Class A and Expansion NAC Modules Installation Instructions
|
|
- Alexina Richard
- 6 years ago
- Views:
Transcription
1 Class A and Expansion NAC Modules Installation Instructions Introduction This publication describes the installation procedure for the following: Flex Amplifier Expansion NAC (XNAC) Flex Amplifier Class A Adapter W Amplifier XNAC W Amplifier Class A Adapter Expansion Signal (XSIG) Card XNAC Expansion Signal (XSIG) Card Class A Adapter This product is compatible with 4100U and 4100ES Fire Alarm Control Panels (FACP). In this Publication This publication discusses the following topics: Topic See Page Cautions and Warnings 2 Introduction to the NAC Modules 3 NAC Module Specifications 4 Installing the NAC Modules onto the Amplifiers or XSIG Card 5 NAC Field Wiring Notes SimplexGrinnell LP. All rights reserved. Specifications and other information shown were current as of publication and are subject to change without notice. Simplex and the Simplex logo are trademarks of Tyco International Ltd. and its affiliates and are used under license Rev. E
2 Cautions and Warnings Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation manual. These instructions must be followed to avoid damage to this product and associated equipment. Product operation and reliability depend upon proper installation. DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED- Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex product supplier. ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be performed by a representative or authorized agent of your local Simplex product supplier. STATIC HAZARD - Static electricity can damage components. Handle as follows: Ground yourself before opening or installing components. Prior to installation, keep components wrapped in anti-static material at all times. 2
3 Introduction to the NAC Modules Overview The NAC modules are offered as optional enhancements to 100 W and Flex amplifiers, as well as the Expansion Signal (XSIG) Card, for either expanding the number of available NACs or converting the existing NACs to Class A operation. This section describes both types of NAC modules. Class A Adapters The (Flex), (100 W), and Expansion Signal Card Class A Adapters are used to convert the existing NACs on the amplifiers to Class A operation. Wiring is normally supervised from the B terminals. In the event of a short or open on the field wiring, power is provided from both the A and B terminals so that all speakers function under a single fault (short or open) condition. Class A wiring does not guarantee all speakers will function if there are multiple faults. Expansion NAC Modules The (Flex), (100W), and Expansion Signal Card XNACs double the NAC capacity of the amplifiers or XSIG card. A Flex Amplifier normally has three (3) Class B NACs available for wiring field circuits. Adding the module to a Flex Amplifier or XSIG card increases the total number of available NACs to six (6). For the 100W Amplifier, the Expansion Modules allow wiring of up to twelve (12) NACs. The additional NACs function in the same way as the original NACs and are monitored for opens, shorts and earth fault isolation while in supervision. NOTE: Using Expansion NAC modules only doubles the number of available NACs, NOT the available power. For example, a 100W amplifier has 100W available for speaker circuits regardless of whether it has six (6) NACs or twelve (12) NACs. Illustration Figure 1 (below) shows the differences in appearance between the XNAC and the Class A adapter /1248/1266 XNAC /1249/1267 Class A Adapter Figure 1. The NAC Modules Note: LEDs 1, 2, and 3 are trouble indicators that correspond to NACs 1, 2, and 3, respectively. 3
4 NAC Module Specifications The specifications below apply to both Class A adapters and XNACs at an operating voltage range of VDC. The current draw specifications listed are for a 24 V DC supply, the nominal battery voltage. Table 1. NAC Module Specifications 24 V Current Draw (in Milliamps) Standby Alarm Flex XNAC Flex Class A Adapter W XNAC W Class A Adapter Expansion Signal Card (XSIG) XNAC Expansion Signal Card (XSIG) Class A Adapter 1 30 Audio NAC Specifications (Per NAC) NAC Rating (Audio) Flex XNAC 50 W, 100 Speakers, or 2 A (whichever is less) Flex Class A Adapter 50 W, 100 Speakers, or 2 A (whichever is less) W XNAC 100 W, 100 Speakers, or 2 A (whichever is less) W Class A Adapter 100 W, 100 Speakers, or 2 A (whichever is less) Expansion Signal Card (XSIG) XNAC 50 W, 100 Speakers, or 1.5 A (whichever is less) Expansion Signal Card (XSIG) Class A Adapter 50 W, 100 Speakers, or 1.5 A (whichever is less) DC NAC Specifications (Per NAC) NAC Rating (DC) Expansion Signal Card (XSIG) XNAC 1.5 A Expansion Signal Card (XSIG) Class A Adapter 1.5 A The equipment operates normally with ambient temperatures outside the cabinet from 32 to 120 F (0 to 49 C), inclusive. The equipment operates normally under non-condensing humidity conditions up to 93% relative humidity at 90 F (32 C). 4
5 Installing the NAC Modules onto the Amplifiers or XSIG Card Mounting NAC Modules The procedure for installing both the Class A and XNAC modules is identical. Refer to Figure 2 and the instructions below to mount the NAC module to an amplifier or XSIG card. Screw Holes TB1 TB1 TB1 P4 or P5 NAC Module 1 P1 P3 NAC Module 2 P1 XSIG Card Flex Amp NAC Module 100 W NAC Module Figure 2. NAC Module Placement 1. Remove and set aside the screws from the area around the NAC expansion header on the amplifier. The screw holes are depicted in Figure Secure threaded metal standoffs provided with modules to the screw holes shown in Figure Align and then connect P1 on the NAC module with one of the following: P1 or P3 on the 100 W amplifier (all Product IDs) P4 on the , -1313, -1326, -1327, -1361, -1362, -1363, & Flex amplifiers or P5 on the , -1213, -1226, -1227, -1261, -1262, -1263, & Flex amplifiers P1 on the XSIG card 4. Secure the NAC module to the metal standoffs using the screws set aside in Step 1. 5
6 NAC Field Wiring Notes Terminal Blocks The table below shows the field wiring terminal block differences between the Class A adapter and the XNAC. Table 2. Terminal Block Specifications Pin Purpose on Class-A Adapter Purpose on Expansion Module 1 NAC 1 Class A (+) terminal NAC 1 Class B (+) terminal 2 NAC 1 Class A (-) terminal NAC 1 Class B (-) terminal 3 Shield connection (0 V) 4 NAC 2 Class A (+) terminal NAC 2 Class B (+) terminal 5 NAC 2 Class A (-) terminal NAC 2 Class B (-) terminal 6 Shield connection (0 V) 7 NAC 3 Class A (+) terminal NAC 3 Class B (+) terminal 8 NAC 3 Class A (-) terminal NAC 3 Class B (-) terminal Field-Replaceable Parts The Class B Expansion Modules (XNACs) contain field-replaceable fuses as follows: Flex Amplifier XNAC: F1, F2, & F Fast-Acting Fuse (3 A) W Amplifier XNAC: F1, F2, & F Fast-Acting Fuse (3 A) Expansion Signal (XSIG) Card XNAC: F1, F2, & F Fast-Acting Fuse (2.5 A) Related Documentation Field wiring diagrams depicting the NAC module can be found in the following publications: Flex Amplifier Installation Instructions ( ) 100W Amplifier Installation Instructions ( ) Expansion Signal (XSIG) Card Installation Instructions ( ) Rev. E
Panel Message Memory Expansion Cards Installation Instructions
Panel Message Memory Expansion Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-1241 Audio Message Memory Expansion Card (4 Megabytes
More information/ XPS Interconnection Diagrams
4100-5153/4100-5154 XPS Interconnection Diagrams Introduction This publication provides interconnection diagrams for 4100-5153 (120 VAC) and 4100-5154 (220/240 VAC) 13 A Expansion Power Supplies (XPS).
More information4100U City and Relay Cards Installation Instructions
4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting
More informationPanel Remote Annunciators Installation Instructions
Panel Remote Annunciators Installation Instructions Introduction This publication describes the installation procedures for the following PIDs: 4100-9607 Remote Annunciator w/ Flexible User Interface Domestic
More informationNetwork Display Unit Installation Instructions
Network Display Unit Installation Instructions Introduction This publication describes the installation procedures for the optional Network Display Units (NDUs). This product is compatible with both the
More information/9308 External Battery Chargers Installation Instructions
4081-9306/9308 External Battery Chargers Installation Instructions Introduction This publication describes the installation procedure for an External Battery Charger used with the 4100U or 4100ES System.
More informationCautions and Warnings. Introduction 4009 NAC POWER EXTENDER
Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately
More information4009 Fiber Optic Link Option Installation Instructions
4009 Fiber Optic Link Option Installation Instructions Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton
More informationAddressable IDNet Isolator Installation Instructions
4090-9116 Addressable IDNet Isolator Installation Instructions Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS - Follow the instructions in this installation manual. These instructions must be followed
More informationAU MX Digital Loop Card Installation Instructions
4100-6077AU MX Digital Loop Card Installation Instructions Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS - Follow the instructions in this installation manual. These instructions must be followed
More information/5121/5122 TrueAlert Power Supply Installation Instructions
4100-5120/5121/5122 TrueAlert Power Supply Installation Instructions Introduction This publication provides an overview of the features, specifications, and capabilities of the TrueAlert power supplies
More informationGENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING
GENERAL The VEC 25/50 is a state-of-the-art, compact, stand-alone or slave Emergency Voice Evacuation Control. The VEC 25/50 is offered in a self-contained, cost-effective design and includes a 25 Watt,
More informationLifeAlarm Fire Alarm Controls
UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity
More informationTrueAlert Addressable Notification Appliances
Fire Control ** IS NORMAL ** :0:pm Mon 9-Feb-9 SY S TE M AC SUPERVISORY TROUB LE SILENCED SUPV TROUBLE SILENCE RESET CONTROL DISC ON NEC T POW ER + V ZONE P WR + 0V ZONE P WR - +IDNE T IDC + - IDNE T IDC
More informationJuly 14, 1999 DF C-100.
www.firelite.com GENERAL The Fire Lite FIRE COMMAND 25/50 is a state-of-theart, compact, stand-alone or slave Emergency Voice Evacuation Control Panel (VECP). The FIRE COMMAND 25/50 is offered in a self-contained,
More informationFire Alarm Testing and Inspection Report
Fire Alarm Testing and Inspection Report Property Name: Property Address: Property Manager: Contact: Phone Number: Central Station: Phone Number: PELICAN ISLE II 35 DOCKSIDE RD. NAPLES, FLORIDA 3110 BILL
More informationTrueAlert Addressable Notification Appliances
UL, ULC Listed* TrueAlert Addressable Notification Appliances Audible/Visible Notification Appliances; Multi-Tone Horn/Strobe with 520 Hz Output Features Individually addressed and controlled multi-tone
More informationFireNET Plus Wiring Instructions
FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to
More informationJune 10, 2002 DF C S2424
GENERAL www.firelite.com The Fire Lite FIRE COMMAND 25/50X is a state-of-theart Emergency Voice Evacuation Control Panel (VECP), with significant technological enhancements that set it apart from other
More informationECC-50/100C. Emergency Command Center
ECC-50/100C Emergency Command Center Canadian DF-60815:B Emergency Communications General Fire-lite s ECC-50/100C is a multipurpose emergency voice evacuation panel for fire applications, mass notification
More informationAFMS Audible Flow Monitoring System TECHNICAL SPECIFICATION
968 AFMS AFMS TECHNICAL SPECIFICATION 08/07 Ref B ATV-ELEKTRONIK GMBH WIENER STRASSE 228 A-4030 LINZ +43 732 301600 FAX. +43 732 301600 21 Page 2 Table of contents General Introduction...3 Overview...3
More informationECC-50/100(E) Emergency Command Center
ECC-50/100(E) Emergency Command Center DF-60734:A9 C-200 General Fire Lite s ECC-50/100 and ECC-50/100E are multipurpose emergency voice evacuation panels for fire applications, mass notification applications,
More informationACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS
II 1400-3 ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS Features: For use with doors or groups of doors that must interlock with each other to regulate control of accessing one area from another,
More informationTrueAlert Addressable Notification Appliances
UL, ULC Approved* TrueAlert Addressable Notification Appliances Audible Notification Appliances; Multi-Tone Horns with 520 Hz Output Features Individually addressed and controlled TrueAlert ES multi-tone
More informationTrueAlert Addressable Notification
UL, ULC Approved* TrueAlert Addressable Notification 4009 IDNAC Repeater; Power and Distance Extender Features IDNAC Repeaters provide enhanced power delivery to TrueAlert/ TrueAlert ES addressable notification
More informationECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS
ECC-50/100(E) Emergency Command Center DF-60734:A4 General Firelite s ECC-50/100 and ECC-50/100E are multipurpose emergency voice evacuation panels for fire applications, mass notification applications,
More informationMulti-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.
M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @
More informationFire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION
Fire Safety Installation Instructions Model SMB- Main Control Board OPERATION The SIEMENS Model SMB- board in each MXL-IQ System controls operations and monitors input device identity, network communication,
More informationInstallation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev
Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control
More informationAddressable NAC Output Module D327A
Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,
More informationACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel
ACC-25/50ZST Zoned System Voice with Telephone Evacuation Control Panel General The AUDIO COMMAND CENTER 25/50 Zone System with FireFighters Telephone (ACC-25/50ZST) is a state-of-the-art Emergency Voice
More informationFire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for 4120 Network. UL, ULC, CSFM Listed; FM Approved* Features
Fire Control Panels UL, ULC, CSFM Listed; FM Approved* Features Compatible with Simplex 4120 Network Converts multiple 4120 network communications signals into a single fiber optic link to: Multiplex audio
More informationRev. B. TrueAlert Addressable Controller Application Manual
574-996 Rev. B TrueAlert Addressable Controller Application Manual This page intentionally blank Copyrights and Trademarks Copyright 000 Simplex Time Recorder Company, Westminster, MA 044-000. All rights
More informationPS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01
PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Warnings and Notices WARNING - To reduce the risk of fire or electric shock, do not expose this product
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS PROFESSIONAL COOKTOP MODELS 48 GAS COOKTOP WITH SEALED BURNERS** 48 NATURAL GAS MODEL *TN047-7 **THIS MODEL IS NOT FIELD CONVERITBLE FOR LP/PROPANE GAS. IT MUST BE ORDERED FROM
More informationWYND DC 54 CEILING FAN Installation Manual
WYND DC 54 CEILING FAN Installation Manual CFFCWY4XXX Remote control included YOUR FANCO WYND 54 DC CEILING FAN Congratulations on purchasing your new Fanco Wynd 54 DC Ceiling Fan. Before attempting to
More informationOperator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B
Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES 579-685 Rev. B ii iii Cautions and Warnings Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation
More informationRM-1 Series. Remote Microphones. (RM-1, RM-1SA) Document Revision B RM-1 RM-1SA. RM-1 on ADP-4 dress panel. RM-1SA in a CAB-RM or CAB-RMR
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. The following products have not received UL
More informationAL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev
AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated
More informationACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX
Page 1 of 10 Model 10807800 January 2014 ACCURATE ELECTRONICS INC PO BOX 1654 97075-1654 8687 SW HALL BLVD 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 WWW.ACCURATE.ORG Practice Section 10807800
More informationCLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. I 2017 Pentair Equipment Protection P/N
CLIMAGUARD Air-to-Air Outdoor Heat Exchangers TX23, TX33, TX38, TX52 Models INSTRUCTION MANUAL Rev. I 2017 Pentair Equipment Protection P/N 10-1008-221 87976519 TABLE OF CONTENTS Warranty and Return Policy...2
More informationSeries SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual
Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual Part Number P84748 Assembly Number A84749 Revision C Revision A Copyright 2006 Printed in U.S.A. All rights reserved.
More informationTrueAlert Notification Appliances
TrueAlert Notification Appliances UL Listed; FM, CSFM and MEA (NYC) Approved* Non-Addressable Audible/Visible Notification Appliances with SmartSync Operation of Strobes and Horns Features Wall mount audible/visible
More informationTrueAlarm ES Analog Sensing
TrueAlarm ES Analog Sensing UL, ULC, CSFM Listed; FM Approved* Features TrueAlarm addressable sensor base with 520 Hz sounder TrueAlarm sensor bases with 520 Hz tone require a TrueAlarm photoelectric,
More informationGreentrol Automation, Inc.
Model GA-100 Technical Manual GreenAlert 100 Series Greentrol Automation, Inc. Installation, Operation and Maintenance Technical Manual GA-100 Document Name: TM_GA-100_R1C TM_GA-100_R1C Part Number: 960--0000
More informationThese instructions detail procedures to follow in order to avoid damage to equipment.
D326A, D334A, D339A Point Contact Modules Installation Guide 1.0 Notice These instructions are for the installation of the D326A, D334A and D339A Point Contact Modules in an analog system controlled by
More informationTrueAlarm Analog Sensing
TrueAlarm Analog Sensing UL, ULC Listed, CSFM Approved* Features Air aspiration duct smoke detection** system provides remote sensor location for ducts with difficult service access: Available as either
More informationPower Supply Display Module PSDM. Installation and Operation Manual
Power Supply Display Module PSDM Installation and Operation Manual Read this manual before using this product. Failure to follow the instructions and safety precautions in this manual can result in serious
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS PROFESSIONAL RANGE MODELS 24 ALL GAS, CONVECTION WITH OPEN BURNERS** 24 NATURAL GAS MODEL *TN480-7BW **THESE MODELS ARE FIELD CONVERITBLE FOR LP/PROPANE GAS.** 24 LP/PROPANE GAS
More informationCertificate of Conformity Certificate num. Registration date Version Valid until
CSIRO Verification Services Highett, Victoria, Australia +61 (0)3 9252 6000 http://www.activfire.gov.au/ Page 1 of 7 Product designation Simplex, Model 4100U/4100U-S1/4100ES/4100ES-S1, fire indicator panel
More informationTraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM
TTC-1 TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION The nvent RAYCHEM TraceTek TTC-1 sensing module is used with TraceTek sensing cables to detect liquid leaks.
More informationPS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option
Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR
More informationModels NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117
Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring
More informationACCURATE ELECTRONICS INC
ACCURATE ELECTRONICS INC Page 1 of 7 Model 108078 2 Sept 09 WWW.ACCURATE.ORG PO BOX 1654 97075-1654 8687 SW Hall Blvd 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 Practice Section 108078 Rev A
More informationCLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N
CLIMAGUARD Air-to-Air Outdoor Heat Exchangers TX23, TX33, TX38, TX52 Model INSTRUCTION MANUAL Rev. H 2015 Pentair Equipment Protection P/N 10-1008-221 87976519 TABLE OF CONTENTS RECEIVING THE HEAT EXCHANGER...3
More informationINSPECTION AND TESTING FORM
INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital
More informationPSN-1000 & PSN 1000(E) Installation Manual
PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com
More informationFUSE PANEL. Technical Practice N N/0803 5/5 GMT Front Access NEBS Level 3 Certified
0803-03B April 17, 2008 Noran Tel PANEL Technical Practice N250110-N/0803 5/5 GMT Front Access NEBS Level 3 Certified FEATURES 2 isolated groups (busses) of 5 GMT fuses in each (15Amps/GMT position). Polarity
More informationLDM Series Lamp Driver Modules For Graphic Annunciation and Control
12 Clintonville Road Northford, CT 06472 (203) 484-7161 FAX: (203) 484-7118 LDM Series Lamp Driver Modules For Graphic Annunciation and Control Used with the System 500, System 5000, AM2020/AFP1010 and
More informationPublic Safety DAS Annunciator Panel
Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This
More informationTrueAlert Addressable Notification Appliances
UL, ULC, CSFM Listed, FM Approved TrueAlert Addressable Notification Appliances Audible/Visible Notification Appliances, Wall Mount Multi-Candela Horn/Strobe, Model Series 49AV Features Individually addressed
More informationPanel Mounted Heat Exchangers by Dantherm, Inc.
Panel Mounted Heat Exchangers by Dantherm, Inc. PRODUCT INFORMATION MANUAL C0028 003 Pinnacle OM Manual Rev AB Page 1 of 14 Dantherm, Inc. 110 Corporate Drive, Suite K Spartanburg, SC 29303 Tel # +1 864
More informationClimaGuard Outdoor Heat Exchanger All Models
INSTRUCTION MANUAL ClimaGuard Outdoor Heat Exchanger All Models Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200 www.mcleanparts.net
More information30.45 Electric Release PDRP-2001
The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or
More informationInstallation Guide for models:
140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp
More informationMulti-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.
M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp
More informationFMR Installation Instructions. Addressable Fire System Controller
FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3
More informationRemote NAC Power Supply D7038
Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus
More informationInstallation Instructions Model SSD-C-REM
Installation Instructions Model SSD-C-REM Remote System Status Display with Control ON ALARM SUPERVISORY SECURITY TROUBLE AUDIBLES SILENCED INTRODUCTION The SIEMENS Model SSD-C-REM is an optional FireFinder
More informationSC-6 Six Supervised Control Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS SC-6 Six Supervised Control Module SPECIFICATIONS Normal Operating Voltage: Stand-By Current: Alarm Current: Temperature Range: Humidity: Dimensions: Accessories:
More informationSAFEPATH SP40/2 D10 D35 AMP P/N P/N Installation, Testing, TONE SW Operation, and W4 Maintenance D54 SHORT
W1 U8 AC N L SAFEPATH4 F2 IN BAT 24V TB7 TB1 AC TBL STB D11GRN YEL RED F1 D13 D14 AC SW1 SW2 RECORD D34 1 2 3 4 SP40/2 D9 D22 DV D10 D35 BAT MIC W2 ON D37 STB SHORT D39 STB OPEN 1 2 3 R SW3 1 2 3 4 TEL
More informationFUSE PANEL Technical Practice N N/L9 10/10 GMT NEBS Level 3 Certified
0226-03K August 13, 2008 FUSE PANEL Technical Practice N250120-N/L9 10/10 GMT NEBS Level 3 Certified FEATURES 2 isolated groups (busses) of 10 GMT fuses in each (15Amps/GMT position). Polarity insensitive
More information6502B RF Distribution
6502B RF Distribution User Guide Revision A - March 2004 Part Number 15247-201 Table of Contents Table of Contents About this User Guide Purpose...................................................... 1
More informationFire Control Panels. Automatic Extinguishing, Deluge and Preaction Sprinkler System Releasing Control
MANUAL RELEASE - IDNET IN + +IDNET IN - RED NA C+ N A C - COIL SUPERVISION MODULE ( 2 AMP) 28-946 INSTALLATION INSTRUCTIONS 574-437 REV YEL MA IN T A IN /4 "S E P A R A T IO N BETW EEN POW ER LIMITED (
More information460H INSTALLATION & OPERATION MANUAL REMOTE STROBE POWER SUPPLY IMPORTANT: 460H TM REMOTE STROBE POWER SUPPLY
INSTALLATION & OPERATION MANUAL 460H TM REMOTE STROBE POWER SUPPLY 460H REMOTE STROBE POWER SUPPLY Contents: Introduction... 2 Standard Features... 2 Specifications... 2 Unpackaging & Pre-installation...
More informationNoran Tel. FUSE PANEL Technical Practice N NCY 2/2 KLM and 4/4 GMT NEBS Level 3 Certified
0232-03J December 13, 2006 FUSE PANEL Technical Practice N215112-NCY 2/2 KLM and 4/4 GMT NEBS Level 3 Certified FEATURES 2 isolated groups (busses) of 2 KLM and 4 GMT fuses in each (30Amps/KLM, 15Amps/GMT).
More informationInstallation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger
Installation Guide for AL400ULM Multi-Output Access Control Power Supply Charger R AL400ULM - Multi-Output Access Control Power Supply/Charger Rev. 072500 Overview: The AL400ULM multi-output access control
More informationThis wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control
File: S8485 Wiring Diagram This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control Panel. The operation of this product is intended for indoor
More informationUnity DAU Voice Alarm System
Unity DAU Voice Alarm System User Manual & Log Book Site Name Address Contractor Commissioned Introduction Voice Alarm (VA) systems are the quickest way to evacuate the public & staff from a building.
More informationMODEL 8144-RD CLOCK SELECTOR/DISTRIBUTION AMPLIFIER INSTRUCTION MANUAL. SPECTRACOM CORPORATION 95 Methodist Hill Drive, Suite 500 Rochester, NY 14623
MODEL 8144-RD CLOCK SELECTOR/DISTRIBUTION AMPLIFIER INSTRUCTION MANUAL SPECTRACOM CORPORATION 95 Methodist Hill Drive, Suite 500 Rochester, NY 14623 PHONE 585-321-5800 FAX 585-321-5218 REVISIONS, IF ANY,
More informationFire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for Panel and Remote Mounting. Features. Operation.
UL, ULC Approved* Fire Control Panels Multiple Signal Fiber Optic Modems and Accessories for Panel and Remote Mounting Features Converts multiple fire alarm communications signals into a single fiber optic
More informationRAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description The TYCO RAPID RESPONSE Model RCP-1 Residential
More informationFUSE PANEL. Technical Practice N N/L33 10/10 GMT Front Access NEBS Level 3 Certified
0220-03J Oct 9, 2006 Noran Tel FUSE PANEL Technical Practice N25020-N/L33 0/0 GMT Front Access NEBS Level 3 Certified FEATURES 2 isolated groups (busses) of 0 GMT fuses in each (5Amps/GMT position). Polarity
More information1U ULTRA Compact System
en atel Supervisory Module SM32 Load 60 00 A IE C60947-2 G B140 4 8.2 CHNT NB1-63 C32 23 0/40 0 V e NaT el OK enatel RM 1848 enatel RM 1848 Battery 60 00A IE C60947-2 G B1 4 04 8.2 CHNT NB 1-63 C32 23
More informationModel T B Intraoffice T1 Repeater User Manual
Model 544-01B Intraoffice Repeater User Manual Model 544-01B 15404-A Content Page INTRODUCTION... 1 Revision History... 2 Trademark Information... 2 1 PRODUCT DESCRIPTION... 2 2 SPECIFICATIONS... 5 3 INSTALLATION...
More information4200 RESCUE ASSISTANCE INSTALLATION GUIDE-OVERVIEW
4200 INSTALLATION GUIDE-OVERVIEW IMPORTANT: THE FOLLOWING FIELD MODIFICATIONS MUST BE COMPLETED AT THE TIME OF INSTALLATION. THE 4200 SYSTEM REQUIRES THE FOLLOWING SETTINGS FOR PROPER OPERATION. ADDITIONAL
More informationTrueAlert ES Addressable Notification Appliances
UL, ULC, CSFM Listed; FM Approved* TrueAlert ES Addressable Notification Appliances Visible Notification Appliances, Wall Mount Multi-Candela Strobes, Model Series 49VO Features Individually addressed
More informationXPS and XNAC Installation Instructions
XPS and XNAC Installation Instructions Introduction This publication describes the installation procedure for 4100-5101 (120 VAC), 4100-5102 (220/230/240 VAC), and 4100-5103 (120 VAC with battery disconnect)
More informationEXTINGUISHING AGENT RELEASE MODULE
EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153
More informationRAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) SECTIONS General Description.... 1 Warnings.... 2 Technical
More informationFCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply
One Fire-Lite Place Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE Field Charger/Power
More informationInstallation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger
Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger
More informationDuct smoke housing, 2-wire D340/D340P
Duct smoke housing, 2-wire D340/D340P en Installation manual Duct smoke housing, 2-wire Notices en 3 1 Notices These instructions cover the installation of the D340 Duct smoke housing and D340P Duct smoke
More information5U Compact System. Installation Manual V1.0. Manufactured by Enatel Ltd. 321 Tuam Street PO Box Christchurch New Zealand
5U Compact System Installation Manual V1.0 Manufactured by Enatel Ltd. 321 Tuam Street PO Box 22-333 Christchurch New Zealand Phone +64-3-366-4550 Fax +64-3-366-0884 Email sales@enatel.net www.enatel.net
More informationThe ACM-8R Annunciator Control Module
12 Clintonville Road Northford, CT 06472 203-484-7161 FAX: 203-484-7118 The Annunciator Control Module For the System 500, System 5000, AFP-200, AM2020, AFP1010 and SFP-1024 Fire Alarm Control Panels Document
More informationAL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs
ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs
More informationACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F
II 1400-2 ACSI 1406-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F INSTALLATION Transformer Model BE31763001 by Basler Electric, Transformer Model 2010028 by Galaxy
More informationBooster Power Supply Manual
Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation
More informationSpecification/ Data Sheet
Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)
More informationXP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card
XP6-C Six Circuit Supervised Control Module and SYNC-1 Accessory Card General NOTIFIER s XP6-C six-circuit supervised control module provides intelligent alarm systems with supervised monitoring of wiring
More information