Installing Foundation Fieldbus H1 in Hazardous Areas. Presented By: Jim Peterson Sr. Applications Engineer MTL/USA

Size: px
Start display at page:

Download "Installing Foundation Fieldbus H1 in Hazardous Areas. Presented By: Jim Peterson Sr. Applications Engineer MTL/USA"

Transcription

1 Installing Foundation Fieldbus H1 in Hazardous Areas Presented By: Jim Peterson Sr. Applications Engineer MTL/USA

2 (Divisions) (Zones) Zone 0 ia) Intrinsically Safe Class I Division 1 Explosion Proof Purged Intrinsic Safety Zone 1 (ia) and (ib) Intrinsically Safe (d) Flameproof (p) Pressurized (e) Increased Safety (q) Powder Filled (m) Encapsulation (o) Oil immersion Class I Division 2 All Types suitable for Division 1 and Nonincendive Zone 2 All types suitable for Zone 0 and 1 (n) Nonincendive Sub-catagories (na) Nonsparking Equip. (nc) Sparking Equip. with contacts protected (nr) Restricted breathing enclosure

3 What are the (Physical Layer) requirements for Hazardous Area FF H1 Installations?

4 A Hazardous Area Fieldbus Segment requires the following: An H1 Fieldbus Host A DC Bulk Power Supply certified for the area A certified Fieldbus Power Conditioner/ Barrier A set of 2 Terminators (1 at each end of a segment) integrated are acceptable Trunk and Spur cable certified for the area Certified (Spur Blocks) Field devices Certified for the area Spur Connectors (where appropriate)

5 Resides at the controller and will accept up to 32 FF Devices although a typical installation of a segment is less than 16 devices

6 A DC Power Source is required to supply the Power Conditioners 2 separate independent sources should power the Bulk Supplies AC line and Battery Backup or UPS typical Over-current protection should be provided for each feed supplying power to the FF Power Conditioners Negative Leg of supplies grounded Should be redundant

7 Power Conditioners must be used otherwise the power supply would absorb signals on the cable trying to maintain a constant voltage level (regulation). Power Conditioners use a circuit that allows the DC voltage on the wiring, but prevents the signal from being absorbed. Some Power Conditioners also provide other functions such as Intrinsic Safety or Repeater capabilities as with some FISCO Power Conditioner/Repeaters.

8 Matches impedance to eliminate reflections Two Required per Segment and for each repeated segment Terminators can be built into some devices such as the Power Conditioner/Repeaters 100 Ohms 1.0 μf

9 FISCO Field devices such as Transmitters and Valve Positioners,, Power Conditioners, and Inter-connecting active components (Spur Blocks with Short Circuit Protection), would have to comply with the Fieldbus Intrinsically Safe Concept (FISCO)

10

11 Point-to- Point Bus with Spurs Daisy-Chain Chicken foot

12 There are 2 ways to approach IS segments Entity Approach: FF816 Entity physical layer. This approach limits field devices to the allowable Capacitance and Inductance of the IS barriers as well as limiting the power available to the segment for these devices. Typically limited to a maximum of (80ma), 4 20ma field devices maximum FISCO Approach: FF816-FISCO The Fieldbus Intrinsically Safe Concept

13 Hazardous Area The Entity FF-816 approach Non- hazardous area SAFE AREA SAFE AREA HAZ. AREA HAZ. AREA MTL vdc bulk supply

14 Fieldbus Intrinsically Safe Concept

15 FISCO (A&B) Power Conditioner/ Repeaters: Up to 6, 20ma FISCO field devices can be applied per Power Conditioner/Repeater in Gas Groups A&B Conditioners/Repeaters are seen by the host as a field device A total of 4 FISCO Conditioner/Repeaters can be used with a single input to an H1 host The maximum # of FISCO devices, (24 field devices), can then be applied in Class I, Division 1, Gas Group A using a single H1 control card

16 UPS Hazardous area Class I, Division 1 or Zone 0, Gas Group A with FISCO approved Field Devices 120VAC H1 Controller Non-Hazardous Area IS FISCO Repeater Isolators Div2/Zone 2 Redundant Bulk DC Supplies Div1/Zone 0 Spur Blocks, Terminators, and FISCO Field Devices

17 FISCO (C&D) Power Conditioner/ Repeaters: Up to 12, 20ma FISCO field devices can be applied per power conditioner/repeater Conditioners/Repeaters are seen by the host as a field device The use of up to 4, FISCO conditioners per H1 host is allowable The maximum # of FISCO devices (a fully loaded segment 28 field devices), may be used in gas groups C&D utilizing a single H1 control card

18 Hazardous area Class I, Division 1, Gas Group C&D with FISCO approved Field Devices UPS 120VAC H1 Controller Non-Hazardous Area IS FISCO Repeater Isolators Div2/Zone 2 Redundant Bulk DC Supplies Div1/Zone 0 Spur Blocks, Terminators, and FISCO Field Devices

19 Entity Approved FF H1 devices can be used on FISCO segments using Spur Connectors Spur Connectors were developed as a temporary solution to the situation of Entity and FISCO interconnection Several solutions are available for various applications and Area Classifications. The use of the Spur Connectors allow a flexible approach to the FISCO concept.

20 Non-Hazardous (SAFE) Area FISCO P/C Hazardous Div 2/Zone 2 Area Spur Connector Class I, Division 1/Zone1 FISCO Devices Entity Approved device

21 Fieldbus Non Incendive Concept

22 This allows Division 2/Zone 2 installations to take advantage of more relaxed ignition curves to provide more power to FISCO or FNICO field devices The FNICO method is allowed to be used ONLY in Division 2/Zone 2 applications, and doesn t t account for faults as FISCO does.

23 H1 Controller Non-hazardous Area UPS 120VAC FNICO Repeater Isolators Hazardous area Class I, Division 2/ Zone 2, Gas Group A& B B with approved Field Devices Redundant Bulk DC Supplies Spur Blocks, Terminators, and FISCO or FNICO Field Devices

24 Protect critical components of segment H1 card and DC bulk supplies Power conditioners Susceptible spurs (long cable runs or with exposure to the elements) at the spur blocks Transmitters and Positioners with exposure risk

25 Protection for Trunk and critical Spurs Protection for Field devices Has no affect on communications Must be certified for Area Classification

26 120 vac SAFE AREA Power Conditioner MTL5995 SAFE AREA Spur Block

Installing Foundation Fieldbus in Hazardous Areas. Understanding your Options and How to Use Them

Installing Foundation Fieldbus in Hazardous Areas. Understanding your Options and How to Use Them Installing Foundation Fieldbus in Hazardous Areas Understanding your Options and How to Use Them Typical Fieldbus Topology Fieldbus-based Field Instruments Fieldbus-based Field Instruments CONTROL/RACK

More information

Fieldbus Non-Incendive Concept takes FISCO into Zone 2 and Division 2 hazardous areas. Phil Saward

Fieldbus Non-Incendive Concept takes FISCO into Zone 2 and Division 2 hazardous areas. Phil Saward Foundation Fieldbus End Users Council Australia Inc. 9 Corcoran St Duncraig, WA 6023 P.O.Box Z5546 Perth, WA 6831 AUSTRALIA ABN 60 120 236 370 Fieldbus Non-Incendive Concept takes FISCO into Zone 2 and

More information

PROCESS AUTOMATION APPLICATION AND SELECTION GUIDELINE FIELDCONNEX FIELDBUS INFRASTRUCTURE

PROCESS AUTOMATION APPLICATION AND SELECTION GUIDELINE FIELDCONNEX FIELDBUS INFRASTRUCTURE PROCESS AUTOMATION APPLICATION AND SELECTION GUIDELINE FIELDCONNEX FIELDBUS INFRASTRUCTURE Application and Selection Guideline Host Power Supply Junction Boxes FieldBarriers Segment Protectors Terminator

More information

Page 1 Copyright by the Fieldbus Foundation All rights reserved.

Page 1 Copyright by the Fieldbus Foundation All rights reserved. Page 1 Copyright by the Fieldbus Foundation 1996-2004.. FOUNDATION Fieldbus Application Guide 31,25 kbit/s Intrinsically Safe Systems AG-163 Revision 2.0 This application guide has been prepared to aid

More information

ACHIEVING REDUNDANT INTRINSICALLY-SAFE FIELDBUS SEGMENTS FOR FISCO & ENTITY DEVICES

ACHIEVING REDUNDANT INTRINSICALLY-SAFE FIELDBUS SEGMENTS FOR FISCO & ENTITY DEVICES Foundation Fieldbus End Users Council Australia Inc. P.O. Box Z5546 Perth AUSTRALIA 6831 ACHIEVING REDUNDANT INTRINSICALLY-SAFE FIELDBUS SEGMENTS FOR FISCO & ENTITY DEVICES Mike O Neill Director, MooreHawke

More information

D SYSTEM CONTROL DWG. APPROVED BY. OrCAD 6 ROSEMOUNT 2410

D SYSTEM CONTROL DWG. APPROVED BY. OrCAD 6 ROSEMOUNT 2410 FIELDBUS INTRINSICALLY SAFE CONCEPT (FISCO) APPROVAL FISCO allows interconnection of intrinsically safe apparatus to associated apparatus not specially examined in such combination. The criteria for interconnection

More information

UL Topic III. Converting European EEx Certificates. Into. North American Division Certificates

UL Topic III. Converting European EEx Certificates. Into. North American Division Certificates Note: While this material was originally prepared for presentation in February 1999, it has been updated to reflect the evolving technical requirements now applicable as of April 2003. UL Topic III Converting

More information

Safety instructions VEGADIF DF65.GX*****H/Z/P/F***** IECEx BVS

Safety instructions VEGADIF DF65.GX*****H/Z/P/F***** IECEx BVS Safety instructions VEGADIF DF65.GX*****H/Z/P/F***** IECEx BVS 10.0008 Ex td A20, A20/21, A20/22, A21 IP66 T 0044 37675 Contents 1 Area of applicability 3 2 General information 3 2.1 Zone 20 instruments

More information

Operating Instructions Edition 02/2007

Operating Instructions Edition 02/2007 Operating Instructions Edition 02/2007 Temperature Transmitter 7NG3214 with PROFIBUS PA 7NG3215 with FOUNDATION Fieldbus sitrans Introduction 1 General safety notes 2 SITRANS T Temperature transmitter

More information

Rosemount 752 Fieldbus Remote Indicator

Rosemount 752 Fieldbus Remote Indicator Product Data Sheet Rosemount 752 Rosemount 752 Fieldbus Remote Indicator ROSEMOUNT 752 DELIVERS: Two-wire segment powered device Displays up to 8 values Link Master Capability Optional PID, Characterizer,

More information

Airo Wireless Intrinsically Safe White Paper. Written By: David Schmitt

Airo Wireless Intrinsically Safe White Paper. Written By: David Schmitt Airo Wireless Intrinsically Safe White Paper Written By: David Schmitt Intrinsically Safe Cell Phone/Smartphone/PDA Intrinsically Safe (IS) is a protection certification for safe operation with electronic

More information

UL HAZARDOUS LOCATIONS SERVICES

UL HAZARDOUS LOCATIONS SERVICES UL HAZARDOUS LOCATIONS SERVICES The international preference in hazardous locations certification for over 100 years ul.com/hazloc Explosive Gas Atmospheres Class I Division S Includes flammable gases,

More information

Model 144H. Product Data Sheet , Rev DB February Content

Model 144H. Product Data Sheet , Rev DB February Content Rosemount 144 PC-Programmable Temperature Transmitter Provides an installation-ready solution for temperature monitoring applications using Complete Point Solutions (CPS) Increases measurement accuracy

More information

Annubar Flowmeter Series

Annubar Flowmeter Series Reference Manual Appendix B Approvals Annubar Flowmeter Series Hazardous Locations Installations.................. page B-1 Rosemount 3051SFA Product Certifications.......... page B-1 Rosemount 3095MFA

More information

Electronic Safety. Hazardous Location. By Jim Marquedant

Electronic Safety. Hazardous Location. By Jim Marquedant Requirements for Electronic Safety Equipment used in a Hazardous Location By Jim Marquedant Agenda FM Global & FM Approvals Overview Ignition In Hazardous Locations Evolution of Intrinsic Safety Recommendations

More information

Integrated redundant fieldbus power for FBM228 Foundation fieldbus modules High-density, compact design Fully isolated

Integrated redundant fieldbus power for FBM228 Foundation fieldbus modules High-density, compact design Fully isolated F0 -segment redundant fieldbus power system for use with Foxboro I/A Series Control System Integrated redundant fieldbus power for FBM Foundation fieldbus modules High-density, compact design Fully isolated

More information

Tank Gauging System Special Safety Instruction

Tank Gauging System Special Safety Instruction Tank Gauging System www.rosemount-tg.com Rosemount TankRadar REX Table of Contents Contents SPECIAL SAFETY INSTRUCTION........................ 1-1 1. GENERAL REQUIREMENTS....................... 1-2 1.1

More information

Enhanced FOUNDATION Fieldbus Physical Layer Diagnostics with the DeltaV System

Enhanced FOUNDATION Fieldbus Physical Layer Diagnostics with the DeltaV System November 2006 Page 1 Enhanced FOUNDATION Fieldbus Physical Layer Diagnostics This document provides possible solutions that allow enhanced Ff (FOUNDATION fieldbus) physical layer diagnostics using the

More information

PROZESSAUTOMATION. Manual SEGMENT PROTECTOR R-SP-!12. Zone 1 Zone 2 / Div 2 FNICO

PROZESSAUTOMATION. Manual SEGMENT PROTECTOR R-SP-!12. Zone 1 Zone 2 / Div 2 FNICO PROZESSAUTOMATION Manual SEGMENT PROTECTOR R-SP-!12 FieldConnex TM Segment Protectors with overloaod protection and short-circuit current limitation for the connection of 12 field devices Zone 1 Zone 2

More information

BA488CF Intrinsically safe Panel mounting Fieldbus Display

BA488CF Intrinsically safe Panel mounting Fieldbus Display BA488CF Intrinsically safe Panel mounting Fieldbus Display Issue: 8 Issue: 8 8 th May 2006 2 CONTENTS 1. Description 1.1 Documentation 1.2 Version 2.0 firmware 2. Operation 2.1 Controls 3. Intrinsic Safety

More information

Model 144H. Product Data Sheet , Rev DB February Content

Model 144H. Product Data Sheet , Rev DB February Content Rosemount 144 PC-Programmable Temperature Transmitter Provides an installation-ready solution for temperature monitoring applications using Complete Point Solutions (CPS) Increases measurement accuracy

More information

A Guide to Safe Electronic Weighing in Hazardous Locations

A Guide to Safe Electronic Weighing in Hazardous Locations SMART SOLUTIONS FOR DEMANDING INDUSTRIES Solutions for Process Weighing and Force Measurement Handbook TC0013 1. Hazardous Locations... 2 2. Methods of Protection... 3 3. Approval/Listing of Equipment...

More information

Engineering Guideline. pac-carriers Type SIEMENS ET-200M Fail-safe signal modules

Engineering Guideline. pac-carriers Type SIEMENS ET-200M Fail-safe signal modules Engineering Guideline pac-carriers Type 9195 SIEMENS ET-200M Fail-safe signal modules pac-carrier Type 9195 2 Engineering Guideline/SIEMENS 19.05.2015 pac-carrier Type 9195 Integration of conventional

More information

Engineering Guideline. pac- Carriers Type Universal

Engineering Guideline. pac- Carriers Type Universal Engineering Guideline pac- Carriers Type 9195 Universal Integration of conventional process automation interfaces pac- Carrier The pac- Carrier reflects the intention of R. STAHL to provide state-of-the-art

More information

YTA Series Temperature Transmitters [Style: S3] EN :2006, -11:2007, -26:2007. Supply circuit: Ui=30 V, Ii=165 ma,

YTA Series Temperature Transmitters [Style: S3] EN :2006, -11:2007, -26:2007. Supply circuit: Ui=30 V, Ii=165 ma, User s Manual YTA Series Temperature Transmitters [Style: S3] Manual Change No. 10-008 Please use the attached sheets in the following manuals when the product is with /KU2 option and EN60000 Series based

More information

Fieldbus Foundation TM Bus diagnostics and troubleshooting

Fieldbus Foundation TM Bus diagnostics and troubleshooting Fieldbus Foundation TM Bus diagnostics and troubleshooting Andreas Agostin MTL Instruments Pte Ltd Singapore On behalf of Fieldbus Foundation TM Marketing Committee (Malaysia) 1 Bus diagnostics and troubleshooting

More information

Competence for Safety. ATEX Category 3 Description. Example of a zone division for combustible fluids (gases) and combustible dust

Competence for Safety. ATEX Category 3 Description. Example of a zone division for combustible fluids (gases) and combustible dust Competence for Safety Within the scope of the creation of the explosion protection document (mandatory for the operator according to ATEX 137), production locations must be divided into zones depending

More information

Installation guide for hazardous areas

Installation guide for hazardous areas Installation guide for hazardous areas This installation guide should not be used as the controlling document for the installation of devices in a hazardous area. This guide is NOT A CONTROL DRAWING. Any

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 14 FROM: Kimberly Shea DATE:

More information

Application Guideline. FOUNDATION TM fieldbus for LEPIU. Prepared by: Thomas Klatt Business Development Manager

Application Guideline. FOUNDATION TM fieldbus for LEPIU. Prepared by: Thomas Klatt Business Development Manager FOUNDATION TM fieldbus for LEPIU The TDC 2000 and TDC 3000 Low Energy Process Interface Unit (LEPIU) provides termination and pre-processing of various temperature signals. Due to the age of various components,

More information

Intrinsic Safety Solenoid Valves :-

Intrinsic Safety Solenoid Valves :- Intrinsic Safety Solenoid Valves :- Intrinsic safety valves can be used for applications that require similar explosion class/ignition degree to d2g4 or Exd II BT5 type (explosion-proof enclosure construction).

More information

User s Manual YTA610 and YTA710 NEPSI Certification

User s Manual YTA610 and YTA710 NEPSI Certification User s Manual YTA60 and YTA70 NEPSI Certification [Option code: /NS, /NS5 and /NF] st Edition . INTRODUCTION Thank you for purchasing the YTA60 and YTA70 Temperature transmitters. This manual contains

More information

Technical Information

Technical Information Technical Information Explosion Protection Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5634 Fax.: 81-422-52-9802 Copyright May 2004 (YK) 15th Edition

More information

Pepperl+Fuchs GmbH Lilienthalstrasse Mannheim Germany

Pepperl+Fuchs GmbH Lilienthalstrasse Mannheim Germany PR-2010-1124PA-eng-Fieldbus planning Pepperl+Fuchs GmbH Lilienthalstrasse 200 68307 Mannheim Germany Please indicate the following contact information for publication: Tel.: +49 621 776-2222, Fax: +49

More information

technical datasheet technical datasheet

technical datasheet technical datasheet technical datasheet technical datasheet F0 redundant fieldbus poer for Yokogaa CENTUM 000 R Control System Integrated redundant fieldbus poer for ALF Foundation fieldbus cards -segment redundancy High-density,

More information

Instrumentation Products and Applications

Instrumentation Products and Applications 1 1/0 Instrumentation Products and Applications 1 Instrumentation Safety barriers I.S. Isolators - DIN rail mounting - Eurocards - Modules Remote I/O Operating and monitoring systems Instrumentation systems

More information

Numerical Standards Listing

Numerical Standards Listing Numerical Standards Listing ISA-RP2.1-1978 - Manometer Tables ISA-5.1-1984 (R1992) - Instrumentation Symbols and Identification (Formerly ANSI/ISA-5.1-1984 [R1992]) ISA-5.2-1976 (R1992) - Binary Logic

More information

Certificate of Compliance

Certificate of Compliance FF0002 Certificate of Compliance Certificate: 70009779 Issued to: Pepperl+Fuchs GmbH Lilienthalstrasse 200 Mannheim, 68307 GERMANY Attention: Martin Holdefer The products listed below are eligible to bear

More information

Rosemount 8800D Series Vortex Flowmeter

Rosemount 8800D Series Vortex Flowmeter Quick Installation Guide Rosemount 8800D Rosemount 8800D Series Vortex Flowmeter Start Step 1: Mount the Flowmeter Step 2: Consider Housing Rotation Step 3: Set Jumpers and Switches Step 4: Connect Wiring

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance Certificate: 1055868 (LR 44092) Master Contract: 152450 Issued to: Micro Motion Incorporated 7070 Winchester Cir Boulder, CO 80301 USA Attention: Ray C. Stengl The products listed

More information

Additional Information. Introduction. Temperature transmitter for all communications protocols. Redundancy thanks to two inputs. Measurement made easy

Additional Information. Introduction. Temperature transmitter for all communications protocols. Redundancy thanks to two inputs. Measurement made easy ABB MEASUREMENT & ANALYTICS COMMISSIONING INSTRUCTION TTF300 Field-mount temperature transmitter Temperature transmitter for all communications protocols. Redundancy thanks to two inputs. Measurement made

More information

Rosemount 3144P Rosemount 3144P Temperature Transmitter

Rosemount 3144P Rosemount 3144P Temperature Transmitter Temperature Transmitter Sensor Drift Alert and Hot Backup features improve measurement reliability while the Transmitter-Sensor Matching feature improves temperature measurement accuracy Statistical Process

More information

Certificate of Compliance

Certificate of Compliance FF0002 Certificate of Compliance Certificate: 2792948 Issued to: Siemens Canada Limited 1954 Technology Drive Peterborough, ON K9J 7B1 Canada Attention: Mr. Lee Rogers The products listed below are eligible

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD IEC 61892-7 INTERNATIONAL STANDARD Edition 2.0 2007-11 Mobile and fixed offshore units Electrical installations Part 7: Hazardous areas INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XA ICS 47.020.60

More information

The R. STAHL Technology Group Worldwide Success with Competence and Customer Support

The R. STAHL Technology Group Worldwide Success with Competence and Customer Support The R. STAHL Technology Group Worldwide Success with Competence and Customer Support The entrepreneurial basis of the R. STAHL Technology Group follows a long tradition. The product range is aimed at specialised

More information

Metal Tube Variable Area Flowmeter with Optional Electronics based on Smart Meter Manager Technology

Metal Tube Variable Area Flowmeter with Optional Electronics based on Smart Meter Manager Technology Data Sheet Brooks Model MT 3810 Metal Tube Variable Area Flowmeter with Optional Electronics based on Smart Meter Manager Technology GENERAL FEATURES Broad range of flow capacities 5% Full scale accuracy

More information

User s Manual. EJA Series Differential Pressure and Pressure Transmitters Installation Manual. 1. Introduction. 2. Handling Cautions. 3.

User s Manual. EJA Series Differential Pressure and Pressure Transmitters Installation Manual. 1. Introduction. 2. Handling Cautions. 3. User s Manual EJA Series Differential Pressure and Pressure Transmitters Installation Manual 1. Introduction 1.1 For Safe Use of Product...2 1.2 Warranty...3 1.3 ATEX Documentation...4 2. Handling Cautions

More information

Intrinsic Safety. Intrinsically Safe Solutions. Accurate Weighing in Hazardous Areas

Intrinsic Safety. Intrinsically Safe Solutions. Accurate Weighing in Hazardous Areas Intrinsic Safety Intrinsically Safe Solutions Accurate Weighing in Hazardous Areas Accidents in hazardous areas can have dramatic consequences for businesses in terms of both human life and profit. Intrinsically

More information

INSTRUCTION MANUAL. SIL 3 - SIL 2 IIB Group Power Supply for Hazardous Area Equipment DIN-Rail Model PSD1001C PSD1001C

INSTRUCTION MANUAL. SIL 3 - SIL 2 IIB Group Power Supply for Hazardous Area Equipment DIN-Rail Model PSD1001C PSD1001C PSD1001C INSTRUCTION MANUAL SIL 3 SIL 2 IIB Group Power Supply for Hazardous Area Equipment DINRail Model PSD1001C PSD1001C SIL 3 SIL 2 IIB Group Power Supply for hazardous Area Equipment ISM006510 General

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 17065:2012 to provide product conformity certification Newport Business Park New Port Road Ellesmere Port CH65 4LZ United Kingdom Contact:

More information

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA. Additional Operating Instructions SITRANS F Vortex flowmeters Ex-nA Edition 08/207 CONTENTS Safety instructions 3. General notes... 3.2 EU conformity... 3.3 Approval according to the IECEx scheme... 3.4

More information

Engineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS

Engineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS Engineering Guideline pac-carriers Type 9195 for Yokogawa ProSafe-RS 2 Engineering Guideline / Yokogawa ProSafe-RS 06.06.2017 Integrated solutions for Yokogawa R. STAHL offers a wide range of customized

More information

Two global companies, one solution.

Two global companies, one solution. Two global companies, one solution. About the Partnership March 2002, Yokogawa Electric Corportation, Japan and Pepperl+Fuchs Germany signed a Global Preferred Vendor Agreement. Solutions found in this

More information

Segment design & and Bus Diagnostics

Segment design & and Bus Diagnostics Segment design & and Bus Diagnostics Arasu Thanigai Business Development Manager Pepperl+Fuchs Pte Ltd, Singapore On behalf of FF End user Council Taiwan 1 Taiwan FF Seminar Part1 - Segment design & Verification

More information

RADAR LEVEL GAUGE SPECIAL SAFETY INSTRUCTION

RADAR LEVEL GAUGE SPECIAL SAFETY INSTRUCTION Special Safety Instruction en RADAR LEVEL GAUGE SPECIAL SAFETY INSTRUCTION Contents TankRadar Pro European ATEX Directive Information............................... 2 ATEX marking and Ex Certification

More information

SmartLine. RMA803 SmartLine Remote Fieldbus Indicator Specification 34-ST-03-90, December Technical Information.

SmartLine. RMA803 SmartLine Remote Fieldbus Indicator Specification 34-ST-03-90, December Technical Information. SmartLine Technical Information RMA803 SmartLine Remote Fieldbus Indicator Specification 34-ST-03-90, December 2015 Introduction The Honeywell RMA803 is a Foundation Fieldbus remote indicator suitable

More information

Temperature Measurement Transmitters for field mounting

Temperature Measurement Transmitters for field mounting Siemens AG 07 Overview Application The SITRANS TF can be used everywhere where temperatures need to be measured under particularly harsh conditions. For that reasons users from all industries have opted

More information

Assembly. Host Sub-D Alarm

Assembly. Host Sub-D Alarm HighDensity Power Hub, Generic Interface Features Assembly 4 segments, loadsharing redundancy Output: 22... 24 V/360 ma, Ex ib IIC for intrinsically safe, highpower segments Redundant connection to PROFIBUS

More information

PROCESS AUTOMATION PRECISE VALUES LEVEL MEASUREMENT TECHNOLOGY

PROCESS AUTOMATION PRECISE VALUES LEVEL MEASUREMENT TECHNOLOGY PROCESS AUTOMATION PRECISE VALUES LEVEL MEASUREMENT TECHNOLOGY POINT LEVEL DETECTION In applications like overfill protection, min/max control, or overflow and dry-run protection, the limit value switches

More information

Ar-Mite TM Low Flow Armored Flowmeter

Ar-Mite TM Low Flow Armored Flowmeter Data Sheet Brooks Ar-Mite TM MT 3750C Ar-Mite TM Low Flow Armored Flowmeter Ar-Mite TM Model MT 3750 Metal Tube Flowmeter Ar-Mite TM Model MT 3750 Metal Tube Flowmeter with Transmitter or Inductive Alarm

More information

Rosemount 2051T In-Line Pressure Transmitter

Rosemount 2051T In-Line Pressure Transmitter Rosemount 2051T In-Line Pressure Transmitter 2051T In-Line Wireless Pressure Transmitter Configuration Transmitter Output Code 4-20 ma HART 2051 A 2051 with Selectable HART (1) Lower Power 2051 2051 with

More information

ARC BRIEF. MTL: Expanding Opportunities with a Focus on Fundamentals. Keywords. Summary. Analysis THOUGHT LEADERS FOR MANUFACTURING & SUPPLY CHAIN

ARC BRIEF. MTL: Expanding Opportunities with a Focus on Fundamentals. Keywords. Summary. Analysis THOUGHT LEADERS FOR MANUFACTURING & SUPPLY CHAIN ARC BRIEF OCTOBER 7, 2008 MTL: Expanding Opportunities with a Focus on Fundamentals By Larry O'Brien Keywords MTL, Cooper Crouse-Hinds, Elpro, Tofino, Intrinsically Safe Ethernet, Redundant FISCO, Wireless

More information

Guide for hazardous areas

Guide for hazardous areas Guide for hazardous areas 1 Hazardous areas definitions 2 Gas and dust s 3 Temperature classifications 4 Common flammable gases, vapours and dust types 5 Protection concepts ATEX and IECEx 6 Protection

More information

OilSET-1000 (12 VDC)

OilSET-1000 (12 VDC) Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 Internet: www.labkotec.fi 20.03.2009 1/11 OilSET-1000 (12 VDC) Oil Separator Alarm Device Copyright 2009

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 17065:2012 to provide product conformity certification Unit 16-18 Abenbury Way Wrexham Industrial Estate Wrexham LL13 9UZ United Kingdom Contact:

More information

Rosemount 8800D Series Vortex Flowmeter

Rosemount 8800D Series Vortex Flowmeter Product Data Sheet May 2013 00813-0100-4004, Rev JB Rosemount 8800D Series Vortex Flowmeter Hart and FOUNDATION fieldbus Protocols All welded, non-clog design provides maximum performance, reliability

More information

... RD0-TI-Ex8.FF.* Temperature Multi-Input Device for Cabinet Installation. Features. Assembly. Function. Connection. Zone 1

... RD0-TI-Ex8.FF.* Temperature Multi-Input Device for Cabinet Installation. Features. Assembly. Function. Connection. Zone 1 emperature Multi-Input Device for Cabinet Installation Features Assembly For 8 temperature or analog sensors Installation in Zone 1/Div. 1, intrinsically safe Sensors in Zone 0/Div. 1 Connection to fieldbus

More information

IS (Intrinsic safety) - Ex (Epsilon x) ATEX CENELEC

IS (Intrinsic safety) - Ex (Epsilon x) ATEX CENELEC IS (Intrinsic safety) - Ex (Epsilon x) ATEX CENELEC By: Helge Knudsen, Test&Approval, Niros Telecommunication A/S You may have heard those expressions concerning Transceivers and other electric equipment

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

OilSET Installation and Operating Instructions. Oil Separator Alarm Device Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 18.11.2010 Internet: www.labkotec.fi 1/10 OilSET-1000 Oil Separator Alarm Device Copyright 2010 Labkotec

More information

HOW TO FIND THE RIGHT DEVICE FOR YOUR FACILITY

HOW TO FIND THE RIGHT DEVICE FOR YOUR FACILITY HOW TO FIND THE RIGHT DEVICE FOR YOUR FACILITY Cell Phones Smartphones PDA integrating people, products and processes Intrinsically Safe Cell Phone/Smartphone/PDA Intrinsically Safe (IS) is a protection

More information

SET-2000 Hi Level/Oil

SET-2000 Hi Level/Oil Labkotec Oy Labkotie 1 FI-36240 KANGASALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 13.03.2008 Internet: www.labkotec.fi Alarm Device for Oil Separators Copyright 2008 Labkotec Oy We reserve

More information

Instructions Dual Spectrum Infrared Flame Detector PM-5MPX. 4.1 Rev: 8/

Instructions Dual Spectrum Infrared Flame Detector PM-5MPX. 4.1 Rev: 8/ Instructions 95-8562 Dual Spectrum Infrared Flame Detector Rev: 8/13 95-8562 Table of Contents Application... 1 Detector use in hazardous areas... 2 Electrical Characteristics.... 2 Environmental Characteristics...

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor Labkotec UK Ltd Adminicle House 1 Lumb Lane Audenshaw Manchester M34 5WH GREAT BRITAIN Tel: 0844 3350 477 Fax: 0161 4281 179 E-mail: info@labkotec.co.uk 10.8.2012 Internet: www.labkotec.co.uk 1/13 OilSET-1000

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance Certificate: 1655492 (219995) Issued to: R.C. Systems Co., Inc. 8621 Hwy 6 Hitchcock, Texas 77563 USA Attention: Roger Carter The products listed below are eligible to bear the

More information

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions SET-000 Oil/Sludge Alarm Device for Oil Separators Copyright 007 Labkotec Oy We reserve the right for changes without notice TABLE OF CONTENTS GENERAL... INSTALLATION... 4. SET-000 Oil/Sludge Control Unit...

More information

TECHNICAL SOLUTIONS APPLICABLE TO ELECTRICAL EQUIPMENTS DESIGNED FOR USE IN EXPLOSIVE GAS ATMOSPHERES

TECHNICAL SOLUTIONS APPLICABLE TO ELECTRICAL EQUIPMENTS DESIGNED FOR USE IN EXPLOSIVE GAS ATMOSPHERES TECHNICAL SOLUTIONS APPLICABLE TO ELECTRICAL EQUIPMENTS DESIGNED FOR USE IN EXPLOSIVE GAS ATMOSPHERES TECHNICAL SOLUTIONS APPLICABLE TO ELECTRICAL EQUIPMENTS DESIGNED FOR USE IN EXPLOSIVE GAS ATMOSPHERES

More information

Temperature measurement with SITRANS T siemens.com/processinstrumentation

Temperature measurement with SITRANS T siemens.com/processinstrumentation Top values in precision and reliability Temperature measurement with SITRANS T siemens.com/processinstrumentation Temperatures firmly under control Top process quality and efficiency are key factors for

More information

Rosemount 752 FOUNDATION Fieldbus Remote Indicator

Rosemount 752 FOUNDATION Fieldbus Remote Indicator Rosemount 752 FOUNDATION Fieldbus Remote Indicator Product Data Sheet 00813-0100-4377, Rev FA Two-wire segment powered device Displays up to eight values Link Master Capability Optional PID, Characterizer,

More information

SET Installation and Operating Instructions. Level switch for one sensor

SET Installation and Operating Instructions. Level switch for one sensor Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel.: +358 29 006 260 Fax: +358 29 006 1260 7.11.2013 Internet: www.labkotec.fi 1/14 SET-1000 Level switch for one sensor Copyright 2013 Labkotec Oy

More information

Official Journal of the European Union

Official Journal of the European Union C 20/16 27.1.2009 Commission communication in the framework of the implementation of the Directive 94/9/EC of the European Parliament and the Council on the approximation of the laws of the Member States

More information

operational excellence Solutions for

operational excellence Solutions for PROCESS AUTOMATION operational excellence Solutions for HONEYWELL control SYSteMS Solutions for HoneYwell control SYStems Trusted Interface Technology Pepperl+Fuchs isolated barriers guarantee safe, reliable

More information

Technical Information

Technical Information Technical Information Explosion Protection Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5634 Fax.: 81-422-52-9802 Copyright May 2004 (YK) 23rd Edition

More information

IECEx Certificate of Conformity

IECEx Certificate of Conformity IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate IECEx

More information

Today's world of increasing

Today's world of increasing Applying Intrinsic Safety Today's world of increasing process control in potentially explosive atmospheres has forced designers and engineers to specify more efficient and effective ways of protecting

More information

Dräger Polytron 8310 IR Detection of flammable gases and vapour

Dräger Polytron 8310 IR Detection of flammable gases and vapour Dräger Polytron 8310 IR Detection of flammable gases and vapour The Dräger Polytron 8310 IR is an advanced explosion proof transmitter for the detection of combustible gases in the lower explosion limit

More information

Brooks MT3750 Low Flow Armored Flowmeter

Brooks MT3750 Low Flow Armored Flowmeter Brooks MT3750 Low Flow Armored Flowmeter ArMite TM Model MT3750 Metal Tube Flowmeter ArMite TM Model MT3750 Metal Tube Flowmeter with Transmitter or Inductive Alarm Benefits: Wetted Parts made from Stainless

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance Certificate: 2007104 Master Contract: 223077 Issued to: Purge Solutions 2201 North Highway 35 Bypass Suite C Alvin, TX 77511 USA Attention: Wallace Trochesset The products listed

More information

Rosemount 2051T In-line Pressure Transmitter

Rosemount 2051T In-line Pressure Transmitter February 2017 T In-line Pressure Transmitter T In-line Wireless Pressure Transmitter Configuration 4 20 ma HART with Selectable HART (1) Lower Power with Selectable HART (1) FOUNDATION Fieldbus PROFIBUS

More information

DB5 Intrinsically Safe Sounder Type DB-5

DB5 Intrinsically Safe Sounder Type DB-5 Operating Instructions RTK Instruments Limited DB5 Intrinsically Safe Sounder Type DB-5 Description The DB5 Sounder is a strong, lightweight warning sounder, CENELEC certified to Ex II 1G EExia IIC T4

More information

Intrinsically Safe Solutions

Intrinsically Safe Solutions Intrinsically Safe Solutions INSTALLATION MANUAL 04/12/14 Rev D DOC-01-029 Documentation Feedback Your feedback helps us keep our documentation up to date and accurate. If you have any comments or suggestions

More information

Inductive slot sensor

Inductive slot sensor 0102 Model Number Features 2 mm slot width Technical Data specifications Switching function Normally closed (NC) Output type NAMUR Slot width 2 mm Depth of immersion (lateral) 5... 7 mm, typ. 6 mm Output

More information

Rosemount 3144P Temperature Transmitter

Rosemount 3144P Temperature Transmitter Temperature Transmitter Sensor Drift Alert and Hot Backup features improve measurement reliability while the Transmitter-Sensor Matching feature improves temperature measurement accuracy Statistical Process

More information

Rosemount 3051CFC Compact Flowmeter

Rosemount 3051CFC Compact Flowmeter CFC Compact Flowmeter CFC Compact Flowmeters provide a quick, reliable installation between existing raised face flanges. Depending on your application needs, you can reduce energy loss with the Compact

More information

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d. Additional Operating Instructions SITRANS F Vortex flowmeters Ex-d Edition 09/208 CONTENTS Safety instructions 3. General notes... 3.2 EU conformity... 3.3 Approval according to the IECEx scheme... 3.4

More information

Rosemount 2051 Pressure Transmitter with 4-20 ma HART and 1-5 Vdc HART Low Power Protocol

Rosemount 2051 Pressure Transmitter with 4-20 ma HART and 1-5 Vdc HART Low Power Protocol Quick Installation Guide August 2009 Rosemount 2051 Rosemount 2051 Pressure Transmitter with 4-20 ma HART and 1-5 Vdc HART Low Power Protocol Start Step 1: Mount the Transmitter Step 2: Consider Housing

More information

5.1 Safety instructions for system configuration and explosion protection. Zone-specific conditions for system configuration

5.1 Safety instructions for system configuration and explosion protection. Zone-specific conditions for system configuration Planning and configuration of the I.S. 1 system 5 ENGINEERING 5.1 Safety instructions for system configuration and explosion protection During engineering, comply with the guidelines set out in EN 60 079-14.

More information

Introduction to Bulk Solids. The Basics

Introduction to Bulk Solids. The Basics Introduction to Bulk Solids The Basics Glossary of Terms Angle of Repose This is the angle that material will naturally mound up when filling a tank, or down when discharging a tank. Dielectric Constant

More information

Quick Start Guide , Rev CB May Rosemount 3144P Temperature Transmitters with FOUNDATION fieldbus Protocol

Quick Start Guide , Rev CB May Rosemount 3144P Temperature Transmitters with FOUNDATION fieldbus Protocol Quick Start Guide 00825-0100-4834, Rev CB Rosemount 3144P Temperature Transmitters with FOUNDATION fieldbus Protocol Quick Start Guide NOTICE NOTICE This guide provides basic guidelines for the Rosemount

More information

NET9000 Fieldbus Connections 912x-IS FISCO power supplies

NET9000 Fieldbus Connections 912x-IS FISCO power supplies NET9000 Fieldbus Connections 912x-IS FISCO power supplies Instruction Manual INM9120-5 CONTENTS INM9120-5 July 2004 1 ABOUT THIS MANUAL...................................................... 1 1.1 Product

More information

Rosemount 848T FOUNDATION Fieldbus High Density Temperature Transmitter

Rosemount 848T FOUNDATION Fieldbus High Density Temperature Transmitter Quick Start Guide 00825-0100-4697, Rev SF Rosemount 848T FOUNDATION Fieldbus High Density Temperature Transmitter Device Revision 8 - Requires New DD/CFF Revision Quick Start Guide NOTICE This guide provides

More information