NFPA 45 NFPA 211 NFPA 1600
|
|
- Melissa Palmer
- 6 years ago
- Views:
Transcription
1 NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1
2 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA 211, and NFPA 1600 Understand some of the areas of each document that may be of interest to APPA
3 Applicable Codes NFPA 45, 2015 Edition NFPA 211, 2012 Edition NFPA 1600, 2012 Edition
4
5 NFPA 45 Process Dates Public Input deadline 01/05/17 First Draft posting 09/07/17 Public Comment deadline 11/16/17 Second Draft posting 08/02/18 NITMAM Deadline 08/30/18
6 Application NFPA 45 Applies to laboratories in which chemicals as defined are handled or stored Standard does not apply to: Lab units with less than 4 L (1 gal) of flammables Pilot plant laboratories Laboratories with a hazard rating of 1 or less for all categories Manufacturing plants Incidental testing facilities Hazards associated with explosive material and radioactive material
7 Scope of NFPA 45 Provide basic requirements for the protection of life and property from fire and explosions in laboratories Control hazards and protect personnel Establish a comprehensive laboratory fire prevention and protection program
8 Retroactivity and Equivalency Unless specified in this standard, provisions do not apply to existing facilities and structures AHJ and unacceptable degree of risk Equivalency
9 Chapter 3 - Definitions Chemicals a substance with one or more hazard ratings as defined by NFPA 704 (health, flammability, instability) Educational Laboratory Unit through 12 th grade Explosive Material explosive, blasting agent, emulsion explosive, water gel, detonator Instructional Laboratory Unit past the 12 th grade and before post college
10 Definitions Laboratory Building Principal use Laboratory Unit Enclosed area including incidental Laboratory Work Area Room or space for lab use Inside Liquid Storage Area Separated room or building for storage of liquids NFPA 30
11 Inside Storage Room NFPA 30
12 Definitions Safety Can Limited to 18.9 L (5 gal) Storage Cabinet For storage of flammable and combustible liquids and complies with NFPA 30 Section 9.5
13 Chapter 4 Laboratory Unit Hazard Classification Class A high fire hazard Class B moderate fire hazard Class C low fire hazard Class D minimal fire hazard Instructional Laboratory Units Class C or Class D
14 Lab Classification
15 Chapter 5 Laboratory Unit Design and Construction Maximum area of laboratory unit based on Fire hazard classification Construction See Table 5.1.1
16
17 Additional Requirements Labs in Educational Occupancies 1-hr separation Alternative Suppression System Allowed Floor Seal and Floor Curbing Prevent Liquid Leakage Fire Barrier Requirements per NFPA 101
18 Additional Requirements Occupancy Classification in NFPA 101 Class A, B, and C lab units Industrial Educational laboratories Educational Instructional Laboratories for past 12 th grade - Business
19 Means of Egress Second Means of Egress Required if: Explosion hazard Class A work area exceeds 46.5 sq m (500 sq ft) Class B, C, or D work area 93 sq m (1,000 sq ft) Hood adjacent to primary means of egress Compressed gas cylinder larger than lecture bottle size location Cryogenic container location Class A and B door swing direction of egress Emergency Lighting if second means of egress required
20 Chapter 6 Fire Protection Minimum Requirements Portable Fire Extinguishers Fire Alarm Systems Evacuation and Emergency Plans Automatic Sprinkler Protection All new laboratories Class A and B ordinary hazard group 2 Class C and D ordinary hazard group 1 Quick-response sprinklers NFPA 25 Maintenance Automatic Suppression to activate fire alarm
21 Chapter 6 Fire Protection Standpipe and Hose Systems 2 or more stories standpipes required NFPA 25 Maintenance Portable Fire Extinguishers NFPA 10 Class A extra hazard spacing Class B, C, and D ordinary/moderate hazard spacing
22 Chapter 6 Fire Protection Fire Alarm Systems NFPA 72 Class A and B manual fire alarm system Audible alarm Tie to local emergency responders or the public fire department Fire Prevention Procedures Maintenance Procedures Emergency Plans
23 Chapter 7 Laboratory Ventilating Systems and Hood Requirements Specific details beyond scope of presentation Applies to: Chemical fume hoods Special local exhaust devices Other systems for exhausting air from laboratory work areas
24 Chapter 8 Chemical Storage, Handling, and Waste Disposal Limit spill less than 5 gal Handling Trained personnel Class 1 liquids not transferred in exit access corridor Chemicals outside storage maintained at lowest level necessary for work Refer to SDS
25 Chapter 8 Chemical Storage, Handling, and Waste Disposal Storage Chemical inventories Max allowable quantities reduced based on stories above grade: Class B above Floor 3: 50% Class C and D Floors 4-6: 25% Class C and D above Floor 6: 50% Class I flammable, and Class II combustible liquids not in use must be stored in safety cans or in storage cabinets Storage in fume hood prohibited
26 Chapter 9 Flammable and Combustible Liquids Quantity Limitations Density and total amount outside of flammable liquid storage rooms shall not exceed quantities in Table 9.1.1(a) and (b) Maximum quantities based on lab classification
27 Chapter 9 Flammable and Combustible Liquids Container Capacity Limitations Container types and maximum capacities must comply with Table 9.1.2
28 Chapter 9 Flammable and Combustible Liquids Liquid Dispensing Dispensing Class 1 liquids in containers less than 5 gal Dispensing Class 1 liquids greater than 5 gal Class I transferring of containers greater than 1 gal (4 L) must be grounded
29 Chapter 10 Compressed and Liquefied Gases Cylinders not in use cannot be stored in the laboratory unit Quantity of compressed and liquefied gases to comply with Table of NFPA 55 Instruction laboratory work areas quantities limited to 10% of NFPA 55 quantities or 10 lecture bottle sized cylinders
30 Other Chapters Chapter 11 Laboratory Operations and Apparatus Chapter 12 Educational and Instructional Laboratory Operations Chapter 13 Hazard Identification Entrances to laboratories identified by signs indicating hazard of contents Labeling of containers
31 NFPA 211 Process Dates Public Input deadline 01/05/17 First Draft posting 09/07/17 Public Comment deadline 11/16/17 Second Draft posting 08/02/18 NITMAM Deadline 08/30/18
32 Application NFPA 211 Design, installation, inspection, and maintenance of chimneys, fireplaces, venting systems, and solid fuel-burning appliances
33 Chapter 4 General Requirements Sizing and Draft Termination (Height) Enclosure Venting Systems in Ducts Flue Lining Caps and Spark Arresters
34 Additional Chapters Chapter 5 Selection of Chimney and Vent Types Chapter 6 13 Specific requirements for each type Chapter 14 Maintenance Chapter 15 Inspection of Existing Chimneys
35 NFPA 1600 Process Dates Public Input deadline 01/05/17 First Draft posting 09/07/17 Public Comment deadline 11/16/17 Second Draft posting 08/02/18 NITMAM Deadline 08/30/18
36 Application NFPA 1600 Establishes a common set of criteria for all-hazards disaster/emergency management and business continuity/continuity of operations programs
37 Table of Contents Chapter 4 Program Management Chapter 5 Planning Chapter 6 Implementation Chapter 7 Training and Education Chapter 8 Exercises and Tests Chapter 9 Program Maintenance and Improvement
38 Annexes Annex A Multiple resource annexes
39 Future Questions. Join our LinkedIn Discussion Groups Life Safety Code People can join the group and submit their questions or People can and submit anonymously Smoke Management Proposed Changes to the IBC Ask the Expert FAQ.Koffel.com
40 Questions? William E. Koffel, P.E., FSFPE Koffel Associates, Inc Centre Park Drive, Suite 200 Columbia, MD Follow us on LinkedIn Expertly Engineering Safety From Fire 40
2008 NYC Fire Code. New Laboratory Standards. Operational & Maintenance Provisions effective July 2008
2008 NYC Fire Code New Laboratory Standards Operational & Maintenance Provisions effective July 2008 Design & Certificate of Fitness Requirements Effective July 1, 2009 History The new Fire Code legislation
More informationLaboratories and Hazardous Materials. Company Overview
Laboratories and Hazardous Materials Don E. Contois, P.E. Sam Sinapi Company Overview R.W. Sullivan Engineering (RWS) was established in 1945 and currently has 95 employees. RWS is a full service engineering
More informationFIRE/SMOKE BARRIER FUNDAMENTALS
FIRE/SMOKE BARRIER FUNDAMENTALS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire OBJECTIVE Identify the different
More information3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials
AMCA International Design Tips For Fire and Smoke Barriers William E. Koffel, P.E., FSFPE President, Koffel Associates, Inc. www.koffel.com Air System Engineering & Technology (ASET) Conference US San
More information2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content
Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015
More informationINSPECTOR I SKILLS ADMINISTRATION
INSPECTOR I SKILLS ADMINISTRATION 1- Prepare inspection reports so that the report is clear and concise and reflects the findings of the inspection in accordance with the applicable codes and standards..
More information2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes
2012 International Fire Code Significant Changes Andrew M. Schneider, P.E. Senior Fire Protection Engineer aschneider@koffel.com Koffel Associates, Inc. www.koffel.com Expertly Engineering Safety From
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International
More informationSetting A Standard on Fire Safety in Laboratories
ASCEL 2017 Setting A Standard on Fire Safety in Laboratories Presented by Hairulnizam Ishak, Senior Safety & Health Manager National University of Singapore Objectives 1.To share key requirements of the
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply
More informationThe Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99
The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99 Sharon S. Gilyeat, P.E. Lauren Schrumpf August 8, 2018 Expertly Engineering
More information2010 FIRE CODE OF NEW YORK STATE
2010 FIRE CODE OF NEW YORK STATE CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION SECTION 1401 GENERAL 1401.1 Scope. This chapter shall apply to structures in the course of construction, alteration,
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities
More information(h) Pesticide Application.
Fire Code Cannabis Amendment Section 13.20.066 is added to the Marysville Municipal Code to read in its entirety as follows: 13.20.066 Cannabis Growing, Processing, or Extraction Facilities (a) Application.
More informationPART 2. Basic Code Requirements - Semiconductor & Microelectronic Facilities using HPM s
PART 2 Basic Code Requirements - Semiconductor & Microelectronic Facilities using HPM s Occupancy Classifications Y A - Assembly Y B - Business Y E - Educational Y F - Factory/Industrial Y H - Hazardous
More informationBUILDING/FIRE CODE REFERENCES 2006 EDITION
BUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform Fire The IBC references the IFC in 97 Code sections. This document
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More informationCalifornia Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19
PART 3 Building and Equipment Design Features Chapters 5 through 19 Chapter 5 Fire Service Features No changes addressed Chapter 6 Building Services and Systems Chapter 7 Fire-Resistance-Rated Construction
More informationFirst Aspen Federal Regulation Set: K LSC 2000 Health Existing
First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST TENANT IMPROVEMENTS Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February
More informationOUTLINE FOR FIRE PREVENTION ACTIVITY
OUTLINE FOR FIRE PREVENTION ACTIVITY Background Buildings under construction present unique fire exposures that require special attention. Fires can result in major losses and long delays in the completion
More informationThe Cannabis Industry: Fire Department Requirements
The Cannabis Industry: Fire Department Requirements RVFD Standard 4.1 Rio Vista Fire Department 350 Main St. Rio Vista, CA. 94571 By: Jeff Armstrong, Fire Chief Updated December 2018 1 The purpose of this
More informationTRI-LAKES MONUMENT FIRE PROTECTION DISTRICT
TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter
More informationIMC Significant Changes Summary Tier I
2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just
More informationInternational Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures
International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project
More informationFire Safety Plan (FSP) Review Checklist 1
Fire Inspection & Prevention Initiative Fire Safety Plan (FSP) Review Checklist 1 (Component of a BC Fire Code (BCFC) compliance inspection) Date: COMPANY INFORMATION Company Name: Building Name: Address:
More informationNew Facilities. Minimum Requirements
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Item Reference Violation General Requirements NFPA 1124-7.1.1 Retail sales of consumer fireworks in both new and existing buildings, structures, and
More informationGUIDELINES FOR INSPECTING GROUND BASED SPARKLING DEVICE (GBSD) RETAIL SALES FACILITIES
OFFICE OF THE FIRE MARSHAL Worcester County GOVERNMENT CENTER - ONE WEST MARKET STREET - ROOM 1003 SNOW HILL, MARYLAND 21863-1194 TEL: 410-632-5666 FAX: 410-632-5664 GUIDELINES FOR INSPECTING GROUND BASED
More informationItem Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15
N/A N/A 2015 International Fire Code 2015 International Building Code Codes Jurisdictions for Fire and Building Codes Source of Information Building Fire Plumbing Mechanical Electrical Energy Code Accessibility
More informationChanges to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)
Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for
More informationFIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION
CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition
More informationFire Safety Plan (FSP) Review Checklist 1
Fire Safety Plan (FSP) Review Checklist 1 (Component of a BC Fire Code (BCFC) compliance inspection) COMPANY INFORMATION Company name: Building Name: Address: Street # and name City/Province Postal Code
More informationFire Hazard Identification Checklist 1
Fire Hazard Identification Checklist 1 (Component of a BC Fire Code (BCFC) compliance inspection) Date: BUILDING INFORMATION Company name: Building Name: Address: Street # and name City/Province Postal
More informationBuilding Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design
June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor
More informationFire Hazard Identification Checklist 1
Fire Hazard Identification Checklist 1 (Component of a BC Fire Code (BCFC) compliance inspection) Date: BUILDING INFORMATION Company name: Building Name: Address: Street # and name City/Province Postal
More informationICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005
ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 Kenneth Kretchman, CIH, CSP Mgr, Industrial Hygiene NC State University Ken_Kretchman@ncsu.edu International Building
More informationModule 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements
Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT RAISA FASHIONS LTD. ACCORD ID: 11741 PLOT# B63, BSCIC INDUSTRIAL ESTATE, KANCHPUR, SONORGAON, NARAYANGANJ OTHER FACTORIES: NONE February 27, 2015 Page 2 SUMMARY was surveyed
More informationSAF-BCF SECOND REVISIONS WITH STATEMENTS
Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More informationDEALING WITH FIRE SAFETY
DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance
More informationFraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.
Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.1) House Name Date Address Inspector(s) No. of Residents
More informationPA 256 of 2011 Michigan Fireworks Safety Act What We Need To Know
We will discuss PA 256 of 2011 Michigan Fireworks Safety Act What We Need To Know Fire Marshal Michael Evans, CFPS Novi Fire Department Documents to be familiar with Definitions of the types of fireworks
More informationMichigan Fireworks. Mike Evans Instructor # 2062 Program approval # A, 1S, 1T
Michigan Fireworks Mike Evans 734.942.3736 Instructor # 2062 Program approval # 17506 1 A, 1S, 1T PA 256 of 2011 Michigan Fireworks Safety Act What We Need To Know We will discuss Documents to be familiar
More informationKoffel Associates, Inc.
NFPA 25: STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEMS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com
More informationRichard B. Alpert, P.E. Senior FPE, Clark Nexsen
Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of
More information4/18/2017. *2012 edition of NFPA 99 has gone through a major overhaul. *This document is now a Code.
Carsten Lunde, ASSE 6050 Instructor April 20, 2017 Carsten s Yearly Analysis, Inc. Any opinions expressed verbally by the speaker before you and all text in this presentation should be considered the speakers
More informationPage 1 of 126 First Revision No. 113-NFPA 45-2013 [ Global Input ] Change all references to Material Safety Data Sheets (MSDS) to Safety Data Sheets (SDS) Submittal Date: Thu May 09 11:40:44 EDT 2013 Response
More informationOsceola County Department of Fire Rescue and Emergency Medical Services
St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner
More informationNatural Ventilation A Green Smoke Control Approach
Natural Ventilation A Green Smoke Control Approach Presented By: William Koffel, P.E., FSFPE Adam Graybeal, P.E. Authored by: Erik Anderson, P.E Koffel Associates Background New Engineering, Aviation,
More informationAgency for Health Care Administration
Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other
More informationCorrectly Classifying and Determining Fire Protection Requirements for High- Hazard Group H Occupancies in New York State (2010 codes)
Correctly Classifying and Determining Fire Protection Requirements for High- Hazard Group H Occupancies in New York State (2010 codes) Presented by: Chad R. Barnes, CFPS, SFPE, CPP Agenda Objectives Statistics
More informationWorking safely with flammable liquids
Flammable Liquids Fire hazards are associated with vapors from the flammable liquid. In order for a fire to occur, the following conditions must be met: Concentration of the vapor must be between the upper
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015
More informationPage 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation
More informationTire Storage. Michigan Fire Inspectors Society Fall Conference
Tire Storage Michigan Fire Inspectors Society Fall Conference September 15, 2016 This material, including the illustrations, represent the opinion of the author and instructor. This material is not designed,
More informationDOD FUELS LABORATORY STANDARDS UFC
DOD FUELS LABORATORY STANDARDS UFC 4-310-03 Prepared for: DLA Energy Worldwide Energy Conference April 12, 2017 Dustin Scheuffele, P.E. POL-MCX Omaha District US Army Corps of Engineers The views, opinions
More informationPlan Submittal Checklist
City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT PORTLAND TEXTILE LTD. ACCORD ID: 11873 PLOT NO. 14-15, SECTOR 6, CHITTAGONG EXPORT PROCESSING ZONE, CHITTAGONG OTHER FACTORIES: NONE November 3, 2015 Page 2 SUMMARY was surveyed
More informationPart I Extraction Process Equipment
745 West Colfax Avenue Denver, CO 80204 p: 720.913.3474 f: 720.913.3596 www.denvergov.org/fire MARIJUANA EXTRACTION GUIDELINE FOR COMMERCIAL / LICENSED FACILITIES The information contained within this
More informationSpecial Occupancy Requirements
Special Occupancy Requirements CHAPTER 2 0 AVIATION FACILITIES CHAPTER 2 1 DRY CLEANING CHAPTER 2 2 COMBUSTIBLE DUST-PRODUCING OPERATIONS Special Occupancies The objective of this module is to make the
More informationGUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS. High-Hazard
GUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS High-Hazard This document shall apply to all Group H, High-Hazard occupancies. GENERAL Scope Reporting of emergencies, coordination with emergency response
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationSummary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016
Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Ohio Administrative Code Rule Number OMC Section IMC origin Reason for proposed 4101:2-2-01 Air, Makeup 2015 Modified definition Air,
More informationOpen to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP
Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com
More informationNFPA 1124 (2006 Edition) Compliance List. Permanent Store
NFPA 1124 (2006 Edition) Compliance List Permanent Store (Multiple Items) Row Labels 7.1 Applicability 7.1.1 General Requirements: all consumer fireworks shall comply with this chapter unless otherwise
More informationGASEOUS HYDROGEN SYSTEMS
CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall
More informationObjectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts
Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Guy R. Colonna, PE Division Manager, NFPA Combustible Dust Symposium Detroit, MI September 20, 2011 1 Objectives
More informationNFPA 1124 (2006 Edition) Compliance List. Permanent Facility
NFPA 1124 (2006 Edition) Compliance List Permanent Facility (Multiple Items) Row Labels 7.1 Applicability 7.1.1 General Requirements: all consumer fireworks shall comply with this chapter unless otherwise
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT VINTAGE GARMENTS LTD EAST NARSHINGPUR, BURI PARA, ASHULIA, SAVAR Other Factories: ne June 1, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was
More informationConsumer Fireworks Retail Sales (CFRS) Facility Requirements.
Consumer Fireworks Retail Sales (CFRS) Facility Requirements. Site Plan. The site plan for tents shall show the location of the tent on the site and indicate the minimum separation distances required by
More informationThe following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101):
The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101): 1.1.1 Title. NFPA 101, Life Safety Code, shall be known as the Life Safety Code, is cited as such, and shall
More informationJanuary 1, 2014 Mandatory Effective Date
2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective
More informationFlammable Liquids!!!!!
Sample Written Program For Your Company For Flammable Liquids Provided By: P.O. Box 2136 Slidell, LA 70458 Phone: 985-781-1444 Fax: 985-718-4957 Email: info@se-safety.com Flammable Liquids Purpose Proper
More information1. Researchers are familiar with the location and contents of: The lab s Chemical Hygiene Plan YES NO
Safety Self-Inspection Checklist for Laboratories One Inspection form per Laboratory Room DATE: BUILDING: ROOM: INSPECTOR: Professor Inspector s Signature Professor s Signature: Answer each question by
More informationFlammable Liquid Storage
Published on UC Davis Safety Services (https://safetyservices.ucdavis.edu) Flammable Liquid Storage SafetyNet #: 523 Properties, Classification, Quantities, Cabinets, Containers and Refrigerators A. Summary
More informationTABLE OF CONTENTS. Part I Administrative... 1 CHAPTER 1 SCOPE AND ADMINISTRATION... 1
Part I Administrative............................. 1 CHAPTER 1 SCOPE AND ADMINISTRATION.... 1 PART 1 GENERAL PROVISIONS................ 1 101 Scope and General Requirements................ 1 102 Applicability................................
More informationNFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering
NFPA 101 and NFPA 99, 2012 Editions Code Update where art meets engineering Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC NFPA 101 and NFPA 99 where art meets
More informationCORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS
CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS FIRE EXTINGUISHER REQUIREMENTS 1. All commercial cooking operations require at least one 2A10BC rated (5 or 6 pound size) fire extinguisher.
More informationWhat are the Contents of an Effective Fire Safety Plan? Name: Date: Address of Project: Building Permit Number:
What are the Contents of an Effective Fire Safety Plan? A study of fire safety plans that have already been produced illustrates that one size does not fit all. Depending upon the complexity of a given
More informationLaboratory Information
Laboratory Information Lab Information Department Room number and function Principal investigator (PI) PI telephone number PI email address Lab Safety contact person Lab Safety contact telephone number
More informationBUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007
BUILDING CODE OF THE CITY OF NEW YORK New York City Department of Buildings 4 June 2007 Fatma Amer, PE, Deputy Commissioner, Technical Affairs James Colgate, RA, Executive Architect John Lee, RA Keith
More informationIFC Significant Changes from the 2009 to the 2015 Edition Tier 1
IFC Significant Changes from the 2009 to the 2015 Edition Tier 1 Several medical care definitions were created and revised in Chapter 2 of the 2012 IBC, as well as through the occupancy descriptions, and
More informationFire and Life Safety Review Form
Exits/Egress Fire and Life Safety Review Form 1. Doors shall swing in the direction of egress travel where serving and occupancy load of 50 or more. IFC 1010.1.2.1 2. Egress shall be readily openable from
More informationFIRE PREVENTION AND PROTECTION*
Chapter 30 (Replaced old ordinance September10, 2012) FIRE PREVENTION AND PROTECTION* * Cross References: Buildings and building regulations, ch. 14; environment, ch. 26; manufactured homes and trailers,
More informationEC EP 14 All other electrical K-920 equipment in patient care vicinity NFPA , Chapter 10
MSL Healthcare Partners, Inc. Wild Card EPs Paraphrase K-tag # EC.02.04.03 EP 14 All other electrical K-920 equipment in patient care vicinity NFPA 992012, Chapter 10 K-924 K-928 K-931 K-tag Description
More informationCommon Building Code Misinterpretations
Common Building Code Misinterpretations Presented by: Ron Melucci, P.E. Technical Manager, FP Division Engineering Planning and Management, Inc. rbm@epm inc.com www.epm inc.com 508 875 2121 Engineering
More informationAgency for Health Care Administration
Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common
More informationPROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE
PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated
More informationNew DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE
DEPARTMENT OF HEALTH & HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - AMBULATORY SURGICAL CENTERS Medicare 1. (A) PROVIDER NUMBER Identifying information as shown in
More informationLOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION
CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...
More informationBuilding & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!
Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?
More informationNarrative Reports As Regulated by 780 CMR, Section 903.0
EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for
More information2012 International Mechanical Code Significant Changes. About the Significant Changes
Significant Changes to the International Mechanical Code and the International Fuel Gas Code With Louisiana Amendments Copyright Materials This presentation is protected by US and International Copyright
More information