Fire Safety. Installation Instructions Model PSR-1 Remote Power Supply INTRODUCTION. Figure 1 PSR-1 Remote Power Supply

Size: px
Start display at page:

Download "Fire Safety. Installation Instructions Model PSR-1 Remote Power Supply INTRODUCTION. Figure 1 PSR-1 Remote Power Supply"

Transcription

1 Fire Safety Installation Instructions Model PSR- Remote Power Supply Figure PSR- Remote Power Supply INTRODUCTION The SIEMENS Model PSR- (See Figure ) is a microprocessor controlled remote power supply and battery charger used with the MXL System. It operates with an MPS-6 or MPS- to provide 6 or amps, respectively, of power for various MXL modules. In addition, the PSR- acts as an interface between remote option modules and the MXL when used with a NET- plug-in communication module (See Instructions P/N -999) or NET-7 plug-in communication module (See Instructions P/N -99). The PSR- can also be used to power an MOI/MOD annunciator driver set. In addition, the PSR- can be used as an auxiliary power supply in a standalone mode without an MXL. The PSR- has LED status indicators for: POWER ON, V AUX ON, V ON, BAT TRBL, TB TRBL (Class A power limited output for the CZM- and PS-), GND FAULT, XMIT, ANY TRBL, and ANY ALARM. The PSR- has two relays used for common alarm and common trouble. These relays also can be programmed for local alarm and local trouble using CSG-M. Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 79 Siemens Building Technologies, Ltd. Kenview Boulevard Brampton, Ontario L6T E CN P/N -99-

2 ELECTRICAL CONNECTIONS Remove all system power before installation, first battery and then AC. Primary Power Primary power for the PSR- is provided by the MPS-6 or MPS-. Both of these mount in the lower right-hand corner of the MXL enclosure. Follow the instructions below for the appropriate power supply. MPS-6 Install the MPS-6 (See MPS-6 Instructions, P/N -9). With the AC mains disconnected, connect the MPS-6 power cable to P of the PSR-. Be sure that the jumper assembly is installed in P of the PSR-. If this jumper is not installed, the PSR- will detect a permanent AC fail or indicate auxiliary power voltage is low. Change F to a A fuse, P/N -9. Change F to a 6A fuse, P/N MPS- Install the MPS- (See MPS- Instructions, P/N -9). Remove and discard the jumper assembly installed in P of the PSR-. Disconnect the AC mains. Connect the MPS- power cable to P of PSR-. Battery Calculations Battery backup is a requirement for the MXL. To determine the size battery you must use, follow the procedures listed below. The MXL can charge a battery of up to amp hours. A battery size calculation form is provided on page.. Record all the modules required in the form on the following page.. Calculate each row across and place the total in the right column: Total Standby VDC Module Current. Total the right-hand column and record it at the bottom of the form opposite Total System Current.. For NFPA 7 Local and 7 Proprietary systems multiply the total system current by and record it at that Total AH location. or For NFPA 7 Municipal Tie and 7 Remote Station systems multiply the total system current by 6 and record it at that Total AH location. or For FM Appoved Deluge/PreAction systems multiply the total system current by 9 and record it at that Total AH location.. Multiply the AH Total by. to obtain the final battery amp hour capacity and record it opposite Battery Size. Three battery models are UL listed for use with the MXL: BP-6 V, AH BTX- a set of V, AH BTX- a set of V, AH, 6 AH, or 7 AH* * Although larger batteries may be used, as noted, the AH capacity must be used for determining battery requirements. Select the battery that meets or exceeds the final calculated battery amp hour rating. Use an external battery box with the BTX- model. Do not connect the batteries at this time. Power Supply Load Calculations To ensure that the power supply is not overloaded, complete the worksheet on page.. Enter the quantity of each module in the enclosure.. Caclulate both the V and V loads for each row.. Total the Active V and Active V columns.. Ensure that both totals are within the power supply output ratings in the table below. POWER SUPPLY OUTPUT RATINGS Module Active VDC Module Current Active VDC Module Current PSR-/MPS-6 6 amps 8 ma PSR-/MPS- amps 8 ma

3 NOTES:. Use this column for battery size calculations.. Power is supplied by a separate UPS.. EOL currents included.. The following modules draw no VDC current and do not need to be included in the battery calculations: OMM- OMM- MOM- MOM- MMM- PLC- TBM- TSW- Modul odule PSR- MKB- RCC-/F/ TSP- CSM- CRM- CZM- ALD-I XLD- CMI- NET- NET-7 NET-7M NIM-R NIM-W NIM-W with NIM-M REP- PS-A PS-N7 MOI-7 MOD-6 MID-6 CZM-/-B6 ICP-/-B6 PIM- IM- AL- DCP Silent Knight ACM- TMM- VSM-/VLM- VFM- ASC- ELD DMC- ASC- OCC- BTC- RCM- ZAC- ZC-8B ZC-AB ZC-8B ZC-AB ZCT-8B Quantit uantity P ) P ) Standby VDC Load Current Per Circuit Module Current End of Line ( (See Note ) Devic evice e Device Current Total Standby VDC Module Current 7mA ma 7mA 7mA ma ma ma ma per active relay ma ma ma.ma per device ma.ma per device ma ma ma ma 7mA NA ma NA ma NA ma ¼ of V load ma + ¼ of V load ma ma ma 6mA ma.ma 8mA K ma NA ( See Note NA ( See Note NA ma 6 ma 8mA 7mA ( See Note ) 7mA 7mA ma ma.ma 9mA ( See Note ) 7mA ma ma 6mA 9mA ( See Note ) 9mA ( See Note ) 9mA ( See Note ) 8mA ( See Note ) ma ( See Note ) Total System Current N FPA Local (7A), Proprietary (7D) - Total AH x = * N FPA Municipal Tie (7B), Remote Station (7C) - Total AH x 6 = * F M Approved Deluge/PreAction - Total AH x 9 = * Battery Size (with Alarm Reserve Correction**) x. = * Total not to exceed Amps ** Maximum Alarm current Amps

4 NOTES:. Use this column to calculate total current from VDC supply to make sure it is not overloaded.. Use this column to calculate total current from VDC supply to make sure it is not overloaded.. PSR- supplies V at 8mA, V at 6A (MPS-6), V at A (MPS-).. The following modules draw no current from either the VDC or VDC power supplies and do not need to be included in these calculations: OMM- OMM- MOM- MOM- MMM- PAL- PIM- PLC- TBM- TSW- Module Quantity Active VDC Module Current Total Active VDC Module Current (See Note ) Active VDC Module Current Total Active VDC Module Current (See Note ) PSR- (See Note ) (See Note ) MKB- ma RCC-/F 8mA TSP- 7mA CSM- ma +.A max ma per circuit CRM- 7mA ma CZM- ALD-I 7mA zones in alarm ma +.ma per device ma XLD- ma +.ma per device CMI- 96mA NET- ma NET-7 ma NET-7M ma NIM-R 6mA NIM-W ma REP- ma MOI-7 ma 7mA MOD-6 8mA max ma MID-6 ma max ma CZM-/-B6 ma ICP-/-B6.A PIM- ma DCP ma Silent Knight ma ACM- 8mA 76mA TMM- 7mA VSM-/VLM- 6mA VFM- 9mA ASC- ma 9mA ASC- 6mA 9mA OCC- 7mA ma BTC- ma DMC- ma RCM- ma 8mA ZAC- A at W ZC-8B 7mA ma ZC-AB 67mA ma ZC-8B ma ma ZC-AB 68mA 8mA ZCT-8B 78mA ma TOTAL TOTAL

5 SETTING THE OPTION DIPSWITCHES ON SWITCH S (See Figure ) To Disable the Network (S-) The Disable Network Switch, located at S-, enables or disables the network connection. DISABLE NETWORK SWITCH SETTINGS S- Network Open (or OFF) Enabled Closed (or ON) Disabled* *When not connected to the MXL network Battery Setting (S-, -, and -) There is only one allowable battery switch setting as shown in the table below. Be sure to set the PSR- battery size in the CSG-M to AH, regardless of the factory battery size. BATTERY SWITCH SETTINGS DIP Switches S- S- S- Open (or OFF) Open (or OFF) Closed (or ON) Charging Current. amps max Figure Switches S and S on the PSR- Security Mode-UL 76 Operation (S-) To Disable the Tamper Switch The PSR- does not support the use of security points from initiating circuits in its enclosure. To disable the tamper switch input of the PSR-, set the security mode to disabled. The Disable Security Mode switch is located at S-. DISABLE SECURITY MODE SWITCH SETTINGS S- UL76 Open (or OFF) Disabled The following table defines the battery voltage thresholds for the listed battery trouble conditions. These voltages can be viewed in the TEST POWER menu on the MKB- annunciator. BATTERY VOLTAGE THRESHOLDS Battery Status Conditions Battery Voltage (Volts) Battery Not Installed <. Charger Disabled <8. Battery Low Fault On Battery <. Battery Low Fault On AC <. Battery High Fault >. Input Power Specifications MPS-6 Input Voltage: VAC, +%, -% Input Current: A max MPS- Input Voltage: VAC, +%, -% Input Current: A max SETTING THE NETWORK ADDRESS (S) (See Figure ) The PSR- occupies one network address in the MXL System. You may have up to PSR- power supplies in your system. Regardless of

6 6 TABLE NETWORK ADDRESS PROGRAMMING DDR A R DD A R DD A R DD A OOOOOOXX OOOOOXOO OOOOOXOX OOOOOXXO OOOOOXXX OOOOXOOO OOOOXOOX OOOOXOXO OOOOXOXX OOOOXXOO OOOOXXOX OOOOXXXO OOOOXXXX OOOXOOOO OOOXOOOX OOOXOOXO OOOXOOXX OOOXOXOO OOOXOXOX OOOXOXXO OOOXOXXX OOOXXOOO OOOXXOOX OOOXXOXO OOOXXOXX OOOXXXOO OOOXXXOX OOOXXXXO OOOXXXXX OOXOOOOO OOXOOOOX OOXOOOXO OOXOOOXX OOXOOXOO OOXOOXOX OOXOOXXO OOXOOXXX OOXOXOOO OOXOXOOX OOXOXOXO OOXOXOXX OOXOXXOO OOXOXXOX OOXOXXXO OOXOXXXX OOXXOOOO OOXXOOOX OOXXOOXO OOXXOOXX OOXXOXOO OOXXOXOX OOXXOXXO OOXXOXXX OOXXXOOO OOXXXOOX OOXXXOXO OOXXXOXX OOXXXXOO OOXXXXOX OOXXXXXO OOXXXXXX OXOOOOOO OXOOOOOX OXOOOOXO OXOOOOXX OXOOOXOO OXOOOXOX OXOOOXXO OXOOOXXX OXOOXOOO OXOOXOOX OXOOXOXO OXOOXOXX OXOOXXOO OXOOXXOX OXOOXXXO OXOOXXXX OXOXOOOO OXOXOOOX OXOXOOXO OXOXOOXX OXOXOXOO OXOXOXOX OXOXOXXO OXOXOXXX OXOXXOOO OXOXXOOX OXOXXOXO OXOXXOXX OXOXXXOO OXOXXXOX OXOXXXXO OXOXXXXX OXXOOOOO OXXOOOOX OXXOOOXO OXXOOOXX OXXOOXOO OXXOOXOX OXXOOXXO OXXOOXXX OXXOXOOO OXXOXOOX OXXOXOXO OXXOXOXX OXXOXXOO OXXOXXOX OXXOXXXO OXXOXXXX OXXXOOOO OXXXOOOX OXXXOOXO OXXXOOXX OXXXOXOO OXXXOXOX OXXXOXXO OXXXOXXX OXXXXOOO OXXXXOOX OXXXXOXO OXXXXOXX OXXXXXOO OXXXXXOX OXXXXXXO OXXXXXXX XOOOOOOO XOOOOOOX XOOOOOXO XOOOOOXX XOOOOXOO XOOOOXOX XOOOOXXO XOOOOXXX XOOOXOOO XOOOXOOX XOOOXOXO XOOOXOXX XOOOXXOO XOOOXXOX XOOOXXXO XOOOXXXX XOOXOOOO XOOXOOOX XOOXOOXO XOOXOOXX XOOXOXOO XOOXOXOX XOOXOXXO XOOXOXXX XOOXXOOO XOOXXOOX XOOXXOXO XOOXXOXX XOOXXXOO XOOXXXOX XOOXXXXO XOOXXXXX XOXOOOOO XOXOOOOX XOXOOOXO XOXOOOXX XOXOOXOO XOXOOXOX XOXOOXXO XOXOOXXX XOXOXOOO XOXOXOOX XOXOXOXO XOXOXOXX XOXOXXOO XOXOXXOX XOXOXXXO XOXOXXXX XOXXOOOO XOXXOOOX XOXXOOXO XOXXOOXX XOXXOXOO XOXXOXOX XOXXOXXO XOXXOXXX XOXXXOOO XOXXXOOX XOXXXOXO XOXXXOXX XOXXXXOO XOXXXXOX XOXXXXXO XOXXXXXX XXOOOOOO XXOOOOOX XXOOOOXO XXOOOOXX XXOOOXOO XXOOOXOX XXOOOXXO XXOOOXXX XXOOXOOO XXOOXOOX XXOOXOXO XXOOXOXX XXOOXXOO XXOOXXOX XXOOXXXO XXOOXXXX XXOXOOOO XXOXOOOX XXOXOOXO XXOXOOXX XXOXOXOO XXOXOXOX XXOXOXXO XXOXOXXX XXOXXOOO XXOXXOOX XXOXXOXO XXOXXOXX XXOXXXOO XXOXXXOX XXOXXXXO XXOXXXXX XXXOOOOO XXXOOOOX XXXOOOXO XXXOOOXX XXXOOXOO XXXOOXOX XXXOOXXO XXXOOXXX XXXOXOOO XXXOXOOX XXXOXOXO XXXOXOXX XXXOXXOO XXXOXXOX XXXOXXXO XXXOXXXX XXXXOOOO XXXXOOOX XXXXOOXO XXXXOOXX XXXXOXOO XXXXOXOX XXXXOXXO XXXXOXXX ON) X = CLOSED (or OFF) O = OPEN (or

7 how many PSR- power supplies are used, you MAY NOT exceed initiating points. Each PSR- must be placed at a unique address in the system. Use the CSG-M printout to determine the address of the PSR-. Set the network address on S using Table. Note that the PSR- network address switch is a 9-position switch. Switch position 9 is not used at this time. Set it to the OFF or Open position. When used as a standalone power supply, the network address does not need to be set. MOUNTING Mount the PSR- Remote Power Supply on the MBR-MP mounting plate in the MME- enclosure as shown in Figure.. Place the PSR- over the four standoffs in the upper left portion of the mounting plate.. Secure it in place using the hardware provided. Figure Mounting the PSR- on the MBR-MP MAKING THE NETWORK CONNECTION (TB) For the PSR- to communicate with the MXL, a NET- or NET-7 network interface card must be installed into P7 of the PSR-. For a NET-, connect the MXL network (MMB) to terminals and of TB as indicated in Figure. Terminate the shield at the MMB only. For a NET-7, refer to Figure of the NET-7 Installation Instructions (P/N -99) and connect the network to terminals,,, and. For a NET-7 network connected to an MMB-, refer to Figure. When the PSR- is used as a standalone power supply, neither NET- nor NET-7 is needed. If an MKB- is installed, the NET-7 must be installed in a MOM. REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION. Figure Network Connection using NET- RES EOL ASSEMBLY OHMS, / W, % P/N

8 RES EOL ASSEMBLY OHMS, /W, % P/N -999 PSR- N E T - 7 TB NO EOLR CHASSIS RES EOL ASSEMBLY OHMS, /W, % P/N -999 MOI-7 REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION. TB PSR- NET-7 OR NET-7M TB NO EOLR Figure Connecting a Style 7 Network to MMB- SHIELD TB RES EOL ASSEMBLY OHMS, /W, % P/N -999 MMB- WIRING Wiring Alarm and Trouble Relays (TB) Two relays are provided for local control of alarm and trouble indication. These relays are controlled by the MXL through CSG-M output logic. The alarm relay transfers if the local alarm default signal is activated by an initiating control board (CZM- or ALD-I). This occurs when the initiating board cannot communicate with the MXL. Likewise, if any local module, including the PSR-, loses communication with the MXL, the trouble relay transfers. When the system is operating normally, these relays are controlled by output logic only. See Figure 6 for ratings and wiring instruction. Auxiliary Power for CZM- and PS-A (TB) A Class A power limited output is provided on TB, terminals -6 for use with the CZM- and PS-A.. This power is available on TB, terminals through 6.. All wiring must be in accordance with Article 76 of NEC or local building codes.. The power for CZM- and PS-A is power limited to NFPA 7 per NEC 76.. Electrical Ratings: VDC, full wave bridge, unregulated A max. You may connect a maximum of CZM-s to the TB power source. Follow the guidelines below when wiring. 6 TB 6 TB + + REFER TO WIRING SPECIFICATION FOR MXL. MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR FURTHER INFORMATION. TROUBLE ALARM RATINGS A, VDC RESISTIVE Figure 6 Alarm and Trouble Relays REFER TO WIRING SPECIFICATION FOR MXL. MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR FURTHER INFORMATION. CLASS A WIRING CZM- NO T-TAPPING ALLOWED VDC, NOT REGULATED A MAX POWER LIMITED TO NFPA 7 PER NEC 76 OHMS MAX (TOTAL) 8 AWG MIN Figure 7 CZM- Power, Class A Wiring 8

9 a. This power may be wired Class A, as shown in Figure 7. Class A wiring can support a maximum of CZM-s, with total line resistance of ohms max. T-tapping is not allowed. b. Refer to Figure 8. Class B wiring can be used to obtain the maximum of CZM-s. Each Class B wire run can support a maximum of CZM-s, ohms max. Multiple Class B power connections can be used if you do not exceed the ratings above ( CZM-s max and ohms per run max). For example, you could have four individual Class B power runs, for a total of devices (for example,, 8, 6, and CZM-s), with each of the four runs not exceeding ohms resistance. T-tapping is allowed, provided the total resistance of all wires does not exceed ohms. 6. Refer to Figures 9 and for wiring instructions for the PS-A. 6 TB REFER TO WIRING SPECIFICATION FOR MXL. MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR FURTHER INFORMATION. + CZM- CZM- CLASS B WIRING CZM- T-TAPPING ALLOWED VDC, NOT REGULATED A MAX POWER LIMITED TO NFPA 7 PER NEC 76 OHMS MAX PER PAIR (TOTAL) 8 AWG MIN Figure 8 CZM- Power, Class B Wiring PSR- REFER TO WIRING SPECIFICATION FOR MXL. MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR FURTHER INFORMATION. PSR- REFER TO WIRING SPECIFICATION FOR MXL. MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR FURTHER INFORMATION. 6 TB + DO NOT USE DO NOT USE 6 TB + + DO NOT USE DO NOT USE VDC, NOT REGULATED A MAX POWER LIMITED TO NFPA 7 PER NEC 76 OHMS MAX PER PAIR (TOTAL) 8 AWG MIN PS-A VDC, NOT REGULATED A MAX POWER LIMITED TO NFPA 7 PER NEC 76 OHMS MAX PER PAIR (TOTAL) 8 AWG MIN PS-A Figure 9 PS-A Power, Class A Wiring MOI-7 Power (P9) The PSR - may be used in standalone mode as the power supply for the MOI-7. In this configuration the MOI-7 and the PSR- must be in the same enclosure. A separate V output is provided for the MOI-7. The PSR- local trouble contact must also be connected as a means of reporting Figure PS-A Power, Class B Wiring PSR- troubles to the MXL. See Figure for the wiring diagram. See Figure if the MOI-7 is in a separate enclosure. In this configuration do not use the V power on P9. A separate PS-A must be included in the remote enclosure with the MOI-7. 9

10 Figure MOI-7 Connection (in Same Enclosure) REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION. TB 6 PSR- TB NETWORK NETWORK 8 AWG MIN Figure MOI-7 Connection (in Remote Enclosure using PS-A) CZM-B6 AND PS-A POWER TO MXL NETWORK 8 AWG MIN OHMS MAX TB + PS-A TB P MOI-7 MOD-6 MOD-6 MOD-6 MID-6 REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION. J SYSTEM ENCLOSURE (OR EQUIVALENT) MOUNTING MOM- Module Connection P6 on the PSR- is the data and V connection for the MOM-. Connect P6 on the PSR- to P7 on the MOM- using the 8 circuit ribbon cable, P/N -96, provided with the MOM-. A second auxiliary non-power limited output is provided on TB for the MOM- card cage. This output is rated at 6 amps (MPS-6) or amps (MPS-) 8- VDC. This capacity must be derated by the current drawn by the CZM- and PS-A power output. If the full amp capacity of the CZM- and PS-A output is used, the MOM- power must be derated to amps (MPS-6) or amps (MPS-). See Figure for wiring instructions. When a PSR- is used with an MKB-, use a MOM- for the NET-7. Connect as shown in Figure.

11 REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION. Figure Connecting a NET-7 in a MOM- REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION. Figure MOM- Connection OMM- Module Connection When using the PSR with voice modules, connect TB- and TB- on PSR to TB at the top of the OMM- on the far left. See Figure. Refer to the OMM- Instructions, P/N for further information. When using the PSR with both OMM-s and MOM-s, connect as shown in Figure 6. Figure OMM- Connection REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION.

12 REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N -977 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION. Figure 6 Connecting OMM-s and MOM-s with a PSR- P/N -99-

Fire Safety. Installation Instructions Model NIM-1W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION NIM-1W

Fire Safety. Installation Instructions Model NIM-1W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION NIM-1W Fire Safety Installation Instructions Model NIM-W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION The SIEMENS Model NIM-W provides a new communication path for the following uses:

More information

Installation Instructions Model MDACT MXL/FireFinder-XLS Multi-Point Digital Alarm Communicator

Installation Instructions Model MDACT MXL/FireFinder-XLS Multi-Point Digital Alarm Communicator Installation Instructions Model MDACT MXL/FireFinder-XLS Multi-Point Digital Alarm Communicator INTRODUCTION The Model MDACT from Siemens Industry, Inc. is a multipoint serial dialer for use in MXL and

More information

Fire Safety. Installation Instructions Model CSM-4 Controllable Signal Module OPERATION INSTALLATION

Fire Safety. Installation Instructions Model CSM-4 Controllable Signal Module OPERATION INSTALLATION Fire Safety Installation Instructions Model SM- ontrollable Signal Module OPERATIO The Model SM- ontrollable Signal Module has two fully supervised, programmable circuits. The outputs supply two lass B

More information

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION Fire Safety Installation Instructions Model SMB- Main Control Board OPERATION The SIEMENS Model SMB- board in each MXL-IQ System controls operations and monitors input device identity, network communication,

More information

MXL/MXLV 19 Rack Mount Equipment

MXL/MXLV 19 Rack Mount Equipment MXL/MXLV 19 Rack Mount Equipment Models: MXL-RK1, ACM-RK, MKB-RK, MMB-RK, MOM-RK, MPS-RK, TSP-RK, VSM-RK, CABLES-RK, MKB-3 ENGINEER AND ARCHITECT SPECIFICATIONS Standard 19 Rack Mounting for MXL and MXLV

More information

Fire Safety. Installation Instructions. Model RCC-2/R and RSE-1 Remote Control Centers OPERATION INTRODUCTION INSTALLATION

Fire Safety. Installation Instructions. Model RCC-2/R and RSE-1 Remote Control Centers OPERATION INTRODUCTION INSTALLATION Fire Safety Installation Instructions Model RCC-/R and RSE- Remote Control Centers INTRODUCTI The SIEMENS Model RCC-/R Remote Command Center (See Figure ) provides the option to remotely annunciate and

More information

Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation.

Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation. Fire Safety nstallation nstructions Model MMB- Main ontrol Board OPERATON The SEMENS Model MMB- board in each MXL System controls operations and monitors input device identity, network communication, and

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS MXL-IQ Advanced Life Safety System ENGINEER AND ARCHITECT SPECIFICATIONS FirePrint Application Specific Fire Detection Capacity for up to 240 Intelligent Analog Detectors Expandable Up to a Stand Alone

More information

Advanced Protection System

Advanced Protection System MXL-IQ Advanced Protection System FirePrint Application Specific Detection Capacity for up to 240 Intelligent Analog Detectors Expandable Up to a Stand Alone System Capacity of 998 Input and Output Points

More information

MXL/MXLV Enclosuress & Equipment Models: MME-3, MBR-MP, MLE-6, MBR-3MP, MDL-1, MDB-1, MDG-1, MHD-1, MHD-2, MHD-3, MHD-4

MXL/MXLV Enclosuress & Equipment Models: MME-3, MBR-MP, MLE-6, MBR-3MP, MDL-1, MDB-1, MDG-1, MHD-1, MHD-2, MHD-3, MHD-4 MXL/MXLV Enclosuress & Equipment Models: MME-3, MBR-MP, MLE-6, MBR-3MP, MDL-1, MDB-1, MDG-1, MHD-1, MHD-2, MHD-3, MHD-4 ENGINEER AND ARCHITECT SPECIFICATIONS Enclosure & Door Package (MME-3) Standard Size

More information

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Fire Safety Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

Marine Fire Detection System Manual MXL Control Panel

Marine Fire Detection System Manual MXL Control Panel Marine Fire Detection System Manual MXL Control Panel US Coast Guard Approved Certificate No. (Cert No:6.002/22/7) Reference ULI File No. S522 Siemens Building Technologies, Inc. Fire Safety 8 Fernwood

More information

Operating Instructions MXL Multi-Line Keyboard/Display Panel

Operating Instructions MXL Multi-Line Keyboard/Display Panel Operating Instructions MXL Multi-Line Keyboard/Display Panel Local Mode Operation TRODUCTION When the MXL Keyboard/Display Panel is installed in a control panel, the components are behind a locked door.

More information

MXL-IQ CONTROL PANEL. Operation, Installation, and Maintenance Manual. Siemens Industry, Inc. Building Technologies Division Florham Park, NJ

MXL-IQ CONTROL PANEL. Operation, Installation, and Maintenance Manual. Siemens Industry, Inc. Building Technologies Division Florham Park, NJ MXL-IQ CONTROL PANEL Operation, Installation, and Maintenance Manual Siemens Industry, Inc. Building Technologies Division Florham Park, NJ P/N 315-093624-13 Siemens Building Technologies, Ltd. Fire Safety

More information

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11 Fire Safety Installation Instructions Model ADBX11 Audible Base INTRODUCTION Model ADBX11 The SIEMENS Model ADBX11 Audible Base consists of a standard Series 11 base combined with an audible device. All

More information

Fire Safety. Installation Instructions Model D2300CPS Fiber Optic Interface INTRODUCTION MOUNTING ELECTRICAL CONNECTIONS. Figure 1 D2300CPS Module

Fire Safety. Installation Instructions Model D2300CPS Fiber Optic Interface INTRODUCTION MOUNTING ELECTRICAL CONNECTIONS. Figure 1 D2300CPS Module Fire Safety Installation Instructions Model Fiber Optic Interface INTRODUCTION The Model from Siemens uilding Technologies, Inc. (See Figure 1) is a Fiber Optic interface for the MXL s RS-485 network (MNET

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

Installation Instructions Model DLC

Installation Instructions Model DLC Installation Instructions Model DLC Device Loop Card INTRODUCTION OPERATION The SIEMENS Model DLC Device Loop Card is the interface for connection of FireFinder-XLS smoke detectors, manual stations, monitor

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

General Routing Interface

General Routing Interface General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: 2002.

More information

Installation Instructions Model SSD-C-REM

Installation Instructions Model SSD-C-REM Installation Instructions Model SSD-C-REM Remote System Status Display with Control ON ALARM SUPERVISORY SECURITY TROUBLE AUDIBLES SILENCED INTRODUCTION The SIEMENS Model SSD-C-REM is an optional FireFinder

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

Series. Access Power Controllers. Installation Guide

Series. Access Power Controllers. Installation Guide Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep. 140 58th St. Brooklyn, NY Power Supply/Chargers Installation Guide Models Include: eflow4n/eflow4nx - 4 amp @ 12VDC or 24VDC eflow4n8/eflow4nx8 eflow4n8d/eflow4nx8d - 4 amp @ 12VDC or 24VDC - 4 amp @ 12VDC

More information

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev RPSMLR2 RPSMLR2BB Panic Device Power Controller Installation Guide LISTED Rev. 102715 Overview: RPSMLR2BB, RPSMLR2 will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed

More information

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs

More information

Remote NAC Power Supply D7038

Remote NAC Power Supply D7038 Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus

More information

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC. M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 042010 Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).

More information

Installation Instructions Model HZM

Installation Instructions Model HZM Installation Instructions Model Remote Conventional Zone Module INTRODUCTION The Model from is an intelligent device that connects a single zone of conventional devices to a DLC (FireFinder-XLS System)

More information

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev Altronix Corp. 140 58th St. Brooklyn, NY AL1042ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 052313 Agency Listings: UL Listed for Control Units for

More information

Multiplex Eight Input Remote Modules

Multiplex Eight Input Remote Modules Multiplex Eight Input Remote Modules 1.0 Introduction These instructions cover the installation of the D7042/D7042B Eight Input Remote Modules in a fire system supervised by an FPD-7024 Fire Alarm Control

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS CSM-4 Controllable Signal/Releasing Module ENGINEER AND ARCHITECT SPECIFICATIONS Supervised Alarm Notification Appliance Circuits Operates Audible or Visual Devices Class A (Style Z) or Class B (StyleY)

More information

ANNUNCIATOR FIXED MODULE

ANNUNCIATOR FIXED MODULE 12 Clintonville Road Northford, CT 06472 Phone: 203-484-7161 Fax: 203-484-7118 THE ANNUNCIATOR FIXED MODULE Installation Manual for the AFM-16ATF and AFM-32AF Annunciator Modules Document # 15970 3/27/95

More information

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel PROTECTOWIRE FireSystems Features Easily expandable Two supervised audible circuits Lamp and system trouble circuit test Ground fault detection Initiating device circuit (IDC) alarm test Monitors up to

More information

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X AL1002ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 071508X Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).

More information

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger

More information

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC. M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X AL1042ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 071508X Agency Listings: UL Listed for Control Units for Fire Protective Signaling Systems (UL

More information

Harrington Signal HS-3100/3200 Fire Alarm Control Unit

Harrington Signal HS-3100/3200 Fire Alarm Control Unit HARRINGTON SIGNAL INC. FIRE ALARM Harrington Signal HS-3100/3200 Fire Alarm Control Unit Installation Manual Revision 2 January 2009 Document # LT-2000HAR Table of Contents 1.0 Technical Information...

More information

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

LDM Series Lamp Driver Modules For Graphic Annunciation and Control 12 Clintonville Road Northford, CT 06472 (203) 484-7161 FAX: (203) 484-7118 LDM Series Lamp Driver Modules For Graphic Annunciation and Control Used with the System 500, System 5000, AM2020/AFP1010 and

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL400ULM Multi-Output Access Control Power Supply Charger R AL400ULM - Multi-Output Access Control Power Supply/Charger Rev. 072500 Overview: The AL400ULM multi-output access control

More information

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control

More information

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES POWER SUPPLY AND BATTERY CHARGER AC AND DC STATUS INDICATORS ENOUGH POWER TO SUPPORT UP TO 3 MAGLOCKS OR ELECTRIC STRIKES PLUS REQUIRED

More information

4100U City and Relay Cards Installation Instructions

4100U City and Relay Cards Installation Instructions 4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

June 10, 2002 DF C S2424

June 10, 2002 DF C S2424 GENERAL www.firelite.com The Fire Lite FIRE COMMAND 25/50X is a state-of-theart Emergency Voice Evacuation Control Panel (VECP), with significant technological enhancements that set it apart from other

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

IDP-Zone-6 Six Zone Interface Module

IDP-Zone-6 Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS IDP-Zone-6 Six Zone Interface Module BEFORE INSTALLING If the modules will be installed in an existing operational system, inform the operator and local authority

More information

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) PATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) NAC ETENDER SUPPLIES Installation Instructions 273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707 Web

More information

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F II 1400-2 ACSI 1406-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F INSTALLATION Transformer Model BE31763001 by Basler Electric, Transformer Model 2010028 by Galaxy

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS SXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 4 Zones Expandable to 8 Zones Microprocessor Based Control Factory Programmed Field Configurable 2 Style Y Notification

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

AL800ULADA. NAC Power Extender. Installation Guide

AL800ULADA. NAC Power Extender. Installation Guide AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery

More information

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL THE GAMEWELL COMPANY PN: 71981 60 PLEASANT STREET ISSUE A ASHLAND, MA 01721 3/22/2001 This page intentionally blank ii

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow6na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow102na8-10a @ 12VDC - Eight

More information

SP-1000X. Panic Device Power Controller Installation Guide. Rev

SP-1000X. Panic Device Power Controller Installation Guide. Rev TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current

More information

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment. LED Driver Module Installation Guide 1.0 Notice These instructions are for installing Radionics LED Driver Module in a fire alarm system controlled by Radionics D8024 or D10024 Fire Alarm Control Panels

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01 PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Warnings and Notices WARNING - To reduce the risk of fire or electric shock, do not expose this product

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

The ACM-8R Annunciator Control Module

The ACM-8R Annunciator Control Module 12 Clintonville Road Northford, CT 06472 203-484-7161 FAX: 203-484-7118 The Annunciator Control Module For the System 500, System 5000, AFP-200, AM2020, AFP1010 and SFP-1024 Fire Alarm Control Panels Document

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

Installation Instructions Model CDC-4

Installation Instructions Model CDC-4 Installation Instructions CDC-4 Conventional Card INTRODUCTION The SIEMENS CDC is a card that allows conventional detectors to be used on the FireFinder-XLS system. It provides four Class or Class B conventional

More information

ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE

ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE K3179V2 2/11 Rev. A ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE FEATURES The ADEMCO 4208SNF Universal Class A Module can be used in either of two different applications.

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow6na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow102na8d - 10A @ 12VDC - Eight

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS PXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 12 Zone System Expandable to 32 10 Amp Base Power Supply Multiple Power Supplies Available - Local or Remote 4 Notification

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

Commercial and Light Industrial Fire Alarm Control Panel

Commercial and Light Industrial Fire Alarm Control Panel FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel Features Easily expandable. All new plug-in board design Two supervised audible circuits Lamp and system trouble circuit test Ground

More information

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE Fire Door Release MODEL AR-D2 MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D2 GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK Installation Manual AQM-20 12vdc/24vdc Series Power Supplies AQM20 Supervised Power Supply/Charger 12vdc 20Amp/24vdc 10Amp Life Time Warranty Quality Manufactured in the USA AQM20 Features: The AQM20 has

More information

Operation and Installation Guide. Fire Alarm Control Panel

Operation and Installation Guide. Fire Alarm Control Panel Operation and Installation Guide Fire Alarm Control Panel 2001 Radionics Page 2 P/N: 36958D Contents Contents 1.0 Notices... 5 1.1 FCC Compliance Notice... 5 1.2 Notice... 5 1.3 Installation Guidelines

More information

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA

More information

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE The Door Switch 11772 Westline Industrial Drive St. Louis, Mo 63146 (877) 998-5625 www.thedoorswitch.com Patent No. RE42,991 and RE44,039 CONTROL PANEL TRANSFORMER (SUPPLIED WITH CONTROL PANEL) NOTIFICATION

More information

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Fire Safety FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

Cerberus TM PRO Fire Safety System A comprehensive fire-protection system

Cerberus TM PRO Fire Safety System A comprehensive fire-protection system s Data Sheet Fire Safety & Security Products Cerberus TM PRO Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the

More information

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels D9412GV2/D7412GV2 EN Approved Applications Compliance Guide Control Panels D9412GV2/D7412GV2 Approved Applications Compliance Guide Listings and Approvals Listings and Approvals Fire UL Underwriters Laboratories

More information

July 14, 1999 DF C-100.

July 14, 1999 DF C-100. www.firelite.com GENERAL The Fire Lite FIRE COMMAND 25/50 is a state-of-theart, compact, stand-alone or slave Emergency Voice Evacuation Control Panel (VECP). The FIRE COMMAND 25/50 is offered in a self-contained,

More information

System Manual W A R N I N G. PC6O1O Software Version 2.1

System Manual W A R N I N G. PC6O1O Software Version 2.1 System Manual W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING GENERAL The VEC 25/50 is a state-of-the-art, compact, stand-alone or slave Emergency Voice Evacuation Control. The VEC 25/50 is offered in a self-contained, cost-effective design and includes a 25 Watt,

More information

PFC-4064 Conventional Fire Alarm Panel

PFC-4064 Conventional Fire Alarm Panel PFC-4064 Conventional Fire Alarm Panel Installation, Operations & Programming Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT SPEC SHEET Simple Expansion Solutions Expand your DMP panel options with a wide array of expansion modules. Add supervised Class B burglary zones. Connect non-powered burglary or fire type devices for

More information

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately

More information

RM-1 Series. Remote Microphones. (RM-1, RM-1SA) Document Revision B RM-1 RM-1SA. RM-1 on ADP-4 dress panel. RM-1SA in a CAB-RM or CAB-RMR

RM-1 Series. Remote Microphones. (RM-1, RM-1SA) Document Revision B RM-1 RM-1SA. RM-1 on ADP-4 dress panel. RM-1SA in a CAB-RM or CAB-RMR This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. The following products have not received UL

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-3 ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS Features: For use with doors or groups of doors that must interlock with each other to regulate control of accessing one area from another,

More information