2017 NEC: Impact to Electrical System Designs
|
|
- Linda Dickerson
- 6 years ago
- Views:
Transcription
1 2017 NEC: Impact to Electrical System Designs We will begin shortly. Turn up your speakers in order to hear the hold music. Feel free to ask questions now in the Q&A widget!
2 Today s broadcast is sponsored by: Innovation at Every Level Expert-To-Expert Education Series Schneider Electric TM has been approved as an Authorized Provider by the International Association for Continuing Education and Training (IACET), 1760 Old Meadow Road, Suite 500, McLean, VA 22102; Schneider Electric - Codes and Standards NEC Changes (c) January 2017
3 How to use this Broadcast Desktop Access Consulting engineer portal and download slides and files Type in questions during the webinar For technical support regarding viewing this webinar Controls your viewing of the slides Complete the participant survey Request to be contacted
4 Moderator: Wendell Leisinger Consulting Engineer Segment Manager, Schneider Electric Over 30 years of experience with Schneider Electric and the construction industry Thought leader on Building Information Modeling Member of IEEE, CSI, AEE, and NEMA High Performance Buildings
5 2017 NEC: Impact to Electrical System Designs
6 FOR THOSE WHOM HAVE ALREADY REGISTERED FOR THE PORTAL Make sure to print your PDH Certificate 12 hours after this webinar There s now a quicker and easier way to print your certificate. FOR THOSE WHOM HAVE NOT ALREADY REGISTERED FOR THE PORTAL Please go to: to register for the portal. There is also a link to the portal on your broadcast dashboard You will then be able to print your certificate 48 hours after registering for the portal If you have any difficulties, please PartnerPortalSupportUS@schneider-electric.com
7 Upon completion of this presentation, you should be able to: Learning Objectives: Recognize the most pertinent changes to the code and the impact on your projects Recognize the new requirements and potential impact of engineering designs Understand the spirit of the Code versus the letter of the Code
8 LIVE IN CHICAGO Aamir Paul Senior Vice President, US Business Operations Schneider Electric
9 Speaker: Alan Manche, P.E. VP, External Affairs, Schneider Electric Member NEC Correlating Committee & NEC CMP 2 & 10 Member of Technical Committee NFPA 110, 70B, and 73 Past Chair of NFPA 70B Board of Directors Western Section IAEI Board of Directors Electric Safety Foundation International (ESFi) Member, Common Wealth of Kentucky Electrical Advisory Committee Member, NEMA Codes and Standards Chair, NEMA Code Adoption Initiative Chair, NEMA Water and Fire Damaged Equipment Committee
10 Speaker: Chad Kennedy, P.E. Manager, Industry Standards, Schneider Electric Member NEC CMP 13 Member of ELS, NFPA 99 Member of NFPA 3, 4 Testing and Commissioning Member of UL, NEMA, & IEEE Technical Committees for Transformers, Panelboards, Switchboards, Switches, Switchgear, Energy Storage, Distribution Automation (Microgrid) Member of NFPA & NFPA Electrical Section IAEI Member Chair, NEMA Sharp Edges Task Force Chair, NEMA LVDE02 Panelboards and Switchboards
11 Speaker: Jim Degnan, P.E., LEED AP Principal at Stantec 40 years of experience in electrical systems design Licensed professional engineer in 11 states. Active member of the American Society of Healthcare Engineers, the Institute of Electrical and Electronics Engineers, and the Illuminating Engineers Society. Supports several associations and governments with code development, including the National Fire Protection Agency (member NFPA 70 Code Making Panel 13), the Washington State Energy Code, and the City of Seattle Electrical Code.
12 110.16(B) Arc Flash Hazard Marking Applies to service equipment rated 1200 A or more (other than dwelling units) Must Mark Nominal System Voltage Available Fault Current Clearing time of overcurrent protective device(s) based on available fault current Date applied Exception Service equipment labeling shall not be required if an arc flash label is applied in accordance with acceptable industry practice
13 Arc Energy Reduction Fuses (Effective 1/1/20) Fuses rated 1200 A or higher Clearing time of 0.07s or less at the available arcing current or a reduction method must be supplied Methods to reduce clearing time shall be one of the following: Differential relaying Energy reducing maintenance switch with local indicator Energy reducing active arc flash mitigation system An approved equivalent means Schneider Electric - Codes and Standards 2017 NEC Changes January 2017 This requirement is similar to that for circuit breakers in
14 Arc Energy Reduction Added arc energy reduction methods for Circuit Breakers: An instantaneous trip setting that is less than the available arcing current An instantaneous override that is less than the available arcing current Unlike existing methods, these methods have performance consideration requiring the calculation of the available arcing fault.
15 210.8(B) Other than Dwellings (GFCI) Applies to receptacle outlets 150 V to ground or less Single phase receptacles expanded from 20 A to 50 A Added 3 phase up to 100 A Added crawl spaces and unfinished portions of basements not intended as habitable rooms
16 Exceptions Lighting Loads for Specified Occupancies Allows lighting loads to be calculated using the adopted energy code where designed and constructed to comply and meets the following: Power monitoring system installed to provide lighting load data and must have alarm(s) to alert the building owner/manager if the lighting load exceeds limits Demand factors in do not apply New Exception expands this allowance where an energy code is adopted and that energy code specifies an overall lighting density of less than 1.2 volt-amperes/1.2 ft 2. It permits the unit lighting loads in Table for office and bank areas within the building to be reduced by 1 volt-amperes/1 ft 2
17 Questions?
18 230.95(C) Performance Testing. (GFPE) Applies to all GFPE provided at the service equipment Test after installation in accordance with the instructions provided with the equipment. Now Requires primary current injection testing Written test record available for AHJ Also impacts Feeders in CK
19 312.8(B) Power Monitoring Equipment Permits the installation of power monitoring equipment in the wiring space where Field installable accessory or listed kit for switch or overcurrent device enclosures and The total area of all conductors, splices, taps, and equipment at any cross section of the wiring space does not exceed 75% of the crosssectional area of that space
20 and Short Circuit Current Rating Marking & Documentation Industrial control panels required to be marked with a short-circuit current rating Documentation must provide the available short-circuit current Date of calculation Available to those authorized to inspect the installation Elevator Control Panels Marked with SCCR based on Listed assembly Approved method UL 508A, Supplement SB
21 Questions?
22 700.3(F) Temporary Source of Power for Maintenance or Repair of the Alternate Source of Power Applies to installations with a single alternate power source Requires a permanent switching means to connect a temporary source Recognizes need for maintenance & repair activities Schneider Electric - Codes and Standards 2017 NEC Changes January 2017
23 620.51(E) Surge Protection Applies to elevators, dumbwaiters, escalators, moving walks, platform & stairway chairlifts supplied by the building emergency system Aligns with the requirements in Article 700 to protect the emergency system from surges Schneider Electric - Codes and Standards 2017 NEC Changes January 2017
24 Surge Protection for Critical Operations Data Systems Recognizes the importance of protecting the electrical infrastructure from surges Location(s) is not specified. Surge protection requires surge protective devices at multiple levels within the system. Location of the devices is based on the system design. Schneider Electric - Codes and Standards 2017 NEC Changes January 2017
25 408.3(A)(2) Service Panelboards Barrier for line side terminations, bus, and exposed energized parts Revision aligns with existing requirements for switchboards and switchgear Single main panelboard configurations Electrical shock protection only, no arc flash energy protection
26 705.12(B)(2)(3)(d) Interconnected Electric Power Sources Center-fed panelboards Dwellings only Bus bar rating for load side connections Permits use of the 120% rule where the connection is at either end of the panel but not both Schneider Electric - Codes and Standards 2017 NEC Changes January 2017
27 Questions?
28 Appendix
29 Retrieving your PDH Certificate from the Portal - Layout tools - BIM models and apps - Calculators, and product specifications - PDH and CEU Continuing Education modules - Latest in products and solutions to give your designs an edge - Access to expertise when questions arise We invite you to register or login today! schneider-electric.us/e2e
30 Retrieving your PDH Certificate from the Portal Step 1: Click on Print Your PDH Step 2: Click on Active dropdown button and change to Completed Step 3: Click on View Certificate
31
ANSI/NETA Standards Update
Specifications and Standards Activity ANSI/NETA Standards Update NOW AVAILABALE!!!! NETA Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems The NETA Acceptance Testing
More information2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100
Significant Changes to the NFPA 70E Standard 2012 Edition Tech Topics: Standards & Codes Note 4, Issue 1 Peter Walsh, PE Sr. Field Engineer Points of Interest: Arc-Rated (AR) vs. Flame-Resistant (FR) Training
More informationElectrical Safety Compliance: NFPA 70E
Electrical Safety Compliance: NFPA 70E From Graybar and Schneider Electric Risks associated with shock and electrocution from inadvertent contact with energized parts have long been recognized as a threat
More informationEFCOG Best Practice #213
EFCOG Best Practice #13 Facility: DOE Complex Best Practice Title: Adoption of NFPA 70 017 in place of NFPA 70 014 Point of Contact: Michael Hicks NE-ID, 08-56-374, hicksmd@id.doe.gov John McAlhaney SRS,
More informationAPPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL
This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC
More informationInformational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017
Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 It has come to the attention of the electrical authorities having jurisdiction (AHJs) at the DOE sites there is inconsistency
More informationInstructor: L. Keith Lofland
One and Two Family Dwelling Electrical Systems 2014 NEC AFCIs, GFCIs, and Other Dwelling Unit Requirements Training Presentation by: International Association of Electrical Inspectors Instructor: L. Keith
More informationPANELBOARDS & BUILDING DISTRIBUTION
262416 PANELBOARDS & BUILDING DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Distribution panelboards 2. Power panelboards B. Related Sections: 1.02 POLICY 1. CU Standard 260500, Basic
More informationOverview of Significant 2017 NEC Changes
Overview of Significant 2017 NEC Changes National Fire Protection Association. All rights reserved. Five New NEC Articles Article 426 Fixed Resistance and Electrode Industrial Heating Equipment Article
More informationNATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY
A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -
More informationControl Circuits in acc. with UL508A
Control Circuits in acc. with UL508A UL guideline, chapter 4.3 Definition of Control Circuits Disconnecting Means Protection of Control Circuits Dimensioning of the wires and cables Loads in the Control
More informationArc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702
Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702 by Reza Tajali, Schneider Electric Engineering Services Summary 1.0 Abstract 2.0 OSHA and NFPA Rules 3.0 Use of NFPA 70E
More informationGuide to Compliance with the Electrical Workplace Safety Standards in the United States
Guide to Compliance with the Electrical Workplace Safety Standards in the United States July 2011/1910DB1102 by Joseph H. Weigel, Product Manager Schneider Electric USA, Inc. Make the most of your energy
More informationUnderstanding NFPA, NEC 2005 Article 409 a White Paper by Paul A. Terry, P.E.
a White Paper by Paul A. Terry, P.E. NFPA 70, NEC 2005: Article 409 Industrial Control Panel Short Circuit Panel Ratings Executive Summary Many panel shops are providing industrial control panels with
More informationNEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015
NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized
More informationAFCI. RECEPTACLEFAQs. What is an arc fault? What causes arc faults?
RECEPTACLEFAQs AFCI 1 What is an arc fault? UL provides a definition for an arc fault in UL 1699 (Standard for Safety Arc Fault Circuit Interrupters). It is an unintentional arcing condition in a circuit.
More informationWIRING AND PROTECTION
5997ch02.qxd_mg_cc 4/6/05 12:42 PM Page 5 2 WIRING AND PROTECTION (Excerpts from Chapter 2) 210.1 Scope ARTICLE 210 BRANCH CIRCUITS I. General Provisions Article 210 applies to all branch circuits except
More informationNFPA Edition Review
This is a photographic template your photograph should fit precisely within this rectangle. NFPA 70 & 99 How Recent Code Changes Effect Healthcare Facilities Sam C. Terry, P.E. Application Engineer Eaton
More informationtechnology using advanced to reduce electrical fires arc fault circuit interrupters
arc fault circuit interrupters using advanced technology to reduce electrical fires NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION Low Voltage Distribution Equipment Section I NTRODUCTION Arc Fault Circuit
More informationElectrical Inspection Service & Distribution
0911 Distribution Panels & Switchgear Equipment, conduit, feeders, and grounding 480 Volt Switchboard: This switchboard contains the utility meter and two main, service, circuit breakers. One circuit breaker
More informationASSESSING THE HIDDEN DANGERS IN YOUR INDUSTRIAL CONTROL PANELS
Schneider Electric NEC 409.2 January 15, 2008 ASSESSING THE HIDDEN DANGERS IN YOUR INDUSTRIAL CONTROL PANELS by Grant Van Hemert, P.E., application engineer, Water and Wastewater Competency Center, Schneider
More informationPhotovoltaic (Solar) Array Installation Guide
Building & Safety Division Community Development Department 7351 Rosanna Street, Gilroy, CA 95020 Phone: 408 846-0451 Fax: 408 846-0429 Visit us: www.cityofgilroy.org Photovoltaic (Solar) Array Installation
More informationA. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationBrown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA
PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities
More informationPART GENERAL 1.01 SECTION INCLUDES
Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,
More informationCurrentGuard TM. Installation, Operation and Maintenance Manual. CurrentGuardTM. Flush Mount. Surge Protective Devices A00
TM CGFS u r g e P R O T E C T I O N CurrentGuardTM Installation, Operation and Maintenance Manual 750-0098-006 A00 Surge Protective Devices CurrentGuard TM Flush Mount Table of Contents Guide to Installation
More informationCITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST
CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST Plan Check No. Plan Check Expiration Date Job Address: Square Footage Use Zone Fire Zone Occ. Group Type of Construction No. of Stories Applicant Phone
More informationGPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators
GPS 140 NEC Requirements for Generators WHAT YOU WILL LEARN NEC requirements for on-site power generation. Recent events have created increased interest in standby power This module organizes NEC requirements
More informationELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING
SEMINAR 301 Part 1: Changes in the 2005 NEC SEMINAR RULES: There are no Rules All Questions need to be asked Stop at any time for an explanation SEMINAR PARTS: ELECTRIC and NEON SIGN STANDARDS By Randy
More informationStudent Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationINSTALLATION, OPERATION AND MAINTENANCE MANUAL
GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Integrally Mounted Medium and High Exposure Surge Protective Devices
More informationSecond Revision No. 321 NFPA [ Detail ] Submitter Information Verification. Committee Statement. Make the following changes to 210.
Second Revision No. 321 NFPA 70 2015 [ Detail ] Make the following changes to 210.8(B): (B) Other Than Dwelling Units. All 125 volt, single phase, 15 and 20 ampere receptacles phase receptacles rated 150
More informationHESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove
HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove Jim Dungar, P.E. Principal Engineer Schneider Electric Engineering Services Jim.dungar@schneider-electric.com (920-766-8012)
More informationSafety requirements for voltage testing instruments
MODEL POLICY Safety requirements for voltage testing instruments 1. FOREWORD 1.1. Approval 1.1.1. This standard is owned by. name of promulgating organization or department 1.1.2. Questions related to
More informationChanges to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC
Changes to NFPA 70E - The Role of PdM &Safe PdM Work Practices Tim Rohrer Exiscan LLC Tim@Exiscan.com 585-705-7775 Joe Gierlach ABM Joseph.Gierlach@ABM.com 412-394-4678 Preview Electrical Safety Risk Management
More informationTOM BURNS, PLANNING DIRECTOR
~~ 0 173 COUNTY OF SANTA CRUZ August 4,2005 PLANNING DEPARTMENT 701 OCEAN STREET, qth FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 TOM BURNS, PLANNING DIRECTOR Agenda:
More informationArc-Fault Circuit Interrupters (AFCIs) and Ground-Fault Circuit Interrupters (GFCIs)
NECA 169-2010 Standard for Arc-Fault Circuit Interrupters (AFCIs) and Ground-Fault Circuit Interrupters (GFCIs) An American national Standard Published by National Electrical Contractors Association NECA
More informationWHITE PAPER: ARC FAULT CIRCUIT INTERRUPTERS EXPANDING HOME SAFETY
WHITE PAPER: ARC FAULT CIRCUIT INTERRUPTERS EXPANDING HOME SAFETY Expanding Home Safety Page 2 INTRODUCTION Smoke alarms, fire extinguishers, emergency escape ladders these are all proven methods for making
More informationConstruction Codes Advisory Council
Construction Codes Advisory Council An overview of the National Electrical Code (NEC) adoption process This is where it all begins.. Minnesota Statute Chapter 326B establishes the State Building Code Minnesota
More informationNECA 169. Standard for Installing and Maintaining Arc-Fault Circuit Interrupters (AFCIs) and Ground-Fault Circuit Interrupters (GFCIs)
NECA 169 Standard for Installing and Maintaining Arc-Fault Circuit Interrupters (AFCIs) and Ground-Fault Circuit Interrupters (GFCIs) Industry Review Draft (Date TBD) National Electrical Installation Standards,
More informationNFPA 70E Standard for Electrical Safety in the Workplace. EEI Safety and Health Meeting May 2011
NFPA 70E Standard for Electrical Safety in the Workplace EEI Safety and Health Meeting May 2011 NFPA Structure NFPA 70E Technical Committee reports to: NEC Technical Correlating Committee reports to: NFPA
More informationVACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES
Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete
More informationIntroduction Consultant shall incorporate the material in the DSS into the project specifications.
DIVISION 16 - ELECTRICAL Section 16000 - General Discussion Introduction Consultant shall incorporate the material in the DSS into the project specifications. Refer any questions, clarifications regarding
More informationRESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS
RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS Key Questions for Residential Inspections 1. What wiring methods will be used, and are the wiring methods suitable for the conditions? 2. Will multiwire branch
More informationTABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51
TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...
More informationRevisions for the 2014 National Electrical Code
PDH Course E428 Revisions for the 2014 National Electrical Code Part 1 Patrick S. Ouillette, P.E. 2014 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org
More informationCONTINUING EDUCATION FOR OREGON ELECTRICIANS. AMERICAN ELECTRICAL INSTITUTE PO Box Spokane, WA
American Electrical Institute 2014 PART 2 83 CONTINUING EDUCATION FOR OREGON ELECTRICIANS AMERICAN ELECTRICAL INSTITUTE PO Box 31131 Spokane, WA 99223 www.aeitraining.com 84 PART 3 American Electrical
More informationArc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance
Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance An arc flash can cause serious injury or death to anyone in its path. The National Electrical Code provides
More informationTABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19
TABLE OF CONTENTS About This Textbook...xiii How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...
More informationElement D Services Electrical
PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as a Specification.
More informationElectrical Hazards and NFPA-70E: Protecting Your Employees
Electrical Hazards and NFPA-70E: Protecting Your Employees Presented By Mark B. Haskins, MS, CSP Practical Safety Solutions, LLC At the CBIA Safety Health and Wellness Conference May 22, 2014 PRESENTATION
More informationWHITE PAPER: THE IMPORTANCE OF ARC FAULT CIRCUIT INTERRUPTER TECHNOLOGY
WHITE PAPER: THE IMPORTANCE OF ARC FAULT CIRCUIT INTERRUPTER TECHNOLOGY 1 Introduction Thousands of deaths and billions of dollars in property loss occur every year due to residential structure fires.
More informationIMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016
IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS June 17th, 2016 RE: City Council Adopts 2014 National Electrical Code with Pool Alarm Requirements On April 25th, 2016 the
More informationTABLE 1-E (2017) Effective July 1, 2017
TABLE 1-E (2017) Effective July 1, 2017 Oregon Amendments to the 2017edition of the National Fire Protection Association (NFPA) 70, National Electrical Code (NEC) for the 2017 Oregon Electrical Specialty
More informationStandards and Safety Update
Standards and Safety Update Presented By: Michael J. Johnston Executive Director Standards and Safety, NECA Update Objectives Update on NFPA 70E and NECA Safety products Update on NECA S National Electrical
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 2 FROM: Kimberly Shea, Administrator,
More informationSECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES
PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,
More informationJoint CCFS/APPA Webinar Series. Low-Frequency Sounders and NFPA 72
Joint CCFS/APPA Webinar Series Low-Frequency Sounders and NFPA 72 Presented by Rodger Reiswig Vice President, Industry Relations Johnson Controls The Center for Campus Fire Safety and the APPA logos are
More informationWhy Selective Coordination is Mandatory -- It Fills the Reliability Hole --
Why Selective Coordination is Mandatory -- It Fills the Reliability Hole -- The NEC has mandatory selective coordination requirements for the following systems. Emergency Systems- Article 700 700.27 Legally
More informationSECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS
SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Nameplates and labels B. Wire and cable markers C. Conduit markers 1.2 REFERENCES A. NFPA 70 - National Electrical
More informationPGR-8800 TECHNICAL FAQ
PGR-8800 SOLAR ARC-FLASH PRODUCTS RELAY CATALOG TECHNICAL FAQ What are the typical applications / system voltages? The PGR-8800 can be used on electrical systems operating at any voltage (AC or DC) since
More information9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.
Chapter 1 GROUNDING AND BONDING 1 Proper grounding practices protect people from the hazards of electric shock and ensure the correct operation of overcurrent protection devices. Grounding is the intentional
More informationORDINANCE NO
ORDINANCE NO. 2017-08-031 AN ORDINANCE OF THE CITY OF LANCASTER, TEXAS, REPEALING THE NATIONAL ELECTRICAL CODE 2014 EDITION IN ITS ENTIRETY AND REPLACING IT WITH THE ADOPTION OF THE NATIONAL ELECTRICAL
More informationNEC 2017 Changes and Their Effect Upon the ICT Industry
NEC 2017 Changes and Their Effect Upon the ICT Industry Today s Presenters John Kacperski, RCDD, OSP, CDT Chair of BICSI Standards BICSI Representative on NFPA 70-CMP 16 Richard S. Anderson, RCDD, CDT,
More informationUltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW
12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes
More informationSDEC 2017 Questions, Group 1
SDEC 2017 Questions, Group 1 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing? Answer: NEC 410.36(B)
More informationCHAPTER 20 SERVICE EQUIPMENT
SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control
More information2014 National Electrical Code & NFPA 70E/Arc Flash
Gain an understanding of the 2014 NEC s latest additions, revisions and changes. Learn the precautions needed when working with and around electricity. People and property need to be safeguarded from the
More informationGROUND FAULT PROTECTION METHODS & 2017 National Electric Code
GROUND FAULT PROTECTION METHODS 2014 & 2017 National Electric Code Ground Fault Protection Methods A Ground Fault Circuit Interrupter, or GFCI, is a device that functions to de-energize a circuit when
More information2017 NEC Presented by: Russ LeBlanc
2017 NEC Presented by: Russ LeBlanc 1. 90.2(A)-installation and removal 2. 90.3-code layout 3. 100-readily accessible 4. 100-field evaluation body (FEB) 5. 100-field labeled 6. 100-receptacle 7. 100-structure
More informationImplementing an Energized Electrical Work Program. SESHA Hill Country Chapter. Brett Jay Davis, PE Zephyr Environmental Corporation
Implementing an Energized Electrical Work Program SESHA Hill Country Chapter May 22, 2009 Brett Jay Davis, PE Zephyr Environmental Corporation bdavis@zephyrenv.com, 512 879-6628 Presentation Outline 1.
More information1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection
Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication
More informationSECTION ISOLATED POWER SYSTEMS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to
More informationVeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage
VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage www.panduit.com/verisafe What is an Absence of Voltage Tester? Absence of Voltage Testers (AVTs) are permanently-mounted
More informationElectrical Safety Program
Electrical Safety Program Developed by: The Office of Environmental Health and Safety June, 2010 Table of Contents Introduction 3 Scope..3 Definitions.3-5 CSU Electrical Shop...5 Responsibilities.5-6 Employees.....5
More informationChapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...
Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph
More informationNECA. Standard for Electrical Safety in the Workplace
4/23/2018 N E R C e- A di st N rib ot ut Fo io r n NECA Significant Changes to the 2018 NFPA 70E Standard for Electrical Safety in the Workplace NFPA 70E Standard for Electrical Safety in the Workplace
More information2009 ELECTRICAL CODE REQUIREMENTS
2009 ELECTRICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Inspection Request Line (231) 533-3510 Electrical requirements
More informationSEL Arc-Flash Solutions
SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment
More informationMay is National Electrical Safety Month, an AND THE ELECTRICAL INSPECTOR. by Mark Hilbert and Laura L. Hildreth
by Mark Hilbert and Laura L. Hildreth AND THE ELECTRICAL INSPECTOR May is National Electrical Safety Month, an annual effort to help reduce electricallyrelated fatalities, injuries, and property loss both
More informationRevisions for the 2011 National Electrical Code - Part 4
PDHonline Course E358 (3 PDH) Revisions for the 2011 National Electrical Code - Part 4 Instructor: Patrick Ouillette 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone &
More informationNational Electrical Code
National Electrical Code 409.30 Disconnecting Means Disconnecting means that supply motor loads shall comply with Part IX of Article 30. 410.81 Control (A) Disconnection Luminaires (fixtures) or lamp installation
More informationBuilding Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
More informationNFPA 70E Elevates Safety. with Heightened Risk Awareness
NFPA 70E 2015 Elevates Safety with Heightened Risk Awareness Next Page NFPA 70E 2015 Elevates Safety with Heightened Risk Awareness: Significant Changes Since 2012 Compel Updated Electrical Safety Training
More informationSEL Arc-Flash Solutions
SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment. Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment
More informationSECTION GENERATOR PARALLELING CONTROLS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable
More informationGraded Project. National Electrical Code
Graded Project National Electrical Code National Electrical Code INTRODUCTION This next portion of your program is a project-based assignment designed for you to demonstrate your understanding of the
More informationSTATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES
STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES Articulation Agreement Identifier: ELT 118 (2005-1) Identifier is the postsecondary course prefix followed by Plan-of-Instruction
More informationShort Circuit Current Rating
Short Circuit Current Rating Customer Need There has been a significant increase in the misapplication of control panel products that brings into question the safety of those installing and using this
More informationll. Consistency Questions
Our Goal is FOR ALL STAKEHOLDERS TO HAVE A SUCCESSFUL PROJECT with us and that together we keep people and structures safe and buildings economically viable to serve the needs of our community. We strive
More informationGround Fault Protection Improvements to Prevent Fires Description of problem and potential solutions Presented by Bill Brooks, PE Principal, Brooks
Ground Fault Protection Improvements to Prevent Fires Description of problem and potential solutions Presented by Bill Brooks, PE Principal, Brooks Engineering Code Official Panel Lead, SolarABCs 1 Ground-Fault
More informationHow to keep you, your family, and your possessions safe usa.siemens.com/circuitbreakers
AFCI and GFCI Homeowner s Guide How to keep you, your family, and your possessions safe usa.siemens.com/circuitbreakers Congratulations on the purchase of your new home. This guide will help you understand
More informationArc Flash Protection Training - NFPA 70e Electrical Safety
Arc Flash Protection Training - NFPA 70e Electrical Safety Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq
More informationONE- AND TWO-FAMILY DWELLING ELECTRICAL CODE HANDOUT (2015 Michigan Residential Code Effective February 8, 2016)
Cheboygan County Department of Building Safety 870 South Main Street P.O. Box 70 Cheboygan, Michigan 49721 TX: (231) 627-8813 FX: (231) 627-8454 www.cheboygancounty.net Service Entrance ONE- AND TWO-FAMILY
More informationWelcome DISCLAIMER. Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard 5/1/ NFPA Conference & Expo
2017 NFPA Conference & Expo Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard Presented by: Tracey D. Bellamy, PE, CFPS Chief Engineering Officer Telgian Corporation Welcome Instructor
More informationIntegrated Solutions. Simple and flexible designs for space and time savings
Integrated Solutions Simple and flexible designs for space and time savings TM Save up to 40% wall space! Integrated Power Center 2 (IPC2) The Integrated Power Center 2 (IPC2) transformer combo was the
More informationThe safe way to verify the absence of voltage.
VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage www.panduit.com/verisafe What is an Absence of Voltage Tester? Absence of Voltage Testers (AVTs) are permanently-mounted
More informationAre Open Bottom Electrical Handholes a NEC Violation? Proposals to Change the 2002 NEC Traffic Signal and Roadway Lighting Related
Are Open Bottom Electrical Handholes a NEC Violation? Proposals to Change the 2002 NEC Traffic Signal and Roadway Lighting Related Introduction One of the proposals to change the 2002 NEC adds a provision
More information