Prefunctional Checklist
|
|
- Rosamund Wood
- 6 years ago
- Views:
Transcription
1 Prefunctional Checklist This Prefunctional Checklist should be completed as part of startup and initial checkout of the equipment in preparation for Functional Performance testing. PC: ITEM: Generator Assemblies ID: (Use one form for each Equipment) AREA SERVED: (Building and Room Number / Name) Form Filled Out By: Name & Company Date GC MC EC BC CC OR A/E CA GC = General Contractor; MC = Mechanical Contractor; EC = Electrical Contractor; BC = Balancing Contractor; CC = Controls Contractor; OR = Owner Representative; A/E = Architect/Engineer; CA = Commissioning Agent XX = No Initials Required 1. DOCUMENTATION VERIFICATION Check if OK. Enter note number if deficient. Item GC MC EC BC CC OR A/E CA Product information submitted Shop drawings submitted Manufacturer s installation instructions submitted Manufacturer s startup instructions submitted O & M Manuals submitted Factory test report submitted. Sequence of Operations submitted PC
2 2. MODEL VERIFICATION Manufacturer Model Serial No. Generator voltage rating Engine rating- HP Generator rating- KVA Temperature rating Altitude rating ATS voltage rating ATS current rating [Other] Fill in requested information. Installed Submitted Specified 3. INSTALLATION VERIFICATION This checklist does not take the place of the manufacturer s recommended checkout and startup procedures or report. Check if OK. Enter Outstanding Item Note number if deficient. Item GC MC EC BC CC OR A/E CA Correct Gen Set Gen Set installed per drawings and manufacturer s recommendations. Diesel engine suitable for No. 2 low sulphur diesel fuel oil. Over speed shutdown device installed properly. Engine fuel oil system components installed correctly. Fuel gauge installed properly. Fuel tank capacity: gallons. Fuel tank rupture basin installed correctly. Fuel tank rupture basin capacity: gallons. Fuel tank rupture basin capacity adequate (150% of fuel tank capacity. (1.5x = gallons). Fuel tank rupture basin presence of liquid device Fuel system piping properly installed and protected. Lubricating oil system components properly Lubricating oil system filters properly Engine Cooling system components properly Engine exhaust system properly PC
3 Item GC MC EC BC CC OR A/E CA Engine Air Induction system properly Air filters installed Cranking system installed Power circuit to water jacket heater system correctly Water jacket heater system Starting batteries correct voltage and capacity rating. Batteries installed and connected. Power circuit to charging system correctly Safety shutdown controls and alarms correctly Generator voltage and rating correct. Voltage Regulator Exciter installed Controls installed correctly Instrumentation and gauges installed correctly Remote annunciator installed Wiring to remote annunciator marked and terminated correctly. Generator and engine mounted on a fabricated steel skid base per the drawings. Vibration isolators installed properly Weather-protective insulated generator enclosure installed correctly. All required features provided in enclosure. Interior of gen set enclosure clean. All openings free of debris. Fire suppression equipment and alarms Automatic Transfer Switch (ATS) installed in correct location. Record settings for adjustments. Loss of Normal power to call for start up: Restoration of normal power to shutdown: Other settings: Correct voltage and current rating for ATS. Correct environmental rating for enclosure. Enclosure installed securely, level and plumb. Incoming and outgoing circuits of proper size and terminated correctly. PC
4 Item GC MC EC BC CC OR A/E CA Verify surge suppression devices installed correctly. Verify all ATS accessories provided and installed correctly. PC
5 4. OUTSTANDING ITEMS Note Outstanding items in table below. Use numbers referenced above. Note Description Resolved (Initial / Date) FIELD NOTES Fill in as appropriate. 6. SIGN OFF System / Equipment has been installed in accordance with the contract documents and is ready for Functional Testing. Contractor s Representative A /E Representative Commissioning Agent Owner s Representative Signature Date END OF CHECKLIST PC
Prefunctional Checklist
This should be completed as part of startup and initial checkout of the equipment in preparation for Functional Performance testing. PC: 28 31 76 ITEM: Fire Alarm/Mass Notification System ID: (Use one
More informationFire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC
PART 1 GENERAL 1.01 SUMMARY SECTION 23 08 00 COMMISSIONING OF HVAC A. This section covers the Contractor's and Commissioning Authority (CA) responsibilities for commissioning; each subcontractor or installer
More informationSecurity CCTV System Construction Checklist
Security CCTV System Construction Checklist Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 23 05 93 - TESTING, ADJUSTMENT AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationMichigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE
PAGE 280800-1 SECTION 280800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More information2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)
2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) Reference: Documents referenced for this bulletin are as follows: San
More informationENGINE GENERATORS AND ACCESSORIES
ENGINE GENERATORS AND ACCESSORIES GENERAL INFORMATION 1.1 This section applies to engine generators and accessories. DESIGN REQUIREMENTS 2.1 The Engineer of Record will consult with the University s Engineering
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL
SECTION 21 30 00 FIRE PROTECTION PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00,
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph
More informationCxA to Answer this Section
EXHIBIT 01 91 13-3, SAMPLE Construction checklist items are to be completed as part of initial checkout and subsequent startup, preparatory to Functional testing. This checklist does not take the place
More informationLABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS
SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",
More informationSECTION EMERGENCY POWER SYSTEMS
SECTION 16620 EMERGENCY POWER SYSTEMS A. Standby Engine/Generator Systems 1. Installations of stationary engine/generator (e/g) systems shall be designed in strict accordance with ANSI/NFPA 70 - National
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 3 Page 1 of 6 I. PURPOSE This procedure establishes guidelines for the weekly or monthly inspection and testing of all fire pumps within the University of Rochester by representatives of
More informationPHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps
Note: The A/E must choose all design values in brackets below before using in project specifications 1 General 1.1 Provide UL listed and FM approved fire pump complete with pump, driver, controller and
More informationBaldor Electric ProSPEC MASTERFORMAT SPECIFICATION 10/26/05
SECTION 16230 - GENERATOR ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY A. Provide factory test, startup by a supplier authorized by the manufacturer, and on-site testing of the system. B. The generator set
More informationCONTENTS AUTOMATIC TRANSFER SWITCHES
CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE PUMP REVIEW Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;
More informationCity of Duluth Festival Center 04/25
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationSMALL WORKS PROJECT REQUEST FOR SEALED BIDS
SMALL WORKS PROJECT REQUEST FOR SEALED BIDS PIERCE COUNTY FIRE PROTECTION DISTRICT #22 18421 OLD BUCKLEY HIGHWAY BONNEY LAKE, WA 98391 (253) 863-1800 (253) 863-1848 (FAX) Date Bid Requested: 5/24/2012
More informationVACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES
Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete
More information1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.
Issued 2006/08/01 Section 13920 Packaged Fire Pumps and Controllers Page 1 of 7 PART 1 GENERAL 1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 21 0800 - COMMISSIONING OF FIRE SUPPRESSION SYSTEMS GENERAL 1.1 SUMMARY General 1. Work under this contract shall meet the requirements of Division 01, General Requirements, Conditions of Contract,
More informationB. Section Transfer Switches: Automatic transfer switch.
SECTION 263213 - ENGINE GENERATORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Packaged engine generator set. B. Exhaust silencer and fittings. C. Remote control panel. D. Battery and charger. E. Weatherproof
More informationSECTION SECURITY TESTING AND COMMISSIONING
SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,
More informationB. Provide factory test, startup by a supplier authorized by the equipment manufacturer(s), and on-site testing of the system.
SECTION 480V PACKAGED GENERATOR SYSTEMS 1.01 SCOPE PART 1 - GENERAL A. Provide complete factory assembled EPA certified low emission stand-by generator set equipment compatible for paralleling with the
More informationAIRPORT OFFICE BUILDING. Smoke Control System. Testing Procedures Manual. September 10, 2016
IMPACT ENGINEERING, INC. AIRPORT OFFICE BUILDING Smoke Control System Testing Procedures Manual September 10, 2016 All Rights Reserved This manual is protected by the U.S. Copyright Law (Title 17 United
More informationPWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R
Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,
More informationSA Series Startup Form
SA Series Startup Form Job Name: Date: Address: Model Number: Serial Number: Tag: Startup Contractor: Address: Phone: Pre Startup Checklist Installing contractor should verify the following items.. Is
More informationSystem Test Report CLEAN AGENT
City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information
More informationThe Participant will select one of the two Approval Categories (below) and submit the appropriate documentation.
ACCL Participant: Date of Inspection: Test Stand Inspection Report Number: Approval Results: FORM ACCL-PC4 ACCL FACILITY APPROVAL PROCEDURE AND CHECKLIST AHRI CERTIFICATION PROGRAM FOR AIR-COOLED (ACCL)
More informationSPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM
1. GENERAL SPECIFICATION 1.1. A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated
More informationSECTION WATER-TUBE BOILERS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections
More informationSTEP 1: SELECT A NITROGEN GENERATOR STEP 2: SELECT A VENT STEP 3: SELECT MONITORING EQUIPMENT STEP 4: CONTACT ECS
STEP 1: SELECT A NITROGEN GENERATOR To ensure the nitrogen generator is adequately sized, the following information is required: The total cumulative size of all dry/preaction sprinkler systems The size
More informationCommissioning Methodologies (CM) MUBS-09 Duct Mounted Temperature & Humidity Sensor Testing Method Statement
Client: Project Name: Project No: Area: Drawing No s: Date: Sheet: 1 of 5 Check Conducted By: Signature: Check Approved By: Signature: INTRODUCTION AI - Analogue Input: (...) The on-site commissioning
More informationTONY ESPOSITO LIGHTING/ELECTRICAL TECHNICAL REPORT II SEPTEMBER 15, 2011 HUNTER S POINT SOUTH INTERMEDIATE SCHOOL AND HIGH SCHOOL QUEENS, NY
LIGHTING/ELECTRICAL TECHNICAL REPORT II SEPTEMBER 15, 2011 HUNTER S POINT SOUTH INTERMEDIATE SCHOOL AND HIGH SCHOOL QUEENS, NY 1 1A. POWER DISTRIBUTION SYSTEMS a. EXECUTIVE SUMMARY b. SUMMARY DESCRIPTION
More informationDENVER INTERNATIONAL AIRPORT MAIN AND NORTH TERMINALS 2016
IMPACT ENGINEERING, INC. MAIN AND NORTH TERMINALS Smoke Control System Testing Procedures Manual September 24, 2016 Copyright Impact Engineering, Inc. 2016 All Rights Reserved This manual is protected
More informationA. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.
1. GENERAL SPECIFICATION 1.1 A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated
More information16620 EMERGENCY POWER SYSTEMS
16620 EMERGENCY POWER SYSTEMS PART 1: GENERAL 1.01 SUMMARY A. This Section provides the University guidelines for the installation of Emergency Power Systems. B. This standard is developed primarily to
More informationDTW Master Specification Section EMCS: Start Up, Verification and Commissioning
Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Related Sections..1 The contractor is to ensure that all related work is co ordinated among all specification sections, as well as between Division 11,
More informationType of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:
DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM
More informationNITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM
NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This section outlines the requirements for the nitrogen-generating sprinkler corrosion inhibiting system. The work
More informationWESTIN HOTEL. Smoke Control System. Testing Procedures Manual. October 10, Copyright Impact Engineering, Inc All Rights Reserved
IMPACT ENGINEERING, INC. WESTIN HOTEL Smoke Control System Testing Procedures Manual October 10, 2016 Copyright Impact Engineering, Inc. 2016 All Rights Reserved This manual is protected by the U.S. Copyright
More informationDiesel Fuel System Report
Transbay Transit Center San Francisco, CA Prepared for: Pelli Clarke Pelli Architects 1056 Chapel Street New Haven, CT 06510 Prepared by: WSP 405 Howard Street, Suite 500 San Francisco, CA 94105 Mechanical
More informationSECTION ELECTRICAL SYSTEMS COMMISSIONING
SECTION 16990 PART 1 - GENERAL 1.01 SECTION INCLUDES A. Section Includes: 1. General requirements for Commissioning (Cx) of lighting systems components, lighting controls and HVAC systems line voltage
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.
More informationFLORIDA SHERIFFS ASSOCIATION & FLORIDA ASSOCIATION OF COUNTIES
FLORIDA SHERIFFS ASSOCIATION & FLORIDA ASSOCIATION OF COUNTIES Name of Dealership Type of Vehicle Zone 600 AMP AUTOMATIC TRANSFER SWITCH (Specification #75) Base Unit Price Mid Florida Diesel, Inc 2018
More informationElectronic Flow Switches
Industries Electronic Flow Switches Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor
More informationEquipment Maintenance Checklist
The Hartford Steam Boiler Inspection and Insurance Co. One State Street P.O. Box 5024 Hartford, CT 06102-5024 Tel: 800-333-4677 Fax: 484-582-1811 Internet: http://www.hsb.com Equipment Maintenance Checklist
More informationCITY OF MEXICO BEACH REQUEST FOR QUOTES: LIFT STATION PANELS REPLACEMENT
CITY OF MEXICO BEACH REQUEST FOR QUOTES: LIFT STATION PANELS REPLACEMENT The City of Mexico Beach is requesting quotes for replacement of 18 lift station control panels. The lift stations range from 2
More informationConstruction Standards Page
Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSoft Start Series MP700 Solid State, Reduced Voltage
Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s
More informationM2 Series Startup Form
M Series Startup Form Job Name: Date: Address: Model Number: Serial Number: Tag: Startup Contractor: Address: Phone: Pre Startup Checklist Installing contractor should verify the following items.. Is there
More informationMASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc
MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model
More informationSECTION INTEGRATED AUTOMATION COMMISSIONING
SECTION 25 08 00 INTEGRATED AUTOMATION COMMISSIONING PART 1. GENERAL 1.01 SECTION INCLUDES: A. BAS and equipment testing and start-up B. Validation of proper and thorough installation of BAS and equipment
More informationSECTION PACKAGED ENGINE GENERATORS
PACKAGED GENERATORS BATON ROUGE, LOUISIANA SECTION 26 32 13 SECTION 26 32 13 PACKAGED ENGINE GENERATORS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged engine-generator sets for emergency
More informationFlorida Department of Transportation
Page 1 of 7 RICK SCOTT GOVERNOR Florida Department of Transportation 1109 S. Marion Avenue Lake City, Florida 32025 ANANTH PRASAD SECRETARY September 27, 2011 To: Proposal Holders Addendum No: 1, E2Q23,
More informationHo-Chunk Gaming THUNDERBIRD ENGINEERING, INC. MILWAUKEE: (414) MADISON: (608)
Ho-Chunk Gaming POWER SYMBOLS X ELECTRICAL PANEL - REFER TO DRAWINGS FOR WIDTH AND PANEL SCHEDULES PANEL NAMING: XXP-#X: DENOTES PANEL FUNCTION: L = LIGHTING P = GENERAL POWER E = EMERGENCY S = OPTIONAL
More informationTESTING, ADJUSTING AND BALANCING
PART 1 GENERAL 1.01 DESCRIPTION A. Work Included: After completion of the work of installation, owner is responsible for procuring an air balancing and testing agency to test and regulate all components
More informationAO Annunciator Module
General Specifications GS48C43Z01-00E-N AO-543-01 Annunciator Module GENERAL Figure 1 This module has two independent annunciator circuits. The circuits handle fault signals and operator actions (acknowledge,
More informationSTATEMENT OF WORK I. SCOPE OF WORK:
STATEMENT OF WORK Purchase and Installation of Diesel Standby Generator Set and Service Entrance Rated Automatic Transfer Switch for Sewage Treatment Plant Nockamixon State Park (Bucks County) I. SCOPE
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION DOMESTIC WATER HEATERS PART 1 - GENERAL
SECTION 22 14 00 DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 00 10,
More informationSECTION AIR COILS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:
More informationAS DIGITAL FIRE PUMP CONTROLLER
AS 2941-2013 DIGITAL FIRE PUMP CONTROLLER COMPLIANT WITH AS2941-2013 CLAUSES 9.4.1 9.4.22 OPERATION INSTRUCTIONS New South Wales Unit 2/1040 Canley Vale Road Wetherill Park NSW 2164 Ph: +61 2 9757 5800
More informationP.C. Simonton & Associates, Inc. Consulting Engineers. Paul C. Simonton
P.C. Simonton & Associates, Inc. Consulting Engineers 309 North Main Street 1050 Parkside Commons Post Office Box 649 Suite 101 Hinesville, Georgia 31310 Greensboro, Georgia 30642 Addendum No. One Date:
More informationA. This Section includes packaged engine-generator sets for [emergency] [standby] power supply with the following features:
SECTION 16231 - PACKAGED ENGINE GENERATOR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationEMERGENCY POWER SYSTEMS
263213 EMERGENCY POWER SYSTEMS PART 1: GENERAL 1.01 SUMMARY A. Section includes: 1. University guidelines for the installation of Emergency Power Systems (EPS). 2. Addresses the design and installation
More informationSPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS
SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification
More information1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.
SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in
More informationEccotemp L5 and L10 Comprehensive Troubleshooting Guide
http://waterheatertimer.org/tent-city-usa-water-heater.html Eccotemp L5 and L10 Comprehensive Listed below are some common questions and troubleshooting guidelines for our various models. Always remember
More informationFreightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3)
www.dometic.com Freightliner Refrigerator Troubleshooting Guide For Before initiating troubleshooting, the following equipment is recommended: Multimeter, 20 gauge (min) wires to use as jumpers, and 12Vdc
More informationRevitalize Building Mechanical Systems (4619)
SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof
More informationMASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc
MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page
More informationNarrative Reports As Regulated by 780 CMR, Section 903.0
EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for
More informationSite Address: Bldg./Suite #: Departments Phone Date Approval Signature A) Planning COMMENTS:
Development Services Department 135 N. 'D' Street P) 951-943-5003 F) 951-943-6504 www.cityofperis.org STEP 1: Prepare for your permit Before you can start this application/permit you will need the following:
More informationEvergreen Liquid Propane Conversion
Weil-McLain brings you a product announcement! Weil-McLain Product Bulletin PB1602 - February 15, 2016 Evergreen Liquid Propane Conversion Installing Propane Venturi In the event that conversion from natural
More informationSECTION INSPECTION AND TESTING OF WORK
SECTION 01455 PART I - GENERAL 1.01 SECTION INCLUDES A. Project Inspections and Procedures B. Scheduling Inspectors Notification requirements 1.02 RELATED SECTIONS A. Section 01310 COORDINATION B. Section
More informationSECTION GENERATOR PARALLELING CONTROLS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable
More informationFM-200 In-Cabinet Series
1. GENERAL SPECIFICATION 1.1 A total flooding, In-Cabinet fire suppression system, employing FM-200 superpressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by
More informationReplacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus
ADDENDUM FORM INVITATION TO TENDER: 2016-067 ADDENDUM NO: 1 DATE ISSUED: June 23, 2016 ISSUED BY: Monty Thibeault DESCRIPTION: Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus
More informationTT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps
TT-1023 1/97 INSTALLATION INSTRUCTIONS Original Issue Date: 2/94 Model: 6-2000 kw Market: Industrial Subject: Flush- or Surface-Mount Remote Annunciator Kits PA-293991 and PA-293991-SD The remote annunciator
More informationSECTION PACKAGED COMPRESSOR AND CONDENSER UNITS
SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply
More informationCold Weather Preparedness Plant Winterization Lessons Learned & Best Practices
Cold Weather Preparedness Plant Winterization Lessons Learned & Best Practices Cold Weather Preparedness RF Criteria For Plant Visits: Generating facilities that experienced repeated freezing or cold weather
More informationSITE REQUIREMENTS & INSTALLATION DSD-201 & SSD-102
Instructions SITE REQUIREMENTS & INSTALLATION DSD-201 & SSD-102 The purpose of this section is to provide the customer with requirements that need to be met before the DSD/SSD can be properly installed.
More informationDGC-500 DIGITAL GENSET CONTROLLER
DGC-500 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-500) offers a low cost microprocessor based integrated alternative for the control and monitoring of small to medium sized
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional
More informationFORM ACCL-PC1 ACCL WITNESS TEST PROCEDURE AND CHECKLIST
FORM ACCL-PC1 ACCL WITNESS TEST PROCEDURE AND CHECKLIST AHRI CERTIFICATION PROGRAM FOR AIR-COOLED WATER-CHILLING PACKAGES USING THE VAPOR COMPRESSION CYCLE ACCL Participant: Date of Test: Witness Test
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST DRY CLEANING Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved, R-Re-inspection
More informationOwners Manual Refrigerated Air Dryer MHT SERIES
Owners Manual Refrigerated Air Dryer MHT SERIES IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS IN- FORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILAR WITH THE PROPER INSTALLATION
More informationDesign & Construction Standards, Revised January
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.
More informationPCD/PEM Power Conversion Department - Equipment Lockout Procedure
September 2008 SR-384-041-42-R0 Page 1 of 7 Section A: Purpose and Scope Purpose: This procedure describes the authorization process and steps for safely locking out the 480 V power to QVB1, QVB2, QVB3
More informationSECTION COMMERCIAL-KITCHEN HOODS
SECTION 23 38 13 COMMERCIAL-KITCHEN HOODS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber
More informationSECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY
SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where
More informationREQUEST FOR PROPOSALS Grand Traverse County Board of Public Works (BPW) Department of Public Works (DPW) Shop Generator Set
REQUEST FOR PROPOSALS Grand Traverse County Board of Public Works (BPW) Department of Public Works (DPW) Shop Generator Set Proposals Due: 3:00 P.M., Friday October 7, 2016 Address Proposals to: DPW Shop
More informationDESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES
SECTION 21 30 00 FIRE PUMPS GENERAL This standard provides general requirements of The University of South Alabama in Mobile Alabama for fire pumps. This document is not intended to serve as a guide specification.
More informationGIRTON CABINET WASHER MODEL 794A
DESCRIPTION GIRTON CABINET WASHER MODEL 794A The washer shall be a Girton Model 794A Cabinet Type Pressure Washer constructed of type-304 stainless steel, utilizing a reciprocating header spray system.
More informationPOWER GENySYS P ROJECT E XPERIENCE I NFORMATION - D ISTRIBUTED G ENERATION
POWER GENySYS Burlington, Ontario. PORT COLBORNE GENERAL HOSPITAL Above: Entrance of,. 2 nd Hospital Cogeneration System in Ontario (1993) In 1993 Marsh Energy Inc. was awarded a turnkey contract by the
More informationLiebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet
The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation
More information