FIRE PROTECTION BASIC MATERIALS AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

Size: px
Start display at page:

Download "FIRE PROTECTION BASIC MATERIALS AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS"

Transcription

1 FIRE PROTECTION BASIC MATERIALS AND METHODS PART 1 GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section Door Hardware B. Section Plumbing Basic Materials and Methods C. Section Backflow Prevention D. Section Fire Alarm and Detection Systems E. Section Water Distribution System 1.02 SUMMARY COMMENTS A. All new construction of academic facilities shall be fully protected with sprinklers. B. All new and renovated residence hall facilities shall be fully protected with sprinklers. C. For all facilities that are currently not provided with sprinkler protection and are undergoing renovations, consideration must be given to providing sprinkler protection within impacted areas. Discussions with Cornell University Facilities Engineering (FE), Environmental Health & Safety (EH&S), and the Authority Having Jurisdiction (AHJ) shall dictate code compliance and scope of work CODES AND STANDARDS A. Design shall comply with the requirements of the latest recognized edition of the following codes and standards: 1. All applicable New York State Codes. 2. All applicable FM Global Standards. Please refer to FM s Data Sheets at for additional information. 3. All applicable NFPA Standards. 4. ANSI A-17.1, Safety Code for Elevators and Escalators. 5. Cornell University Cross Connection Control Program Manual. DATE: 12/8/17 DATE: 12/8/17 BASIC MATERIALS AND METHODS Page 1 of 12

2 B. In the event of an overlap or conflict between the requirements of the codes (NFPA & FM), laws, ordinances and this standard, negotiations involving FE, FM, the AHJ and Environmental Health & Safety (EH&S) shall bring resolution to the dispute. C. As part of the Contract Document production, the Engineer shall incorporate the following language in the drawing general notes or specifications: 1.04 DEFINITIONS Contractor shall provide copies of Shop Drawings and Hydraulic Calculations to the following for approval: 1. Ithaca Fire Department 2. Cornell Environmental Health and Safety 3. Cornell Fire Protection Engineer 4. FM Global Contractor shall not commence with construction until all parties listed above have given their approval. A. Authority Having Jurisdiction (AHJ): shall be defined at the inception of the project and has the potential to vary in conjunction with project location. Consult with the Cornell University Project Manager or Facilities Engineering to obtain the appropriate AHJ. B. EH&S Cornell University Environmental Health and Safety Fire Protection Section. EH&S provides acceptance and inspection of all fire protection and suppression systems. C. Contractor When referenced within Section , contractor shall refer to the firm responsible for preparation of hydraulic calculations and shop drawings, and for installation of fire protection system(s). D. Project Engineer The Professional Engineer (P.E.) of record who represents the Design/Engineering firm. E. Owner Cornell University and/or appointed representative shall be considered the Project Manager or Construction Manager as assigned. F. FM FM Global (formerly known as Factory Mutual) G. UL Underwriters Laboratories DATE: 12/8/17 DATE: 12/8/17 BASIC MATERIALS AND METHODS Page 2 of 12

3 1.05 DESIGN REQUIREMENTS A. General Requirements: 1. All fire protection systems shall be hydraulically calculated and designed by a fire protection engineer or qualified designer. 2. Design densities and demand areas shall be determined per either NFPA or FM requirements, whichever is more stringent. 3. Systems shall be designed such that the resulting available pressure is at least 10 PSI greater than the required demand pressure. 4. FM Global s demand area and sprinkler spacing requirements are more stringent than those of NFPA 13. Therefore, it is implicit that FM Global DOES NOT recognize NFPA s reduced demand area or small room rules. As such, reduced demand area and small room rules are not allowed for use in designing sprinkler systems on campus. Contract Documents need to explicitly state this. 5. Contract Documents need to explicitly state that all materials shall be UL-Listed AND FM-Approved. 6. Contract Documents need to explicitly state that all installation work shall comply with the FM Datasheets. 7. All fire protection systems shall be supervised by the building fire alarm system and Cornell University Central Station (Barton Hall). 8. All buildings equipped with fire sprinkler systems shall also have an exterior local alarm (electric bell) located in the same vicinity as the fire department connection (FDC) and post indicator valve (PIV), and initiated by the flow detection device. Water motor gongs shall not be used. 9. All drains shall discharge to sanitary where applicable. Verify capability of existing drains to accept full flow discharge. If connection to sanitary sewer is determined to be infeasible or cost prohibitive, alternatives like discharging water to grade (lawn areas, only) with splash blocks to prevent erosion may be considered with review and approval by Cornell University Environmental Health & Safety Fire Protection Section and Environmental Compliance. 10. The point of delineation between the water service main and the building fire protection service shall be at the Post Indicator Valve (PIV), with the valve considered part of the water service main. DATE: 12/8/17 DATE: 12/8/17 BASIC MATERIALS AND METHODS Page 3 of 12

4 11. Flushing full-port ball valves shall still be provided on underground mains (inside the building) and above-ground mains, cross-mains, branch lines and run outs of new sprinkler systems (wet and dry), to facilitate any future periodic internal inspections, obstruction investigations and as-needed flushing work. Valves shall be sized by the Engineer of Record and per NFPA 25, in order to obtain the NFPA required minimum velocity of 10ft/s for any given pipe size. As an alternative to the hydraulic calculation valve sizing method, the following sizing rules can be applied: 1-inch thru 2 ½-inch pipe: Line-size full-port ball valve 3-inch pipe: One (1) 2 ½-inch ball valve 4-inch pipe: Two (2) 2 ½-inch ball valves 6-inch pipe: Three (3) 2 ½-inch ball valves 8-inch pipe: Four (4) 2 ½-inch ball valves 12. In buildings not employing fire pumps, forward flow test headers shall be provided for the purpose of annual backflow preventer testing. The number of hose connections on the header will be based on a flow rate of 250GPM from each connection required to achieve 10ft/s in the underground main. Sizing the header for the flushing rate instead of for the system demand flow eliminates the need for flushing valves on the underground main. Engineer can refer to NFPA 25-14, Table D.5.1, Flushing Rates to Accomplish Flow of 10 ft/sec (3 m/sec), for flow rates based on pipe size. 13. Above-ceiling (concealed) type sprinkler zone control assemblies are not allowed. Installations shall be located in stairways, and shall be exposed or located in properly sized wall cabinets. Valves shall be located approximately 7-feet above finished floor. 14. Global Vision Inc. Zone Check flow switch assemblies (with a key-operated wall switch) are required for all zones. This device allows the annual inspections to be performed without the discharge of system water to drain. Said assemblies shall be exposed and at an elevation (approx. 7 above finished floor), that allows easy access for maintenance. The key-operated switch shall be installed 48 above finished floor. 15. Manual inspector s test and drain valves are also required for zones where Zone Checks are installed. 16. Per the City of Ithaca and Ithaca Fire Department, fully sprinkler-protected new and existing buildings shall be allowed to employ Manual Class I standpipe systems. As a result, a fire pump should not be required unless an unusually high sprinkler demand warrants the need. The Engineer shall perform due DATE: 12/8/17 DATE: 12/8/17 BASIC MATERIALS AND METHODS Page 4 of 12

5 diligence in designing the sprinkler system such that the sprinkler demand can be satisfied with the available water distribution system pressure. 17. The use of Pressure Reducing Valves in sprinkler and standpipe systems shall not be allowed. 18. All fire pump installations shall fully comply with NFPA 20 and shall include the following: a. An FM recommended Falk-type all-metal coupling between the pump and motor. Standard two-piece couplings with elastomeric spiders are not allowed. b. A venturi flow meter for around-the-pump flow testing. Flow meter shall not be installed in the pump test header piping. c. Main relief valves shall be pilot type (Cla-Val). Spring-type relief valves are not allowed. d. Relief valve discharge shall be directed to drain (see Item A.9, Section 1.05 for drain requirements). If relief valve cannot be discharged to drain, consult with Facilities Engineering for alternative solutions. B. System Design Considerations: 1. Wet-pipe systems are preferred and shall be the primary consideration for all applications. 2. New antifreeze systems are not allowed per NFPA 13. If an existing antifreeze system requires modification or extension, consideration shall be given to converting it to a water-based system. If that is not possible, employ glycerin at a concentration required by NFPA 13 to provide freeze protection for this geographical region. 3. Dry-pipe systems are also discouraged and shall only be used for incidental areas susceptible to freezing conditions, or to meet specific requirements of special-use facilities. The Engineer shall perform due diligence in preventing water from being trapped in dry-pipe systems. During the design phase and shop drawing phases, the Engineer shall look for obstructions to gravity drainage, and provide drum drips at all low points in dry-pipe systems. During construction, the engineer shall thoroughly inspect systems for potential water traps. DATE: 12/8/17 DATE: 12/8/17 BASIC MATERIALS AND METHODS Page 5 of 12

6 4. Perfluorooctanoic acid (PFOA-acid), ammonium perfluorooctanoate (PFOAsalt), perfluorooctane sulfonic acid (PFOS-acid), and perfluorooctane sulfonate (PFOS-salt) have been declared hazardous substances in New York State. The listing of these compounds may impact proposed fire-fighting foam systems that use these compounds and result in the need for additional infrastructure and ongoing management by Cornell in accordance with 6 NYCRR part 597. Proposed fire-fighting foam systems shall not utilize perfluorooctanoic acid (PFOA-acid), ammonium perfluorooctanoate (PFOA-salt), perfluorooctane sulfonic acid (PFOS-acid) or perfluorooctane sulfonate (PFOS-salt) without the written approval of the University Engineer. Consultant shall provide a written justification for usage of these perfluorinated compounds in any proposed firefighting foam systems with a detailed explanation of why alternatives are not viable for the intended application for the University Engineer s approval. 5. Nitrogen anti-corrosion treatment systems are required for certain wet-pipe and dry-pipe systems, depending on the application and/or environment. Please consult with Facilities Engineering for guidance on implementation of a nitrogen treatment system when designing a wet- or dry-pipe system. Air driers have been found to be ineffective, so they should not be applied in dry-pipe sprinkler systems. Chemical anti-corrosion treatment is also not allowed. C. Application Requirements: 1. Application requirements for the following areas: a. Elevator Machine Rooms and Shafts Flow switches may be specified as deemed appropriate by the engineer. Control valves shall be specified for shaft sprinklers. Design and installation shall be in accordance with ANSI A17.1. b. Transformer Rooms Double interlock preaction systems shall be provided. c. Information Technology Rooms Shall not contain wet piping. Wet sidewall heads are acceptable, although pre-action protection is preferred, if feasible. d. The sprinkler system shall be zoned per floor, or by multiple zones per floor (if required by FM & NFPA), in order to minimize building-wide impacts due to maintenance and impairments. e. All other zoning is at the discretion of the Engineer. DATE: 12/8/17 DATE: 12/8/17 BASIC MATERIALS AND METHODS Page 6 of 12

7 D. Existing Equipment: 1. The re-use and/or consolidation of existing equipment (in fire protection systems being modified or augmented) shall be evaluated in conjunction with Facilities Management, EH&S and Facilities Engineering at the commencement of schematic design. 2. All existing equipment or piping shall be inspected and tested for operational integrity and must be in compliance with current code prior to direction being given. PART 2 PRODUCTS 2.01 PREFERRED PRODUCTS A. Portable Fire Extinguishers: 1. Amerex Co. 2. Badger 3. General Fire Extinguisher Corp. B. Resilient Seat Gate Valves: 1. Kennedy Valve 2. Nibco Inc. 3. Mueller C. Butterfly and Ball Valves: 1. Central 2. Kennedy Valve 3. Nibco Inc. 4. Milwaukee 5. Victaulic 6. Watts D. Grooved Mechanical Couplings: 1. Gruvlok 2. Tyco-Grinnell 3. Victaulic DATE: 12/8/17 DATE: 12/8/17 BASIC MATERIALS AND METHODS Page 7 of 12

8 E. Sprinkler Heads: 1. Reliable 2. Victaulic 3. Viking Corp. F. Fire Protection Specialties: 1. Croker 2. Potter Roemer, Inc. 3. Guardian Fire Equipment, Inc. G. Fire System Backflow Preventers (RPZ): 1. Refer to Reduced Pressure Backflow Prevention Standard for acceptable devices. Detector assemblies are not allowed. H. Fire System Backflow Preventers (DCV): 1. Refer to Reduced Pressure Backflow Prevention Standard for acceptable devices. Detector assemblies are not allowed. I. Check Valves (must include a bolted access cover, for inspection purposes): 1. Mueller 2. Kennedy Valve 3. Viking Corp. J. Specialty Valves (Dry and Preaction): 1. Reliable 2. Viking Corp. K. Alarm Flow and Tamper: 1. Potter Electric Signal 2. System Sensor DATE: 12/8/17 DATE: 12/8/17 BASIC MATERIALS AND METHODS Page 8 of 12

9 L. Fire Department Connection (FDC); 5 STORZ, only: 1. Croker 2. Elkhart 3. Guardian 4. Potter Roemer, Inc. M. Post Indicator Valves: 1. Refer to Water Distribution System for acceptable manufacturers N. Hydrants 1. Refer to Water Distribution System for acceptable manufacturers O. Fire Pumps 2.02 PIPING 1. Allis-Chalmers 2. Aurora 3. Patterson 4. Peerless A. All piping and fittings shall be UL-listed and FM-Approved for fire protection service. B. All aboveground piping between the building service entrance and the backflow preventer shall be considered part of the municipal water distribution system. Therefore this piping and associated fittings shall be cement-lined ductile or copper. Galvanized and black steel pipe is not allowed. C. Schedule 10, Thin-Wall or any other piping with a wall thickness less than that of Schedule 40 piping is not allowed. D. All wet-pipe system piping shall be Schedule 40 black steel, Type F or Type S piping with cast or malleable-iron threaded or ductile iron grooved-end fittings. Type E is not allowed. E. All dry-pipe system piping shall be Schedule 40 black steel piping with cast or malleable-iron threaded or ductile iron grooved-end fittings. Grooved-end coupling gaskets employed shall be specific to dry-pipe systems. Type E and Galvanized piping are not allowed. DATE: 12/8/17 DATE: 12/8/17 BASIC MATERIALS AND METHODS Page 9 of 12

10 F. Copper tubing is acceptable and shall be used if the engineer identifies reasonable advantages. G. Chlorinated Poly Vinyl Chloride (CPVC) is acceptable for areas of light hazard and residential classification in accordance with all applicable codes. Use of this product requires prior written authorization from Cornell University EH&S and Facilities Engineering. H. Threaded fittings are preferred for exposed systems in aesthetically sensitive areas. I. The use of plain end fittings shall not be allowed VALVES A. Resilient seat OS&Y valves shall be used on the suction of fire pumps and as required for the installation of backflow preventers. B. All other control valves shall be ball or butterfly with electronic position indicating tamper switches. C. All valves shall be suitable for a minimum of 175 psi working pressure. In the event of the pressure exceeding 175 psi due to fire pump operation, 250 psi components shall be specified. D. All fire service mains shall be controlled by a PIV (post indicator valve) at the building service entrance. Please refer to Water Distribution for PIV specifics BACK FLOW PREVENTERS A. Regarding acceptable RPZs and DCVAs, please refer to Backflow Prevention for acceptable backflow preventer makes and models. Detector assemblies are not allowed FIRE DEPARTMENT HOSE VALVES AND CABINETS A. Hose valves shall NOT include a pressure restriction feature. B. All hose valves shall be 2 ½" NTS and positioned to readily accept a storz coupling. C. The engineer shall NOT specify or require fire hoses for hose cabinets in campus buildings. DATE: 12/8/17 DATE: 12/8/17 BASIC MATERIALS AND METHODS Page 10 of 12

11 D. Hose valves shall reside on the intermediate levels (between floors) of stairways. E. Hose valves shall be centered in cabinets to allow adequate clearance for gloved-hand operation FIRE DEPARTMENT CONNECTION (FDC) A. The AHJ shall dictate the type and style of FDC connection. Location shall be on the street-side of the building, preferably in the same location as the PIV. The FDC shall be easily accessible and visible. Consideration should also be given to snow removal procedures. B. FDC shall be located a minimum of 18" above grade. For installed heights above 18, a 22.5-degree elbow shall be provided EMERGENCY ACCESS LOCK BOXES (KNOX BOXES) A. The installation of Knox Boxes will be required when there are any revisions or modifications made to an existing fire alarm and or sprinkler system. See Cornell Design & Construction Standard Door Hardware. PART 3 EXECUTION 3.01 FIELD QUALITY CONTROL A. All testing shall be in accordance with specified procedures in the listed codes and standards. B. A representative of Environmental Health and Safety shall witness flushing of the underground main, hydrostatic and air testing of new sprinkler installations and alterations. The authority having jurisdiction (AHJ) requires that one of their representatives witnesses underground main hydrostatic testing and flushing, and sprinkler/standpipe hydrostatic testing of new installations that are within their jurisdiction. Advance notice and scheduling is required through EH&S. The Engineer shall include this information in the contract documents. C. New sprinkler systems shall not be treated for MIC. D. In existing systems that were previously chemically treated for MIC: After modifications or additions to existing systems have been applied, make-up water for said systems no longer needs to be chemically treated. DATE: 12/8/17 DATE: 12/8/17 BASIC MATERIALS AND METHODS Page 11 of 12

12 E. For all new sprinkler systems, underground piping requires hydrostatic testing and flushing (per the edition of NFPA 24 referenced in the current Building Code) before it can be connected to the new sprinkler system. The Engineer shall include this requirement in the Contract Documents, as well as the requirement for the contractor to flush per the minimum velocity as dictated in NFPA 24. The Engineer shall also include requirements for the appropriate number of 2 ½-inch valves applied during flushing, based on the size of the main (see item A.11, Section 1.05 for specifics). F. Pre-acceptance hydrostatic testing and flushing of new and existing aboveground sprinkler systems shall be performed per NFPA 13 (sprinklers) or NFPA 14 (standpipes). DATE: 12/8/17 DATE: 12/8/17 BASIC MATERIALS AND METHODS Page 12 of 12

A. This section includes design and performance information for fire protection and suppression systems.

A. This section includes design and performance information for fire protection and suppression systems. SECTION 21 00 10: FIRE PROTECTION SYSTEM DESIGN 1. SUMMARY A. This section includes design and performance information for fire protection and suppression systems. 2. GENERAL A. All fire protection materials

More information

SECTION : FIRE PROTECTION SYSTEMS

SECTION : FIRE PROTECTION SYSTEMS SECTION 21 00 10: FIRE PROTECTION SYSTEMS 1. GENERAL A. This section applies to the design and performance information for fire protection and suppression systems. B. All fire protection materials and

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES DIVISION 21 FIRE SUPPRESSION PART 1 GENERAL 1.01 DESCRIPTION A. Provide UL listed, FM approved listed fire protection specialties or accessories as required by either the equipment manufacturer or the

More information

Environmental Health & Safety

Environmental Health & Safety Environmental Health & Safety Oklahoma State University FIRE SPRINKLER SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu

More information

Gas Station & C Store SECTION CWM Job No

Gas Station & C Store SECTION CWM Job No SECTION 21 1300 - PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract

More information

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids. SECTION 211300 FIRE SUPPRESSION SYSTEMS 1.0 All new and renovated buildings shall be provided with automatic sprinklers throughout and fire standpipe systems. The design and installation of these systems

More information

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section PART 1 - GENERAL 1.00 GENERAL PROVISIONS A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section 1.01 DESCRIPTION OF WORK A. Work Included: Provide

More information

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5 DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

Port of St Helens SIA Aircraft Hanger Scappoose, OR

Port of St Helens SIA Aircraft Hanger Scappoose, OR Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

WET-PIPE SPRINKLER SYSTEMS

WET-PIPE SPRINKLER SYSTEMS SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

B. Related Sections: The following Sections contain requirements that relate to this Section.

B. Related Sections: The following Sections contain requirements that relate to this Section. SECTION 211313- FIRE-SUPPRESSION PIPING PART1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general prov1s1ons of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following: SECTION 21 10 00 - WATER-BASED FIRE-SUPPRESSION PART I - GENERAL 1.1 SUMMARY A. Inclusion of sprinkler and standpipe systems shall be as determined by NFPA National Fire Code pamphlet 101 and program statement.

More information

2. Welding Materials and Procedures shall conform to the ASME Code.

2. Welding Materials and Procedures shall conform to the ASME Code. PART 1 GENERAL 1.01 Scope of Standard A. The design guidelines contained herein include the requirements for systems, materials, fittings and valves utilized for fire protection systems at Sam Houston

More information

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses PART 1 - GENERAL 1.1 SCOPE A. Through Class III Commodity Classification, up to 12.2m of single, double or multiple row rack storage, up to 14.6m building height (VanQuish Fire Sprinkler System). Cartoned

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14 SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

ADDENDUM NO. 3 March 19, 2018

ADDENDUM NO. 3 March 19, 2018 ADDENDUM NO. 3 March 19, 2018 PROJECT: MT. VIEW ELEMENTARY CASSIA SCHOOL DISTRICT NO 151 BURLEY, IDAHO The following addenda apply to the Project Manual and / or Drawings for this project and shall be

More information

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements. FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment

More information

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University. 15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.

More information

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13. 21 10 00 PART 1 - GENERAL 1.01 SCOPE A. The following standards and procedures apply to the design and installation of all wet pipe and dry pipe sprinkler systems. The design of fire suppression systems

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 13900 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain

More information

Western Michigan University Facilities Management Engineering Division

Western Michigan University Facilities Management Engineering Division Western Michigan University Facilities Management Engineering Division Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG21-1 Fire Suppression Systems & Equipment I. GENERAL... 1 A. General

More information

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum.

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum. Page 211200-1 SECTION 211200 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21 Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21 SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A.

More information

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.

More information

North Hanover Township School District North Hanover Township, New Jersey

North Hanover Township School District North Hanover Township, New Jersey SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

CONSTRUCTION REQUIREMENTS

CONSTRUCTION REQUIREMENTS CONSTRUCTION REQUIREMENTS Note: The buildings on the UCCS campus are divided into two categories: General Fund and Auxiliaries. General Fund Buildings include academic and administrative functions. Auxiliary

More information

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION DIVISION 21 FIRE SUPPRESSION 21 00 00 FIRE SUPRESSION 21 01 00 Operation and Maintenance of Fire Suppression 21 01 10 Operation and Maintenance of Water Based Fire Suppression Systems 21 01 20 Operation

More information

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8 City of Ottawa Project No. CR006230 Page 1 of 8 PART 1 - GENERAL 1.1 Reference Standards.1 Conform to the following:.1 Provincial and municipal building and fire regulations as approved by Provincial Fire

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION FIRE-SUPPRESSION SYSTEMS

SECTION FIRE-SUPPRESSION SYSTEMS SECTION 13900 FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Automatic wet-type, Class I, fire-suppression standpipes and branches for sprinklers. 2. Wet-pipe, fire-suppression

More information

SECTION WATER BASED FIRE SUPPRESSION SYSTEMS

SECTION WATER BASED FIRE SUPPRESSION SYSTEMS PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University-San Marcos for automatic fire sprinkler and standpipe systems.

More information

CITY OF PASADENA FIRE DEPARTMENT

CITY OF PASADENA FIRE DEPARTMENT Page 1 of 8 CITY OF PASADENA FIRE DEPARTMENT INSTALLATION OF COMMERCIAL SPRINKLERS (Revised 12/10/2014) SCOPE: This standard applies to the design and installation of automatic fire sprinkler systems in

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES SECTION 21 30 00 FIRE PUMPS GENERAL This standard provides general requirements of The University of South Alabama in Mobile Alabama for fire pumps. This document is not intended to serve as a guide specification.

More information

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION FIRE-SUPPRESSION STANDPIPES PART 1 - GENERAL 1.1 DESCRIPTION Fire-suppression wet and manual dry standpipes. 1.2 SCOPE OF WORK SECTION 21 12 00 A. Design, installation and testing shall be in accordance with NFPA 14 except for specified

More information

SECTION FIRE PROTECTION

SECTION FIRE PROTECTION SECTION 15300 - FIRE PROTECTION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure. SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES SECTION 21 13 00 - FIRE SUPRESSION SPRINKLER SYSTEMS SCOPE OF WORK This standard provides general guidance concerning the specific preferences of The University of South Alabama for automatic fire sprinkler

More information

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following: PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe

More information

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS DIVISION 21 - FIRE SUPPRESSION Includes the following sections: None DESIGN REQUIREMENTS It is the policy of City of Santa Cruz to install fire sprinkler systems in all new construction/facilities. If

More information

DIVISION 21 FIRE SUPPRESSION

DIVISION 21 FIRE SUPPRESSION Table of Contents 21 00 00 FIRE SUPPRESSION...2 A. REFERENCE ABBREVIATIONS... 2 B. GENERAL... 2 C. DESIGN REQUIREMENTS... 2 D. DOCUMENTATION... 2 21 08 00 FIRE SUPPRESSION COMMISSIONING...2 A. PIPE CLEANING...

More information

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES SECTION 15300 FIRE PROTECTION PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. Dartmouth College is currently insured by Factory Mutual. References to the owner s insurance company in this specification

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS PART 1 GENERAL 1.01 SCOPE OF WORK SECTION 21 13 13 FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS A. Furnish all labor, materials, equipment services and incidentals required to design and install properly

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with

More information

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN DIVISION 21 - FIRE SUPPRESSION (REFER TO SECTION 23 05 00 FOR BASIC FIRE SUPPRESSION REQUIREMENTS) 21 05 00 Common Work Results for Fire Suppression 21 13 13 Wet-Pipe Sprinkler Systems END OF SECTION FIRE

More information

SECTION WET FIRE SPRINKLER SYSTEMS

SECTION WET FIRE SPRINKLER SYSTEMS SUNY GENESEO 211310-1 PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in

More information

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION SECTION 21 1301- FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY: A. This Section includes fire-suppression piping and equipment for the following building systems: 1. Wet-pipe, fire-suppression

More information

Backflow Prevention for Fire Sprinkler Systems. State of Illinois Plumbing Code

Backflow Prevention for Fire Sprinkler Systems. State of Illinois Plumbing Code Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code Backflow Prevention Fire safety systems connected to a public water supply will require a backflow prevention device between

More information

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS SECTION 13930 WET-PIPE FIRE-SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install complete wet-pipe fire sprinkler system in new addition only as specified

More information

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

Course FP100 BACKFLOW PREVENTERS (BFPs) 101 FOR AUTOMATIC FIRE SPRINKLER SYSTEM M. Nabeel Waseem, M.Eng, PE, CFPS 2018

Course FP100 BACKFLOW PREVENTERS (BFPs) 101 FOR AUTOMATIC FIRE SPRINKLER SYSTEM M. Nabeel Waseem, M.Eng, PE, CFPS 2018 Course FP100 BACKFLOW PREVENTERS (BFPs) 101 FOR AUTOMATIC FIRE SPRINKLER SYSTEM M. Nabeel Waseem, M.Eng, PE, CFPS 2018 1 Introduction If you have ever been exposed to automatic fire sprinkler system, there

More information

SECTION AUTOMATIC SPRINKLER PIPING

SECTION AUTOMATIC SPRINKLER PIPING SECTION 15330 AUTOMATIC SPRINKLER PIPING ****** ***** **** *** ** * ** *** **** ***** ****** NOTE TO SPECIFIER: This section contains several types of automatic sprinkler piping. Some piping is allowed

More information

SPRINKLERS TABLE OF CONTENTS

SPRINKLERS TABLE OF CONTENTS SPRINKLERS TABLE OF CONTENTS SECTION 21 13 13 WET PIPE SPRINKLER SYSTEMS SECTION 211313 - WET PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS DIVISION 21: FIRE SUPPRESSION 21 1000 WATER BASED FIRE SUPRESSION SYSTEMS 21 1200 FIRE-SUPPRESSION DRY STANDPIPES 21 1313 WET PIPE SPRINKLER PROTECTION SYSTEM 21 1314 WET-PIPE AUTOMATIC SPRINKLER SYSTEM

More information

A. This Section includes the following fire-suppression piping inside the building:

A. This Section includes the following fire-suppression piping inside the building: SECTION 211000 - WATER-BASED FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following fire-suppression piping inside the building: 1. Automatic wet-type, standpipe systems.

More information

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals 1 General 1.1 Provide all material, labor, engineering and operations for the installation of complete and operable fire suppression systems as shown in the job scope and as specified herein. 1.2 Provide

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS Ul611-0l SECTION 211316- DRY-PIPE SPRINKLER SYSTEMS PARTl-GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions, and Division 1 Specification

More information

Water Purveyor s Guide to 2006 Fire Sprinklers in Single Family Dwellings

Water Purveyor s Guide to 2006 Fire Sprinklers in Single Family Dwellings Water Purveyor s Guide to 2006 Fire Sprinklers in Single Family Dwellings Fire sprinklers have long been used in commercial buildings and large residential occupancies to provide economical life safety

More information

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

A. Section includes wet-pipe sprinkler system, system design, installation, and certification. SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes wet-pipe sprinkler system, system design, installation, and certification. 1.2 REFERENCES A. General: Comply

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

SECTION PREACTION SPRINKLER SYSTEMS

SECTION PREACTION SPRINKLER SYSTEMS PART 1 GENERAL SECTION 211316 - PREACTION SPRINKLER SYSTEMS 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION Fire Pumps

SECTION Fire Pumps SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.

More information

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed.

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed. Page 1 of 10 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK504 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED

More information

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,

More information

DESIGN & CONSTRUCTION GUIDELINES

DESIGN & CONSTRUCTION GUIDELINES ADMINISTRATIVE SERVICES 4202 E. FOWLER AVENUE, FPC110 PHONE: (813) 974-2625 FACILITIES PLANNING & CONSTRUCTION TAMPA, FLORIDA 33620-7550 WEBSITE: USF.EDU/FPC DESIGN & CONSTRUCTION GUIDELINES DIVISION 21

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements. SECTION 21 13 13 FIRE PROTECTION SPRINKLER SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section includes labor and materials for the installation of a hydraulically calculated automatic, wet-pipe sprinkler

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

SECTION FIRE-SUPPRESSION PIPING

SECTION FIRE-SUPPRESSION PIPING SECTION 211313 FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Reprinted with permission from NFPA 13D Installation of Sprinkler Systems in One- and two-family Dwellings and Manufactured

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION STANDPIPE AND FIRE SPRINKLER STANDARDS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION STANDPIPE AND FIRE SPRINKLER STANDARDS PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES: A. This design build specification shall not be modified, amended, or altered. B. The Architect and/or Engineer shall clearly define the scope of

More information

esfr dry pendent sprinkler Vk502 (k14.0)

esfr dry pendent sprinkler Vk502 (k14.0) Page 1 of 11 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

esfr dry pendent sprinkler Vk501 (k14.0)

esfr dry pendent sprinkler Vk501 (k14.0) September 13, 2012 Sprinkler 122a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK501 is a fast response fusible element type sprinkler designed for use in storage

More information

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS SECTION 13935 DRY-PIPE FIRE-SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install complete fire sprinkler system as specified in Contract Documents. B.

More information

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6 Page 1 of 6 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 20 00 05 Mechanical - General Requirements.2 Section 22 05 00 Plumbing - General Requirements.3 UBC Standard Fire Hydrant Drawings.4 Section

More information

DIVISION 21 FIRE SUPPRESSION

DIVISION 21 FIRE SUPPRESSION DIVISION 21 FIRE SUPPRESSION Table of Contents 21 00 01 General 21 00 02 Scope 21 00 03 Codes 21 00 04 Design Intent Report 21 00 05 Coordination with University of Minnesota Departments 21 00 06 Access

More information

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Inspection of Fire Sprinkler Systems NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Objective To familiarize Facility Managers with the process of routine inspection

More information

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why

More information

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 1314D - AUTOMATIC SPRINKLER SYSTEMS (DRY-PIPE) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1 TO CONTRACT DOCUMENTS ENTITLED: PROJECT MANUAL FOR: Women s and Children s Hospital New Water Service Main PROJECT NUMBER: CP172631 ADVERTISEMENT DATE: July

More information

City of Vista Fire Department

City of Vista Fire Department City of Vista Fire Department Development Services Section 600 Eucalyptus Avenue, Vista CA 92084 Guideline: Underground Piping for Private Fire Hydrants & Fire Sprinkler Supply. Updated: January, 2008

More information

MODULE 2. Water-Based Suppression System Basics

MODULE 2. Water-Based Suppression System Basics MODULE 2 Water-Based Suppression System Basics Based on the Ohio Building Code (OBC) National Fire Protection Association (NFPA) & Ohio Fire Code (OFC) 1 WATER-BASED SUPPRESSION SYSTEM BASICS-PART ONE

More information