Water Leak Detector BA/LDT Accessories Termination and Troubleshooting
|
|
- Steven Nash
- 6 years ago
- Views:
Transcription
1 Overview & Identification The is designed to sense the presence of water and alert a central monitoring system of the potentially destructive situation. Upon water detection, an alarm relay changes state, and a local red LED illuminates. The transmitter can be set for latching alarm or non-latching alarm with normally energized or de-energized operation. An optional remote water sensor is available for small inaccessible locations such as AHU pans or under floor water detection. Fig. 1: Water Leak Detector with Internal Sensor Probe Fig. 2: with Built In Sensor and a 5 Amp Relay in a System Diagram (Side View) Fig. 3: with Remote Spot Sensor (right) and Water Rope Sensor (below) Fig. 4: with Remote Spot Sensor or optional Water Rope Sensor (not shown) and a 5 Amp Relay in a System Diagram (Side View) 1 of 6
2 Mounting Place the transmitter in a location where a water leak is likely to cause damage such as a cooling coil pan, a hot water tank pan, under a sink, under an elevated floor, or in a drop ceiling under pipes. The transmitter can be independently mounted in a visible location by using a remote water sensor and waterproof cable as shown in Fig. 4. Terminate the transmitter as shown in the termination section. 1. Set the transmitter where water is most likely to be a problem or in the collection pan under the water coil or heater (Fig. 5). Alternatively the water sensor can be attached to the pan edge with two set screws (Fig. 6). Do not over tighten or puncture the pan. Alternatively a remote water sensor can be attached to the pan or floor with mounting tape (Fig. 7). Clean surface thoroughly before setting the sensor in place and push sensor down firmly. Mount the detector enclosure in a visible location within cable length of the remote water sensor. Alternatively a remote water sensor can be attached to the floor with screws (Fig. 8). Mount the detector enclosure in a more visible location within cable length of the remote water sensor. Alternatively the rope water sensor can be laid on the floor or under pipes as shown in Figs. 10, 11, 12 & 13. Cable clamps can be used to secure the sensor to the floor. 2. Adjust the depth screw on the sensor probe in the middle of the open enclosure to the alarm depth (Fig. 5). If using a remote water sensor, adjust the depth screw as shown in Fig. 9. The rope sensor detects water 1/8 off the floor and has no adjustment. 3. Run the cable to the transmitter location leaving enough slack to terminate and allow for some repositioning as needed. Use a strain relief on the entering cable so the wires do not tug on the terminals directly. 4. Terminate and configure in accordance with the termination section. Fig. 5: Leak Detector with Sensor in a BAPI-Box Pan edge mounting screws Detection depth adjust screw Fig. 6: Water Sensor Pan Rim Mounting Firmly push down on clean surface Fig. 7: Remote Water Sensor Tape Mount Fig. 8: Remote Water Sensor Floor Mount Installer-provided mounting screws Fig. 9: Remote Water Sensor Depth Adjusting Detection depth adjust screw Reference probe Detection depth adjust from 1/16 to 1/2 depth Up Down 1. Loosen wing nut. 2. Set the required depth of the sensor probe screw using a #2 Phillips screwdriver. 3. Hold the sensor probe screw stationary with the screwdriver. 4. Turn the wing nut down the probe screw until it engages the plastic. 5. Tighten the wing nut 1/4 turn into the plastic. 2 of 6
3 Mounting continued... Fig. 10: Hot Water Tank Pan Mounting Fig. 11: Sub-Floor Sensor Mounting Fig. 12: Vertical Pipe Sensor Mounting The following combinations of sensors can be used: 1. Two rope sensors with a combined length of no more than Two spot sensors with a combined length of no more than One spot sensor with a maximum length of 25 and one rope sensor of no more than 50. Note: Shielded or twisted pair wire cannot be used to extend the sensor wires. This applies to both the remote spot sensor as well as the rope sensor. Fig. 13: Horizontal Pipe Sensor Mounting 3 of 6
4 Wiring and Termination Terminal Description A...Water Sensor (No polarity to water sensor cable) B...Water Sensor (No polarity to water sensor cable) NC2*...Alarm Contact 2, Normally Closed to C2 when De-energized C2...Alarm Contact 2, Common NO2...Alarm Contact 2, Normally Open to C2 when De-energized NC1*...Alarm Contact 1, Normally Closed to C1 when De-energized C1...Alarm Contact 1, Common NO1...Alarm Contact 1, Normally Open to C1 when De-energized GND/NEU Power supply ground/neutral Fig. 14: Leak Detector Circuit Board V+/HOT...Power supply input 24VAC/VDC +/- 10% *Not used for low current relay version, SPST, Form A Sensitivity Adjustment for 10 and 100 Remote Rope Sensors The unit s leak detection sensitivity is set at the factory. However, for the 10 and 100 remote rope sensors, the sensitivity may need to be adjusted in the field. If you are using a 10 remote rope and it won t respond, rotate the sensitivity adjustment potentiometer 5 turns counterclockwise. If you are using a 100 remote rope and it is too sensitive, then rotate the sensitivity adjustment potentiometer 5 turns clockwise. Sensitivity Adjustment Potentiometer Fig. 15: Leak Detector Circuit Board 4 of 6
5 Set Up and Commissioning Indication/Controls Description Red LED...LED illuminates when water is detected Green LED...LED illuminates when normal power is applied Reset Button...Resets latching alarm contact (only if water is no longer present) Latching Relay...Left side of J1 set to top two pins listed as L Non-Latching Relay...Left side of J1 set to bottom two pins listed as N (Default) Supervised Relay***...Right side of J1 set to top two pins listed as S (Default) Unsupervised Relay...Right side of J1 set to bottom two pins listed as U *** Supervised means the relay is energized when not in alarm and the relay de-energizes on a power failure or alarm. 1. After the unit is installed and wired, turn on the power. (24VAC/VDC +/- 10%) 2. Check that the green LED is on. If it is not on, check the power source. 3. Dampen a cloth or sponge and touch both the sensor probe tip and the sensor base. An alarm should occur within 5 seconds. 4. The red LED should illuminate and the relay(s) should de-energize, or energize if set up as unsupervised. (To check relay status, measure the resistance at the relay contacts or monitor the status from the BAS screen.) 5. Remove the dampened rag or sponge to clear the alarm. If the unit is set up for a non-latching relay (J1 jumper across the N pins), the red LED and relay(s) will energize, or de-energize if set up as a unsupervised relay. If the unit is set up for a latching relay (J1 jumper across the L pins), the operator must push the reset switch on the detector board or interrupt power to clear the alarm. 6. Check the depth screw (see Mounting Section) to be sure it s at the appropriate water depth for alarm. Operation Sequence When power is applied, the green LED will illuminate and and the unit will start to detect for water at the sensor probe. When there is no detection of water (normal condition), the relays are not in an alarm state and the red LED remains off. For units set up in the unsupervised relay mode, the relays are de-energized. For units set up in the supervised relay mode (default), the relays will be energized. (Note: When there is a loss of power, a supervised relay will drop out indicating a water detection alarm.) Within 5 seconds of water detection, the relays go into an alarm state and the red LED illuminates. For units set up in the unsupervised relay mode, the relays are energized. For units set up in the supervised relay mode (default), the relays are de-energized. If the unit is in non-latching or auto-reset (default) operation, then the alarm state will automatically reset when the water has dried up. If the unit is in latching or manual-reset operation, then the unit will stay in an alarm state until the reset button is pressed or power is cycled. If there is still water detected during a reset button push, the unit will not reset. If there is still water detected after a power interrupt, the unit will initiate another alarm within 5 seconds. Diagnostics Possible Problem Green LED Not On Red LED Not Working Or Relay Not Energizing. Unit Will Not Reset Possible Solution 1. Check for proper power to the unit (see power specs on back page). 1. Check for proper power to the unit (see power specs on back page). 2. Check if water is touching the sensor probe and reference probe. 3. Adjust sensor probe depth. 4. For rope sensor units, check the sensitivity adjustment as described on page Check for the presence of water or debris touching the two sensor probes. 2. Be sure the sensor wires are not shorted. 3. If the L pins on J1 are shorted, push the reset button or cycle power. 4. For rope sensor units, check the sensitivity adjustment as described on page 4. 5 of 6
6 Maintenance Check the water sensor probe once a year to be sure there is no dirt or debris collected around the probes. Dirt or debris around the probes may cause nuisance alarms in moist situations. Change the service intervals depending on environmental conditions. In very clean conditions the probe may never need maintenance. Rope sensor may be wiped down with isopropyl alcohol, warm soapy water on a cotton cloth or placed in a dishwasher. Cautions/Warnings This unit is not intended to be a safety device. In no event shall BAPI or its officers, directors, employees or agents be liable to any company or individual for any indirect, incidental, special, exemplary, punitive or consequential damages including, without limitation, economic or commercial losses, arising out of or resulting from the misuse of this water detector as a safety device. Specifications Power: 24VAC/VDC +/- 10% 5 Amp Relays: 4 Watt/ 4 VA max 0.5 Amp Relays: 2 Watt/ 2 VA max (not intended to switch a load) Wiring: Relays Transmitter Mounting: Sensor: Standard Optional Optional Flex Connector or Liquid Tight Fitting Up to 6 wires 2 wires for Power Lays in the pan or attached with a pan edge hook with screws Single SS probe from bottom of BB with adjustable depth screw from.063 to.84 Remote water sensor with depth screw with adjustable depth from 1/16 to 1/2 Remote long line water sensor (Rope) Detects water over the full length at depths > Note: 100 ft maximum including non-sensing extension cable. Detector Transmitter: Alarm Contacts LDT1: One SPST, 0.5A relay output, 10W max LDT2: Two SPST, 0.5A relay outputs, 10W max LDT3: One SPDT, 5A relay output LDT4: Two SPDT, 5A relay outputs Indication Reset Action SPST or SPDT, 30 VAC/DC max Selectable as normally Energized or De-energized 1 Green Power LED, 1 Red Alarm LED If latching, local push button or power interrupt Sensor Reaction Responds to presence of water within 5 seconds Termination: Agency: Terminal strip, 4-10 terminals, 12-24AWG RoHS, UL94V-0, UV-rated in Enclosure Set Up: BB Sensor Remote Sensor Latching Jumper Adjustable depth from.063 to.84 ( 1/16th default) Adjustment depth from 1/16 to 1/2 ( 1/16th default) Latching Version - Stays energized after water has dried up Non-Latching Version (default) - Alarm follows wet or dry surface Supervision Supervised Version (default) - Jumper De-energized when in alarm. Note: Relay will drop out on loss of power indicating a water detection alarm. Unsupervised Version - Energized when in alarm. Enclosure Ratings: Remote Sensor Submersible, w/fep plenumrated, waterproof cable Rope Sensor Plenum rated Transmitter BAPI-Box, NEMA 4 Ambient: Remote Sensor -40 to 185ºF (-40 to 85ºC), 0 to 100%RH, Condensing Transmitter (BB) -40 to 185ºF (-40 to 85ºC), 0 to 95%RH, Non-condensing Rope Sensor 32 to 167ºF (0 to 75ºC), 0 to 95%RH, Non-condensing Enclosure Materials: Remote Sensor Aluminum bracket w/abs plastic shell Transmitter (BB) Polycarbonate Note: This unit is not intended to be a safety device. 6 of 6
Water Leak Detector. Installation and Troubleshooting. Overview
Overview Water Leak Detector The Water Leak Detector is designed to sense the presence of water and alert a central monitoring system of the potentially destructive situation. Upon water detection, an
More informationTraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM
TTC-1 TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION The nvent RAYCHEM TraceTek TTC-1 sensing module is used with TraceTek sensing cables to detect liquid leaks.
More informationDuct and Rough Service Carbon Monoxide Sensor
Product Identification and Overview Duct and Rough Service Carbon Monoxide Sensor BAPI s Carbon Monoxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations.
More informationWD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.
Data Sheet Ref: 90501085 WD-CS Water leak detection cable Technical Overview The WD-CS range of cable sensors are typically used to detect water leaks usually under floors, and are used in conjunction
More informationSentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.
Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH Liquid Level Alarm 2.2 LOW Liquid Level Alarm 3. INSTALLATION...
More informationaquilar - leak detection solutions
AT-SZA Single Zone Alarm OPERATI & MAINTENANCE MANUAL AT-SZA Single Zone Alarm OPERATI & MAINTENANCE MANUAL Product Information SZA Power consumption Relays Temperature Enclosure Approvals Additional items
More informationInstallation, Operation and Maintenance Manual
ECO-1 (AT-EL-1) Single Zone Leak Detection Alarm Panel Installation, Operation & Maintenance Manual ECO-1 (AT-EL-1) Single Zone Leak Detection Alarm Panel Installation, Operation and Maintenance Manual
More informationDH500ACDC Intelligent Air Duct Smoke Detector Housing
INSTALLATION AND MAINTENANCE INSTRUCTIONS DH500ACDC Intelligent Air Duct Smoke Detector Housing 3825 Ohio Avenue St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 Specifications Length: 14.5
More informationbreeze easytm model # F100-1W
DewStop breeze easytm model # F100-1W Installation Guide Read and Save These Instructions LISTED Questions, Problems, Missing Parts? Please Call 1-360-876-2974 or E-Mail info@dewstop.com please retain
More informationaquilar - leak detection solutions
AT-MZA Multi Zone Alarm OPERATI & MAINTENANCE MANUAL AT-MZA Multi Zone Alarm OPERATI & MAINTENANCE MANUAL Product Information MZA 115Vac +15%, -20%; 50/60 Hz 230Vac ±10%; 50/60 Hz 12Vdc ±20% Power consumption
More informationRK-OXY Oxygen Sample-Draw Detector Operator s Manual Part Number: RK Revision: P1 Released: 7/18/02
35-3000RK-OXY Oxygen Sample-Draw Detector Operator s Manual Part Number: 71-0071RK Revision: P1 Released: 7/18/02 RKI Instruments Inc. 1855 Whipple Road Hayward, CA 94544 PH: 800-754-5165 Fax: 510-441-5650
More informationBUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
More informationSnifter. User Manual. Distributor
Snifter User Manual Distributor Version 1.3 08/09/2009 1 Table of Contents 1. INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 3 1.3 How does it work?... 3 2. INSTALLATION... 4 2.1 Selecting the
More informationTTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.
TTSIM-1A TraceTek Sensor Interface Module with Relay Installation Items (not supplied) General Information Installation/Operation Instructions Please read these instructions and keep them in a safe place.
More informationB.I.C.A Built-In Coffee Appliance
B.I.C.A Built-In Coffee Appliance Automatic Coffee Brewer Parts & Service Models: 1033510, 1033510S & 1033511 3828 S. Main St. Los Angeles, CA 90037-1491 800-421-6860 310-787-5444 Fax 310-787-5412 e-mail:
More informationMANUAL RESET ALARM RELEASE
Fire Door Release MODEL AR-D MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS T CLASS TPA Series 7.5 AND 10 TON HEAT PUMPS 7.5 TO 10 TONS 506148 01 10/2011 Supersedes 06/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean
More informationOPERATING and MAINTENANCE INSTRUCTIONS Models: H138NPSCLCMCQRL Merchandising Hot Cabinets
Rev. (/) Page of 0 OPERATING and MAINTENANCE INSTRUCTIONS Models: H8NPSCLCMCQRL Merchandising Hot Cabinets Cabinet model number: Cabinet serial number: Authorized Service Agency: Ph: Fax: Keep this manual
More informationCC-2222C-PL, CC-2222C-PRL, CC-2222C-PR-2, CC-2222C-PL-2,
Rev. 14 (10/08) Page 1 of 16 INSTALLATION, OPERATION and MAINTENANCE MANUAL for Cres Cor Models: CC-2222C-PR, CC-2222C-PL, CC-2222C-PRL, CC-2222C-PR-2, CC-2222C-PL-2, and CC-2222C-PRL-2 Rev. 14 (10/08)
More informationUser's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm
User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm Table of Contents Page Introduction 1 Description 1 Specifications 2 Installation 3 Calibration 4 General Maintenance 5 List of
More informationUltraviolet Monitoring System. Part Numbers UV/MS-1 V3 UV/MS-2 V3. Installation And Operations Manual
Ultraviolet Monitoring System Part Numbers UV/MS-1 V3 UV/MS-2 V3 Installation And Operations Manual 2 System Description The Wyckomar UV Monitor measures true UV intensity at 254 nm, which is the effective
More informationOPERATING and MAINTENANCE INSTRUCTIONS Models: H138NPS36CLCMQRL i7 Hot Cabinet
Rev. 0 (/) Page of 9 OPERATING and MAINTENANCE INSTRUCTIONS Models: HNPS6CLCMQRL i7 Hot Cabinet Cabinet model number: Cabinet serial number: Authorized Service Agency: Ph: Fax: Keep this manual for future
More informationMODEL /4" Conduit. (By others) Terminal Strips Companion unit (without electronics) not shown. Approximate Preload
2900 FIREGUARD Electromechanical Closer-Holder Device Models 12-2960, 9-2960 and 2960 Multipoint Hold Open with Rigid Arms Pull (Hinge) Side Installation Instructions CAUTION: FAILURE TO INSTALL OR ADJUST
More informationLIMITED LIFETIME WARRANTY
Congratulations on your purchase of a Minka-Aire TM ceiling fan! Your new fan will be a beautiful addition to you home, and will keep you comfortable throughout the year. Minka-Aire TM offers a variety
More informationInstallation & Maintenance Instructions
Portable High Temperature Blower Attention: Do not operate this heater in explosive areas. Installation & Maintenance Instructions Dear Owner, Congratulations! Thank you for purchasing this new heater
More informationDS9370-BEL. Installation Instructions TriTech Ceiling Mount PIR/Microwave Intrusion Detector
DS970-BEL EN Installation Instructions TriTech Ceiling Mount PIR/Microwave Intrusion Detector DS970-BEL Installation Instructions.0 Installation Considerations.0 Installation Considerations Not suitable
More informationWiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door
CAUTION Hinge Edge of Door Wiring Instructions Checkmate Series with Single Point Hold-Open Combination Door Closer-Holder and Releasing Device with or without Integral Smoke Detector INSTALLER: LEAVE
More informationINSTALLATION INSTRUCTIONS FOR 8330*63**, 8530*63** CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY
RV Products Division INSTALLATION INSTRUCTIONS FOR 8330*63**, 8530*63** CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY DESIGNED AND MANUFACTURED BY THE MAKERS OF COLEMAN -MACH AIR CONDITIONERS TABLE OF CONTENTS
More informationSTEAMPRO. Steam Generator Troubleshooting and Service Guide
STEAMPRO Steam Generator Troubleshooting and Service Guide TABLE OF CONTENTS Page PREFACE... 1 I. STEAMPRO STEAM GENERATOR SYSTEM...2 II. PLUMBING AND ELECTRICAL...3-4 III. SYSTEM OVERVIEW... 5-10 IV.
More informationSP-1000X. Panic Device Power Controller Installation Guide. Rev
TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current
More informationGate Operator. Modfications
Gate Operator Modfications 100va Transformer G90 100 OP1 - Single Phase G90 100 OP3 -Three Phase Upgrades the transformer in the operator enclosure from 40va to 100va. Provides additional control circuit
More informationNS1100 / NS2200 Installation Guide & Owner s Manual
NS1100 / NS2200 Installation Guide & Owner s Manual Installation Tips Contents 1 Control Panel 1 Spool of Signal Wire 2 Mounting Screws & Drywall Inserts 2 Wire Clips 3 Wire Ties Tools you will need Phillips
More informationOxygen (O2) Single-Point Gas Detection System
Oxygen (O) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in oxygen (O) sensor, accepts one analog remote device such as a secondary gas sensor, temperature or humidity
More informationMacurco HD-11 Hydrogen Gas Detector
Macurco HD-11 Hydrogen Gas Detector User Instructions Important: Keep these User Instructions for reference TABLE OF CONTENTS GENERAL SAFETY INFORMATION 3 Intended Use 3 List of Warnings and Cautions 3
More informationMacurco HD-11 Hydrogen Gas Detector User Instructions. Important: Keep these User Instructions for reference
Macurco HD-11 Hydrogen Gas Detector User Instructions Important: Keep these User Instructions for reference 2 TABLE OF CONTENTS GENERAL SAFETY INFORMATION 4 INTENDED USE 4 LIST OF WARNINGS AND CAUTIONS
More informationNitrogen Dioxide (NO2) Single-Point Gas Detection System
Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary
More informationOperations Manual. Motion Detector Module Model ZS10
Motion Detector Module Model ZS10 The must be referred to for correct installation. Failure to comply with the shall void all warranties and liabilities. Overview The ZS10 Motion Detector Module is an
More informationDISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:
DISHWASHER Models DW2432 and DW2432SS Installation Manual Write Serial Number (on inner door of unit) here: Felix Storch, Inc. Summit Appliance Division 770 Garrison Avenue Bronx, New York 10474 www.summitappliance.com
More informationVENTILATION FAN. MFG Model : VFB80HLED2/VFB080C4L2 /VFB080C4LED2/ VFB100HLED2/VFB100C4LED1 READ AND SAVE THESE INSTRUCTIONS
VENTILATION FAN MODEL 80HLED/80L/80LED/00HLED/00LED TABLE OF CONTENTS Package Contents General Safety Information 3 Preparation Assembly Instructions 5 New Construction 5 Existing Construction 6 Connect
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS T CLASS TPA Series HEAT PUMPS 7.5 TO 10 TONS 506148 01 12/08 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act of 1990 bans the intentional
More informationINSTALLATION INSTRUCTIONS. Aluminum Blinds - Standard - - Lift & Lock -
1 INSTALLATION INSTRUCTIONS Aluminum Blinds - Standard - - Lift & Lock - 1 Deluxe 1 Traditional 1 Value & 1 Basic 2 Macro Thank you for your purchase. This blind has been custom built for you from the
More informationINSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS
RV Products Division INSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330C755 CONTROL BOX KIT (12 VDC HEAT READY) 8530-750 CONTROL BOX KIT
More informationMulti-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.
Fire Sentry Corporation (FSC) 593 Apollo Street Tel.: 714-671-1100 Brea, California 92821 Fax: 714-671-5821 Multi-Spectral, Digital, Infrared Electro-Optical FSC Model No. s FS10-R and FS10-A Unitized,
More informationThree Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.
Three Phase Simplex Installation Instructions and Operation/Troubleshooting Manual This control panel must be installed and serviced by a licensed electrician in accordance with the National Electric Code
More informationWARNING WARNING WARNING WARNING HEALTHY CLIMATE GERMICIDAL LIGHT AIR CLEANERS/ FILTERS
AIR CLEANERS/ FILTERS 2001 Lennox Industries, Inc. Dallas, Texas USA 504,327M 07/2001 HEALTHY CLIMATE GERMICIDAL LIGHT INSTALLATION INSTRUCTIONS FOR LENNOX MODELS UV-500, UV-1000, UV-2000 General The Lennox
More informationWiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector
Wiring Instructions for the 900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR
More informationFAUX WOOD BLINDS 2 & 2-1/2 SLAT SIZES
INSTALLATION INSTRUCTIONS FAUX WOOD BLINDS 2 & 2-1/2 SLAT SIZES STANDARD RECTANGULAR Thank you for your purchase. This blind has been custom built for you from the highest quality materials. To avoid errors
More information30-YEAR LIMITED WARRANTY
PROGRESS LIGHTING 30-YEAR LIMITED WARRANTY PROGRESS LIGHTING FAN MOTORS ARE WARRANTED TO THE END USER TO BE FREE OF ELECTRICAL AND/OR MECHANICAL DEFECTS FOR A PERIOD OF 30 (THIRTY) YEARS FROM DATE OF SALE.
More informationSEC 2000 Millenium Infrared Gas Detector
SEC 2000 Millenium Infrared Gas Detector Instruction and Operation Manual Sensor Electronics Corporation 5500 Lincoln Drive Minneapolis, Minnesota 55436 USA (952) 938-9486 Fax (952) 938-9617 Email: sales@sensorelectronic.com
More informationRKA-LEL Sample Draw Combustible Gas Detector
35-3000RKA-LEL Sample Draw Combustible Gas Detector Specifications Table 1 lists specifications for the sample draw combustible gas detector. Table 1: Specifications Target Gas Input Power Combustible
More informationDETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS
TEST LOG Detector Identification Information Manufacturer and Serial Date Detector Model: Number: Installed: Description of Detector Location: Test Results and Maintenance Data Date Test Test Maintenance
More informationK Series (Model A) Fan Forced Wall Heaters
(400mm) 15-3/4" (35mm) 1-3/8" (95mm) 3-3/4" K Series (Model A) Fan Forced Wall Heaters (485mm) 19-1/8" (463mm) 18-1/4" FILE #E21609 Installation & Maintenance Instructions Dear Owner, Congratulations Thank
More informationTwo-Channel Gas Controller
Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously
More informationGasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.
Gasflag Single Channel Control Panel Alarm Only Apparatus Installation, operating and maintenance instructions, M07225 Issue 2 1/07/05 Crowcon Detection Instruments Ltd 2 Blacklands Way Abingdon Business
More informationINSTALLATION INSTRUCTIONS FOR MOUNTING KIT
RV Products Division INSTALLATION INSTRUCTIONS FOR 8330-5501 MOUNTING KIT 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330B755 CONTROL BOX KIT (12 VDC HEAT/COOL) 8530-750 CONTROL BOX KIT (24 VAC COOL ONLY)
More informationAMC-RAM-4. Refrigerant Alarm Module USER MANUAL. Please read the installation and operating instructions completely and carefully before starting.
AMC-RAM-4 Refrigerant Alarm Module USER MANUAL IMPORTANT: Please read the installation and operating instructions completely and carefully before starting. Filename: 3310405B, DOC, AMC_RAM4_Manual.doc
More informationITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual
ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,
More informationImPress IRONING STATION
CONSUMER SERVICES TECHNICAL EDUCATION GROUP PRESENTS L-73 ImPress IRONING STATION Model LFB2611L JOB AID Part No. 8178203 FORWARD This Whirlpool Job Aid, ImPress Ironing Station, (Part No. 8178203), provides
More informationSingle Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors
Hinge Edge of Door Hinge Edge of Door Wiring Instructions for the Sargent 0 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL
More informationDISHWASHER INSTALLATION INSTRUCTIONS
DISHWASHER INSTALLATION INSTRUCTIONS IMPORTANT! Read all of these instructions before installing the dishwasher. AUTOMATIC HIGH LOOP The drain hose is fastened to the back of the machine at the best height.
More informationPO Box 827 Hawley, MN (218) Fax (218)
Introduction Before proceeding with the installation or operation of the Oil Alert System, read all instructions thoroughly, as well as complying with all Federal, State and Local codes, Regulations and
More informationELECTRIC STOVE HEATER Models: FS2213B
ELECTRIC STOVE HEATER Models: FS2213B OWNER S MANUAL WARNING Read and understand this entire owner s manual, including all safety information, before plugging in or using this product. Failure to do so
More informationFLCH4R Garage and Utility Electric Heater
FLCH4R Garage and Utility Electric Heater Installation, Operation & Maintenance Instructions Model No. Volts Amps Watts BTU/HR Phase High Low High Low High Low Min Fuse Size* FLCH4R 208 17.3 8.66 3600
More informationSERIES 500. Installation & Maintenance Instructions. Ceiling Mounted Fan Forced Heater WARNING SAVE THESE INSTRUCTIONS. Recessed Mount.
Recessed Mount Ceiling Mounted Fan Forced SERIES 500 Surface Mount Installation & Maintenance Instructions Dear Owner, Congratulations Thank you for purchasing this new heater manufactured by Marley Engineered
More informationInstalling the Cisco ONS FAP-4 Fuse Alarm Panel
Installing the Cisco ONS 15454-FAP-4 Fuse Alarm Panel Product Number: 15454-FAP-4= This document explains how to install, test, operate, and maintain the Cisco ONS 15454-FAP-4 fuse alarm panel. This document
More informationAnalog Room Pressure Monitor RPC Series
Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the
More informationInstallation Instructions. For the 18 Built-In Dishwasher and Front Color Panels
Installation Instructions For the 18 Built-In Dishwasher and Front Color Panels Printed in USA 154232102 Before You Begin DO NOT INSTALL DISHWASHER UNTIL YOU HAVE READ ALL INSTRUCTIONS. FOR YOUR SAFETY,
More informationInstallation Manual. Features SMART SWITCH OCCUPANCY SENSOR. Maximum Versatility. Maximum Energy Savings
Features SMART SWITCH OCCUPANCY SENSOR Installation Manual Maximum Energy Savings Maximum Versatility Sensitive 140 view passive infrared motion detector keeps lights on only when rooms are in use. Switches
More informationINSTALLATION INSTRUCTIONS FOR 7370A736 FLUSH MOUNT CEILING PLENUM
INSTALLATION INSTRUCTIONS FOR 7370A736 FLUSH MOUNT CEILING PLENUM TABLE OF CONTENTS Warnings...2 Package Contents...2 General Information...3 Ceiling Plenum Installation Requirement...3 Supply Ducting
More informationINSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY
INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY TABLE OF CONTENTS Warnings...3 Package Contents...3 General Information...3 Supply Ducting And Registers...3 Routing 115 VAC Wiring...5
More informationSide Entry Bushing (SEB) High Temperature Cable Clamp Bushing Installation Instructions
Page: 1 of 6 High Temperature Cable Clamp Bushing is a strain relief, and stress protection product that can be placed around a wire bundle and under a saddle clamp backshell adapter after the contacts
More informationALUMA INSTRUCTION MANUAL WARRANTY CERTIFICATE
ALUMA BY INSTRUCTION MANUAL WARRANTY CERTIFICATE Manual design and all elements of manual design are protected by U.S. Federal and/or State Law, including Patent, Trademark and/or Copyright laws. Minka-Aire
More informationCEILING FAN OWNER'S MANUAL
Style that revolves around you. CEILING FAN OWNER'S MANUAL QUATRO 10/09 WARNING: Read and follow these instructions carefully and be mindful of all warnings shown throughout. GENERAL INSTALLATION & OPERATION
More informationP4200PM / P5000PM Remote Air Dryer User s Guide
P4200PM / P5000PM Remote Air Dryer User s Guide 1. Welcome & Congratulations Congratulations on your purchase of a new PUREGAS P4200PM / P5000PM Air Dryer! We here at PUREGAS are very proud of our products
More informationREV: 000. Lumitron/ Luminator
REV: 000 Lumitron/ Luminator Table Of Contents Introduction 3 Standard Operating Guide 3 Features & Specs 3 External Layout 4-8 Internal Layout 9-10 Wiring Diagrams 11 F.A.Q. 12-14 Ballast to Lamp Relationship
More informationCEILING FAN OWNER S MANUAL
CEILING FAN OWNER S MANUAL 5/03 I/O THE INDOOR/OUTDOOR FAN WARNING: Read and follow these instructions carefully and be mindful of all warnings shown throughout. GENERAL INSTALLATION & OPERATION INSTRUCTIONS
More informationinstallation and operation manual for Hunter Ceiling Fans
For Your Records and Warranty Assistance Model Name: Catalog/Model No.: Serial No.: Date Purchased: Where Purchased: For reference also attach your receipt or a copy of your receipt to the manual. installation
More informationCeiling Fan Ow n e r s Manual
Style that revolves around you. Ceiling Fan Ow n e r s Manual Akina 1/08 WARNING: Read and follow these instructions carefully and be mindful of all warnings shown throughout. General Installation & Operation
More informationMAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER
PNEUMERCATOR Liquid Level Control Systems Electronic Systems Excluding LC2000 And TMS Series MAINTENANCE & TROUBLESHOOTING GUIDE 400 300 500 FUEL LEVEL LEAK MONITOR 1 200 600 OIL/GAS NORMAL WATER PNEUMERCATOR
More informationSintrol Snifter A1+ Manual. Version 1.2.2
Sintrol Snifter A1+ Manual Version 1.2.2 Table of Contents 1 INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 3 1.3 How does it work?... 3 2 INSTALLATION... 4 2.1 Selecting the installation location...
More informationDryAire DRYING CABINET
CONSUMER SERVICES TECHNICAL EDUCATION GROUP PRESENTS L-72 DryAire DRYING CABINET Model LMA1053L JOB AID Part No. 8178202 FORWARD This Whirlpool Job Aid, DryAire Drying Cabinet, (Part No. 8178202), provides
More information60" Lyndon Patio. Instruction Manual Customer Service :30 AM to 5:00 PM EST, Monday - Friday A Kichler Decor ceiling fan
60" Lyndon Patio TM 310140 A Kichler Decor ceiling fan Includes wall mount control system Kichler Lighting 7711 East Pleasant Valley Road P.O. Box 318010 Cleveland, Ohio 44131-8010 Instruction Manual Customer
More informationGasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08
GasScanner 4C Four Channel Monitor Operator s Manual MINT-0280-XX Rev. A 02/25/08 Product Warranty Matheson Tri-Gas., warrants gas alarm equipment sold by us to be free from defects in materials, workmanship,
More informationFeatures TREASURE HUNTER S CODE OF ETHICS
63-3013.fm Page 3 Wednesday, July 26, 2000 9:42 AM ˆ Features With your Famous Trails Metal Detector, you can hunt for coins, relics, jewelry, gold, and silver just about anywhere. The Metal Detector is
More informationDIGITAL METERS Large Display Temperature Meters Instruction Manual
DIGITAL METERS Large Display Temperature Meters PD755 PD756 PD757 Handles Thermocouple & RTD Inputs with Simplicity J, K, T, E, R, & S Thermocouples 100 Ω Platinum RTD (0.00385 or 0.00392 curve) Large
More informationCEILING FAN OWNER'S MANUAL
Style that revolves around you. CEILING FAN OWNER'S MANUAL Vail with DC motor 10/15 WARNING: Read and follow these instructions carefully and be mindful of all warnings shown throughout. GENERAL INSTALLATION
More informationBuilt-In Dishwasher. Installation Instructions. BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT The dishwasher MUST be
Installation Instructions Built-In Dishwasher If you have questions, call 800.GE.CARES (800.432.2737) or visit our website at: www.ge.com BEFORE YOU BEGIN Read these instructions completely and carefully.
More informationControlled Energy Corp. 340 Mad River Park Waitsfield, VT TOLL FREE
Controlled Energy Corp. 340 Mad River Park Waitsfield, VT 05673 TOLL FREE 866-330-2729 www.controlledenergy.com/tech Important Safety Instructions When using this electrical equipment, basic safety precautions
More informationALUMA INSTRUCTION MANUAL WARRANTY CERTIFICATE
ALUMA BY INSTRUCTION MANUAL WARRANTY CERTIFICATE Manual design and all elements of manual design are protected by U.S. Federal and/or State Law, including Patent, Trademark and/or Copyright laws. The Minka-Aire
More informationTRADITIONAL CONCEPT INSTRUCTION MANUAL WARRANTY CERTIFICATE
TM TRADITIONAL CONCEPT BY INSTRUCTION MANUAL WARRANTY CERTIFICATE Manual design and all elements of manual design are protected by U.S. Federal and/or State Law, including Patent, Trademark and/or Copyright
More information(3 plastic wire connectors,blade balancing kit, 2 extra mounting screws #10-32 for outlet box.)
Excel Lighting & Manufacturing Ltd. Lifetime Limited Warranty Excel Lighting & Manufacturing Ltd. Warrants the fan motor to be free from defects in workmanship and material present at time of shipment
More informationUser s Manual & Operating Instructions
User s Manual & Operating Instructions Model Numbers REM-03-240-GH / REM-05-240-GH CONSUMER: READ AND SAVE THESE INSTRUCTIONS Use this heater only as described in this manual. Any other use not recommended
More informationSOLO OWNERS MANUAL, OPERATING INSTRUCTIONS & INSTALLATION INSTRUCTIONS
SOLO OWNERS MANUAL, OPERATING INSTRUCTIONS & INSTALLATION INSTRUCTIONS READ MANUAL BEFORE OPERATING SYSTEM Read the owner s manual thoroughly before operating to ensure the most efficient use of the system.
More informationThe feedhorn heaters consist of heater wire attached to a strap and covered with heatshrink. They are attached to a rib on the feedhorn.
Satellite Antenna De-icing Systems for Dish Antennas Automatic De-icing System for Protection against Snow and Ice Simple to Field Install and Operate Engineered for Customer Specified Voltages Low Energy
More informationSnifter ATEX22 VERSION. User Manual. Distributor
Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5
More informationSingle Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual
We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239
More informationPipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual
MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...
More informationRoanoke 48 in Ceiling Fan Owner s Manual. Roanoke Ventilador de Techo de 1,22 m Manual del Propietario
160 854 Roanoke 48 in Ceiling Fan Owner s Manual Roanoke Ventilador de Techo de 1,22 m Manual del Propietario 48 Roanoke Ceiling Fan by Hampton Bay Thank you for purchasing our ceiling fan. This product
More informationSeries. Access Power Controllers. Installation Guide
Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse
More informationINSTALLATION, OPERATION and MAINTENANCE MANUAL for Cres Cor 2kW RETHERMALIZER
Rev. 1 (1/16) Page 1 of 12 INSTALLATION, OPERATION and MAINTENANCE MANUAL for Cres Cor 2kW RETHERMALIZER REVOLUTION FOODS MODEL CO151027 Rev. 1 (1/16) Page 2 of 12 TABLE OF CONTENTS SUBJECT PAGE INSTALLATION
More information