1 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction with the requirements of this Section, and all related Sections..2 The Work of this Section and related Work specified in other Sections shall comply with all requirements of Division 1..3 The Work of this Section and related Work specified in other Sections shall comply with all requirements of Division 16 section Electrical General provisions. 1.2 SUMMARY.1 This new fire alarm system shall be single stage addressable. System Includes:.1 Materials and installation for fire alarm systems..2 Control panel to carry out fire alarm and protection functions including receiving alarm signals, initiating [general] [two-stage] alarm, supervising system continuously, actuating zone annunciators, and initiating trouble signals..3 Trouble signal devices..4 Power supply facilities..5 Manual alarm stations..6 Automatic alarm initiating devices..7 Audio Visual signal devices..8 End-of-line devices..9 Annunciators..10 Ancillary devices.. 11 Passive Graphic..12 Connection to non addressable fire alarm system components and sprinkler system. 1.3 REFERENCE
2 Belleville, Ontario Page 2 of 10.1 Sections and Section CAN/ULC-S Installation of Fire Alarm Systems.3 ULC-S Audible Signal Appliances, Fire Alarm.4 CAN/ULC-S Control Units, Fire Alarm.5 ULC-S Manually Actuated Signalling Boxes, Fire Alarm.6 CAN/ULC-S529-M87 Smoke Detectors, Fire Alarm.7 ULC-S Heat Actuated Fire Detectors, Fire Alarm.8 CAN/ULC-S Inspection and Testing of Fire Alarm Systems.9 CAN/ULC-S Verification of Fire Alarm Systems.10 OBC-2006 Ontario Building Code 1.4 REQUIREMENTS OF REGULATORY AGENCIES.1 System:.1 To the approval of the Ontario Fire Marshall s Office..2 To the approval of local Fire Department Safety Officer. 1.5 SUBMITTALS.1 Submit shop drawings and product data in accordance with Div Include:.1 Layout of equipment..2 Zoning..3 Complete wiring diagram, including schematics of modules..4 Equipment..5 Out put and input devices..6 Passive Graphic. 1.6 CLOSEOUT SUBMITTALS
3 Belleville, Ontario Page 3 of 10.1 Provide operation and maintenance data for Fire Alarm System incorporation into manual..2 Include:.1 Operation and maintenance instructions for complete fire alarm system to permit effective operation and maintenance..2 Technical data - illustrated parts lists with parts catalogue numbers..3 Copy of approved shop drawings. 1.7 QUALITY CONTROL.1 Perform tests in accordance with CAN/ULC-S Fire alarm system:.1 Test each device and alarm circuit to ensure manual stations, thermal and smoke detectors transmit alarm to control panel and actuate general alarm ancillary devices..2 Check annunciator panels to ensure zones are shown correctly..3 Simulate grounds and breaks on alarm and signaling circuits to ensure proper operation of trouble signals..4 Manufacturer's verification is to be performed on the complete fire alarm system, including all existing devices and connections. This subcontractor is responsible to provide a complete and operational system acceptable to the engineer and local authorities..5 Include independent system verification to validate programming of addressable system. All costs are to be included in the contract..4 Training: After system is fully functional, manufacturer s representative to Provide 4 hours of on-site staff training. 1.8 WARRANTY.1 Provide one year free maintenance with two inspections by manufacturer during year. Inspection tests to conform to ULC-S536. Submit inspection report to Consultant. 2 PRODUCTS
4 Belleville, Ontario Page 4 of MATERIALS.1 Equipment and devices: ULC listed and labeled and supplied by single manufacturer throughout the project. Acceptable Products:.1 GE (Edwards)..2 Notifier.3 Simplex.4 Mircom.5 Siemens..4 Power supply: to CAN/ULC-S Audible signal devices: to ULC-S Control unit: to CAN/ULC-S Manual fire alarm stations: to ULC-S Thermal detectors: to ULC-S Smoke detectors: to CAN/ULC-S SYSTEM OPERATION.2 Single stage addressable operation. Operation of any alarm initiating device to:.1 Cause audible signal devices to sound throughout building..2 Transmit signal to station alarm system..3 Cause zone of alarm device to be indicated on control panel and remote annunciator panels on a LED display..4 Cause designated air conditioning and ventilating fans to shut down or to function so as to provide required control of smoke movement..5 Cause fire doors and smoke control doors if normally held open, to close automatically..6 Capability to program smoke detector status change confirmation on any or all zones in accordance with CAN/ULC-S527, Appendix C.
5 Belleville, Ontario Page 5 of 10.7 Cause identify of device in alarm to be indicated on control panel and remote communicator panels on a LCD..8 Combination Smoke and Fire Damper Control Module: This module shall provide control and status tracking of a Form "C" contact. The two-wire signaling line circuit shall supply power and communications to the module. Module shall be used for the control and operation of the smoke dampers as indicated on the drawings. Addressable control relays are Form C Dry contact type. Electrical contractor to provide a double pole double throw contactor for operation of the 120V AC Damper/s. 2.3 CONTROL PANEL ANNUNCIATOR.1 Class A alarm circuits and signal circuits..1 One stage operation..2 Zoned..3 Non-coded..4 Addressable.5 Supervised, modular design with plug-in modules:.6 Alarm receiver with trouble and alarm indications provision for remote supervised annunciation, for class.7 Spare zones will be compatible with smoke detectors and open circuit devices..8 Space for future modules. Control panel will have 32 zone total capacity..9 Latching type supervisory receiver circuits. Discrete indication for both off-normal and trouble..2 Components:.1 Two stage alarm pulse rate panels:.2 Two stage stroke control type for output to signal control panel continuously..3 Audible signal control panel with control circuits complete with terminals for wiring and plug-in modules for ac signals up to 2.0 A load with trouble indication with class B connections..3 Common control and power units:.1 Control panel containing following indications and controls:.1 "Power on" LED (green) to monitor primary source of power to system..2 "Power trouble" indication..3 "Ground trouble" indication..4 "Remote annunciator trouble" indication.
6 Belleville, Ontario Page 6 of 10.5 "System trouble" indication..6 "System trouble" buzzer and silence switch c/w trouble resound feature..7 System reset switch..8 "LED test" switch if applicable..9 "Alarm silence" switch to silence signals manually. If new alarm occurs after signals have been silenced, signals to resound..10 Remote Station Module..11 Master power supply panel to provide 24 V dc to system from 120 V ac, 60 Hz input..12 Auxiliary relays: plug-in type, dust cover, supervised against unauthorized removal by common trouble circuit and c/w individual bypass switch..13 Contacts: 2.0 A, 24V dc or 120V ac, for functions such as release of door holders or initiation of fan shut down..14 Contact terminal size: capable of accepting AWG wire. 2.4 REMOTE ANNUNCIATOR PANEL PASSIVE GRAPHIC..1 LED and LCD display. Audible trouble indication and silencing switch..2 Enclosure: Flush mounted EEMAC 1 enclosure, complete with lockable, concealed hinged door. Full viewing window, flush lock and 2 keys..3 Passive graphic is to have a stainless steel frame with glass cover to be located near the annunciator panel at main entrance to the Building. This graphic shall indicate all floors, zones and you are here 2.5 POWER SUPPLY.1 120V AC, 60 Hz input, 24Vdc output from rectifier to operate alarm and signal circuits, with standby power of gell cell batteries minimum expected life of 4 years, sized in accordance with OBC.
7 Belleville, Ontario Page 7 of ADDRESSABLE MODULES 1. Addressable modules to take the normally open or normally closed contact signal from a device and register an address and indicate a zone alarm or supervisory signal as required for devices such as non addressable heat detectors, sprinkler flow switches, sprinkler valve limit switches sprinkler pressure switches and related devices. The addressable module is also to supervise the wiring connection between itself and the contact. 2.7 MANUAL ALARM STATIONS.1 Manual alarm stations: Addressable 2-stage, pull lever, wall mounted semi-flush type, non-coded single pole normally open contact for single stage operation. Identification in English..2 Manual alarm stations will be weatherproof where exposed to the elements and exterior environments. 2.8 AUTOMATIC ALARM INITIATING DEVICES.1 Heat detectors, addressable, fixed temperature and rate of rise non-restorable, rated 92 C...2 Heat detectors, addressable, fixed temperature and rate of rise non-restorable, rated 57 C..3 Heat detectors, addressable, fixed temperature, non-restorable, rated 57 C..4 Heat detectors, addressable, fixed temperature, non-restorable, rated 92 C..5 Thermal fire detectors, addressable, combination fixed temperature and rate of rise, non-restorable fixed temperature element, self-restoring rate of rise, fixed temperature 57 C, rate of rise 8.3 C per minute..6 Non addressable heat detectors are to be used in the elevator shaft and they are to be connected to addressable modules.
8 Belleville, Ontario Page 8 of DUCT TYPE SMOKE DETECTOR.1 Duct type smoke detector: addressable, ionization type, air duct type, with sampling tubes and protective housing. Duct detectors tubes shall be of sufficient length to traverse duct..2 Twistlock Plug-in type with fixed base..3 Wire-in base assembly with integral red alarm LED, and terminals for remote relay alarm LED SMOKE DETECTOR.1 Photo Electric Type..2 Tamper Proof..3 Visual alarm indication..4 Field adjustable sensitivity..5 Twist Lock Wire in base assembly..6 Addressable 2.11 AUDIO/VISUAL SIGNAL DEVICES.1 Horns & Strobe Combination-90db at 10-0 to ULC requirements in semi recessed boxes END-OF-LINE DEVICES.1 End-of-line devices to control supervisory current in alarm circuits and signalling circuits, sized to ensure correct supervisory current for each circuit. Open, short or ground fault in any circuit will alter supervisory current in that circuit, producing audible and visible alarm at main control panel and remotely as indicated.
9 Belleville, Ontario Page 9 of LEGENDS AND DIAGRAMS.1 Fire alarm system riser diagram: in glazed frame on black lamacoid sheet with beveled edges, white lettering and designations, minimum size 600 x 600 mm. Install this diagram adjacent to the fire alarm control panel in the main electrical room..2 Legends shall be typewritten and complete. 3 EXECUTION 3.1 INSTALLATION.1 Install systems in accordance with CAN/ULC-S524 and DFC-410(M)..2 Install new main control panel in existing enclosure in the existing electrical room..3 Install remote annunciators in new main entrance vestibule ant at care centres..4 Install passive graphics beside remote annunciators and control panel..5 Provide telephone conduit 25mm (1") directly to telephone backboard for connection by monitoring company..6 Locate and install detectors and connect to alarm circuit wiring. Do not mount detectors within 1 m of air outlets..7 Maintain at least 600 mm radius clear space on ceiling, below and around detectors..8 Locate and install horns and visual signal devices and connect to signalling circuits..9 Connect signalling circuits to main control panel. Provide a minimum of 2 signalling circuits. Alternate devices to each circuit.
10 Belleville, Ontario Page 10 of Install end-of-line devices at end of signaling circuits..11 Standpipe system and sprinkler: wire pressure, flow and supervisory switches and connect to control panel. END OF SECTION
PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R
Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,
More informationFort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS
HVAC Upgrades Phase 2 Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Materials and installation for fire alarm systems upgrades..2 Audible signal devices..3 End-of-line devices..4 Sustainable
More informationPakenham Branch Library Section MacFarlane Street MULTIPLEX FIRE ALARM SYSTEM Project No Page 1 of 12
Project No. 16563.001 Page 1 of 12 1. General 1.1. WORK INCLUDED 1.1.1. Section 26 05 01 GENERAL INSTRUCTIONS FOR ELECTRICAL SECTIONS. 1.1.2. Section 26 05 04 SUBMITTALS/SHOP DRAWINGS. 1.1.3. Section 26
More information16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5
Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series
More informationFIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS
VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More informationSmoke Detector Activation of any smoke detector shall start the alarm verification mode.
Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,
More informationThe following information shall become and form part of the contract documents.
October 4, 206 To: Attention: Re: All Bidders All Bidders JCBE Gymnasium HVAC Upgrades BC#: 206433 Edmonds Project No.: BHM6090 All bidders, The following information shall become and form part of the
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationArchitect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition
PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.
More informationSECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS
PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101
More informationSECTION INTRUSION DETECTION
(NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION
More informationDIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM
DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,
More informationSECTION FIRE ALARM SYSTEMS
SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationOSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM
OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,
More informationHinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.
More informationFunctional Performance Test
Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency
More informationChanges to this Division since the last issuance are indicated with yellow highlighted text.
Table of Contents 28 10 00 ELECTRONIC ACCESS CONTROL AND INTRUSION DETECTION... 2 A. GENERAL... 2 B. DESIGN REQUIREMENTS... 2 C. CONSTRUCTION REQUIREMENTS... 3 28 20 00 ELECTRONIC SURVEILLANCE... 4 A.
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards
More informationA. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system.
SECTION 283111 - PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationgood things in small packages
FireShield Control Panels good things in small packages life safety for small buildings and shops A perfect arrangement FireShield offers the very best conventional fire alarm technology available, with
More informationCOUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III
SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationSECTION FIRE DETECTION AND ALARM
PART 1 - GENERAL 1.1 RELATED SECTIONS: Refer to Section 15300 for requirements regarding fire protection systems. 1.2 SCOPE OF SECTION: This section contains the requirements for equipment and installation
More information1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This
More informationSECTION FIRE ALARM
SECTION 16740 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationINTELLIGENT FIRE ALARM CONTROL PANEL
INTELLIGENT FIRE ALARM CONTROL PANEL FX-2000 SERIES Description Mircom s FX-2000 Series Intelligent Analog Fire Alarm Control Panel is designed to provide maximum flexibility of analog system requirements
More information30.45 Electric Release PDRP-2001
The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or
More informationSECTION FIRE ALARM SYSTEMS
SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work
More informationStandard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.
A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable
More informationMS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels
R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:
More informationDESIGN & CONSTRUCTION GUIDELINES
Facilities Management 4202 E. Fowler Avenue, OPM 100 Phone: (813) 974-2625 Design & Construction Tampa, Florida 33620-7550 Website: usf.edu/fm-dc DESIGN & CONSTRUCTION GUIDELINES DIVISION 28 ELECTRONIC
More informationSECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM
SECTION 283111 DIGITAL, ADDRESSABLE FIRE ALARM PART 1 - GENERAL 1.1 GENERAL A. This Section includes the following: 1. Fire-alarm control panel. 2. Manual fire-alarm boxes. 3. Smoke detectors. 4. Heat
More informationBuilding Name: Our Lady of Sorrows Date: July 10, 2013
1 E1. FIRE ALARM SYSTEM ANNUAL TEST AND INSPECTION REPORT (Reference: 5.1.2) Building Name: Our Lady of Sorrows Date: July 10, 2013 Address 19 Mohns Avenue Petawawa, ON System Manufacturer: Siemens Model
More informationSECTION CLEAN AGENT FIRE SUPPRESSION SYSTEMS
SECTION 21 22 00 CLEAN AGENT FIRE SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTE: Delete between // --- // if not applicable to the project. Also delete any other item or paragraph
More informationB. Special Documentation Requirements. C. Materials and methods of Construction
DIVISION 13 SPECIAL CONSTRUCTION 13100 LIGHTNING PROTECTION 1. Lightning Protection: Each building shall be considered individually to determine the necessity for lightning protection. The building location,
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal
More informationCONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA
CONVENTIONAL FIRE ALARM CONTROL UNITS MR-2300 SERIES Fire Alarm Control Units Description Secutron s MR-2300 Series fire alarm control panels consist of six and twelve zone models which are equipped with
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.
More informationCAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS
2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED
More information2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014
2012 OBC Changes Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC New Sentence 3.2.4.2(6) Buildings interconnected by walkways permitted in Articles
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-28 31 74.00 20 (February 2010) ----------------------------------- Preparing Activity: NAVFAC Superseding UFGS-28 31 74.00 20 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationDIGITAL, ADDRESSABLE FIRE ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in
More informationCONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description
CONVENTIONAL FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped with
More informationMichigan State University Construction Standards FIRE DETECTION AND ALARM PAGE
PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationSECTION ADDRESSABLE FIRE ALARM SYSTEM
SECTION 16723 ADDRESSABLE FIRE ALARM SYSTEM 1 PART 1 GENERAL 1.1 DESCRIPTION A. This section outlines the requirements for the installation, programming and configuration of Addressable Fire Alarm System
More informationCAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning
CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region
More informationBrighton Area Fire Authority
615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following
More information51 Third Avenue Queen s Park New Westminster, BC. BID DUE: 3:00 PM (Local Time) on Wednesday, September 1, 2010
Fire Alarm Panel Upgrade, Queen s Park Arena NWIT-10-40 TENDER DOCUMENTS COVERING PAGE PROJECT TITLE: Fire Alarm Panel Upgrade PROJECT LOCATION: Queen s Park Arena 51 Third Avenue Queen s Park New Westminster,
More informationSECTION (13900) - FIRE SUPPRESSION SYSTEMS
PART 1 GENERAL 1.01 SUMMARY SECTION 21 10 00 (13900) - FIRE SUPPRESSION SYSTEMS A. Section Includes: 1. Pipe and Fittings. 2. Sprinklers. B. Related Documents: 1. Marriott s Fire Protection and Life Safety
More informationLake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 283111 A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationSPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM
SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125
More informationCITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1
CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device
More informationSECTION : FIRE ALARM & DETECTION SYSTEMS
SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction
More informationNew Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationSANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)
FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:
More informationNew Auburn University Veterinary Facility Gulf Shores, AL
SECTION 220405 - PLUMBING IDENTIFICATION PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following plumbing identification materials and their installation: 1. Pipe markers. 2. Stencils. 3. Valve
More informationSECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS
SECTION 280500 COMMON WORK RESULTS FOR SAFETY AND SECURITY PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 28 work shall, in addition to all division 1 specification sections, comply with all of
More informationSPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125 as the fire extinguishing agent
More informationMR-2602 Two Zone Fire Alarm Control Panel
MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...
More informationCAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS
RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 13852- PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationData Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906
s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones
More informationFA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel
LAMP TEST REMOTE CPU FAULT GROUND FAULT SIGNAL SILENECE FIRE DRILL BUZZER SILENCE INFO AC ON ALARM SUPERVISORY BATTERY SYSTEM RESET AUXILIARY DISCONNECT LAMP TEST MENU LAMP TEST REMOTE CPU FAULT GROUND
More informationCommercial and Light Industrial Fire Alarm Control Panel
FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel Features Easily expandable. All new plug-in board design Two supervised audible circuits Lamp and system trouble circuit test Ground
More information2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This
More informationFire alarm system specification for multiple tenant retail buildings
Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:
More informationMPC-6000 / MPC-7000 / RND-2
MPC-6000 / MPC-7000 / RND-2 Fire Alarm System Control Unit Installation, Operation and Maintenance Manual Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600
More informationCONTENTS AUTOMATIC TRANSFER SWITCHES
CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-28 31 13.00 40 (February 2017) ----------------------------------- Preparing Activity: NASA Superseding UFGS-28 31 13.00 40 (May 2013) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationFire Alarm System Fundamentals
Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom
More information1.3 REFERENCE STANDARDS
SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises
More informationAND ARCHITECT SPECIFICATIONS
SXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 4 Zones Expandable to 8 Zones Microprocessor Based Control Factory Programmed Field Configurable 2 Style Y Notification
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-28 31 63.00 20 (October 2007) ---------------------------------- Preparing Activity: NAVFAC Superseding UFGS-28 31 63.00 20 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationDIVISION 21 FIRE SUPPRESSION
Table of Contents 21 00 00 FIRE SUPPRESSION...2 A. REFERENCE ABBREVIATIONS... 2 B. GENERAL... 2 C. DESIGN REQUIREMENTS... 2 D. DOCUMENTATION... 2 21 08 00 FIRE SUPPRESSION COMMISSIONING...2 A. PIPE CLEANING...
More informationSECTION FIRE DETECTION AND ALARM
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 46 00 SPEC WRITER NOTES: 1. The A/E must obtain a copy of the VA ENGINEERING GUIDE FOR FIRE PROTECTION DESIGN which provides fire alarm system criteria that
More informationFireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel
PROTECTOWIRE FireSystems Features Easily expandable Two supervised audible circuits Lamp and system trouble circuit test Ground fault detection Initiating device circuit (IDC) alarm test Monitors up to
More informationSFC-200 SERIES LED FIRE ALARM PANEL
SFC-200 SERIES LED FIRE ALARM PANEL USER GUIDE LT-953SUM SFC-200 Series LED Version User Guide Contents Contents... i Introduction... 1 About this Manual... 1 Technical Support... 1 Main Display... 2
More informationEnvironmental Health & Safety
Environmental Health & Safety Oklahoma State University ADDRESSABLE FIRE ALARM SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu
More informationSPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL
SECTION 1 GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing FK-5-1-12 as the fire extinguishing agent and with a
More informationC. All control equipment must have transient protection devices to comply with UL864 requirements.
SECTION 28 31 11 - PART 1 - GENERAL 1.1 SCOPE & RELATED DOCUMENTS A. The work covered by this section of the specifications includes the furnishing of all labor, equipment, materials, and performance of
More informationSECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM
SECTION 13966 TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Total
More informationSECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM
SECTION 2 8 31 00 FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Request For Proposal apply to this Section.
More information16721 FIRE ALARM AND DETECTION SYSTEMS
16721 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose
More informationOKLAHOMA STATE UNIVERSITY
ENVIRONMENTAL HEALTH & SAFETY ADDRESSABLE FIRE ALARM SYSTEM STANDARD Revised 6/15 Revised: 6/15 Contact(s) Implementation Date Comments Gerald Petre, EHS June 2016 Review and Update Page 1 1.1 GENERAL
More informationDIVISION 28 ELECTRONIC SAFETY AND SECURITY
281300 - ACCESS CONTROL A. General DIVISION 28 ELECTRONIC SAFETY AND SECURITY At the beginning of the project, schedule a meeting with the Facilities Access/Maintenance Coordinator with questions and concerns.
More informationSPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi CONTROL PANEL
SECTION 1 GENERAL CONDITIONS I. SCOPE: SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing
More informationSECTION INTRUSION DETECTION SYSTEM
SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing
More informationConcerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3
Technical Service Note Detection Systems, Inc. Fairport, New York 14450-9199 Technical Service (800) 374-7454 Sales: (800) 289-0096 and (585) 223-4060 Fax: (585) 223-9180 Concerns: Affects: Dated: June
More informationFull Service Central Station Fire Alarm Listing Evaluation
Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm
More informationTECHNICAL DATA OBSOLETE
Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)
More informationHIGH-RISE RETROFIT ORDINANCES - NO and NO
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL
SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationVerdugo Woodlands Elementary School 2016 Interim Housing. Subject: Specifications and Drawings, dated December 10, 2015
Addendum No. 2 To: All Bidders Date: April 6, 2016 Project: Verdugo Woodlands Elementary School 2016 Interim Housing Subject: Specifications and Drawings, dated December 10, 2015 Page 1 of 5 THIS ADDENDUM
More informationCAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015
CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 Fire Commissioning in Canadian Codes and Standards BACKGROUND Why Commissioning?
More informationLifeAlarm Fire Alarm Control Panels
LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient
More information1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract.
PART 1 - GENERAL SECTION 28 31 11 STANDARD 1.1 FIRE ALARM SYSTEM REQUIREMENTS A. Contractor Requirements 1. The fire detection and alarm system (including the conduit) shall be a separate bid item and
More information