS DETECTION TYPES EXPLAINED STAGE ONE DETECTION - ACTIVE AIR SAMPLING\\INCIPIENT AND IN- VISIBLE SMOKE STAGE AIR SAMPLING

More information

InstrumentationTools.com

InstrumentationTools.com Author: Instrumentation Tools Categories: Fire & Gas System Overview of Fire/Smoke/Flame/Heat/Gas Detectors Fire Detectors Fire detectors are available for residential, commercial, and industrial use.

More information

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 8-24 ZONE CONVENTIONAL FIRE ALARM PANEL LOG BOOK & CERTIFICATES

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 8-24 ZONE CONVENTIONAL FIRE ALARM PANEL LOG BOOK & CERTIFICATES 8-24 ZONE CONVENTIONAL FIRE ALARM PANEL LOG BOOK & CERTIFICATES Approved Document No: GLT.MAN-113 It is recommended that this LOG BOOK be maintained by the responsible person(s) on site, who should ensure

More information

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation)

FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation) Fire Safety Technical Guide FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation) UCL Fire Alarm Standards & Specific

More information

False Alarm Management

False Alarm Management False Alarm Management This document is intended only for fire system professionals who are already experienced in the selection and positioning of fire detectors. Whenever you apply any False Alarm Management

More information

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are

More information

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 714.522.2246 Corporate Headquarters 800.845.6692

More information

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures 161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means

More information

Residential Fire Protection

Residential Fire Protection Chapter 13: Residential/Farm Fires Residential fires have become a significant problem throughout the United States. The National Fire Protection Association (NFPA) estimates that residential fires in

More information

Multi-Point Peripherals

Multi-Point Peripherals UL, ULC Approved* Multi-Point Peripherals TrueAlarm CO Sensor Bases for Smoke, Heat, and Photo/Heat Sensors using IDNet Communications Features Fig 1: TrueAlarm CO Sensor Base with Sounder (shown with

More information

5 Key Stages to Risk Assessment

5 Key Stages to Risk Assessment 5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

The 2013 National Fire Alarm and Signaling Code

The 2013 National Fire Alarm and Signaling Code ARE YOU A MEMBER OF AFAA? WHY SHOULD YOU BE A MEMBER BECAUSE YOUR BUSINESS IS IMPORTANT James Mongeau The 2013 National Fire Alarm and Signaling Code 1 NFPA 72 Organization Be*er organiza2on Easier to

More information

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 7240-19 First edition 2007-08-15 Fire detection and alarm systems Part 19: Design, installation, commissioning and service of sound systems for emergency purposes Systèmes de

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

NY Fire Safety Institute Coordinator of Fire Safety & Alarm Systems F-80

NY Fire Safety Institute Coordinator of Fire Safety & Alarm Systems F-80 Established 1995 Preparing the future High Rise Building Fire Safety Directors Presents the FDNY Coordinator of Fire Safety and Alarm Systems Homeless Shelters (Premise Related) Certificate of Fitness

More information

Following are the systems proposed as per NBC & Local Fire Authority:

Following are the systems proposed as per NBC & Local Fire Authority: 1. OBJECTIVES AND STRATEGIES OF THE FIRE PROTECTION DESIGN This report describes the design parameters, system requirements of fire protection system for mixed occupancy (Assembly + Business) building

More information

THE BASICS OF FIRE ALARM PLAN REVIEW

THE BASICS OF FIRE ALARM PLAN REVIEW THE BASICS OF FIRE ALARM PLAN REVIEW Art Shaw A Shaw & Associates, LLC. ashaw@arthurshaw.com 231.838.3269 Fire Protection System Plan Reviewer FP000006 NFPA Certified Plans Examiner 02-0005 NFPA Certified

More information

Frequently Asked Questions

Frequently Asked Questions Frequently Asked Questions For Life Safety System Designers, Building Owners, and Installers P/N 85000-0395 Introduction Provisions in NFPA 72 (The National Fire Alarm and Signaling Code) now require low

More information

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 PAT E N T System 88 COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 Pg 1 of 12 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description

More information

Fire Command Keypad. XR5 User s Guide

Fire Command Keypad. XR5 User s Guide Fire Command Keypad XR5 User s Guide Silencing an Alarm While the fire alarm horns, strobes, or sirens are sounding use one of the following methods to silence the alarm depending on which type of keypad

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS CONTENTS 1. System Overview 2. User responsibilities 3. First Line controls and indications 3.1 Logging on to the fire alarm system 3.2 Checking system status

More information

SOUTH AFRICAN NATIONAL STANDARD

SOUTH AFRICAN NATIONAL STANDARD ISBN 978-0-626-19281-5 SOUTH AFRICAN NATIONAL STANDARD Fire detection and alarm systems for buildings System design, installation and servicing Published by Standards South Africa 1 dr lategan road groenkloof

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

Design Guidelines Fire Safety in New and Refurbished Buildings

Design Guidelines Fire Safety in New and Refurbished Buildings Design Guidelines Fire Safety in New and Refurbished Buildings Introduction All major new or refurbishment projects must comply with the Technical Standards (Scotland) Regulations as a matter of course.

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Maritime Studios Pendennis Rise Falmouth TR11 4FB Carried out by: Date: October 2015 Review Date: October 2016 Les Carter CMIOSH Health & Safety Consultant Mobile 07831 636751, Email

More information

Consultant Specification AGILE Wireless Fire Detection System

Consultant Specification AGILE Wireless Fire Detection System Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...

More information

Safety Engineering. Fire Protection Systems and Life Safety Systems

Safety Engineering. Fire Protection Systems and Life Safety Systems Safety Engineering Fire Protection Systems and Life Safety Systems Introduction 2 A key aspect of fire protection is to identify a developing fire emergency in a timely manner, and to alert the building's

More information

LifeAlarm Fire Alarm Controls

LifeAlarm Fire Alarm Controls UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

Division 28 - Electronic Safety and Security

Division 28 - Electronic Safety and Security Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm

More information

FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL GK FIRE & SECURITY LTD, UNIT 1 GREBE RD, PRIORSWOOD IND EST, TAUNTON, TA2 8PZ

FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL GK FIRE & SECURITY LTD, UNIT 1 GREBE RD, PRIORSWOOD IND EST, TAUNTON, TA2 8PZ BS5839-1 : 2013 FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL Forward It is recommended that this logbook be maintained by a relevant member of the premises management, to ensure that every entry

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

Fire Alarm Wiring. Circuit types, styles and limitations

Fire Alarm Wiring. Circuit types, styles and limitations Fire Alarm Wiring Circuit types, styles and limitations What we will cover Types Classes Notification Appliance Circuits (NAC) Initiating Device Circuits (IDC) Signaling Line Circuits (SLC) Class A, B,

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

Firefighting operations on fire alarm panels F5-04 GD

Firefighting operations on fire alarm panels F5-04 GD DESIGNER S GUIDE Firefighting operations on fire alarm panels F5-04 GD Introduction Alarm system devices Alarm system types A fire alarm system consists of one or more devices and/or control mechanisms

More information

Canadian Fire Alarm Association (CFAA)

Canadian Fire Alarm Association (CFAA) An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems Canadian Fire Alarm Association (CFAA) CAN/ULC - S524-01 STANDARD FOR THE INSTALLATION OF FIRE ALARM SYSTEMS Installation

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

Frequently Asked Smoke Alarm Questions

Frequently Asked Smoke Alarm Questions Frequently Asked Smoke Alarm Questions Why should my home have smoke alarms? Most fire deaths are caused by smoke not flames. Most fire deaths and injuries occur between midnight and 8 a.m. when people

More information

The EN54 Part 2 and 4 Fire System

The EN54 Part 2 and 4 Fire System Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire

More information

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Prepared by: EH&S The probability of casualties and major structural damage increases when fire

More information

University of Maryland FIRE EVACUATION PLAN

University of Maryland FIRE EVACUATION PLAN University of Maryland FIRE EVACUATION PLAN PLAZA PARKING GARAGE POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your building will immediately

More information

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number: 109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr

More information

FIRE DETECTION & ALARM SYSTEM BASICS

FIRE DETECTION & ALARM SYSTEM BASICS FIRE DETECTION & ALARM SYSTEM BASICS. 8 Fernwood Road Florham Park, New Jersey 07932 Siemens Building Technoloiges, Inc. ii Table of Contents Fire Detection and Alarm System Basics 1 General System Types

More information

GENERAL FIRE SAFETY TERMS & DEFINITIONS

GENERAL FIRE SAFETY TERMS & DEFINITIONS UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification

More information

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Conventional Fire System BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Contents Contents 1. INTRODUCTION... 3 1.1 Purpose...3 1.2 Definitions....3 Premises Management...

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building

More information

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

Multi-Point Peripherals

Multi-Point Peripherals Multi-Point Peripherals UL, ULC, CSFM Listed; FM Approved* TrueAlarm CO Sensor Bases for Smoke, Heat, and Photo/Heat Sensors using IDNet Communications Features TrueAlarm addressable CO sensor bases contain

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

16721 FIRE ALARM AND DETECTION SYSTEMS

16721 FIRE ALARM AND DETECTION SYSTEMS 16721 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information