1 Guidance Note Watermist Fire Protection of Plant Rooms
2 SCOPE This document sets out the requirements for protection of plant rooms with watermist systems and should be read in conjunction with BS PLANT ROOM CLASSIFICATION Plant rooms are facilities providing building services such as water, electricity, heating and HVAC within or adjacent to buildings. The fire risk within plant rooms is complex and varied, and in order to ensure that a suitable suppression system is selected, a risk assessment should be undertaken at the design stage by a suitably qualified competent person. Generally, plant rooms can be classified as below. Low fire load plant rooms Low fire load facilities characterised by non-combustible ducting and/or limited electrical cabling. These facilities contain no storage. High fire load plant rooms High fire load facilities characterised by combustible ducting and/or significant electrical cabling. These facilities contain limited storage. Machinery space plant rooms High fire load facilities characterised by machinery such as combustion engines/boilers or other equipment, using fuel and/or lubrication fluids less volatile than or equal to heptane, and incidental use or storage of limited quantities of flammable liquids of not more than two 55 gallon (208 litre) drums. When selecting the plant room classification, the assessment must be made on the worst case risk. 2 of 5
3 APPLICABLE FIRE TEST PROTOCOLS Nozzle performance characteristics and spacing criteria should be determined by full scale fire testing to one of the below applicable fire test protocols. Plant Room Classification Low fire load plant rooms Applicable Fire Test Protocols BS FM 5560:2016, Appendix G High fire load plant rooms VdS 3188 Annex K1.6 Machinery space plant rooms BS Machinery spaces <80m 3 FM 5560:2016, Appendix A Machinery spaces <260m³ Machinery spaces >260m³ Pool and spray fires local application VdS 3188 Annex K2.2 FM 5560:2016, Appendix C FM 5560:2016, Appendix E BS FM 5560:2016, Appendix I 3 of 5
4 RESTRICTIONS Storage of combustible liquids, gases or other highly flammable substances in plant rooms is not permitted. With the exception of machinery space plant rooms where storage of no more than two 55 gallon (208 litre) drums of substances less volatile than, or equal to heptane, is permitted. ASSUMED MAXIMUM AREAS OF OPERATION Low and high fire load plant rooms shall be designed taking into account an assumed maximum area of operation (AMAO) of at least 144m². Machinery space plant rooms shall be designed as a total flood system, taking into account all nozzles within the risk. HYDRAULIC PIPEWORK CALCULATION System piping shall be fully hydraulically designed, taking into consideration the entire piping system, to deliver the minimum required water flow and pressure to the AMAO. OBSTRUCTIONS Obstructions in plant rooms usually take the form of either ducts or cable/pipe trays/racks. They can create physical barriers to the distribution of mist by removal of mist due to droplets coalescing on them, as well as by impairing the distribution of the watermist droplets. Nozzles produce a wide range of spray patterns and spray velocities. The degree to which obstructions can affect the performance of any particular nozzle will differ, according to the spray technology and type of obstruction. Where watermist protection is delivered through open nozzles, obstructions are largely overcome through the delivery of a uniform mist density through the plant room surrounding obstructions. In all instances and to ensure that there is an even watermist spray pattern, minimum head centres must be maintained. Where this cannot be achieved due to either vertical or horizontal obstructions, additional spray heads should be added. However, where automatic nozzles, successfully tested for this application are used, the testing should provide a determination of nozzle positions in relation to obstructions. Ducts normally pose no fire threat but can remove mist and/or block distribution. Nozzles should be positioned to compensate where mist loss from nozzle deliveries is likely to occur. Cable and or pipe trays/racks may pose partial obstruction of mist distribution. The cables may pose a fire hazard in themselves. Watermist solutions can take the form of: Placement of nozzles on either side or the trays/racks to discharge onto and under the trays/racks. Placement of nozzles above and below the trays/racks. 4 of 5
5 DISCLAIMER The information set out in this document is believed to be correct in the light of information currently available but it is not guaranteed and neither the Fire Industry Association nor its officers can accept any responsibility in respect of the contents or any events arising from use of the information contained within this document. Tudor House, Kingsway Business Park, Oldfield Road, Hampton, Middlesex TW12 2HD Tel: +44 (0) of 5
Additional Requirements for Watermist Systems Protecting High-rise Buildings
Guidance Note Additional Requirements for Watermist Systems Protecting High-rise Buildings Additional Requirements for Watermist Systems Protecting High-rise Buildings SCOPE... 3 DESIGN PARAMETERS... 3
More informationFact File 78. Portable Fire Extinguishers under the ADR. Note: This Fact File supersedes Fact File 060 which is withdrawn
Fact File 78 Portable Fire Extinguishers under the ADR Note: This Fact File supersedes Fact File 060 which is withdrawn The European Agreement concerning the International Carriage of Dangerous Goods by
More informationTudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0) Website:
Fact File No 0055 Tudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0)20 3166 5002 Website: www.fia.uk.com Watermist Systems 1. INTRODUCTION Over the past twenty
More informationGuidance Note. Visual Alarm Devices: Conflict between BS 5839 and EN 54-23
Guidance Note Visual Alarm Devices: Conflict between BS 5839 and EN 54-23 Visual Alarm Devices: Conflict between BS 5839 and EN 54-23 INTRODUCTION... 3 EXTENSION OF THE COEXISTENCE PERIOD FOR EN 54-23...
More informationFact File 46 Guidance to recyclers on treatment of domestic ionisation chamber smoke detectors (ICSD)
Fact File 46 Guidance to recyclers on treatment of domestic ionisation chamber smoke detectors (ICSD) Guidance to recyclers on treatment of domestic ionisation chamber smoke detectors (ICSD) BACKGROUND...
More informationFact File 69 Fire Detection & Alarms
Fact File 69 Fire Detection & Alarms Revision of BS 5446-3 Detection and alarm devices for dwellings Part 3: Specification for fire alarm and carbon monoxide alarm systems for deaf and hard of hearing
More informationGuidance Note. Guidance Document on Best Practice for Fire Detector Testing/Test Equipment
Guidance Note Guidance Document on Best Practice for Fire Detector Testing/Test Equipment Guidance Document on Best Practice for Fire Detector Testing/Test Equipment 1. SCOPE OF THIS DOCUMENT... 3 2. COMPETENCY
More informationEnvironmental Guidance Foam Fire Extinguishers
Fact File 25 Environmental Guidance Foam Fire Extinguishers Environmental Guidance Foam Fire Extinguishers INTRODUCTION... 3 ENVIRONMENTAL ISSUES... 4 EXTINGUISHERS ON SITE... 5 EXTINGUISHERS OFF SITE/AT
More informationThe Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE
The Protection of Machinery Spaces by means of the Local Application of Water Mist Dr. Tim R. Nichols CPhys FIFireE 2017 Johnson Controls. All rights reserved. Tyco Fire Products LP is a subsidiary of
More informationApplication of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE
Application of BS 8489 to the Protection of Generator Enclosures IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE Agenda Generator Enclosure Characteristics Generator Fire Characteristics Machinery
More informationThe requirements of BS Watermist Fire System standard and how to demonstrate compliance
The requirements of BS8489-1 Watermist Fire System standard and how to demonstrate compliance Bob Whiteley C. Eng.; F.I.Mech.E.; M.I.Fire E.; B.Tech(Hons) Chair: BSI Watermist Working Group Overview What
More informationGuidance Note FIA Application Guidance on BS :2015
Guidance Note FIA Application Guidance on BS 7273-4:2015 FIA Application Guidance on BS 7273-4:2015 1. INTRODUCTION... 3 2. OVERVIEW... 3 2.1. WHAT IS A DOOR RELEASE MECHANISM?...3 2.2. WHY INSTALL DOOR
More informationFarms and Similar Agricultural Facilities
Guidance Note Farms and Similar Agricultural Facilities This is information for FIA members and their customers, who have to determine the scale of provision of portable fire extinguishers on farms and
More informationFact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems:
Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems: Compatibility and connectivity assessment of system components Guide to BS EN 54-13:2017 Fire Detection and alarm systems: Compatibility
More informationGuidance on Video Smoke Detection Technology (VSD)
Guidance Note Guidance on Video Smoke Detection Technology (VSD) Guidance on Video Smoke Detection Technology (VSD) SCOPE... 3 INTRODUCTION... 4 WHAT IS VSD?... 5 STANDARDS... 7 GENERAL GUIDANCE ON THE
More informationGuidance Note. Fire Alarm Detector Applications and Documentation of the Selection
Guidance Note Fire Alarm Detector Applications and Documentation of the Selection Fire Alarm Detector Applications and Documentation of the Selection INTRODUCTION... 3 FLOW CHART FOR THE SELECTION OF...
More informationEnvironmental Guidance Fire Fighting Powder and Powder Fire Extinguishers
Fact File 26 Environmental Guidance Fire Fighting Powder and Powder Fire Extinguishers Environmental Guidance Fire Fighting Powder and Powder Fire Extinguishers INTRODUCTION... 3 TYPES OF FIRE EXTINGUISHING
More informationFact File 39 Environmental Guidance
Fact File 39 Environmental Guidance Foam Fire Extinguisher Disposal Foam Fire Extinguisher Disposal INTRODUCTION... 3 ENVIRONMENTAL ISSUES... 4 FOAM EXTINGUISHERS... 5 HANDLING OF EXTINGUISHERS OFF SITE/AT
More informationCO 2 Fire Extinguishing Systems
Guidelines for Fire Extinguishing Systems Planning and Installation Content 0 Foreword... 10 0.1 Application of the VdS guidelines... 10 1 General... 10 1.1 Scope... 10 1.2 Aims... 11 1.3 Description...
More informationMORE THAN JUST FIRE PROTECTION
MORE THAN JUST FIRE PROTECTION VID Fire-Kill is a world leading innovative developer and manufac turer of water based firefighting products, specializing in fixed water based systems utilizing environmental
More informationFIA Guidance on Manual Call Point - Protection - False Alarm Mitigation
Guidance Note FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation FIA Guidance on Manual Call Point - Protection False Alarm Mitigation 1. INTRODUCTION... 3 2. BS 5839-1 RECOMMENDATIONS...
More informationFact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems
Fact File 75 Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems INTRODUCTION... 3 BACKGROUND...
More informationFixed fire protection solutions
Risk Engineering Fixed fire protection solutions At a glance Fixed fire protection can reduce the severity of fire events and positively impact Risk Engineering Assessments. To provide an effective solution
More informationFact File 15 Ionisation Chamber Smoke Detectors and The Radioactive Material (Road Transport) Regulations 2002
Fact File 15 Ionisation Chamber Smoke Detectors and The Radioactive Material (Road Transport) Regulations 2002 Ionisation Chamber Smoke Detectors and The Radioactive Material (Road Transport) Regulations
More informationMORE THAN JUST FIRE PROTECTION
MORE THAN JUST VID Fire-Kill is a world leading innovative developer and manufac turer of waterbased firefighting products, specializing in fixed water-based systems utilizing environmental friendly firefighting
More informationHow to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?
Plumis White Paper April 2017 How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? As with the introduction of every new formal product category through
More informationLow Pressure INNOVATIVE FIRE PROTECTION SOLUTIONS in the. Woodworking Industry INNOVATIVE FIRE PROTECTION. VID Fire-Kill. Denmark.
INNOVATIVE Low Pressure INNOVATIVE SOLUTIONS in the Woodworking Industry INNOVATIVE Threats in the Wood Working Industry The abundance of fuel-loads and the volatile nature of particle-rich atmospheres
More informationPOSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS
FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The
More informationGuidance Document on Caravan and Camping Sites Fire Safety Equipment Requirements
Guidance Document on Caravan and Camping Sites Fire Safety Equipment Requirements FIA Guidance for the Fire Protection Industry This Guidance Note is intended as a general guidance and is not a substitute
More informationSTANDARDS FOR ACTIVE FIRE PROTECTION. Stewart Kidd Loss Prevention Consultancy Ltd
STANDARDS FOR ACTIVE FIRE PROTECTION Stewart Kidd Loss Prevention Consultancy Ltd This presentation will consider: The risks to both new and existing buildings which can be countered by active fire protection
More informationTudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0) Website: EQUALITY ACT 2010
Tudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0)20 3166 5002 Website: www.fia.uk.com EQUALITY ACT 2010 1. INTRODUCTION This Fact File aims to highlight some
More informationFM Approvals & Water Mist Systems. Paul Bardsley Engineer, FM Approvals
FM Approvals & Water Mist Systems Paul Bardsley Engineer, FM Approvals Presentation Outline Introduction to FM Global Introduction to FM Approvals FM 5560 - Water Mist Systems Who are FM Global? The largest
More informationSafer.Smarter.Tyco. Watermist fire protection Technology you can trust
Safer.Smarter.Tyco. Watermist fire protection Technology you can trust / 2 / / 3 / Trust in Tyco Tyco s AquaMist Systems Tyco Fire Protection Products helps to keep people, property and the environment
More informationAustralian Standard. Water mist fire protection systems System design, installation and commissioning AS
AS 4587 1999 Australian Standard Water mist fire protection systems System design, installation and commissioning This Australian Standard was prepared by Committee FP/12, Aqueous Fire Protection Systems.
More informationIMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS
INTERNATIONAL MARITIME ORGANIZATION E IMO ASSEMBLY 23rd session Agenda item 17 A 23/Res.951 25 February 2004 Original: ENGLISH Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED
More informationI wish I could protect my business with the most suitable Water Mist solution to fit my needs.
I wish I could protect my business with the most suitable Water Mist solution to fit my needs. Wish granted! Tyco AquaMist systems are a versatile and highly efficient fire-fighting resource, featuring
More informationBS 5839: Part THE CHANGES
BS 5839: Part 1 2013 THE CHANGES INTRODUCTION This document has been created to summarise the main changes that have been made to the BS 5839 Part 1 2013. This data is correct at the time of publication
More informationThe Science Behind Water Mist Protection of Typical Building Hazards
The Science Behind Water Mist Protection of Typical Building Hazards SUPDET 2014 Zachary Magnone, P.E. Zachary.Magnone@tycofp.com Presentation Goals What is water mist? How does it work? How is it tested
More informationFIRE PROTECTION, NATURALLY AQUASONIC Water-Atomizing Fire Suppression System
FIRE PROTECTION, NATURALLY AQUASONIC Water-Atomizing Fire Suppression System A LOOK INSIDE THE INNOVATION The ANSUL AQUASONIC TM Water-Atomizing Fire Suppression System is a revolution in Class B fire
More informationFEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS
FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS ARE BASED UPON LIVE FIRE TESTING OF PREP STATIONS
More informationWater Mist Fire Protection Systems for the Protection of Industrial Oil Cookers. 8th March 2016 Dr Tim Nichols CPhys MIFireE
Water Mist Fire Protection Systems for the Protection of Industrial Oil Cookers 8th March 2016 Dr Tim Nichols CPhys MIFireE Industrial Oil Cookers 2 What are Industrial Oil Cookers Large cooker of food
More informationGUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS
12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety
More informationHI-FOG for buildings. Technical introduction. Protecting people, property and business continuity. Jussi Tiainen
HI-FOG for buildings Technical introduction Jussi Tiainen Protecting people, property and business continuity Contents Introduction to HI-FOG...3 How HI-FOG fights fire...4 Principles of HI-FOG system
More informationFEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems
FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations are based upon Live Fire Testing of Prep Stations
More informationCertificate No: EWS534
Certificate No: EWS534 Plumis Automist Smartscan Hydra Description of Product This is an assessment of the Plumis Automist multiroom Smartscan Hydra targeted fire suppression system. The system utilises
More informationMethod for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches
2014-09-19 SP Method 4912 Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches 2014-09-19 page 2 (17) Copyright This test method
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International
More informationThis document is a preview generated by EVS
TECHNICAL SPECIFICATION SPÉCIFICATION TECHNIQUE TECHNISCHE SPEZIFIKATION CEN/TS 14972 May 2008 ICS 13.220.20 English Version Fixed firefighting systems - Watermist systems - Design and installation Installations
More informationProtection against Internal Hazards in the Design of Nuclear Power Plants
IAEA SAFETY STANDARDS for protecting people and the environment Step 8 December 2017 Protection against Internal Hazards in the Design of Nuclear Power Plants DS 494 DRAFT SAFETY GUIDE Revision and merge
More informationProtection against Internal Hazards in the Design of Nuclear Power Plants
IAEA SAFETY STANDARDS for protecting people and the environment Step 7a7b September November 2017 Protection against Internal Hazards in the Design of Nuclear Power Plants DS 494 DRAFT SAFETY GUIDE Revision
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply
More informationWater Mist v Sprinklers
Water Mist v Sprinklers 15 th November 2018 Gary Howe EngTech FIFireE MIFPO Senior Fire Protection Engineer Zurich Risk Engineering Photo source: Stuart Lloyd, Zurich Zurich Fire Protection BS8489 FIA
More informationWATER MIST CONVENTION AND EXHIBITION
INTERNATIONAL WATER MIST ASSOCIATION IWMA SEMINARS S ON WATER MIST TECHNOLOGY DUBAI INTERNATIONAL CONVENTION AND EXHIBITION CENTRE Water mist fire protection: The most innovative fire fighting technology
More informationEmergency shutdown systems. Procedures for bypassing ESD s
HYDROCARBON PROCESS SAFETY 2 - ELEMENT 3 - UNIT IOG1 Emergency shutdown systems Emergency shutdown systems (ESD s) are intended to minimise the consequences of emergency situations, for example, the uncontrolled
More informationProven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist
Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Water Mist for Transformer Fire Protection
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply
More informationWater Mist Fire Suppression
Water Mist Fire Suppression How less water has a big impact. HELPING PROTECT YOUR BUSINESS AND VALUED ASSETS WITH WATER MIST FIRE PROTECTION SYSTEM INTRODUCTION Many buildings have specific areas that
More informationFOREFRONT AT THE OF PROTECTION
AT THE FOREFRONT OF PROTECTION SIEX WF B combines the benefits of water as an extinguishing agent with the most innovative advances to achieve fire protection causing the least possible damage and exceeding
More informationZurich s experience case studies
Zurich s experience case studies April 24 th 2018 Stuart Lloyd EngTech TIFireE Principal Fire Protection Engineer Gary Howe EngTech FIFireE MIFPO Senior Fire Protection Engineer Zurich Risk Engineering
More informationWatermist Applications and Approvals
Watermist Applications and Approvals IWMA Seminar 19 th January 2014 Dubai, UAE By Alex Palle, VID Fire-Kill, Denmark For a technology to commercialize STANDARDS are needed. STANDARDS can be divided into
More informationNFPA 45 NFPA 211 NFPA 1600
NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA
More information26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 Telex: 23588 IMOLDN G IMO E Ref. T4/4.01 MSC/Circ.1007 26 June 2001 GUIDELINES FOR THE
More informationTECHNICAL NOTES. Literature Review on Hybrid Fire Suppression Systems. Peter Raia Michael J. Gollner University of Maryland
TECHNICAL NOTES Literature Review on Hybrid Fire Suppression Systems Peter Raia Michael J. Gollner University of Maryland Fire Protection Research Foundation May 2014 The Fire Protection Research Foundation
More informationWATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS
WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,
More informationWater Mist System. Principle of Water mist evolves from combination of 3 main effects:
Water Mist System - by T R A Krishnan 1. Introduction A water mist system is a fire suppression system that, when activated, will discharge a spray of water droplets from a nozzle (or array of nozzles).
More informationWater Spray Systems: NFPA 15
Water Spray Systems: NFPA 15 WILLIAM HICKS MSc, CFEI, CFPS, IAAI-CFI, MIFireE, EFO, CFOD, F-IAFI Associate Professor Eastern Kentucky University William.Hicks@eku.edu System Maintenance Objectives Identify
More informationMaking sense of risk Risk engineering. Metalworking operations
Making sense of risk Risk engineering Metalworking operations Metalworking operations Metalworking operations involve the fabrication of ferrous or nonferrous metal products, structural metal products,
More informationThe Route to Third Party Certification
www.fia.uk.com INTRODUCTION If you work in any part of the fire safety industry you will at least have heard of Third Party Certification (TPC) but you may not be too sure what it is. Even if you work
More informationAbrasion Resistance of Fluoropolymer and polyester Coatings
Abrasion Resistance of Fluoropolymer and polyester Coatings British Standards British Standard 476 refers to fire tests on building materials and structures. The parts of this standard that are of most
More informationMSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017
Procedure Number: E1-03 Revision Date: 02/16/2017 References: S. T. Brady, CDR, Chief, Engineering Division a. National Fire Protection Association (NFPA) 750, 1996 Edition, Standard on Water Mist Fire
More informationAnnex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005
Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate D-PL-11035-03-00 according to DIN EN ISO/IEC 17025:2005 Period of validity: 25.10.2017 to 24.10.2022 Holder of certificate: DMT
More informationFire protection for buildings
Fire protection for buildings HI-FOG high-pressure water mist Ghelamco Group Protecting people, property and business continuity A fire in a building can lead to serious consequences. Even a harmless fire
More informationICC CODE CORNER 2015 International Fire Code
SECTION 606 MECHANICAL REFRIGERATION [M] 606.1 Scope. Refrigeration systems shall be installed in Code. [M] 606.2 Refrigerants. The use and purity of new, recovered and reclaimed refrigerants shall be
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities
More informationMSC Guidelines for Automatic Sprinkler Systems
S. J. Kelly, CDR, Chief of Engineering Division References a. Title 46 CFR 56.20, 56.50 & 56.60 (Subchapter F) b. National Fire Protection Association (NFPA) 13, 1996 Edition, Installation of Sprinkler
More informationChapter 17, Initiating Devices
Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.
More information4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 IMO E Ref.: T4/4.01 MSC.1/Circ.1272 4 June 2008 GUIDELINES FOR THE APPROVAL OF FIXED WATER-BASED
More informationWater-mist systems in mass-production industries: A successful application to a tissue-converting plant
Water-mist systems in mass-production industries: A successful application to a tissue-converting plant Paolo E. Santangelo a, Paolo Tartarini a, Massimiliano Bettati b, Luca Tarozzi b, Silvano Pane c
More informationCode of Practice for Design, Installation, Commissioning & Maintenance of Duct Smoke Detector (DSD) Systems
Code of Practice for Design, Installation, Commissioning & Maintenance of Duct Smoke Detector (DSD) Systems Issue 1.0 Page 1 of 35 Fire Industry Association Code of Practice for Design, Installation, Commissioning
More informationVELMIST. System Mgły Wodnej Niskociśnieniowej
VELMIST System Mgły Wodnej Niskociśnieniowej VID Fire-Kill Innovative Solutions FM Approved Low Pressure Watermist nozzles for commercial and industrial applications. Complete range of Low Pressure Watermist
More informationReport on First Revision June 2014 NFPA 5000
5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-32798-9 SOUTH AFRICAN NATIONAL STANDARD Gas measuring equipment primarily for use in mines Part 5: Fire detectors WARNING This standard references other documents normatively. Published
More informationODS & SGG Alternatives for the Fire Protection Industry 2018
Fire Protection Industry (ODS & SGG) Board www.fpib.com.au Fact Sheet ODS & SGG Alternatives for the Fire Protection Industry 2018 The Australian Government is committed to reducing emissions of ozone
More informationSchedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK
2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 17065:2012 to provide product conformity certification Newport Business Park New Port Road Ellesmere Port CH65 4LZ United Kingdom Contact:
More informationTECHNICAL DATA 1. PRODUCT NAME 2. DISTRIBUTOR 3. INTRODUCTION 4. FIELD OF APPLICATION 5. TECHNICAL DATA. Page 1 of 6
Page 1 of 6 1. PRODUCT NAME Viking Model EM Low Pressure Mist Nozzle System VK824, 125 Spray Pattern, K Factor Metric = 12.0, US = 0.82, Viking P/N - 13633 VK825, 95 Spray Pattern, K Factor Metric = 7.0,
More informationDescription of the European standard EN 378: Refrigerating systems and heat pumps Safety and environmental requirements
: Refrigerating systems and heat pumps Safety and environmental requirements Prof. Dr. Risto Ciconkov, dipl. ing. Faculty of Mechanical Engineering, University Ss. Cyril & Methodius Skopje, R. Macedonia
More informationSimulation of Engine Room Fire and Water Mist. Einar Kolstad and Bjarne P. Husted Stord/Haugesund University college
Simulation of Engine Room Fire and Water Mist Einar Kolstad and Bjarne P. Husted Stord/Haugesund University college Fire on MS Nordlys 15th September 2011 a fire started in the engine room of the cruise
More informationMoving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System. Part 1: Concept Design
Moving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System Part 1: Concept Design 2 Amy L. Porter, P.E. (TX,VA, NM) AND Michael Wojcik, P.E. (AZ, CO, MA,
More informationTN-25 Tunnel Fire Protection System. Safer. Smarter. Tyco.
TN-25 Tunnel Fire Protection System Safer. Smarter. Tyco. Expert Fire Protection for Tunnels Tyco provides a complete fire protection solution to protect the infrastructure of tunnels. Whether it is rail,
More informationFinalized Draft AUTOMOTIVE INDUSTRY STANDARD ARAI
Finalized Draft AUTOMOTIVE INDUSTRY STANDARD Fire Detection and Alarm System (FDAS) & Fire Detection and Suppression Systems (FDSS) for Buses - Requirements ARAI Date of hosting on website: 12 th Last
More informationAugust Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification
Electrical Engineering Guide for Determining Electrical Area Classification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice
More informationPalm Beach State College Florida s First Public Community College FIRE PREVENTION PLAN
Palm Beach State College Florida s First Public Community College FIRE PREVENTION PLAN Emergency Contact Information Site Organization/Personnel Telephone Number Boca Raton Campus Security (561) 862-4600
More informationFire Hazard Identification Checklist 1
Fire Hazard Identification Checklist 1 (Component of a BC Fire Code (BCFC) compliance inspection) Date: BUILDING INFORMATION Company name: Building Name: Address: Street # and name City/Province Postal
More informationFactors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment
Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Hong-Zeng (Bert) Yu FM Global 16 th International Water Mist Conference September 21-22, 2016 Vienna,
More informationFact File 66. Guide to Beam Smoke Detectors
Fact File 66 Guide to Beam Smoke Detectors Guide to Beam Smoke Detectors INTRODUCTION... 3 TERMINOLOGY... 4 PURPOSE OF BEAM DETECTORS... 5 PROS AND CONS OF BEAM DETECTORS... 6 FUNDAMENTAL PRINCIPLES OF
More informationInstallation and Maintenance Requirements
Installation and Maintenance Requirements Water Mist Systems in Buildings John Sinclair Compco Fire Systems This Presentation Will Cover: 1. Water mist systems for buildings and local applications 2. Products
More informationCeasefire Watermist Hydrant Systems
No fire is too big to beat. Ceasefire Watermist Hydrant Systems Never underestimate a fire. With enough oxygen and other fuels, even the smallest flame can turn into a full-scale blaze, destroying everything
More informationEngineering Simulation in Built Environment and Civil Engineering Projects
Engineering Simulation in Built Environment and Civil Engineering Projects Fluid Dynamics Simulation Mark Owens ANSYS UK Ltd 2010 ANSYS, Inc. All rights reserved. 1 ANSYS, Inc. Proprietary Fires and Smoke
More informationPRIMATECH WHITE PAPER PROCEDURE FOR DUST HAZARD ANALYSIS (DHA)
PRIMATECH WHITE PAPER PROCEDURE FOR DUST HAZARD ANALYSIS (DHA) Glossary of Terms Combustible dust: A finely divided combustible particulate solid that presents a flash-fire hazard or explosion hazard when
More informationCopy of article submitted to Fire Safety Engineering for publication January/February 2009
Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Metal faced sandwich panels with plastic foam cores - a challenge to fire safety by Gordon Cooke Confusion, misleading
More information