Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation.

Size: px
Start display at page:

Download "Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation."

Transcription

1 Fire Safety nstallation nstructions Model MMB- Main ontrol Board OPERATON The SEMENS Model MMB- board in each MXL System controls operations and monitors input device identity, network communication, and operator commands that are entered through the MKB-/ Annunciator/ Keyboard. The MMB- also provides two analog loop driver circuits. Each ALD loop can be used as lass B or lass A and can monitor and control up to 60 intelligent devices as well as programmable device relays. The MMB- module is field programmable. t is equipped with two programmable lass B (Style Y) or lass A (Style Z) notification appliance circuits. Each circuit can activate up to. amps of audible or visual notification appliances. The module also has auxiliary relays for the external monitoring of ommon System Alarm, ommon System Trouble, and ommon Supervisory conditions. The ommon Supervisory relay is user programmable. The MMB- includes a built-in battery charger and transfer circuit. The charger is microprocessor controlled and incorporates a brownout circuit that switches the System to standby batteries during the loss or reduction of the primary source A. The System can display the real time battery voltage, the A voltage, and the charger current on the MKB-/ alphanumeric display. t also has a amp, VD output that powers ZM- modules. NSTALLATON Always remove power before installation. nstalling the MMB- Board Unpack the MMB-. nspect the module, looking for such things as integrated circuits (s) not firmly seated in their sockets, bent pins, connectors not properly installed, dirt, packing material on the board, etc. The installation kit consists of the following: Four #0 nuts Two resistors Battery cable with wire To install the MMB-:. Place the MMB- with the mounting bracket over the four standoffs on the MBR-MP mounting plate in the upper left portion of the backbox (See Figure ).. Secure in place using the hardware provided. Be sure the screws and nuts are tight, as they provide the earth ground connection for the MMB-. Siemens Building Technologies, nc. 8 Fernwood Road Florham Park, New Jersey 079 Siemens Building Technologies, Ltd. Kenview Boulevard Brampton, Ontario L6T E N P/N

2 Figure nstalling the MMB- F BATTERY P P B NA 0A MPS-6 MPS- B NA P P0 S7 S D00P TB P BATTERY P POWER TO MOM- AMP MAX. TB LOOP TB LOOP P A TO MOM- DO NOT USE MNET PRNTER PROGRAMMER P P6 F MOM- AMP 0 MOM- 0 F MPS-6 8 AMP MMB- (MXL Rev. 9 and higher) 6 K K P GND FAULT DSONNET P6 (MXL Rev. 8 and lower) 0 Figure MMB- Main Board P7 EXPANSON P8 TO ANN- OFF P7 F TAMPER SWTH ON AMP ZM- POWER NA NA SPV TRBL ALR ZM- POWER

3 ONFGURATON The MMB- has two jumpers jumper P for MNET and jumper P7 for Real Time clock which must be set for proper operation. Refer to Figure for the location of the jumpers. MNET To configure the MNET for either Style or Style 7 operation, set jumper P on the MMB-. f the MMB- has no remote PSR-s or is connected to remote PSR-s with a Style MNET, set the jumper to position S. f the MMB- is connected to remote PSR-s with a Style 7 MNET, set the jumper to S7 and install a NET-7 (Refer to the NET-7 nstallation nstructions, P/N -099). Real Time lock The second jumper on the MMB- is P7 which must be set for the real time clock to operate properly. Move the jumper to the on position to provide backup battery power to the real time clock. Note: The real time clock requires MXL/MXLV firmware Revision 9.0 or higher to operate. nternal Wiring To complete the MMB- internal wiring connections, follow the steps below, skipping those that do not apply to your particular MXL System.. Main Power onnections Primary power for the MMB- is provided by the MPS-6/-6W or MPS-/-W. Both of these mount in the lower right-hand corner of the MXL enclosure. Follow the instructions below for the appropriate power supply. MPS-6/-6W nstall the MPS-6/-6W (See MPS-6/-6W nstructions, P/N -090/W). With the A mains disconnected, connect the MPS-6/-6W power cable to P of the MMB-. Be sure that the jumper assembly is installed in P of the MMB-. f this jumper is not installed, the MMB- will detect a permanent A fail or indicate auxiliary power voltage is low. MPS-/-W nstall the MPS-/-W (See MPS-/-W nstructions, P/N /W). Remove and discard the jumper assembly installed in P of the MMB-. Disconnect the A mains. onnect the MPS-/-W power cable to P of MMB-.. Battery Power onnection The MMB- kit includes a battery cable (wiring harness). Use the harness to connect the V backup batteries to P of MMB-.. MOM- Optional Module ard age There are two connections between the MMB- and the MOM- board. a. The first is the V power connection. P provides backward compatibility with the MMB- and should only be used when replacing an MMB-. P is limited to amps. The MMB- allows the use of either an MPS-6/-6W or an MPS-/-W. TB terminals and supply V to the MOM- with a maximum of 6 amps (MPS-6/-6W) or amps (MPS-/-W) available. This output must be derated by the total current drawn from NA (.A max), NA (.A max) and the ZM-, power (A max) on the MMB-. onnect TB, and on the MMB- to TB6, and on the MOM. Refer to Figure for the wiring diagram. MOM- TB6 _ P7 _ TB AWG MN 6A MAX (MPS-6) A MAX (MPS-) 8- VD NOT POWER LMTED MMB- Figure MOM- V onnection P6 ABLE P/N SUPPLED WTH MOM-

4 Figure ZM- Supervised Auxiliary Power lass B Wiring Figure ZM- Supervised Auxiliary Power lass A Wiring Refer to Wiring Specification for MXL, MXL-Q and MXLV Systems, P/N revision 6 or higher, for additional wiring information. b. The second provides V power and the communication interface. onnect the 8-wire ribbon cable from P7 on the MOM- to P6 on the MMB-. Field Wiring (Refer to Figure ) The screw terminals for the field wiring circuits are located on the left and right sides of the MMB-. They are labeled TB through TB. The field wiring circuits available are: ZM- power Analog device loop Analog device loop Notification appliance circuit (Styles Y and Z) Notification appliance circuit (Styles Y and Z) ommon alarm relay ommon supervisory relay ommon trouble relay Style RS-8 Network (MNET) The following sections describe each circuit type and give the related instructions. Refer also to the wiring diagrams. Auxiliary lass A V Power Auxiliary power is available on TB, terminals 9 through. The circuit is power limited per NE Article 760 and is rated at amp, 8- VD. This power supply is for use with the ZM- Remote onventional Zone module. Figure shows lass B wiring; Figure shows lass A wiring. lass B wiring can be used to obtain the maximum of 0 ZM-s. Each lass B wire run can support a maximum of 0 ZM-s, ohms max. Multiple lass B power connections can be used provided you do not exced the rating above (0 ZM-s max and ohms per run max). For example, you could have four individual lass B power runs, for a total of 0 devices (6,,, and 7 ZM-s), each of the four runs not exceeding ohms resistance. Analog Device Loops and (TB and TB) These two loops each support up to 60 analog type devices. To install a device for lass B, refer to Figure 6 and the electrical specifications. To install a device for lass A, refer to Figure 6 and the electrical specifications. Electrical Specifications for the Analog Device Loops. Electrical ratings: SUPERVSORY: 0 VD peak, 0mA max ALARM: 0 VD peak, 0mA max (60 devices in alarm). All wiring must be in accordance with Article 760 of NE or the local building codes. Refer to Figure 6.

5 . Only the list of devices in Table may be used. A maximum of 60 devices may be connected to a single loop.. No end of line device is required.. Both circuits are power limited per NFPA 70, NE. Each detector, or group of detectors, requires a twowire circuit of 8 AWG minimum thermoplastic fixture wire, enclosed in a conduit, or 8 AWG limited-energy shielded cable without conduit, if permitted by local building codes. 6. Total circuit resistance must not exceed 00 ohms. Maximum capacitance: 0.µF between loop and loop 0.8µF between loop and chassis 0.8µF between loop and chassis 7. T-tapping is NOT allowed on lass A loops. ompatible Devices TABLE OMPATBLE DEVES Base nstallation nstructions ZM- P/N ZM-B6 P/N -09- FP-/FPT-* D-60/60H D-60A/60AH D-60B/60BH L-/H L-A/AH L-B/BH LP-/LPT- LP-(d) LP-** LP-**(d) LT- DB-S with DB-ADPT DB- P/N P/N DB-S, DB-XRS P/N DB-S, DB-XRS P/N AD- AD-XR P/N P/N -09- DB-S, DB-XRS P/N DB-S, DB-XRS P/N AD- AD-XR P/N P/N -09- DB-S, DB-XRS P/N AD-LP AD-XRLP P/N -09- P/N -09- DB-S, DB-XRS P/N AD-LP AD-XRLP P/N P/N -09- DB-S P/N M S-0/0 P/N M S-0B/0B P/N M S-MB6 P/N T R-B6/B6D/B6R P/N -09- T R-B6M P/N * The FP/FPT- is only compatible with MXL/MXLV Rev. 0.0 or greater firmware. **The LP- is only compatible with MXL/MXLV Rev. 8.0 or greater firmware. When the SG-M is configured, the DUT application must be selected when the device is used in an air duct housing or in a spot duct application. Refer to Wiring Specification for MXL, MXL-Q and MXLV Systems, P/N revision 6 or higher, for additional wiring information. Figure 6 Wiring the Analog Loops

6 Notification Appliance ircuits (TB, - and TB, -8) (Refer to Figure 7). These circuits are for notification appliances only, NFPA 7 Local. For NFPA 7 Municipal Tie or NFPA 7 Leased Line, use the Model SM-.. All wiring must be in accordance with Article 760 of NE or local building codes.. Both notification appliance circuits are power limited to NFPA 70 and NE.. Electrical ratings: Supervisory: 8 to VD, ma max Alarm: 8 to VD,.A max. End of line device: P/N Line Resistance: Must not exceed ohms max 7. For a list of ompatible Notification Appliances, refer to P/N TB Refer to Wiring Specification for MXL, MXL-Q and MXLV Systems, P/N revision 6 or higher, for additional wiring information. LASS B WRNG (STYLE Y) SUPERVSED POWER LMTED 8, 7, 6, _ NOTFATON APPLANES EOL*.K /W, *EOL DEVE P/N LASS A WRNG (STYLE Z) SUPERVSED POWER LMTED 8, 7, 6, TB _ EOL*.K /W NOTFATON APPLANES, _ *EOL DEVE P/N Figure 7 Wiring Notification Appliance ircuits (Polarity Shown n Supervisory) 6

7 ommon Alarm Relay The common alarm relay changes state whenever a fire alarm is detected. The relay is rated A, 0 VD/0 VA resistive. See Figure 8 for the wiring connections. Use only with power limited/lass circuits. ommon Supervisory Relay The supervisory relay changes state whenever a supervisory trouble is detected. t may be used for alternate functions if programmed by SG-M for them. The relay is rated A, 0 VD/0 VA resistive. Refer to Figure 8 for wiring connections. Use only with power limited/lass circuits. ommon Trouble Relay The trouble relay changes state whenever a System trouble is detected. The relay is rated for A, 0 VD/0 VA resistive. Refer to Figure 8 for the wiring connections. Use only with power limited/lass circuits. Refer to Wiring Specification for MXL, MXL-Q and MXLV Systems, P/N revision 6 or higher, for additional wiring information. RATNGS A, 0 VD/0 VA RESSTVE OLS ARE SUPERVSED WHEN DE-ENERGZED ONTATS ARE SHOWN N NORMAL STATE Figure 8 MMB- Relay onnections 7

8 Style Network (MNET) The MMB- provides a Style MNET network for connection to remote power supplies (PSR-) and annunciators (MO-/7, R-/F). See Figure 9 for wiring instructions. f a Style 7 network is required, a NET-7 must be used. Refer to the NET-7 nstallation nstructions, P/N -099, for wiring diagrams. FUSE REPLAEMENT N THE MXL SYSTEM F F F F MPS-6 nput Battery Reversal ZM- Power FUSE RATNGS V Output (TB, terminals and ) 8A, AG, Normal Blow 0A, AG, Normal Blow A, AG, Normal Blow A, AG, Normal Blow NOTE: The fuses are located on the upper left and right corners of the MMB- board. Refer to Wiring Specification for MXL, MXL-Q and MXLV Systems, P/N revision 6 or higher, for additional wiring information. Figure 9 Style Network (MNET) P/N

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION Fire Safety Installation Instructions Model SMB- Main Control Board OPERATION The SIEMENS Model SMB- board in each MXL-IQ System controls operations and monitors input device identity, network communication,

More information

Fire Safety. Installation Instructions. Model RCC-2/R and RSE-1 Remote Control Centers OPERATION INTRODUCTION INSTALLATION

Fire Safety. Installation Instructions. Model RCC-2/R and RSE-1 Remote Control Centers OPERATION INTRODUCTION INSTALLATION Fire Safety Installation Instructions Model RCC-/R and RSE- Remote Control Centers INTRODUCTI The SIEMENS Model RCC-/R Remote Command Center (See Figure ) provides the option to remotely annunciate and

More information

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11 Fire Safety Installation Instructions Model ADBX11 Audible Base INTRODUCTION Model ADBX11 The SIEMENS Model ADBX11 Audible Base consists of a standard Series 11 base combined with an audible device. All

More information

Installation Instructions Model DLC

Installation Instructions Model DLC Installation Instructions Model DLC Device Loop Card INTRODUCTION OPERATION The SIEMENS Model DLC Device Loop Card is the interface for connection of FireFinder-XLS smoke detectors, manual stations, monitor

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS MXL-IQ Advanced Life Safety System ENGINEER AND ARCHITECT SPECIFICATIONS FirePrint Application Specific Fire Detection Capacity for up to 240 Intelligent Analog Detectors Expandable Up to a Stand Alone

More information

Installation Instructions Model HZM

Installation Instructions Model HZM Installation Instructions Model Remote Conventional Zone Module INTRODUCTION The Model from is an intelligent device that connects a single zone of conventional devices to a DLC (FireFinder-XLS System)

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Fire Safety Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

ANNUNCIATOR FIXED MODULE

ANNUNCIATOR FIXED MODULE 12 Clintonville Road Northford, CT 06472 Phone: 203-484-7161 Fax: 203-484-7118 THE ANNUNCIATOR FIXED MODULE Installation Manual for the AFM-16ATF and AFM-32AF Annunciator Modules Document # 15970 3/27/95

More information

Operating Instructions MXL Multi-Line Keyboard/Display Panel

Operating Instructions MXL Multi-Line Keyboard/Display Panel Operating Instructions MXL Multi-Line Keyboard/Display Panel Local Mode Operation TRODUCTION When the MXL Keyboard/Display Panel is installed in a control panel, the components are behind a locked door.

More information

Advanced Protection System

Advanced Protection System MXL-IQ Advanced Protection System FirePrint Application Specific Detection Capacity for up to 240 Intelligent Analog Detectors Expandable Up to a Stand Alone System Capacity of 998 Input and Output Points

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

4100U City and Relay Cards Installation Instructions

4100U City and Relay Cards Installation Instructions 4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

Marine Fire Detection System Manual MXL Control Panel

Marine Fire Detection System Manual MXL Control Panel Marine Fire Detection System Manual MXL Control Panel US Coast Guard Approved Certificate No. (Cert No:6.002/22/7) Reference ULI File No. S522 Siemens Building Technologies, Inc. Fire Safety 8 Fernwood

More information

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

LDM Series Lamp Driver Modules For Graphic Annunciation and Control 12 Clintonville Road Northford, CT 06472 (203) 484-7161 FAX: (203) 484-7118 LDM Series Lamp Driver Modules For Graphic Annunciation and Control Used with the System 500, System 5000, AM2020/AFP1010 and

More information

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Fire Safety FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

Fire Safety. Installation Instructions Model NIM-1W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION NIM-1W

Fire Safety. Installation Instructions Model NIM-1W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION NIM-1W Fire Safety Installation Instructions Model NIM-W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION The SIEMENS Model NIM-W provides a new communication path for the following uses:

More information

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels GE Security EST Life Safety & ommunications onventional Small Building Solutions Overview The FireShield Plus fire alarm family consists of 3, 5 and 10 zone conventional fire alarm s, an integrated DAT/Dialer,

More information

Fire Safety. Installation Instructions Model PSR-1 Remote Power Supply INTRODUCTION. Figure 1 PSR-1 Remote Power Supply

Fire Safety. Installation Instructions Model PSR-1 Remote Power Supply INTRODUCTION. Figure 1 PSR-1 Remote Power Supply Fire Safety Installation Instructions Model PSR- Remote Power Supply Figure PSR- Remote Power Supply INTRODUCTION The SIEMENS Model PSR- (See Figure ) is a microprocessor controlled remote power supply

More information

Installation Instructions Model SSD-C-REM

Installation Instructions Model SSD-C-REM Installation Instructions Model SSD-C-REM Remote System Status Display with Control ON ALARM SUPERVISORY SECURITY TROUBLE AUDIBLES SILENCED INTRODUCTION The SIEMENS Model SSD-C-REM is an optional FireFinder

More information

E-FSC. Conventional Fire Alarm Control Panels. Standard Features. Overview

E-FSC. Conventional Fire Alarm Control Panels. Standard Features. Overview Edwards Signaling atalog u Fire Alarm ontrol Panels E-FS onventional Fire Alarm ontrol Panels Overview The E-FS fire alarm family consists of 3, 5 and 10 zone conventional fire alarm s, an integrated DAT/Dialer,

More information

Conventional Fire Alarm Systems

Conventional Fire Alarm Systems Kidde atalog u Small Building Fire Alarm Solutions Technology that saves lives onventional Fire Alarm Systems FX-10RD, FX-10R, FX-5RD, FX-5R OA 6230 Overview Kidde brand conventional fire alarm systems

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control

More information

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual Replace the following pages of Document Number 50734 (I56-993-01/D770-19-00), Revision B with the corresponding revised

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

MXL-IQ CONTROL PANEL. Operation, Installation, and Maintenance Manual. Siemens Industry, Inc. Building Technologies Division Florham Park, NJ

MXL-IQ CONTROL PANEL. Operation, Installation, and Maintenance Manual. Siemens Industry, Inc. Building Technologies Division Florham Park, NJ MXL-IQ CONTROL PANEL Operation, Installation, and Maintenance Manual Siemens Industry, Inc. Building Technologies Division Florham Park, NJ P/N 315-093624-13 Siemens Building Technologies, Ltd. Fire Safety

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately

More information

Remote NAC Power Supply D7038

Remote NAC Power Supply D7038 Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC. M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

Fire Safety. Installation Instructions Model CSM-4 Controllable Signal Module OPERATION INSTALLATION

Fire Safety. Installation Instructions Model CSM-4 Controllable Signal Module OPERATION INSTALLATION Fire Safety Installation Instructions Model SM- ontrollable Signal Module OPERATIO The Model SM- ontrollable Signal Module has two fully supervised, programmable circuits. The outputs supply two lass B

More information

Installation Instructions Model CDC-4

Installation Instructions Model CDC-4 Installation Instructions CDC-4 Conventional Card INTRODUCTION The SIEMENS CDC is a card that allows conventional detectors to be used on the FireFinder-XLS system. It provides four Class or Class B conventional

More information

June 10, 2002 DF C S2424

June 10, 2002 DF C S2424 GENERAL www.firelite.com The Fire Lite FIRE COMMAND 25/50X is a state-of-theart Emergency Voice Evacuation Control Panel (VECP), with significant technological enhancements that set it apart from other

More information

Harrington Signal HS-3100/3200 Fire Alarm Control Unit

Harrington Signal HS-3100/3200 Fire Alarm Control Unit HARRINGTON SIGNAL INC. FIRE ALARM Harrington Signal HS-3100/3200 Fire Alarm Control Unit Installation Manual Revision 2 January 2009 Document # LT-2000HAR Table of Contents 1.0 Technical Information...

More information

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC. M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp

More information

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL400ULM Multi-Output Access Control Power Supply Charger R AL400ULM - Multi-Output Access Control Power Supply/Charger Rev. 072500 Overview: The AL400ULM multi-output access control

More information

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX Page 1 of 10 Model 10807800 January 2014 ACCURATE ELECTRONICS INC PO BOX 1654 97075-1654 8687 SW HALL BLVD 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 WWW.ACCURATE.ORG Practice Section 10807800

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

IDP-Zone-6 Six Zone Interface Module

IDP-Zone-6 Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS IDP-Zone-6 Six Zone Interface Module BEFORE INSTALLING If the modules will be installed in an existing operational system, inform the operator and local authority

More information

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS MODEL XR5FC/XR5SL COMMAND PROCESSOR INSTALLATION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and, if not installed

More information

FX Intelligent Analog Fire Alarm Control Panel. Installation and Operation Manual

FX Intelligent Analog Fire Alarm Control Panel. Installation and Operation Manual Advanced Life Safety Solutions Advanced Life Safety Solutions FX-2000 Intelligent Analog Fire Alarm Control Panel Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 Fax: 905-660-4113 U.S.A.

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

I NSTALLATION M ANUAL

I NSTALLATION M ANUAL MR-2900 Fire Alarm Control Unit I NSTALLATION M ANUAL September 2009 Document #: LT-2010 Rev.2 WARNING : This manual contains information on limitations regarding product use and function and information

More information

Multiplex Eight Input Remote Modules

Multiplex Eight Input Remote Modules Multiplex Eight Input Remote Modules 1.0 Introduction These instructions cover the installation of the D7042/D7042B Eight Input Remote Modules in a fire system supervised by an FPD-7024 Fire Alarm Control

More information

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EMC COMPATIBILITY UNPACKING...

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EMC COMPATIBILITY UNPACKING... ZXA / ZXE FIRE ALARM CONTROL PANEL MORLEY-IAS Table of Contents 1 INTRODUCTION...1 1.1 NOTICE... 1 1.2 WARNINGS AND CAUTIONS... 1 1.3 NATIONAL APPROVALS... 2 1.4 EMC COMPATIBILITY... 2 2 UNPACKING...3

More information

General Routing Interface

General Routing Interface General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: 2002.

More information

I TS-12 1 Y K DO WHAT THEY DON T. Model. INSTALLATION lnstrljctlons. FIRE BURGLARY lnstrumentsrn INC.

I TS-12 1 Y K DO WHAT THEY DON T. Model. INSTALLATION lnstrljctlons. FIRE BURGLARY lnstrumentsrn INC. Model I TS-12 1 INSTALLATION lnstrljctlons Y K FIRE BURGLARY lnstrumentsrn INC. 50 Engineers Road, Hauppauge, N.Y. 11788 516-582-6j61 800-645-5430 DO WHAT THEY DON T.......................................................................................

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

TotalPac 3 Deluge, Electric release Self-contained system

TotalPac 3 Deluge, Electric release Self-contained system (Optional) DESRIPTION This TOTALPA 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and mechanical

More information

NETWORK FIRE ALARM CONTROL PANEL. Features

NETWORK FIRE ALARM CONTROL PANEL. Features NETWORK FIRE ALARM CONTROL PANEL FX-2009-12N Description FX-2009-12N in a BB-5008 enclosure. Mircom s FleX-Net TM FX-2009-12N Network Fire Alarm Control Panel offers modular components to meet a wide variety

More information

Notification Appliance Circuit Module

Notification Appliance Circuit Module Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS SXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 4 Zones Expandable to 8 Zones Microprocessor Based Control Factory Programmed Field Configurable 2 Style Y Notification

More information

These instructions detail procedures to follow in order to avoid damage to equipment.

These instructions detail procedures to follow in order to avoid damage to equipment. D326A, D334A, D339A Point Contact Modules Installation Guide 1.0 Notice These instructions are for the installation of the D326A, D334A and D339A Point Contact Modules in an analog system controlled by

More information

The ACM-8R Annunciator Control Module

The ACM-8R Annunciator Control Module 12 Clintonville Road Northford, CT 06472 203-484-7161 FAX: 203-484-7118 The Annunciator Control Module For the System 500, System 5000, AFP-200, AM2020, AFP1010 and SFP-1024 Fire Alarm Control Panels Document

More information

Series. Access Power Controllers. Installation Guide

Series. Access Power Controllers. Installation Guide Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse

More information

Installation Instructions Model ABHW-4S

Installation Instructions Model ABHW-4S Installation Instructions Model ABHW-4S Intelligent Audible Base for Sleeping Area with 520Hz Low Frequency Sounder Introduction Application note The Model ABHW-4S audible base from Siemens Industry, Inc.

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual P/N 315-049353-1 Siemens Building Technologies Fire Safety TABLE OF CONTENTS INTRODUCTION... 1 CONTROL PANEL

More information

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES POWER SUPPLY AND BATTERY CHARGER AC AND DC STATUS INDICATORS ENOUGH POWER TO SUPPORT UP TO 3 MAGLOCKS OR ELECTRIC STRIKES PLUS REQUIRED

More information

PS914 Power Supply. 900-KL Keylock (optional) Page BB Battery Backup (optional) Page 3

PS914 Power Supply. 900-KL Keylock (optional) Page BB Battery Backup (optional) Page 3 F1! DANGER 44487056 These instructions cover the following parts: PS914 Power Supply Installation Instructions! DANGER: To avoid risk of electric shock, turn off A power before installing or servicing

More information

MPC-6000 / MPC-7000 / RND-2

MPC-6000 / MPC-7000 / RND-2 MPC-6000 / MPC-7000 / RND-2 Fire Alarm System Control Unit Installation, Operation and Maintenance Manual Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600

More information

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep. 140 58th St. Brooklyn, NY Power Supply/Chargers Installation Guide Models Include: eflow4n/eflow4nx - 4 amp @ 12VDC or 24VDC eflow4n8/eflow4nx8 eflow4n8d/eflow4nx8d - 4 amp @ 12VDC or 24VDC - 4 amp @ 12VDC

More information

Conventional Releasing Control Panel

Conventional Releasing Control Panel s Data Sheet Fire Safety Products Conventional Releasing Control Panel Pre-Action Deluge Agent-Releasing Fire System Model TXR-320 Remote configurable Up to two (2) hazard areas Operable with the following:

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

/5121/5122 TrueAlert Power Supply Installation Instructions

/5121/5122 TrueAlert Power Supply Installation Instructions 4100-5120/5121/5122 TrueAlert Power Supply Installation Instructions Introduction This publication provides an overview of the features, specifications, and capabilities of the TrueAlert power supplies

More information

Cerberus TM PRO Fire Safety System A comprehensive fire-protection system

Cerberus TM PRO Fire Safety System A comprehensive fire-protection system s Data Sheet Fire Safety & Security Products Cerberus TM PRO Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the

More information

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment. LED Driver Module Installation Guide 1.0 Notice These instructions are for installing Radionics LED Driver Module in a fire alarm system controlled by Radionics D8024 or D10024 Fire Alarm Control Panels

More information

MXL/MXLV Enclosuress & Equipment Models: MME-3, MBR-MP, MLE-6, MBR-3MP, MDL-1, MDB-1, MDG-1, MHD-1, MHD-2, MHD-3, MHD-4

MXL/MXLV Enclosuress & Equipment Models: MME-3, MBR-MP, MLE-6, MBR-3MP, MDL-1, MDB-1, MDG-1, MHD-1, MHD-2, MHD-3, MHD-4 MXL/MXLV Enclosuress & Equipment Models: MME-3, MBR-MP, MLE-6, MBR-3MP, MDL-1, MDB-1, MDG-1, MHD-1, MHD-2, MHD-3, MHD-4 ENGINEER AND ARCHITECT SPECIFICATIONS Enclosure & Door Package (MME-3) Standard Size

More information

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER Installation Instructions Model AD-HR Air Duct Monitoring Housing INTRODUCTION The SIEMENS Model AD-HR is a sampling tube, air duct monitoring housing. When used with a compatible smoke detector, smoke

More information

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING GENERAL The VEC 25/50 is a state-of-the-art, compact, stand-alone or slave Emergency Voice Evacuation Control. The VEC 25/50 is offered in a self-contained, cost-effective design and includes a 25 Watt,

More information

LifeAlarm Fire Alarm Controls

LifeAlarm Fire Alarm Controls UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity

More information

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels D9412GV2/D7412GV2 EN Approved Applications Compliance Guide Control Panels D9412GV2/D7412GV2 Approved Applications Compliance Guide Listings and Approvals Listings and Approvals Fire UL Underwriters Laboratories

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

The TC-4F. Time Control Module C P/N 15972:C ECN For the Sensican 2000 Fire Alarm Control Panel

The TC-4F. Time Control Module C P/N 15972:C ECN For the Sensican 2000 Fire Alarm Control Panel 12 Clintonville Road Northford, CT. 06472 (203) 484-7161 FAX:(203) 484-7118 The TC-4F Time Control Module For the Sensican 2000 Fire Alarm Control Panel Document # 15972 3/27/95 Revision C P/N 15972:C

More information

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation

More information

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

D326A/D334A/D339A. Installation Instructions. Point Contact Modules D326A/D334A/D339A EN Installation Instructions Point Contact Modules D326A/D334A/D339A Installation Instructions 1.0 Description Notice Use these instructions to install the D326A, D334A, and D339A Point

More information

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control File: S8485 Wiring Diagram This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control Panel. The operation of this product is intended for indoor

More information

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT SPEC SHEET Simple Expansion Solutions Expand your DMP panel options with a wide array of expansion modules. Add supervised Class B burglary zones. Connect non-powered burglary or fire type devices for

More information

July 14, 1999 DF C-100.

July 14, 1999 DF C-100. www.firelite.com GENERAL The Fire Lite FIRE COMMAND 25/50 is a state-of-theart, compact, stand-alone or slave Emergency Voice Evacuation Control Panel (VECP). The FIRE COMMAND 25/50 is offered in a self-contained,

More information

ACCURATE ELECTRONICS INC

ACCURATE ELECTRONICS INC ACCURATE ELECTRONICS INC Page 1 of 7 Model 108078 2 Sept 09 WWW.ACCURATE.ORG PO BOX 1654 97075-1654 8687 SW Hall Blvd 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 Practice Section 108078 Rev A

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS PXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 12 Zone System Expandable to 32 10 Amp Base Power Supply Multiple Power Supplies Available - Local or Remote 4 Notification

More information

Desigo TM Fire Safety System A comprehensive fire-protection system

Desigo TM Fire Safety System A comprehensive fire-protection system s Desigo TM Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the 252- point and 504-point systems One (1) or (2)

More information

XR10/XR20 Command Processor Panels Installation Guide

XR10/XR20 Command Processor Panels Installation Guide XR10/XR20 Command Processor Panels Installation Guide 10/26 Zone Burglary/Fire/Access Control Panels with Built-in Communicator LT-0229 (5/97) MODEL XR10/XR20 COMMAND PROCESSOR INSTALLATION GUIDE FCC NOTICE

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL THE GAMEWELL COMPANY PN: 71981 60 PLEASANT STREET ISSUE A ASHLAND, MA 01721 3/22/2001 This page intentionally blank ii

More information

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual FA-1000 SERIES Microprocessor-Based Fire Alarm Control Panel Installation and Operation Manual LT-600 Rev. 19 May 2017 Table of Contents 1.0 Introduction 8 1.1 About this Manual... 8 1.2 About the FA-1000...

More information

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014 January 16, 2014 Release Control Panel 290a 1. Description The Viking VFR400 is a microprocessor based releasing control panel for use on preaction, deluge, Surefire, Firecycle multicycle sprinkler systems,

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

Installation Guide. XR5FC and XR5SL

Installation Guide. XR5FC and XR5SL Installation Guide XR5FC and XR5L Commercial Fire Panels MODEL XR5FC/XR5L COMMAND PROCEOR INTALLATION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and, if not installed and

More information

IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL

IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL INSTALLATION & OPERATION MANUAL GAMEWELL P/N 71810 60 PLEASANT STREET ISSUE 3, 10/04/2000 ASHLAND, MA 01721 FIRMWARE VER. 7 THIS PAGE INTENTIONALLY

More information