COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

Size: px
Start display at page:

Download "COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III"

Transcription

1 SECTION DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this section. B. The Fire Alarm system shall be furnished and installed as an extension of the existing Fire Alarm system. The existing system shall be expanded as required. C. Refer to Mechanical Division 23 specifications and drawings for responsibilities, sequence of operation and for coordination requirements. Refer specifically to M1.01 Smoke Control Matrix and the Smoke Control Rational Analysis Report for detailed Smoke Control system (SCS) functional information and provide accordingly. D. All Fire Alarm wiring shall be in conduit. Refer to for conduit and cable requirements. Conduit is not shown on Fire Alarm plans. Coordinate conduit installation requirements with the Division 26 contractor. E. Equipment installation and testing shall meet the project commissioning requirements. Refer to , General Commissioning Requirements. Installing Contractor is to provide a test plan sequence for startup, functional testing, blank forms to be used, integration sequence schedule for review/approval by Owner and Commissioning Agent. This submittal and commissioning sequence is to integrate with the Master Schedule. 1.2 SCOPE AND RESPONSIBILITY A. The scope of this section shall be carried out by a qualified contractor certified and trained by the manufacturer to work on the existing Notifier system. B. Furnish and install all devices, wiring, and programming to connect the new fire alarm devices to the existing Facility Fire Alarm system. Provide a complete automatic fire detection and alarm system including control panel, detectors, annunciators, manual stations, alarm devices, wiring, components, relays, appurtenances and accessories, and all wiring and connections to devices furnished by others. Coordination with divisions 23 and 26 is required to assure that system operates correctly. C. Related work Furnished and Installed by Division 26: 1. Section Security & Communication Conduit/Raceway System 2. Section Vibration and Seismic Controls for Security Systems 3. All 120 VAC electrical power. DIGITAL ADDRESSABLE FIRE ALARM SYSTEM

2 1.3 CODE REFERENCES A. Applicable Publications: The Fire Alarm system shall be furnished and installed in accordance with the following: California Building Code (CBC) (2012 IBC as amended by CA). 2. Title 24 CCR, Part California Electrical Code (CEC) (2011 NEC as amended by CA) National Fire Protection Association Standard 72 (CA Amended). 4. Incorporate California Code of Regulations, Title 19 as applicable. 5. Local Codes and Authorities Having Jurisdiction requirements. 6. See list of all applicable codes sheet CP0.00. B. All equipment shall be UL listed for the intended purpose. C. All equipment shall be CSFM listed for the intended purpose by the California State Fire Marshal's Office. D. Furnish a copy of the license for the master electrician who will supervise the installation of the fire alarm system. 1.4 SYSTEM DESCRIPTION A. The existing Fire Alarm panel is located in Central Control and is a Notifier Voice evacuation system. All new devices shall be UL listed with the panel and incorporated into the system. B. Miscellaneous points shall be monitored or controlled by an addressable module located within three feet of the device controlled as required by NFPA C. Fire Alarm supplier shall furnish and install fire fighter's smoke override panels as required by code and for each area utilizing a smoke control system. The system provider shall refer to and coordinate this system completely with the division 23 specifications and plans specifically M1.01 Smoke Control Matrix. D. Furnish and install addressable inputs and all required terminations to monitor the fire pump for the fire suppression system in accordance with NFPA edition. Provide a monitoring module for Pump On/Running, Phase/AC Loss, and Phase Reversal at a minimum with bid. Final location will be determined in the Automatic Sprinkler System deferred submittal. E. Furnish and install addressable output modules to open and close all smoke/fire dampers and dampers related to the SCS functionality. Coordinate all damper locations with the Division 23 plans. F. Each address shall have a unique label indicating the building (or area), dayroom, and device type. G. The system shall be capable of performing time base control functions and shall contain the ability to be programmed for a holiday schedule. H. The system shall be capable of operating both intelligent/analog and non-addressable devices. DIGITAL ADDRESSABLE FIRE ALARM SYSTEM

3 I. Duct detectors shall shut down ( AH OFF ) their respective unit when they sense smoke in the unit. J. The Kitchen, Day Reporting, and classroom areas will sound evacuation signals independently. K. The system shall function as follows when an area detector, duct detector, manual station or water-flow switch operates: 1. Activate audible and visual notification devices in the building of alarm. 2. Annunciate audibly and visually on Fire Alarm Control Panels (FACP) and Fire Alarm Annunciators (FAA) in the building of alarm, central control, fire command center, and front lobby of Administration building. 3. Display individual detector and/or zone number on alphanumeric display with user defined message on Fire Alarm Control Panels and Fire Annunciators in the building of alarm, central control, fire command center, and front lobby of Administration building. 4. Printed record on existing FACP printer in central control. 1.5 SMOKE CONTROL A. Provide sequence of operation as specified in the Mechanical Division 23 documents. B. Control relays shall be mounted within three feet for the controlled appliance as required by NFPA C. Provide a fully functional Underwriters Laboratory UUKL listed Smoke Control Panel (SCP) where indicated. D. Where smoke/fire dampers are provided on units less than 2000 CFM, furnish and install an addressable module to shut the unit down. Coordinate fully with all trades. E. System shall monitor and annunciate positive confirmation of exhaust fan activation and presence of power as defined by the IBC. F. Furnish and install a switch for each smoke zone at the area Fire Alarm Control Panel to by-pass the smoke control system. G. Refer to SE4.01 for Smoke Control Panel (SCP) drawing. Locate smoke control panel as indicated on plans. Refer detail 9/SE3.01 for proposed SCP location. H. The SCP shall control and annunciate as a unit each smoke zone in accordance with the exception of CBC AUXILIARY FUNCTION A. Furnish and install an addressable monitor device to monitor a dry contact on the area Stand-by Emergency Generator Automatic Transfer Switch. B. Furnish and install an addressable control relay at each AC unit to drop the condenser coil in addition to any modules required for smoke control. DIGITAL ADDRESSABLE FIRE ALARM SYSTEM

4 C. When normal electrical power is lost and the building is transferred to emergency power, turn off all AC condensers in the affected area. Fully coordinate with all other trades. D. Provide addressable relay output modules to control smoke exhaust fans and related dampers. E. Provide input modules to monitor sail switches associated with the smoke exhaust fans, exhaust fans, and HVAC units used in the smoke control sequences. F. Furnish and install a red alarm bell and red flashing light suitable for exterior mounting for each sprinkler riser at each area. 1.7 SUBMITTALS A. Basic Submittals: Provide submittals as required by Section Common Work Results for Electronic Safety and Security and division 1. B. Special Submittal Requirements: In addition to the contract requirements for submittals provide the following: 1. Riser diagram indicating integration with other systems. Identify all major components, interconnections, and subsystems. 2. Identify spare capacity of each circuit either by schedule, device identification, or notation. 3. Battery calculations for each panel. 4. Voltage drop calculations for each signal circuit using the following model: a. All device loads will be treated as if at the end of the circuit. b. No circuit shall have a voltage drop of more than 10%. c. Identify circuit current, voltage drop, wire size, and percentage drop. 5. Provide letter confirming coordination for smoke, exhaust, and related damper controls occurred with the related Division 23 documents. C. Provide approvals and comments from California State Fire Marshal s Office. D. Furnish a copy of the UUKL listing for the smoke control equipment. 1.8 SYSTEM INTEGRATION A. HVAC: Integrate the fire alarm with the HVAC system by means of dry contacts and addressable devices. B. Sprinkler System: Monitor ALL Fire Sprinkler Flow and Supervisory devices provided and installed by others. The Automatic Fire Sprinkler System is a deferred submittal. The Fire Alarm contractor shall include associated cost to monitor a sprinkler riser flow and tamper switch for each of the new areas (G, H, J, and K). Final location will be determined in the deferred submittal. PART 2 - PRODUCTS DIGITAL ADDRESSABLE FIRE ALARM SYSTEM

5 2.1 FIRE ALARM SYSTEM A. ACCEPTABLE MANUFACTURERS 1. Notifier 2.2 FIRE ALARM CONTROL PANEL A. The main control panel is existing and shall remain. Provide additional FACP s where shown on the plans. B. Supervision: Dynamic supervision of system electronics, wiring, detection devices, and software shall be provided by the control system. C. Ground fault: Ground fault detection shall be provided for all circuits. D. Power: The control panel shall operate from a two wire 120 VAC supply with internal 24 VDC backup battery. E. Analog Operation: The control panel shall measure and adjust within UL guidelines the sensitivity of analog smoke detectors. F. Supervision: The control shall report the failure of a device's transmitting component(s), open or shorted, on an intelligent/analog detection circuit. G. Device number: The controls shall report, by specific device number, any device removed from an intelligent/analog detection circuit and all other devices shall continue to function. H. New Alarms: New unacknowledged alarms and troubles shall be distinctively displayed visually differentiated from previous alarms and troubles. I. System Reset: It shall not be possible to reset the system until all off normal indications have been acknowledged. J. Logic: Control functions shall be assigned on the basis of system initiation patterns of detection devices such as "anding" zones, counting zones, counting devices, "anding" groups, and "anding" types of detection devices. K. Addressing: Sprinkler water flow switches, air duct smoke detectors, tamper switches, OS & Y valves, manual stations, and thermal detectors shall be equipped with a unique address. L. Signal Circuits: Provide notification appliance circuits capable of providing 1.5 amp at 24 VDC per circuit as required to power evacuation signals. M. The addressable Signaling Line Circuit shall be so constructed that all devices shall continue to communicate even with a single wire fault. (Style 6 - Class A operation) N. The facility fire alarm system shall meet the requirements for a Proprietary Fire Alarm System as defined by NFPA 72, 2013 edition with California Amendments. O. Provide automatic detectors with built in relays where indicated on the plans or required. DIGITAL ADDRESSABLE FIRE ALARM SYSTEM

6 P. Provide signaling line circuits for communication with addressable devices as required by the number of devices Q. Additional circuits for operation of DC audible devices, leased line, or city tie, shall be provided by a Signal Module. R. Provide a controllable relay output module for control of air handling units and other building life safety functions. S. Cabinet: Provide a NEMA 1 cabinet to house all controls, power supplies, motherboards, relays, and accessories. 2.3 FIRE ALARM ANNUNCIATOR A. Furnish and install Fire Alarm Annunciator where shown on the plans. B. Each annunciator shall provide alarms as displayed on the main Fire Alarm Control Panel and duplicate the command keys. 2.4 ALARM INITIATING DEVICES A. All intelligent/analog smoke and thermal detectors shall contain an integral alarm LED. B. The intelligent/analog smoke detector shall be a plug-in, twist/lock unit which shall be capable of removal from or installation into its base with one hand. C. Furnish and install protective guards on ceiling spot smoke detectors located in inmate accessible areas. Unit shall be the Shaw-Perkins Protection Steel Smoke Detector Guard model #SDG or equal, be UL listed and constructed of heavy-duty double wall 16 gauge steel. Holes shall be staggered between the double walls. Guard shall be secured with pin-torx style security fasteners. D. The intelligent thermal detectors shall be of the rate compensated fixed temperature type. The intelligent thermal detectors shall be individually annunciated on the control panel. The intelligent thermal detectors shall contain an integral alarm lamp. The intelligent detector's address shall be set by electronic means only, no mechanical means such as programming pins, dipswitches or rotary dials shall be used. E. The intelligent manual fire station shall be non-coded and shall operate on any addressable detection circuit. The intelligent manual fire station shall be individually annunciated on the control panel. Provide key activation option in inmate areas. Operation of station requires the use of a special key. F. The air duct detector shall operate on a cross-sectional air sampling principle to overcome stratification and the skin effect. The air duct detector shall consist of a standard intelligent/analog ionization detector mounted in an air duct sampling assembly and sampling tube that protrudes across the duct of the ventilating system. The air duct detector shall retain the features of the intelligent/analog or non-addressable ionization detector, and be installed in the DIGITAL ADDRESSABLE FIRE ALARM SYSTEM

7 ventilating duct as indicated in the manufacturer's instructions. Provide an air duct detector for all HVAC units with indicated as 2000CFM or larger. G. Furnish and install addressable modules for remote operation of fans and devices. H. Miscellaneous relays: Where fire alarm relay module contacts are not large enough to handle the control current, provide larger relays and contactors mounted in NEMA 1 boxes. 2.5 ALARM INDICATING DEVICES A. The alarm speakers shall be UL listed with the existing voice system. B. Alarm visual strobes shall be clear with a flash rate not to exceed two (2) flashes per second, not less than 1 flash per second throughout the voltage range of the appliance. Source intensity not to exceed 1000 candela. C. All strobe appliances shall be synchronized so that all strobes visible at a single point flash simultaneously. D. Furnish and install a protective cover for each strobe or audio visual device located in inmate areas. 2.6 FIRE DOOR HOLDERS A. Furnish and install magnetic door holders where indicated on the plans. Coordinate installation and special requirements with all trades. 2.7 TRANSIENT SURGE SUPPRESSION A. Acceptable manufacturers are as follows: 1. Northern Technologies Incorporated 2. DITEK 3. PolyPhaser Corporation 4. Transtector B. Suppression: Provide surge protection for wiring that leaves the building. Provide Northern Technologies series PLP-s units matched to the voltage of the circuit suppressed. The suppressors shall have a peak pulse power dissipation rating of 10 joules each mode, minimum. C. System Power: Provide surge protection for 120 power connections both inside and outside the building. Devices shall be equal to Northern Technologies TCS-HWR series rated for the power of the circuit suppressed. The suppressors shall have a peak pulse power dissipation rating of 300 joules L-N, minimum. Units shall provide a dry contact monitored by the security system and identified by electrical panel circuit number. DIGITAL ADDRESSABLE FIRE ALARM SYSTEM

8 2.8 CABLING AND WIRE A. Acceptable manufacturers: 1. Liberty Wire and Cable 2. Eastman Wire & Cable 3. West Penn Wire 4. Belden 5. Carol 6. General Cable 7. Clifford of Vermont, Inc. B. Wire Size: Furnish and install sufficient wire gauge to limit voltage drop to 5%. C. Initiating device wiring: Furnish and install data grade fire alarm cabling to all addressable devices equal to West Penn D975 #18 twisted shielded pair. AQ224 for wet rated use. D. Alarm Indicating Appliance Circuits: Wiring for signal circuits, power, and miscellaneous controls shall be a minimum of #14 THWN. E. Cable shall be wet rated when placed in conduit buried under ground. 2.9 FABRICATION A. Assemble and Test: Assemble all smoke detectors and annunciating devices so that they are addressed according to the prints. B. Device Identification: Identify smoke detectors and annunciating devices with the loop address assigned according to the prints. Label should be visible after detector has been placed into the base. PART 3 - EXECUTION 3.1 COORDINATION A. Preliminary Coordination: Coordinate all required embeds, block-outs, and construction as required by the plans. B. Coordination with the Authority Having Jurisdiction (AHJ): Provide all documentation required and obtain all applicable permits to expand the existing Notifier Voice Evacuation Fire Alarm System. 3.2 INSTALLATION A. The cost of any required changes required by compliance with codes shall be covered by the contractor. B. Wire: Install in accordance with all applicable codes. All wire shall be installed in conduit. DIGITAL ADDRESSABLE FIRE ALARM SYSTEM

9 C. Panels: Control and other panels shall be mounted with sufficient clearance for observation, service, and testing. All fire alarm control panels must be clearly marked for easy identification. D. Junction Boxes: All fire alarm junction boxes must be clearly marked for easy identification. E. Flexible Connectors: Flexible connectors shall be used for all devices mounted in suspended layin ceiling panels. Flexible connections shall be securely supported by the building structure and limited to a maximum of three feet. F. Continuous Grounding: All conduit, mounting boxes, junction boxes and panels shall be securely hung and fastened with appropriate fittings to insure positive grounding throughout the entire system. G. Shared Raceway: No wiring other than that directly associated with fire alarm detection, alarm or auxiliary fire protection functions shall be permitted in fire alarm conduits. H. Splices: Wiring splices are not acceptable between devices. Electrical boxes provided are to be used as pull points, not junction points. I. Wire Quality: All wiring shall be checked and tested to insure that there are no grounds, opens or shorts. J. Listing: All wiring and raceways shall be listed for the intended installation and installed in strict accordance with the National Electric Code as required by the conditions of where it is installed. This includes but is not limited to ratings for riser, plenum, or wet installations. K. Coordination: Fully coordinate all equipment installation with division 23 and division 26 contractors. L. Licensed Electrician: All fire alarm systems shall be installed under the supervision of a C-10 License. M. Seismic: The entire system shall be installed to meet the seismic requirements for the area. 3.3 SOFTWARE A. For the modified Fire Alarm Control Panel, furnish to the owner an electronic copy of the programming and all point lists. B. Furnish Adobe Acrobat PDF file detailing all passwords required. 3.4 SPARES A. Turn over to the owner devices in their original shipping boxes with the part number and description of each device contained. B. Furnish to the owner, two spares of each device installed. C. Furnish to the owner a key for each panel lock and 5 keys for keyed pull stations. DIGITAL ADDRESSABLE FIRE ALARM SYSTEM

10 3.5 FIELD QUALITY CONTROL A. Test and Certification: The contractor shall perform all electrical and mechanical tests required by the equipment manufacturer's certification form. In addition, they shall measure and adjust each of the detectors to the sensitivity setting appropriate to the area. This must be performed with the detector at its installed location under normal environmental conditions. Bench settings are not acceptable. All test and report costs shall be in the base price. Technicians shall complete the NFPA 72 fire alarm certification report and submit copies to the owner and the engineer. B. Final Test: Final tests and inspection shall be held in the presence of architect's representatives and to their satisfaction. The contractor shall supply personnel and required auxiliary equipment for this test without additional cost. Final test to be witnessed and approved by the AHJ. END OF SECTION DIGITAL ADDRESSABLE FIRE ALARM SYSTEM

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101

More information

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Fire alarm system specification for multiple tenant retail buildings

Fire alarm system specification for multiple tenant retail buildings Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:

More information

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Smoke Detector Activation of any smoke detector shall start the alarm verification mode. Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,

More information

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,

More information

The following information shall become and form part of the contract documents.

The following information shall become and form part of the contract documents. October 4, 206 To: Attention: Re: All Bidders All Bidders JCBE Gymnasium HVAC Upgrades BC#: 206433 Edmonds Project No.: BHM6090 All bidders, The following information shall become and form part of the

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 283111 A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

OKLAHOMA STATE UNIVERSITY

OKLAHOMA STATE UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY ADDRESSABLE FIRE ALARM SYSTEM STANDARD Revised 6/15 Revised: 6/15 Contact(s) Implementation Date Comments Gerald Petre, EHS June 2016 Review and Update Page 1 1.1 GENERAL

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract.

1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract. PART 1 - GENERAL SECTION 28 31 11 STANDARD 1.1 FIRE ALARM SYSTEM REQUIREMENTS A. Contractor Requirements 1. The fire detection and alarm system (including the conduit) shall be a separate bid item and

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

STATE OF NORTH CAROLINA

STATE OF NORTH CAROLINA STATE OF NORTH CAROLINA DEPARTMENT OF ADMINISTRATION STATE CONSTRUCTION OFFICE Fire Alarm GUIDELINES AND POLICIES 2011 Instruction to Designers: 1. Designers for State projects involving fire alarm systems

More information

Changes to this Division since the last issuance are indicated with yellow highlighted text.

Changes to this Division since the last issuance are indicated with yellow highlighted text. Table of Contents 28 10 00 ELECTRONIC ACCESS CONTROL AND INTRUSION DETECTION... 2 A. GENERAL... 2 B. DESIGN REQUIREMENTS... 2 C. CONSTRUCTION REQUIREMENTS... 3 28 20 00 ELECTRONIC SURVEILLANCE... 4 A.

More information

Environmental Health & Safety

Environmental Health & Safety Environmental Health & Safety Oklahoma State University ADDRESSABLE FIRE ALARM SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 13852- PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

16721 FIRE ALARM AND DETECTION SYSTEMS

16721 FIRE ALARM AND DETECTION SYSTEMS 16721 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 DIGITAL, ADDRESSABLE FIRE ALARM PART 1 - GENERAL 1.1 GENERAL A. This Section includes the following: 1. Fire-alarm control panel. 2. Manual fire-alarm boxes. 3. Smoke detectors. 4. Heat

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS HVAC Upgrades Phase 2 Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Materials and installation for fire alarm systems upgrades..2 Audible signal devices..3 End-of-line devices..4 Sustainable

More information

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO Prepared For: Public Schools Facilities Authority State of New Mexico 2019 Galisteo, Suite

More information

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Alarm, Water Flow Alarm & Signaling Systems Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving

More information

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General

More information

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 RELATED SECTIONS: Refer to Section 15300 for requirements regarding fire protection systems. 1.2 SCOPE OF SECTION: This section contains the requirements for equipment and installation

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

SECTION FIRE ALARM

SECTION FIRE ALARM SECTION 16740 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125 as the fire extinguishing agent

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125

More information

16721 FIRE ALARM AND DETECTION SYSTEMS

16721 FIRE ALARM AND DETECTION SYSTEMS 16721 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

SECTION GENERATOR PARALLELING CONTROLS

SECTION GENERATOR PARALLELING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION ADDRESSABLE FIRE ALARM SYSTEM

SECTION ADDRESSABLE FIRE ALARM SYSTEM SECTION 16723 ADDRESSABLE FIRE ALARM SYSTEM 1 PART 1 GENERAL 1.1 DESCRIPTION A. This section outlines the requirements for the installation, programming and configuration of Addressable Fire Alarm System

More information

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS SECTION 280500 COMMON WORK RESULTS FOR SAFETY AND SECURITY PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 28 work shall, in addition to all division 1 specification sections, comply with all of

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

WINDOW & HVAC REPLACEMENT PEMBERTON TOWNSHIP BOE REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5450E

WINDOW & HVAC REPLACEMENT PEMBERTON TOWNSHIP BOE REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5450E SECTION 283111 DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary General Conditions of the

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

FIRE ALARM AND DETECTION SYSTEMS

FIRE ALARM AND DETECTION SYSTEMS 283100 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

B. Special Documentation Requirements. C. Materials and methods of Construction

B. Special Documentation Requirements. C. Materials and methods of Construction DIVISION 13 SPECIAL CONSTRUCTION 13100 LIGHTNING PROTECTION 1. Lightning Protection: Each building shall be considered individually to determine the necessity for lightning protection. The building location,

More information

SENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification

SENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification This sample specification is for a duress only stand-alone SCAN system using SR series receivers with zone-within-a-zone and graphic display. SECTION 17 DURESS SYSTEM PART 1.00 - GENERAL 1.01 DESCRIPTION

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY

DIVISION 28 ELECTRONIC SAFETY AND SECURITY 281300 - ACCESS CONTROL A. General DIVISION 28 ELECTRONIC SAFETY AND SECURITY At the beginning of the project, schedule a meeting with the Facilities Access/Maintenance Coordinator with questions and concerns.

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 46 00 SPEC WRITER NOTES: 1. The A/E must obtain a copy of the VA ENGINEERING GUIDE FOR FIRE PROTECTION DESIGN which provides fire alarm system criteria that

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 283112 DIGITAL ADDRESSABLE FIRE ALARM SYSTEM VOICE NOTIFICATION PART 1 GENERAL 1.1 SUMMARY NETWORK FIRE ALARM CONTROL PANEL (NODE) A. Network fire alarm control panels shall include all features

More information

Brighton Area Fire Authority

Brighton Area Fire Authority 615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL SECTION 1 GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing FK-5-1-12 as the fire extinguishing agent and with a

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening. DIVISION 8 OPENINGS SECTION 08 33 23 PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead coiling counter fire doors. 1.2 RELATED SECTIONS A. Section 05500 - Metal Fabrications: Support framing and framed opening.

More information

Control/Communicator

Control/Communicator Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality

More information

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM SECTION 2 8 31 00 FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Request For Proposal apply to this Section.

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION (13730) - INTRUSION DETECTION

SECTION (13730) - INTRUSION DETECTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: SECTION 28 16 00 (13730) - INTRUSION DETECTION 1. Intrusion Detection Sensors 2. Signal Equipment 3. System Controls 4. Alarm Displays 5. Alarm Indicating

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

Pakenham Branch Library Section MacFarlane Street MULTIPLEX FIRE ALARM SYSTEM Project No Page 1 of 12

Pakenham Branch Library Section MacFarlane Street MULTIPLEX FIRE ALARM SYSTEM Project No Page 1 of 12 Project No. 16563.001 Page 1 of 12 1. General 1.1. WORK INCLUDED 1.1.1. Section 26 05 01 GENERAL INSTRUCTIONS FOR ELECTRICAL SECTIONS. 1.1.2. Section 26 05 04 SUBMITTALS/SHOP DRAWINGS. 1.1.3. Section 26

More information

DONALD H. BERG, ARCHITECT

DONALD H. BERG, ARCHITECT DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:

More information

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE SUPERVISION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SUPERVISION OF ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS FIRE ALARM AND DETECTION SYSTEMS The Fire Alarm

More information

Brown University Revised April 12, 2013 Facilities Design & Construction Standards

Brown University Revised April 12, 2013 Facilities Design & Construction Standards SECTION 28 31 10 - FIRE ALARM SYSTEMS, SMOKE ALARMS, CARBON MONOXIDE PART 1 - GENERAL 1.1 SUMMARY: A. Section Includes: 1. Fire Alarm and Detection Systems 2. Single Station Smoke Alarms 3. Single Station

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS 2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 2400CA - CLEAN AGENT CHEMICAL SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION ADDRESSABLE FIRE ALARM SYSTEM

SECTION ADDRESSABLE FIRE ALARM SYSTEM SECTION 16720 - ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

DESIGN & CONSTRUCTION GUIDELINES

DESIGN & CONSTRUCTION GUIDELINES Facilities Management 4202 E. Fowler Avenue, OPM 100 Phone: (813) 974-2625 Design & Construction Tampa, Florida 33620-7550 Website: usf.edu/fm-dc DESIGN & CONSTRUCTION GUIDELINES DIVISION 28 ELECTRONIC

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

A. This Section covers fire alarm systems, including initiating devices, notification appliances, controls, and supervisory devices.

A. This Section covers fire alarm systems, including initiating devices, notification appliances, controls, and supervisory devices. SECTION 28 31 11 ADDRESSABLE FIRE ALARM SYSTEM 1. GENERAL 1.1 SUMMARY A. This Section covers fire alarm systems, including initiating devices, notification appliances, controls, and supervisory devices.

More information

Fire - Rescue. November 2016

Fire - Rescue. November 2016 Fire - Rescue Fire Alarm and Central Station Monitoring Plan Submittal Guidelines November 2016 Plan Submittal Guidelines are provided based on the 2015 International Fire Code, Policies, and Local Amendments.

More information

A. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system.

A. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system. SECTION 283111 - PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: INFORMATION PROJECT ADDRESS:

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED

More information

Unified Fire Authority - Fire Prevention Bureau

Unified Fire Authority - Fire Prevention Bureau Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance

More information

IN2 Digital, Addressable Fire-alarm System

IN2 Digital, Addressable Fire-alarm System Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Digital, Addressable Fire-alarm System Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

FIRE ALARM DETECTION SYSTEM

FIRE ALARM DETECTION SYSTEM SECTION 16721 FIRE ALARM DETECTION SYSTEM ****** ***** **** *** ** * ** *** **** ***** ****** NOTE TO SPECIFIER: Edit for addressable systems. Use non-addressable systems at existing facilities only when

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1 CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device

More information

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5 Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series

More information