Commissioning the Fire Suppression System for 500/230 kv Transformers of EGAT s Nongchok Substation

Size: px
Start display at page:

Download "Commissioning the Fire Suppression System for 500/230 kv Transformers of EGAT s Nongchok Substation"

Transcription

1 Commissioning the Fire Suppression System for 500/230 kv Transformers of EGAT s Nongchok Substation S. Chaipitak, Electricity Generating Authority of Thailand, , Chaipitak.som@egat.co.th ABSTRACT EGAT s Nongchok substation is one of the largest substations in Thailand, as it transmits electrical power from outbound power plants and supplies to metropolitan area where most of the country s industry and economy located in. Fire suppression with liner heat detector and foam-water spray system is installed in order to protect six single-phase 500/ kv 200 MVA oil-filled transformers. Before the commissioning this fire suppression system, problems are found as the transformers are not de-energized before the foam-water spray system is activated and when the foam-water spraying, high possibility flammable spots of the transformers are not covered in the nozzles spraying area. This paper represents the problem found in the commissioning process which mainly about essential flammable spots which the oil-filled transformer s spraying area of the fire suppression system should be focused on. KEYWORDS: fire suppression system, fire protection system, automatic fixed foam, foam-water, transformer 1. Introduction When an oil-filled transformer catches on fire either by internal or external fault, the fire should be extinguished as soon as possible as it will spread and cause severe damage to the transformer. The damaged transformer may take from several weeks to months to replace and re-connect to the grid which depends on spare transformers available. Moreover, in the grid network reliability aspect, if this occurs to high-load utilization transformers, the grid will be weakened and may not support the N-1 scheme. EGAT s Nongchock substation is one of the largest transmission substations in Thailand. It consists of four voltage levels; 500 kv, 230 kv, 115 kv and 22 kv. There are sixteen oil-filled power transformers in total four are 230/ kv (200 and 300 MVA) three-phase transformers and other twelve are 500/ kv (3x200 MVA) single-phase transformers. In order to prevent the severe damaged that may cause by fire, six single-phase 500/ kv 200 MVA transformers have been installed with a fire suppression system called an Automatic fixed foam system in the beginning of This system uses 3% concentrated foam-water solution to suppress the fire. Figure 1: Six single-phase 500/ kv 200 MVA transformers Installed with the automatic fixed foam fire suppression system at EGAT s Nongchok substation 1

2 However, in order to maximize the fire suppression to full effectiveness, there are two recommendations in the installation of the automatic fixed foam fire suppression system that EGAT found during commissioning. Transformers are not de-energized before the foam-water spray system is activated and high possibility flammable spots of the transformers are not covered in the nozzles spraying area. 2. Commissioning the Fire Suppression System 2.1 The automatic fixed foam fire suppression system The automatic fixed foam fire suppression system consists of three main parts which are: 1) Foam and water supply and storage system this system consists of a diesel fire pump and an electrical jockey pump with a water storage tank and a concentrated foam bladder tank. In readyto-operate stage, the jockey pump is used to maintain the water pressure inside a fire suppression supply line ( psi) if the pressure drops below a setting valve (causes from minor leakage or evaporation) the pump will start in order to make the water pressure back to working value. When the system operates, pressure will suddenly drop and the diesel fire pump will start operate and pump water from the storage tank to suppress fire at the transformer. Before reaching the transformer, water will pass through the foam-water bladder tank where a foam-water mixer is located. The mixer will mix the concentrated foam and water at a fixed ratio of 3% foam and 97% water. a) b) c) d) Figure 2: Foam and water supply and storage system; a) Diesel fire pump, b) Jockey pump, c) Water storage tank, d) Concentrated foam bladder tank 2) Fire detector and evaluation unit a unit consists of closed-loop copper tubes which are used for heat detection and an evaluation unit which is used to automatically send and trigger an operation of foam-water releasing system. When air pressure inside the closed-loop copper tube is increasing, which caused by rising temperature, an evaluation unit will evaluate a rate of temperature rise. If the rate of rise meets with the conditions, the unit will send an alarm to a fire protection panel. The panel will send the command to open a solenoid valve at a deluge valve in order to spray a foam-water solution. 2

3 a) b) Figure 3: Fire detector and evaluation unit; a) Evaluation unit connected with closed-loop copper tube, b) Fire control panel 3) Foam-water releasing system consists of a deluge valve and nozzles are used to spray a foamwater solution to suppress fire at the transformers. When a fire control panel commands a solenoid valve of a deluge valve to open, a diaphragm inside the deluge valve will be depressurized and opened, releasing foam-water solution through nozzles. The diaphragm can also be opened manually by manual station located at the deluge valve. 2.2 Commissioning process a) b) Figure 4: Foam-water releasing system a) deluge valves, b) spraying nozzles In a commissioning process, EGAT s commissioning team had found two major problems during the transformer spray test (the conducted test using only water in order to monitor a spray pattern of the fire suppression system) that should be put into a consideration. The first major problem found when the fire suppression system is activated as the evaluation unit sent the alarm and the fire control panel opened the solenoid valve to spray foam-water solution through nozzles, the transformer is still energized. This seemed to be normal for water spraying; however, for 3% foam concentrated solution might not. The more foam concentrated solution, the more conductivities the solution will have as shown in Figure 5 (at 3% foam concentrated, the solution s conductivity is approximately 710 µs/cm) Figure 5: The conductivities of foam-water concentrated solution at 1% (540 µs/cm), 3% (710 µs/cm), And 6% (1310 µs/cm), 3

4 From the measured conductivity result, it is shown that if the foam-water concentrated solution is sprayed while the transformer is energizing, there is a possibility that the transformer will break down and cause even more severe damages. It is recommended that the transformer should be de-energized prior to the foamwater spraying via a transformer self protection relay contact. The second major problem found when the foam-water solution is sprayed. High possibility flammable spots of the transformers are not covered in the nozzles spraying area (shown in Figure 6 and 7). The considerable spots are shown in Figure 8: 1) The pocket of the high side and low side bushings, and tertiary bushing pockets of transformers bushing have high flammable possibility as they are located higher from top of the transformer and separate the high voltage part and transformer s main tank. When the foam-water solution is sprayed, the solution might not cover the fire as it flows from top to bottom. 2) Diverter switch s pits of the on-load tap changer (OLTC) During and OLTC operation, there will be an arc occurring inside the diverter switch s pit if the arc quenching equipment is not in a good condition, there is a flammable possibility. 3) Manholes, oil pipes, and cables if fire breaks out, it will spread along oil pipes, manholes and cables. All of these spots are located on top of the transformer. However, if there is any leakage of the transformer tank, the fire will also spread at the transformer s bottom. Fire suppression pipe and nozzles layout design should consider these issues. Figure 6: High possibility flammable spots of the transformers at EGAT s Nongchok substation are not covered in the nozzles spraying area 4

5 Figure 7: Spraying layout design does not cover the high possibility flammable spots (Highlighted in red) Figure 8: Transformers high possibility flammable spots 5

6 3. Results Figure 9: A transformer on fire at a Salt River Project electrical substation on June, 1 st Retrieved from: From the design layout of the EGAT s Nongchok substation fire suppression system, the commissioning team has found two major problems which are: 1. Transformer is not automatically de-energized before a foam-water solution is sprayed. 2. The nozzles spraying area is not covered high possibility flammable spots The first major problem may cause severe damages to the transformer if the fire suppression system is activated by either malfunction or manually operated by the operator. It is suggested that for system that using a conductive foam-water solution, should automatically de-energize the transformer prior spraying to prevent this problem. The second problem can be fixed by adjusting the nozzle s spraying angle as the most of high possibility flammable spots are located on top of the transformer, however, it is recommended to redesign the layout at the first hand. 4. Conclusion When the fire suppression system is triggered to operate, the catching fire transformer should be deenergized by the transformer s protection. However, in case of the malfunction or manually operation of the fire suppression systems whether there is fire or not, the transformers should be automatically de-energized in order to protect the transformer s equipment. As the fire suppression system is activated, foam-water enters the pipe line and sprays on the transformers through nozzles. Foam-water spraying should be designed for two functions which are: 1) Cooling down the transformers. 2) Covering the top of the transformers or oil to prevent combustion and separate oxygen from oil. The high possibility flammable spots of the transformers should be also considered in the design of the spraying layout. The high possibility flammable spots of the oil-filled transformer are: 1) The pockets of the high side and low side bushings, and tertiary bushing. 2) Diverter switch s pits of the on-load tap changer (OLTC). 3) Manholes, oil pipes, and cables. Fire suppression system is a need in preventing the spreading damage that may cause the severe damage to the transformer. Effective system should be carefully design, especially the spraying layout area of the foamwater. High side, low side, and tertiary bushing including diverter switch of the OLTC should be put into a design consideration as these are high possibility flammable spots of the oil-filled transformer. 6

7 5. Reference Associated Press. (2016). Substation fire sends smoke over west side of Phoenix area. Retrieved from 7

RD:30 Specification No. TI/SPC/PSI/AUTOTR/0090 For 50U5/150 MVA, 220/132 kv Auto Transformer

RD:30 Specification No. TI/SPC/PSI/AUTOTR/0090 For 50U5/150 MVA, 220/132 kv Auto Transformer RD:30 Specification No. TI/SPC/PSI/AUTOTR/0090 For 50U5/150 MVA, 220/132 kv Auto Transformer Annexure-4 TECHNICAL SPECIFICATIONS FOR NITROGEN INJECTION FIRE PREVENTION AND EXTINGUISHING SYSTEM FOR OIL

More information

High-expansion foam plant UNI EN 13565

High-expansion foam plant UNI EN 13565 High-expansion foam plant UNI EN 13565 Protection of an automated storage tank for flammable liquids by means of a foam suppression system AUTHORS: Gianluca Galeotti Fire Safety Engineer - FSE PROGETTI

More information

Deluge System. Pneumatic Release. Deluge System. Pneumatic Release

Deluge System. Pneumatic Release. Deluge System. Pneumatic Release Deluge System Pneumatic Release Deluge System Pneumatic Release When the fixed temperature release () is activated by fire, pressure in the release system escapes from the open device, allowing the pneumatic

More information

MODULE 2. Water-Based Suppression System Basics

MODULE 2. Water-Based Suppression System Basics MODULE 2 Water-Based Suppression System Basics Based on the Ohio Building Code (OBC) National Fire Protection Association (NFPA) & Ohio Fire Code (OFC) 1 WATER-BASED SUPPRESSION SYSTEM BASICS-PART ONE

More information

AUTOMATIC FIRE EXTINGUISHING SYSTEM for TUNNEL PROTECTION with SPREAD REMOTE CONTROLLED MONITORS (TUDEM-LEGIO)

AUTOMATIC FIRE EXTINGUISHING SYSTEM for TUNNEL PROTECTION with SPREAD REMOTE CONTROLLED MONITORS (TUDEM-LEGIO) AUTOMATIC FIRE EXTINGUISHING SYSTEM for TUNNEL PROTECTION with SPREAD REMOTE CONTROLLED MONITORS (TUDEM-LEGIO) Generals Innovating fire extinguishing system for tunnel fires, for fully automatic intervention

More information

Part: I TECHNICAL SPECIFICATION

Part: I TECHNICAL SPECIFICATION Part: I TECHNICAL SPECIFICATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS FOR THE WORK OF DESIGN, SUPPLY, ERECTION AND COMMISSIONING INCLUDING CIVIL WORK OF NITROGEN INJECTION

More information

Contents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7

Contents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7 Practical Power System Protection for Engineers and Technicians Contents Preface ix Chapter 1 Need for protection 1 1.1 Need for protective apparatus 1 1.2 Basic requirements of protection 2 1.3 Basic

More information

AUTOMATIC FIRE SUPPRESSION SYSTEMS

AUTOMATIC FIRE SUPPRESSION SYSTEMS AUTOMATIC FIRE SUPPRESSION SYSTEMS Effective automatic fire suppression systems are essential for the fire protection of mechanical equipment and special technologies. CONTENTS RSBP FIRE PROTECTION OF

More information

Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist

Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Water Mist for Transformer Fire Protection

More information

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION Generals Caccialanza & C. developed in the last years some technologically very innovative products, aimed to provide a very

More information

SECURITY BLANKET Foam Fire Protection Products

SECURITY BLANKET Foam Fire Protection Products SECURITY BLANKET Foam Fire Protection Products REAL DANGERS DEMAND REAL SOLUTIONS If your business manufactures, stores, or transports flammable liquids, the thought of a devastating fire always burns

More information

Nitrogen Injection Fire Prevention System for Oil Filled Transformers

Nitrogen Injection Fire Prevention System for Oil Filled Transformers Nitrogen Injection Fire Prevention System for Oil Filled Transformers Sarvesh Vitthal Ghadge UG Student, Dept. of Electrical Engineering, AISSMS s Institute of Information Technology, Pune, India.. Mr.

More information

The metering orifice is sized according to the type and percentage of concentrate used and is also secured with a stainless steel retaining ring)

The metering orifice is sized according to the type and percentage of concentrate used and is also secured with a stainless steel retaining ring) Legend: 1 Deluge Valve (DV-5) 2 Isolation Valve 3 Diaphragm Supply Valve 4 Manual Control Station 5 Automatic Shut-off Valve 6 Automatic Drain Valve 7 Pressure Switch 8 Water Motor Gong 9 Releasing Panel

More information

Deluge & Preac tion Systems

Deluge & Preac tion Systems Deluge & Preaction Systems Deluge Systems are normally used in special hazard installations where water must be applied to an entire area for protection. They use open sprinklers or spray nozzles attached

More information

Deluge Valves. Model 68 DE\ EL. Electrically Actuated Remote-Reset Deluge Valve. Dorot Fire Protection Division. Certification & compliance by design

Deluge Valves. Model 68 DE\ EL. Electrically Actuated Remote-Reset Deluge Valve. Dorot Fire Protection Division. Certification & compliance by design Fire Protection Div. Dorot Fire Protection Division Deluge Valves Model 68 DE\ EL Electrically Actuated Remote-Reset Deluge Valve Certification & compliance by design 1 ANSI FCI 70-2 Class VI seat leakage

More information

Enclosure 4- RISK ASSESSMENT

Enclosure 4- RISK ASSESSMENT Enclosure 4- RISK ASSESSMENT RISK ASSESSMENT Risk is a potential that a chosen action or activity will lead to a loss of human or property. Risk assessment is a step for Risk Management. Risk assessment

More information

Fire Suppression. Water-Mist : A Revolutionary Green Technology in. - by Nimit Sheth TALL, SMART, SAFE BUILDINGS FOR SMART CITIES.

Fire Suppression. Water-Mist : A Revolutionary Green Technology in. - by Nimit Sheth TALL, SMART, SAFE BUILDINGS FOR SMART CITIES. Water-Mist : A Revolutionary Green Technology in Fire Suppression - by Nimit Sheth Introduction Water-Mist... A Revolutionary Green Technology in Fire Suppression is being researched for more than 50-years

More information

Foam Products ENGLISH

Foam Products ENGLISH Foam Products ENGLISH Tyco Fire & Building Products Foam Products Today s technological innovations bring chemical and material fire hazards. Our lines of sprinklers and alarm valves have an excellent

More information

Fire Safety. Version 1.0

Fire Safety. Version 1.0 This document is intended to provide basic safety guidelines for the Physical Plant Department at Community College of Allegheny County. The information provided in this guide may vary by site. Version

More information

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems STEVEN WOLIN, VICE PRESIDENT, PRODUCT TECHNOLOGY & COMPLIANCE ANTONIO LUIS, TECHNICAL SERVICES MANAGER RELIABLE AUTOMATIC SPRINKLER

More information

Water mist fire suppression systems. Minifog ProCon Low-pressure water mist system

Water mist fire suppression systems. Minifog ProCon Low-pressure water mist system Water mist fire suppression systems Minifog ProCon Minifog ProCon Low-pressure water mist system IRE PROTECTION Efficient even for non-enclosed equipment Minifog ProCon systems by Minimax use innovative

More information

NEBOSH International Technical Certificate in Oil and Gas Operational Safety

NEBOSH International Technical Certificate in Oil and Gas Operational Safety IOG1 - Element 4 - Fire protection and emergency response July 2012 NEBOSH International Technical Certificate in Oil and Gas Operational Safety Licence details RMS Publishing Victoria House, Lower High

More information

Improvement of HEMP Resilience of Automatic Fire Suppression System

Improvement of HEMP Resilience of Automatic Fire Suppression System Improvement of HEMP Resilience of Automatic Fire Suppression System Vladimir Gurevich Central Electric Laboratory, Israel Electric Corp., POB 10, Haifa 31000, Israel Abstract - Automatic fire suppression

More information

RE: BASIC FIRE SAFETY PROCEDURES AND OPERATION OF FIRE EQUIPMENT

RE: BASIC FIRE SAFETY PROCEDURES AND OPERATION OF FIRE EQUIPMENT March 15, 2016 Security Staff Training Memo RE: BASIC FIRE SAFETY PROCEDURES AND OPERATION OF FIRE EQUIPMENT Dear Staff Officers: As part of your daily rounds, security officers must look out for any unsafe

More information

Minifog PressProtect Fire protection solutions for industrial presses BRANCH SOLUTION

Minifog PressProtect Fire protection solutions for industrial presses BRANCH SOLUTION Minifog PressProtect ire protection solutions for industrial presses BRANCH SOLUTION RISKS detect During the production of OSB, PB, MD and HD boards with continuous or multi-opening presses, combustible

More information

A.U.P.C.I ASOCIACIÓN URUGUAYA DE PROTECCION CONTRA INCENDIO AUPCI

A.U.P.C.I ASOCIACIÓN URUGUAYA DE PROTECCION CONTRA INCENDIO AUPCI A.U.P.C.I ASOCIACIÓN URUGUAYA DE PROTECCION CONTRA INCENDIO Foam Overview Applications Flammable Liquid Storage Tanks Diked Storage Tanks Loading Racks/Transfer Stations Closed Head Sprinkler Systems Deluge

More information

Power Generation. ASD 535 Application Report

Power Generation. ASD 535 Application Report ASD 535 Application Report Content Application Drivers Early Detection Serviceability Stratification Dilution Obstruction Power Generation Risks, Cause & Damage Challenges Application Scenarios Benefits

More information

Ceasefire Watermist Hydrant Systems

Ceasefire Watermist Hydrant Systems No fire is too big to beat. Ceasefire Watermist Hydrant Systems Never underestimate a fire. With enough oxygen and other fuels, even the smallest flame can turn into a full-scale blaze, destroying everything

More information

The Next Generation of Foam Fire Suppression. Automatic CAF Fire hose reel system FEATURES

The Next Generation of Foam Fire Suppression. Automatic CAF Fire hose reel system FEATURES Fire hose reel system The first automatic CAF, fire hose reel system FEATURES The Automatic CAF Fire Hose Systems are ideal for firefighting needs in locations that require foam as a fire fighting agent.

More information

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS This standard was reviewed and approved by key managers on September 6, 2011. Officer approval of this revision is not required. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Utility with

More information

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett Fire Protection System and Life Safety Evaluation of Building X Presented by Anthony W. Sublett Culminating Project Master of Science in Fire Protection Engineering California Polytechnic State University

More information

US Navy Leading the Way in Switchboard Protection

US Navy Leading the Way in Switchboard Protection US Navy Leading the Way in Switchboard Protection Rick Kurek Naval Sea Systems Command (NAVSEA) 2341 Jefferson Davis Highway Arlington, VA 22202 Ph: 202-781-1274 rick.kurek@navy.mil Abstract According

More information

New fire control system design for fire fighting and rescue equipment Jianguo LUO1, a, Zehao BU2, b

New fire control system design for fire fighting and rescue equipment Jianguo LUO1, a, Zehao BU2, b 6th International Conference on Information Engineering for Mechanics and Materials (ICIMM 2016) New fire control system design for fire fighting and rescue equipment Jianguo LUO1, a, Zehao BU2, b 1 Department

More information

Chapter 7 Fire Protection

Chapter 7 Fire Protection Chapter 7 Fire Protection 7.1 Risk and Fire Protection Planning 140 7.2 Fire Detection System 142 7.3 Fire Alarm Center and Systems Engineering 143 7.4 Alarm and Evacuation 144 7.5 Fire Extinguishing Systems

More information

Fire protection for emergency power supply

Fire protection for emergency power supply Fire protection for emergency power supply Protection of IT infrastructure, data and business continuity For data centers emergency power supply (e.g. generators or battery/ups rooms) is mission critical

More information

The Development of Automatic Fire Alarm Standards and Related Products in China

The Development of Automatic Fire Alarm Standards and Related Products in China The Development of Automatic Fire Alarm Standards and Related Products in China Hongjun Ding Shenyang Fire Research Institute, Shenyang, China Abstract This paper aims to introduce the development of automatic

More information

Major Fault Caused by Stator Winding Circuit Ring Failure

Major Fault Caused by Stator Winding Circuit Ring Failure Case study Major Fault Caused by Stator Winding Circuit Ring Failure Joël Pedneault-Desroches, P. Eng. Presentation Outline Introduction Inspection report Chronology of events Repair Conclusion 2 Introduction

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

...extinguish it with a water spray.

...extinguish it with a water spray. WATER SPRAY EXTINGUISHING SYSTEMS...extinguish it with a water spray. Water spray systems Safe for certain. RODUCT EXTINGUISHING WITH WATER SPRAY. Every year, fires cause huge damage and cost the economy

More information

FIRE PLAN. In order to assure the safety of patients, visitors and staff, a standard response to fire or the potential of fire is required.

FIRE PLAN. In order to assure the safety of patients, visitors and staff, a standard response to fire or the potential of fire is required. FIRE PLAN PURPOSE In order to assure the safety of patients, visitors and staff, a standard response to fire or the potential of fire is required. This fire plan sets out the standard response for all

More information

Intelligent Signature Series Analog Detection

Intelligent Signature Series Analog Detection Intelligent Signature Series Analog Detection With Signature Series intelligence, you re covered by the most advanced detection technology from the world leader in life safety and security innovation.

More information

Design of the Fiber-optic Fence Warning System with Distributed Video Real-Time Display Function Qiang-yi YI and Zheng-hong YU *

Design of the Fiber-optic Fence Warning System with Distributed Video Real-Time Display Function Qiang-yi YI and Zheng-hong YU * 2016 International Conference on Artificial Intelligence: Techniques and Applications (AITA 2016) ISBN: 978-1-60595-389-2 Design of the Fiber-optic Fence Warning System with Distributed Video Real-Time

More information

Vancouver Airport Fuel Delivery Project. Fire Prevention, Preparedness and Emergency Response

Vancouver Airport Fuel Delivery Project. Fire Prevention, Preparedness and Emergency Response Vancouver Airport Fuel Delivery Project Fire Prevention, Preparedness and Emergency Response 1 FIRE PREVENTION, PREPAREDNESS AND EMERGENCY RESPONSE 1.1 Introduction This document is associated with fire-related

More information

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The

More information

Branch Solution Wood based panel plants. Fire protection solutions for wood based panel plants

Branch Solution Wood based panel plants. Fire protection solutions for wood based panel plants Branch Solution Wood based panel plants Fire protection solutions for wood based panel plants afety throughout the production process R The versatility of wood as a raw material and the fact that it is

More information

FDF Foam Pump Controllers Features

FDF Foam Pump Controllers Features FDF100 Diesel Engine Foam Pump Controllers 1-1 Product Description The FDF Series of Foam Pump Controllers are designed for use with foam concentrate injection, foam transfer and water mist systems for

More information

NEC Requirement Guidelines 2002 Code Options for the Installation of Listed Less-Flammable Liquid-Filled Transformers

NEC Requirement Guidelines 2002 Code Options for the Installation of Listed Less-Flammable Liquid-Filled Transformers NEC Requirement Guidelines 2002 Code Options for the Installation of Listed Less-Flammable Liquid-Filled Transformers BULLETIN 92046 APPLICATION INFORMATION NOVEMBER 2002 SUPERSEDES August 2002 CONTENTS

More information

Aerosol flame projector with spark effect Safety instructions and operating manual

Aerosol flame projector with spark effect Safety instructions and operating manual Aerosol flame projector with spark effect Safety instructions and operating manual Flame projector Pyromaster Safety instructions Caution The directions in this manual must be followed strictly. The safety

More information

Intelligent. Signature Series Multisensor Detection. An EDWARDS brand.

Intelligent. Signature Series Multisensor Detection. An EDWARDS brand. Intelligent Signature Series Multisensor Detection See what s possible now. An EDWARDS brand. Photoelectric and ionization detectors see smoke, but not all fires produce it. Heat detectors spot temperature

More information

WATER MIST CONVENTION AND EXHIBITION

WATER MIST CONVENTION AND EXHIBITION INTERNATIONAL WATER MIST ASSOCIATION IWMA SEMINARS S ON WATER MIST TECHNOLOGY DUBAI INTERNATIONAL CONVENTION AND EXHIBITION CENTRE Water mist fire protection: The most innovative fire fighting technology

More information

Implementation of Building Management System using Renewable Energy Source (Solar), PLC and SCADA

Implementation of Building Management System using Renewable Energy Source (Solar), PLC and SCADA Implementation of Building Management System using Renewable Energy Source (Solar), PLC and SCADA Omkar Naik 1, Shreya Pomaje 2, Prof. S S Tamhane 3 1,2BE & Pune, 3Dept. of Electrical Engineering, NBNSSOE,

More information

INDUSTRY FIREFIGHTING NETWORK SYSTEMS AND WET NETWORKS. Setting your Dreams and Ours in Motion. YEARS.

INDUSTRY FIREFIGHTING NETWORK SYSTEMS AND WET NETWORKS. Setting your Dreams and Ours in Motion. YEARS. S.A. INGENIERÍA E INNOVACIÓN PARA LA INDUSTRIA Y MINERÍA. Metaproject in its 20 years history totals more than 1000 successful projects to its credit, with an average of 50 projects per year, about 80,000

More information

Microcontroller based design for Tele-sensing and extinguishing fire

Microcontroller based design for Tele-sensing and extinguishing fire Microcontroller based design for Tele-sensing and extinguishing fire Hany abdelhady Almedhegi 1, Ameen babekr abdelnaby 2, Abdelrasoul Jabar Alzubaidi 3 1 Sudan Academy of Sciences (SAS); Council of Engineering

More information

PYROSELF Innovative Snow Sensor and Controller for 2 x 24A loads outputs. Installation and Operating manual

PYROSELF Innovative Snow Sensor and Controller for 2 x 24A loads outputs. Installation and Operating manual Innovative Snow Sensor and Controller for 2 x 24A loads outputs Installation and Operating manual Index Introduction.... 3 Schematic system layout......... 4 Safety warnings......... 5 - The outdoor snow

More information

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles Peter Stahl Wagner Schweiz AG, Wallisellen, Switzerland Abstract Fire detection system and firefighting solutions are getting a

More information

DET-TRONICS. SPECIFICATION DATA Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION FEATURES

DET-TRONICS. SPECIFICATION DATA Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION FEATURES DET-TRONICS SPECIFICATION DATA Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION Eagle Quantum Premier is a configurable, distributed, intelligent safety system providing flame

More information

Incident Summary #II (#8165) (FINAL)

Incident Summary #II (#8165) (FINAL) Incident Summary #II-727632-2018 (#8165) (FINAL) Incident Date June 26, 2018 Location White Rock SUPPORTING INFORMATION Regulated industry sector Impact Injury Damage Qty injuries 0 Injury description

More information

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered

More information

Foam Systems U.S. Quick Reference Guide

Foam Systems U.S. Quick Reference Guide Foam Systems U.S. Quick Reference Guide This guide is intended for general reference only. Prior to the design, layout, and/or installation of any sprinkler system, please refer to Viking s technical documentation

More information

How can you minimize consequential damages in case of a fire?

How can you minimize consequential damages in case of a fire? How can you minimize consequential damages in case of a fire? With intelligent extinguishing solutions from Siemens. Sinorix 227 fast, effective, and reliable. Answers for infrastructure. Reliability the

More information

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS This standard was reviewed and approved by key managers with final approval by an officer of Oncor Electric Delivery on. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Customer with the Company

More information

Fire prevention plans: environmental permits. The fire prevention measures in this guidance have been designed to meet these 3 objectives:

Fire prevention plans: environmental permits. The fire prevention measures in this guidance have been designed to meet these 3 objectives: Guidance Fire prevention plans: environmental permits Published 29 July 2016 Contents 1. Fire prevention objectives 2. Who this guidance applies to 3. Who this guidance doesn t apply to 4. Types of combustible

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 6 Utilities Electrical Emergencies Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 6 Utilities Electrical Emergencies Revised Truck Module Page 1 of 6 ELECTRICAL EMERGENCIES Classification of Voltage For firefighting purposes, voltage can be considered in one of two classes, either high or low. As a general rule, the larger the

More information

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D40 FIRE PROTECTION 02/18

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D40 FIRE PROTECTION 02/18 NAVFAC PTS-D40 (February 2018) -------------------------------- Preparing Activity: NAVFAC SUPERSEDING PTS-D40 (September 2016) PERFORMANCE TECHNICAL SPECIFICATION SECTION D40 FIRE PROTECTION 02/18 NOTE:

More information

OPEN SPRINKLER SYSTEM

OPEN SPRINKLER SYSTEM OPEN SPRINKLER SYSTEM Introduction Competence and innovation driven by consistent market development and customer requirements have shaped the successful development of the SHIELD Brand. The extensive

More information

Propane Flame Projector Safety instructions and operating manual

Propane Flame Projector Safety instructions and operating manual Bigflame Propane Flame Projector Safety instructions and operating manual 1 Flame projector Bigflame Safety instructions Caution The directions in this manual must be followed strictly. It is imperative

More information

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE Page 1 of 8 1. DESCRIPTION Viking Deluge Systems utilize a Viking Deluge Valve to control the water supply to system piping equipped with open sprinklers and/or spray nozzles. The system piping remains

More information

Emergency shutdown systems. Procedures for bypassing ESD s

Emergency shutdown systems. Procedures for bypassing ESD s HYDROCARBON PROCESS SAFETY 2 - ELEMENT 3 - UNIT IOG1 Emergency shutdown systems Emergency shutdown systems (ESD s) are intended to minimise the consequences of emergency situations, for example, the uncontrolled

More information

ST 40 Oil Burner. Installation & Maintenance Manual

ST 40 Oil Burner. Installation & Maintenance Manual ST 40 Oil Burner Installation & Maintenance Manual 178 093 13 Thank you for choosing a Nu-way burner. As you would expect from a Company who has a pedigree of more than 75 years in the heating industry,

More information

To: Honorable Public Utilities Board Submitted by: /s/ Douglas Draeger AGM Engineering and Operations

To: Honorable Public Utilities Board Submitted by: /s/ Douglas Draeger AGM Engineering and Operations AGENDA ITEM NO.: 5.D.1 MEETING DATE: 0/4/014 ADMINISTRATIVE REPORT NO.: 014-48 To: Honorable Public Utilities Board Submitted by: /s/ Douglas Draeger AGM Engineering and Operations From: Tito R. Nagrampa

More information

JET-X HIGH-EXPANSION FOAM GENERATORS Data/Specifications

JET-X HIGH-EXPANSION FOAM GENERATORS Data/Specifications JET-X HIGH-EXPANSION FOAM GENERATORS Data/Specifications FEATURES Reliable, Water Motor Powered No Electrical Power Requirements Foam apacities to 28,800 FM (816 m 3 /m) UL Listed Models FM Approved Models

More information

Page 1 of 12 Input No. 62-NFPA 409-2013 [ Section No. 3.3.9 ] 3.3.9 Hangar Building Cluster. A group of buildings with more than one area for the storage and servicing of aircraft and all attached or contiguous

More information

BERMAD Fire Protection

BERMAD Fire Protection Model: 400E-3M Bermad Electro-Pneumatically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with

More information

Reliance Fire Protection Systems

Reliance Fire Protection Systems +91-8048075998 Reliance Fire Protection Systems https://www.indiamart.com/reliance-fire-protection/ Reliance Fire has been named Licensed Agency for the purposes of Fire Protection & Life Safety Measures

More information

things simple. At any rate, it is an elementary system and there seems to be little possibility of trouble.

things simple. At any rate, it is an elementary system and there seems to be little possibility of trouble. Fail safe design Logic circuits, whether comprised of electromechanical relays or solid-state gates, can be built in many different ways to perform the same functions. There is usually no one "correct"

More information

PLYWOOD INDUSTRY JOB EVALUATION PROGRAM JOB DESCRIPTION. Points: 242 Grade: 18

PLYWOOD INDUSTRY JOB EVALUATION PROGRAM JOB DESCRIPTION. Points: 242 Grade: 18 PLYWOOD INDUSTRY JOB EVALUATION PROGRAM JOB DESCRIPTION Date Revised: 16-Feb-12 Points: 237 Grade: 17 Date Prepared: 30-Apr-14 Points: 242 Grade: 18 Person Interviewed or Comment: No. of Incumbents: 1.

More information

Fire Safety Checklist

Fire Safety Checklist FIRE SAFETY RISK ASSESSMENT, FIRE HAZARDS PREVENTION & PLANNING: ESSENTIAL MEASURES Fire Safety Checklist Potential causes for fire hazards Fires need three ingredients to start: a heating source, fuel

More information

BUS ENGINE COMPARTMENT FIRE PROTECTION SYSTEM FIREPRO TEST REPORT PEER REVIEW

BUS ENGINE COMPARTMENT FIRE PROTECTION SYSTEM FIREPRO TEST REPORT PEER REVIEW & e. INDUSTRIAL LOSS CONTROL & eng Analisi e Controllo dei Rischi Industriali HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE & ENGINEERING BUS ENGINE COMPARTMENT FIRE PROTECTION SYSTEM FIREPRO TEST REPORT

More information

FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK

FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK USEFUL TERMINOLOGY BASIC PROCESS CONTROL SYSTEM (BPCS) System which responds to input signals from the process, its associated equipment, other programmable

More information

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 1. Purpose This policy sets forth requirements for preventing and detecting fires, sounding an alarm, and suppressing fires. Fire protection

More information

24V PCU CORE FIRE PROTECTION INSTALLATION SUMMARY

24V PCU CORE FIRE PROTECTION INSTALLATION SUMMARY 24V PCU CORE FIRE PROTECTION INSTALLATION SUMMARY 06/13/2011 Rev. 6 Pollution Control Unit PCU CORE CONNECTIONS, 3/8" NPT CONNECTION, ONE PER MODULE LINE FROM PACKAGE MUST BE BRANCHED TO EACH MODULE..

More information

THE FIXED AEROSOL EXTINGUISHING SYSTEM - FIRE JACK

THE FIXED AEROSOL EXTINGUISHING SYSTEM - FIRE JACK THE FIXED AEROSOL EXTINGUISHING SYSTEM - FIRE JACK 1. Introduction A) General information According to the European Community standard 2037/2000, it is prohibited in Europe, to employ extinguishing equipment

More information

Water Mist Fire Suppression

Water Mist Fire Suppression Water Mist Fire Suppression How less water has a big impact. HELPING PROTECT YOUR BUSINESS AND VALUED ASSETS WITH WATER MIST FIRE PROTECTION SYSTEM INTRODUCTION Many buildings have specific areas that

More information

Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015

Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015 Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015 Fire Protection I. INTRODUCTION II. GENERAL GUIDELINES III.

More information

Following are the systems proposed as per NBC & Local Fire Authority:

Following are the systems proposed as per NBC & Local Fire Authority: 1. OBJECTIVES AND STRATEGIES OF THE FIRE PROTECTION DESIGN This report describes the design parameters, system requirements of fire protection system for mixed occupancy (Assembly + Business) building

More information

IFE Level 4 Certificate in Fire Science and Fire Safety

IFE Level 4 Certificate in Fire Science and Fire Safety Unit 2: Fire Safety Unit Reference Number: D/505/5932 Introduction This unit focuses on the application of fire safety measures in complex premises and environments. Complex premises and environments include

More information

NEW HV/LV TRANSFORMER SUBSTATION WITHIN A BUILDING INTENDED FOR OTHER NON ELECTRICAL USES WITH ADVANCED FUNCTIONALITIES

NEW HV/LV TRANSFORMER SUBSTATION WITHIN A BUILDING INTENDED FOR OTHER NON ELECTRICAL USES WITH ADVANCED FUNCTIONALITIES NEW HV/LV TRANSFORMER SUBSTATION WITHIN A BUILDING INTENDED FOR OTHER NON ELECTRICAL USES WITH ADVANCED FUNCTIONALITIES Javier CORMENZANA Ormazabal Spain jco@orrmazabal.com Sergio SEBASTIAN Ormazabal -

More information

TWINTEMP JR. HYDRONIC SYSTEM 2/2013

TWINTEMP JR. HYDRONIC SYSTEM 2/2013 TWINTEMP JR. HYDRONIC SYSTEM 2/2013 TwinTemp Description of Operation and Sequence of Operation Technical Description of Operation The TwinTemp systems provide quiet space heating utilizing liquid to air

More information

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions 4201 Lien Rd Madison, WI 53704 TS-140F Revised 09-10 Owner s Manual Therma-Stor III Heat Recovery System Installation, Operation & Service Instructions Read and Save These Instructions Table Of Contents

More information

SIGNALISATION AND VISUAL GUIDE INTERACTIVE SYSTEM for EVACUATION ROUTES in TUNNELS and CONFINED AREAS

SIGNALISATION AND VISUAL GUIDE INTERACTIVE SYSTEM for EVACUATION ROUTES in TUNNELS and CONFINED AREAS SIGNALISATION AND VISUAL GUIDE INTERACTIVE SYSTEM for EVACUATION ROUTES in TUNNELS and CONFINED AREAS 19-03-2010 rev.3 P_gal_5a_EN page 1 Description and technical data of the system Innovating system

More information

DELUGE SYSTEMS FALSE OPERATIONS

DELUGE SYSTEMS FALSE OPERATIONS DELUGE SYSTEMS FALSE OPERATIONS Deluge Water/Foam Systems: False operations result in significant water/foam damages and might also cause destruction by fire! Deluge Foam Systems: In case of Fire, the

More information

Standards Manager Web Standards List ULC-Underwriters Laboratories of Canada

Standards Manager Web Standards List ULC-Underwriters Laboratories of Canada Standards Manager Web Standards List ULC-Underwriters Laboratories of Canada Id Number Title Year Organization Page 1 ANSI.CAN.UL. NULL 2016 ULC 64 1201 2 CAN.ULC- NULL 2016 ULC 176 60839-11-1-2016 3 CAN.ULC-IEC

More information

NITOL INSURANCE COMPANY LIMITED

NITOL INSURANCE COMPANY LIMITED NITOL INSURANCE COMPANY LIMITED 1. Name and Address of the Insured : PROPOSAL FORM 2. Nature of Risk : 3. Location : 4. Period of Insurance : From: To: 5. Sum Insured : (Section-wise) (a) Section-I (Property

More information

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description FIREFLEX VACTEC description This FIREFLEX VACTEC integrated fire protection system consists of a vacuum system trim totally pre-assembled, prewired and factory tested. All electrical and mechanical components

More information

Fire Safety PPT-SM-FIRESFTY V.A.0.0

Fire Safety PPT-SM-FIRESFTY V.A.0.0 Fire Safety 1 Fire Theory Definition of fire Rapid, persistent chemical change that releases heat and light Accompanied by flame Produces rapid oxidation 2 Fire Tetrahedron A fire needs four main elements

More information

Watermist Systems. Versatile, Affordable Water Mist Fire Suppression. your TRUSTED partner in fire safety

Watermist Systems. Versatile, Affordable Water Mist Fire Suppression. your TRUSTED partner in fire safety Watermist Systems Versatile, Affordable Water Mist Fire Suppression your TRUSTED partner in fire safety A New Era in Water-Based Fire Protection Water is the safe, natural way to extinguish a fire. But,

More information

PRINCIPLES OF DESIGN SPRINKLER INSTALLATION FOR FIRE FIGHTING IN THE UNDERGROUND GARAGES AND SUPPLEMENTARY LEGAL ACTS

PRINCIPLES OF DESIGN SPRINKLER INSTALLATION FOR FIRE FIGHTING IN THE UNDERGROUND GARAGES AND SUPPLEMENTARY LEGAL ACTS PRINCIPLES OF DESIGN SPRINKLER INSTALLATION FOR FIRE FIGHTING IN THE UNDERGROUND GARAGES AND SUPPLEMENTARY LEGAL ACTS Dragomir Aćimović 1, Nebojša Panić 2, Damnjan Radosavljevic 3 1 VPTS, Uzice, SERBIA,

More information

OUTLINE FOR FIRE PREVENTION ACTIVITY

OUTLINE FOR FIRE PREVENTION ACTIVITY OUTLINE FOR FIRE PREVENTION ACTIVITY Background Buildings under construction present unique fire exposures that require special attention. Fires can result in major losses and long delays in the completion

More information

Carbon Dioxide Fire Suppression Systems

Carbon Dioxide Fire Suppression Systems Carbon Dioxide Fire Suppression Systems The original "clean agent," carbon dioxide suppresses fire without leaving behind water, foam or dry chemical to damage sensitive equipment. And because there is

More information

Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230

Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230 Technologies Gas extinguishing systems MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230 ire protection Efficient and compact MX 1230 fire extinguishing systems fight fires using Novec

More information