Second Revision No. 601 NFPA [ Section No [Excluding

Size: px
Start display at page:

Download "Second Revision No. 601 NFPA [ Section No [Excluding"

Transcription

1 Second Revision No. 601 NFPA [ Section No [Excluding any Sub Sections] ] Where subject to physical damage, conductors, raceways, and cables shall be protected. Informational Note: Minor damage to a raceway, cable armor, or cable insulation does not necessarily violate the integrity of either the contained conductors or the conductors insulation. Submittal Date: Mon Nov 02 11:49:07 EST 2015 Committee The informational note provides guidance to an electrical inspector that minor Statement: (superficial) damage to the jacket of a cable is not an issue. The first sentence of the proposed informational note is unnecessary since it states the obvious that physical damage doesn t just occur from normal building operation. Public Comment No NFPA [Section No [Excluding any Sub Sections]] 1/37

2 Second Revision No. 623 NFPA [ Section No (A) ] 2/37

3 (A) Minimum Cover Requirements. 3/37

4 Direct buried cable, or conduit, or other raceways shall be installed to meet the minimum cover requirements of Table Table Minimum Cover Requirements, 0 to 1000 Volts, Nominal, Burial in Millimeters (Inches) Location of Wiring Method or Circuit All locations not specified below Column 1 Direct Burial Cables or Conductors Type of Wiring Method or Circuit Column 2 Rigid Metal Conduit or Intermediate Metal Conduit Column 3 Nonmetallic Raceways Listed for Direct Burial Without Concrete Encasement or Other Approved Raceways Column 4 Residential Branch Circuits Rated 120 Volts or Less with GFCI Protection and Maximum Overcurrent Protection of 20 Amperes Column 5 Circuits for Control of Irrigation and Landscape Lighting Limited to Not More Than 30 Volts and Installed with Type UF or in Other Identified Cable or Raceway mm in. mm in. mm in. mm in. mm in a, b In trench below 50 mm (2 in.) thick concrete or equivalent Under a building (in raceway or Type MC or Type MI cable identified for direct burial) Under minimum of 102 mm (4 in.) thick concrete exterior slab with no vehicular traffic and the slab extending not less than 152 mm (6 in.) beyond the underground installation (in raceway or Type MC or Type MI cable identified for direct burial) 6 a, b (in raceway or Type MC or Type MI cable identified for direct burial) (direct burial) (direct burial) (in raceway) (in raceway) Under streets, highways, roads, 600 alleys, driveways, and parking lots 4/37

5 One and twofamily dwelling driveways and outdoor parking areas, and used only for dwellingrelated purposes In or under airport runways, including adjacent 450 areas where trespassing prohibited a A lesser depth shall be permitted where specified in the installation instructions of a listed low voltage lighting system. b A depth of 150 mm (6 in.) shall be permitted for pool, spa, and fountain lighting, installed in a nonmetallic raceway, limited to not more than 30 volts where part of a listed low voltage lighting system. Notes: 1. Cover is defined as the shortest distance in millimeters mm (inches in. ) measured between a point on the top surface of any direct buried conductor, cable, conduit, or other raceway and the top surface of finished grade, concrete, or similar cover. 2. Raceways approved for burial only where concrete encased shall require concrete envelope not less than 50 mm (2 in.) thick. 3. Lesser depths shall be permitted where cables and conductors rise for terminations or splices or where access is otherwise required. 4. Where one of the wiring method types listed in Columns 1 through 3 is used for one of the circuit types in Columns 4 and 5, the shallowest depth of burial shall be permitted. 5. Where solid rock prevents compliance with the cover depths specified in this table, the wiring shall be installed in a metal raceway, or a nonmetallic raceway permitted for direct burial. The raceways shall be covered by a minimum of 50 mm (2 in.) of concrete extending down to rock. Supplemental Information File Name 300.5_SR623_LM.docx Description Submittal Date: Tue Nov 03 10:35:31 PST /37

6 Committee Swimming pool, spa, and fountain low voltage lighting in a nonmetallic raceway or Statement: similar installation should not be required to be installed any deeper than any other Column 5 less than 30 volt low voltage landscape lighting. Since the actual text covering pools, spas and fountains is not located in Column 5, there are inspectors who require the nonmetallic raceway containing these low voltage lighting conductors to be installed at an 18 inch depth. 6/37

7 Second Revision No. 602 NFPA [ Section No (B) ] (B) Expansion, Expansion Deflection, and Deflection Fittings. Raceways shall be provided with expansion, expansion deflection, or deflection fittings where necessary to compensate for thermal expansion, deflection, and contraction. Informational Note: Table and Table provide the expansion information for polyvinyl chloride (PVC) and for reinforced thermosetting resin conduit (RTRC), respectively. A nominal number for steel conduit can be determined by multiplying the expansion length in Table by The coefficient of expansion for steel electrical metallic tubing, intermediate metal conduit, and rigid metal conduit is ( mm per mm of conduit for each C in temperature change) [ ( in. per inch of conduit for each F in temperature change)]. A nominal number for aluminum conduit and aluminum electrical metallic tubing can be determined by multiplying the expansion length in Table by The coefficient of expansion for aluminum electrical metallic tubing and aluminum rigid metal conduit is ( mm per mm of conduit for each C in temperature change) [ ( in. per inch of conduit for each F in temperature change)]. Submittal Date: Mon Nov 02 13:01:37 EST 2015 Committee The revised text makes it clear to inspectors, designers, and contactors that Statement: expansion deflection and deflection fittings are acceptable to be used with raceways to address thermal expansion, deflection, and contraction. Revising the text also requires a revision of the title to this subsection. Public Comment No. 99 NFPA [Section No (B)] 7/37

8 Second Revision No. 603 NFPA [ Section No (B)(1) ] (1) Fire Rated Assemblies. Wiring located within the cavity of a fire rated floor ceiling or roof ceiling assembly shall not be secured to, or supported by, the ceiling assembly, including the ceiling support wires. An independent means of secure support shall be provided and shall be permitted to be attached to the assembly. Where independent support wires are used, they shall be distinguishable by color, tagging, or other effective means from those that are part of the fire rated design. Exception: The ceiling support system shall be permitted to support wiring and equipment that have been tested as part of the fire rated assembly. Informational Note: One method of determining fire rating is testing in accordance with ANSI/ASTM E , Method for Fire Tests of Building Construction and Materials. Submittal Date: Mon Nov 02 13:48:28 EST 2015 : The ANSI/ASTM E119 has been changed from 2014 to Public Comment No. 122 NFPA [Section No (B)(1)] Public Comment No. 801 NFPA [Section No (B)(1)] 8/37

9 Second Revision No. 604 NFPA [ Section No (A) ] (A) Spacing Intervals Maximum. Conductors in vertical raceways shall be supported if the vertical rise exceeds the values in Table (A). At least one support method shall be provided for each conductor or cable assembly at the top of the vertical raceway or as close to the top as practical. Intermediate supports shall be provided as necessary to limit supported conductor lengths to not greater than those values specified in Table (A). Exception: Steel wire armor cable shall be supported at the top of the riser with a cable support that clamps the steel wire armor. A safety device shall be permitted at the lower end of the riser to hold the cable in the event there is slippage of the cable in the wire armored cable support. Additional wedge type supports shall be permitted to relieve the strain on the equipment terminals caused by expansion of the cable under load. Table (A) Spacings for Conductor Supports Conductors Conductor Size Support of Conductors in Vertical Raceways Aluminum or Copper Clad Aluminum Copper m ft m ft 18 AWG through 8 AWG Not greater than AWG through 1/0 AWG Not greater than /0 AWG through 4/0 AWG Not greater than Over 4/0 AWG through 350 kcmil Not greater than Over 350 kcmil through 500 kcmil Not greater than Over 500 kcmil through 750 kcmil Not greater than Over 750 kcmil Not greater than Submittal Date: Mon Nov 02 13:51:21 EST /37

10 Committee Statement: Deleting cable assembly ensures that each individual conductor is supported at the top of a vertical raceway. Public Comment No NFPA [Section No (A)] Second Revision No. 605 NFPA [ Section No (C)(3) ] (3) Equipment. Electrical equipment with a metal enclosure, or electrical equipment with a nonmetallic enclosure listed for use within an air handling space and having low smoke and heat release properties, and associated wiring material suitable for the ambient temperature shall be permitted to be installed in such other space unless prohibited elsewhere in this Code. Informational Note: One method to determine low smoke and heat release properties is that the equipment exhibits a maximum peak optical density of 0.50 or less, an average optical density of 0.15 or less, and a peak heat release rate of 100kW or less when tested in accordance with ANSI/UL , Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air Handling Spaces. Exception: Integral fan systems shall be permitted where specifically identified for use within an air handling space. Submittal Date: Mon Nov 02 14:16:41 EST 2015 Committee Statement: This updates the informational note to the latest version of UL ANSI has been retained in the title of the UL Standard. Public Comment No. 163 NFPA [Section No (C)(3)] 10/37

11 Second Revision No. 624 NFPA [ Section No ] Aboveground Wiring Methods. Aboveground conductors shall be installed in rigid metal conduit, in intermediate metal conduit, in electrical metallic tubing, in RTRC and PVC conduit, in cable trays, in auxiliary gutters, as busways, as cablebus, in other identified raceways, or as exposed runs of metal clad cable suitable for the use and purpose. In locations accessible to qualified persons only, exposed runs of Type MV cables, bare conductors, and bare busbars shall also be permitted. Busbars shall be permitted to be either copper or aluminum. Exception: Airfield lighting cable used in series circuits that are powered by regulators and installed in restricted airport lighting vaults shall be permitted as exposed cable installations. Informational Note: FAA L 824 cables installed as exposed runs within a restricted vault area are common applications. Submittal Date: Tue Nov 03 11:12:31 PST 2015 Committee This revision recognizes that these cables are often installed exposed within a Statement: restricted airport lighting vault to facilitate easy access for modifications and reconnections during emergency situations. Public Comment No. 108 NFPA [Section No ] Public Comment No. 113 NFPA [Section No ] Public Comment No. 115 NFPA [Section No ] Public Comment No NFPA [Section No ] Public Comment No NFPA [Section No ] Public Comment No. 246 NFPA [Section No ] 11/37

12 Second Revision No. 606 NFPA [ Section No (G) ] (G) Splices. A box, conduit body, or other enclosure, with a cover installed, shall be required for all splices except where: (1) The circuit conductors being spliced are all from nonmetallic multiconductor cord or cable assemblies, provided that the equipment grounding continuity is maintained with or without the box. (2) The circuit conductors being spliced are all from metal sheathed cable assemblies terminated in listed fittings that mechanically secure the cable sheath to maintain effective electrical continuity. Submittal Date: Mon Nov 02 16:08:00 EST 2015 Committee Statement: The addition of nonmetallic ensures that (1) applies to splices of multiconductor cords or cable assemblies with a nonmetallic jacket. Public Comment No. 826 NFPA [Section No (G)] 12/37

13 Second Revision No. 607 NFPA [ Section No (J) ] (J) Support. Cable assemblies and flexible cords and cables shall be supported in place at intervals that ensure that they will be protected from physical damage. Support shall be in the form of staples, cable ties, straps, or similar type fittings installed so as not to cause damage. Cable assemblies and flexible cords and cables installed as branch circuits or feeders shall not be installed on the floor or on the ground. Extension cords shall not be required to comply with 590.4(J). Multiconductor cord or cable of a type identified in Table for hard usage or extra hard usage shall not be required to comply with 590.4(J). Vegetation shall not be used for support of overhead spans of branch circuits or feeders. Exception: For holiday lighting in accordance with 590.3(B), where the conductors or cables are arranged with strain relief devices, tension take up devices, or other approved means to avoid damage from the movement of the live vegetation, trees shall be permitted to be used for support of overhead spans of branch circuit conductors or cables. Submittal Date: Mon Nov 02 16:11:00 EST 2015 Committee Multiconductor cords or cables that are identified in Table for hard usage or Statement: extra hard usage shall not be required to comply with 590.4(J) as far as support is concerned. The extra text helps clarify what types of cords are acceptable for this temporary application. Public Comment No NFPA [Section No (J)] 13/37

14 Second Revision No. 608 NFPA [ Section No (B) ] (B) Use of Other Outlets. For temporary wiring installations, receptacles, other than those covered by 590.6(A)(1) through (A)(3) used to supply temporary power to equipment used by personnel during construction, remodeling, maintenance, repair, or demolition of buildings, structures, or equipment, or similar activities, shall have protection in accordance with (B)(1), (B)(2), or the assured equipment grounding conductor program in accordance with (B)(2) (3). (1) GFCI Protection. Ground fault circuit interrupter protection for personnel. (2) SPGFCI Protection. Special purpose ground fault circuit interrupter protection for personnel. (3) Assured Equipment Grounding Conductor Program. A written assured equipment grounding conductor program continuously enforced at the site by one or more designated persons to ensure that equipment grounding conductors for all cord sets, receptacles that are not a part of the permanent wiring of the building or structure, and equipment connected by cord and plug are installed and maintained in accordance with the applicable requirements of , , 406.4(C), and 590.4(D). (a) The following tests shall be performed on all cord sets, receptacles that are not part of the permanent wiring of the building or structure, and cord and plug connected equipment required to be connected to an equipment grounding conductor: (1) All equipment grounding conductors shall be tested for continuity and shall be electrically continuous. (2) Each receptacle and attachment plug shall be tested for correct attachment of the equipment grounding conductor. The equipment grounding conductor shall be connected to its proper terminal. (3) All required tests shall be performed as follows: a. Before first use on site b. When there is evidence of damage c. Before equipment is returned to service following any repairs d. At intervals not exceeding 3 months (b) The tests required in item (2) (3) (a) shall be recorded and made available to the authority having jurisdiction. Supplemental Information File Name Description 590.6_B_SR608_JS.docx Word document shows changes made in SR /37

15 Submittal Date: Mon Nov 02 16:19:21 EST 2015 Committee The changes to 590.6(B) involving special purpose ground fault circuit interrupter Statement: protection (SPGFCI) for personnel are accepted since Panel 2 has accepted a new definition of SPGFCI, however, Equipment Ground Fault Protective Devices (EGFPD) is listed by UL for equipment protection, not personnel protection. Since the requirements in are for protection of personnel, the changes suggested for EGFPD are not accepted. Public Comment No. 615 NFPA [Section No (B)] 15/37

16 Second Revision No. 609 NFPA [ Section No (C) ] (C) Ducts, Plenums, and Other Air Handling Spaces. Class 1, Class 2, and Class 3 circuits installed in ducts, plenums, or other space used for environmental air shall comply with Exception No. 1: As permitted in Class 2 and Class 3 cables selected in accordance with Table and installed in accordance with (B) and (B), Exception shall be permitted to be installed in ducts specifically fabricated for environmental air.. Exception No. 2: Class 2 and Class 3 cables selected in accordance with Table and installed in accordance with (C) shall be permitted to be installed in other spaces used for environmental air (plenums). Submittal Date: Mon Nov 02 16:24:52 EST 2015 Committee The First Revision FR 614 modified (B) by adding a new Exception indicating Statement: Class 2 and Class 3 cables are permitted in ducts specifically fabricated for environmental air with two conditions (a) The wiring methods or cabling systems shall be permitted only if necessary to connect to equipment or devices associated with the direct action upon, or sensing of the contained air and (b) The total length of such wiring methods or cabling systems shall not exceed 1.2 m (4 ft). These two conditions correspond to Section in NFPA 90A The 2017 First Revision FR 614 in (B) reads as follows: Exception: Wiring methods and cabling systems, listed for use in other spaces used for environmental air (plenums), shall be permitted to be installed in ducts specifically fabricated for environmental air handling purposes under the following conditions: (a) The wiring methods or cabling systems shall be permitted only if necessary to connect to equipment or devices associated with the direct action upon, or sensing of the contained air and (b) The total length of such wiring methods or cabling systems shall not exceed 1.2 m (4 ft). Class 2 or Class 3 plenum rated cable is acceptable in ducts specifically fabricated 16/37

17 for environmental air but only where connecting to equipment used to sense or has direction action on the contained air and limited to a maximum of 4foot length based on NFPA 90A. Public Comment No. 460 NFPA [Section No (C)] Second Revision No. 610 NFPA [ New Section after (B) ] (C) The power sources for limited power circuits in (A)(3) and limited power circuits for listed audio/video information technology (equipment) and listed industrial equipment in (A)(4) shall have a label indicating the maximum voltage and current output for each connection point. The effective date shall be January 1, Submittal Date: Mon Nov 02 17:03:37 EST 2015 Committee This new section addresses labeling of limited power circuit output connection Statement: points on listed IT equipment and listed industrial control panels and equipment. Bundling of large numbers of Class 2 conductors from IT servers and other similar IT and industrial equipment can create safety issues with very small current levels so having the output ports identified with the current and voltage rating is critical so the installer can connect the proper cable types. Labeling the output connections will permit the installer to have ready access to the current and voltage levels at the point of connection at the equipment, rather than internally within the equipment. The effective date was inserted to allow the manufacturers to comply with this requirement. Public Comment No NFPA [New Section after ] 17/37

18 Second Revision No. 612 NFPA [ Section No ] Installation of Conductors and Equipment in Cables, Compartments, Cable Trays, Enclosures, Manholes, Outlet Boxes, Device Boxes, Raceways, and Cable Routing Assemblies for Class 2 and Class 3 Circuits. Conductors and equipment for Class 2 and Class 3 circuits shall be installed in accordance with through Submittal Date: Mon Nov 02 19:38:52 EST 2015 : The addition of requires modification of Public Comment No. 689 NFPA [Section No ] 18/37

19 Second Revision No. 613 NFPA [ Section No (A) ] (A) Listing. Class 2, Class 3, and PLTC cables installed in buildings shall be listed and labeled. Submittal Date: Tue Nov 03 08:10:11 PST 2015 Committee FR 638 already accepted this text. The panel reaffirms its stance on this topic: By Statement: adding the word "labeled," it will identify that listed products also need to be labeled. Both terms "listed" and "labeled" are defined in Article 100, but are not used consistently throughout the NEC. Public Comment No NFPA [Section No (A)] 19/37

20 Second Revision No. 620 NFPA [ Section No (K) ] (K) Other Building Locations. The following wires and cables shall be permitted to be installed in building locations other than the locations covered in (B) through (I): (1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables (2) A maximum of 3 m (10 ft) of exposed Type CL2X wires and cables in nonconcealed spaces (3) A maximum of 3 m (10 ft) of exposed Type CL3X wires and cables in nonconcealed spaces (4) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables installed in the following: a. Plenum communications raceways b. Plenum cable routing assemblies c. Riser communications raceways d. Riser cable routing assemblies e. General purpose communications raceways f. General purpose cable routing assemblies (5) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC cables installed in raceways recognized in Chapter 3 (6) Type CMUC undercarpet communications wires and cables installed under carpet, floor covering, modular tiles, or planks. Carpet, floor covering, modular tiles, or planks shall be free floating and shall use interlocking means to attach to each other or shall be adhered to the floor and shall be attached with release type adhesives, but shall not be attached to the floor using grout, nails, or screws modular flooring, and planks Submittal Date: Tue Nov 03 09:59:16 PST 2015 Committee Type CMUC under carpet communication wire and cables are permitted to be Statement: installed under carpet with an installation expansion for modular flooring and planks. 20/37

21 The installation instructions for free floating and interlocking does not necessarily apply to all kinds of modular flooring and planks and could be overly restrictive. Public Comment No. 223 NFPA [Section No (K)] 21/37

22 Second Revision No. 621 NFPA [ Section No (L) ] (L) Multifamily Dwellings. The following wires and cables shall be permitted to be installed in multifamily dwellings in locations other than the locations covered in (B) through (I): (1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC wires and cables (2) Type CL2X wires and cables less than 6 mm ( 1 4 in.) in diameter in nonconcealed spaces (3) Type CL3X wires and cables less than 6 mm ( 1 4 in.) in diameter in nonconcealed spaces (4) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC wires and cables installed in the following: a. Plenum communications raceways b. Plenum cable routing assemblies c. Riser communications raceways d. Riser cable routing assemblies e. General purpose communications raceways f. General purpose cable routing assemblies (5) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC wires and cables installed in raceways recognized in Chapter 3 (6) Type CMUC undercarpet communications wires and cables installed under carpet, floor covering, modular tiles, or planks. Carpet, floor covering, modular tiles, or planks shall be free floating and shall use interlocking means to attach to each other or shall be adhered to the floor and shall be attached with release type adhesives, but shall not be attached to the floor using grout, nails, or screws modular flooring, and planks Submittal Date: Tue Nov 03 10:02:54 PST 2015 Committee Type CMUC under carpet communication wire and cables are permitted to be Statement: installed under carpet with an installation expansion for modular flooring and planks. 22/37

23 The installation instructions for free floating and interlocking does not necessarily apply to all kinds of modular flooring and planks and could be overly restrictive. Public Comment No. 224 NFPA [Section No (L)] 23/37

24 Second Revision No. 622 NFPA [ Section No (M) ] (M) One and Two Family Dwellings. The following wires and cables shall be permitted to be installed in one and two family dwellings in locations other than the locations covered in (B) through (I): (1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC wires and cables (2) Type CL2X wires and cables less than 6 mm ( 1 4 in.) in diameter (3) Type CL3X wires and cables less than 6 mm ( 1 4 in.) in diameter (4) Communications wires and Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables installed in the following: a. Plenum communications raceways b. Plenum cable routing assemblies c. Riser communications raceways d. Riser cable routing assemblies e. General purpose communications raceways f. General purpose cable routing assemblies (5) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC wires and cables installed in raceways recognized in Chapter 3 (6) Type CMUC undercarpet communications wires and cables installed under carpet, floor covering, modular tiles, or planks. Carpet, floor covering, modular tiles, or planks shall be free floating and shall use interlocking means to attach to each other or shall be adhered to the floor and shall be attached with release type adhesives, but shall not be attached to the floor using grout, nails, or screws modular flooring, and planks Submittal Date: Tue Nov 03 10:03:55 PST 2015 Committee Type CMUC under carpet communication wire and cables are permitted to be Statement: installed under carpet with an installation expansion for modular flooring and planks. The installation instructions for free floating and interlocking does not necessarily apply to all kinds of modular flooring and planks and could be overly restrictive. 24/37

25 Second Revision No. 614 NFPA [ Part IV. ] Listing and Marking of Equipment for Power and Data Transmission. The listed power source for circuits intended to provide power and data over Class 2 cables to remote equipment shall be as specified in (A)(1), (A)(2), (A)(3), or (A)(4). In accordance with (B), the power sources shall not have the output connections paralleled or otherwise interconnected, unless listed for such interconnection. Powered devices connected to a circuit supplying data and power shall be listed. Marking of equipment output connections shall be in accordance with (C). Submittal Date: Tue Nov 03 08:14:41 PST 2015 Committee This new section provides appropriate references to other Sections within Article Statement: 725 that apply to Power and Data Transmission equipment. Marking of the output connections was referred back to (C) where the marking requirement originates. Public Comment No. 691 NFPA [Part IV.] 37/37

26 Public Comment No. 225 NFPA [Section No (M)] 25/37

27 Second Revision No. 611 NFPA [ New Section after ] Transmission of Power and Data. The requirements of (A) and (B) shall apply to Class 2 and Class 3 circuits that transmit power and data to a powered device. The requirements of Parts I and III of Article 725 and shall apply to Class 2 and Class 3 circuits that transmit power and data. The conductors that carry power for the data circuits shall be copper. The current in the power circuit shall not exceed the current limitation of the connectors. Informational No. 1: One example of the use of cables that transmit power and data is the connection of closed circuit TV cameras (CCTV). Informational Note No. 2: The 8P8C connector is in widespread use with powered communications systems. These connectors are typically rated at 1.3 amperes maximum. Table Ampacities of Each Conductor in Amperes in 4 Pair Class 2 or Class 3 Data Cables Based on Copper Conductors at an Ambient Temperature of 30 C (86 F) with all All Conductors in All Cables Carrying Current, 60 C (140 F), 75 C (167 F), and 90 C (194 F) Rated Cables AWG Number of 4 Pair Cables in a Bun Temperature Rating Temperature Rating Temperature Rating Temperature Rating 60 C 75 C 90 C 60 C 75 C 90 C 60 C 75 C 90 C 60 C 75 C 90 C 60 C Note 1: For bundle sizes over 192 cables, or for conductor sizes smaller than 26 AWG, ampacities shall be permitted to be determined by qualified personnel under engineering supervision. Note 2: Where only half of the conductors in each cable are carrying current, the values in the table shall be permitted to be increased by a factor of 1.4. Informational Note: The conductor sizes in data cables in wide spread use are typically AWG. Te 26/37

28 (A) Use of Class 2 or Class 3 Cables to Transmit Power and Data. Where Types CL3P, CL2P, CL3R, CL2R, CL3, or CL2 transmit power and data, the following shall apply, as applicable: (1) The ampacity ratings in Table shall apply at an ambient temperature of 30 C (86 F). (2) For ambient temperatures above 30 C (86 F), the correction factors of (B) (2) shall apply. Informational Note: One example of the use of Class 2 cables is a network of closed circuit TV cameras using 24 AWG, 60 C rated, Type CL2R, Category 5e local area network (LAN) cables. (B) Use of Class 2 LP or Class 3 LP Cables to Transmit Power and Data. Types CL3P LP, CL2P LP, CL3R LP, CL2R LP, CL3 LP, or CL2 LP shall be permitted to supply power to equipment at a current level up to the marked ampere limit located immediately following the suffix LP and shall be permitted to transmit data to the equipment. The Class 2 LP and Class 3 LP cables shall comply with the following, as applicable: Informational Note 1: The (xxa) following the suffix LP indicates the ampacity of each conductor in a cable. Informational Note 2: An example of a limited power (LP) cable is a cable marked Type CL2 LP(0.5A), 23 AWG. A Type CL2 LP(0.5), 23 AWG could be used in any location where a Type CL2 could be used; however, the LP cable would be suitable for carrying up to 0.5 A per conductor, regardless of the number of cables in a bundle. If used in a 7 cable bundle, the same cable could carry up to 1.2 amperes per conductor. (1) Cables with the suffix LP shall be permitted to be installed in bundles, raceways, cable trays, communications raceways, and cable routing assemblies. (2) Cables with the suffix LP and a marked ampere level shall follow the substitution hierarchy of Table and Figure (A) for the cable type without the suffix LP and without the marked ampere level. (3) System design shall be permitted by qualified persons under engineering supervision. Supplemental Information File Name _SR611_JS.docx Description For staff use. 27/37

29 Submittal Date: Mon Nov 02 19:37:38 EST 2015 Committee The new section and the accompanying table has been added based upon Statement: the Fact Finding Report on Power over Local Area Network type cables with additionally an introduction to new cable type LP that provides the current limitation due to cable bundling and some other installation considerations for power over Ethernet. Public Comment No. 692 NFPA [Section No ] Public Comment No NFPA [Section No ] 28/37

30 Second Revision No. 617 NFPA [ Section No (A) ] (A) Listing. PLFA cables installed in buildings shall be listed and labeled. Submittal Date: Tue Nov 03 08:55:04 PST 2015 Committee FR 634 already accepted this text. The panel reaffirms its stance on this topic: By Statement: adding the word "labeled," it will identify that listed products also need to be labeled. Both terms "listed" and "labeled" are defined in Article 100, but are not used consistently throughout the NEC. Public Comment No NFPA [Section No (A)] 34/37

31 Second Revision No. 615 NFPA [ Section No ] Listing and Marking of Class 2, Class 3, and Type PLTC Cables. Class 2, Class 3, and Type PLTC cables, installed as wiring methods within buildings, shall be listed as resistant to the spread of fire and other criteria in accordance with (A) through (H I ) and shall be marked in accordance with (J) (J) (J) (J) (I). (A) Types CL2P and CL3P. Types CL2P and CL3P plenum cable shall be listed as suitable for use in ducts, plenums, and other space for environmental air and shall be listed as having adequate fire resistant and low smoke producing characteristics. Informational Note: One method of defining a cable that is low smoke producing and fire resistant is that the cable exhibits a maximum peak optical density of 0.50 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 1.52 m (5 ft) or less when tested in accordance with NFPA , Standard Method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air Handling Spaces. (B) Types CL2R and CL3R. Types CL2R and CL3R riser cables shall be marked as Type CL2R or CL3R, respectively, and be listed as suitable for use in a vertical run in a shaft or from floor to floor and shall be listed as having fire resistant characteristics capable of preventing the carrying of fire from floor to floor. Informational Note: One method of defining fire resistant characteristics capable of preventing the carrying of fire from floor to floor is that the cables pass the requirements of ANSI/UL , Test for Flame Propagation Height of Electrical and Optical Fiber Cable Installed Vertically in Shafts. (C) Types CL2 and CL3. Types CL2 and CL3 cables shall be marked as Type CL2 or CL3, respectively, and be listed as suitable for general purpose use, with the exception of risers, ducts, plenums, and other space used for environmental air, and shall be listed as resistant to the spread of fire. Informational Note: One method of defining resistant to the spread of fire is that the cables do not spread fire to the top of the tray in the UL flame exposure, vertical tray flame test in ANSI/UL , Standard for Safety for Vertical Tray Fire Propagation and Smoke Release Test for Electrical and Optical Fiber Cables. The smoke measurements in the test method are not applicable. Another method of defining resistant to the spread of fire is for the damage (char length) not to exceed 1.5 m (4 ft 11 in.) when performing the CSA vertical flame test for cables in cable trays, as described in CSA C22.2 No. 0.3 M 2001, Test Methods for Electrical Wires and Cables. 29/37

32 (D) Types CL2X and CL3X. Types CL2X and CL3X limited use cables shall be marked as Type CL2X or CL3X, and be listed as suitable for use in dwellings and raceways and shall be listed as resistant to flame spread. Informational Note: One method of determining that cable is resistant to flame spread is by testing the cable to the VW 1 (vertical wire) flame test in ANSI/UL , Reference Standard for Electrical Wires, Cables and Flexible Cords. (E) Type PLTC. Type PLTC nonmetallic sheathed, power limited tray cable shall be listed as being suitable for cable trays and shall consist of a factory assembly of two or more insulated conductors under a nonmetallic jacket. The insulated conductors shall be 22 AWG through 12 AWG. The conductor material shall be copper (solid or stranded). Insulation on conductors shall be rated for 300 volts. The cable core shall be two or more parallel conductors, one or more group assemblies of twisted or parallel conductors, or a combination thereof. A metallic shield or a metallized foil shield with drain wire(s) shall be permitted to be applied over the cable core, over groups of conductors, or both. The cable shall be listed as resistant to the spread of fire. The outer jacket shall be a sunlight and moisture resistant nonmetallic material. Type PLTC cable used in a wet location shall be listed for use in wet locations or have a moisture impervious metal sheath. Exception No. 1: Where a smooth metallic sheath, continuous corrugated metallic sheath, or interlocking tape armor is applied over the nonmetallic jacket, an overall nonmetallic jacket shall not be required. On metallic sheathed cable without an overall nonmetallic jacket, the information required in shall be located on the nonmetallic jacket under the sheath. Exception No. 2: Conductors in PLTC cables used for Class 2 thermocouple circuits shall be permitted to be any of the materials used for thermocouple extension wire. Informational Note: One method of defining resistant to the spread of fire is that the cables do not spread fire to the top of the tray in the UL flame exposure, vertical tray flame test in ANSI/UL , Standard for Safety for Vertical Tray Fire Propagation and Smoke Release Test for Electrical and Optical Fiber Cables. The smoke measurements in the test method are not applicable. Another method of defining resistant to the spread of fire is for the damage (char length) not to exceed 1.5 m (4 ft 11 in.) when performing the CSA vertical tray flame test for cables in cable trays, as described in CSA C22.2 No. 0.3 M 2001, Test Methods for Electrical Wires and Cables. (F) Circuit Integrity (CI) Cable or Electrical Circuit Protective System. Cables that are used for survivability of critical circuits under fire conditions shall meet either (F)(1) or (F)(2) as follows: (1) Circuit Integrity (CI) Cables. Circuit Integrity (CI) cables, specified in (A), (B), (C), and (E), and used for survivability of critical circuits, shall have the additional classification using the suffix CI. Circuit integrity (CI) cables shall only be permitted to be installed in a raceway where specifically listed and marked as part of an electrical circuit protective system as covered in (F)(2). 30/37

33 (2) Electrical Circuit Protective System. Cables specified in (A), (B), (C), (E), and (F)(1) that are part of an electrical circuit protective system shall be identified with the protective system number and hourly rating printed on the outer jacket of the cable and installed in accordance with the listing of the protective system. Informational Note No. 1: One method of defining circuit integrity (CI) cable or an electrical circuit protective system is by establishing a minimum 2 hour fireresistive rating when tested in accordance with UL , Standard for Tests of Fire Resistive Cables. Informational Note No. 2: UL guide information for electrical circuit protective systems (FHIT) contains information on proper installation requirements to maintain the fire rating. (G) Class 2 and Class 3 Cable Voltage Ratings. Class 2 cables shall have a voltage rating of not less than 150 volts. Class 3 cables shall have a voltage rating of not less than 300 volts. Class 2 and Class 3 cables shall have a temperature rating of not less than 60 C (140 F). (H) Class 3 Single Conductors. Class 3 single conductors used as other wiring within buildings shall not be smaller than 18 AWG and shall be Type CL3. Conductor types described in (B) that are also listed as Type CL3 shall be permitted. Informational Note: One method of defining resistant to the spread of fire is that the cables do not spread fire to the top of the tray in the UL flame exposure, vertical tray flame test in ANSI/UL , Standard for Safety for Vertical Tray Fire Propagation and Smoke Release Test for Electrical and Optical Fiber Cables. The smoke measurements in the test method are not applicable. Another method of defining resistant to the spread of fire is for the damage (char length) not to exceed 1.5 m (4 ft 11 in.) when performing the CSA vertical tray flame test for cables in cable trays, as described in CSA C22.2 No. 0.3 M 2001, Test Methods for Electrical Wires and Cables. (I) Limited Power (LP) Cables. Limited power (LP) cables shall be listed as suitable for carrying power and data circuits up to a specified current limit for each conductor without exceeding the temperature rating of the cable where the cable is installed in cable bundles in free air or installed within a raceway, cable tray, or cable routing assembly. The cables shall be marked with the suffix LP with the ampere limit located immediately following the suffix LP, where the current limit is in amperes per conductor. Informational Note: The ampere limit located immediately following the suffix LP is the ampacity of each conductor in a cable. For example, 1 ampere Class 2 limited power cables would be marked CL2 LP (1.0A), CL2R LP (1.0A), or CL2 LP (1.0A). 31/37

34 (J) Marking. Cables shall be marked in accordance with (A)(2), (A)(3), (A)(4), (A)(5), and Table (K) Table (J). Voltage ratings shall not be marked on the cables. Temperature rating shall be marked on the jacket of Class 2 and Class 3 cables that have a temperature rating exceeding 60 C (140 F). Informational Note: Voltage markings on cables may be misinterpreted to suggest that the cables may be suitable for Class 1 electric light and power applications. Exception: Voltage markings shall be permitted where the cable has multiple listings and a voltage marking is required for one or more of the listings. Temperature rating shall be marked on the jacket of Class 2 and Class 3 cables that have a temperature rating exceeding 60 C (140 F). Table (J) Cable Marking CL3P CL2P CL3R CL2R PLTC CL3 CL2 CL3X CL2X Cable Marking Type Class 3 plenum cable Class 2 plenum cable Class 3 riser cable Class 2 riser cable Power limited tray cable Class 3 cable Class 2 cable Class 3 cable, limited use Class 2 cable, limited use Informational Note: Class 2 and Class 3 cable types are listed in descending order of fire resistance rating, and Class 3 cables are listed above Class 2 cables because Class 3 cables can substitute for Class 2 cables. Submittal Date: Tue Nov 03 08:20:28 PST 2015 : Information on limited power cables is being added to the Code. Public Comment No. 688 NFPA [Section No ] 32/37

35 Second Revision No. 616 NFPA [ Section No (B) ] (B) Ducts, Plenums, and Other Air Handling Spaces. Section , where Power limited and non power limited fire alarm cables installed in ducts or, plenums, or other spaces used for environmental air shall comply with Exception No. 1: As permitted in (B)(1) and (B)(2) and Table Power limited fire alarm cables selected in accordance with Table and installed in accordance with (B) and (B), Exception shall be permitted to be installed in ducts specifically fabricated for environmental air. Exception No. 2: Power limited fire alarm cables selected in accordance with Table and installed in accordance with (C) shall be permitted to be installed in other spaces used for environmental air (plenums). Submittal Date: Tue Nov 03 08:40:41 PST 2015 Committee The existing exception was not in compliance with the NEC Style manual. The Statement: second exception was inserted to deal with power limited fire alarm cables installed in other spaces used for environmental air (plenums). The reference to (B), Exception was inserted to ensure correlation with the requirements in NFPA 90A. Public Comment No. 454 NFPA [Section No (B)] 33/37

36 Second Revision No. 618 NFPA [ Section No [Excluding any Sub Sections] ] Non power limited fire alarm cables installed as wiring within buildings shall be listed in accordance with (A) and (B) and as being resistant to the spread of fire in accordance with (C) through (F), and shall be marked in accordance with (G). Cable used in a wet location shall be listed for use in wet locations or have a moisture impervious metal sheath. Non power limited fire alarm cables shall have a temperature rating of not less than 60 C (140 F). Submittal Date: Tue Nov 03 08:57:59 PST 2015 Committee Statement: The temperature rating of these cables is required to provide pertinent information so the installer is aware of the temperature limitation of the conductors. Public Comment No. 461 NFPA [Section No [Excluding any Sub Sections]] 35/37

37 Second Revision No. 619 NFPA [ Section No (C) ] (C) Ratings. The cable shall have a voltage rating of not less than 300 volts. The cable shall have a temperature rating of not less than 60 C (140 F). Submittal Date: Tue Nov 03 08:59:57 PST 2015 Committee Statement: The temperature rating of these cables is required to provide pertinent information so the installer is aware of the temperature limitation of the conductors. Public Comment No. 450 NFPA [Section No (C)] 36/37

SUBJECT: NFPA 70 Second Draft TC Ballot Final Results (A2016)

SUBJECT: NFPA 70 Second Draft TC Ballot Final Results (A2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: NEC Code-Making Panel 3 FROM: Kimberly Shea, Administrator, Technical

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 3 From: Kimberly Shea, Project Administrator

More information

Fire Alarm Systems ARTICLE. Introduction to Article 760 Fire Alarm Systems. Part I. General

Fire Alarm Systems ARTICLE. Introduction to Article 760 Fire Alarm Systems. Part I. General ARTICLE 760 Fire Alarm Systems Introduction to Article 760 Fire Alarm Systems Article 760 covers the installation of wiring and equipment for fire alarm systems, including all circuits controlled and powered

More information

NEC 2017 Changes and Their Effect Upon the ICT Industry

NEC 2017 Changes and Their Effect Upon the ICT Industry NEC 2017 Changes and Their Effect Upon the ICT Industry Today s Presenters John Kacperski, RCDD, OSP, CDT Chair of BICSI Standards BICSI Representative on NFPA 70-CMP 16 Richard S. Anderson, RCDD, CDT,

More information

IDENTIFYING TRAY CABLES FOR YOUR NEXT INSTALLATION A WHITE PAPER

IDENTIFYING TRAY CABLES FOR YOUR NEXT INSTALLATION A WHITE PAPER IDENTIFYING TRAY CABLES FOR YOUR NEXT INSTALLATION A WHITE PAPER Published 3/23/2012 T hough rapidly increasing in popularity, tray cables are still a point of confusion for many. While the term tray cable

More information

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017 CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017 The City of Portsmouth adopts the State Building Code, which adopts by reference The National Electrical Code, 2017(NEC), as Chapter 15, Part IV, of the

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

Chapter 1 General... 5

Chapter 1 General... 5 About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of

More information

Fee $15 Course: NEC Changes 5 This course is valid for these credentials: Credential Description Cred Code Credit Hours

Fee $15 Course: NEC Changes 5 This course is valid for these credentials: Credential Description Cred Code Credit Hours www.garyklinka.com Page 1 of 9 Instructions: Fee $15 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 2017-08-031 AN ORDINANCE OF THE CITY OF LANCASTER, TEXAS, REPEALING THE NATIONAL ELECTRICAL CODE 2014 EDITION IN ITS ENTIRETY AND REPLACING IT WITH THE ADOPTION OF THE NATIONAL ELECTRICAL

More information

Municipal Code of Chicago TITLE 14E ELECTRICAL CODE

Municipal Code of Chicago TITLE 14E ELECTRICAL CODE Municipal Code of Chicago TITLE 14E ELECTRICAL CODE Ch. 14E-1 General Ch. 14E-2 Wiring and Protection Ch. 14E-3 General Requirements for Wiring Methods and Materials Ch. 14E-4 Equipment for General Use

More information

Electrical Tech Note 107

Electrical Tech Note 107 Electrical Tech Note 107 Biosystems & Agricultural Engineering Department Michigan State University Understanding the Construction Code Rules, Part 8 1 Based on the 2014 NEC and the 2015 MRC The State

More information

CORFLEX TYPE MC-HL POWER, CONTROL & INSTRUMENTATION CABLES

CORFLEX TYPE MC-HL POWER, CONTROL & INSTRUMENTATION CABLES CORFLEX TYPE MC-HL POWER, CONTROL & INSTRUMENTATION CABLES CORFLEX TYPE MC-HL POWER, CONTROL & INSTRUMENTATION CABLES INDEX Corflex MC-HL Instrumentation - Pairs and Triads (0V*)... 1 - CORFLEX Cables

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 It has come to the attention of the electrical authorities having jurisdiction (AHJs) at the DOE sites there is inconsistency

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Updated section on Manufacturers 3 1. 6/15/16 Updated division section from 16120 to 26 05 00, - mgl44

More information

CORFLEX. TYPE MC-HL & MV-105 or MC-HL OIL & GAS CABLES

CORFLEX. TYPE MC-HL & MV-105 or MC-HL OIL & GAS CABLES CORFLEX TYPE MC-HL & MV-105 or MC-HL OIL & GAS CABLES INDEX Instrumentation Cables - Pairs and Triads (0V*)... 2 - The Original MC-HL Technology In 1958 Canada Wire and Cable, which s now part of Nexans,

More information

S U B S T I T U T E O R D I N A N C E BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF CHICAGO: ARTICLE I ELECTRICAL CODE

S U B S T I T U T E O R D I N A N C E BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF CHICAGO: ARTICLE I ELECTRICAL CODE S U B S T I T U T E O R D I N A N C E BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF CHICAGO: This ordinance is organized into eight Articles, as follows: Article I. Article II. Article III. Article

More information

2011 and 2014 National Electrical Code Changes Residential Only

2011 and 2014 National Electrical Code Changes Residential Only 2011 and 2014 National Electrical Code Changes Residential Only Sponsored By: and.net Instructor: Fritz Gunther, Chief Electrical Inspector 585-436-4460 www.nyeia.com NEW YORK ELECTRICAL INSPECTION AGENCY

More information

EFCOG Best Practice #213

EFCOG Best Practice #213 EFCOG Best Practice #13 Facility: DOE Complex Best Practice Title: Adoption of NFPA 70 017 in place of NFPA 70 014 Point of Contact: Michael Hicks NE-ID, 08-56-374, hicksmd@id.doe.gov John McAlhaney SRS,

More information

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod Journeyman and Master Common Exam 2 1 The grounding terminal of a grounding-type receptacle installed in a metal box shall be? A. Connected to the equipment ground B. Bonded to the box C. Connected to

More information

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013 Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013 1. Is a standard wire-nut approved for a wet location as in an outside j-box? Is there a listed

More information

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19 TABLE OF CONTENTS About This Textbook...xiii How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems. SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning

More information

Town of Cicero Local Code Amendments

Town of Cicero Local Code Amendments Town of Cicero Local Code Amendments 2009 International Residential Code Local Amendments: DELETE Table R302.1 (Exterior Walls), see Attachment A. DELETE Exception for Subsection R313.2 (One and Two-Family

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Is low voltage cable allowed to be run through drilled

More information

J-PRO TM Cable Support System

J-PRO TM Cable Support System Frequently Asked Questions Cable Support System What references define how and where J-hooks are used? J-hooks are a horizontal pathway promoted in the BICSI TDM manual as a means to route small to medium

More information

2017 NEC Significant Code Changes Part 3

2017 NEC Significant Code Changes Part 3 2017 NEC Significant Code Changes Part 3 Eight (8) Continuing Education Hours Wisconsin Department of Safety and Professional Services (DSPS) Course Approval #18959 Approved Continuing Education for Wisconsin

More information

Second Revision No. 321 NFPA [ Detail ] Submitter Information Verification. Committee Statement. Make the following changes to 210.

Second Revision No. 321 NFPA [ Detail ] Submitter Information Verification. Committee Statement. Make the following changes to 210. Second Revision No. 321 NFPA 70 2015 [ Detail ] Make the following changes to 210.8(B): (B) Other Than Dwelling Units. All 125 volt, single phase, 15 and 20 ampere receptacles phase receptacles rated 150

More information

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35 SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1 Overview of Low-Voltage and Power-Limited Systems...3 Chapter 4 Equipment for General Use...3 Chapter 5 Special Occupancies...3 Chapter 6 Special Equipment...4

More information

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS Key Questions for Residential Inspections 1. What wiring methods will be used, and are the wiring methods suitable for the conditions? 2. Will multiwire branch

More information

Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products

Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Manufacturers Statement of Compliance with NFPA 70, National Electric Code,

More information

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

SECTION ELECTRICAL GENERAL PROVISIONS

SECTION ELECTRICAL GENERAL PROVISIONS PART 1 GENERAL 1.01 SECTION INCLUDES A. General provisions for Electrical Systems B. Wire and cable for 600 volts and less. C. Wiring connectors. D. Electrical tape. E. Heat shrink tubing. F. Wire pulling

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Flame Retardant EP/CPE POWER, CONTROL & INSTRUMENTATION CABLES

Flame Retardant EP/CPE POWER, CONTROL & INSTRUMENTATION CABLES Flame Retardant EP/CPE POWER, CONTROL & INSTRUMENTATION CABLES 37-754 FLAME RETARDANT EP/CPE TYPE TC OR TC-ER POWER CABLE Two Five Conductor + Ground (Two, Three & Four Conductor) 600 V Rated 90 C Conductor*

More information

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING SEMINAR 301 Part 1: Changes in the 2005 NEC SEMINAR RULES: There are no Rules All Questions need to be asked Stop at any time for an explanation SEMINAR PARTS: ELECTRIC and NEON SIGN STANDARDS By Randy

More information

TOM BURNS, PLANNING DIRECTOR

TOM BURNS, PLANNING DIRECTOR ~~ 0 173 COUNTY OF SANTA CRUZ August 4,2005 PLANNING DEPARTMENT 701 OCEAN STREET, qth FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 TOM BURNS, PLANNING DIRECTOR Agenda:

More information

2014 National Electrical Code & NFPA 70E/Arc Flash

2014 National Electrical Code & NFPA 70E/Arc Flash Gain an understanding of the 2014 NEC s latest additions, revisions and changes. Learn the precautions needed when working with and around electricity. People and property need to be safeguarded from the

More information

Overview of Significant 2017 NEC Changes

Overview of Significant 2017 NEC Changes Overview of Significant 2017 NEC Changes National Fire Protection Association. All rights reserved. Five New NEC Articles Article 426 Fixed Resistance and Electrode Industrial Heating Equipment Article

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION FIBER OPTIC DATA NETWORK

2016 CDM Smith All Rights Reserved July 2016 SECTION FIBER OPTIC DATA NETWORK PART 1 GENERAL 1.01 SCOPE OF WORK SECTION 27 12 23 FIBER OPTIC DATA NETWORK A. Furnish, install, terminate, and test all fiber optic equipment and cabling necessary for a complete and functional data highway

More information

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

Applying the NEC to Telecom Design Morning Session. By Tim Kuhlman, PE RCDD CDT TEECOM

Applying the NEC to Telecom Design Morning Session. By Tim Kuhlman, PE RCDD CDT TEECOM Applying the NEC to Telecom Design Morning Session By Tim Kuhlman, PE RCDD CDT TEECOM Safety Moment Schedule 9:00am to 10:15am 10:15am 15 minute break 10:30am to 12:00pm 12:00pm to 1:30pm - Lunch 1:30pm

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW) SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill

More information

NFPA Changes

NFPA Changes Chapter 12, Circuits and Pathways Summary. Chapter 12, Circuits and Pathways, is a new chapter. It brings together requirements that were formerly found in SIG-FUN, Fundamentals of Fire Alarm Systems regarding

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES SECTION 26 05 19 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

*REPORT OF THE MOTIONS COMMITTEE

*REPORT OF THE MOTIONS COMMITTEE *REPORT OF THE MOTIONS COMMITTEE ON CERTIFIED AMENDING MOTIONS FOR PRESENTATION AT THE 2016 NFPA TECHNICAL MEETING JUNE 16, 2016 LAS VEGAS, NV FOR THE NFPA 70, NATIONAL ELECTRICAL CODE I. Introduction.

More information

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification Public Comment No. 2-NFPA 73-2014 [ Section No. 4.1.3 ] 4.1.3 Unused Openings. 4.1.3.1 Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or

More information

Oberon s NEC Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products

Oberon s NEC Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Oberon s NEC Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Manufacturers Statement of Compliance with NFPA 70, National Electric Code Oberon s suspended ceiling

More information

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. SUPPLEMENTAL CORRECTION SHEET FOR METHANE MITIGATION SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations... Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6

More information

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015 NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized

More information

MEDIUM, LOW AND CONTROL VOLTAGE CABLES

MEDIUM, LOW AND CONTROL VOLTAGE CABLES Related Sections U-M Design Guideline Sections: 260800 - Electrical Acceptance Tests Products Medium Voltage Primary Cables Primary power distribution cable shall be single conductor stranded copper, with

More information

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to: PREFACE Because of changes in installation codes, the increasing complexity of the equipment involved, and other factors, more and more markings are being used on electrical heating and cooling equipment.

More information

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Electrical identification materials and devices required to comply with ANSI C2, NFPA

More information

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR September 2012, rev. 00 26 0553 Identification for Electrical Systems PART 1. GENERAL 1.01 Summary A. Section Includes: 1.02 Submittals 1. Identification for raceways. 2. Identification of power and control

More information

5. Identification products.

5. Identification products. Essex County College - West Essex Campus Addition And Renovations dib # 54292 / 11-14 [SECTION 260523- CONTROL-VOLTAGE ELECTRICAL POWER CABLES PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general

More information

ONE- AND TWO-FAMILY DWELLING ELECTRICAL CODE HANDOUT (2015 Michigan Residential Code Effective February 8, 2016)

ONE- AND TWO-FAMILY DWELLING ELECTRICAL CODE HANDOUT (2015 Michigan Residential Code Effective February 8, 2016) Cheboygan County Department of Building Safety 870 South Main Street P.O. Box 70 Cheboygan, Michigan 49721 TX: (231) 627-8813 FX: (231) 627-8454 www.cheboygancounty.net Service Entrance ONE- AND TWO-FAMILY

More information

TABLE 1-E (2017) Effective July 1, 2017

TABLE 1-E (2017) Effective July 1, 2017 TABLE 1-E (2017) Effective July 1, 2017 Oregon Amendments to the 2017edition of the National Fire Protection Association (NFPA) 70, National Electrical Code (NEC) for the 2017 Oregon Electrical Specialty

More information

Corra/Clad MC Cable The contractors cable of choice in place of conduit and wire.

Corra/Clad MC Cable The contractors cable of choice in place of conduit and wire. Corra/Clad MC Cable The contractors cable of choice in place of conduit and wire. Installs fast and easy Lowers labor costs Replaces conduit and wire Provides superior grounding UL Listed Corra/Clad MC

More information

I dedicate this book to the Lord Jesus Christ, my mentor and teacher. Proverbs 16:3 NOTICE TO THE READER ABOUT THE AUTHOR

I dedicate this book to the Lord Jesus Christ, my mentor and teacher. Proverbs 16:3 NOTICE TO THE READER ABOUT THE AUTHOR NOTICE TO THE READER The publisher does not warrant or guarantee any of the products described herein or perform any independent analysis in connection with any of the product information contained herein.

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

Product Guide. Fire Alarm Cables. Initiating Device, SLC Lines, and NAC Cables.

Product Guide. Fire Alarm Cables. Initiating Device, SLC Lines, and NAC Cables. Fire Alarm Cables Initiating Device, SLC Lines, and NAC Cables Product Guide STANDARDS Fire Alarm Systems A fire alarm system is number of devices working together to detect and warn people through visual

More information

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist

More information

REPORT ON DISCUSSIONS DURING UL MEETINGS WITH ELECTRICAL INSPECTORS AT THE 2003 IAEI 75 th JUBILEE MEETING

REPORT ON DISCUSSIONS DURING UL MEETINGS WITH ELECTRICAL INSPECTORS AT THE 2003 IAEI 75 th JUBILEE MEETING REPORT ON DISCUSSIONS DURING UL MEETINGS WITH ELECTRICAL INSPECTORS AT THE IAEI 75 th JUBILEE MEETING September 1, 2004 TO: SUBJECT: Attendees of Underwriters Laboratories Inc. Meetings with Electrical

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY SECTION 280513 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Coaxial cabling. 2. RS-232 cabling. 3. RS-485 cabling. 4. Low-voltage control

More information

Spring Test 6 due 04/26/2013

Spring Test 6 due 04/26/2013 Spring Test 6 due 04/26/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. The article that covers TV wiring installations in residences

More information

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

2017 NEC Presented by: Russ LeBlanc

2017 NEC Presented by: Russ LeBlanc 2017 NEC Presented by: Russ LeBlanc 1. 90.2(A)-installation and removal 2. 90.3-code layout 3. 100-readily accessible 4. 100-field evaluation body (FEB) 5. 100-field labeled 6. 100-receptacle 7. 100-structure

More information

Special Provision No. 683S28 December 2017

Special Provision No. 683S28 December 2017 FIBRE OPTIC COMMUNICATION CABLES, AERIAL ON MESSENGER CABLE - Item No. FIBRE OPTIC COMMUNICATION CABLES, AERIAL ON MESSENGER CABLE (TEMPORARY) - Item No. Special Provision No. 683S28 December 2017 1. SCOPE

More information

SOUTHERN NEVADA PROPOSED AMENDMENTS TO THE 2011 NATIONAL ELECTRICAL CODE

SOUTHERN NEVADA PROPOSED AMENDMENTS TO THE 2011 NATIONAL ELECTRICAL CODE SOUTHERN NEVADA PROPOSED AMENDMENTS TO THE 2011 NATIONAL ELECTRICAL CODE ELECTRICAL CODE COMMITTEE SEPTEMBER 12, 2012 PREFACE This document was developed by the Southern Nevada Building Officials Electrical

More information

AFC Cable Systems: the Cable Industry Leader for Over 80 Years

AFC Cable Systems: the Cable Industry Leader for Over 80 Years AFC Cable Systems: the Cable Industry Leader for Over 80 Years AFC Cable Systems, Inc, is proud to announce the launch of two new Type MC cables, MC-Quik and MC-Stat. These two new cables offer the fastest

More information

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application. 1.3.1 This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except

More information

Student Guide. Wiring Edition. Compliments of. Georgia EMC East Exchange Place Tucker, GA (770)

Student Guide. Wiring Edition. Compliments of. Georgia EMC East Exchange Place Tucker, GA (770) Student Guide to Wiring 2017 Edition Compliments of Georgia EMC 2100 East Exchange Place Tucker, GA 30084 (770) 270-6950 www.georgiaemc.com Electric Membership Cooperatives of Georgia In Georgia, the 41

More information

NFPA Changes

NFPA Changes Chapter 27, Public Fire Emergency Alarm Reporting Systems Summary. Chapter 27 was Chapter 9 in NFPA 72-2007. The word fire is replaced by the word emergency. The term public fire service communications

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 17 From: Kimberly Shea, Project Administrator

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

Revisions for the 2011 National Electrical Code - Part 1

Revisions for the 2011 National Electrical Code - Part 1 PDHonline Course E355 (3 PDH) Revisions for the 2011 National Electrical Code - Part 1 Instructor: Patrick Ouillette 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone &

More information

Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004

Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004 Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004 1. A 2 PVC conduit was installed in the ground prior to setting a factory manufactured home on the foundation. The required service

More information

SECTION RADIANT-HEATING ELECTRIC CABLES PART 1 - GENERAL 1.1 SECTIONS INCLUDES

SECTION RADIANT-HEATING ELECTRIC CABLES PART 1 - GENERAL 1.1 SECTIONS INCLUDES SECTION 238313 - RADIANT-HEATING ELECTRIC CABLES PART 1 - GENERAL 1.1 SECTIONS INCLUDES A. Low-voltage Electric Snow and ice heating elements "under" finished roof materials (shingles or metal), gutters,

More information

FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS - Item No. FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS (TEMPORARY) - Item No.

FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS - Item No. FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS (TEMPORARY) - Item No. FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS - Item No. FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS (TEMPORARY) - Item No. Special Provision No. 683S01 December 2017 1. SCOPE This Special Provision covers

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

Article by: Ark Tsisserev, Principal, Stantec Consulting Ltd.

Article by: Ark Tsisserev, Principal, Stantec Consulting Ltd. Re: CEC 2012 Article by: Ark Tsisserev, Principal, Stantec Consulting Ltd. Conductors Do we have a problem with this? Apparently, we do. However, there is no reason to generalize this problem. Although

More information

Electrical Safety Requirements

Electrical Safety Requirements Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

ARTICLE 760 FIRE ALARM SYSTEMS

ARTICLE 760 FIRE ALARM SYSTEMS Mike Holt s Illustrated Guide to ARTICLE 760 FIRE ALARM SYSTEMS Based on the 2014 NEC Extracted from Mike Holt s Illustrated Guide to Understanding the National Electrical Code Volume 2 For more information

More information

SECTION (16140) - WIRING DEVICES

SECTION (16140) - WIRING DEVICES SECTION 26 27 26 (16140) - WIRING DEVICES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Receptacles, Connectors, Switches, and Finish Plates. B. Related Sections: 1. Section 00 31 13.43 (00370) -

More information

Important Upcoming Dates

Important Upcoming Dates 2011 NEC ROP Report NFPA Conference and Expo Chicago, IL June 9, 2009 Important Upcoming Dates ROP Available: On or about 6/19 Comment Closing Date: 10/23@ 5:00PM EDT ROC Meeting: 12/2 12 TCC ROC Meeting:

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 220533 - HEAT TRACING FOR PLUMBING PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes plumbing piping heat tracing for freeze prevention, domestic hot-water-temperature maintenance, and

More information

SDEC 2017 Questions, Group 1

SDEC 2017 Questions, Group 1 SDEC 2017 Questions, Group 1 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing? Answer: NEC 410.36(B)

More information

Revisions for the 2011 National Electrical Code - Part 4

Revisions for the 2011 National Electrical Code - Part 4 PDHonline Course E358 (3 PDH) Revisions for the 2011 National Electrical Code - Part 4 Instructor: Patrick Ouillette 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone &

More information

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Automatic FireAlarm Association SURVIVING SURVIVABILITY - A USER S GUIDE TO Larry D. Rietz, SET

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 83 00.00 20 (April 2006) -------------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-15768N (September 1999) UNIFIED FACILITIES GUIDE

More information

Alberta Municipal Affairs

Alberta Municipal Affairs Alberta Municipal Affairs Upcoming Already Approved by Unanimous Vote Not Required to be Considered in Charlottetown in June Clarence C. Cormier, P.Eng. Chief Electrical Inspector Bob Hall, SCO Electrical

More information