Transcription

1 Foam Solutions, LLC 2251 Performance Parkway, Columbus, Ohio Ph ; Fax Foam Proportioner Test Manual Aqua Foam Test Method U.S. Patent 7,080,694/7,513,315. Other patents pending Jan. 10, 2010

2 CONTENTS Page 1.0 INTRODUCTION Foam Fire Protection Requirements for Foam System Testing Foam System Inspection and Testing AQUA FOAM TEST METHOD General Description of the Method Attributes of the Method A Complete Foam System Inspection and Testing Program DESCRIPTION OF THE HARDWARE AND FORMS FOR AQUA FOAM TESTING... ERROR! BOOKMARK NOT DEFINED. 3.1 Components for an Aqua Foam Test...Error! Bookmark not defined. 3.2 Test Form...Error! Bookmark not defined. 3.3 Care and Maintenance of the Equipment...Error! Bookmark not defined. 4.0 INSTRUCTIONS FOR CONDUCTING AN AQUA FOAM TEST...ERROR! BOOKMARK NOT DEFINED. 4.1 Bladder Tank Systems ILBP System...Error! Bookmark not defined. 5.0 EXAMPLE OF AQUA FOAM TESTING... ERROR! BOOKMARK NOT DEFINED. 6.0 EQUIPMENT REQUIRED Bladder Tank Systems ILBP Systems 19

3 1.0 INTRODUCTION 1.1 Foam Fire Protection FOAM PROPORTIONER TEST MANUAL AQUA FOAM TEST METHOD Foam fire protection systems are installed in many high hazard/high value locations. These systems are intended to suppress or extinguish very challenging Class B (flammable liquid) fires. Flammable liquid fires can grow extremely rapidly with tremendous heat output and must be rapidly controlled before building systems, contents and structures are destroyed. Foam fire protection systems discharge a foam solution (a mixture of foam concentrate at 1-6 percent concentration in water). The foam solution also is mixed with air at the discharge device or picks up air as the foam solution stream is applied. This water/concentrate/air mixture generates a mass of stable bubbles that form a foam blanket on the surface of a flammable liquid. The foam blanket extinguishes the fire primarily by sealing off and halting the vaporizing flammable liquid. The foam blanket also cools the fuel and fire exposed structure or contents. The foam blanket must be applied to and/or be able to flow over the entire flammable liquid surface to extinguish it. Flammable liquid firefighting relies on the foam blanket, which can only be generated when the proper ratio of foam concentrate is added to the water stream. It is imperative for the proper operation of a foam system, and the ability to provide flammable liquid fire protection, that the foam proportioning system is functioning properly. 1.2 Requirements for Foam System Testing The annual foam test is a crucial part of plant maintenance, these systems in most cases protect the most hazardous and flammable part of the facility. There are many cases where the systems are not flushed after the original acceptance testing. These systems tend to have blockages and corrosion in concentrate supply and proportioning equipment. NFPA 11 requires annual inspection and testing. The goal of this inspection and testing is to ensure that the system is in full operating condition and that it remains in that condition until the next inspection (section ). NFPA 409 (section ) requires an operational test with actual foam discharge on the foam proportioning device every 5 years. NFPA 16 also requires annual testing. In addition, most states have made testing part of their revised codes. 1

4 1.3 Foam System Inspection and Testing A. Background of foam system test difficulties: 1. The cost of concentrate is in the range of $20 to $40 per gallon. 2. A test on a 1000 Gallon Bladder Tank could use from 50 to 200 Gallons of foam concentrate for a foam only cost of $1500 to $6, The disposal of the foam consists of three parts. Capturing the foam Transportation / Clean up Disposal 4. Capturing the foam / Trucks, Tankers, Drivers ($800 per day) 5. Disposal of foam / Waste water treatment Plant/ Incineration/ Recycling (.20 to 2.00 per gallon) 6. Clean up and spillage / Vacuum tanks and Trucks, Labor ($500 - $5000) 7. The ongoing testing has several obstacles The Facility management and the A.H.J having proper knowledge and training of the system. Coordinating a test that can involve: Plant, Environmental department, Safety, Maintenance, Production. Outside, AHJ, Underwriter, Fire Protection Contractor, Foam Manufacturer, Transport Company, Offsite disposal facility. The overall cost. 2

5 2.0 AQUA FOAM TEST METHOD 2.1 General Description of the Method In this document, the word system is used to refer to the actual installed foam system. An Aqua Foam test is a single run of the system with water used in place of foam concentrate. The word method is used to refer to the overall process of testing a foam system; including the initial foam system discharge test, the first Aqua Foam test, the Aqua Foam test apparatus and the follow on Aqua Foam tests. The method relies on an initial foam system discharge test to establish that the system is working properly and to determine the concentration the proportioner is developing. This test is conducted in the same fashion as any other foam proportioning system acceptance test. This test is immediately followed by an Aqua Foam test (AFT) at the exact same conditions as the initial foam discharge test. This is a patented method, U.S. Patent 7,080,694/7,513,315 and other patents pending. An Aqua Foam test essentially replaces the foam concentrate supply to the proportioner with water, see Figure 1 and Figure 2. The flow rate of the system and the flow rate of the water used in place of the concentrate are both measured with precision flow meters, and an AFT proportioning rate is established. The proportioning system can then be tested in the future by repeating an AFT and comparing the results to the initial AFT. Flow of foam concentrate is not necessary. As long as the water proportioning rate from the original AFT and the new AFT are within +/- 5 percent, or a limit established by the Authority Having Jurisdiction, the system is considered to be proportioning within the bounds of the original foam concentrate acceptance test. For a complete test of the operation of the foam system, the following would also typically be performed; a concentrate test (sample sent to the manufacturer or other test lab), a concentrate delivery test (the foam pump would be run and tested for pressure and flowrate at the proportioner the concentrate being returned to the tank), and a valve operation test (ensure all valves are operating properly), etc 3

6 2.2 Attributes of the Method After the initial foam system acceptance test, this method of foam proportioning system testing has several positive attributes over continuing tests with foam concentrate. These include: A. Cost savings of the foam concentrate. B. Water only testing which has no environmental or clean up concerns. C. Ability to allow the system to operate for longer period of time while only flowing water. D. Ability to vary the system operating parameters over a wide range of flow rates. E. Simple set-up of equipment and ease of conducting the tests. F. Meeting manufactures requirements for flushing the system with water. Currently, discharge testing of foam systems (outside of system acceptance testing) is rarely performed because of the cost, clean up, and complications. The advantages of this method could lead to a significant increase in the frequency of system testing and also to more thorough and complete testing. An increase in system reliability would be expected. For a new foam system installation (or possibly even for some existing systems), the required piping and/or instrumentation for Aqua Foam testing could be permanently included as part of the system. This would result in very efficient and inexpensive testing of the system, along the lines of a sprinkler system flow test. A cost comparison is shown in Table A Complete Foam System Inspection and Testing Program A. Describe as part of a complete test program for a foam system. 1. The foam concentrate sample must be sent to certified lab for testing 2. The foam pump flow rate and pressure which must meet manufactures specifications 3. All controllers and activation equipment must be tested 4. The system total water flow must be tested and verified 5. The level of the foam concentrate tank must be verified 6. All foam makers and nozzles must be inspected 7. The foam proportioning system must be tested 4

7 5

8 6

WILLIAM HICKS. MSc, CFEI, CFPS, IAAI-CFI, MIFireE, EFO, CFOD, F-IAFI. Associate Professor Eastern Kentucky University

WILLIAM HICKS. MSc, CFEI, CFPS, IAAI-CFI, MIFireE, EFO, CFOD, F-IAFI. Associate Professor Eastern Kentucky University Foam Systems WILLIAM HICKS MSc, CFEI, CFPS, IAAI-CFI, MIFireE, EFO, CFOD, F-IAFI Associate Professor Eastern Kentucky University William.Hicks@eku.edu Objectives Classify high, medium, and lowexpansion

More information

Foam Products ENGLISH

Foam Products ENGLISH Foam Products ENGLISH Tyco Fire & Building Products Foam Products Today s technological innovations bring chemical and material fire hazards. Our lines of sprinklers and alarm valves have an excellent

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE August 4, 2006 Foam 73a 1. DESCRIPTION Hi-expansion Water Powered High Expansion Foam Generators are designed to expand foam solution into millions of tiny stable bubbles. Expansion rates of 350 to 600

More information

SECURITY BLANKET Foam Fire Protection Products

SECURITY BLANKET Foam Fire Protection Products SECURITY BLANKET Foam Fire Protection Products REAL DANGERS DEMAND REAL SOLUTIONS If your business manufactures, stores, or transports flammable liquids, the thought of a devastating fire always burns

More information

Foam Systems U.S. Quick Reference Guide

Foam Systems U.S. Quick Reference Guide Foam Systems U.S. Quick Reference Guide This guide is intended for general reference only. Prior to the design, layout, and/or installation of any sprinkler system, please refer to Viking s technical documentation

More information

Technical Article. High Expansion Foam Systems. Martin Workman Viking Product Manager. September,

Technical Article. High Expansion Foam Systems. Martin Workman Viking Product Manager. September, Technical Article High Expansion Foam Systems Martin Workman Viking Product Manager September, 2008 Worldwide Fire Protection www.vikinggroupinc.com TABLE OF CONTENTS INTRODUCTION 3 SYSTEM DESIGN 5 SYSTEM

More information

A.U.P.C.I ASOCIACIÓN URUGUAYA DE PROTECCION CONTRA INCENDIO AUPCI

A.U.P.C.I ASOCIACIÓN URUGUAYA DE PROTECCION CONTRA INCENDIO AUPCI A.U.P.C.I ASOCIACIÓN URUGUAYA DE PROTECCION CONTRA INCENDIO Foam Overview Applications Flammable Liquid Storage Tanks Diked Storage Tanks Loading Racks/Transfer Stations Closed Head Sprinkler Systems Deluge

More information

TECHNICAL DATA 3% AR-AFFF

TECHNICAL DATA 3% AR-AFFF June 25, 21 Foam 14a The Viking Corporation, 21 N Industrial Park Drive, Hastings MI 4958 Telephone: 269-945-951 Technical Services: 877-384-5464 Fax: 269-818-168 Email: techsvcs@vikingcorp.com 1. DESCRIPTION

More information

Self Expanding Foam Fire Suppression System SPECIFICATION SHEET Rev

Self Expanding Foam Fire Suppression System SPECIFICATION SHEET Rev Self Expanding Foam Fire Suppression System SPECIFICATION SHEET Rev 1.0 03-07-2017 Description Self Expanding Foam Systems (SEFS) are the alternative solution to existing flammable and combustible liquid

More information

A Building Manager s Guide to Maintaining Fire Code Compliance

A Building Manager s Guide to Maintaining Fire Code Compliance A Building Manager s Guide to Maintaining Fire Code Compliance Know your role in conducting fire protection system inspections : Fire Alarm Codes and Standards Maintaining your compliance with fire code

More information

II Brazilian Sprinkler Conference October 27-28, 2016

II Brazilian Sprinkler Conference October 27-28, 2016 II Brazilian Sprinkler Conference October 27-28, 2016 1 Foam Sprinkler Systems Foam Basics 101 Foam systems components: Foam Concentrates Proportioning Equipment Discharge Devices Foam agent formulation

More information

Second Revision No. 11-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement

Second Revision No. 11-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement Second Revision No. 11-NFPA 16-2014 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 11, Standard for Low-, Medium-, and High-Expansion Foam, 2010 2015 edition. NFPA 13, Standard

More information

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why

More information

POLY extinguishing systems. The high-performance, unique, and versatile extinguishing system for initial, effective fire fighting.

POLY extinguishing systems. The high-performance, unique, and versatile extinguishing system for initial, effective fire fighting. POLY extinguishing systems The high-performance, unique, and versatile extinguishing system for initial, effective fire fighting. Rosenbauer POLY extinguishing systems Powerful CAFS firefighting equipment.

More information

MODULE 2. Water-Based Suppression System Basics

MODULE 2. Water-Based Suppression System Basics MODULE 2 Water-Based Suppression System Basics Based on the Ohio Building Code (OBC) National Fire Protection Association (NFPA) & Ohio Fire Code (OFC) 1 WATER-BASED SUPPRESSION SYSTEM BASICS-PART ONE

More information

Water Mist Fire Suppression

Water Mist Fire Suppression Water Mist Fire Suppression How less water has a big impact. HELPING PROTECT YOUR BUSINESS AND VALUED ASSETS WITH WATER MIST FIRE PROTECTION SYSTEM INTRODUCTION Many buildings have specific areas that

More information

The Next Generation of Foam Fire Suppression. Automatic CAF Fire hose reel system FEATURES

The Next Generation of Foam Fire Suppression. Automatic CAF Fire hose reel system FEATURES Fire hose reel system The first automatic CAF, fire hose reel system FEATURES The Automatic CAF Fire Hose Systems are ideal for firefighting needs in locations that require foam as a fire fighting agent.

More information

UFGS (June 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (June 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCESA / NASA UFGS-10 44 16 (May 2009) ------------------------- Preparing Activity: NASA Superseding UFGS-10 44 16 (June 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS References are in

More information

INSTRUCTOR GUIDE COURSE: FIREFIGHTER PRE-BASIC SESSION REFERENCE: 1 TOPIC: ORIENTATION AND FIRE BEHAVIOR LEVEL OF INSTRUCTION:

INSTRUCTOR GUIDE COURSE: FIREFIGHTER PRE-BASIC SESSION REFERENCE: 1 TOPIC: ORIENTATION AND FIRE BEHAVIOR LEVEL OF INSTRUCTION: COURSE: FIREFIGHTER PRE-BASIC SESSION REFERENCE: 1 INSTRUCTOR GUIDE TOPIC: ORIENTATION AND FIRE BEHAVIOR LEVEL OF INSTRUCTION: TIME REQUIRED: THREE HOURS MATERIALS: APPROPRIATE AUDIO VISUAL AIDS REFERENCES:

More information

Hazard Control Technologies, Inc.

Hazard Control Technologies, Inc. Hazard Control Technologies, Inc. Suggested Operating Guidelines Note: This information is submitted as a suggested guide to establish a Departmental SOG when using F-500 EA as part of your Hazard Control

More information

DEPARTMENT OF DEFENSE HANDBOOK COVERED STORAGE 1. THE FOLLOWING PAGES OF MIL-HDBK-1032/2 HAVE BEEN REVISED AND SUPERSEDE THE PAGES LISTED:

DEPARTMENT OF DEFENSE HANDBOOK COVERED STORAGE 1. THE FOLLOWING PAGES OF MIL-HDBK-1032/2 HAVE BEEN REVISED AND SUPERSEDE THE PAGES LISTED: NOTICE OF CHANGE INCH-POUND NOTICE 1 15 May 1999 TO ALL HOLDERS OF : DEPARTMENT OF DEFENSE HANDBOOK COVERED STORAGE 1. THE FOLLOWING PAGES OF HAVE BEEN REVISED AND SUPERSEDE THE PAGES LISTED: NEW PAGE

More information

Technical Article. Foam Systems - Low Expansion, Medium Expansion, High Expansion. Martin Workman, Product Manager Special Hazards Division

Technical Article. Foam Systems - Low Expansion, Medium Expansion, High Expansion. Martin Workman, Product Manager Special Hazards Division Technical Article Foam Systems - Low Expansion, Medium Martin Workman, Product Manager Special Hazards Division March, 2006 Worldwide Fire Protection www.vikingcorp.com TABLE OF CONTENTS DEFINITION - FOAM

More information

Airport Firefighter Recertification Core Competency Task Book

Airport Firefighter Recertification Core Competency Task Book 2011 Airport Firefighter Recertification Core Competency Task Book Agency:_ TASK BOOK ASSIGNED TO: INDIVIDUAL S PRINTED NAME & TITLE 1 2 DO NOT COMPLETE THIS UNLESS YOU ARE RECOMMENDING THE INDIVIDUAL

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-10 44 16 (May 2015) ------------------------ Preparing Activity: NASA Superseding UFGS-10 44 16 (May 2012) UNIFIED FACILITIES GUIDE SPECIFICATIONS References are in agreement

More information

FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION

FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT TECHNICAL DATA MODELS FCA-65, FCA-80 & FCA-100 FCA-150 Carbon Steel Construction INLET SIZE WORKING PRESSURE FCA-S 65, FCA-S 80 & FCA-S 100, FCA-S 150 Stainless

More information

Chapter 3 FF II Fire Department Communications

Chapter 3 FF II Fire Department Communications Chapter 3 FF II Fire Department Communications After completing this lesson, the student shall be able to discuss on-scene communications and postincident reports. 1. Describe the aspects that make up

More information

MSC Guidelines for Foam Fire Suppression Systems

MSC Guidelines for Foam Fire Suppression Systems References: S. T. Brady, CDR, Chief, Engineering Division a. 46 CFR 34.17, Tank Vessel Fixed Foam b. 46 CFR 34.20, Tank Vessel Deck Foam c. 46 CFR 76.17 Passenger Vessel Foam d. 46 CFR 95.17, Cargo Vessel

More information

Reducing the Cost and Risk of Dust Collection in Coal

Reducing the Cost and Risk of Dust Collection in Coal Reducing the Cost and Risk of Dust Collection in Coal Daniel Marshall, Martin Engineering 1 Martin Place, Neponset, IL, 61345, 1800-455-2947 ex 401 danielm@martin-eng.com Table of Contents 1. Background

More information

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

More information

The Combustion Process THE FIRE TETRAHEDRON FUEL TEMPERATURE

The Combustion Process THE FIRE TETRAHEDRON FUEL TEMPERATURE Worldwide Safety Services Fire Extinguisher Training D 1 Objectives Understand the combustion process and different fire classes. Understand d fire extinguisher i types, operating procedures, capabilities,

More information

5.0 CONTINGENCY PLAN. It is necessary to amend the plan if:

5.0 CONTINGENCY PLAN. It is necessary to amend the plan if: 5.0 CONTINGENCY PLAN This Contingency Plan for the Safety-Kleen Systems, Inc. - Denton Recycle Center is prepared in accordance with the requirements of 40 CFR 264 Subpart D and 40 CFR 264.37. The intent

More information

FOAM CHAMBER MODEL - FCA & FCA-S TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100. Stainless Steel Construction

FOAM CHAMBER MODEL - FCA & FCA-S TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100. Stainless Steel Construction MODEL - FCA & FCA-S TECHNICAL DATA MODELS FCA-65, FCA-80 & FCA-100 Carbon Steel Construction FCA-S 65, FCA-S 80 & FCA-S 100 Stainless Steel Construction INLET SIZE 65, 80, 100 NB WORKING Min 2.8 Kg/cm

More information

The requirements of BS Watermist Fire System standard and how to demonstrate compliance

The requirements of BS Watermist Fire System standard and how to demonstrate compliance The requirements of BS8489-1 Watermist Fire System standard and how to demonstrate compliance Bob Whiteley C. Eng.; F.I.Mech.E.; M.I.Fire E.; B.Tech(Hons) Chair: BSI Watermist Working Group Overview What

More information

FoamFatale INTRODUCTION OF A NOVEL HIGH END TECHNOLOGY FOR LARGE ATMOSPHERIC STORAGE TANK FIRES. TFEX 1 Ltd.

FoamFatale INTRODUCTION OF A NOVEL HIGH END TECHNOLOGY FOR LARGE ATMOSPHERIC STORAGE TANK FIRES. TFEX 1 Ltd. INTRODUCTION OF A NOVEL HIGH END TECHNOLOGY FOR LARGE ATMOSPHERIC STORAGE TANK FIRES TFEX 1 Ltd. FoamFatale technology makes it possible to make a huge step forward in protecting the environment against

More information

The Antifreeze Fire Sprinkler System Dilemma Eliminating One Issue has Opened the Door to Another. Jennifer Poynter, Esq. Charles B.

The Antifreeze Fire Sprinkler System Dilemma Eliminating One Issue has Opened the Door to Another. Jennifer Poynter, Esq. Charles B. The Antifreeze Fire Sprinkler System Dilemma Eliminating One Issue has Opened the Door to Another Jennifer Poynter, Esq. Charles B. Sullivan Wide Spread Impact of Code Changes Based on information available

More information

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 An Engineered Carbon Dioxide Fire Suppression System shall be installed to meet a minimum design concentration of %, by volume in all designated spaces/areas to be protected.

More information

A HISTORICAL REVIEW OF FLUORINATED FOAM FIREFIGHTING AGENTS, PERFORMANCE REQUIREMENTS/ ENVIRONMENTAL SAFEGUARDS REVIEW

A HISTORICAL REVIEW OF FLUORINATED FOAM FIREFIGHTING AGENTS, PERFORMANCE REQUIREMENTS/ ENVIRONMENTAL SAFEGUARDS REVIEW A HISTORICAL REVIEW OF FLUORINATED FOAM FIREFIGHTING AGENTS, PERFORMANCE REQUIREMENTS/ ENVIRONMENTAL SAFEGUARDS REVIEW CMDR (ret) John P. Farley, Naval Research Laboratory (NRL), and Joseph L. Scheffey,

More information

D. Reference Standards (Utilize latest editions available):

D. Reference Standards (Utilize latest editions available): 1.01 Scope of Standard A. This standard provides general requirements of The Sam Houston State University for fireextinguishing systems other than water-based fire suppression systems. This document is

More information

The development Of the new CEN standard For fire fighting foam systems EN13565 Part 2

The development Of the new CEN standard For fire fighting foam systems EN13565 Part 2 The development Of the new CEN standard For fire fighting foam systems EN13565 Part 2 Presented by: Bob Whiteley Engineering & Standards Manager Tyco Fire & Integrated Solutions Ltd Convenor CEN/TC191/WG2

More information

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1. A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

SPECIFICATION: ARGONITE Engineered Fire Suppression System

SPECIFICATION: ARGONITE Engineered Fire Suppression System 1. GENERAL SPECIFICATION 1.1 A total flooding, clean agent, fire suppression system, filled with Argonite agent shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.

More information

TWO TIMES THE FIGHT Twin-Agent Fire Suppression Systems

TWO TIMES THE FIGHT Twin-Agent Fire Suppression Systems TWO TIMES THE FIGHT Twin-Agent Fire Suppression Systems A TOUGH SOLUTION FOR TOUGH FIRES No fire should be taken lightly. Yet, there are some that go far beyond a typical fire. These extremely hazardous

More information

Antibiotic production by fermentation

Antibiotic production by fermentation Antibiotic production by fermentation Commodity: Antibiotic fermentation model SDL-1/3/5/7/10L Lab Scale Fermentor Aniaml Cell Vessel Fermentation of antibiotics details: 1. With compatible Price about

More information

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids. SECTION 211300 FIRE SUPPRESSION SYSTEMS 1.0 All new and renovated buildings shall be provided with automatic sprinklers throughout and fire standpipe systems. The design and installation of these systems

More information

Summary. firefighter training in Since that time the firefighter had attended semi-annual

Summary. firefighter training in Since that time the firefighter had attended semi-annual Summary On August 25, 2005 a live fire training exercise was conducted at a North Carolina County airport. Personnel involved in the training evolution were three employees of the airport who were employed

More information

BUILDING CODE INTERPRETATION

BUILDING CODE INTERPRETATION BUILDING CODE INTERPRETATION November 2017 14-BCI-009 Page 1 of 6 FIRE ALARM AND FIRE SUPPRESSION SYSTEM VERIFICATION AND TESTING CERTIFICATES PURPOSE This STANDATA has been developed to give municipalities

More information

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 FREQUENTLY ASKED QUESTIONS CONCERNING COMMERCIAL COOKING PROTECTION Published by FIRE ENGINEERING DIVISION

More information

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES SHIPPING NOTICE Maritime Authority of the Cayman Islands Head Office 3 rd Floor, Government Administration Building, 133 Elgin Avenue PO Box 2256, Grand Cayman, KY1-1107, Cayman Islands Tel: +1 345 949

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Public Comment No. 2-NFPA 16-2013 [ Section No. 3.3.6 ] 3.3.6* Foam-Water Sprinkler System. A piping network connected to a source of foam concentrate and to a water supply. The piping network is equipped

More information

Based on NFPA 1001: Standard for Fire Fighter Professional Qualifications, 2013 Edition.

Based on NFPA 1001: Standard for Fire Fighter Professional Qualifications, 2013 Edition. Based on NFPA 1001: Standard for Fire Fighter Professional Qualifications, 2013 Edition. Revised 02/10/2017 Alabama Fire College Firefighter II Instructional JPR Verification Sheet Full Name: Fire Department:

More information

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection 1. GENERAL SPECIFICATION 1.1 A total flooding, Novec 1230 fluid, fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in

More information

High-expansion foam plant UNI EN 13565

High-expansion foam plant UNI EN 13565 High-expansion foam plant UNI EN 13565 Protection of an automated storage tank for flammable liquids by means of a foam suppression system AUTHORS: Gianluca Galeotti Fire Safety Engineer - FSE PROGETTI

More information

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition. 1. GENERAL SPECIFICATION 1.1 A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

Setting the Standard in Third-party Certification

Setting the Standard in Third-party Certification Setting the Standard in Third-party Certification 1 Benefits enjoyed by FM Approvals customers FM Approvals can help you: Meet client demands Fulfill jurisdictional requirements Differentiate your product

More information

Summary. Introduction

Summary. Introduction Summary On March 8, 2006, a North Carolina Fire Department conducted Fire Ground Operations training under Live Fire Conditions at a 9600 cubic foot, 4 story fire training facility owned by the local community

More information

HIGH-EXPANSION FOAM GENERATORS

HIGH-EXPANSION FOAM GENERATORS HIGH-EXPANSION FOAM GENERATORS INSTALLATION, OPERATION, AND MAINTENANCE MANUAL 010040 One Stanton Street Marinette, WI 54143-2542, USA +1-715-735-7411 www.ansul.com 2018 Johnson Controls. All rights reserved.

More information

TN-25 Tunnel Fire Protection System. Safer. Smarter. Tyco.

TN-25 Tunnel Fire Protection System. Safer. Smarter. Tyco. TN-25 Tunnel Fire Protection System Safer. Smarter. Tyco. Expert Fire Protection for Tunnels Tyco provides a complete fire protection solution to protect the infrastructure of tunnels. Whether it is rail,

More information

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS 2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED

More information

Tel Web: dyayan.com

Tel Web: dyayan.com 1 Our Products DYAYAN specializes in three main areas: - Manufacturing of Dry Chemical Powders - Manufacturing of Foam Concentrates - Project designing, assembly and maintenance of Fire Safety Systems.

More information

EXHIBIT G REFRIGERANT MANAGEMENT POLICY

EXHIBIT G REFRIGERANT MANAGEMENT POLICY EXHIBIT G REFRIGERANT MANAGEMENT POLICY Table of Contents Refrigerant Manager... 3 Basic Refrigerant Management Policy... 3 Policy... 4 Tenant responsibility... 5 Contractor responsibility... 6 Sample

More information

Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015

Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015 Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015 Fire Protection I. INTRODUCTION II. GENERAL GUIDELINES III.

More information

junctioncrew.com FR28 INNOVATIVE PERFORMANCE MADE SIMPLE SUREFIRE SUREFIRE BLOCK HEATER THE INDUSTRY S STRONGEST WARRANTY HOSE HEATER

junctioncrew.com FR28 INNOVATIVE PERFORMANCE MADE SIMPLE SUREFIRE SUREFIRE BLOCK HEATER THE INDUSTRY S STRONGEST WARRANTY HOSE HEATER HEATING SYSTEM ADDITIONAL ACCESSORIES A super efficient heating system designed to save you time and money The Helix FR28 s advanced heating system provides direct heat starting the instant material enters

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

Above Ground Fuel Tank Requirements

Above Ground Fuel Tank Requirements FIRE DEPARTMENT in cooperation with Above Ground Fuel Tank Requirements The purpose of this document is to provide information about general Fire Code requirements for above ground storage within the unincorporated

More information

Linear Heat Detection Engineering Specifications

Linear Heat Detection Engineering Specifications Linear Heat Detection Engineering Specifications July, 2007 SAFE Fire Detection Inc. 5915 Stockbridge Dr. Monroe, NC 28110 Phone: (704) 821-7920 Fax: (704) 821-4327 Website: www.safefiredetection.com E-mail:

More information

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Michael Billstroem Director of International Technical Services The Reliable Automatic Sprinkler Co.,

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

AUTOMATIC FIRE SUPPRESSION SYSTEMS

AUTOMATIC FIRE SUPPRESSION SYSTEMS AUTOMATIC FIRE SUPPRESSION SYSTEMS Effective automatic fire suppression systems are essential for the fire protection of mechanical equipment and special technologies. CONTENTS RSBP FIRE PROTECTION OF

More information

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER HEATER 1. General Description The Contractor shall furnish and install (Qty) Yazaki model CH- Gas Fired,

More information

The 2012 Fire Suppression Rating Schedule (FSRS)

The 2012 Fire Suppression Rating Schedule (FSRS) The 2012 Fire Suppression Rating Schedule (FSRS) Summary of Changes March 21, 2017 How to Get a Copy of the FSRS Only FIRE CHIEFS may request a free copy of the FSRS. Submit (via e-mail only) an ATTACHED

More information

Portable Fire Extinguishers

Portable Fire Extinguishers Portable Fire Extinguishers Workbook Activities The following activities have been designed to help you. Your instructor may require you to complete some or all of these activities as a regular part of

More information

The Science Behind Water Mist Protection of Typical Building Hazards

The Science Behind Water Mist Protection of Typical Building Hazards The Science Behind Water Mist Protection of Typical Building Hazards SUPDET 2014 Zachary Magnone, P.E. Zachary.Magnone@tycofp.com Presentation Goals What is water mist? How does it work? How is it tested

More information

Making sense of risk Risk engineering. Metalworking operations

Making sense of risk Risk engineering. Metalworking operations Making sense of risk Risk engineering Metalworking operations Metalworking operations Metalworking operations involve the fabrication of ferrous or nonferrous metal products, structural metal products,

More information

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND 1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless

More information

Talking about NFPA History of NFPA NFPA Standard 1710: Organization and Deployment of Fire Suppression Operations, EMS

Talking about NFPA History of NFPA NFPA Standard 1710: Organization and Deployment of Fire Suppression Operations, EMS NFPA Standard 1710: Organization and Deployment of Fire Suppression Operations, EMS and Special Ops The History The Right Description and The 2015 Revision Recognized early aggressive and offensive primary

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

HKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009

HKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009 (II) 23, 25 June and 7, 9 July 2009 Organization by Co-organized by the Association of Registered Fire Service Installation contractors of Hong Kong Ltd (FSICA) Gas and Foam Suppression Systems Peter Bressington

More information

RIM SEAL SYSTEMS E-BOOK

RIM SEAL SYSTEMS E-BOOK RIM SEAL SYSTEMS E-BOOK RIM SEAL SYSTEMS Rim Seal floating roof tank fires represent one of the most dangerous threats for chemical and petrochemical storage farms. Industry data base shows that the oil

More information

MINIMAX FIRE PRODUCTS WHITE PAPER THE COST-BENEFIT ADVANTAGES OF REPLACING HALON WITH 725 PSI MX 1230 CLEAN AGENT FIRE SUPPRESSION SYSTEMS

MINIMAX FIRE PRODUCTS WHITE PAPER THE COST-BENEFIT ADVANTAGES OF REPLACING HALON WITH 725 PSI MX 1230 CLEAN AGENT FIRE SUPPRESSION SYSTEMS MINIMAX FIRE PRODUCTS WHITE PAPER THE COST-BENEFIT ADVANTAGES OF REPLACING HALON WITH 725 PSI MX 1230 CLEAN AGENT FIRE SUPPRESSION SYSTEMS Table of Contents The History behind Halon...3 Addressing the

More information

Handling Petroleum Products & Static Ignition Hazards Introduction

Handling Petroleum Products & Static Ignition Hazards Introduction Handling Petroleum Products & Static Ignition Hazards Introduction Static electricity in one form or another is a phenomenon of nature and often results in electrostatic discharges that can cause fires

More information

Economic Impact of Building Regulations

Economic Impact of Building Regulations Economic Impact of Building Regulations Resources from NFPA and the Fire Protection Research Foundation May 9, 2017 Amanda Kimball, P.E.: Research Director Agenda Background NFPA s statistical activities

More information

SECTION FM-200 FIRE SUPPRESSION SYSTEM

SECTION FM-200 FIRE SUPPRESSION SYSTEM SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to

More information

Twin-Agent Fire Fighting/Securing Systems Specifications

Twin-Agent Fire Fighting/Securing Systems Specifications Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50, 450/100, 900/100 & 1350/200 INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,

More information

The metering orifice is sized according to the type and percentage of concentrate used and is also secured with a stainless steel retaining ring)

The metering orifice is sized according to the type and percentage of concentrate used and is also secured with a stainless steel retaining ring) Legend: 1 Deluge Valve (DV-5) 2 Isolation Valve 3 Diaphragm Supply Valve 4 Manual Control Station 5 Automatic Shut-off Valve 6 Automatic Drain Valve 7 Pressure Switch 8 Water Motor Gong 9 Releasing Panel

More information

NEBOSH International Technical Certificate in Oil and Gas Operational Safety

NEBOSH International Technical Certificate in Oil and Gas Operational Safety IOG1 - Element 4 - Fire protection and emergency response July 2012 NEBOSH International Technical Certificate in Oil and Gas Operational Safety Licence details RMS Publishing Victoria House, Lower High

More information

The regulatory section first discusses codes and standards and then Federal and State legislative and local requirements.

The regulatory section first discusses codes and standards and then Federal and State legislative and local requirements. 4.7 FIRE PROTECTION AND EMERGENCY RESPONSE This section addresses the fire protection and emergency response resources related to the proposed Project. These resources include the existing services and

More information

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition

More information

Beneficial Use of Landfill Gas for Leachate Evaporation and Power Generation

Beneficial Use of Landfill Gas for Leachate Evaporation and Power Generation Beneficial Use of Landfill Gas for Leachate Evaporation and Power Generation Efficient use of Energy Turning waste to energy, liabilities to assets and visions into reality. Table of Contents BENEFICIAL

More information

JET-X HIGH-EXPANSION FOAM GENERATORS Data/Specifications

JET-X HIGH-EXPANSION FOAM GENERATORS Data/Specifications JET-X HIGH-EXPANSION FOAM GENERATORS Data/Specifications FEATURES Reliable, Water Motor Powered No Electrical Power Requirements Foam apacities to 28,800 FM (816 m 3 /m) UL Listed Models FM Approved Models

More information

FANERGY Far more than just a fan.

FANERGY Far more than just a fan. FANERGY Far more than just a fan. Protects emergency crews. Saves lives. 2 Rosenbauer FANERGY FANERGY Rosenbauer The crucial difference New All In One Airflow Technology Powerful Pull-out fan unit Largest

More information

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 Kenneth Kretchman, CIH, CSP Mgr, Industrial Hygiene NC State University Ken_Kretchman@ncsu.edu International Building

More information

Emergency shutdown systems. Procedures for bypassing ESD s

Emergency shutdown systems. Procedures for bypassing ESD s HYDROCARBON PROCESS SAFETY 2 - ELEMENT 3 - UNIT IOG1 Emergency shutdown systems Emergency shutdown systems (ESD s) are intended to minimise the consequences of emergency situations, for example, the uncontrolled

More information

CERTIFICATION SAFETY & BEYOND

CERTIFICATION SAFETY & BEYOND CERTIFICATION SAFETY & BEYOND Ferhun Emeksiz & R.M ( Max) Bradbury Client Manager & Fire Products Program Manager Global-Mark Pty Ltd Content Product Certification Understanding the framework Fundamental

More information

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The

More information

COUNTY OF BERGEN DEPARTMENT OF PUBLIC SAFETY LAW AND PUBLIC SAFETY INSTITUTE POLICE, FIRE & EMS ACADEMIES 281 Campgaw Road Mahwah, N.J.

COUNTY OF BERGEN DEPARTMENT OF PUBLIC SAFETY LAW AND PUBLIC SAFETY INSTITUTE POLICE, FIRE & EMS ACADEMIES 281 Campgaw Road Mahwah, N.J. COUNTY OF BERGEN DEPARTMENT OF PUBLIC SAFETY LAW AND PUBLIC SAFETY INSTITUTE POLICE, FIRE & EMS ACADEMIES 281 Campgaw Road Mahwah, N.J. 07430 (201)785-6000 Police FAX (201)785-6036 Fire FAX (201)785-6036

More information

Waste Recycling. Korn Recycling GmbH. Stationary Fire Protection Case Study

Waste Recycling. Korn Recycling GmbH. Stationary Fire Protection Case Study Waste Recycling Korn Recycling GmbH Stationary Fire Protection Case Study Rosenbauer Case Study Extinguishing Systems Korn Recycling Two successful enterprises. Korn and Rosenbauer leaders in their areas.

More information