Combination Type AFCI
|
|
- Edwin Rudolf Johnson
- 6 years ago
- Views:
Transcription
1 Combination Type AFCI Evolution of the Arc Fault Circuit Interrupter 2
2 Alarming Statistics According to the U.S. Fire Administration (USFA), an estimated 67,800 fires, 485 deaths, and approximately 2,300 injuries occur each year that can be associated with home wiring totaling $868 million in property losses. a The CPSC estimates that AFCI devices currently on the market may address 50% or more of these fires. b The National Electric Code has responded to this identified problem by requiring the use of AFCIs beginning with the 1999 version of the NEC and continuing that focus on safety with a requirement from combination AFCI beginning January 1, 2008, according to the 2005 NEC. The issue is so significant that the U.S. CPSC and the National Association of State Fire Marshalls (NASFM) are promoting the use of AFCI protection in both new and existing homes. The Combination AFCI is the latest technology that provides maximum available protection against the effects of arcing faults. a On the Safety Circuit: A Fact Sheet on Home Electrical Fire Prevention United States Fire Administration (2006) b Oct.1, 2002 CPSC2NFPA Technical Committee Document Proposal Form What is a Combination AFCI? Let s begin with what a Combination AFCI is NOT. It is not a replacement for a Ground Fault Circuit Interrupter (GFCI). A GFCI is intended for personal protection and interrupts the circuit to the load when the ground fault current exceeds 6mA, but not when the ground fault current is 4mA or less. An AFCI is a device intended to mitigate the effects of arcing faults by functioning to de-energize the circuit when an arc-fault is detected. * These are very different functions for very different applications. Neither device can replace the need for the other. * UL 1699 Arc Fault Circuit Interrupters (Second Edition) The Branch/Feeder AFCI can only detect line-to-neutral and line-to-ground arcing faults, as illustrated above. A Combination Type AFCI detects all three types of arcing: line-to-neutral, line-to-ground, and series arcing. The Combination Type AFCI differs from the Branch/Feeder AFCI in its ability to detect series arcing faults. 3
3 What are the differences? Conventional circuit breakers have two tripping mechanisms The short circuit or magnetic trip (electromagnetic element) 4Occurs when two current-carrying conductors touch and a low resistance path for current between the conductors is created 4Results in a surge current that will quickly trip a standard circuit breaker Current Overload or thermal trip (bimetal element) 4Occurs when the rated capacity of the circuit breaker is exceeded because additional devices are added to a circuit or existing devices require additional current AFCIs have the same tripping mechanisms above PLUS Arcing fault trip (electronic) 4Results from brief, intermittent current flow between current-carrying conductors 4Sporadic and high-resistance in nature 4Results in low-level current surges that are unlikely to trip a conventional circuit breaker due to the sporadic characteristics 4
4 What is unique about the Siemens Combination Type AFCI? Siemens features unique trip indicators on each AFCI product, providing a valuable analysis tool to help electricians pinpoint the type of trip. These indicators are in the form of LEDs that appear near the handle of the breaker. The LED indications will appear for 5 seconds each time the AFCI is turned ON up to 30 days after the last trip. One LED will be illuminated if the last trip was a result of an arcing fault. On the 2-pole AFCI, the leg on which the arcing fault was detected can be determined based on which single LED was illuminated. Two LEDs (three LEDs on the 2-pole AFCI) will be illuminated if the last trip was a result of an arcing fault to ground. No indication will be displayed if the AFCI trips as a result of an overcurrent condition. This last known trip indication can also be cleared from memory to assist with verifying resolution of the problem. LED trip indicators 1-pole CAFCI LED indication guide LED indicator Last known trip condition LED (A) LED (B) OFF OFF Overcurrent ON OFF Arc Fault ON ON Arc Fault to ground 2-pole CAFCI LED indication guide Last known trip LED indicator condition Yellow 1 Yellow 2 Yellow 3 OFF OFF OFF Overcurrent ON OFF OFF Arc fault (Leg A) OFF OFF ON Arc fault (Leg B) ON ON ON Arc fault to ground 5
5 With a 160 year history of engineering and innovation, Siemens strives to develop products that provide increased levels of safety. The Combination Type AFCI is another example in which Siemens has used advanced technology to ensure fit, form, and function for customers. Both performance and reliability are ensured by the technology implemented. This technology has been thoroughly tested by third-party laboratories and in the field. Specifically, the advanced semiconductor technology utilizes proprietary components designed to detect and react to the unique characteristics of arcing while maintaining a high level of reliability. This reliability is ensured by detailed design and verified by extensive testing. 6
6 Intelli-Arc Diagnostic Tool Improves troubleshooting accuracy Reduces the number of visits to the problem site Can be used with any circuit breaker regardless of brand. Currently AFCI protection devices only monitor and protect branch circuits in the home against arc faults. Although the LEDs on the Siemens Combination Type AFCIs can help to point an electrician in the right direction for troubleshooting, these AFCIs do not help to pinpoint the portion of the branch circuit that contained the fault. Arc faults are often intermittent which can make troubleshooting the branch circuit very difficult. In these cases, it is important to determine whether the fault condition exists in the permanent wiring, in connected equipment, or in a power cord. Intelligent arc detection technology The Siemens Intelli-Arc Diagnostic Tool helps to accurately diagnose the circuit in which a fault has occurred. When used in conjunction with good troubleshooting techniques, this tool allows the electrical contractor to determine and locate the root cause or source of the fault. The Intelli-Arc Diagnostic Tool presents information as to the type and magnitude of fault. Since the fault may not cause an AFCI to trip for various reasons, i.e. duration too short, current level too low, the tool provides an indication showing how close an event is to causing an AFCI to trip. The goal of the diagnostic tool is to speed the troubleshooting process for the electrical contractor. The device drastically improves the accuracy of the troubleshooting process. This, in turn, will significantly reduce the number of visits to the problem site. Every intent of this device is directed as saving the electrical contractor time for each branch circuit that must be evaluated. The Intelli-Arc Diagnostic Tool can be used with any circuit breaker regardless of brand. Thoroughly tested AFCIs help to ensure the safety of those who will live, work, or play in the buildings by protecting them from hidden faults that can smolder for hours before breaking into the open in spectacular form. Few building trades do as much to protect the American public as electrical contractors, and AFCIs are important tools in the electrician s safety arsenal. 7
7 Intelli-Arc Diagnostic Tool Features Wireless communication Hook location for attaching base unit to the load center Amp indicator (A) Ground fault indicator (B) Power indicator Communication indicator with hand-held Arc fault indicator (C) Communication with base unit Clear (last event) Power button Push and hold "clear" button while pressing "power" button to test the hand-held functionality Wire terminals to load Hand-held unit Wire terminals to breaker Base unit Intelli-Arc Diagnostic Tool LED troubleshooting indications Three sets of LED indicators are provided on the hand-held device for use in troubleshooting branch circuit issues. These three indications give information regarding current ( AMPS ), ground fault level ( GF ), and arc fault level ( AF ). A.Current ( AMPS ) 1. The full scale current for this LED indication is 20+A 2. LED indicators do not increase by uniform intervals. 3. The 5A point is marked on hand-held device for reference. B.Ground Fault ( GF ) 1. The full scale current for this LED indication is 50+ ma. C. Arc Fault ( AF ) 1. This LED indication does not display in reference to current level but rather in severity of events, with a full scale reading (red LED) representing an event that is very likely to cause an AFCI device to trip. 2. Partial readings (yellow LEDs) should be evaluated. Combined independent events may cause an AFCI to trip. 3. Transitional events, i.e. turning on an appliance, are likely to register as some low level on the arc fault scale. 4.The action taken that produces the highest level of indication should be thoroughly evaluated for any issues that may be present. 2. LED indicators do not increase by uniform levels. 8
8 National Electrical Code Progression The need for AFCI has been established by various respected organizations. Requirements are already in place to mandate the use of the Combination Type AFCI. These Combination Type AFCIs provide the maximum protection available today for reducing the possibly catastrophic effects of arcing faults NEC J Listed AFCI future requirement in Code - Allows Branch/Feeder AFCI J January 1, 2002: bedroom receptacles 2002 NEC J Listed AFCI in ALL bedroom circuits - Allows Branch/Feeder AFCI 2005 NEC J Combination Type AFCI in bedroom circuits J Branch/Feeder AFCI permitted until January 1, NEC J Combination Type AFCI J Expand to 1 pole, 15220A circuits installed in family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas Siemens Industry, Inc. Building Technologies Division 5400 Triangle Parkway Norcross, GA info.us@siemens.com Subject to change without prior notice Order No.: RPFL-COMBO-1009 All rights reserved Printed in USA 2009 Siemens Industry, Inc. The information provided in this brochure contains merely general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.
How to keep you, your family, and your possessions safe usa.siemens.com/circuitbreakers
AFCI and GFCI Homeowner s Guide How to keep you, your family, and your possessions safe usa.siemens.com/circuitbreakers Congratulations on the purchase of your new home. This guide will help you understand
More informationPocket Guide to Whole House Safety. Whole house safety
Pocket Guide to Whole House Safety Whole house safety Use electricity safely everywhere in your home. Most of us take the safety of our home s electrical system for granted. And yet faulty electrical
More informationWHITE PAPER: THE IMPORTANCE OF ARC FAULT CIRCUIT INTERRUPTER TECHNOLOGY
WHITE PAPER: THE IMPORTANCE OF ARC FAULT CIRCUIT INTERRUPTER TECHNOLOGY 1 Introduction Thousands of deaths and billions of dollars in property loss occur every year due to residential structure fires.
More informationWHITE PAPER: ARC FAULT CIRCUIT INTERRUPTERS EXPANDING HOME SAFETY
WHITE PAPER: ARC FAULT CIRCUIT INTERRUPTERS EXPANDING HOME SAFETY Expanding Home Safety Page 2 INTRODUCTION Smoke alarms, fire extinguishers, emergency escape ladders these are all proven methods for making
More informationPocket Guide usa.siemens.com/afci
Whole House Safety Pocket Guide usa.siemens.com/afci Use electricity safely everywhere in your home. What causes arc faults? Arc faults can occur for many reasons and anywhere in a home s electrical system.
More informationwhole house safety Pocket Guide to Whole House Safety Siemens Energy & Automation, Inc Old Milton Parkway Alpharetta, GA 30005
Pocket Guide to Whole House Safety whole house SAFETY whole house Siemens Energy & Automation, Inc. 3333 Old Milton Parkway Alpharetta, GA 30005 1-800-964-4114 info.sea@siemens.com www.sea.siemens.com/afci
More informationtechnology using advanced to reduce electrical fires arc fault circuit interrupters
arc fault circuit interrupters using advanced technology to reduce electrical fires NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION Low Voltage Distribution Equipment Section I NTRODUCTION Arc Fault Circuit
More informationAFCI. RECEPTACLEFAQs. What is an arc fault? What causes arc faults?
RECEPTACLEFAQs AFCI 1 What is an arc fault? UL provides a definition for an arc fault in UL 1699 (Standard for Safety Arc Fault Circuit Interrupters). It is an unintentional arcing condition in a circuit.
More informationCompatibility between Smoke Alarms and Arc-Fault Circuit Interrupters
Page 2 A NEMA Low Voltage Distribution Equipment Section Document ABP 11-2016 Compatibility between Smoke Alarms and Arc-Fault Circuit Interrupters Published by National Electrical Manufacturers Association
More informationGE Industrial Solutions. Residential Electronic Circuit Interrupters
GE Industrial Solutions Residential Electronic Circuit Interrupters Dual Function Circuit Interrupter (DFCI) Provides ground fault and arc fault circuit protection in one unit The 2014 National Electric
More informationArc-Fault Circuit Interrupters (AFCIs) Frequently Asked Questions
Arc-Fault Circuit Interrupters (AFCIs) Frequently Asked Questions Please note, as of September 6 th, 2012, a full 2,000 W (16A) of connected dimming load can now be achieved without false tripping using
More informationData Bulletin. Determining the Cause of AFCI Tripping Class 760
Data Bulletin 0760DB0204 06/2002 Cedar Rapids, IA, USA Determining the Cause of AFCI Tripping Class 760 Retain for future use. INTRODUCTION DANGER HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This document
More informationCONTINUING EDUCATION FOR OREGON ELECTRICIANS. AMERICAN ELECTRICAL INSTITUTE PO Box Spokane, WA
American Electrical Institute 2014 PART 2 83 CONTINUING EDUCATION FOR OREGON ELECTRICIANS AMERICAN ELECTRICAL INSTITUTE PO Box 31131 Spokane, WA 99223 www.aeitraining.com 84 PART 3 American Electrical
More informationArc Fault Circuit Interrupters The Next Generation of Fire Prevention - The Next Generation of Recovery Opportunities
Arc Fault Circuit Interrupters The Next Generation of Fire Prevention - The Next Generation of Recovery Opportunities By: William N. Clark, Esq. Cozen O Connor 1900 Market Street Philadelphia, PA 19103
More informationInstructor: L. Keith Lofland
One and Two Family Dwelling Electrical Systems 2014 NEC AFCIs, GFCIs, and Other Dwelling Unit Requirements Training Presentation by: International Association of Electrical Inspectors Instructor: L. Keith
More informationUnderstanding Your Options: AFCI Protection and the 2015 CE Code
Understanding Your Options: AFCI Protection and the 2015 CE Code November 25, 2014 Eaton 2008 Eaton Corporation. All rights reserved. Classifying An Arc Fault Operational Arcs - occur in a properly functioning
More information2011 and 2014 National Electrical Code Changes Residential Only
2011 and 2014 National Electrical Code Changes Residential Only Sponsored By: and.net Instructor: Fritz Gunther, Chief Electrical Inspector 585-436-4460 www.nyeia.com NEW YORK ELECTRICAL INSPECTION AGENCY
More informationGROUND FAULT PROTECTION METHODS & 2017 National Electric Code
GROUND FAULT PROTECTION METHODS 2014 & 2017 National Electric Code Ground Fault Protection Methods A Ground Fault Circuit Interrupter, or GFCI, is a device that functions to de-energize a circuit when
More informationArc-Fault Circuit Interrupters (AFCIs) and Ground-Fault Circuit Interrupters (GFCIs)
NECA 169-2010 Standard for Arc-Fault Circuit Interrupters (AFCIs) and Ground-Fault Circuit Interrupters (GFCIs) An American national Standard Published by National Electrical Contractors Association NECA
More information2014 NEC for. Understanding the. AFCI protection AFCI code compliant safety. Eaton is a registered trademark.
2014 AFCI code compliant safety Understanding the 2014 NEC for AFCI protection Eaton is a registered trademark. All other trademarks are property of their respective owners. Eaton 1000 Eaton Boulevard
More informationUltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW
12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes
More informationPANELBOARDS & BUILDING DISTRIBUTION
262416 PANELBOARDS & BUILDING DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Distribution panelboards 2. Power panelboards B. Related Sections: 1.02 POLICY 1. CU Standard 260500, Basic
More informationNECA 169. Standard for Installing and Maintaining Arc-Fault Circuit Interrupters (AFCIs) and Ground-Fault Circuit Interrupters (GFCIs)
NECA 169 Standard for Installing and Maintaining Arc-Fault Circuit Interrupters (AFCIs) and Ground-Fault Circuit Interrupters (GFCIs) Industry Review Draft (Date TBD) National Electrical Installation Standards,
More informationFIRE ALARM: BY OTHERS, IF REQUIRED.
x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,
More informationPART 4 ELECTRICAL STANDARDS
PART 4 ELECTRICAL STANDARDS 1.0 INTRODUCTION AND SCOPE: These standards reflect the general requirements and recommendations of elevator contractors, with respect to the power distribution system to achieve
More informationTECHNICAL ARTICLE. Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009
TECHNICAL ARTICLE Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009 Many inspectors were contractors in some prior life. The progression from contractor to inspecting
More informationAF/GF dual-purpose receptacles
Eaton Wiring Devices OBC AF/GF dual-purpose receptacles AF/GF dual-purpose receptacles Arc fault and ground fault protection in one device In Stock July 2016! Eaton Wiring Devices OBC AF/GF dual-purpose
More information9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.
Chapter 1 GROUNDING AND BONDING 1 Proper grounding practices protect people from the hazards of electric shock and ensure the correct operation of overcurrent protection devices. Grounding is the intentional
More informationFIRE ALARM: BY OTHERS, IF REQUIRED.
x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT
More informationINSTALLATION, OPERATION AND MAINTENANCE MANUAL
GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Integrally Mounted Medium and High Exposure Surge Protective Devices
More informationA HOMEOWNERS HANDBOOK
ELECTRICAL A HOMEOWNERS HANDBOOK By Everett H. Rawlings Electricity in the home plays a critical role in our lives. From activating our alarm clock in the morning to all aspects of our lives for the rest
More informationA. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationBuilding Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
More informationSECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL
SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 2 FROM: Kimberly Shea, Administrator,
More informationStudent Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationUse & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)
Use & Care Manual With Installation Instructions for the Installer Electric Tankless Water Heaters The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations
More informationElectrical Safety Through Design. Mersen EP formerly Ferraz Shawmut
Electrical Safety Through Design Mersen EP formerly Ferraz Shawmut Agenda Who is Mersen? Selective Coordination Code Requirements Coordination Made Easy Mitigating Arc Flash Energy on Transformer Secondary
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph
More informationAfci TR Duplex 20A 125V Iv. Features amperage rating. Dimensions and Weight. Descriptions
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 TRAFCI20V Afci TR Duplex 20A 125V Iv Eaton Wiring Devices Catalog Number Manufacturer Description Weight per unit Product
More informationMODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT
TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel
More informationAfci TR Duplex 20A 125V La. Features amperage rating 20. Dimensions and Weight Width 3.3. Long Description
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 TRAFCI20LA Afci TR Duplex 20A 125V La Eaton Wiring Devices Catalog Number Manufacturer Weight per unit Product Category
More informationMODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL
TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External
More informationAdvances in Load Center Technologies and End-of-Life GFCI Breaker Limitations
Advances in Load Center Technologies and End-of-Life GFCI Breaker Limitations Advances in Load Center Technologies and End-of-Life GFCI Breaker Limitations Rob Spragis, Director of Business Development
More informationDual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual
We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239
More informationSECTION ISOLATED POWER SYSTEMS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to
More informationVACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES
Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete
More informationNEC ROP/ROC Code Making Panel Meetings
Phoenix AZ - December 4-16 2000 Log # 2367 2-64 - ( 210-8(b)(3) ): SUBMITTER: Monte R. Ewing State of Wisconsin The panel reaffirms its action and statement on Proposal 2-81. There is no supporting data
More information2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100
Significant Changes to the NFPA 70E Standard 2012 Edition Tech Topics: Standards & Codes Note 4, Issue 1 Peter Walsh, PE Sr. Field Engineer Points of Interest: Arc-Rated (AR) vs. Flame-Resistant (FR) Training
More informationDual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual
We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239
More informationASSESSING THE HIDDEN DANGERS IN YOUR INDUSTRIAL CONTROL PANELS
Schneider Electric NEC 409.2 January 15, 2008 ASSESSING THE HIDDEN DANGERS IN YOUR INDUSTRIAL CONTROL PANELS by Grant Van Hemert, P.E., application engineer, Water and Wastewater Competency Center, Schneider
More informationHESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove
HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove Jim Dungar, P.E. Principal Engineer Schneider Electric Engineering Services Jim.dungar@schneider-electric.com (920-766-8012)
More informationPipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual
MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...
More informationSECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the
More informationRESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS
RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS Key Questions for Residential Inspections 1. What wiring methods will be used, and are the wiring methods suitable for the conditions? 2. Will multiwire branch
More informationElectrical Tech Note 107
Electrical Tech Note 107 Biosystems & Agricultural Engineering Department Michigan State University Understanding the Construction Code Rules, Part 8 1 Based on the 2014 NEC and the 2015 MRC The State
More informationNFPA Edition Review
This is a photographic template your photograph should fit precisely within this rectangle. NFPA 70 & 99 How Recent Code Changes Effect Healthcare Facilities Sam C. Terry, P.E. Application Engineer Eaton
More informationTPI Corporation P.O. BOX 4973 JOHNSON CITY, TN
TPI Corporation P.O. BOX 4973 JOHNSON CITY, TN 37602 www.tpicorp.com GF-SK-1 Ground Fault Sensor Switch For FSS AND FSP Series Cart Heaters REFER TO COMPLETE INDEX OF INFORMATION ON PAGE 2 INDEX GENERAL
More informationNEC Code Changes. Overview of 2011 Related to Electrical Wiring Devices. Cablofil. Pass & Seymour. Wiremold
NEC Code Changes Overview of 2011 Related to Electrical Wiring Devices Cablofil Pass & Seymour Wiremold 104 P Street Belle Chasse, LA 70037 504-394-4132, fax 504-394-6922 www.pembaserv.com Legrand/Pass
More informationArc Fault Sensing Device: Residential Testing Scenario
Jason A. Bender ECET 491/ ENG 421 Spring 2010 According to the United States Fire Administration, approximately 67,800 fires occur annually due to problems in a home s electrical system 485 deaths 2,300
More informationNEC {CODE CHANGES. OVERVIEW OF 2014 Related to Electrical Wiring Devices. Cablofil. Pass & Seymour. Wiremold
NEC {CODE CHANGES OVERVIEW OF 2014 Related to Electrical Wiring Devices { Cablofil Pass & Seymour Wiremold TABLE OF CONTENTS Page i NEC SECTION DESCRIPTION PAGE 210.8(A)(9) GFCI Protection of Receptacles
More informationSingle Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual
We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239
More informationNATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY
A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -
More informationNFPA 70 May 2001 ROP Copyright 2000, NFPA
(Log #4129) 2-99 - (210-11(d) (New) ): Reject SUBMITTER: David T. Brender, Cooper Development Assn. Inc. RECOMMENDATION: Add text to read as follows: (d) Dwelling Unit - Habitable Room Branch Circuits.
More informationONE- AND TWO-FAMILY DWELLING ELECTRICAL CODE HANDOUT (2015 Michigan Residential Code Effective February 8, 2016)
Cheboygan County Department of Building Safety 870 South Main Street P.O. Box 70 Cheboygan, Michigan 49721 TX: (231) 627-8813 FX: (231) 627-8454 www.cheboygancounty.net Service Entrance ONE- AND TWO-FAMILY
More informationSECTION AUTOMATIC TRANSFER SWITCHES
SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationIntellectual Properties, Trademarks and Copyrights
Intellectual Properties, Trademarks and Copyrights ExamREVIEW.NET (a.k.a. ExamREVIEW) is an independent content developer not associated/affiliated with the certification vendor(s) mentioned throughout
More informationResidential Wiring (2014 NEC) (Homestudy)
Residential Wiring (2014 NEC) (Homestudy) Oregon Electrical License This course will cover the requirements in the 2014 NEC for installing electrical systems in dwelling units. Code sections for residential
More informationSECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.
SECTION 16470 PANELBOARDS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16120 - Wire and Cable. 3. 16475 - Overcurrent Protective Devices. 1.02 SYSTEM DESCRIPTION A. Performance
More informationIMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016
IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS June 17th, 2016 RE: City Council Adopts 2014 National Electrical Code with Pool Alarm Requirements On April 25th, 2016 the
More informationINSTALLATION AND OPERATING INSTRUCTIONS. For Reliance Controls Emergency Power Transfer Switch Kit Model Number 30216BRK
INSTALLATION AND OPERATING INSTRUCTIONS For Reliance Controls Emergency Power Transfer Switch Kit Model Number 30216BRK Congratulations on your purchase of the Reliance Controls Generator Power Transfer
More informationSAFETY INFORMATION AND WARNINGS
This manual refers to the Model SST-3 control panel manufactured since October 31, 2013, which uses a universal (100 277 VAC; 50/60 Hz) power supply. Older units use a voltage-specific power supply and
More informationPlease make yourselves familiar with the changes and start implementing them immediately so you can be better prepared for June 30 th, 2018.
Included below are the top fifteen changes within the 2018 Canadian Electrical Code (CEC). Here in Newfoundland and Labrador, the 2018 Code was adopted as of January 1 st, 2018 and will be enforced as
More informationAPPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL
This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with
More informationBonding Requirements For Gas Piping Systems
Bonding Requirements For Gas Piping Systems Bob Torbin February 2008 Summary of Presentation Why do we bond and ground systems? What are the requirements in the codes? What are the CSST bonding requirements?
More informationARC MAPPING IN THE ADVENT OF AFCI, GFCI, AND GFEP CIRCUIT PROTECTION DEVICES
ARC MAPPING IN THE ADVENT OF AFCI, GFCI, AND GFEP CIRCUIT PROTECTION DEVICES Kevin R. Davis, PE, CFEI, CVFI And Mark Goodson, PE Goodson Engineering, Denton, TX ABSTRACT Arc mapping is a tool that can
More informationRevisions for the 2011 National Electrical Code - Part 1
PDHonline Course E355 (3 PDH) Revisions for the 2011 National Electrical Code - Part 1 Instructor: Patrick Ouillette 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone &
More informationOverview of Significant 2017 NEC Changes
Overview of Significant 2017 NEC Changes National Fire Protection Association. All rights reserved. Five New NEC Articles Article 426 Fixed Resistance and Electrode Industrial Heating Equipment Article
More information3. RCCB (residual current operated circuit-breaker without integral overcurrent protection)
RESIDUAL CURRENT DEVICE (RCD) - Contents 1. Introduction 2. General 3. RCCB (residual current operated circuit-breaker without integral overcurrent 4. RCBO (residual current operated circuit-breaker with
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC
More informationCONTACTORS FOR AEROSPACE GROW SMARTER AND MORE CAPABLE
CONTACTORS FOR AEROSPACE GROW SMARTER AND MORE CAPABLE Karl Kitts, Director of Development Engineering for High Performance Relays AEROSPACE, DEFENSE & MARINE /// WHITE PAPER - CONTACTORS FOR AEROSPACE
More informationin the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put Into Perspective Electrocutions Can Be Prevented
Home fires are a major problem in the United States Each year, home electrical problems alone account for an estimated 53,600 fires. These fires cause more than 500 deaths, 1,400 injuries, and $1.4 billion
More informationNFPA 70E. Electrical Safety in the Workplace. KTR Associates. Joseph Deane, PE. Engineering Solutions
NFPA 70E Electrical Safety in the Workplace KTR Associates Engineering Solutions Joseph Deane, PE Goal for Today Better understanding of NFPA 70E Raise the awareness of Electrical Hazards Why the sudden
More informationEntry Level Assessment Blueprint Electrical Construction Technology
Blueprint Electrical Construction Technology Test Code: 4230 / Version: 01 Specific Competencies and Skills Tested in this Assessment: Introduction to the Electrical Construction Technology Career Identify
More informationInstallation Instructions
Installation Instructions 30 Electric Cooktop JP340, JP350, JP930, JP93, JP938, JP939 If you have questions, call 800.GE.CARES or visit our website at: www.geappliances.com BEFORE YOU BEGIN Read these
More informationGuide Specification Model CTG Automatic Transfer Switch
Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production
More informationINTELLILEVEL AUTOMATIC WATER LEVELING SYSTEM FOR POOL AND SPA
INTELLILEVEL AUTOMATIC WATER LEVELING SYSTEM FOR POOL AND SPA INSTALLATION AND USER S GUIDE IMPORTANT SAFET Y INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS 2 CUSTOMER SERVICE /
More informationManifold Installation Controller MIC-180. Installation and Operation Instructions
Manifold Installation Controller MIC-180 Installation and Operation Instructions For Use With Rheem-Ruud and Paloma Commercial Tankless Water Heaters Table of Contents Safety Information... 1-2 Manifold
More informationElectrisaver User and Installation Instructions
Electrisaver User and Installation Instructions The Electrisaver push button boost timer can be used to control immersion elements and other electrical appliances up to 3kW or as an override/extension
More informationAging Residential Wiring Issues: Concerns for Fatalities, Personal Injuries, and Loss of Property
Aging Residential Wiring Issues: Concerns for Fatalities, Personal Injuries, and Loss of Property Joyce Rasdall, Ph.D., Associate Professor Family and Consumer Sciences Department, Ball State University,
More informationAUTOGUARD Hubbell Self Test Ground Fault Circuit Interrupters. More innovation. More protection. More safety.
AUTOGUARD Hubbell Self Test Ground Fault Circuit Interrupters. More innovation. More protection. More safety. The GFCI that Tests Itself! You may forget, but Hubbell AutoGuard GFCI won't. Nothing delivers
More informationB. Shop Drawings: List of legends and description of materials and process used for premarking wall plates.
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 26 2416 - PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationAir Pump Up to 800 gallons
Air Pump Up to 800 gallons REMINDER CALL 1-888-755-6750 BEFORE RETURNING TO STORE. PACKAGE CONTENTS ITEM #PBPAPK40W Questions, problems, missing parts? Before returning to your retailer, call our customer
More informationTypical Installation Breaker Box Class A 50 amp, 120/240 volt, GFCI
READ THIS FIRST!!!! TYPICAL GFCI INSTALLATION GUIDELINES ATTENTION ELECTRICIAN: All PDC Spa Units must be installed with an approved G.F.C.I. in accordance with all applicable codes. Installation of G.F.C.I.
More informationSITRANS T temperature transmitters A broad product family for every application. sitrans
SITRANS T temperature transmitters A broad product family for every application sitrans The SITRANS T family High-precision, intrinsically safe, and available for a wide variety of sensors Whether you
More informationSpring Test 6 due 04/26/2013
Spring Test 6 due 04/26/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. The article that covers TV wiring installations in residences
More informationThe Association of Electrical and Medical Imaging Equipment Manufacturers Arc Fault Circuit Interrupter
Arc Fault Circuit Interrupter SUCCESS STORIES AFCIs avert potential disaster in South Carolina I would like to take the time and thank you for the Arc Fault breaker, your product saved our lives and our
More information2014 National Electrical Code & NFPA 70E/Arc Flash
Gain an understanding of the 2014 NEC s latest additions, revisions and changes. Learn the precautions needed when working with and around electricity. People and property need to be safeguarded from the
More information100A / 200A. Maximum Heating Load: Enclosure Type: NEMA 4
Contactor Panel with GFEP Data Sheet GENERAL PRODUCT INFORMATION Simplify your snowmelt installation with ProLine Radiant contactor panels with built in GFEP. These rugged panels feature built-in ground
More information