Micro-controller X C C1 C2 AL1 AL2 AL3. Model: PXR4/5/9. Operation Manual SEL PXR. ECNO:406e

Size: px
Start display at page:

Download "Micro-controller X C C1 C2 AL1 AL2 AL3. Model: PXR4/5/9. Operation Manual SEL PXR. ECNO:406e"

Transcription

1 C C1 C2 AL1 AL2 AL3 Micro-controller X Model: PXR4/5/9 PXR SEL Operation Manual ECNO:46e

2 Table of Contents Part Names and Functions... 6 Operations Parameter list Basic operations Parameter functions and method of settings Manual mode setting Standby setting Local/remote operation setting Ramp-soak control Canceling the alarm latch Au-tuning function... 2 ing ON-delay alarm or the remaining time of timers Setting alarm 1, 2 and Upper limit of alarm 1, 2 and Lower limit of alarm 1, 2 and Key lock Proportional band Integral time Derivative time Hysteresis range for ON/OFF control Cooling-side proportional band coefficient Cooling-side proportional band shift (Dead band/overlap band) Output offset value... 3 Anti-reset windup... 3 Control algorithm (Measured value) stable range HYS (Hysteresis) mode at ON/OFF control Cycle time of control output Cycle time of control output 2 (Cooling-side) Input signal code Setting the measuring range (Input range)... 4 Selection C / F... 4 Decimal point position (Measured value) offset (Setting value) offset Time constant of input filter Alarm types Selecting ramp-soak patterns Ramp-soak status display st 8th target st 8th ramp segment time st 8th soak segment time... 5 Ramp-soak modes

3 Specifying control action and output direction at input burn-out (Setting value) lower limiter (Setting value) upper limiter The time of ON-delay alarm or timer function ing current detecr input HB (Set value of heater break alarm) Hysteresis alarm 1, 2 and Options of alarm 1, 2 and Upper and lower limits for control output Upper and lower limits for control output Output limit types Output value display RCJ (Cold junction compensation) Adjusting the (Measured value) display (%) Adjusting the (Measured value) display (1%) DI1/2 (Digital input 1/2) operation Station No. for communication... 7 Parity for communication Communication procol setting Re-transmission output type setting Re-transmission base and span scale Remote input (%) adjustment Remote input (1%) adjustment Remote input filter constant Remote input value display Parameter display mask Troubleshooting Index

4 PXR4 PXR Digit Specification Note 4 <Front dimensions> 48 X 48mm 4 5 <Input signal> Thermocouple C Thermocouple F Resistance bulb Pt1 3-wire type C Resistance bulb Pt1 3-wire type F 1 5V DC 4 2mA DC 6 <Control output 1> Relay contact output Voltage pulse output (24V DC) 4 2mA DC output Note 1 7 <Control output 2> None Relay contact output Note 2 Voltage pulse output (24V DC) Note 2 4 2mA DC output Note 2 Re-transmission output (4 2mA DC) Note 2 8 <Revision code> 9 <Optional specifications 1> None Alarm (1 pc.) Alarm for heater break Note 3 Alarm (1 pc.) + Alarm for heater break Note 3 Ramp-soak Alarm (1 pc.) + Ramp-soak Alarm for heater break + Ramp-soak Note 3 Alarm (1 pc.) + Alarm for heater break + Ramp-soak Note 3 Alarm (2 pcs.) Alarm (2 pcs.) + Ramp-soak Alarm (2 pcs.) + Alarm for heater break + Ramp-soak Note 3 Alarm (3 pcs.) Remote Note 3 Remote + Alarm (2 pcs.) Note 3 1 <Instruction manual> <Power supply voltage> None 1 24V AC English 1 24V AC None 24V DC English 24V DC 11 <Optional specifications 2> 12 None 13 RS485 (Modbus) communication RS485 (ASCII) communication Digital input 1 point Digital input 2 points Note 4 RS485 (Modbus) communication + Digital input 1 point RS485 (ASCII) communication + Digital input 1 point T R N S A B A C E Y A C E R F G H M D P N V C B M N S T V W Note 1: Cannot be combined with heater break alarm. ( 2, 3, 6, 7, H cannot be specified on 9th digit.) Note 2: Cannot be combined with alarm (1 pc.) + heater break alarm, alarm (2 pcs.), or alarm (3pcs.). ( 3, 7, F, G, H, M, P cannot be specified on 9th digit.) Note 3: Cannot be combined with RS point digital input. (V and W cannot be specified on 11th digit.) Note 4: In the case of control output 2, either of heater break alarm or remote input can be selected. (A, C, E and R on the 7th digit, and 2,3,6,7,H, D and P on the 9th digit cannot be specified.) Input signal, measurement range, and set value at the time of deliver are as follows. When thermocouple is specified: Thermocouple K, Measurement range; 4 C, Set value; C When resistance bulb is specified: Pt, Measurement range; 15 C, Set value; C When voltage/current is specified: Scaling; 1%, Set value; % For the cases other than the above, specify input signal and measurement range. Input signal of the thermocouple and the resistance bulb can be switched by key operation on the front panel. The actuating method of the control output has been set reverse for control output 1, and direct for control output 2 at the time of delivery. Note that reverse and direct actuation can be switched by key operation on the front panel. 4

5 PXR5/9 PXR Digit Specification Note 4 <Front dimensions> 48 X 96mm 96 X 96mm 5 <Input signal> Thermocouple C Thermocouple F Resistance bulb Pt1 3-wire type C Resistance bulb Pt1 3-wire type F 1 5V DC 4 2mA DC 6 <Control output 1> Relay contact output Voltage pulse output (24V DC) 4 2mA DC output Note 1 7 <Control output 2> None Relay contact output Voltage pulse output (24V DC) 4 2mA DC output Re-transmission output (4 2mA DC) 8 <Revision code> 9 <Optional specifications 1> None Alarm (1 pc.) Alarm for heater break Note 2 Alarm (1 pc.) + Alarm for heater break Note 2 Ramp-soak Alarm (1 pc.) + Ramp-soak Alarm for heater break + Ramp-soak Note 2 Alarm (1 pc.) + Alarm for heater break + Ramp-soak Note 2 Alarm (2 pcs.) Alarm (2 pcs.) + Ramp-soak Alarm (2 pcs.) + Alarm for heater break + Ramp-soak Note 2 Alarm (3 pcs.) Remote Note 2 Remote + Alarm (2 pcs.) Note 2 1 <Instruction manual> <Power supply voltage> None 1 24V AC English 1 24V AC None 24V DC English 24V DC 11 <Optional specifications 2> 12 None 13 RS485 (Modbus) communication RS485 (ASCII) communication Digital input 1 point Digital input 2 points Note 3 RS485 (Modbus) communication + Digital input 1 point RS485 (ASCII) communication + Digital input 1 point 5 9 T R N S A B A C E Y A C E R F G H M D P N V C B M N S T V W Note 1: Cannot be combined with heater break alarm. ( 2, 3, 6, 7, H cannot be specified on 9th digit.) Note 2: Cannot be combined with RS point digital input. (V and W cannot be specified on 11th digit.) Note 3: In the case of control output 2, either of heater break alarm or remote input can be selected. (A, C, E and R on the 7th digit, and 2,3,6,7,H, D and P on the 9th digit cannot be specified.) Input signal, measurement range, and set value at the time of deliver are as follows. When thermocouple is specified: Thermocouple K, Measurement range; 4 C, Set value; C When resistance bulb is specified: Pt, Measurement range; 15 C, Set value; C When voltage/current is specified: Scaling; 1%, Set value; % For the cases other than the above, specify input signal and measurement range. Input signal of the thermocouple and the resistance bulb can be switched by key operation on the front panel. The actuating method of the control output has been set reverse for control output 1, and direct for control output 2 at the time of delivery. Note that reverse and direct actuation can be switched by key operation on the front panel. 5

6 1 Part Names and Functions This chapter explains the part names and functions on the face panel. The face panel has the and displays, the status indicating lamp, and the setting keys, etc. Those functions are explained below. Please read and understand them before using the PXR. For details about the setting of parameters, see Chapter w Lamp for control output 2 q Lamp for control output 1 e Alarm lamp C1 C2 AL1 AL2 AL3 C r (Measured value) display i lamp PXR SEL t (Setting value) display o Au-tuning/self-tuning/manual mode lamp y SEL key u keys q Lamp for control output 1 Lights up while control output 1 stays ON. w Lamp for control output 2 Lights up while control output 2 stays ON. e Alarm lamp Lights up on detecting an alarm. The alarm output is turned ON at the same time. If the optional heater break alarm is provided, the AL3 lamp lights up on detecting a heater break. r (Measured value) display s the. When setting a parameter, its name appears. t (Setting value) display s the. When setting a parameter, its value appears. y SEL key Used select a parameter block and a parameter, and register a set value. u keys Used change the, call parameters, and change parameter values. i lamp Lights up while the is displayed in the display. When parameters and data are displayed, the lamp goes out. o Au-tuning/self-tuning/manual mode lamp Flashes under an au-tuning or self-tuning operation. The lamp is kept on in manual mode. 6

7 2 Operations This chapter explains how set the (Setting value) and the parameters for the PXR. 2-1 Parameter list Parameters for the PXR are classified in operation parameters, and the first block, the second block and the third block parameters according the frequency of use. The second and the third block parameters are used at initialization or when they are absolutely necessary. Operation parameter Parameter display symbol () () Parameter display symbol Parameter name Measured temperature (Measurement value) Set temperature (Set value) Parameters of the first block Parameter name Manual mode selection Standby setting Remote/local setting Ramp-soak control Alarm latch cancel Set value of alarm 1 Lower limit value of alarm 1 Upper limit value of alarm 1 Set value of alarm 2 Lower limit value of alarm 2 Upper limit value of alarm 2 Set value of alarm 3 Lower limit value of alarm 3 Upper limit value of alarm 3 Description Switches between Au and Manual operation modes. Cancels the alarm latch. Timer 1 display s the remaining time of timer Timer 2 display s the remaining time of timer Timer 3 display s the remaining time of timer Sets the value at which alarm 1 is detected. Sets the lower limit value at which alarm 1 is detected. Sets the upper limit value at which alarm 1 is detected. Sets the value during which alarm 2 is detected. Sets the lower limit value at which alarm 2 is detected. Sets the upper limit value at which alarm 2 is detected. Sets the value at which alarm 3 is detected. Sets the lower limit value at which alarm 3 is detected. Sets the upper limit value at which alarm 3 is detected. Description s the currently measured temperature (Measurement value). Switches between RUN and Standby for control. Switches between remote and local operations. Au-tuning Used for setting the constants for,, and by au-tuning. is displayed when alarm type 1 is 15, or 32 34, and or is displayed when alarm type 1 is 16 3 is displayed when alarm type 2 is 15 or 32 34, and or is displayed when alarm type 2 is 16 3 is displayed when alarm type 3 is 15 or 32 34, and or is displayed when alarm type 3 is 16 3 Specifies whether or not allow the change of parameters. Setting range and Parameter facry default setting (*) mask DSP Setting not allowed. Setting range and facry default setting (*) on: Manual mode off: Au mode* on: Control standby (Output: OFF, Alarm: OFF) off: Control RUN* rem: Remote LoCL: Local off: Sp* run: Start HLd: Hold : Keeps the alarm latch.* 1: Opens up the alarm latch. : OFF (Resets the au-tuning or does not use it.)* 1: ON (Performs the au-tuning in the standard type.) 2: ON (Performs the au-tuning in low type ( value-1%fs).) - (Unit: seconds) - (Unit: seconds) - (Unit: seconds) When the alarm type is absolute value: 1%FS (*:1) When the alarm type is deviation: -1 1%FS (*:1) When the alarm type is absolute value: 1%FS (*:1) When the alarm type is deviation: -1 1%FS (*:1) When the alarm type is absolute value: 1%FS (*:1) When the alarm type is deviation: -1 1%FS (*:1) dp13-64 s the set temperature (Set value). 1%FS (*: %FS) Mask not allowed. : All settings are changeable both from the face panel and via communication.* 1: All settings are unchangeable from the face panel, but changeable via communication. 2: Only the is changeable from the face panel, and all settings are changeable via communication. 3: All settings are changeable from the face panel, but unchangeable via communication. 4: All settings are unchangeable from the face panel or via communication. 5: Only the is changeable from the face panel, but all settings are unchangeable via communication. User s set value Note: The parameters for which * is marked with the page number in Reference page are related Remedies of 4 on page 79. Reference page See page 78 for the method of turning on/off. 14 Parameter mask DSP dp13-32 dsp1-1 dp13-8 dsp1-2 dsp1-4 dsp1-8 dsp1-16 dsp1-32 dsp1-64 dsp1-128 dsp2-1 dsp2-2 dsp2-4 dsp2-8 dsp2-16 dsp2-32 dsp2-64 dsp2-128 dsp3-1 Reference page * 22 * 22 * 22 * 22 * 22 * 22 * 22 * 22 * 23 7

8 Parameters of the second block Note: The parameters for which * is marked with the page number in Reference page are related Remedies of 4 on page 79. Parameter display symbol Parameter name Proportional band Integral time Derivative time Hysteresis range for ON/OFF control Description Setting range and facry default setting (*) User s set value Parameter mask DSP Reference page Set. select the ON/OFF % (*: ) control (Two-position control). 32 seconds (*: 24) seconds (*: ) Sets the hysteresis for ON/OFF 5%FS (*: equivalent of C) control. dsp3-2 dsp3-4 dsp3-8 dsp * 27 Cooling-side proportional band coefficient. (*: ) dsp Cooling-side proportional band shift - + (*:.) dsp Output convergence value -1 1% (*: single., dual ) dsp Anti-reset windup 1%FS (*: 1%FS) dsp4-1 3 * Control algorithm Selects the control algorithm. PID: Runs normal PID control.* FUZY: Runs PID control with fuzzy logic. SELF: Runs PID control with self-running. dsp (Measured value) stable range Sets the stable range for the selftuning operation. 1%FS (*: 2%FS) dsp * Setting HYS (Hysteresis) mode Selects the hysteresis operation at ON/OFF control. off: Starts the two-position control at the values of +HYS/2 and -HYS/ on: Starts the two-position control at the values of and +HYS, or and -HYS.* dsp Cycle time of control output 1 Not shown at 4-2mA DC output RLY, SSR: 1 15 seconds (*: Contact output = 3, SSR/SSC-driven output = 2) dsp Cycle time of control output 2 (cooling-side) 1 15 seconds (*: 3) dsp Input signal code Set this parameter when changing the types of temperature sensors (*: specified by cusmer while ordering) Note 1 dsp Lower limit of measuring range (*: specified by cusmer while ordering) Note 1 dsp Upper limit of measuring range (*: specified by cusmer while ordering) Note 1 dsp5-1 4 Setting the decimal point position 2 (*: specified by cusmer while ordering) Note 1 dsp C / F selection (Measured value) offset (Setting value) offset Time constant of input filter C / F -1 1%FS (*: ) -5 5%FS (*: ). 9. seconds (*: ) dsp5-4 dsp5-8 dsp5-16 dsp * * Alarm type 1 Alarm type 2 Alarm type 3 Sets the types of alarm operations. Sets the types of alarm operations. Sets the types of alarm operations. 34 (*: /5) 34 (*: /9) 34 (*: ) dsp5-64 dsp5-128 dsp Status display of ramp-soak - (*: OFF) dsp6-2 5 Selecting rampsoak execute type Selects ramp-soak patterns. 1: Performs 1st 4th segments.* 2: Performs 5th 8th segments. 3: Performs 1st 8th segments. dsp st target value /Switching- value Sets the 1st target of ramp-soak operation. / Selected at switching- function for DI1 Within the limit. (*: %FS) dsp6-8 5 * First ramp segment time Sets the first ramp segment time. 99h59m (*:.) dsp

9 Note: The parameters for which * is marked with the page number in Reference page are related Remedies of 4 on page 79. Parameter display symbol Parameter name Description Setting range and facry default setting (*) User s set value Parameter mask DSP Reference page 1st soak segment time Sets the 1st soak segment time. 99h59m (*:.) dsp nd target Sets the 2nd target of ramp-soak operation. Within the limit. (*: %FS) dsp6-64 * 5 2nd ramp segment time Sets the 2nd ramp segment time. 99h59m (*:.) dsp nd soak segment time Sets the 2nd soak segment time. 99h59m (*:.) dsp rd target Sets the 3rd target of ramp-soak operation. Within the limit. (*: %FS) dsp7-2 * 5 3rd ramp segment time Sets the 3rd ramp segment time. 99h59m (*:.) dsp rd soak segment time Sets the 3rd soak segment time. 99h59m (*:.) dsp th target Sets the 4th target of ramp-soak operation. Within the limit. (*: %FS) dsp7-16 * 5 4th ramp segment time Sets the 4th ramp segment time. 99h59m (*:.) dsp th soak segment time Sets the 4th soak segment time. 99h59m (*:.) dsp th target Sets the 5th target of ramp-soak operation. Within the limit. (*: %FS) dsp7-128 * 5 5th ramp segment time Sets the 5th ramp segment time. 99h59m (*:.) dsp th soak segment time Sets the 5th soak segment time. 99h59m (*:.) dsp th target Sets the 6th target of ramp-soak operation. Within the limit. (*: %FS) dsp8-4 * 5 6th ramp segment time Sets the 6th ramp segment time. 99h59m (*:.) dsp th soak segment time Sets the 6th soak segment time. 99h59m (*:.) dsp th target Sets the 7th target of ramp-soak operation. Within the limit. (*: %FS) dsp8-32 * 5 7th ramp segment time Sets the 7th ramp segment time. 99h59m (*:.) dsp th soak segment time Sets the 7th soak segment time. 99h59m (*:.) dsp th target Sets the 8th target of ramp-soak operation. Within the limit. (*: %FS) dsp9-1 * 5 8th ramp segment time Sets the 8th ramp segment time. 99h59m (*:.) dsp th soak segment time Sets the 8th soak segment time. 99h59m (*:.) dsp9-4 5 Ramp-soak mode Selects the power-on start, repeat, and standby functions for ramp-soak operations. 15 (*: ) dsp9-8 5 Note 1: When a cusmer does not specify the settings while ordering, the following settings are selected as facry defaults. Thermocouple input: Thermocouple K Measured range: 4 C Resistance bulb input: Measured range: 15 C Voltage/Current input: Scaling: 1% 9

10 Parameters of the third block Note: The parameters for which * is marked with the page number in Reference page are related Remedies of 4 on page 79 Parameter display symbol Parameter name Description Setting range and facry default setting (*) User s set value Parameter mask DSP Reference page Control action Specifies control action and output at the input burn-out. 19 (*: specified by cusmer while ordering) Note 2 dsp (Setting value) lower limiter Sets the lower limit of the. 1%FS (*: %FS) dsp9-32 * 54 (Setting value) upper limiter Sets the upper limit of the. 1%FS (*: 1%FS) dsp9-64 * 54 Delay time 1 Delay time 2 Delay time 3 Current transe display HB (Set value of heater break alarm) setting Alarm 1 hysteresis Delay time or timer value for alarm 1 relay seconds (*: ) Delay time or timer value for alarm 2 relay seconds (*: ) Delay time or timer value for alarm 3 relay seconds (*: ) s the current detecr input value for HB alarm. - Sets the operation value that detects the heater break. Sets the hysteresis range of ON and OFF of alarm A (Setting.A turns off the HB alarm.) (*:.) 5%FS (*: 1) dsp9-128 dp1-1 dp1-2 dp1-4 dp1-8 dp * 59 Alarm 2 hysteresis Sets the hysteresis range of ON and OFF of alarm 5%FS (*: 1) dp1-32 * 59 Alarm 3 hysteresis Sets the hysteresis range of ON and OFF of alarm 5%FS (*: 1) dp * Alarm 1 options Sets the optional functions of alarms 1, 2 and 111 (*: ) dp Alarm 2 options Alarm 3 options Alarm latch (1: use, : not use) Alarm of error status (1: use, : not use) De-energized output (1: use, : not use) 111 (*: ) 111 (*: ) dp11-1 dp Lower limit for output 1 Sets the lower limit for output - 1% (*: -) dp Upper limit for output 1 Sets the upper limit for output - 1% (*: 1) dp Lower limit for output 2 Sets the lower limit for output - 1% (*: -) dp Upper limit for output 2 Sets the upper limit for output - 1% (*: 1) dp Output limit types Sets the limit types of outputs 1 and 2 (breaking the limit, or maintained within the limit). 15 (*: ) dp Output value (MV) display s the value of output - dp Output value (MV) display s the value of output - dp RCJ (Cold junction compensation) setting Sets the cold junction compensation function ON/OFF. ON: Performs the RCJ (Cold junction compensation).* OFF: Does not perform the RCJ (Cold junction compensation). dp gradient.1 (*: ) dp12-4 User-definable zero adjustment Shifts the zero point of input value. -5 5%FS (*: ) dp12-8 * 66 User-definable span adjustment Shifts the span of input value. -5 5%FS (*: ) dp12-16 * 66 DI1 (Digital input 1) operation Sets the DI1 operations. 12 (*: =OFF) dp DI2 (Digital input 2) operation Sets the DI2 operations. 12 (*: =OFF) dp Station No. Sets the station No. for communication. 255 (Setting does not start the communications function.) (*: 1) dp Parity setting Sets the parity for communication. (The baud rate is fixed at 96bps. : Odd parity* 1: Even parity 2: No parity dp Note 2: The following settings are selected as facry defaults depending on the model you order. Seventh digit = Y model: Seventh digit = A model: 4 1

11 Note: The parameters for which * is marked with the page number in Reference page are related Remedies of 4 on page 79. Parameter display symbol Parameter name Description Setting range and facry default setting (*) User s set value Parameter mask DSP Reference page Communication procol setting Switches communication procols between Modbus and ASCII : Z-ASCII 1 : Modbus (RTU) dp Re-transmission output type setting Sets the type of signals be outputted from re-transmission output. Setting range : / 1 : / 2 : MV/ 3 : DV (* : ) dp Re-transmission output scaling base side setting Re-transmission output scaling setting on the base side Setting range - % (*:.) dp Re-transmission output scaling span side setting Re-transmission output scaling on the span side Setting range - % (*: ) dp Remote input zero adjustment Shifts the zero point of input value. -5 5%FS (*: ) dp Remote input span adjustment Shifts the span point of input value. -5 5%FS (*: ) dp Remote input filter constant Sets the filter constant of remote input value.. 9. seconds (*:.) dp Remote input value display s remote input value. - dp Parameter mask Sets whether or not display each parameter. 255 (*: specified by cusmer while ordering) 78 11

12 2-2 Basic operations Just after power-on: The display below appears just after power-on. C1 C2 AL1 AL2 AL3 C C1 C2 AL1 AL2 AL3 C PXR SEL Status at delivery <In Au mode> PXR SEL <In Manual mode> How switch parameters: The figure below shows the basic operations for the PXR. Just after power-on (/ displayed) Setting parameters C C1 C2 AL1 AL2 AL3 Changes. Not operated for 3 seconds. SEL PXR SEL SEL SEL (approx. (approx. (approx. 1 second) 3 seconds) 5 seconds) SEL SEL Parameters of the first block Parameters of the second block Parameters of the third block Pressing and holding the keys makes the value increase or decrease fast. Basic operations for the PXR (In Au mode) 12

13 Just after power-on (/MV displayed) (/ displayed) Setting parameters Not operated for 3 seconds. C C1 C2 AL1 AL2 AL3 SEL C C1 C2 AL1 AL2 AL3 Changes MV. PXR SEL SEL PXR SEL Changes. SEL SEL SEL (approx. (approx. (approx. 1 second) 3 seconds) 5 seconds) SEL SEL Parameters of the first block Parameters of the second block Basic operations for the PXR (In Manual mode) Parameters of the third block Pressing and holding the keys makes the value increase or decrease fast. How set values: key: One press increases the value by Press and hold this key increase the value fast. key: One press decreases the value by Press and hold this key decrease the value fast. How register the set data: By pressing the SEL key, the displayed values are registered. Note that the () will be registered in 3 seconds without any operation. 13

14 2-3 Parameter functions and method of settings Method of setting the (Setting value) The is a target value for control. Any that is outside of the range set in the parameters of (lower limit) and (upper limit) of the third block cannot be set. (See page 5) Related parameters: (page 54) (page 54) [Setting example] Changing the from 25 C 1195 C Press the or keys display. will be registered in the () in three seconds. After that, the controller will operate with the being

15 Manual mode setting (Settings: off/on) This parameter switches the control mode between Au and Manual. During Manual operation, the decimal point is kept on at the far right in the display section. During Manual operation, au tuning or self tuning is not done. If the mode is switched Manual while au or self tuning is being done, the tuning is forcibly terminated. The PID parameter remains the same in such cases. Manual operation output is not limited by MV limit. Manual operation can be carried out during standby operation. The operation output set value during Au/Manual operation mode and manual mode is sred in non-volatile memory. It is kept sred even if a power interruption occurs. When the power is turned on again, the state before the power interruption is resumed. The following table lists the operation output at the time of switching between Au and Manual.. Au Manual Manual Au Balanceless bumpless MV output according (Switches manual mode, PID operation holding the MV value just (Sudden change may occur before the switching.) the MV value.) Manual MV Manual Single output Manual PID calculation AUTO MAnU = ON P-n1 = Single Dual output MV1 MV2 Au Au Limit Limit Standby Standby Error output Error output OUT1 OUT2 Manual [Setting example] Switching manual mode Press and hold the SEL key for one second, and is displayed. Press the SEL key once, and the current set value ( ) on the display section starts flickering. Press the or the keys display. Press the SEL key once, and the manual lamp at the lower right corner comes on, indicating that the mode has been switched Manual. To display operation status, press and hold the SEL key for two seconds. 15

16 Standby setting (Settings: off/on) This parameter switches the control between RUN and Standby. During standby, the control output and the alarm output stay OFF, like the standby for ramp-soak operation. While the alarm with a hold is selected, the hold function takes effect after changing the Standby setting from ON OFF. is displayed during the standby for ramp-soak operations or the controller changes the standby state in case of the occurrence of errors. The other operations are the same as those of the rampsoak standby. The setting of ON/OFF for standby is saved after poweroff. When the standby is set ON during the au-tuning, self-tuning, and ramp-soak operations, those operations will sp. (The PID constant will not be renewed.) Even through it is set OFF later, the au-tuning, self-tuning, and ramp-soak operations will not be re-started. During standby, the ON-delay timer is reset. When returning RUN from the standby state, the timer will start from the beginning. [Setting example] Starting the control Press and hold the SEL key for one second. will be displayed. Then press the key once. The current setting ( ) flashes on the display. Press the or keys display. The standby state for control is selected. (control output and all the alarm outputs: OFF) If you want display the operation status, press and hold the SEL key for two seconds. The value on the display will flash, indicating the standby status. 16

17 Local/remote operation setting (Setting range: LoCL/rEM) (Option) This parameter is used switch between local and remote operations. Set value Operation Performs local operation. Performs remote operation. ( and the set value () are displayed alternately in the display section on the front face while in remote operation.) Related parameters: (page 75) (page 75) (page 76) (page 77) * Local operation: Control by set by the keys on the front face, ramp-soak operation, selection determined by digital input, and setting via communication * Remote operation: Control by determined by Remote input [Setting example] Switching remote operation Press and hold the SEL key for one second. will be displayed on the display section. Press the keys display. The current setting ( ) in the display section flickers. Press the keys display. Flickering sps and the operation is switched remote. To display the operation status, press and hold the SEL key for two seconds. 17

18 Ramp-soak control (Settings: off/run/hld) (Option) This function aumatically changes the (Setting value) according the program pattern set in advance as shown in the right line graph. Up eight pairs of rampsoak operation can be programmed. The first ramp starts at the (Measured value) that is the one just before running the program. The program can also aumatically run at power-on (Power-on starting function). Refer the parameter of (page 47). Related parameters: (page 5) (page 5) (page 5) (page 5) (page 5) (page 49) Up First ramp TM1r First soak Second ramp Second soak Third ramp Ramp: the section in which the changes ward the target value. Soak: the section in which the is the target value, and remains unchanged. Third soak TM1S TM2S TM3S TM2r TM3r Fourth ramp TM4r Fourth soak TM4S Up TM8s Up TM8r [Setting example] Starting the ramp-soak operation Press and hold the SEL key for one second. will be displayed on the display. Press the key display The current setting ( ) flashes on the display. Press the or keys display. Then, the program will start according the ramp-soak pattern that is set in advance. If you want display the operation status, press and hold the SEL key for two seconds. 18

19 Canceling the alarm latch (Setting range: /1) (Option) This parameter cancels the alarm latch when it is latching. Related parameters: (page 6) [Setting example] Opening up the alarm latch Press and hold the SEL key for one second. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the or keys display. will sp flashing and will change in a few seconds. If you want display the operation status, press and hold the SEL key for two seconds. 19

20 Au-tuning function (Settings: /1/2) [Note] If the controller is powered off during au-tuning, this makes the au-tuning ineffective with each parameter of,, and unchanged. To start the au-tuning operation, set 1 or 2 again. To suspend the au-tuning, set. This makes the au-tuning cancel with each parameter of,, and unchanged. Once the parameters of,, and are set aumatically by the au-tuning, those parameters are sred in the controller even after it is powered off. Therefore, it is not necessary execute the au-tuning again. By setting 1 or 2, the au-tuning operation starts, and at the end of the tuning, will be displayed aumatically. After the au-tuning operation, the controller starts operate at the aumatically set values of,, and. A decimal point at the right end of the display flashes during au-tuning. There are two codes for AT: Setting code [1]: standard type Performs the au-tuning based on the. Setting code [2]: Low type Performs the au-tuning based on the -1%FS. [Note] Since ON/OFF control is performed during au-tuning, overshoot against the may occur. To reduce the overshoot, execute the au-tuning operation with the setting code [2] (Low ) selected. The au-tuning can be executed both just after power-on and in a control or stable status. Related parameters: (page 24) (page 25) (page 26) (page 3) (page 28) [Setting example] Setting the au-tuning operation 1 Press and hold the SEL key for one second. will be displayed on the display. 7. Press the key display. The current setting ( ) flashes on the display. Press the or keys display. will sp flashing and the au-tuning will start. During au-tuning, a decimal point at the right end of the display flashes. When the au-tuning finishes properly, a decimal point sps flashing, and the set values of,, and parameters change. When the au-tuning finishes abnormally, a decimal point sps flashing, but the set values of,, and parameters remain unchanged. If you want display the operation status, press and hold the SEL key for two seconds. 2

21 ,, ing ON-delay alarm or the remaining time of timers (unit: seconds) (Option) These parameters display the remaining time of Timers display parameter 1, 2 and The remaining time of the ON/OFF-delay timer is counted down. When the counter shows, the alarm relay is closed. Remaining time (seconds) During count-down, if the changes the value of the temperature at which the alarm is set OFF, or if DI for the timer is set OFF, the counter is reset, and the alarm relay is opened. [Setting example] ing ON-delay alarm or the remaining time of timers Press and hold the SEL key for one second. will be displayed. Press the key display. The remaining time of timer 1 will be displayed. Press the or keys display the remaining time of, and. If you want display the operation status, press and hold the SEL key for two seconds. 21

22 Setting alarm 1, 2 and 3 Upper limit of alarm 1, 2 and 3 Lower limit of alarm 1,2 and 3 (Setting range: Absolute value alarm: 1%FS Deviation value alarm: -1 1%FS ) }(Option) These parameters are used for settings of alarm 1, 2 and When the alarm type (, or ) is set 15, alarms 1, 2 and 3 (, and ) can be set. When the alarm type (, or ) is set any value other than 15, the upper and lower limits of alarm 1, 2 and 3 (,,,,, ) can be set. [Note] Setting codes (12 15) cannot be selected in alarm type 1 and 3 ( / ). Related parameters:,, (page 46),, (page 59),, (page 55),, (page 6) [Setting example] Setting the operation value of alarm 2-1 C Press and hold the SEL key for one second. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the or keys display. will sp flashing and will be registered for. After that, the controller will operate with the operation value of alarm 2 being -1 C. If you want display the operation status, press and hold the SEL key for two seconds. 22

23 Key lock (Setting range: 5) This parameter makes the set values of parameters unchangeable. However, the parameter name and the set values can be displayed. To reset the key lock, change. Even when the key lock is set, control and alarm functions can operate properly. There are six levels of the key lock: : Unlocked (reset) : All settings are unchangeable from the controller, but changeable via communication. : Only the is changeable from the controller, and all settings are changeable via communication. : All settings are changeable from the controller, but unchangeable via communication. : All settings are unchangeable from the controller or via communication. : Only the is changeable from the controller, but all settings are unchangeable via communication. [Setting example] Setting the key lock 2 Press and hold the SEL key for one second. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the or keys display. will sp flashing and will be registered for. After that, any setting other than the cannot be changed from the front panel. If you want display the operation status, press and hold the SEL key for two seconds. 23

24 Proportional band (Setting range: % of the measured range) To select the ON/OFF control (two-position control), set.. It is not necessary set and. can be aumatically set by the au-tuning operation. When is o small, control will be unstable, and when is o large, the response will be delayed. Set the hysteresis of the ON/OFF control (two-position control) in the parameter. If au-tuning is run after the ON/OFF control is selected, the ON/OFF control changes the PID control. To keep the ON/OFF control selected, do not execute the autuning. [Setting example] Changing the proportional band from % 1% Press and hold the SEL key for three seconds. will be displayed on the display. The current setting ( ) flashes on the display. Press the or keys display. controller will operate with being 1%. will sp flashing and will be registered for. After that, the If you want display the operation status, press and hold the SEL key for two seconds. 24

25 Integral time (Setting range: 32 seconds) can be set aumatically by the au-tuning operation. can also be set manually. When is set, the integral operation does not start. When is set., this makes the setting of ineffective. [Setting example] Changing the integral time from 24 seconds 6 seconds Press and hold the SEL key for three seconds. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the or keys display. will sp flashing and will be registered for. After that, the controller will operate with being seconds. If you want display the operation status, press and hold the SEL key for two seconds. 25

26 Derivative time (Setting range: seconds) can be set aumatically by the au-tuning operation. can also be set manually. When is set, the differential operation does not start. When is set., this makes the setting of ineffective. [Setting example] Changing the differential time from seconds seconds Press and hold the SEL key for three seconds. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the or keys display. will sp flashing and will be registered for. After that, the controller will operate with being seconds. If you want display the operation status, press and hold the SEL key for two seconds. 26

27 Hysteresis range for ON/OFF control (Setting range: 5%FS) To select the ON/OFF control (two-position control), set.. It is not necessary set and. When the hysteresis range (Range of ON/OFF control) is o small, the output may switch the ON/OFF frequently. (This may affect the life of the device be controlled, especially when contact output is selected.) The unit of the set value of this parameter is C or F (engineering unit). The setting range varies according the measured range of input. [Ex] Input Thermocouple K : At measured range of 4 C, the setting range is 2 C. Resistance bulb : At measured range of 15 C, the setting range is 75 C. Related parameters: (page 24) (page 36) [Setting example] Changing the hysteresis range from 1 C 35 C Press and hold the SEL key for three seconds. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the or keys display. will sp flashing and will be registered for. After that, the controller will operate with the hysteresis range being 35 C. If you want display the operation status, press and hold the SEL key for two seconds. 27

28 Cooling-side proportional band coefficient (Option: Available for DUAL output only) (Setting range:. ) This parameter is used for setting the cooling-side proportional band. (See the figure below.) Heating side Heating-side proportional band Output 5 Cooling-side proportional band Proportional band (P) Cooling side Coefficient:.5 Coefficient: Coefficient: MV Before setting the cooling-side proportional band, set the heating-side proportional band an optimum value. To select the two-position control for the cooling side, set.. Cooling-side Proportional band (P) = Coefficient proportional band 2 When is set. and is set. in the dual output type, the cooling output is as shown in the figure below. The hysteresis is fixed at.5%fs. Heating output (Output 1) Cooling output (Output 2) ON.5%.5% ON OFF OFF HYS DB Related parameters: (page 27) (page 24) (page 29) Ex) When making the proportional band of 1% of the full scale with the proportional band (P) being 5%: 5% 1% = Coefficient 2 Consequently, the coefficient is. [Setting example] Changing the cooling-side proportional band coefficient from 5 Press and hold the SEL key for three seconds. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the or keys display. will sp flashing and will be registered for. After that, the controller will operate with the cooling-side proportional band coefficient being If you want display the operation status, press and hold the SEL key for two seconds. 28

29 Cooling-side proportional band shift (Dead band/overlap band) (Option: Available for DUAL output only) (Setting range: - +) This parameter is used for shifting the cooling-side proportional band from the set value. (See the figure below.) and when it is a negative value, the Overlap band. When is a positive value, it is called the Dead band, Since the unit of is same one used for MV [%], if you Output want set in the unit of deviation [%], must be Heating side Cooling side converted using the equation below. MV Overlap band Dead band MV 1 DB [%] = Deviation [%] P Ex) When making a dead band with a deviation of [%] from the while the proportional band (P) is %: 1 DB [%] = = 2 [%] MV=5% Consequently, set the parameter 2 [%]. Related parameters: (page 24) [Setting example] Shifting the cooling-side proportional band by Press and hold the SEL key for three seconds. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the or keys display. will sp flashing and will be registered for. After that, the controller will operate with being %. If you want display the operation status, press and hold the SEL key for two seconds. 29

30 Output offset value (Setting range: - %) Anti-reset windup (Setting range: 1%FS) The anti-reset windup ( ) is aumatically set an optimum value by the au-tuning operation. By setting, the amount of overshoot can be adjusted. [Note] By making use of the fuzzy control system equipped with PXR, the amount of overshoot can be minimized without setting and. AR value AR value } } In this range, the integral operation is not performed. In this range, the integral operation is performed. } In this range, the integral operation is not performed. [Setting example] Changing the anti-reset windup from 6 C 8 C. Press and hold the SEL key for three seconds. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the or keys display. will sp flashing and will be registered for. After that, the controller will operate with the anti-reset windup being 8 C. If you want display the operation status, press and hold the SEL key for two seconds. 3

31 Control algorithm (Settings: PID/FUZY/SELF) This parameter is used for selecting PID control, FUZZY- PID control, or PID control with self-tuning. To select the PID control or FUZZY-PID control, it is necessary set the parameters of,,, and manually or by the au-tuning in advance. For the ON/OFF control (Two-position control), select the PID control and then set.. For detailed information, refer (page 24). Refer the next page for the PID control with self-tuning. [Setting example] Changing the control system from PID FUZZY Press and hold the SEL key for three seconds. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the or keys display. will sp flashing and will be registered for. After that, the controller will operate with the FUZZY control system activated. If you want display the operation status, press and hold the SEL key for two seconds. 31

32 [Self-tuning] 1 Function: With the self-tuning function, PID parameters are aumatically re-optimised depending on the actual condition of device be controlled and the setting temperature (). 2 How execute: Follow the procedure shown below set and execute the self-tuning. The self-tuning starts run at the appropriate conditions. (See page 31) q Power on the PXR. w Set the. e Select in the parameter of.* 1 r Power off the PXR. If the device that is be controlled has powered ON at this point: Wait until the temperature of the device that is be controlled falls and stabilizes. To re-start the self-tuning: Select in the parameter of. t Power on the device be controlled. y Power on the PXR. The device be controlled and the PXR should be powered ON at the same time or in order of the left flowchart. (Tuning / Control) * 2 *1: How set the parameter of : SEL SEL *2: during self-tuning is shown below: This lamp flashes. 32

33 3 Conditions under which the self-tuning runs: q At power-on: The self-tuning runs when all of the following conditions are met. The that appears at power-on is not the same one when the,,, and were set previously. (i.e. the,,, and set by the self-tuning, au-tuning, manual setting, and writing by communications ols at previous time) The (-) at power-on is larger than (the value of input range) or (the set value of ). w When the is changed: The self-tuning runs when all the conditions below are met. The changed is larger than the that was set when the,,, and were selected previously. The changed amount of the is larger than. The changed amount of the is larger than (the set value of input range) or (the set value of ). e When output becomes unstable: The self-tuning runs when control becomes unstable and the hunting of the operating output (MV) occurs. (The selftuning runs only once as long as the is not changed.) r When the control standby mode is cancelled: The self-tuning runs by the same reason as q At power-on are met. * Only when the PXR is set standby mode at power-on. 4 Conditions under which the self-tuning does not run: q During control standby mode w During two-position control (Parameter of = ) e During au-tuning operation r During ramp-soak operation t Error display ( or is displayed.) y During dual output (The set value of the parameter of is larger than ) u When setting the parameters of,,, and manually (including the setting written by communications ols) 5 Conditions under which the self-tuning is suspended: q At the condition described in 4 shown above w When the is changed during self-tuning operation e When the self-tuning operation can not be completed within approx. 9 hours 6 Caution q Once the PID constant is set, the self-tuning does not operate at next power-on as long as the is not changed. w For an accurate tuning, be sure power on the device be controlled before or at the same time as the PXR is powered on. If the PXR has be powered on first for reasons of the system configuration, perform the au-tuning with the PID or FUZZY control. e If the device be controlled is powered on under temperature change (especially when it rises), accurate tunings can not be performed. Be sure power on the PYX when the temperature of device be controlled is stabilized. r The self-tuning does not run for cooling system control under Direct Action output (Parameter = 2 or 3). t In case the control is not stable after performing the self-tuning, change the algorithm the PID or FUZZY control and perform the au-tuning. 33

34 7 Reference [About the self-tuning method] The PID constant is calculated in one of the following two methods. The method is selected aumatically depending on the characteristics of the device be controlled. Step response method Limit cycle method The following figures show the operations at power-on and changing the, and under unstable control. q Operations at power-on Step response method Limit cycle method During tuning Time During tuning Time w Operations at changing the Step response method Limit cycle method Changing the Changing the During tuning Time During tuning Time e Operation under unstable control Limit cycle method Unstable control During tuning Time 1% MV 34

35 (Measured value) stable range (Setting range: 1%FS) Self-tuning logic recognizes that control is stable if is staying within the ±. It is not necessary set this parameter under normal conditions. [Setting example] Changing the stable range from 2 3 Press and hold the SEL key for three seconds. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the or keys display. will sp flashing and will be registered for. After that, the controller will operate with the range being If you want display the operation status, press and hold the SEL key for two seconds. 35

36 HYS (Hysteresis) mode at ON/OFF control (Settings: off/on) This parameter is used for selecting the hysteresis operation mode at ON/OFF control. onof : OFF onof : ON : Starts the ON/OFF control at the values of HYS HYS + and : Starts the ON/OFF control at the values of and +HYS, or and -HYS. Default setting: ON Reverse action Direct action HYS HYS HYS HYS [Setting example] Setting the hysteresis mode ON Press and hold the SEL key for three seconds. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the key display. will sp flashing and will be registered for. After that, the controller will operate with the hysteresis being as shown in the figure of ON above. If you want display the operation status, press and hold the SEL key for two seconds. 36

37 Cycle time of control output 1 (Setting range: 1 15 seconds) This parameter is applicable for the contact output and SSR-driving output. While input is within the proportional band, output changes between ON and OFF in cycles. These cycles are called cycle time. Output: ON Cycle time Cycle time Do not set this parameter "". For contact output: The higher the frequency of output is, the more precise the control becomes. However a high frequency of output may shorten the life of the contacts and the device be controlled. Be sure adjust the proportional cycles considering controllability and the life of the device and the contacts. Typical: 3 seconds For SSR-driving output: Use in short cycles if there is no problem with the device be controlled. Typical: 1 2 seconds [Setting example] Setting the cycle time from 3 seconds 2 seconds Press and hold the SEL key for three seconds. will be displayed on the display. Press the key display. The current setting ( ) flashes on the display. Press the or key display. will sp flashing and will be registered for. After that, the controller will operate with the cycle time being 2 seconds. If you want display the operation status, press and hold the SEL key for two seconds. 37

CONTENTS. Micro-controller X Model : PXR5/9. Instruction Manual. INP-TN1PXR5/9f-E

CONTENTS. Micro-controller X Model : PXR5/9. Instruction Manual. INP-TN1PXR5/9f-E Instruction Manual Micro-controller X Model : PXR5/9 INP-TNPXR5/9f-E International Sales Div Sales Group Gate City Ohsaki, East Tower, -, Osaki -chome, Shinagawa-ku, Tokyo 4-, Japan http://www.fujielectric.com

More information

CONTENTS. Micro-controller X Model : PXR3. Instruction Manual

CONTENTS. Micro-controller X Model : PXR3. Instruction Manual Instruction Manual Micro-controller X Model : PXR3 INP-TN1PXR3c-E Head Office 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo, 141-32 Japan Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo,

More information

CONTENTS. Micro-controller X Model : PXR5/9. Instruction Manual

CONTENTS. Micro-controller X Model : PXR5/9. Instruction Manual Instruction Manual Micro-controller X Model : PXR5/9 INP-TNPXR5/9-E Head Office -, Osaki -chome, Shinagawa-ku, Tokyo, 4-3 Japan Sales Div. International Sales Dept. No., Fuji-machi, Hino-city, Tokyo, 9-85

More information

CONTENTS. Micro-controller X Model : PXR4, PXR7. Instruction Manual. INP-TN1PXRj-E

CONTENTS. Micro-controller X Model : PXR4, PXR7. Instruction Manual. INP-TN1PXRj-E Instruction Manual Micro-controller X Model : PXR4, PXR7 INP-TNPXRj-E Head Office Gate City Ohsaki, East Tower, -2, Osaki -chome, Shinagawa-ku, Tokyo 4-32, Japan http://www.fesys.co.jp/eng Instrumentation

More information

CONTENTS. Instruction Manual Micro-controller X Model: PXR4

CONTENTS. Instruction Manual Micro-controller X Model: PXR4 Instruction Manual Micro-controller X Model: PXR4 INP-TN1PXRa-E Fuji Electric Co., Ltd. Head Office 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo, 141-32 Japan http://www.fujielectric.co.jp Fuji Electric Instruments

More information

F4 Process Controller Installation and Operation Guide

F4 Process Controller Installation and Operation Guide F4 Process Controller Installation and Operation Guide 1.Introduction 1.1.Highlight Features Space saving, only 55mm panel depth required Higher sampling rate (1mS) results in better control performance

More information

MICRO CONTROLLER S Z SERIES

MICRO CONTROLLER S Z SERIES Instruction Manual MICRO CONTROLLER S Z SERIES TYPE: PYW 4 5 7 9 Fuji Electric Co.,Ltd. INP-TN1PYWf-E INTRODUCTION You are now the owner of Fuji's digital Temperature Controller. Before using, be sure

More information

Example of Applications and Parameter Functions

Example of Applications and Parameter Functions PX-series digital temperature controller Example of Applications and Functions ECNO:1158 I. Example of Applications 1 Controlling both heating and cooling with a single controller Only one controller is

More information

Communications None RS-232C RS-422* RS-485* BCD Transmission output*/** (4 to 20 ma) E5AX- E5AX- L(M)A02 L(M)A03

Communications None RS-232C RS-422* RS-485* BCD Transmission output*/** (4 to 20 ma) E5AX- E5AX- L(M)A02 L(M)A03 Digital Controller A 96 x 96-mm (DIN) Digital Process Controller Optimum PID control with feed-forward control circuitry. High accuracy (+0.3% FS +1 digit max.). Replaceable Output Units. Models with communications

More information

CONTENTS. Micro-controller X. Instruction Manual. (Socket type) Model : PXR4 Socket INP-TN1PXR4S-E

CONTENTS. Micro-controller X. Instruction Manual. (Socket type) Model : PXR4 Socket INP-TN1PXR4S-E Instruction Manual Micro-controller X (Socket type) Model : PXR Socket INP-TNPXRS-E Head Office Gate City Ohsaki, East Tower, -, Osaki -chome, Shinagawa-ku, Tokyo -, Japan http://www.fesys.co.jp/eng Instrumentation

More information

CN4800 Series CONTROLLER

CN4800 Series CONTROLLER CN4800 Series CONTROLLER Operator's Manual PV SV OUT1 OUT2 ALM1 ALM2 SEL M1791/0502 Contents I. PREPARING THE OPERATION... 4 1. THE BASIC INSTALLATION PROCEDURE... 5 2. CHECK OF SPECIFICATIONS... 6 2.1

More information

Temperature Controllers

Temperature Controllers Model TEC-4100 1/4 DIN Model TEC-4100 1/4 DIN Temperature Controller Ordering Code: Power Input BOX 1 4 = 90-250 VAC 5 = 11-26 VAC / VDC TEC-4100- Configurable for 4 Programmable Outputs and NEMA 4X/IP65

More information

Micro Controller PXR Series

Micro Controller PXR Series Digital Temperature Controller Micro Controller PXR Series 2B-E-002 PXR Micro Controller PXR [] Features ( Except PXR3 ) [ 99mm ] [ 89mm ] [ 7272mm ] [ 88mm ] [ 28mm ] option RS8 communication Digital

More information

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER FCS-23A

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER FCS-23A INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER Thank you for your purchase of our Microcomputer based Temperature Indicating Controller. This manual contains instructions

More information

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1 VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1. INTRODUCTION This manual contains information for the installation and operation and tuning of our Vertex VT10 series self-tuning

More information

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER JCD-13A, JCR-13A

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER JCD-13A, JCR-13A INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER JCD-13A, JCR-13A Preface Thank you for the purchase of our Microcomputer based Temperature Indicating Controllers JCD-13A or

More information

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS EN0I-6041 4/01 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC1000 and UDC1500 are microprocessor-based 1/16 DIN and 1/8 DIN controllers

More information

TEMPERATURE CONTROL MODULE MODEL R3-TC2

TEMPERATURE CONTROL MODULE MODEL R3-TC2 INSTRUCTION MANUAL R3-TC2 TEMPERATURE CONTROL MODULE MODEL R3-TC2 CONTENTS BEFORE USE... 2 POINTS OF CAUTION... 2 COMPONENT IDENTIFICATION... 2 INSTALLATION... 2 EXTERNAL DIMENSIONS unit: mm (inch)...

More information

I/A Series 716C 1/16 DIN Temperature Controller

I/A Series 716C 1/16 DIN Temperature Controller Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of

More information

DIN RAIL MOUNTED INDICATING CONTOLLER DCL-33A INSTRUCTION MANUAL

DIN RAIL MOUNTED INDICATING CONTOLLER DCL-33A INSTRUCTION MANUAL DIN RAIL MOUNTED INDICATING CONTOLLER DCL-A INSTRUCTION MANUAL Preface Thank you for purchasing our DIN rail mounted indicating controller DCL-A. This manual contains instructions for the mounting, functions,

More information

Safety Information. Functional Description. Operation. DANGER Do not touch or contact the input/output terminals because it may cause electric shock.

Safety Information. Functional Description. Operation. DANGER Do not touch or contact the input/output terminals because it may cause electric shock. Temperature Controller KXN Series INSTRUCTION MANUAL Thank you for purchasing HANYOUNG NUX CO,.Ltd. Product. Please check whether the prouduct you purchased is the exactly same as you ordered. Before using

More information

Instruction manual Temperature Controller KT7

Instruction manual Temperature Controller KT7 Instruction manual Temperature Controller KT7 No. KT71E7 201.05 To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual. SAFETY PRECAUTIS Be sure

More information

Temperature Controller

Temperature Controller E5AN Temperature Controller Temperature Controller OMRON Corporation Industrial Automation Company Industrial Devices and Components Division H.Q. Measuring Components Department Shiokoji Horikawa, Shimogyo-ku,

More information

02/11/2015

02/11/2015 MIC48 With RS 485 link Part number 89422418 Heating and / or cooling function 2 independent alarms Load break detection 2 setpoint which can be selected remotely Manual / automatic power adjustment RS

More information

Nov 08 PRODUCT SPECIFICATION SHEET

Nov 08 PRODUCT SPECIFICATION SHEET Honeywell UDC1200 and UDC1700 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS 51-52-03-35 Nov 08 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC1200 & UDC1700 are microprocessor-based 1/16 DIN and 1/8 DIN

More information

Serie Rugghölzli 2 CH Busslingen. Tel. +41 (0) Fax +41 (0)

Serie Rugghölzli 2 CH Busslingen. Tel. +41 (0) Fax +41 (0) Serie 5000 Tel. +1 (0)5 222 Fax +1 (0)5 222 12 PRODUCT INTRODUCTI PRODUCT INTRODUCTI 5 Series programmable temperature controller is FineTek's mid-range series of controllers. It uses a 12bit analog /

More information

Warning Caution INSTRUCTION MANUAL DIN RAIL MOUNTING TYPE INDICATING CONTROLLER

Warning Caution INSTRUCTION MANUAL DIN RAIL MOUNTING TYPE INDICATING CONTROLLER INSTRUCTI MANUAL DIN RAIL MOUNTING TYPE INDICATING CTROLLER 1 DCL-A DC No.DCLDCE1 2007.01 Thank you for purchasing our DIN rail mounting type indicating controller DCL-A DC. This manual contains instructions

More information

MICRO CONTROLLER E Z SERIES

MICRO CONTROLLER E Z SERIES Instruction Manual MICRO CONTROLLER E Z SERIES TYPE: PYZ 4 5 7 9 Fuji Electric Co.,Ltd. INP-TN2PYZDe-E INTRODUCTION You are now the owner of Fuji's Digital Temperature Controller. Before using, be sure

More information

Series Digital Controller Instruction Sheet

Series Digital Controller Instruction Sheet 216/3/11 Series Digital Controller Instruction Sheet Thank you very much for purchasing DELTA DTC Series Temperature Controller. Please read this instruction sheet before using your DTC series to ensure

More information

Series Temperature Controller Instruction Sheet

Series Temperature Controller Instruction Sheet Series Temperature Controller Instruction Sheet Thank you very much for purchasing DELTA A Series. Please read this instruction sheet before using your A series to ensure proper operation and please keep

More information

4TEMPERATURE CONTROLLER

4TEMPERATURE CONTROLLER Universal Input Output and High Accuracy 0.5 class 250ms TEMPERATURE ONTROLLER RAMP function PID Auto-tuning Universal input /, Reverse/Direct action selectable Remote/Local input selectable Model and

More information

SA100. General Description. Features. Temperature Controller SA100. Corresponding to Various Applications. Simple Mounting on DIN Rail

SA100. General Description. Features. Temperature Controller SA100. Corresponding to Various Applications. Simple Mounting on DIN Rail Temperature Controller General Description The is a socket mounting type temperature controller and is available for mounting inside the panel or by easily mounting on DI rail. The has features such as

More information

VT4810 SINGLE / DUAL ZONE CONTROLLER INSTALLATION MANUAL

VT4810 SINGLE / DUAL ZONE CONTROLLER INSTALLATION MANUAL Thermocouple Type BS4937 (IEC584-3): Outer / + / - BS1843 (Old UK Standard) Outer / + / - US Outer / + / - J : Iron / Copper-Nickel Black / Black / White Black / Yellow / Blue Black / White / Red VT4810

More information

SA200. General Description. Features. Temperature Controller SA200. Self-Tuning Algorithm. Close Vertical or Horizontal Mounting

SA200. General Description. Features. Temperature Controller SA200. Self-Tuning Algorithm. Close Vertical or Horizontal Mounting Temperature Controller General Description The is a high performance 3 nd DI controller that has been specifically designed for applications where panel space is critical. Though small in size, this controller

More information

02/11/2015

02/11/2015 CTH 46 - CTD 43 / 46 CTD 46 Part number 89422108 CTH 46 Heating / cooling function Measurement and setpoint display CTD 43 Heating or cooling function Measurement display Measurement deviation display-setpoint

More information

INSTRUCTION MANUAL Micro-computer based digital indicating controller

INSTRUCTION MANUAL Micro-computer based digital indicating controller INSTRUCTI MANUAL Micro-computer based digital indicating controller TP4A To prevent accidents arising from the misuse of this controller, please ensure the operator using it receives this manual. Caution

More information

Non-contact voltage (for SSR drive): V DC DC current: 4 to 20mA DC Thermocouple: K, J, E Input. RTD: Pt100, JPt100

Non-contact voltage (for SSR drive): V DC DC current: 4 to 20mA DC Thermocouple: K, J, E Input. RTD: Pt100, JPt100 INSTRUCTI MANUAL Micro-computer based Temperature Indicating Controller 1 GCS-00 No.GCS1E 200.11 To prevent accidents arising from the use of this controller, please ensure the operator receives this manual.

More information

Instruction manual Micro-computer based digital indicating controller

Instruction manual Micro-computer based digital indicating controller Instruction manual Micro-computer based digital indicating controller JCS-33A To prevent accidents arising from the misuse of this controller, please ensure the operator using it receives this manual.

More information

TAIE. Features. FY600 (96mm X 48mm) Application:Control temperature,humidity, FY Series Digital PID Controller

TAIE. Features. FY600 (96mm X 48mm) Application:Control temperature,humidity, FY Series Digital PID Controller TAIE FY Series Digital PID Controller FY600 (96mm X 48mm) Application:Control temperature,humidity, FY series controllers are microprocessor based controllers. Which have been Designed with high accuracy

More information

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications Instruction Manual Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications Manual PCT30006, Revision 9/20/2016 The PCT30006 control enclosure incorporates

More information

Instruction manual for DIN rail mounting type indicating controller DCL-33A

Instruction manual for DIN rail mounting type indicating controller DCL-33A Instruction manual for DIN rail mounting type indicating controller DCL-33A To prevent accidents arising from the misuse of this controller, please ensure the operator using it receives this manual. Caution

More information

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Instruction Manual Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Manual PCT-3000 Revision 9/2014 The PCT-3000 series control console incorporates

More information

GCS-300 No.GCS31E

GCS-300 No.GCS31E INSTRUCTI MANUAL Micro-computer based Temperature Indicating Controller GCS-00 No.GCS1E 200.0 To prevent accidents arising from the use of this controller, please ensure the operator receives this manual.

More information

DCL-33A No.DCL31E To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.

DCL-33A No.DCL31E To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual. INSTRUCTI MANUAL DIN RAIL MOUNTING TYPE INDICATING CTROLLER DCL-A No.DCL1E5 200.08 To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual. SAFETY

More information

TAIE. Features. FY900 (96mm X 96mm) Application:Control temperature,humidity, FY Series Digital PID Controller

TAIE. Features. FY900 (96mm X 96mm) Application:Control temperature,humidity, FY Series Digital PID Controller TAIE FY Series Digital PID Controller FY900 (96mm X 96mm) Application:Control temperature,humidity, FY series controllers are microprocessor based controllers. Which have been Designed with high accuracy

More information

Communications* None RS-232C RS-422 RS-485 BCD Transmission output** (4 to 20 ma)

Communications* None RS-232C RS-422 RS-485 BCD Transmission output** (4 to 20 ma) TEMPERATURE CONTROLLER DIN-sized (96 x 96-mm) Temperature Controller Featuring Advanced PID Control and Heater Burnout Detection Advanced PID control with two degrees of freedom to improve stability and

More information

Communications type RS-232C RS-422 RS-485 E5AJ-A2H02 E5EJ-A2H02

Communications type RS-232C RS-422 RS-485 E5AJ-A2H02 E5EJ-A2H02 Temperature Controller Fuzzy Self-tuning Temperature Controller with Advanced PID (2-PID) Control DIN-size: 6 x 6 mm (E5AJ), 2 x 2 mm (E5BJ), 4 x 4 mm (E5CJ), 4 x 6 mm (E5EJ) Fuzzy self-tuning and Auto-tuning

More information

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS NOVA PD56 Series Thermocouple, RTD, & Process Inputs Universal Power Supply 1-24 VAC Up to 3 Alarm Relays Retransmitting 4-2 ma Output Input Max/Min

More information

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Process & TeMPerATUre UniversAl input DigiTAl MeTers Process & TeMPerATUre UniversAl input DigiTAl MeTers nova PD56 series Thermocouple, rtd, & Process inputs Universal Power supply 1-24 va c Up to 3 Alarm relays retransmitting 4-2 ma output input Max/Min

More information

VERTEX F4 Instruction Manual

VERTEX F4 Instruction Manual VERTEX F4 Instruction Manual 02/2018 The VERTEX F4 controller 1/16 DIN is our LOW COST yet HIGH SPEC controller. Configurable on input between various thermocouples from the keypad by the user or when

More information

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual. INSTRUCTION MANUAL MICRO-COMPUTER BASED DIGITAL INDICATOR JIR-31-M No.JIR31E3 24.7 To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual. SAFETY

More information

Model 96VTR ¼ DIN Process Controller

Model 96VTR ¼ DIN Process Controller 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 96VTR Product Info Page INSTRUCTION MANUAL Model 96VTR ¼ DIN

More information

UDC1000 & UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

UDC1000 & UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS UDC1000 & UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS EN0I-6041 11/98 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC1000 & UDC 1500 are microprocessor-based 1/16 DIN and 1/8 DIN controllers which

More information

TEMPERATURE CONTROLLER

TEMPERATURE CONTROLLER TEMPERATURE CONTROLLER E5CX(-H) DIN-sized super-compact (48 x 48-mm) Temperature Controller Featuring Advanced PID Control Advanced PID control with two degrees of freedom improves stability and response

More information

The range of ATR243 controllers comes in three versions. Refer to the table below to easily select your preferred model.

The range of ATR243 controllers comes in three versions. Refer to the table below to easily select your preferred model. Summary 1 Introduction... 3 2 Model Identification... 3 3 Technical Data... 4 3.1 General Features... 4 3.2 Hardware Features... 4 3.3 Software Features... 5 4 Dimensions and Installation... 5 4.1 Panel

More information

UDC 700 Universal Digital Controllers and Indicator Specifications

UDC 700 Universal Digital Controllers and Indicator Specifications UDC 700 Universal Digital Controllers and Indicator Specifications 51-52-03-28 August 2002 Overview The UDC 700 is a 1/32 DIN (49 x 25 mm) controller which combines a high degree of technology and quality

More information

+ A B V B NO NC V COM PV PV

+ A B V B NO NC V COM PV PV + - A + B B - V + - NO NC COM + - + - V + - PV PV Ramp Soak 100 70 50 30 3 5 3 8 5 3 Minute Steam Heating Sensor Cooling Water PID Hotplate Specifications Input power supply AC 100 to 240V, 50/60Hz, DC

More information

4000 1/4 DIN /16 DIN /8 DIN

4000 1/4 DIN /16 DIN /8 DIN 4000series 18 Quick Reference Guide PID Adjustment Guide iv Set-up Menu Press key for 3 seconds to enter the set-up menu. The flow chart shows a complete listing of all parameters. The number of available

More information

Installation Manual Tracker 221

Installation Manual Tracker 221 Installation Manual Tracker 221 KSR KUEBLER AG Im Kohlstatterfeld 17 D-69439 Zwingenberg / Germany www.ksr-kuebler.com Contents About this Installation Manual...4 Description Tracker 220-series...4 Installing

More information

DC1000 Series Digital Controller Product Manual August 2005

DC1000 Series Digital Controller Product Manual August 2005 DC1000 Series Digital Controller Product Manual 51-52-25-113 August 2005 Industrial Measurement and Control Copyright, Notices and Trademarks Printed in Taiwan - Copyright 2005 by Honeywell Revison 1 -

More information

General Specifications

General Specifications General Specifications GS J0H-0E Model MVHK Digital Limit Alarm (DC Type) with Active Color PV Display General This plug-in type Digital Limit Alarm for DC input receives DC current or DC voltage signal.

More information

DIGITAL INDICATING CONTROLLER FCS-23A INSTRUCTION MANUAL

DIGITAL INDICATING CONTROLLER FCS-23A INSTRUCTION MANUAL DIGITAL INDICATING CONTROLLER FCS-23A INSTRUCTION MANUAL Preface Thank you for purchasing our Digital indicating controller FCS-23A. This manual contains instructions for the mounting, functions, operations

More information

SHIMADEN DIGITAL INDICATORS

SHIMADEN DIGITAL INDICATORS Shimaden, Temperature and Humidity Control Specialists C %RH MICROPROCESSOR-BASED SHIMADEN DIGITAL INDICATORS & NRTL /C approved BASIC FEATURES DIN Size 48 x 96 mm ±.25% High Accuracy Indication User-Selectable

More information

Refrigerated air dryers

Refrigerated air dryers Refrigerated air dryers OPERATING AND MAINTENANCE MANUAL Original instructions 38178800319 OPERATING AND MAINTENANCE MANUAL - Contents 1 CONTENTS CONTENTS... 1 Chapter 1 IDRY ELECTRONIC CONTROLLER...

More information

Terwin Instruments Ltd.

Terwin Instruments Ltd. Terwin Instruments Ltd. Temperature PID Controllers MC-x8 OPERATIONAL MANUAL MC 8 / MC 8 / MC 8 MC 8 / MC 88 ( Display unit & Indication lamps ~ =Measured value display =Set value dispaly Alarm output

More information

CEMA CM20 Series Digital Controller Operation Manual CM24 CM22 CM21 CM23 CM25

CEMA CM20 Series Digital Controller Operation Manual CM24 CM22 CM21 CM23 CM25 CEMA CM20 Series Digital Controller Operation Manual CM24 CM22 CM21 CM23 CM25 Contents 1 Safety Guide... 1 1.1 Specifications... 2 1.2 Model Selection Guide... 3 1.3 Model Guide... 3 1.4 Optional Spec....

More information

Table of Contents SECTION PAGE

Table of Contents SECTION PAGE Table of Contents SECTION PAGE SECTION 1 INTRODUCTION................... 1.1 Description.............................. 1.2 Features................................ 1.3 Models.................................

More information

Universal controller for panel mounting Models CS6S, CS6H, CS6L

Universal controller for panel mounting Models CS6S, CS6H, CS6L Accessories Universal controller for panel mounting Models CS6S, CS6H, CS6L WIKA data sheet AC 85.08 Applications Plant and industrial furnace construction Process engineering Plastics technology and processing

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual. INSTRUCTI MANUAL MICRO-COMPUTER BASED DIGITAL INDICATOR JIR-31-M No.JIR31E6 28.8 To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual. SAFETY

More information

99 Washington Street Melrose, MA Phone Toll Free Visit us at

99 Washington Street Melrose, MA Phone Toll Free Visit us at 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 48VTR Product Info Page Instruction Manual English / Español

More information

Temperature Controller SA100. Initial Setting Manual IMR01J03-E1 RKC INSTRUMENT INC.

Temperature Controller SA100. Initial Setting Manual IMR01J03-E1 RKC INSTRUMENT INC. Temperature Controller SA100 Initial Setting Manual RKC INSTRUMENT INC. IMR01J03-E1 Modbus is a registered trademark of Schneider Electric. Company names and product names used in this manual are the trademarks

More information

TC515 and TC600 Installation Manual. a Winters company

TC515 and TC600 Installation Manual. a Winters company THERMOLINE TEMPERATURE CONTROLLERS TC515 and TC600 Installation Manual a Winters company Guarantee 12 months Congratulations on the purchase of this new product. Special care with the design, workmanship

More information

GETTING STARTED. Next, press the INDEX key to display Unit. Press the DOWN ARROW until the display shows C. Press ENTER.

GETTING STARTED. Next, press the INDEX key to display Unit. Press the DOWN ARROW until the display shows C. Press ENTER. CONTENTS Installation... 4 Wiring... 5 Wiring for Transmitter inputs... 6 Wiring for 15 VDC Outputs... 6 Wiring for Optional Inputs and Outputs... 7 Front Panel Key Functions... 8 Notation Conventions

More information

AutomationDirect. PC35 Configuration Sheet

AutomationDirect. PC35 Configuration Sheet Part#: Project: AutomationDirect PC35 Configuration Sheet Name: Date: Main Setpoint (): Cycle 5 INPUT DEFAULT CODE/VALUE Type 1 Dppo OFF Unit [ Offs 0 Spll -150 Spkl 1370 Rsll -150 Rskl 1370 Cycle 6 I/O

More information

TEMPERATURE CONTROLLER OPERATION MANUAL

TEMPERATURE CONTROLLER OPERATION MANUAL TEMPERATURE CTROLLER OPERATI MANUAL M.R.C.LTD. ICES: Hagavish 3, HOL 58394 P.O.B.1684, TEL-AVIV 6116, ISRAEL TEL: 972-3-559315,972-3-5595252, FAX: 972-3- Before using please check whether range, input

More information

ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER

ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI-208 (V7.6) User Manual I. Model Code Symbol The type of AI-208 is made up of 4 parts: AI-208 A G L2 Part 1 (Series) Part 2 (Size) Part 3 (Oupt) Part 4

More information

OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR 06261

OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR 06261 TLK 38 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR 06261 FOREWORD: This manual contains the information necessary for the product to be installed

More information

INSTRUCTIONS FOR THE 2600 SERIES MICROPROCESSOR BASED TEMPERATURE /PROCESS CONTROL

INSTRUCTIONS FOR THE 2600 SERIES MICROPROCESSOR BASED TEMPERATURE /PROCESS CONTROL Bulletin 949-1194 INSTRUCTIONS FOR THE 2600 SERIES MICROPROCESSOR BASED TEMPERATURE /PROCESS CONTROL LOVE LOVE CONTROLS a Division of Dwyer Instruments, Incorporated PO Box 338 Michigan City, IN 46361-0338

More information

KC-400 KC-600 KC-700 KC-800 KC-900

KC-400 KC-600 KC-700 KC-800 KC-900 KCE Series Micro Processor Controller Operation Manual KC-400 KC-600 KC-700 KC-800 KC-900 KCE Contents 1 Safety Guide... 1 1.1 Specifications... 2 1.2 Model Selection Guide... 3 1.3 Model Guide... 3 1.4

More information

Alarm Output None. Code 5 N Y N R2 R3 A AC/DC100~240V. 2 Relays 3 Relays R4 4 Relays O2 2 Open Collect O3 3 Open Collect O4 4 Open Collect

Alarm Output None. Code 5 N Y N R2 R3 A AC/DC100~240V. 2 Relays 3 Relays R4 4 Relays O2 2 Open Collect O3 3 Open Collect O4 4 Open Collect 5 DIGIT MICO-POCESS LVDT METE with 2~4 AMS / ANOG OUTPUT / S-485 + FEATUES! Accuracy: 0.05% F.S. Measuring Distance / Interval / Thickness High brightness 0.8" LED display range: -19999~99999; decimal

More information

CG Series Digital Temperature Controller OPERATIONS MANUAL

CG Series Digital Temperature Controller OPERATIONS MANUAL CG-15001 Series Digital Temperature Controller OPERATIONS MANUAL C 3800 North Mill Road Vineland, NJ 08360 USA Tel: 1-800-843-1794 Fax: 1-800-922-4361 Index Page Quick Set-Up..3 Tuning..4 Auto-Tuning...4

More information

7EF/7HF/7EC/7ES Temperature Controllers

7EF/7HF/7EC/7ES Temperature Controllers 7EF/7HF/7E/7ES Temperature ontrollers Dual 4 Digit LED Display Universal Input (6 T/, RTD, mv, V, ma) Autotuning NEMA 4X 100 to 240 Vac Switching Power Supply Algorithms for Heat or Heat/ool ontrol 2 Independent

More information

User s Guide CN616A. Universal 6 Channel ¼ DIN Process Controller. Shop online at omega.com

User s Guide CN616A. Universal 6 Channel ¼ DIN Process Controller. Shop online at omega.com TM User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: www.omegamanual.info CN616A Universal 6 Channel ¼ DIN Process Controller omega.com info@omega.com U.S.A. Headquarters:

More information

ELK 38 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER. OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR 06261

ELK 38 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER. OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR 06261 ELK 38 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR 06261 INDEX 1 INSTRUMENT DESCRIPTION 1.1 GENERAL DESCRIPTION 1.2 FRONT PANEL DESCRIPTION 2 PROGRAMMING

More information

TLK 31 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER. OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR TECNOLOGIC S.p.A.

TLK 31 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER. OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR TECNOLOGIC S.p.A. TLK 31 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER OPERATING INSTRUCTIONS Vr. 2 (ENG) - cod.: ISTR 6258 TECNOLOGIC S.p.A. VIA INDIPENDENZA 56 2729 VIGEVANO (PV) ITALY TEL.: +39 381 69871 FAX: +39

More information

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER GCD-200, GCR-200

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER GCD-200, GCR-200 INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER GCD-200, GCR-200 PV PV AT AT OUT1 OUT2/HB A1 A2 OUT1 OUT2/HB A1 A2 MODE OUT MODE OUT GCD GCR Preface Thank you for the purchase

More information

INSTRUCTIONS FOR THE 8500 SERIES MICROPROCESSOR BASED TEMPERATURE CONTROL

INSTRUCTIONS FOR THE 8500 SERIES MICROPROCESSOR BASED TEMPERATURE CONTROL INSTRUCTIONS FOR THE 8500 SERIES MICROPROCESSOR BASED TEMPERATURE CONTROL December, 1998 Page 1 949-1275-1 TABLE OF CONTENTS MODEL IDENTIFICATION... 4 INSTALLATION... 4 WIRING... 5 FRONT PANEL KEY FUNCTIONS...

More information

UDC100 Universal Digital Controller Specifications

UDC100 Universal Digital Controller Specifications UDC100 Universal Digital Controller Specifications 51-52-03-29 November 1999 Overview The UDC100 Universal Digital Controller is a microprocessor-based 1/4 DIN low cost temperature controller. It combines

More information

R Relay output S SSR drive output C Selectable current output or SSR drive output VAC 50/60Hz

R Relay output S SSR drive output C Selectable current output or SSR drive output VAC 50/60Hz Controller Features Super high-speed sampling with 50ms Improved visibility with LCD display Communication function supported: RS485 (Modbus RTU) Convenient parameter setting (RS485 communication) : Free

More information

TLK39 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER. OPERATING INSTRUCTIONS Vr (ENG) - cod.: ISTR 06262

TLK39 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER. OPERATING INSTRUCTIONS Vr (ENG) - cod.: ISTR 06262 TLK39 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER OPERATING INSTRUCTIONS Vr. 02.1 (ENG) - cod.: ISTR 06262 FOREWORD: This manual contains the information necessary for the product to be installed

More information

NOVUS AUTOMATION 1/5. Range: -35 to 720 C (-31 to 1328 F) Range: -90 to 1300 C (-130 to 2372 F) Range: 0 to 1760 C (-32 to 3200 F)

NOVUS AUTOMATION 1/5. Range: -35 to 720 C (-31 to 1328 F) Range: -90 to 1300 C (-130 to 2372 F) Range: 0 to 1760 C (-32 to 3200 F) E N R S B Pt100 Pt100 Range: -35 to 720 C (-31 to 1328 F) Range: -90 to 1300 C (-130 to 2372 F) Range: 0 to 1760 C (-32 to 3200 F) Range: 0 to 1760 C (-32 to 3200 F) Range: 150 to 1820 C (302 to 3308 F)

More information

Temperature + Humidity (%RH) Control & Recording System with 8 / 16 Channel Mapping. Touch Panel PPI

Temperature + Humidity (%RH) Control & Recording System with 8 / 16 Channel Mapping. Touch Panel PPI HumiTherm Ultra Temperature + Humidity (%RH) Control & Recording System with 8 / 16 Channel Mapping Mapping Unit Micro PLC Control Unit Touch Panel Touch Operation Panel PPI HumiTherm Ultra GSM Module

More information

Specification , July 2015

Specification , July 2015 Technical Information PrecisionLine Controllers EDC21 / EDC22 / EDC23 EASYSET DIGITAL CONTROLLERS Specification 51-52-3-48, July 215 Introduction The EDC21, EDC22 and EDC23 controllers provide precise

More information

TLK 43 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER. OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR 6267

TLK 43 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER. OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR 6267 TLK 43 MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR 6267 FOREWORD: This manual contains the information necessary for the product to be installed

More information

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs User Manual Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs Models 89800-03 and 89800-04 THE STANDARD IN PRECISION MEASUREMENT Table of Contents

More information

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL 1 Operations Manual for the VTI Model itc5000 Heat Tracing Control System Description The VTI Model itc5000 Heat Tracing Control System consists

More information

R Air flows from high pressure side to low pressure side. This principle can be applied to keep clean-air in the room or, alternatively, not to leak p

R Air flows from high pressure side to low pressure side. This principle can be applied to keep clean-air in the room or, alternatively, not to leak p The first edition contrasted April 2011 Yamamoto Electric Works Co.,Ltd. T H E G E N E R A L C A T A L O G R We appreciate the importance of air. Manostar gage h t t p : / / w w w. m a n o s t a r. c o.

More information

INSTRUCTIONS FOR THE 32A SERIES 1/32 DIN MICROPROCESSOR BASED TEMPERATURE / PROCESS CONTROL

INSTRUCTIONS FOR THE 32A SERIES 1/32 DIN MICROPROCESSOR BASED TEMPERATURE / PROCESS CONTROL Bulletin 949-1311 INSTRUCTIONS FOR THE 32A SERIES 1/32 DIN MICROPROCESSOR BASED TEMPERATURE / PROCESS CONTROL LOVE CONTROLS DIVISION Phone: 219/879-8000 DWYER INSTRUMENTS, INC. www.love-controls.com P.O.

More information

Microprocessor-based digital electronic controller TLK 38

Microprocessor-based digital electronic controller TLK 38 1. General description is a single loop digital microprocessor-based controller, with ON/OFF, Neutral Zone ON/ OFF, PID single action, PID dual action (direct and reverse) control and with AUTO-TUNING

More information