MEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems

Size: px
Start display at page:

Download "MEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems"

Transcription

1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: MEMORANDUM TO: FROM: Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems Jenny Depew, Project Administrator DATE: November 17, 2016 SUBJECT: NFPA 72 First Draft Technical Committee FINAL Ballot Results (A2018) According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. 26 Members Eligible to Vote 2 Members Not Returned (Hall, Merrick) 22 Members Voted Affirmative on All Revisions 0 Members Voted Affirmative w/ Comment on one or more Revisions 1 Members Voted Negative on one or more Revisions (Marrion) 1 Members Abstained on one or more Revisions (Joseph) The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each revision. To pass ballot, each revision requires: (1) a simple majority of those eligible to vote and (2) an affirmative vote of 2 /3 of ballots returned. See Sections (c) and of the Regulations Governing the Development of NFPA Standards.

2 1 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] Air Sampling Type Detector. A detector that consists of a piping or tubing distribution network that runs from the detector to the area(s) to be protected. An aspiration fan in the detector housing draws air from the protected area back to the detector through air- sampling ports, piping, or tubing. At the detector, the air is analyzed for fire products. (SIG-IDS) Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 17:42:25 EDT 2016 Committee Statement Committee Statement: Response Message: A Correlating Committee task group on language/terms reviewed the language of the Code for consistency and grammar. Editorial correction. The Term air sampling is generally not hyphenated and majority of usage in the code is not hyphenated. Revised to align with other usage in the Code Public Input No. 643-NFPA [Section No ] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All

3 2 of 52 11/16/2016 4:26 PM Aho, Jr., Wayne J. Boone, Mark S. Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

4 3 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] The performance, selection, use, and location of automatic or manual initiating devices, including but not limited to fire detection devices, carbon monoxide or other gas detection devices, devices that detect the operation of fire suppression and extinguishing systems, waterflow detectors, pressure switches, manual fire alarm boxes, and other supervisory signal initiating devices (including guard tour reporting) used to ensure timely warning for the purposes of life safety and the protection of a building, a space, a structure, an area, or an object shall comply with the minimum requirements of this chapter. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 18:15:56 EDT 2016 Committee Statement Committee Statement: Response Message: This change is made as one of numerous changes needed to incorporate and integrate the NFPA 720 requirements for carbon monoxide detection into NFPA 72. This change identifies that CO and other gas detectors will be in the scope of Chapter 17 which addresses various initiating devices. Public Input No. 591-NFPA [Section No ] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J.

5 4 of 52 11/16/2016 4:26 PM Boone, Mark S. Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

6 5 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] Where subject to mechanical damage, an initiating device shall be protected. A mechanical guard used to protect a smoke, heat, or radiant energy sensing detector an initiating device shall be listed for use with the detector device. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 18:40:39 EDT 2016 Committee Statement Committee Statement: Response Message: This revision is one of numerous revisions proposed as part of the integration of NFPA 720 carbon monoxide detection requirements into the NFPA 72 Fire Alarm and Signaling Code. This change provides recognition of use, application and/or installation requirements consistent with other device requirements in Chapter 17. Public Input No. 592-NFPA [Section No ] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J. Boone, Mark S.

7 6 of 52 11/16/2016 4:26 PM Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

8 7 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] * Duplicate terminals, leads, or connectors that provide for the connection of installation wiring shall be provided on each initiating device for the express purpose of connecting into the fire alarm system to monitor the integrity of the signaling and power wiring. Exception: Initiating devices connected to a system that provides the required monitoring Where initiating devices are connected to a system that provides the required monitoring, duplicate terminals, leads, or connectors shall not be required. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 12:44:58 EDT 2016 Committee Statement Committee Statement: Exception language is revised to comply with the Manual of Style. Response Message: Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J. Boone, Mark S.

9 8 of 52 11/16/2016 4:26 PM Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

10 9 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No [Excluding any Sub-Sections] ] Where fire detectors are installed in concealed locations more than 10 ft (3.0 m) above the finished floor or in arrangements where the detector s alarm or supervisory indicator is not visible to responding personnel, the detectors shall be provided with remote alarm or supervisory indication in a location acceptable to the authority having jurisdiction. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 18:44:55 EDT 2016 Committee Statement Committee Statement: Response Message: This revision is one of numerous revisions proposed as part of the integration of NFPA 720 carbon monoxide detection requirements into the NFPA 72 Fire Alarm and Signaling Code. This change provides recognition of use, application and/or installation requirements consistent with other device requirements in Chapter 17 and where such requirements are applicable to carbon monoxide detection devices and other detectors. Public Input No. 605-NFPA [Section No [Excluding any Sub-Sections]] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J.

11 10 of 52 11/16/2016 4:26 PM Boone, Mark S. Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

12 11 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] Fire detectors Detectors installed in concealed locations where the specific detector alarm or supervisory signal is indicated at the control unit (and on the drawings with its specific location and functions) shall not be required to be provided with remote alarm indicators as specified in Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 18:46:56 EDT 2016 Committee Statement Committee Statement: Response Message: This revision is one of numerous revisions proposed as part of the integration of NFPA 720 carbon monoxide detection requirements into the NFPA 72 Fire Alarm and Signaling Code. This change provides recognition of use, application and/or installation requirements consistent with other device requirements in Chapter 17 and where such requirements are applicable to carbon monoxide detection devices and other detectors. Public Input No. 606-NFPA [Section No ] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J. Boone, Mark S.

13 12 of 52 11/16/2016 4:26 PM Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

14 13 of 52 11/16/2016 4:26 PM First Revision No NFPA [ New Section after ] Heat sensing fire detectors shall be listed in accordance with applicable standards such as ANSI/UL 521, Standard for Heat Detectors for Fire Protective Signaling Systems, and installed in accordance with their listing. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 18:59:16 EDT 2016 Committee Statement Committee Statement: Response Message: Sections and include requirements related to heat detector listings. This revision clarifies that heat detectors are required to be listed, and identifies as an example the ANSI/UL standard used to list these detectors. This does not preclude FM 3210 or other standards. Public Input No. 682-NFPA [New Section after ] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J. Boone, Mark S.

15 14 of 52 11/16/2016 4:26 PM Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

16 15 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] Classification. Heat-sensing fire detectors of the fixed-temperature or rate-compensated, spot type shall be classified as to the temperature of operation in accordance with Table Table Temperature Classification and Color Code for Heat-Sensing Fire Detectors Temperature Classification Temperature Rating Range Maximum Ceiling Temperature F C F C Color Code Low* Uncolored Ordinary Uncolored Intermediate White High Blue Extra high Red Very extra high Green Ultra high Orange *Intended only for installation in controlled ambient areas. Units shall be marked to indicate maximum ambient installation temperature. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 11:06:41 EDT 2016 Committee Statement Committee Statement: Response Message: Based on the recommendation from the Metric Values Task Group, SIG-IDS is correlating the metric value of 100 degrees F to be 38 degrees C. Public Input No. 565-NFPA [Global Input] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments

17 16 of 52 11/16/2016 4:26 PM 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J. Boone, Mark S. Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

18 17 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] * On ceilings 10 ft to 30 ft (3.0 m to 9.1 m) high, heat detector spacing shall be reduced in accordance with Table prior to any additional reductions for beams, joists, or slope, where applicable. Table Heat Detector Spacing Reduction Based on Ceiling Height ft Ceiling Height Greater than (>) m ft Up to and Including m Multiply Listed Spacing by Exception: Table shall not apply to the following detectors, which rely on the integration effect: Line-type electrical conductivity detectors (see ) Pneumatic rate-of-rise tubing heat detectors (see ) In these cases, the manufacturer s published instructions shall be followed for appropriate alarm point and spacing For line-type electrical conductivity detectors (see ) and pneumatic rate-of-rise tubing heat detectors ( see ), which rely on the integration effect, the derating required by Table shall not apply, and the manufacturer s published instructions shall be followed for appropriate alarm point and spacing. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 12:47:59 EDT 2016 Committee Statement

19 18 of 52 11/16/2016 4:26 PM Committee Statement: Exception language is revised to comply with the Manual of Style. Response Message: Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J. Boone, Mark S. Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David

20 19 of 52 11/16/2016 4:26 PM Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

21 20 of 52 11/16/2016 4:26 PM First Revision No NFPA [ New Section after ] * Smoke detectors installed in ducts and other locations with air velocities greater than 300 ft/min (1.5 m/sec) shall be listed for the velocity conditions anticipated and installed in accordance with the manufacturer s instructions. Supplemental Information File Name FR_2015_A docx Description New annex material Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 19:32:29 EDT 2016 Committee Statement Committee Statement: Response Message: This revision identifies the fact that smoke detectors installed in ducts and other locations with air velocities > 300 ft/min. need to be listed for those air velocity environments. The annex item cites, as an example, ANSI/UL 268A. Another example is FM Public Input No. 677-NFPA [New Section after ] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D.

22 21 of 52 11/16/2016 4:26 PM Affirmative All Aho, Jr., Wayne J. Boone, Mark S. Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

23 A The velocities indicated in individual duct detector listings are based on applicable standards such as ANSI/UL 268A.

24 22 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] Smoke Spot-type smoke detectors that have provision for field adjustment of sensitivity via a mechanical means shall have an adjustment range of not less than 0.6 percent per foot (1.95 percent per meter) obscuration. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 19:51:55 EDT 2016 Committee Statement Committee Statement: Response Message: The existing text dates back to the days when smoke alarms had mechanical adjustments for sensitivity. In looking at UL 217, the requirement is interpreted as a mechanical adjustment in Section of the eighth edition. As currently written in NFPA , the requirement may create confusion if it is viewed within the context of high sensitivity aspirated detectors, which have sensitivity settings outside of the normal UL range of 0.5 to 4%/ft. Aspirated detectors have a number of very high sensitivity threshold settings that may not differ by the amount required in Public Input No. 373-NFPA [Section No ] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J.

25 23 of 52 11/16/2016 4:26 PM Boone, Mark S. Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

26 24 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] Air Sampling Type Smoke Detector General * In the absence of specific performance-based design criteria, each sampling port of an air sampling type smoke detector shall be treated as a spot-type smoke detector for the purpose of location and spacing in accordance with , sensitivity, and the manufacturer s published instructions Air sampling type smoke detectors shall produce trouble signals if the airflow is outside the manufacturer s specified range If provided, atmospheric contaminant filtration shall be listed for use with the detector and installed and maintained in accordance with the air sampling type smoke detector manufacturer s published instructions Pipe Network Maximum air sample transport time from the farthest sampling port to the detector shall not exceed 120 seconds Sampling pipe networks shall be designed on the basis of, and shall be supported by, computer-based fluid dynamics design calculations to ensure required performance The sampling pipe network design calculations shall include pressure, volumetric flow, and alarm sensitivity at each sampling port Software applications for the design of pipe networks shall be listed for use with the manufacturer s equipment Sampling system piping shall be conspicuously identified as SMOKE DETECTOR SAMPLING TUBE DO NOT DISTURB, as follows: (1) At changes in direction or branches of piping (2) At each side of penetrations of walls, floors, or other barriers (3) At intervals on piping that provide visibility within the space, but no greater than 20 ft (6.1 m) * Sampling ports shall be identified as such * If provided, test ports at the end (most remote location) of a pipe run installed in the pipe network solely for the purpose of validating consistency in performance (also referred to as benchmark test points) shall be included in the design calculations and allowed, but not required, to comply with the requirements of

27 25 of 52 11/16/2016 4:26 PM If the piping and fittings are painted, the painting shall be performed in accordance with the air sampling type smoke detector manufacturer s published instructions * Pipe network materials, sizing, and installation shall be in accordance with the manufacturer s published requirements and suitable for use in the environment in which they are installed Where used, capillary tubing shall be sized and affixed in accordance with the manufacturer s published instructions and computer-based design calculations Installation and Spacing * Air sampling pipe network fittings shall be installed air-tight and permanently affixed Sampled air shall be exhausted to a lessor or equal pressure zone. The pressure differential between the sampled air and detector exhaust shall not exceed the manufacturer s published instructions * Supports for sampling pipe shall be in accordance with the air sampling type smoke detector manufacturer s published instructions Special Applications Air Duct Applications. (A) The air sampling system shall be listed for air duct applications and shall be installed in accordance with the manufacturer s published instructions. (B) The inlet and exhaust sections of pipe that are installed inside the air duct shall be air-tight and shall exhaust the sampled air in accordance with the manufacturer s published instructions * Electrical Cabinet Applications. For protection of cabinets containing electrical equipment, the air sampling ports shall be located in the main airflow at the exhaust vents, downstream of the airflow distribution path, or in accordance with the manufacturer s published instructions Each sampling port of an air sampling type smoke detector shall be treated as a spot-type detector for the purpose of location and spacing Maximum air sample transport time from the farthest sampling port to the detector shall not exceed 120 seconds * Sampling pipe networks shall be designed on the basis of, and shall be supported by, sound fluid dynamic principles to ensure required performance Sampling pipe network design details shall include calculations showing the flow characteristics of the pipe network and each sample port Air-sampling detectors shall give a trouble signal if the airflow is outside the manufacturer s specified range.

28 26 of 52 11/16/2016 4:26 PM * The sampling ports and in-line filter, if used, shall be kept clear in accordance with the manufacturer s published instructions Air-sampling network piping and fittings shall be airtight and permanently fixed Sampling system piping shall be conspicuously identified as SMOKE DETECTOR SAMPLING TUBE DO NOT DISTURB, as follows: At changes in direction or branches of piping At each side of penetrations of walls, floors, or other barriers At intervals on piping that provide visibility within the space, but no greater than 20 ft (6.1 m) Supplemental Information File Name FR_2008_ docx Description For staff use Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 17:38:57 EDT 2016 Committee Statement Committee Statement: The SIG-IDS Chair had formed a task group to propose changes that would assist the fire protection community with the application, installation, inspection, testing, and maintenance of air sampling-type smoke detection systems. This change is a result of that task group's efforts. Additionally, the task group proposed a complete re-write of section which the Technical Committee accepted with revisions. The SIG-IDS Technical Committee provides additional guidance for air sampling-type smoke detection systems in NFPA 72. New subsections are introduced to categorize the different sections that apply to an installation or application : Adds criteria for performance based design, ties back to and manufacturer s published instructions. In absence, application would otherwise be limiting : Relocate under new general subsection, edited to include the word smoke after Air Sampling for consistency with the section title : New language intended to prevent use of improper filtration media that may hinder system performance : Relocate to new subsection for proper categorization : Relocate to new subsection for proper categorization, edit language for clarity. Sound / principles not specific.

29 27 of 52 11/16/2016 4:26 PM : Relocate for proper categorization, additional requirements are added for clarity of calculated performance verification : New language to ensure modelling programs be specific to the manufacturer s equipment and set criteria that the program be listed : Relocate to new subsection for proper categorization : New language to avoid challenges with respect to identifying sampling ports to avoid damage, non-engineered alterations, and points where maintenance may be required : New language to not unnecessarily burden system capacity or performance by placing a test point at accessible locations. This does not remove the requirement to meet 120 sec from last sampling port in fire zone. A : Add appendix material to provide additional guidance with respect to benchmark test point : New material to prevent damage to pipe from non-compatible chemistries and/or blockage of sampling ports as a result of painting in the field New language to address suitability of sampling pipe network with respect to the environment in which they are installed : New language extending requirements to capillary tubes, also, acknowledges permissible use of capillaries and requires that they be included in calculations : Relocate to new subsection : New language to prevent systems from not performing their intended function. Pressure differentials, if not within manufacture's published guidelines results in systems performing unpredictably : New language to assure proper methods and materials are used as it relates to support of air sampling pipe distribution networks : New language to ensure that the detector selected is suitable and listed for duct application and to improve clarity of installation for intent of performance. Response Message: : New language to provide guidance for application in electrical cabinets noting requirements for placement of ports for interception of smoke. Public Input No. 644-NFPA [Section No ] Public Input No. 645-NFPA [Section No ] Public Input No. 531-NFPA [Section No ] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments

30 28 of 52 11/16/2016 4:26 PM 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J. Boone, Mark S. Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

31 29 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] Supply Air System. Where the detection of smoke in the supply air system is required by other NFPA standards, a detector(s) listed for the air velocity present and that is located in the supply air duct downstream of both the fan and the filters shall be installed. Exception: Additional smoke detectors shall not be required to be installed in ducts where the air duct system passes through other smoke compartments not served by the duct. (A) Where the detection of smoke in the supply air system is required by other NFPA standards, a detector(s) listed for the air velocity present and that is located in the supply air duct downstream of both the fan and the filters shall be installed. (B) Where the air duct system passes through other smoke compartments not served by the duct, additional smoke detectors shall not be required to be installed. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 12:50:20 EDT 2016 Committee Statement Committee Statement: Exception language is revised to comply with the Manual of Style. Response Message: Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D.

32 30 of 52 11/16/2016 4:26 PM Affirmative All Aho, Jr., Wayne J. Boone, Mark S. Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

33 31 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Sections (B), (C) ] (B) Each group of three or more doorway openings shall be treated separately. Figure (B) shall apply. Figure (B) Detector(s) Location +/ 24 in. ±24 in. (0.6 m) (610 mm) Requirements for Group Doorways. (C) Each group of doorway openings that exceeds 20 ft (6.1 m) in width, measured at its overall extremes, shall be treated separately. Figure (C) shall apply. Figure (C) Detector(s) Location +/ 24 in. ±24 in. (0.6 m) (610 mm) Requirements for Group Doorways over 20 ft (6.1 m) in Width. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 11:10:45 EDT 2016 Committee Statement Committee Statement: Response Message: Based on the recommendation from the Metric Values Task Group, SIG-IDS is correlating the metric value of 24 inches to be 610 mm. Public Input No. 576-NFPA [Global Input] Ballot Results This item has passed ballot

34 32 of 52 11/16/2016 4:26 PM 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J. Boone, Mark S. Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

35 33 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] Air- sampling or projected beam smoke detectors shall be installed in accordance with the manufacturer s published instructions. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Fri Jul 29 14:58:35 EDT 2016 Committee Statement Committee Statement: Response Message: A Correlating Committee task group on language/terms reviewed the language of the Code for consistency and grammar. Editorial correction. The Term air sampling is generally not hyphenated and the majority of usage in the code is not hyphenated. The Technical Committee revises to align with other usage in the Code Public Input No. 646-NFPA [Section No ] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J. Boone, Mark S.

36 34 of 52 11/16/2016 4:26 PM Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

37 35 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] General. The purpose and scope of Section shall be to provide requirements for the selection, installation, and operation of gas detectors other than carbon monoxide detectors. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 20:44:41 EDT 2016 Committee Statement Committee Statement: Response Message: Carbon monoxide detection requirements are separate and distinct from the gas detection requirements of A new section is added to cover CO detection (17.12). Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J. Boone, Mark S. Cholin, John M. Dungan, Kenneth W. Fields, Gary P.

38 36 of 52 11/16/2016 4:26 PM Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

39 37 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] Gas detection equipment shall be listed in accordance with applicable standards such as ANSI/UL 1484, Standard for Residential Gas Detectors, or ANSI/UL 2075, Standard for Gas and Vapor Detectors and Sensors, for the specific gas or vapor it is intended to detect. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 20:01:03 EDT 2016 Committee Statement Committee Statement: Response Message: The text identifies representative applicable standards for gas and vapor detectors. Devices may also be listed to other applicable standards such as FM 6320, 6325, or Public Input No. 407-NFPA [Section No ] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J. Boone, Mark S. Cholin, John M. Dungan, Kenneth W.

40 38 of 52 11/16/2016 4:26 PM Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Marrion, Chris Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Abstention Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

41 39 of 52 11/16/2016 4:26 PM First Revision No NFPA [ New Section after ] Carbon Monoxide Detectors Carbon monoxide detectors shall not be located in areas where environmental conditions cause an adverse effect on the detectors ability to detect the targeted hazardous gas Carbon monoxide detectors shall be installed as specified in the manufacturer s published instructions in accordance with (1) and (2), or (3): (1)* On the ceiling in the same room as permanently installed fuel-burning appliances (2)* Centrally located on every habitable level and in every HVAC zone of the building (3) A performance-based design in accordance with Section Carbon monoxide detectors shall be marked in accordance with their listing. Detector thresholds shall be set to respond at the levels specified by ANSI/UL 2034, Standard for Single and Multiple Station Carbon Monoxide Alarms All carbon monoxide detectors shall be located and mounted so that accidental operation will not be caused by jarring or vibration The location of carbon monoxide detectors shall be based on an evaluation of potential ambient sources and flows of carbon monoxide, moisture, temperature, dust, or fumes and of electrical or mechanical influences to minimize nuisance alarms The selection and placement of carbon monoxide detectors shall take into account both the performance characteristics of the detector and the areas into which the detectors are to be installed to prevent nuisance and unintentional alarms or improper operation after installation Unless specifically designed and listed for the expected conditions, carbon monoxide detectors shall not be installed where any of the following ambient conditions exist: (1) Temperature below 32 F (0 C) (2) Temperature above 100 F (38 C) (3) Relative humidity outside the range of 10 percent to 95 percent Unless tested and listed for recessed mounting, carbon monoxide detectors shall not be recessed into the mounting surface Protection During Construction Where detectors are installed for signal initiation during construction, they shall be replaced prior to the final commissioning of the system Where detection is not required during construction, detectors shall not be installed until after all other construction trades have completed cleanup.

42 40 of 52 11/16/2016 4:26 PM Carbon Monoxide Detectors for Control of Carbon Monoxide Spread System designers shall consider the spread of carbon monoxide through an occupancy through the HVAC system Interaction with smoke control systems, if such is provided, shall be coordinated. Supplemental Information File Name FR_2018_A _1_and_2_.docx Description New annex material Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 20:10:57 EDT 2016 Committee Statement Committee Statement: Response Message: This revision is one of numerous revisions proposed as part of the integration of NFPA 720 carbon monoxide detection requirements into the NFPA 72 Fire Alarm and Signaling Code. This change provides recognition of use, application and/or installation requirements consistent with other device requirements in Chapter 17 and where such requirements are applicable to carbon monoxide detection devices. Public Input No. 607-NFPA [New Section after ] Public Input No. 608-NFPA [New Section after A ] Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 22 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D.

43 41 of 52 11/16/2016 4:26 PM Affirmative All Aho, Jr., Wayne J. Boone, Mark S. Cholin, John M. Dungan, Kenneth W. Fields, Gary P. Lang, Scott R. Lessar, Michael Makowka, Norbert W. Mann, Larry W. Miller, Samuel M. Morphew, Jr., Ovid E. Mottorn, II, James W. Nadgir, Abhay Nielson, Lynn O'Connor, Daniel J. Ouimette, Ronald D. Parssinen, John L. Royse, David L. Schneider, Kenneth R. Sides, Michael D. Swerdin, Mark Waite, David Negative with Comment Marrion, Chris Section needs to be revised and updated. This should include addressing such items as: Section replace with Carbon monoxide detectors shall be located based on an assessment of the space and environmental conditions and adverse environmental conditions will be assessed and mitigated. If carbon monoxide cannot be provided, other mitigation measures will be implemented to address the carbon monoxide hazard. This section currently sounds like it allows not providing CO detectors if the environment is adverse (garage in wintertime) but doesn t indicate that other alternate measures should be taken This section needs more detail as is unclear where detectors are needed and appears to be overly onerous w/potential limited beneficial impact. This should include updating terms that are vague centrally located, every HVAC zone of the building, etc delete permanently installed and replace appliances with equipment. This doesn t address other equipment that may not be permanent that is likewise a hazard add sleeping rooms and areas all of the design sections should be consolidated and clarified. There also appears to be discrepancies in the various requirements e.g , , etc add Carbon monoxide detector designs shall take into consideration the location of the carbon monoxide producing source, its exhaust equipment including accounting for leakage in equipment and ductwork, its potential movement throughout a space as well as the building both horizontally and vertically, the impact of hvac equipment on transporting it throughout the building, etc. and locate carbon monoxide detectors to address the hazards within the overall building appropriately revise to state carbon monoxide detectors shall be installed as per their listing. It currently appears as if those conditions will make it ok not to install detectors. Eg. a mechanical room, garage, etc. that goes below freezing in winters, boiler rooms, etc this should also address code requirements and what they are requiring in relation to this so that they are coordinated. Abstention

44 42 of 52 11/16/2016 4:26 PM Joseph, Steven W. Abstaining as Scott Lang also with Honeywell has voted "affirmative on all".

45 A (1) Carbon monoxide detectors are located on the ceiling above permanently installed fuel burning appliances because of the buoyancy of the heated combustion gases as compared to normal ambient temperatures. Detectors should be located as close as practical to the permanently installed fuel burning appliance consistent with considerations of detector accessibility, sources of detector contamination, and nuisance sources. Siting considerations can include transient backdrafting spillage of flue gases during startup and ventilation supply or exhaust vents. A (2) The purpose of detectors centrally located on every habitable level is to detect the migration of carbon monoxide from permanently installed fuel burning appliances and other sources of carbon monoxide. Other sources of carbon monoxide can include vehicles or other equipment that uses an internal combustion engine, barbecue grills, propane operated equipment, and systems used to generate hydrogen. Detector location and spacing should be based on an engineering evaluation that considers potential sources and migration of carbon monoxide. HVAC systems should be considered in the locating of carbon monoxide detectors because the HVAC systems provide a good means of mixing and the migration of carbon monoxide. Other considerations when locating carbon monoxide detectors are areas with closed doors and rated demising walls, which can isolate or separate areas within HVAC zones. Additional information for the location of carbon monoxide detectors is available in the Fire Protection Research Foundation (FPRF) technical report, Development of a Technical Basis for Carbon Monoxide Detector Siting.

46 43 of 52 11/16/2016 4:26 PM First Revision No NFPA [ Section No ] Manually actuated alarm-initiating devices shall be listed in accordance with applicable standards such as ANSI/UL 38, Standard for Manual Signaling Boxes for Fire Alarm Systems. for initiating signals other than for fire alarm shall be permitted if the devices are differentiated from manual fire alarm boxes by a color other than red and labeling Manually actuated alarm-initiating devices for initiating signals other than for fire alarm shall be permitted if the devices are differentiated from manual fire alarm boxes by a color other than red and labeling. Submitter Information Verification Submitter Full Name: SIG-IDS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jul 28 20:52:45 EDT 2016 Committee Statement Committee Statement: Response Message: This revision provides an example of an applicable listing standard for manual fire alarm boxes. Ballot Results This item has passed ballot 26 Eligible Voters 2 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Not Returned Hall, Robert A. Merrick, Justin D. Affirmative All Aho, Jr., Wayne J.

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Supervising Station

More information

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Protected Premises Fire Alarm

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle)

M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications

More information

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Fire Alarm

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic

More information

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018) M EM O RA N D UM TO: FROM: DATE: SUBJECT: Correlating Committee on Combustible Dusts Yiu Lee, Project Administrator January 27, 2017 NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

Chapter 17, Initiating Devices

Chapter 17, Initiating Devices Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.

More information

MEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Emergency Power Supplies Kelly

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Item No. Subject 13-6-1 Call to Order (8:00 A.M) 13-6-2 Roll Call 13-6-3 Approval

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014

M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications

More information

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Industrial and Medical Gases

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Alternative Approaches to

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017)

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Code Kelly Carey,

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 14 From: Kimberly Shea, Project Administrator

More information

Correlating Committee on Automatic Sprinkler Systems

Correlating Committee on Automatic Sprinkler Systems Correlating Committee on Automatic Sprinkler Systems M E M O R A N D U M DATE: May 14, 2014 TO: FROM: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems Matt Klaus,

More information

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN) 4 of 326 11/21/2013 1:03 PM First Revision No. 161-NFPA 72-2013 [ Section No. 3.3.11 ] 3.3.11 Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Portable Fire Extinguishers

More information

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Correlating Committee on Signaling Systems for

More information

M E M O R A N D U M. NFPA Technical Committee on Fire Safety and Emergency Symbols. NFPA 170 Second Draft TC FINAL Ballot Results (F2014)

M E M O R A N D U M. NFPA Technical Committee on Fire Safety and Emergency Symbols. NFPA 170 Second Draft TC FINAL Ballot Results (F2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Fire Safety

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Residential Occupancies Kelly

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Building Service and

More information

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fundamentals of Fire

More information

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted

More information

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 1410-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 1500, Standard on Fire Department

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

MEMORANDUM. NFPA 99 Second Draft Correlating Committee FINAL Ballot Results (A2017)

MEMORANDUM. NFPA 99 Second Draft Correlating Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Correlating Committee on Health Care Facilities Elena

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Residential

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 17 From: Kimberly Shea, Project Administrator

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

MEMORANDUM. Technical Committee on Fundamentals of Combustible Dusts. NFPA 652 First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Fundamentals of Combustible Dusts. NFPA 652 First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Combustible

More information

Committee Input No. 60-NFPA [ Sections , ]

Committee Input No. 60-NFPA [ Sections , ] Page 1 of 15 Committee Input No. 60-NFPA 34-2013 [ Sections 3.3.7.1, 3.3.7.2 ] Sections 3.3.7.1, 3.3.7.2 3.3.7.1 Combustible Liquid. A Any liquid that has a closed-cup flash point at or above 100 F (37.8

More information

Circulation Report for SIG-TMS Comments Document # 72

Circulation Report for SIG-TMS Comments Document # 72 1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15

More information

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12.

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12. 2/18/2016 National Fire Protection Association Report Committee Input No. 70 NFPA 54 2015 [ Section No. 12.5 ] This was a First Revision that failed ballot. 12.5 Type of Venting System to Be Used. 12.5.1

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Daniel O Connor (SIG-IDS), Jensen Hughes Robert Schifiliti (SIG-NAS), R.P. Schifiliti Associates William Koffel (SIG-ECS), Koffel

More information

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification Public Comment No. 2-NFPA 73-2014 [ Section No. 4.1.3 ] 4.1.3 Unused Openings. 4.1.3.1 Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement 10/20/ :03 AM

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement 10/20/ :03 AM of 496 10/20/2016 11:03 AM First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value 0.0375 lumens/ft 2 is used the metric equivalent shall be

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels

More information

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.

More information

TECHNICAL COMMITTEE ON FIRE CODE

TECHNICAL COMMITTEE ON FIRE CODE TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2

More information

NFPA 101 Life Safety Code Culture change 2012

NFPA 101 Life Safety Code Culture change 2012 NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted

More information

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Notification Appliances

More information

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM 2 of 326 11/21/2013 1:03 PM First Revision No. 82-NFPA 72-2013 [ Section No. 2.3.4 ] 2.3.4 ISO Publications. International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56, CH-1211

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Water Additives

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in

More information

M E M O R A N D U M. NFPA 1911 Second Draft Technical Committee FINAL Ballot Results (F2016 Cycle)

M E M O R A N D U M. NFPA 1911 Second Draft Technical Committee FINAL Ballot Results (F2016 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Department Apparatus

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Correlating Committee on Combustible Dusts Susan

More information

MEMORANDUM. NFPA Technical Committee on Handling and Conveying of Dusts, Vapors, and Gases. NFPA 654 Second Draft TC FINAL Ballot Results (A2016)

MEMORANDUM. NFPA Technical Committee on Handling and Conveying of Dusts, Vapors, and Gases. NFPA 654 Second Draft TC FINAL Ballot Results (A2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Handling and Conveying

More information

MEMORANDUM. NFPA Technical Committee on Hazard and Risk of Contents and Furnishings. NFPA 556 First Draft TC FINAL Ballot Results (A2015)

MEMORANDUM. NFPA Technical Committee on Hazard and Risk of Contents and Furnishings. NFPA 556 First Draft TC FINAL Ballot Results (A2015) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Hazard and Risk of Contents

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

THE BASICS OF FIRE ALARM PLAN REVIEW

THE BASICS OF FIRE ALARM PLAN REVIEW THE BASICS OF FIRE ALARM PLAN REVIEW Art Shaw A Shaw & Associates, LLC. ashaw@arthurshaw.com 231.838.3269 Fire Protection System Plan Reviewer FP000006 NFPA Certified Plans Examiner 02-0005 NFPA Certified

More information

Page 1 of 40 First Correlating Revision No. 15-NFPA 72-2014 [ Global Input ] 10.5.4 Plans Examiners and Inspectors. 10.5.4.1 Fire alarm system and emergency communications system plans and specifications

More information

SUBJECT: NFPA 302 Second Draft TC Final Ballot Results (A2014)

SUBJECT: NFPA 302 Second Draft TC Final Ballot Results (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Motor Craft Lawrence B. Russell, Staff

More information

First Revision No. 88-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement. 3 of /21/2013 1:03 PM

First Revision No. 88-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement. 3 of /21/2013 1:03 PM 3 of 326 11/21/2013 1:03 PM First Revision No. 88-NFPA 72-2013 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 70, National Electrical Code, 2011 2014 edition. NFPA 96, Standard

More information

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture

More information

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM of 28 11/18/2016 2:25 PM First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] 1.6 Units and Formulas. 1.6.1 The units of measure in this standard are presented first in U.S. customary units (inch-pound

More information

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM 1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Furnishings

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical self-closing device

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 496-2014 [ Section No. 5.2.2 ] 5.2.2 Where When the enclosure has been opened or if the protective gas supply has failed to maintain the required positive pressure, the enclosure

More information

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting.

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting. Input No. 7-NFPA 80-2013 [ Section No. 3.3.8 ] 3.3.8 Automatic Fire Detector. A device designed to detect the presence of a fire signature and to initiate action. For the purpose of this standard, automatic

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

CARBON MONOXIDE ALARM STANDARDS ACT - ENACTMENT Act of Dec. 18, 2013, P.L. 1229, No. 121 Cl. 35 An Act

CARBON MONOXIDE ALARM STANDARDS ACT - ENACTMENT Act of Dec. 18, 2013, P.L. 1229, No. 121 Cl. 35 An Act CARBON MONOXIDE ALARM STANDARDS ACT - ENACTMENT Act of Dec. 18, 2013, P.L. 1229, No. 121 Cl. 35 An Act Providing standards for carbon monoxide alarms; and imposing penalties. The General Assembly of the

More information

First Revision No. 20-NFPA [ Section No ]

First Revision No. 20-NFPA [ Section No ] of 25 7/15/2015 8:30 AM First Revision No. 20-NFPA 56-2015 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by NFPA

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Protected Premises

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Notification

More information

Committee Input No. 28-NFPA 13R-2013 [ Global Input ]

Committee Input No. 28-NFPA 13R-2013 [ Global Input ] Page 1 of 6 Committee Input No. 28-NFPA 13R-2013 [ Global Input ] 6.2.2 Outside Dwelling Units. 6.2.2.1 All sprinklers used outside of the dwelling units shall be in accordance with 6.2.2 7.2 and 7.3.

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Residential Sprinkler

More information

NFPA 96, 2017 REVIEW SUMMARY

NFPA 96, 2017 REVIEW SUMMARY NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information