1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: MEMORANDUM TO: FROM: Technical Committee on Residential Occupancies Kelly Carey, Project Administrator DATE: October 18, 2016 SUBJECT: NFPA 101 Second Draft Ballot FINAL Ballot Results (A2017) According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. 29_ Members Eligible to Vote _4_ Members Not Returned (Boyd, Damron, Meehan and ) 13_ Members Voted Affirmative on All Revisions _4_ Members Voted Affirmative with Comment on one or more Revisions (Coats, Klein, Nickson and Weaver) _ 8_ Members Voted Negative on one or more Revisions (Asp, Isman, Klein, Lampella, Longhitano, Mayl, Spangler and Weaver) 0_ Members Abstained on one or more Revisions The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each revision. To pass ballot, each revision requires: (1) a simple majority of those eligible to vote and (2) an affirmative vote of 2 /3 of ballots returned. See Sections (c) and of the Regulations Governing the Development of NFPA Standards.
2 NFPA 101 TC ON RESIDENTIAL OCCUPANCIES SECOND DRAFT BALLOT RESULTS SR-6003, Section No , See SR-6003 Agree with the deletion. I am voting negative on the entire document because it is my opinion that the adoption of GRAB BARS is so far afield from a standard on protection of human life from fire it calls into question the motives and credibility of the entire document. Are we now experts on fall prevention? What's next? Having the fire marshal enforce rules about what kind of slip-resistant shoes people need to wear in their homes? Is there anyone who really believes that people who invest $25,000 to $50,000 on renovating their bathrooms want the town fire marshal to tell them that the lack of grab bars on their tub or shower is a fire code violation?? SR-6005, Section No , See SR-6005 Page 1 of 14
3 Agree with the deletion. SR-6006, Section No , See SR-6006 Agree with proposal. Page 2 of 14
4 SR-6007, Section No , See SR-6007 Agree with proposal. SR-6008, Section No , See SR-6008 Affirmative with Comment 0 Negative 2 This change does not recognize when a gas-fired water heater or other appliance is in a room inside an apartment that is accessed from the outside. Page 3 of 14
5 SR-6013, Section No , See SR-6013 Affirmative 21 Affirmative with Comment 3 Marshall A. Klein Staff copied the type of occupancies from SR-6007 into this SR 6013 new Section without changing them from "...hotel and dormitory occupancies..." to "...apartment occupancies...". This is a staff error and needs to be corrected because Chapter 30 covers the requirements for new apartments (SR-6013) and Chapter 28 is for new hotels and dormitory occupancies. This was strictly a "copy and paste" error by Staff at the Second Draft Meeting since it was the Committee's intent to apply this requirement to the occupancies covered in Chapters 28 and 30. Ronald G. Nickson Agree with proposal. When SR-6007 was copied into SR 6013 the term "...hotel and dormitory occupancies..." was not changed to "...apartment occupancies..." which is necessary to make the approved change appropriate for apartments. Page 4 of 14
6 SR-6009, Section No , See SR-6009 Affirmative 22 Negative 2 Kevin Spangler Agree with proposal. It should read 36 inches or the door width. There is no reason to have a 36 inch wide landing with a smaller door. SR-6014, New Section after , See SR-6014 Affirmative 20 Affirmative with Comment 0 Negative 5 I do not agree with the proposed change as the cost to install grab bars exceeds the cost benefit of installing them. Current federal law and building codes require the installation of blocking for the owner to install grab bars at their discretion. Page 5 of 14
7 Eric N. Mayl Kevin Spangler Gary Lampella While this provision may reduce injuries, it is overly intrusive. Grab bars in showers are for fall protection, not for means of egress. Grab bars in one and two family dwellings are for personal preference and should not be mandated by NFPA 101. The information/documentation provided at the last meeting did not have substantial technical information that indicated that the falls that were referenced were in one or two family dwellings. At a minimum, section should be in when the floor does not exceed 6 inches in height. A six inch curb has not proven to be a fall hazard in any of the documentation provided. Of concern is the statement that all new bathtubs, bathtub-shower combinations and showers be provided with grab bars will include replacements. These will be regulated by the plumbing code with no reference back to these sections. We also have concerns with replacement (new) fixtures as there was committee discussion on retrofitting grab bars and the proponent mentioned a test for an epoxy/glue attachment in-lieu of the typical mechanical attachment to solid blocking/backing. We have reservations about promoting this type of attachment. An epoxy/glue attachment is only as strong as the surface it is attached to, not just new construction. We would suggest maybe adding an explanatory note to indicating epoxy/glue attachments may not meet the structural loading requirements and mechanical attachment to solid blocking/backing is the preferred method. There is also the issue of the proposed vertical grab bars, especially those from the floor to the ceiling, which will be inviting for children to climb. This will more than likely lead to the unintended consequence of serious injuries due to the misuse of the grab bars in dwelling units. It is obvious that the ramifications of this major change to the nation s living spaces has not been fully vetted. We are not convinced that these devices should be regulated by the person enforcing this code, which would be the fire code official. We are also concerned about putting these requirements in the means of egress chapters while other activities in and around a bathroom are not specifically regulated. Such as, transferring from a chair to a wheelchair, getting on and off a bed and other daily functions that pose a safety risk to many persons. We think the issue of new tub/showers, retrofits and inserting the language in the means of egress chapters should be addressed prior to insertion into the code. Page 6 of 14
8 SR-6001, Section No , See SR-6001 Agree with the deletion. SR-6002, Section No , See SR-6002 Agree with the proposal. Page 7 of 14
9 SR-6004, New Section after , See SR-6004 Agree with the proposal. SR-6015, New Section after , See SR-6015 Affirmative 20 Affirmative with Comment 0 Negative 5 I do not agree with the proposed change as the cost to install grab bars exceeds the cost benefit of installing them. Current federal law and building codes require the installation of blocking for the owner to install grab bars at their discretion. Page 8 of 14
10 Eric N. Mayl Kevin Spangler Gary Lampella While this provision may reduce injuries, it is overly intrusive. Grab bars in showers are for fall protection, not for means of egress. Information provided as documentation for the falls did not provide substantial information that grab bars would prevent the falls. At a minimum, section should be in when the floor does not exceed 6 inches in height. A six inch curb has not proven to be a fall hazard in any of the documentation provided. Of concern is the statement that all new bathtubs, bathtub-shower combinations and showers be provided with grab bars will include replacements. These will be regulated by the plumbing code with no reference back to these sections. We also have concerns with replacement (new) fixtures as there was committee discussion on retrofitting grab bars and the proponent mentioned a test for an epoxy/glue attachment in-lieu of the typical mechanical attachment to solid blocking/backing. We have reservations about promoting this type of attachment. An epoxy/glue attachment is only as strong as the surface it is attached to, not just new construction. We would suggest maybe adding an explanatory note to indicating epoxy/glue attachments may not meet the structural loading requirements and mechanical attachment to solid blocking/backing is the preferred method. There is also the issue of the proposed vertical grab bars, especially those from the floor to the ceiling, which will be inviting for children to climb. This will more than likely lead to the unintended consequence of serious injuries due to the misuse of the grab bars in dwelling units. It is obvious that the ramifications of this major change to the nation s living spaces has not been fully vetted. We are not convinced that these devices should be regulated by the person enforcing this code, which would be the fire code official. We are also concerned about putting these requirements in the means of egress chapters while other activities in and around a bathroom are not specifically regulated. Such as, transferring from a chair to a wheelchair, getting on and off a bed and other daily functions that pose a safety risk to many persons. We think the issue of new tub/showers, retrofits and inserting the language in the means of egress chapters should be addressed prior to insertion into the code. Page 9 of 14
11 SR-6010, New Section after , See SR-6010 Affirmative 21 Affirmative with Comment 2 Paul D. Coats Agree with the proposal. I've looked in NFPA 72 for when the mass notification system would be required, and it's not indicated unless I missed it. I'm a little uncomfortable requiring an analysis so broadly when the decision as to when it's required is subjective. I can see the potential benefits, but I wonder if it may not be better to have a more conservative and firm indicator for triggering the analysis. I voted affirmative because I'm uncertain how much burden doing the analysis is in cases where mass notification is not likely to be needed. Negative 2 Kevin Spangler Mass notification is an owners preference. Mass notification is not required for any particular occupancies. A mass notification analysis may be requested by the owner, but it should not be a mandated document. This is an unnecessary cost to the owner who has ultimate say in whether or not a mass notification system should be installed. As a consulting engineer that would be hired to do these assessments, I would estimate a minimum of $6,000, and more likely around $10,000 would be charged to the client for a report/assessment that is being required in this new section. Page 10 of 14
12 SR-6016, New Section after , See SR-6016 Affirmative 19 Negative 5 Marshall A. Klein Roland A. Asp Agree with the proposal. I agree with the negative ballots of Ken Isman and Roland ASP on this Second Revision proposal. The negative ballot is cast for several reasons. The result of the proposed text is far reaching and will have multiple outcomes when it is enforced by local authorities having jurisdiction. Integrated system is not defined in NFPA 101 and the definition in NFPA 4 is very unclear as to the extent of the testing, especially as explained by the annex text (A ) in NFPA 4. Furthermore, the life safety system and fire protection system is also not defined in NFPA 101 or NFPA These definitions are important to go forward with this language to provide uniform enforcement. It is very important to note that if this proposal goes forward, it will conflict with the other model building and fire codes (IBC/IFC, proposal F145-16) that are developing their 2018 editions. The IFC/IBC is limiting NFPA 4 to high rise buildings (as is the First Draft Report, NFPA 101, Section ) and where smoke control systems are integrated. It is common in several states that the IBC and NFPA 101 is used across multiple jurisdictions. Having conflicting requirements between the documents is not new, but the extent of testing integrated systems should be consistent for building owners, contractors, and authorities having jurisdiction. Page 11 of 14
13 Kenneth E. Isman Kevin Spangler A wet pipe or dry pipe sprinkler system with the waterflow switch set up as an initiating device for the alarm system meets the definition of an integrated system, but should not have to be tested as an integrated system. The integrated system testing is more expensive than the individual testing of the sprinkler and alarm systems and is not justified. If the link between the sprinkler system and the alarm system fails for some reason, the sprinkler system can still do its job. The alarm system is not preventing the sprinkler system from functioning, so there is no reason to require them to be tested together. I can see how a preaction sprinkler system would need to be tested with the alarm system in an integrated fashion. If the alarm system does not work, then the sprinkler system won t operate properly. But for a regular wet pipe or dry pipe sprinkler system, that does not rely on the alarm system for operational purposes, causing the sprinkler system to be tested as an integrated system just because it is tied to the alarm system is too much. See Kenneth Isman comments. SR-6017, New Section after , See SR-6017 Affirmative 19 Negative 5 Marshall A. Klein Agree with the proposal. I agree with the negative ballots of Ken Isman and Roland ASP on this Second Revision proposal. Page 12 of 14
14 Roland A. Asp The negative ballot is cast for several reasons. The result of the proposed text is far reaching and will have multiple outcomes when it is enforced by local authorities having jurisdiction. Integrated system is not defined in NFPA 101 and the definition in NFPA 4 is very unclear as to the extent of the testing, especially as explained by the annex text (A ) in NFPA 4. Furthermore, the life safety system and fire protection system is also not defined in NFPA 101 or NFPA These definitions are important to go forward with this language to provide uniform enforcement. It is very important to note that if this proposal goes forward, it will conflict with the other model building and fire codes (IBC/IFC, proposal F145-16) that are developing their 2018 editions. The IFC/IBC is limiting NFPA 4 to high rise buildings (as is the First Draft Report, NFPA 101, Section ) and where smoke control systems are integrated. It is common in several states that the IBC and NFPA 101 is used across multiple jurisdictions. Having conflicting requirements between the documents is not new, but the extent of testing integrated systems should be consistent for building owners, contractors, and authorities having jurisdiction. Kenneth E. Isman A wet pipe or dry pipe sprinkler system with the waterflow switch set up as an initiating device for the alarm system meets the definition of an integrated system, but should not have to be tested as an integrated system. The integrated system testing is more expensive than the individual testing of the sprinkler and alarm systems and is not justified. If the link between the sprinkler system and the alarm system fails for some reason, the sprinkler system can still do its job. The alarm system is not preventing the sprinkler system from functioning, so there is no reason to require them to be tested together. I can see how a preaction sprinkler system would need to be tested with the alarm system in an integrated fashion. If the alarm system does not work, then the sprinkler system won t operate properly. But for a regular wet pipe or dry pipe sprinkler system, that does not rely on the alarm system for operational purposes, causing the sprinkler system to be tested as an integrated system just because it is tied to the alarm system is too much, even in a high rise building. Page 13 of 14
15 Kevin Spangler See Kenneth Isman comments. Page 14 of 14
MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities
More informationMEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Building Service and
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and
More informationM E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and
More informationNational Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Residential
More information9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification
Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry
More information1. The meeting was called to order by Chair James Lathrop at 8:00 AM (CDT) on Wednesday, August 26, 2015.
MINUTES NFPA Technical Committee on Residential Occupancies NFPA 101 and NFPA 5000 First Draft Meeting Wednesday, August 26, 2015 InterContinental Milwaukee Milwaukee, WI 1. The meeting was called to order
More informationCirculation Report for SIG-TMS Comments Document # 72
1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15
More informationNational Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance
More informationTECHNICAL COMMITTEE ON FIRE CODE
TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2
More informationNational Fire Protection Association
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M (AMENDMENT) TO: FROM: Technical Committee on Mercantile
More informationM E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter
More informationMEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Portable Fire Extinguishers
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Correlating Committee on Combustible Dusts Susan
More information1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Residential
More informationFirst Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement
of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable
More informationNFPA Talking Points on NFPA 1 Fire Code update to the 2015 Edition:
NFPA Talking Points on NFPA 1 Fire Code update to the 2015 Edition: The legislative study committee established by HB 427 report dated November 1, 2016 reads Members support uniformity for the most fundamental
More informationMEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fundamentals of Fire
More informationMEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fire Code (FCC-AAA) Gregory
More informationDiane D. Matthews, Administrator, Technical Projects. The September 19, 2013 date for receipt of the NFPA 5000 Second Draft Ballot has passed.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Fire Protection Features Diane D. Matthews,
More informationMEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Correlating Committee on Signaling Systems for
More informationM E M O R A N D U M. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action.
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Marshal Professional Qualifications Stacey Van Zandt DATE: July 13, 2010 SUBJECT: NFPA 1037 ROP TC Letter Ballot (F2011) The ROP letter ballot
More informationNFPA Technical Committee on Fire Tests
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Tracy
More informationDelayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.
9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical
More informationAD HOC HEALTHCARE COMMITTEE MEANS OF EGRESS WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B MOE COMMITTEE
AD HOC HEALTHCARE COMMITTEE MEANS OF EGRESS WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B MOE COMMITTEE This report includes 6 code change proposals from the Adhoc Health Care, Means of Egress committee
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 2 FROM: Kimberly Shea, Administrator,
More informationDelayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.
Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical self-closing device
More informationM E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter
More informationThe Technical Committee on Commissioning and Integrated Testing
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: The Technical Committee on Commissioning and Integrated Testing
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Technical Committee on Testing and Maintenance
More informationPublic Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input
of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August
More informationUnderstanding, Applying and Enforcing NFPA 25. James D. Lake NFSA Director of Training
Understanding, Applying and Enforcing NFPA 25 James D. Lake NFSA Director of Training When Sprinklers Are Ineffective Water did not reach fire 8% 7% 7% 5% 44% Not enough water released Damaged Component
More informationMEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Standpipes Elena
More informationAmend Base Code. Amend Base Code. Amend Base Code. Disposition. (Statute, Rule, FBC, Industry) Y/N
Code Reference NFPA 101 1.1.1.2 (2009 1.1.1.1 (2012 1.1.7 (New) 1.3.1.1 Florida Specific Amendment Anytime a reference is made to NFPA 1 or NFPA 101 within this Code, it shall be the Florida specific version
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Correlating Committee on
More informationTAC: Fire. Total Mods for Fire in Approved as Submitted: 1. Total Mods for report: Glitch. Fire. Page 2 of 8. 27/06/2013 Page 2 of 8
Page 1 of 8 Proposed Code Modifications Glitch Modifications This document created by the Florida Department of Business and Professional Regulation - 850-487-1824 27/06/2013 Page 1 of 8 Total Mods for
More informationMEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Emergency Power Supplies Kelly
More informationMEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Alternative Approaches to
More informationM E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Furnishings
More informationCODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B
CODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B This report includes 3 code change proposal from the CTC Nursing Care Facilities Coordination committee
More informationNarrative Reports As Regulated by 780 CMR, Section 903.0
EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for
More informationM E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic
More informationCenter for Life Safety Education
Center for Life Safety Education Fire Sprinklers 101 Introduction, Building Codes, and Water Supplies Reprinted with permission from NFPA 13, Installation of Sprinkler Systems, Copyright 2007, National
More informationSTATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT
STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device
More informationM E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Code Kelly Carey,
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Residential Sprinkler
More information1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Pumps Patti
More informationMEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Fire Alarm
More informationCommittee on 51A M E M O R A N D U M. NFPA Technical Committee on Industrial and Medical Gases
Committee on 51A M E M O R A N D U M To: From: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant Date: June 14, 2010 Subject: NFPA 51A ROC Letter Ballot Circulation
More information9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification
of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked
More informationTECHNICAL COMMITTEE MEMBERS WHO PARTICIPATED
MEETING MINUTES NFPA Correlating Committee on Safety to Life (SAF-AAC) November 7, 2013 Second Draft Meeting Embassy Suites Atlanta Hartsfield Airport Hotel Atlanta, GA 1. Call to Order. The meeting was
More information9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement
Second Revision No. 5501-NFPA 5000-2016 [ New Section after 29.2.1.2 ] 29.2.1.3 Bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars in accordance with the provisions
More informationSecond Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement
of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections
More informationSPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.
STATE OF LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BOULEVARD, BATON ROUGE, LA 70806 800-256-5452 225-925-4920
More informationMEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Protected Premises Fire Alarm
More informationNovember 17, Sent Via Electronic and Regular Mail
November 17, 2017 Sent Via Electronic and Regular Mail Kathleen Asher Department of Community Affairs PO Box 800 Trenton, New Jersey 08625 E-mail: Kathleen.Asher@dca.nj.gov Fax Number: (609) 984-669620
More informationReport on First Revision June 2014 NFPA 5000
5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Road Tunnel and Highway
More informationRecommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region
Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing
More informationChanges in NFPA
Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration
More informationPublic Comment No. 2-NFPA [ Section No ]
Public Comment No. 2-NFPA 16-2013 [ Section No. 3.3.6 ] 3.3.6* Foam-Water Sprinkler System. A piping network connected to a source of foam concentrate and to a water supply. The piping network is equipped
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels
More informationSubject: BSR Uniform Mechanical Code, 2015 Edition: Appeal on Proposal #333
Paul Cabot Administrator National Fuel Gas Ms. Gabriella Davis Recording Secretary, IAPMO Standards Council International Association of Plumbing and Mechanical Officials (IAPMO) IAPMO Group World Headquarters
More informationMEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 17 From: Kimberly Shea, Project Administrator
More informationPublic Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification
Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the
More information1. Call to order. Call meeting to order by Interim Chair B. Cronin at 8:00 a.m. on August 22, 2018.
AGENDA NFPA Technical Committee on Residential Occupancies NFPA 101 and NFPA 5000 First Draft Meeting Wednesday-Thursday, August 22-23, 2018 Minneapolis Marriott City Center Minneapolis, Minnesota 1. Call
More informationhome smoke candles alarms electrical burns smoking medical oxygen cooking FIREFIGHTING MATCHES & LIGHTERS SPRINKLERS
FIREFIGHTING home smoke alarms REGULATIONS GOVERNING THE NFPA EDUCATIONAL MESSAGES DESK REFERENCE FOR THE FIRE SERVICE AND FIRE AND LIFE SAFETY EDUCATORS MATCHES & LIGHTERS medical oxygen cooking FIRE
More informationTable EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c
Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in
More informationNational Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Construction
More informationNEW YORK CITY FIRE DEPARTMENT. Notice of Public Hearing and Opportunity to Comment on Proposed Rule
NEW YORK CITY FIRE DEPARTMENT Notice of Public Hearing and Opportunity to Comment on Proposed Rule What are we proposing? The Fire Department is proposing to comprehensively update Section 3004-01 of Title
More informationUnwanted Fire Alarms. Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA (617)
Unwanted Fire Alarms Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA 02169-7471 (617) 984-7463 mahrens@nfpa.org Unwanted fire alarms, however they are defined, are a problem
More informationOklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference:
Oklahoma 310:451-1-3. Adopted references The Board of Health hereby incorporates by reference the International Code Council (ICC) 2006 (IBC) Edition International Building Code; the 2007 Edition Standard
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Sprinkler System
More informationFire Sprinklers Working Group Final Report
Introduction The Building Act received Royal Assent on March 25, 2015. The Act aims to establish more consistent building requirements across British Columbia and create a more robust and modern building
More informationSC # /16/17/18/19/23/24 D#03-24
SC #03-7-15/16/17/18/19/23/24 D#03-24 Casey C. Grant, P.E. Secretary, Standards Council 26 July 2003 To: Interested Parties Subject: Standards Council Decision (Final): D#03-24 Standards Council Agenda
More information1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Sprinkler System
More informationU.S. Codes & Standards for Energy Storage Systems. Joe Cain, P.E. Chair, SEIA Codes & Standards Working Group
U.S. Codes & Standards for Energy Storage Systems Joe Cain, P.E. Chair, SEIA Codes & Standards Working Group Regulatory Update: U.S. Codes & Standards Agenda NFPA 70 (NEC) UL 1973 & 9540 Fire Codes NFPA
More informationCTC Meeting #27 JUNE 17 18, 2013 NIST report on the Charleston sofa store fire
CTC Meeting #27 JUNE 17 18, 2013 NIST report on the Charleston sofa store fire The following 2013 Group B changes have been compiled for the above noted CTC Area of Study. Code changes with an (*) indicate
More informationFire Prevention Coffee Break Training. May 2017
Fire Prevention Coffee Break Training May 2017 Agenda Introduction Submittals - Phelan Changes to NFPA 13 - Phelan Questions and Answers Open Forum Please welcome our S ummer Intern Charlie Poppe Small
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations
More informationMinimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016
1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Technical Committee on Fundamentals of Fire
More informationNFPA Marine Fire Protection Codes and Standards An Overview. Guy R. Colonna, P.E. National Fire Protection Association. Quincy, MA USA
Proceedings of the ASME/USCG 2013 3rd Workshop on Marine Technology and Standards MTS2013 July 24-25, 2013, Arlington, VA, USA MTS2013-0321 NFPA Marine Fire Protection Codes and Standards An Overview Guy
More informationH BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION
STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H
More informationMEMORANDUM. TERESA McCLISH, COMMUNITY DEVELOPMENT DIRECTOR
MEMORANDUM TO: FROM: BY: CITY COUNCIL TERESA McCLISH, COMMUNITY DEVELOPMENT DIRECTOR KELLY HEFFERNON, ASSOCIATE PLANNER SUBJECT: CONSIDERATION OF ADOPTION OF AN ORDINANCE AMENDING CHAPTER 16.84 OF THE
More informationSOMERSWORTH CODE FIRE PREVENTION AND LIFE SAFETY CHAPTER 21
SOMERSWORTH CODE FIRE PREVENTION AND LIFE SAFETY CHAPTER 21 ARTICLE I FIRE PREVENTION CODE 21-1. Statutory authority 21-2. Adoption of standards 21-3. Definitions 21-4. Exceptions to Fire Prevention Code
More informationQuestions for the HFD regarding Bill 69, Evaluation Worksheet for High-Rise Residential Buildings User s Guide ( New User s Guide or NUG )
Questions for the HFD regarding Bill 69, Evaluation Worksheet for High-Rise Residential Buildings User s Guide ( New User s Guide or NUG ) 1. Condo and co-op associations believed that the Life Safety
More informationM E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities
More information2019 COURSE CATALOG (rev )
2019 COURSE CATALOG (rev. 02.07.19) www.afaa.org CEUs Available for NICET, Engineers and Other! 3246 Noe-Bixby Road, Suite 101, Columbus, OH 43232 844-438-2322 Page 1 Page No. Seminar Name 3. A User s
More informationMEMORANDUM. Subject: NFPA 1124 Proposed Tentative Interim Amendment (TIA) No. 1094
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Pyrotechnics Elena Carroll,
More informationNFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014
NFPA 13 2016 Edition NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s Committees created the First Draft at meetings between July 2013 and December 2013 Balloting ended in early 2014 First Draft decisions
More informationMEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Initiating Devices for Fire
More informationField Guide for Healthcare Facilities
Field Guide for Healthcare Facilities Jennifer L. Frecker James K. Lathrop Written by industry experts Jennifer L. Frecker and James K. Lathrop and using an easy-to-digest format, The New Life Safety Code
More informationMULTI-PHASED FIRE ALARM AND MASS NOTIFICATION SYSTEM UPGRADES: The Authority Having Jurisdiction (AHJ) and Proper Planning
CAMPUS FIRE SAFETY CODE TALK Campus Fire Safety e-newzone MULTI-PHASED FIRE ALARM AND MASS NOTIFICATION SYSTEM UPGRADES: The Authority Having Jurisdiction (AHJ) and Proper Planning By Ernesto Vega Janica,
More informationResolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.
Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in
More information2009 IRC. and Fuel gas Provisions
2009 IRC Q &A Plumbing, MechanICAl and Fuel gas Provisions TABLE OF CONTENTS PREFACE... vii ABOUT THE INTERNATIONAL CODE COUNCIL...viii PLUMBING PROVISIONS... 1 CHAPTER 25 PLUMBING ADMINISTRATION....3
More information