Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018

Size: px
Start display at page:

Download "Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018"

Transcription

1 Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Automatic FireAlarm Association SURVIVING SURVIVABILITY - A USER S GUIDE TO Larry D. Rietz, SET 23 May 2018 Content is Copyright 2018 Jensen Hughes, Inc. All Rights Reserved PRESENTATION LEARNING OBJECTIVES What is the Code history of circuit survivability? What effect does product listing have on survivable cable? What fire alarm circuits must be survivable and how can this be accomplished? How can a designer provide and an AHJ approve a survivable cable installation? NFPA and NFPA 72 are registered trademarks of the National Fire Protection Association. NFPA documents are copyrighted by the NFPA. 3 1

2 Disclaimer Portions of this program are reprinted from NFPA , National Fire Alarm and Signaling Code, Copyright 2015, National Fire Protection, Quincy, MA and other previous editions of NFPA 72. This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety. NFPA 72 is a registered trademark of the National Fire Protection Association, Quincy, MA This presentation does not reflect the official position of the National Fire Protection Association. The content, opinions, and conclusions contained in this presentation are solely those of the presenter and do not necessarily represent the views of Underwriters Laboratories. UL makes no guarantee or warranty as to the accuracy or completeness of any information published herein. UL and the UL logo are trademarks of UL LLC 2017 All Rights Reserved. 4 SURVIVING SURVIVABILITY OF CIRCUIT SURVIVABILITY 5 Survivability is NOT new! 1993 National Fire Alarm Code 6 2

3 1996 National Fire Alarm Code National Fire Alarm Code National Fire Alarm Code 9 3

4 2007 National Fire Alarm Code National Fire Alarm and Signaling Code Most significant changes to circuit or pathway survivability 2 New Chapters: Chapter 12: Circuits and Pathways Chapter 24: Emergency Communications Systems (ECS) National Fire Alarm and Signaling Code Chapter

5 2010 National Fire Alarm and Signaling Code Chapter National Fire Alarm and Signaling Code Chapter 24 EVACS Fire Alarm Systems National Fire Alarm and Signaling Code Chapter 24 Requirements: In-Building MNS: Level 0 or greater per Risk Analysis Wide Area MNS: Level 0 or greater per Risk Analysis Two-way In-Building Wired ECS: Level 2 or 3 Two-way Radio Communications Enhancement: Level 2 or 3, except antennae (2016 moved to NFPA 1221) Area of Refuge (Area of Rescue Assistance) Emergency Communications: Level 2 or 3, except off-premises communications Elevator Emergency Communications: Level 0, 1, 2, or 3 Other ECS: Determined by Risk Analysis 15 5

6 2010 National Fire Alarm and Signaling Code Chapter 24 Further Requirements for Relocation or Partial Evac: National Fire Alarm and Signaling Code Only a few minor changes to the above noted language Chapter 23 section changed to only refer to tone fire alarm system, but the same conflict with Chapter 24 exists National Fire Alarm and Signaling Code Chapter 12 and 23 remain basically unchanged regarding survivability. Chapter 24 makes some changes. 18 6

7 Important Definitions Pathway Survivability: The ability of any conductor, optic fiber, radio carrier, or other means for transmitting system information to remain operational during fire conditions. (NFPA ) Pathway Class: Classification of a circuit (pathway) based on performance characteristics. Code defines performance of Class A, B, C, D, E, N, and X. Redundant: A second, return, or alternate path; a backup. Mostly closely associated with Class A, N, and X pathways. 19 Important Definitions Evacuation Zone: A signaling zone. (Term is not used in NFPA and later) Signaling Zone: An area consisting of one or more notification zones where signals are actuated simultaneously. (NFPA ) Notification Zone: A discrete area of a building, bounded by building outer walls, fire or smoke compartment boundaries, floor separations, or other fire safety sub-divisions, in which occupants are intended to receive common notification. (NFPA ) 20 Important Definitions Evacuation: The withdrawal of occupants from a building. (NFPA ) Partial Evacuation: The partial withdrawal of occupants from a building (usually by floor, smoke zone, or area). Relocation: The movement of occupants from a fire zone to a safe area within the same building. (NFPA ) 21 7

8 Important Definitions Raceway: An enclosed channel of metal or nonmetallic materials designed expressly for holding wires, cables or busbars. (NEC) Cable: An assembly of one or more wires running side by side, which is used to carry electric current. Cable System / Electrical Circuit Protective System(s): An electrical circuit integrity system consisting of components and materials intended for installation as protection for specific electrical wiring systems, with respect to the disruption of electrical circuit integrity upon exterior fire exposure. (UL) 22 SURVIVING SURVIVABILITY OF SURVIVABLE CABLE 23 Circuit Integrity (CI) Cable is listed to ANSI/UL 2196 Standard for Tests for Fire Resistive Cables Standard was issued on May 11, 2001 with Revisions issued: March 25, 2004 December 7, 2006 March 30, 2012 Referenced Standards: UL 1424 Standard for Cables for Power-Limited Fire-Alarm Circuits UL 1425 Standard for Cables for Non-Power-Limited Fire-Alarm Circuits UL 1724 Outline of Investigation for Fire Tests for Electrical Circuit Protective Systems 24 8

9 Products fall into two categories: Fire-Resistive Cable (FHJR) Electric Circuit Integrity Systems (FHIT) Cable and System must survive a fire test of approximately 1,800 F (982 C) for 2 hours and a hose stream test, and still remain intact and the circuit operational. Depending on Listing, cable may be installed in free air or in conduit September 2012 Northbrook, IL September 12, 2012 UL has recently conducted research on a wide array of current products and systems originally certified under UL 2196, Tests for Fire Resistive Cables and ULC- S139, Standard Method of Fire Test for Evaluation of Integrity of Electrical Cables and determined that they no longer consistently achieve a two-hour fire-resistive rating when subjected to the standard Fire Endurance Test of UL2196 or ULC-S139. Consequently, UL and ULC will not be able to offer certification to the currently existing program related to these standards. As a result, manufacturers are no longer authorized to place the UL mark or ULC mark on the following products: UL Classified Fire Resistive Cable (FHJR) ULC Listed Fire Resistant Cable (FHJRC) UL Listed cable with -CI suffix (Circuit Integrity) Furthermore, UL has removed from its certification directory all Electrical Circuit Protective Systems (FHIT) constructed with Fire Resistive Cable. 27 9

10 This action left designers, contractors and AHJs with no cost effective way to meet the Code requirements for survivability. Many struggled with: Performance-based Designs Building Construction Changes Use of alternate cables or systems, like Mineral Insulated (MI) Cable Diagram Courtesy NFPA Handbook 28 The Situation Now Several products are listed for fire alarm CI use At least two different manufacturers Both Conduit and Free Air models are available Cables are Listed with system components like conduit, enclosures, supports, pulling lubricant, etc. 29 Currently Listed Products as of 4/10/2018: 30 10

11 Fire-Resistive Cable Listing 31 System Installation Requirements 32 The Listing now results in a system that must be installed to exacting standards! 33 11

12 SURVIVING SURVIVABILITY SURVIVABILE FIRE ALARM CIRCUITS 34 For Proper Fire Alarm Design, Need to Answer: What Circuits Need Survivability? Where Do These Circuits Need Survivable Components? How Will Survivability be Achieved? FIRST? 35 Before anything, must need to know the Emergency Response Plan for the building! General Alarm? Selective Floor Evacuation? Relocation? Partial Evacuation? Selective Signaling? What other systems may require survivability and how will that survivability be achieved? 36 12

13 If survivable cable is needed, you need a complete copy of the architectural drawings. Wall and Floor Ratings Electrical and Communication Room Wall Ratings Coordinated Riser Locations Smoke Zone Boundaries 37 What Circuits Need Survivability? Notification Appliance Circuits Loudspeaker circuits (audible textual notification appliance circuits) Audible tone circuits (horns, chimes, etc.) Visual notification appliance circuits (strobes, textual appliances, etc) 38 What Circuits Need Survivability? Network Circuit(s) or Remote Unit Communication When used to control/trigger remote control units, amplifiers, or power supplies

14 What Circuits Need Survivability? Network Circuit(s) and Fiber Optic Media Is there 2-hour fiber optic cable? 40 What Circuits Need Survivability? Signaling Line Circuit (SLC) When used to trigger remote NAC power supplies or booster power supplies. When used to for control modules that trigger circuits or amplifiers 41 What Circuits Need Survivability? Certain Riser Circuits Audio riser circuits. Dual / Multiple channel audio Fire Fighter Telephone (two-way emergency communications) 24VDC Power Circuits Sounder Base Power Circuits 42 14

15 Where Do These Circuits Need Survivable Components? Remember the Code requirement: Survivable from Control Unit until they enter the notification zone. Suggest cable/conduit extend at least 12 into/beyond the fire rated wall. 43 Where Do These Circuits Need Survivable Components? For circuits feeding remote panels (network, audio risers, etc.), suggest continuing cable/conduit to the remote panel. 44 Where Do These Circuits Need Survivable Components? Termination Points Provide Through-Penetration Firestop Systems (XHEZ) when passing through all fire rated floors and walls

16 How Will Survivability be Achieved? Use of Fire Alarm Circuit Integrity (CI) Cable Conduit System Free Air Diagram Courtesy NFPA Handbook 46 How Will Survivability be Achieved? Use of 2-Hour Rooms Use of 2-Hour Enclosures Other Equivalent Means Acceptable to the AHJ Diagram Courtesy NFPA Handbook 47 SURVIVING SURVIVABILITY DESIGN AND AHJ APPROVAL OF SURVIVABLE CIRCUITS 48 16

17 DESIGN AND AHJ APPROVAL So how can you properly design a survivable cable system so that the AHJ can provide a review (at shop drawing level) and approval (at acceptance test)? 49 DESIGN AND AHJ APPROVAL Know the Code Understand Key Definitions, including Pathway Survivability, Pathway Class, Signaling Zone, and Notification Zone. Chapter 12 contains your Pathway Survivability Levels, but does not dictate which ones must be used. Chapter 23 requires anyfire alarm system using partial evacuation or relocation to be survivable. Chapter 24 contains the specific requirements ( WHEN ) survivability levels must be provided for EVACS and MNS. 50 DESIGN AND AHJ APPROVAL Know Your System Each Fire Alarm System is unique. Centralized amplifiers and power supplies vs. de-centralized (remote) equipment Networking communication schemes Peer-to-Peer, Master-Subordinate, etc. Programming requirements for selective signaling NAC control options and capacity Understand Effect on Calculations Wire gage requirements and effect on voltage drop #12AWG FPLP Resistance of ohms/1000 ft #12AWG CI Cable Resistance of ohms/1000 ft 51 17

18 DESIGN AND AHJ APPROVAL Understand Your Options What advantages can the building construction provide for you? How long are your survivable cable or cable system runs? Length of vertical runs can require extra installation requirements. Will cable splices be required? Is free air cable an option? Need to follow maximum allowable support spacing (usually ) Is a performance-based alternative your best option? If so, how will you document that alternative? Cost? Fire Alarm Vendor vs. Installer? 52 DESIGN AND AHJ APPROVAL Explain Thoroughly Your Design How can you communicate with the installing contractor on the exact type of cable, conduit and support system installation requirements? Floor Plan Riser Installation Details Calculations Your design can help the AHJ! 53 DESIGN AND AHJ APPROVAL Inspect the Installation Cable Conduit / System Conduit or Cable Supports Fire Stopping Variations from Design Documents? 54 18

19 DESIGN AND AHJ APPROVAL Help the AHJ to Understand The system s infrastructure. The system s dependencies. Clearly explain the evacuation sequence. Provide installation details that can be reviewed on shop drawing review and at acceptance testing. 55 QUESTIONS? Contact Larry D. Rietz, SET lrietz@jensenhughes.com For More Information Visit jensenhughes.com With grateful acknowledgement, much of this presentation was taken from, and in direct coordination with, information published by Wayne Moore. Wayne Moore wmoore@jensenhughes Warwick, RI Content is Copyright 2018 Jensen Hughes, Inc. All Rights Reserved 56 19

Hospital Fire Alarm Systems Recurring Misapplications and Misused Requirements

Hospital Fire Alarm Systems Recurring Misapplications and Misused Requirements Hospital Fire Alarm Systems Recurring Misapplications and Misused Requirements Wayne D. Moore, P.E., CFPS Vice President, Jensen Hughes October 8, 2018 Hospital Fire Alarm Systems Recurring Misapplications

More information

Fire Alarm Wiring. Circuit types, styles and limitations

Fire Alarm Wiring. Circuit types, styles and limitations Fire Alarm Wiring Circuit types, styles and limitations What we will cover Types Classes Notification Appliance Circuits (NAC) Initiating Device Circuits (IDC) Signaling Line Circuits (SLC) Class A, B,

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

Surviving the Survivable Cable Crunch

Surviving the Survivable Cable Crunch Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Surviving the Survivable Cable Crunch by Dean K. Wilson, P.E. Question: I am a fire inspector in a mid-western city. We have recently received preliminary

More information

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Wayne D. Moore, P.E., CFPS, SET Vice President JENSEN HUGHES 117 Metro Center Boulevard, Suite 1002

More information

Fire Resistant Cables - Update Alan Cavers Engineering Manager Certificate Services Group

Fire Resistant Cables - Update Alan Cavers Engineering Manager Certificate Services Group Fire Resistant Cables - Update Alan Cavers Engineering Manager Certificate Services Group History Impact on Standards Where It s At Where It s Going 2 A concern was investigated related to the presence

More information

J-PRO TM Cable Support System

J-PRO TM Cable Support System Frequently Asked Questions Cable Support System What references define how and where J-hooks are used? J-hooks are a horizontal pathway promoted in the BICSI TDM manual as a means to route small to medium

More information

Unified Fire Authority - Fire Prevention Bureau

Unified Fire Authority - Fire Prevention Bureau Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

First Revision No. 339-NFPA [ Section No. 2.2 ]

First Revision No. 339-NFPA [ Section No. 2.2 ] 8 of 326 11/21/2013 1:03 PM First Revision No. 339-NFPA 72-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard

More information

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

Questions/Comments for Richard Roux from Webinar on 7/11/13

Questions/Comments for Richard Roux from Webinar on 7/11/13 Questions/Comments for Richard Roux from Webinar on 7/11/13 Below are the questions and comments from the July 11, 2013 webinar 2013 NFPA 72: Design and Installation Requirements for Mass Notification

More information

Page 1 of 40 First Correlating Revision No. 15-NFPA 72-2014 [ Global Input ] 10.5.4 Plans Examiners and Inspectors. 10.5.4.1 Fire alarm system and emergency communications system plans and specifications

More information

Article by: Ark Tsisserev, Principal, Stantec Consulting Ltd.

Article by: Ark Tsisserev, Principal, Stantec Consulting Ltd. Re: CEC 2012 Article by: Ark Tsisserev, Principal, Stantec Consulting Ltd. Conductors Do we have a problem with this? Apparently, we do. However, there is no reason to generalize this problem. Although

More information

Comtran s VITALink 2 Hour Fire Resistive CIC & CI Free Air Cables. Your trusted solution for fire safety

Comtran s VITALink 2 Hour Fire Resistive CIC & CI Free Air Cables. Your trusted solution for fire safety Comtran s VITALink 2 Hour Fire Resistive CIC & CI Free Air Cables Your trusted solution for fire safety When it comes to life and fire safety, trust the experts! Comtran has been a trusted source in the

More information

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 STUDY AND TEST MATERIAL FOR THE FA2 and FA4 ASSESSMENTS (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 This document contains sample questions to help participants study for the FA2 and FA4

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 2017-08-031 AN ORDINANCE OF THE CITY OF LANCASTER, TEXAS, REPEALING THE NATIONAL ELECTRICAL CODE 2014 EDITION IN ITS ENTIRETY AND REPLACING IT WITH THE ADOPTION OF THE NATIONAL ELECTRICAL

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

MNEC NFPA 72 WHITE PAPER

MNEC NFPA 72 WHITE PAPER MNEC NFPA 72 WHITE PAPER In 2010, the National Fire Protection Assocation (NFPA), significantly changed their code # 72 (National Fire Alarm Code) and has forever improved the importance of communicating

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

VITALink. FAQs I. GENERAL QUESTIONS

VITALink. FAQs I. GENERAL QUESTIONS I. GENERAL QUESTIONS 1) Why do I need to use Circuit Integrity cables? Circuit Integrity cables are utilized to protect critical emergency circuits and maintain operability of fire alarm system in order

More information

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel ACC-25/50ZST Zoned System Voice with Telephone Evacuation Control Panel General The AUDIO COMMAND CENTER 25/50 Zone System with FireFighters Telephone (ACC-25/50ZST) is a state-of-the-art Emergency Voice

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

SP40S-D. Kingfisher Company, inc. Features: Description:

SP40S-D. Kingfisher Company, inc. Features: Description: Kingfisher Company, inc. SP40S-D Features: Multi-use applications The system can function as an evacuation system, an emergency messaging system, and an employee notification system Fire code applications

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

Product Guide. Fire Alarm Cables. Initiating Device, SLC Lines, and NAC Cables.

Product Guide. Fire Alarm Cables. Initiating Device, SLC Lines, and NAC Cables. Fire Alarm Cables Initiating Device, SLC Lines, and NAC Cables Product Guide STANDARDS Fire Alarm Systems A fire alarm system is number of devices working together to detect and warn people through visual

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

E3 Series Broadband System

E3 Series Broadband System Voice Evacuation E3 Series Broadband System Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System General The, E3 Series Broadband System is a modular design and

More information

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208) Idaho Surveying & Rating Bureau, Inc. 1871 South Cobalt Point Way Tel: (208) 343-5483 Meridian, Idaho 83642 FAX: (208) 895-8059 www.isrb.com e-mail info@isrb.com Joseph C. Harbacheck, CIC Secretary - General

More information

Print Specification. Publication. Instructions. Specific requirements. General requirements

Print Specification. Publication. Instructions. Specific requirements. General requirements Print Specification Publication GSA-CC1 Single Input Signal Module Installation Sheet P/N P-047550-1802-EN REV 04 ISS 23JUN15 Instructions This page is the print specification for the publication. It is

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

Photovoltaic (Solar) Array Installation Guide

Photovoltaic (Solar) Array Installation Guide Building & Safety Division Community Development Department 7351 Rosanna Street, Gilroy, CA 95020 Phone: 408 846-0451 Fax: 408 846-0429 Visit us: www.cityofgilroy.org Photovoltaic (Solar) Array Installation

More information

Fire alarm system specification for multiple tenant retail buildings

Fire alarm system specification for multiple tenant retail buildings Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:

More information

E3 Series Broadband System

E3 Series Broadband System Broadband System Description The, Broadband System includes the NetSOLO Broadband System. Like the Net- SOLO Broadband System, the Broadband is of modular design and allows a wide range of configurations

More information

Frequently Asked Questions

Frequently Asked Questions Frequently Asked Questions For Life Safety System Designers, Building Owners, and Installers P/N 85000-0395 Introduction Provisions in NFPA 72 (The National Fire Alarm and Signaling Code) now require low

More information

Shut Down The Fan: A Reprise by Dean K. Wilson, P.E.

Shut Down The Fan: A Reprise by Dean K. Wilson, P.E. Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Shut Down The Fan: A Reprise by Dean K. Wilson, P.E. Question: My grandfather passed away last summer. He had spent many years as a fire fighter. Among

More information

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES [B] APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL

More information

Multiple Input and Output Modules

Multiple Input and Output Modules Kingfisher Company, inc. Multiple Input and Output Modules Features: Removable 12 to 18 AWG plug-in terminal blocks Individual LED indicators Unused addresses may be disabled Rotary address switches Class

More information

NFPA Changes

NFPA Changes Chapter 12, Circuits and Pathways Summary. Chapter 12, Circuits and Pathways, is a new chapter. It brings together requirements that were formerly found in SIG-FUN, Fundamentals of Fire Alarm Systems regarding

More information

Autonomous control unit

Autonomous control unit Supersedes October 2016 Autonomous control unit Description Eaton s Autonomous Control Unit (), part of the ALERiTY integrated MNS platform, is a supervised in-building emergency communications system

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology Warehouse Protection of Exposed Expanded Group-A Plastics with Sprinkler Technology Zachary L. Magnone, Jeremiah Crocker, Pedriant Peña Tyco Fire Protection Products, Cranston, RI, USA Abstract The focus

More information

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

SIGA-CC1 Single Input Signal Module Installation Sheet

SIGA-CC1 Single Input Signal Module Installation Sheet SIGA-CC1 Single Input Signal Module Installation Sheet Personality codes Use the personality codes described below to configure the SIGA-CC1 module. See Table 1 for listing information Table 1: Personality

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

NetSOLO Broadband. Voice Evacuation. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System

NetSOLO Broadband. Voice Evacuation. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System Voice Evacuation NetSOLO Broadband Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System General The NetSOLO Broadband is a revolutionary advance in fire detection

More information

The 2013 National Fire Alarm and Signaling Code

The 2013 National Fire Alarm and Signaling Code ARE YOU A MEMBER OF AFAA? WHY SHOULD YOU BE A MEMBER BECAUSE YOUR BUSINESS IS IMPORTANT James Mongeau The 2013 National Fire Alarm and Signaling Code 1 NFPA 72 Organization Be*er organiza2on Easier to

More information

DONALD H. BERG, ARCHITECT

DONALD H. BERG, ARCHITECT DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES [B] APPENDIX SR GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon SECTION SR101

More information

Applying Performance-based Fire Alarm System Design Part 4

Applying Performance-based Fire Alarm System Design Part 4 Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Applying Performance-based Fire Alarm System Design Part 4 by Dean K. Wilson, P.E. Over the course of the last four issues I have continued to discuss

More information

Brighton Area Fire Authority

Brighton Area Fire Authority 615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following

More information

E3 Series Broadband. Description. Features. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System

E3 Series Broadband. Description. Features. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System Broadband Description Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System The Broadband System includes the Net- SOLO Broadband System. Like the NetSOLO Broadband

More information

I dedicate this book to the Lord Jesus Christ, my mentor and teacher. Proverbs 16:3 NOTICE TO THE READER ABOUT THE AUTHOR

I dedicate this book to the Lord Jesus Christ, my mentor and teacher. Proverbs 16:3 NOTICE TO THE READER ABOUT THE AUTHOR NOTICE TO THE READER The publisher does not warrant or guarantee any of the products described herein or perform any independent analysis in connection with any of the product information contained herein.

More information

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

Use this product according to this instruction manual. Please keep this instruction manual for future reference. 273 Branchport Avenue Long Branch, NJ 07740 (732) 222-6880 Thank you for using our products. INSTALLATION INSTRUCTIONS REMOTE MICROPHONE (SINGLE CIRCUIT) Use this product according to this instruction

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 46 00 SPEC WRITER NOTES: 1. The A/E must obtain a copy of the VA ENGINEERING GUIDE FOR FIRE PROTECTION DESIGN which provides fire alarm system criteria that

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO Prepared For: Public Schools Facilities Authority State of New Mexico 2019 Galisteo, Suite

More information

ARTICLE 760 FIRE ALARM SYSTEMS

ARTICLE 760 FIRE ALARM SYSTEMS Mike Holt s Illustrated Guide to ARTICLE 760 FIRE ALARM SYSTEMS Based on the 2014 NEC Extracted from Mike Holt s Illustrated Guide to Understanding the National Electrical Code Volume 2 For more information

More information

Advanced Fire Alarm Systems Training Program Outline (5 Day)

Advanced Fire Alarm Systems Training Program Outline (5 Day) Advanced Fire Alarm Systems Training Program Outline (5 Day) Day 1 Prescriptive and Performance-Based Design Understand the methodology in accessing the threat of fire within a structure. Know the difference

More information

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing

More information

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015 FIRE ALARM SYSTEMS & 780 CMR Dave LeBlanc, PE, FSFPE March 17, 2015 BIOGRAPHY David J. LeBlanc, PE, FSFPE BS EE & MS FPE - WPI 23 Years PE Technical Committee Member NFPA72 - National Fire Alarm Code NFPA3

More information

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015 NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized

More information

Fire Alarm Systems ARTICLE. Introduction to Article 760 Fire Alarm Systems. Part I. General

Fire Alarm Systems ARTICLE. Introduction to Article 760 Fire Alarm Systems. Part I. General ARTICLE 760 Fire Alarm Systems Introduction to Article 760 Fire Alarm Systems Article 760 covers the installation of wiring and equipment for fire alarm systems, including all circuits controlled and powered

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture

More information

Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products

Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Manufacturers Statement of Compliance with NFPA 70, National Electric Code,

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

LifeAlarm Fire Alarm Controls

LifeAlarm Fire Alarm Controls UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity

More information

Typical Areas of Poor RF Coverage

Typical Areas of Poor RF Coverage 1 Typical Areas of Poor RF Coverage Buildings, especially basement levels. Subways, mines. Parking Garages. Naturally Shadowed da Areas : (Canyons, behind hills, river bottoms, etc.) In Public Safety A

More information

SECTION ADDRESSABLE FIRE ALARM SYSTEM

SECTION ADDRESSABLE FIRE ALARM SYSTEM SECTION 16723 ADDRESSABLE FIRE ALARM SYSTEM 1 PART 1 GENERAL 1.1 DESCRIPTION A. This section outlines the requirements for the installation, programming and configuration of Addressable Fire Alarm System

More information

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.

More information

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT 1. GENERAL SPECIFICATION 1.1 This specification outlines the requirements for a pre-engineered fire extinguishing system comprising Kidde Fire Systems WHDR Wet Chemical Fire Suppression System, Kidde APC

More information

Case Study Media Contact Beth Welch, or

Case Study Media Contact Beth Welch, or Case Study Media Contact Beth Welch, 203-484-6202 or beth.welch@honeywell.com Specialized Fire Protection for Special Community The Sisters of St. Joseph of the Third Order of St. Francis built the Clare

More information

Review of Revisions to NFPA 1, 2015 Edition

Review of Revisions to NFPA 1, 2015 Edition James S Peterkin, PE, LEED AP Senior Fire Protection Engineer TLC Engineering for Architecture Anthony Apfelbeck, CFPS, CBO, CFO, FM, FIFireE, MPA Building and Fire Official City of Altamonte Springs,

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

Figure 1. Figure 2. See notes 1 and 2 below.

Figure 1. Figure 2. See notes 1 and 2 below. 273 Branchport Avenue Long Branch, N.J. 07740 (800) 631-2148 Thank you for using our products. www.wheelockinc. com INSTALLATION INSTRUCTIONS HORN SPEAKER WITH AMPLIFIER Use this product according to this

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life

More information

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA Presentation Objective Compare fire alarm system design methods

More information

Rev. B. TrueAlert Addressable Controller Application Manual

Rev. B. TrueAlert Addressable Controller Application Manual 574-996 Rev. B TrueAlert Addressable Controller Application Manual This page intentionally blank Copyrights and Trademarks Copyright 000 Simplex Time Recorder Company, Westminster, MA 044-000. All rights

More information

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual Part Number P84748 Assembly Number A84749 Revision C Revision A Copyright 2006 Printed in U.S.A. All rights reserved.

More information

WINDOW & HVAC REPLACEMENT PEMBERTON TOWNSHIP BOE REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5450E

WINDOW & HVAC REPLACEMENT PEMBERTON TOWNSHIP BOE REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5450E SECTION 283111 DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary General Conditions of the

More information

Fire Alarm System Inspection and Testing Report

Fire Alarm System Inspection and Testing Report Fire Alarm System and ing Report Date of : Time of : 1. PROPERTY INFORMATION: Name of Property: Address: of property: Occupancy Type: Name of property representative: Address: Phone: Fax: E-mail: Local

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Notification

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: INFORMATION PROJECT ADDRESS:

More information