This Addendum includes the following changes and clarifications to the Contract Documents:

Size: px
Start display at page:

Download "This Addendum includes the following changes and clarifications to the Contract Documents:"

Transcription

1 August 17, 2018 IFB#: IFB Closing on: August 28, 2018 ADDENDUM NO. FIVE TO THE CONTRACT DRAWINGS AND SPECIFICATIONS FOR THE REFERENCED PROJECT, DATED JULY 11, 2018, AS PREPARED BY GRIMM + PARKER ARCHITECTS, 123 EAST MAIN STREET, 2 ND FLOOR, CHARLOTTESVILLE, VA and as previously amended, This Addendum includes the following changes and clarifications to the Contract Documents: CHANGES TO SPECIFICATIONS: ITEM NO. 1: MODIFY: TABLE OF CONTENTS Add the following entry to the Table of Contents: IT CABLE SYSTEM ITEM NO. 2: SECTION EMERGENCY GENERATOR Entire section Section attached. ITEM NO. 3: SECTION EMPTY CONDUIT SYSTEM Entire section Section attached. ITEM NO. 4: ADD: SECTION IT CABLE SYSTEM Section attached CHANGES TO DRAWINGS: ITEM NO. 5: SHEET M101 FIRST FLOOR PART A & SECOND FLOOR HVAC PLANS

2 Shenandoah County Sheriff s Office Addendum No. 5 Page 2 of 3 Sheet M101. Revisions are clouded and identified as Add 5 to include: - Ductwork revisions for ceiling height and wall location coordination. - Additional fire damper location. - Mounting height clarification at FCU. ITEM NO. 6: SHEET P101 1ST FLOOR PART SANITARY/STORM - AREA A Sheet P101. Revisions are clouded and identified as Add 5 to include: - Pipe relocations for coordination with existing construction and architectural plan. - Addition of air admittance valve (AAV). - Connection for sink at room 160. ITEM NO. 7: SHEET P102 1ST FLOOR WATER PLAN - AREA A Sheet P102. Revisions are clouded and identified as Add 5 to include: - Pipe relocations for coordination with existing construction and architectural plan. - Connection for sink at room Addition of yard hydrant on site. - Addition of fire system audible alarm at Sprinkler Room. ITEM NO. 8: SHEET P103 1ST FLOOR GAS PLAN - AREA A Sheet P103. Revisions are clouded and identified as Add 5 to include: - Pipe routing change to avoid stairwell. ITEM NO. 9: SHEET P201 ROOF STORM PLAN Sheet P201. Revisions are clouded and identified as Add 5 to include: - Overflow roof drain line relocations to coordinate with architectural. ITEM NO. 10: SHEET P301 PLUMBING RISERS Sheet P301. Revisions are clouded and identified as Add 5 to include: - Coordination of floor drain sizes and site hydrant. ITEM NO. 11: SHEET E001 ELECTRICAL SCHEDULES, DIAGRAMS & RISER

3 Shenandoah County Sheriff s Office Addendum No. 5 Page 3 of 3 Sheet E001. Revisions are clouded and identified as Add 5 to include: - Power Riser Diagram updates. ITEM NO. 12: SHEET E002 ELECTRICAL PANEL SCHEDULES Sheet E002. Revisions are clouded and identified as Add 5 to include: - Panel Schedule updates ITEM NO. 13: SHEET E101 FIRST FLOOR AREA A POWER PLAN Sheet E101. Revisions are clouded and identified as Add 5 to include: - Power and cable/data location changes. ITEM NO. 14: SHEET E102 FIRST FLOOR AREA B AND SECOND FLOOR POWER PLANS Sheet E102. Revisions are clouded and identified as Add 5 to include: - Power and cable/data location changes. ITEM NO. 15: SHEET E201 FIRST FLOOR AREA A SYSTEMS PLAN Sheet E201. Revisions are clouded and identified as Add 5 to include: - Additional system connections. ITEM NO. 16: SHEET E401 FIRST FLOOR AREA A LIGHTING PLAN Sheet E401. Revisions are clouded and identified as Add 5 to include: - Additional lights at EC07. ITEM NO. 17: SHEET E501 SITE ELEC. & PHOTOMETRIC PLAN Sheet E501. Revisions are clouded and identified as Add 5 to include: - Revised exterior lighting at building entry. - Revised information for future shed power and for transformer coordination. END OF ADDENDUM NO. 5

4 SECTION EMERGENCY GENERATOR 1. GENERAL 1.1 WORK INCLUDED A. Emergency Generator 1.2 RELATED WORK A. Concrete B. Automatic Transfer Switch 1.3 QUALITY ASSURANCE A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for installation of units required for this Project. 1. Maintenance Proximity: Not more than four hours' normal travel time from Installer's place of business to Project site. B. Manufacturer Qualifications: A qualified manufacturer. Maintain, within 200 miles of Project site, a service center capable of providing training, parts, and emergency maintenance repairs. C. Source Limitations: Obtain packaged generator sets and auxiliary components through one source from a single manufacturer. D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. E. Comply with ASME B15.1. F. Comply with NFPA 37. G. Comply with NFPA 70. H. Comply with NFPA 99. I. Comply with NFPA 110 requirements for Level 1 emergency power supply system. J. Comply with UL K. Engine Exhaust Emissions: Comply with applicable state and local government requirements. L. Noise Emission: Comply with applicable state and local government requirements for maximum noise level at adjacent property boundaries due to sound emitted by generator set including engine, engine exhaust, engine cooling-air intake and discharge, and other components of installation. M. The supplier shall provide all installation and test supervision necessary for final approval and acceptance. N. Generator shall meet all EPA requirements for emissions at the time of installation. 2. PRODUCTS 2.1 EMERGENCY GENERATOR A. Provide standby power systems for the supply of power in the event of failure of normal supply, consisting of diesel engine-driven generator set of the latest commercial type and design. All material and equipment shall be new and undamaged and shall meet the requirements of NFPA-110 standards. Install generator set and accessories outside and shall be weather enclosed. B. Provide fully automatic operation so that unit takes full load within 10 seconds after power failure per NFPA 110 for Level 1 Applications. On resumption of normal power after time delay on transfer switch, automatically retransfer load to normal power and automatically shut down generator, load to normal power and automatically shut down generator, returning to starting condition ready for another operating cycle. EMERGENCY GENERATOR

5 C. Generator shall not extend beyond the foot print as shown on the current architectural drawings. Fuel tank shall be constructed as to provide a walkway for accessing the generator enclosure. D. Provide the engines with antifreeze (a solution of 50% ethylene glycol) and suitable unit mounted immersion type 1500W jacket water heater(s) incorporating a thermostatic switch to maintain engine jacket water at 90 degrees F, in an ambient temperature of 0 degrees F. E. The unit shall be equipped with two main line molded case, three-pole, single throw circuit breakers rated at 104 degree F (40 degree C) ambient temperature. The breakers shall be installed for three phase overloads and/or short circuit protection. They shall operate both manually for normal switching functions and automatically during overload and short circuit conditions. The trip unit for each pole shall have elements providing inverse time delay during overload conditions and instantaneous magnetic tripping for short circuit protection. The circuit breaker shall meet standards established by Underwriter Laboratories (UL), National Electric Manufacturers Association, and National Electric Code. The breakers shall be sized per drawings and 100% rated. F. Standby KW rating as shown on the plans and equipped with: 1. Rated for 130 degree C rise HZ, 3 phase, 4 wire, 120/208 volts hour runtime at full load minimum belly tank with extra capacity for testing. a. Fuel tank shall comply with all applicable codes and standards. 4. Load bank testing breakers as required for full testing operations. 5. Level 2 sound attenuated enclosure. 6. All accessories required or recommended by the references or the manufacturer shall be provided. G. Engine shall be stationary, liquid cooled, Diesel fired with the following: volt, solenoid shift electric starter. 2. Positive displacement oil pump, replaceable oil filter elements, pressure relief valve, dipstick and oil drain valve with extension hose. 3. Replaceable heavy duty air cleaner. 4. Mechanical governing system to control system frequency. 5. Thermostatically controlled jacket heater. 6. Engine starter battery charging alternator and solid state voltage regulator. 7. Engine mounted radiator with belt driven fan, coolant pump and thermostatic temperature control. 8. Exhaust muffler with critical silencer and flexible connectors. 9. Manual reset exciter field circuit breaker. 10. Battery rack with 12 volt starting batteries, cables and connectors. Alternator strip heater. 11. Engine mounted vibration isolators. 12. Outdoor protective housing with removable side panels and hinged door for instrument panel access. Sound attenuated enclosure, 75DBA at 23'-0" under 100% load. 13. Incoming mainline circuit disconnect switches as shown on plans. 14. Fuel regulators. H. Generator Control Panel: 1. Enclose the generator control panel in a generator mounted unit interwired with automatic start. The instruments and control shall include the following: a. Digital instruments, including ammeter, voltmeter, frequency meter, tachometer, and hour meter. Auto start stop control module with cycle crank and cooldown. Phase selector switch. Engine control switch for auto, start/run, off/reset, stop. Digital oil pressure and water temperature gauges. Shutoffs with indicators for low oil pressure, high water temperature, overspeed, overcrank, and emergency stop pushbutton. Voltage adjust rheostat. System diagnostic codes digital readout. Lamp display. D.C. panel illumination lights with switch. Connections for remote annunciation of low oil pressure prealarm, high water temperature prealarm, low EMERGENCY GENERATOR

6 water temperature, battery charger malfunction, low fuel level, and engine running in accordance with NFPA Provide automatic engine starting controls to meet the following: a. To automatically start and stop the engine generator plant. b. When engine fires, starting control shall automatically disconnect cranking controls. The cranking disconnect means shall be electrically self regulating to a low level. If engine fails to start, or any safety device should operate while engine is running, engine shall be stopped immediately and the starting controls locked out, requiring manual resetting. c. Arrange starting controls so that cranking shall start immediately upon closing of a single pole contact in the automatic transfer switch. I. Generac or the equivalent by: 1. Kohler 2. Cat 3. Onan 4. MTU 5. Detroit Diesel 2.2 REMOTE ANNUNCIATOR A. Provide a 21-Light NFPA99/110 Approved Remote Annunciator for the Generator. Annunciator must be able to be placed up to 500 feet from generator. Installation to be the responsibility of the installing contractor. Setup and Programming by Generator Supplier personnel. B. Audio/visual alarm remote annunciator with the following: 1. Alarm silence and lamp test switch. 2. LED annunciator lamps as follows: a. High battery voltage. b. Low battery voltage. c. Normal battery voltage. d. Generator running. e. Normal utility power. f. Genset supplying power. g. Pre-low oil pressure. h. Low oil pressure. i. Pre-high coolant temperature. j. High coolant temperature. k. Low engine temperature. l. Overspeed. m. Overcrank. n. Not in automatic. o. Battery charger malfunction. p. Low fuel. q. Owner selected fault. 3. EXECUTION 3.1 INSTALLATION A. Install emergency generator and accessories in accordance with the manufacturer's requirements. Installation: Install unit complete and make operational. B. Generator shall be completely field wired and connected. C. Coordinate routing of feeder and branch circuits with other trades to provide an efficient and wellcoordinated layout. D. Wiring and Connections: 1. Provide conduit, wiring and connections required and recommended by unit supplier. 2. Install all power and alarm wiring in rigid metal conduit. EMERGENCY GENERATOR

7 3. Provide grounding at generator. Where 4-pole automatic transfer switches are utilized, connect neutral point of generator by green insulated copper conductor. Installation shall be in conformance with the currently enforced NEC, Article 250, for grounding of separately derived system. E. Provide a sign at the service entrance equipment indicating the type and location of on-site emergency power sources per NEC F. Where the grounded circuit conductor connected to the emergency source is connected to a grounding electrode conductor at a location remote from the emergency source, provide a sign at the grounding location that shall identify all emergency and normal sources connected at that location. Provide this sign for generator installations where the neutral conductor is not switched by the transfer switch. G. Provide rebar reinforced concrete pad for emergency generator as recommended by the manufacturer. H. Fill all engine fluids. I. Leave generator with full tank of fuel. J. All materials, equipment and parts comprising the units shall be new and unused, of current manufacturer and of highest grade, free from all defects or imperfections affecting performance. Workmanship shall be of the highest grade in accordance with modern practice. K. The design and construction of the electric set shall be such that it is neat and clean in appearance, and the normal adjustments and maintenance can be effected without the use of special tools. 3.2 START-UP AND TESTING A. Initial start-up shall be performed by a factory-trained representative of the emergency generator manufacturer. B. Provide the manufacturer's standard certified testing at the factory. Prior to acceptance of the installation, field test the equipment to demonstrate it will start automatically, and subject it to a full load test, shut down and reset as indicated herein. C. Correct, prior to acceptance, any defect that becomes evident during this test. Perform the test in accordance with the following requirements and include any other tests that may be recommended by the manufacturer for the purpose of evaluation. 1. Load Bank Testing shall be per NFPA 110 Standards. The Resistive Loadbank shall be furnished by the provider of the Generator. 2. Fuel for Testing is the responsibility of the Contractor. 3. Submit a full written certified test report indicating BHP developed, KW output, voltage, current and frequency variations to the Engineer for evaluation and disposition. Perform all tests in the presence of the Owner's authorized representatives and the manufacturer's representative, who both shall validate the report. D. Engine generator set shall have sufficient capacity to pick up the specified full load and stabilize within +5% of rated frequency within 10 seconds after loss of normal power. E. Visit installation prior to the required start-up and testing. Review installation for pressure, pipe sizes and proper regulator installation. Contractor is fully responsible for any changes or modifications in fuel system prior to start-up and testing. 3.3 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain packaged engine generators. B. On completion of the installation, provide the initial start up by a factory-trained representative of the engine supplier. At the time of start up, explain operating instructions and maintenance procedures to the Owner's operating personnel. The factory-trained representative shall provide a minimum of 4 hour of operating and maintenance instructions to the Owner's operating personnel, which shall include the generator and associated equipment. END OF SECTION EMERGENCY GENERATOR

8 SECTION EMPTY CONDUIT / CABLE TRAY SYSTEMS 1. GENERAL 1.1 WORK INCLUDED A. Equipment Spaces B. Conduit for cable systems C. Cable tray systems 1.2 RELATED WORK A. Raceways and Fittings 2. PRODUCTS 2.1 COMPONENTS A. Conduit and Boxes 1. Refer to appropriate Sections. B. Pull cord 1. Polypropylene rope. C. Equipment Space 1. 3/4", fire rated plywood, smooth one side, full 8'-0" high, width as shown on the drawings. D. Cable Tray 1. B-line flextray system or equal, basket type tray, 4 deep, width as indicated on the plans. 2. Center post type supporting. 3. Electroplated zinc galvanized finish 3. EXECUTION 3.1 CONDUIT INSTALLATION A. Install as shown on plans. B. Provide pull string in conduits. C. Paint all sides and edges of equipment space with 2 coats of gray enamel paint prior to installation. D. At project closeout, provide blank coverplates for rough-ins not utilized by the Owners cabling contractors. 3.2 CABLE TRAY INSTALLATION A. Run #4 ground wire alongside of tray and attach to each section and on each side of cut in accordance with NEMA standards. B. Install in strict accordance with the manufacturer s recommendations. C. Support at a minimum of 5-0 on center. D. Coordinate with sprinkler piping, ductwork, and structural members that may be encountered. Cable tray shall be routed to be as accessible as possible below all other trades. END OF SECTION EMPTY CONDUIT / CABLE TRAY SYSTEMS

9 SECTION IT CABLE SYSTEM 1. GENERAL 1.1 WORK INCLUDED A. Category 6E Cable B. Coax Cable C. Fiber Cable D. Jacks and Trim E. Labeling F. Testing 1.2 RELATED WORK A. Section Raceways and Fittings B. Section Wire and Cable C. Section Boxes D. Section Empty Conduit/Cable Tray System 2. PRODUCTS 2.1 VOICE AND DATA A. Category 6E Cable and 24 strand single mode fiber cables. B. All equipment required for a complete turnkey system Provide all equipment required for a complete system, including but not limited to bulk cable, patch panels, patch cables, wiring blocks and jacks. C. Jacks shall be category 6, dual or quad port wall or in floor box as detailed below. 2.2 TELEVISION A. RG-6 low loss coax 3. EXECUTION 3.1 INSTALLATION A. ECC Server Room EC15 serves only the rooms which are part of the ECC suite. All other areas of the building shall be served from Server Room 115B. B. Pull Cat. 6E cables from the respective server room serving that area to the communications outlets. C. In general pull (2) Cat. 6E cables to each communications outlet except as follows: a. Pull (4) Cat. 6E cables to each low wall outlet in Dispatch Room EC09, IT Office EC14, and Supervisor Office EC09A. b. Pull (3) Cat. 6E and (1) Coax cable to each high wall display/monitor outlets. D. Pull fiber from main wiring backboard in Elec 146U to each server room. E. Pull (1) coax and (3) Cat. 6 cables from each television outlet to the wiring backboard serving that area, provide coax between server room boards and on to the main board in Elec. 146U. F. Cabling system shall be fully tested and certified. G. Provide and install coverplates for all communications outlets matching terminations present at each outlet. H. Label each coverplate and each end of cable for easy identification. I. Provide an additional 5 feet of wiring at each cable pull end, neatly coiled and tied. J. Provide all plugs, accessories, etc. as required for connecting to owner s patch-thru boxes. K. Provide HDMI cable from each projector location and wall monitor location to multi-media box. (1) multi-media box shall be located in the following rooms: Command Conference Room, ECC Conference Room, and Training Room. Verify the location of multi-media box in the room with the owner prior to rough-in. IT CABLE SYSTEM

10 END OF SECTION IT CABLE SYSTEM

B. Section Transfer Switches: Automatic transfer switch.

B. Section Transfer Switches: Automatic transfer switch. SECTION 263213 - ENGINE GENERATORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Packaged engine generator set. B. Exhaust silencer and fittings. C. Remote control panel. D. Battery and charger. E. Weatherproof

More information

Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus

Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus ADDENDUM FORM INVITATION TO TENDER: 2016-067 ADDENDUM NO: 1 DATE ISSUED: June 23, 2016 ISSUED BY: Monty Thibeault DESCRIPTION: Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus

More information

ENGINE GENERATORS AND ACCESSORIES

ENGINE GENERATORS AND ACCESSORIES ENGINE GENERATORS AND ACCESSORIES GENERAL INFORMATION 1.1 This section applies to engine generators and accessories. DESIGN REQUIREMENTS 2.1 The Engineer of Record will consult with the University s Engineering

More information

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps. Issued 2006/08/01 Section 13920 Packaged Fire Pumps and Controllers Page 1 of 7 PART 1 GENERAL 1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

SECTION ISOLATED POWER SYSTEMS

SECTION ISOLATED POWER SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

SECTION GENERATOR PARALLELING CONTROLS

SECTION GENERATOR PARALLELING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices. SECTION 16470 PANELBOARDS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16120 - Wire and Cable. 3. 16475 - Overcurrent Protective Devices. 1.02 SYSTEM DESCRIPTION A. Performance

More information

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps TT-1023 1/97 INSTALLATION INSTRUCTIONS Original Issue Date: 2/94 Model: 6-2000 kw Market: Industrial Subject: Flush- or Surface-Mount Remote Annunciator Kits PA-293991 and PA-293991-SD The remote annunciator

More information

PART 4 ELECTRICAL STANDARDS

PART 4 ELECTRICAL STANDARDS PART 4 ELECTRICAL STANDARDS 1.0 INTRODUCTION AND SCOPE: These standards reflect the general requirements and recommendations of elevator contractors, with respect to the power distribution system to achieve

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

A. This Section includes packaged engine-generator sets for [emergency] [standby] power supply with the following features:

A. This Section includes packaged engine-generator sets for [emergency] [standby] power supply with the following features: SECTION 16231 - PACKAGED ENGINE GENERATOR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION EXTERIOR LIGHTING

SECTION EXTERIOR LIGHTING SECTION 26 56 00 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of exterior luminaries, controls, poles and supports. 1.2 RELATED WORK A. Section 26

More information

STATEMENT OF WORK I. SCOPE OF WORK:

STATEMENT OF WORK I. SCOPE OF WORK: STATEMENT OF WORK Purchase and Installation of Diesel Standby Generator Set and Service Entrance Rated Automatic Transfer Switch for Sewage Treatment Plant Nockamixon State Park (Bucks County) I. SCOPE

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,

More information

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,

More information

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features: PART 1 - GENERAL 1.1 SUMMARY A. This Section includes fast-transfer central battery inverters with the following features: 1. Emergency-only circuits. 1.2 DEFINITIONS A. LCD: Liquid-crystal display. B.

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

STA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16

STA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16 ST-97106N Revised 07-04 Section 25 (00-02-0283) STA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16 Certain danger to human safety and to equipment may occur if some equipment

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL SECTION 21 30 00 FIRE PROTECTION PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00,

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 83 00.00 20 (April 2006) -------------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-15768N (September 1999) UNIFIED FACILITIES GUIDE

More information

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS HVAC Upgrades Phase 2 Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Materials and installation for fire alarm systems upgrades..2 Audible signal devices..3 End-of-line devices..4 Sustainable

More information

Baldor Electric ProSPEC MASTERFORMAT SPECIFICATION 10/26/05

Baldor Electric ProSPEC MASTERFORMAT SPECIFICATION 10/26/05 SECTION 16230 - GENERATOR ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY A. Provide factory test, startup by a supplier authorized by the manufacturer, and on-site testing of the system. B. The generator set

More information

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

A. This Section includes transfer switches rated 600 V and less, including the following:

A. This Section includes transfer switches rated 600 V and less, including the following: SECTION 16415 - TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

16620 EMERGENCY POWER SYSTEMS

16620 EMERGENCY POWER SYSTEMS 16620 EMERGENCY POWER SYSTEMS PART 1: GENERAL 1.01 SUMMARY A. This Section provides the University guidelines for the installation of Emergency Power Systems. B. This standard is developed primarily to

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

PART GENERAL 1.01 SECTION INCLUDES

PART GENERAL 1.01 SECTION INCLUDES Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,

More information

SECTION EMERGENCY POWER SYSTEMS

SECTION EMERGENCY POWER SYSTEMS SECTION 16620 EMERGENCY POWER SYSTEMS A. Standby Engine/Generator Systems 1. Installations of stationary engine/generator (e/g) systems shall be designed in strict accordance with ANSI/NFPA 70 - National

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

SECTION POWER SUPPLIES AND DISTRIBUTION

SECTION POWER SUPPLIES AND DISTRIBUTION SECTION 17460 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for Power Supplies and Power Distribution for Station communications. 1.02 REFERENCE STANDARDS A. American National Standards

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

performed by City of Virginia Beach Public Utilities

performed by City of Virginia Beach Public Utilities City of Virginia Beach Public Utilities Sanitary Sewer Pump Station Specifications - Amendments Section Sub-Section Name Date Modification 1502 3.01 Pump Station Flow Control 6/24/2014 Add the following

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#57297 /Page 1/July 21, 2017 ELECTRICAL SYSTEMS NARRATIVE REPORT The following is the Electrical Systems narrative, which defines the scope of work and capacities of the Power and Lighting systems, as

More information

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low voltage power panelboards 1.02 RELATED SECTIONS 1.03 REFERENCES

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCESA / NASA UFGS-26 28 21.00 40 (August 2008) ----------------------------------- Preparing Activity: NASA Superseding UFGS-26 28 21.00 40 (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

SECTION DOMESTIC WATER HEATERS

SECTION DOMESTIC WATER HEATERS SECTION 223500 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION (16140) - WIRING DEVICES

SECTION (16140) - WIRING DEVICES SECTION 26 27 26 (16140) - WIRING DEVICES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Receptacles, Connectors, Switches, and Finish Plates. B. Related Sections: 1. Section 00 31 13.43 (00370) -

More information

SECTION AIR DOORS

SECTION AIR DOORS SECTION 23 34 33 AIR DOORS Berner Series VSA air doors are designed for openings up to 12 ft for environmental separation and up to 10 ft for insect control. Berner Series VSB air doors are designed for

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

B. Provide factory test, startup by a supplier authorized by the equipment manufacturer(s), and on-site testing of the system.

B. Provide factory test, startup by a supplier authorized by the equipment manufacturer(s), and on-site testing of the system. SECTION 480V PACKAGED GENERATOR SYSTEMS 1.01 SCOPE PART 1 - GENERAL A. Provide complete factory assembled EPA certified low emission stand-by generator set equipment compatible for paralleling with the

More information

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing

More information

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S.

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. NAME OF TENDER: CONSTRUCT, DELIVER AND COMMISSION 3 (THREE) LIFT STATION ELECTRICAL LOCATION OF WORK: 3 Separate work sites in

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 82 16 AIR COILS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in the section

More information

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

SECTION COMMERCIAL-KITCHEN HOODS

SECTION COMMERCIAL-KITCHEN HOODS SECTION 23 38 13 COMMERCIAL-KITCHEN HOODS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber

More information

IN2 Lighting Control Devices

IN2 Lighting Control Devices Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Lighting Control Devices Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

SECTION Fire Pumps

SECTION Fire Pumps SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.

More information

Spectron LSN (Life Safety Network) Suggested Specifications

Spectron LSN (Life Safety Network) Suggested Specifications 1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without

More information

The following information shall become and form part of the contract documents.

The following information shall become and form part of the contract documents. October 4, 206 To: Attention: Re: All Bidders All Bidders JCBE Gymnasium HVAC Upgrades BC#: 206433 Edmonds Project No.: BHM6090 All bidders, The following information shall become and form part of the

More information

DGC-500 DIGITAL GENSET CONTROLLER

DGC-500 DIGITAL GENSET CONTROLLER DGC-500 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-500) offers a low cost microprocessor based integrated alternative for the control and monitoring of small to medium sized

More information

Liebert CSU3000 Chiller

Liebert CSU3000 Chiller CSI 15620 - Packaged Water Chillers Liebert CSU3000 Chiller Guide Specifications for 7.5-37 Ton CS/CD/CT Models 1.0 GENERAL 1.1 CS/CD MODELS The main-frame coolant supply unit shall be a Liebert Model,

More information

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers. September 2012, rev. 00 26 2416 Panelboards PART 1. GENERAL 1.01 Summary A. Section includes: 1.02 Definitions 1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load

More information

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates.

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates. SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

15900 HVAC INSTRUMENTATION AND CONTROLS

15900 HVAC INSTRUMENTATION AND CONTROLS 15900 HVAC INSTRUMENTATION AND CONTROLS PART 1 GENERAL - Andover Controls BAS system is the standard for the University, and may be specified as a proprietary item. 1.0 RELATED DOCUMENTS A. Drawings and

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 2017-08-031 AN ORDINANCE OF THE CITY OF LANCASTER, TEXAS, REPEALING THE NATIONAL ELECTRICAL CODE 2014 EDITION IN ITS ENTIRETY AND REPLACING IT WITH THE ADOPTION OF THE NATIONAL ELECTRICAL

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 2400CA - CLEAN AGENT CHEMICAL SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses PART 1 - GENERAL 1.1 SCOPE A. Through Class III Commodity Classification, up to 12.2m of single, double or multiple row rack storage, up to 14.6m building height (VanQuish Fire Sprinkler System). Cartoned

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

SECTION INTERIOR LIGHTING

SECTION INTERIOR LIGHTING SECTION 26 51 00 INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

DGC-1000 DIGITAL GENSET CONTROLLER

DGC-1000 DIGITAL GENSET CONTROLLER DGC-1000 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-1000) offers a low cost microprocessor based integrated alternative for small to medium sized genset control and monitoring.

More information

Emery County Senior Center Green River 06/07

Emery County Senior Center Green River 06/07 SECTION 260923 - LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

DIVISION 16 ELECTRICAL

DIVISION 16 ELECTRICAL DIVISION 16 ELECTRICAL Saratoga Springs / standards / 02-2004 Page - 0 ELECTRICAL SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.01 SECTION INCLUDES A. Grounding electrodes and conductors, equipment

More information

SECTION (15767) - UNIT HEATERS

SECTION (15767) - UNIT HEATERS SECTION 23 82 39 (15767) - UNIT HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Unit Heaters. 2. Cabinet Unit Heaters. 3. Duct Heaters. 4. Baseboard Heaters. B. Related Sections: 1. Section

More information

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters. SECTION 15622 DIRECT GAS-FIRED BURNER & MANIFOLD SYSTEM PART 1: GENERAL 1.1 Section includes: A. Direct gas-fired heater modules B. Controls C. Equipment schedule 1.2 Related Sections A. Section 01655:

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 AUTOMATIC TRANSFER SWITCH PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install automatic transfer switch (ATS) with number of poles, amperage, voltage and withstand current ratings as shown

More information

SENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification

SENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification This sample specification is for a duress only stand-alone SCAN system using SR series receivers with zone-within-a-zone and graphic display. SECTION 17 DURESS SYSTEM PART 1.00 - GENERAL 1.01 DESCRIPTION

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

CP1-C5 COMPACTOR SPECS 2009

CP1-C5 COMPACTOR SPECS 2009 SECTION 11172 / 14560 TRASH COMPACTOR This section is based on a system produced by: Architectural Refuse Solutions, LLC 525 Kennedy Road Akron, Ohio 44305 Part 1 GENERAL 1.1 RELATED DOCUMENTS A. The general

More information

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Boiler specifications A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Burner General: Q. Burner and burner safeguards shall comply with the CGA

More information